GATE Practice Set

GATE 2026 Power Systems Questions and Solutions

Instructor: Prof. Mithun Mondal Institution: BITS Pilani Subject: Power Systems
About this set. These are original practice questions written in GATE style for the 2026 Power Systems syllabus, with fully worked solutions. They are not reproductions of the official GATE 2026 question paper.
Question 01

Question 1

A completely transposed single-circuit three-phase overhead line has its three conductors placed in one horizontal plane. The spacings are \(D_{ab}=4\) m, \(D_{bc}=4\) m and \(D_{ca}=8\) m. Each conductor has a geometric mean radius of 1.2 cm. The inductance per phase per kilometre of the line is

  1. 0.804 mH/km
  2. 1.208 mH/km
  3. 1.398 mH/km
  4. 2.416 mH/km

Solution

For a transposed line the mutual spacing is replaced by the geometric mean of the three pairwise distances (see Inductance of a Transmission Line):

Equation
\[D_{eq} = \sqrt[3]{D_{ab}D_{bc}D_{ca}} = \sqrt[3]{4 \times 4 \times 8} = \sqrt[3]{128} = 5.0397~\text{m}\]

The inductance per phase per unit length of a transposed line with conductors of geometric mean radius \(D_s\) is

Equation
\[L = 2 \times 10^{-7}\,\ln\!\left(\frac{D_{eq}}{D_s}\right) \quad \text{H/m}\]
Equation
\[\frac{D_{eq}}{D_s} = \frac{5.0397}{0.012} = 419.98, \qquad \ln(419.98) = 6.0402\]
Equation
\[L = 2 \times 10^{-7} \times 6.0402 = 1.2080 \times 10^{-6}~\text{H/m} = 1.208~\text{mH/km}\]
B
Final Answer
Correct answer: (B) 1.208 mH/km.
Question 02

Question 2

A three-phase, 50 Hz medium transmission line is represented by its nominal-\(\pi\) equivalent. The total series impedance is \(Z = 20 + j60~\Omega\) per phase and the total shunt admittance is \(Y = j4 \times 10^{-4}~\text{S}\) per phase, the latter being split equally between the two ends. The line delivers 100 MVA at 0.8 power factor lagging at a receiving-end line voltage of 220 kV. The sending-end line voltage, in kV, is _____ (round off to one decimal place).

Solution

For the nominal-\(\pi\) model the generalised constants are \(A = D = 1 + \tfrac{ZY}{2}\) and \(B = Z\) (see Medium Transmission Line). First evaluate \(A\):

Equation
\[ZY = (20 + j60)(j4\times 10^{-4}) = j8\times10^{-3} - 2.4\times10^{-2} = -0.024 + j0.008\]
Equation
\[A = 1 + \frac{ZY}{2} = 1 + (-0.012 + j0.004) = 0.988 + j0.004\]

Take the receiving-end phase voltage as the reference phasor:

Equation
\[V_R = \frac{220 \times 10^{3}}{\sqrt{3}} \angle 0^\circ = 127017.1 \angle 0^\circ~\text{V}\]
Equation
\[|I_R| = \frac{S}{\sqrt{3}\,V_L} = \frac{100 \times 10^{6}}{\sqrt{3} \times 220 \times 10^{3}} = 262.43~\text{A}\]

At 0.8 power factor lagging the current lags \(V_R\) by \(36.87^\circ\):

Equation
\[I_R = 262.43\angle -36.87^\circ = 209.95 - j157.46~\text{A}\]

Now apply \(V_S = A V_R + B I_R\):

Equation
\[A V_R = (0.988 + j0.004)(127017.1) = 125492.9 + j508.1~\text{V}\]
Equation
\[Z I_R = (20 + j60)(209.95 - j157.46) = 13646.5 + j9447.6~\text{V}\]
Equation
\[V_S = 139139.4 + j9955.7~\text{V}, \qquad |V_S| = \sqrt{139139.4^2 + 9955.7^2} = 139495.0~\text{V}\]

This is the phase value; the sending-end line voltage is \(\sqrt{3}\) times as large:

Equation
\[|V_{S,\text{line}}| = \sqrt{3} \times 139495.0 = 241612~\text{V} = 241.6~\text{kV}\]
Final Answer
Correct answer: 241.6 kV.
Question 03

Question 3

A synchronous generator is rated 100 MVA, 13.8 kV and has a subtransient reactance of 0.20 pu on its own rating as base. When this machine is included in a system study that uses a base of 200 MVA and 13.2 kV at the generator terminals, its subtransient reactance in per unit is _____ (round off to three decimal places).

