Part 5 · Chapter 22

Symmetrical Components

Any three unbalanced phasors can be written as the sum of three balanced sets — one of positive sequence, one of negative sequence and one of zero sequence — and because a balanced network cannot mix those sets, the transformation turns one intractable coupled problem into three ordinary single-phase ones.

Electric Power Systems Prof. Mithun Mondal Reading time ≈ 45 min
i What you'll learn
  • Why an unsymmetrical fault destroys the one assumption — balance — on which every calculation from Chapter 3 to Chapter 21 depended.
  • Fortescue's theorem: three unbalanced phasors resolve uniquely into a positive-, a negative- and a zero-sequence balanced set.
  • How the operator \(a\) of Chapter 3 and the identity \(1+a+a^2=0\) build the transformation matrix \(\mathbf{A}\) and, with almost no extra work, its inverse.
  • Why the neutral current is exactly \(3I_{a0}\), and why a delta winding or an isolated neutral admits no zero-sequence line current at all.
  • That total complex power is \(3\big(V_{a0}I_{a0}^*+V_{a1}I_{a1}^*+V_{a2}I_{a2}^*\big)\) — the sequences carry power independently.
  • How \(\mathbf{A}\) diagonalises the impedance matrix of any balanced network, which is the reason three separate sequence networks exist.
  • How the terminal conditions of each fault type read in sequence variables, ready for Chapters 23 and 24.
Section 22-1

Where Per-Phase Analysis Breaks Down

Every calculation in this book so far has rested on a single structural fact. In a balanced three-phase circuit the three phases carry identical quantities displaced by \(120^\circ\), so knowing one phase is knowing all three. Chapter 3 turned that into the per-phase equivalent circuit, Chapter 4 turned the per-phase circuit into a per-unit impedance diagram, Part 3 computed line performance on one phase, Part 4 solved load flow one phase at a time, and Chapter 21 analysed the three-phase fault on one phase because that fault leaves the symmetry intact.

Now consider a single conductor falling to earth. Phase \(a\) is shorted to the reference; phases \(b\) and \(c\) are untouched. The three phase currents are no longer equal in magnitude, no longer \(120^\circ\) apart, and no longer derivable from one another. Whatever is true of phase \(a\) tells us nothing about phase \(b\). The per-phase circuit has no meaning, and with it goes the per-unit diagram, the \(\mathbf{Y}_{bus}\), the \(\mathbf{Z}_{bus}\) and every result of the last eighteen chapters.

The brute-force alternative is to write the network in full three-phase detail: every line becomes a \(3\times3\) impedance matrix with mutual terms, every transformer a coupled six-winding element, and an \(n\)-bus system a \(3n\)-dimensional problem with no symmetry to exploit. It is possible, it is what a modern electromagnetic transient program actually does, and it is entirely unsuited to hand calculation or to understanding.

In 1918 Charles LeGeyt Fortescue published the alternative. Instead of abandoning balance, decompose the unbalanced problem into balanced ones. The observation is a change of variables, nothing more; its power comes from the fact that the balanced network — which is still balanced, even though the fault at its terminals is not — treats those new variables independently.

The fault is unbalanced; the network is not. A transposed transmission line, a three-limb transformer and a cylindrical-rotor machine are all symmetric in their three phases; what breaks the symmetry is the connection made at one point by the fault. Symmetrical components exploit exactly that division of labour: the network is handled three times over in balanced form, and all the asymmetry is concentrated into the boundary conditions at the fault point. Chapter 24 is nothing but the systematic application of that idea.
Section 22-2

Fortescue's Theorem: Three Balanced Sets

The claim is this. Given any three phasors \(V_a\), \(V_b\), \(V_c\) — arbitrary magnitudes, arbitrary angles — there exist three sets of three phasors each, whose term-by-term sum reproduces the original set, and which have the following structures.

SetSubscriptStructurePhase sequence
Positive sequence1three equal phasors \(120^\circ\) apartsame as the original system, \(a\)–\(b\)–\(c\)
Negative sequence2three equal phasors \(120^\circ\) apartreversed, \(a\)–\(c\)–\(b\)
Zero sequence0three equal phasors, no displacementnone — all three in phase

The decomposition is unique. That is easy to believe on a counting argument: three complex phasors carry six real numbers, and the three sets are described by \(V_{a1}\), \(V_{a2}\), \(V_{a0}\) — again six real numbers, since the other two members of each set follow from the first. A transformation from six numbers to six numbers can be one-to-one, and Section 22-4 shows that this one is by exhibiting the inverse explicitly.

Writing the phase quantities as the sum of their three components,

Superposition of the three sets
\[ V_a = V_{a0}+V_{a1}+V_{a2}, \qquad V_b = V_{b0}+V_{b1}+V_{b2}, \qquad V_c = V_{c0}+V_{c1}+V_{c2} \]

The subscripts \(b\) and \(c\) can be eliminated at once, because each set is balanced and therefore determined entirely by its \(a\)-phase member. That is the whole reason the transformation is useful, and it is where the operator \(a\) of Chapter 3 re-enters.

positive, I₁ a b c 6.67∠0°, 6.67∠−120°, 6.67∠120° (a-b-c) negative, I₂ a b c 3.33∠60°, 3.33∠180°, 3.33∠−60° (a-c-b) zero, I₀ a = b = c 3.33∠−60° three times, all in phase + + = resultant a b c = 0 10∠0°, 10∠−120°, 0 one conductor open
An open phase resolved into positive, negative and zero sequence sets — Example 1
Section 22-3

The Operator a and the Synthesis Matrix

Chapter 3 defined \(a\) as the unit phasor that advances an angle by \(120^\circ\), and derived the identity on which everything here depends. Collecting the properties that will be used:

The operator \(a\)
\[ a = 1\angle120^\circ = -\tfrac12+j\tfrac{\sqrt3}{2}, \qquad a^2 = 1\angle240^\circ = -\tfrac12-j\tfrac{\sqrt3}{2} = a^*, \qquad a^3=1,\;\; a^4=a \]
\[ \boxed{\,1+a+a^2 = 0\,}, \qquad a-a^2 = j\sqrt3, \qquad a^2-a = -j\sqrt3 \]

The first identity is Chapter 3's statement that three equal phasors \(120^\circ\) apart sum to zero; the two that follow it