Solution

Per-unit impedance scales directly with the base MVA and inversely with the square of the base voltage (see Per-Unit Quantities):

Equation
\[X_{new} = X_{old} \times \frac{S_{base,new}}{S_{base,old}} \times \left(\frac{V_{base,old}}{V_{base,new}}\right)^{2}\]
Equation
\[X_{new} = 0.20 \times \frac{200}{100} \times \left(\frac{13.8}{13.2}\right)^{2} = 0.20 \times 2 \times 1.09298\]
Equation
\[X_{new} = 0.4372~\text{pu}\]

The reactance grows because the new base MVA is larger, and grows a little further because the new base voltage is smaller than the machine rating.

Final Answer
Correct answer: 0.437 pu.
Question 04

Question 4

A two-bus system has bus 1 as the slack bus with \(V_1 = 1.0\angle 0^\circ\) pu. The two buses are joined by a single line of series admittance \(y_{12} = 2 - j6\) pu, and the line charging is neglected. Bus 2 is a load bus drawing \(0.5 + j0.2\) pu. Starting from a flat start \(V_2^{(0)} = 1.0\angle 0^\circ\) pu, the magnitude of \(V_2\) after one Gauss-Seidel iteration is _____ pu (round off to four decimal places).

Solution

With no shunt elements the bus admittance matrix entries for bus 2 are \(Y_{22} = y_{12} = 2 - j6\) and \(Y_{21} = -y_{12} = -2 + j6\). The scheduled injection at a load bus is negative: \(P_2 = -0.5\) pu and \(Q_2 = -0.2\) pu. The Gauss-Seidel update (see Gauss-Seidel Load Flow) is

Equation
\[V_2^{(1)} = \frac{1}{Y_{22}}\left[\frac{P_2 - jQ_2}{\left(V_2^{(0)}\right)^{*}} - Y_{21}V_1\right]\]

Evaluate the two terms in the bracket:

Equation
\[\frac{P_2 - jQ_2}{\left(V_2^{(0)}\right)^{*}} = \frac{-0.5 - j(-0.2)}{1.0} = -0.5 + j0.2\]
Equation
\[-Y_{21}V_1 = -(-2 + j6)(1.0) = 2 - j6\]
Equation
\[\text{bracket} = (-0.5 + j0.2) + (2 - j6) = 1.5 - j5.8\]

Divide by \(Y_{22}\), rationalising with the conjugate \(2 + j6\):

Equation
\[V_2^{(1)} = \frac{1.5 - j5.8}{2 - j6} = \frac{(1.5 - j5.8)(2 + j6)}{2^2 + 6^2} = \frac{37.8 - j2.6}{40} = 0.9450 - j0.0650\]
Equation
\[\left|V_2^{(1)}\right| = \sqrt{0.9450^2 + 0.0650^2} = \sqrt{0.89725} = 0.9472~\text{pu} \;\angle -3.93^\circ\]
Final Answer
Correct answer: 0.9472 pu.
Question 05

Question 5

An unloaded 50 MVA, 11 kV synchronous generator has its neutral solidly grounded. Its sequence reactances on the machine rating as base are \(X_1 = 0.25\) pu, \(X_2 = 0.20\) pu and \(X_0 = 0.05\) pu; all resistances are negligible. With the prefault terminal voltage at 1.0 pu, a single line-to-ground fault occurs on phase a at the machine terminals. The magnitude of the fault current is

  1. 2.62 kA
  2. 5.25 kA
  3. 15.75 kA
  4. 47.24 kA

Solution

For a single line-to-ground fault the three sequence networks are connected in series, so the three sequence currents are equal (see Single Line-to-Ground Fault):

Equation
\[I_{a1} = I_{a2} = I_{a0} = \frac{E_a}{j(X_1 + X_2 + X_0)} = \frac{1.0}{j(0.25 + 0.20 + 0.05)} = \frac{1.0}{j0.50} = -j2.0~\text{pu}\]

The faulted phase current is the sum of the three sequence components:

Equation
\[I_a = I_{a0} + I_{a1} + I_{a2} = 3I_{a1} = -j6.0~\text{pu}, \qquad |I_a| = 6.0~\text{pu}\]

Convert to amperes using the base current at the 11 kV level:

Equation
\[I_{base} = \frac{S_{base}}{\sqrt{3}\,V_{base}} = \frac{50 \times 10^{6}}{\sqrt{3} \times 11 \times 10^{3}} = 2624.3~\text{A}\]
Equation
\[|I_f| = 6.0 \times 2624.3 = 15746~\text{A} = 15.75~\text{kA}\]
C
Final Answer
Correct answer: (C) 15.75 kA.
Question 06

Question 6

The line currents of a three-phase, four-wire system are measured as \(I_a = 6\angle 0^\circ\) A, \(I_b = 4\angle -90^\circ\) A and \(I_c = 8\angle 150^\circ\) A. The zero-sequence component of the phase-a current is

  1. 0 A
  2. \(0.309\angle 180^\circ\) A
  3. \(0.928\angle 180^\circ\) A
  4. \(3.000\angle 0^\circ\) A

Solution

The zero-sequence current is the average, not the sum, of the three phase currents (see Symmetrical Components):

Equation
\[I_{a0} = \frac{1}{3}\left(I_a + I_b + I_c\right)\]

Resolve each phasor into rectangular form:

Equation
\[I_a = 6 + j0, \qquad I_b = -j4, \qquad I_c = 8(\cos 150^\circ + j\sin 150^\circ) = -6.9282 + j4\]
Equation
\[I_a + I_b + I_c = (6 - 6.9282) + j(-4 + 4) = -0.9282 + j0\]
Equation
\[I_{a0} = \frac{-0.9282}{3} = -0.3094 = 0.3094\angle 180^\circ~\text{A}\]

The neutral current, for reference, is \(I_n = 3I_{a0} = 0.928\angle 180^\circ\) A, which is choice C. That is the trap: option C omits the factor of one third.

B
Final Answer
Correct answer: (B) \(0.309\angle 180^\circ\) A.
Question 07

Question 7

A lossless synchronous generator with inertia constant \(H = 5\) MJ/MVA is connected to an infinite bus through a transmission link. In the prefault condition the power-angle characteristic is \(P_e = 2.0\sin\delta\) pu and the constant mechanical input is \(P_m = 1.0\) pu. A three-phase fault at the generator terminals reduces the electrical power output to zero, and the fault is cleared by restoring the original prefault network. For a system frequency of 50 Hz, the critical clearing time is _____ s (round off to three decimal places).

Solution

The initial rotor angle follows from \(P_m = P_{max}\sin\delta_0\):

Equation
\[\delta_0 = \sin^{-1}\!\left(\frac{1.0}{2.0}\right) = 30^\circ = 0.5236~\text{rad}\]

Because the postfault characteristic is identical to the prefault one, the maximum swing angle is

Equation
\[\delta_{max} = 180^\circ - \delta_0 = 150^\circ = 2.6180~\text{rad}\]

Applying the equal-area criterion with zero power transfer during the fault, the accelerating area from \(\delta_0\) to \(\delta_{cc}\) must equal the decelerating area from \(\delta_{cc}\) to \(\delta_{max}\) (see Equal Area Criterion):

Equation
\[\cos\delta_{cc} = \frac{P_m(\delta_{max} - \delta_0)}{P_{max}} + \cos\delta_{max}\]
Equation
\[\cos\delta_{cc} = \frac{1.0(2.6180 - 0.5236)}{2.0} + \cos 150^\circ = 1.0472 - 0.8660 = 0.1812\]
Equation
\[\delta_{cc} = \cos^{-1}(0.1812) = 79.56^\circ = 1.3886~\text{rad}\]

During the fault the electrical power is zero, so the swing equation integrates in closed form and the clearing time corresponding to \(\delta_{cc}\) is

Equation
\[t_{cc} = \sqrt{\frac{2H(\delta_{cc} - \delta_0)}{\pi f P_m}} = \sqrt{\frac{2 \times 5 \times (1.3886 - 0.5236)}{\pi \times 50 \times 1.0}}\]
Equation
\[t_{cc} = \sqrt{\frac{8.650}{157.08}} = \sqrt{0.05507} = 0.2347~\text{s}\]
Final Answer
Correct answer: 0.235 s (critical clearing angle \(79.56^\circ\)).
Question 08

Question 8

Two thermal units supply a total load of 250 MW. Their fuel cost characteristics, in Rs./h with the outputs in MW, are

Equation
\[C_1 = 0.02P_1^{2} + 16P_1 + 50, \qquad C_2 = 0.04P_2^{2} + 12P_2 + 80\]

The generation limits are \(50 \le P_1 \le 200\) MW and \(30 \le P_2 \le 100\) MW. Transmission losses are neglected. For the economic dispatch, the output of unit 1 is _____ MW.

Solution

The incremental cost of each unit is the derivative of its cost characteristic:

Equation
\[\frac{dC_1}{dP_1} = 0.04P_1 + 16, \qquad \frac{dC_2}{dP_2} = 0.08P_2 + 12\]

Ignoring the limits for the moment, equal incremental cost with \(P_1 + P_2 = 250\) gives (see Economic Load Dispatch)

Equation
\[0.04(250 - P_2) + 16 = 0.08P_2 + 12 \Rightarrow 26 - 0.04P_2 = 0.08P_2 + 12\]
Equation
\[0.12P_2 = 14 \Rightarrow P_2 = 116.67~\text{MW}, \qquad P_1 = 133.33~\text{MW}\]

This trial value of \(P_2\) exceeds its 100 MW upper limit, so it is not feasible. Unit 2 is therefore held at its limit and the balance is taken by unit 1:

Equation
\[P_2 = 100~\text{MW}, \qquad P_1 = 250 - 100 = 150~\text{MW}\]

The system incremental cost is now set by the free unit:

Equation
\[\lambda = 0.04(150) + 16 = 22~\text{Rs./MWh}\]

The solution is consistent because the fixed unit sits at its maximum and its incremental cost there, \(0.08(100) + 12 = 20\) Rs./MWh, is below \(\lambda\); loading it further would still be cheap, but the limit forbids it. Both outputs lie within the stated ranges.

Final Answer
Correct answer: \(P_1 = 150\) MW (with \(P_2 = 100\) MW, \(\lambda = 22\) Rs./MWh).
Question 09

Question 9

A feeder is protected by an IDMT overcurrent relay of the normal inverse type fed from a current transformer of ratio 400/5 A. The relay plug setting is 125 percent and the time multiplier setting is 0.3. The relay operating time is given by

Equation
\[t = \frac{0.14 \times \text{TMS}}{(\text{PSM})^{0.02} - 1}~\text{s}\]

For a symmetrical fault current of 4000 A in the primary, the relay operating time is _____ s (round off to three decimal places).

Solution

Refer the fault current to the relay coil through the CT ratio:

Equation
\[I_{relay} = 4000 \times \frac{5}{400} = 50~\text{A}\]

A plug setting of 125 percent means the relay picks up at 1.25 times the CT secondary rated current:

Equation
\[I_{pickup} = 1.25 \times 5 = 6.25~\text{A}\]

The plug setting multiplier is the ratio of the two:

Equation
\[\text{PSM} = \frac{50}{6.25} = 8\]

Evaluate the characteristic. Since \(8^{0.02} = e^{0.02\ln 8} = e^{0.041589} = 1.042466\),

Equation
\[t = \frac{0.14 \times 0.3}{1.042466 - 1} = \frac{0.042}{0.042466} = 0.989~\text{s}\]
Final Answer
Correct answer: 0.989 s.
Question 10

Question 10

A lossless 400 kV three-phase transmission line has a series inductance of 1.0 mH/km and a shunt capacitance of 11.1 nF/km per phase. The surge impedance loading of the line is

  1. 267 MW
  2. 533 MW
  3. 800 MW
  4. 1066 MW

Solution

For a lossless line the surge impedance depends only on the ratio of the distributed parameters, not on the line length (see Surge Impedance Loading):

Equation
\[Z_c = \sqrt{\frac{L}{C}} = \sqrt{\frac{1.0 \times 10^{-3}}{11.1 \times 10^{-9}}} = \sqrt{90090} = 300.2~\Omega\]

The surge impedance loading is the three-phase power delivered when the line is terminated in \(Z_c\), with \(V_L\) the rated line-to-line voltage:

Equation
\[\text{SIL} = \frac{V_L^{2}}{Z_c} = \frac{(400 \times 10^{3})^{2}}{300.2} = \frac{1.6 \times 10^{11}}{300.2}\]
Equation
\[\text{SIL} = 5.33 \times 10^{8}~\text{W} = 533~\text{MW}\]
B
Final Answer
Correct answer: (B) 533 MW.
Previous2025
GATE Power Systems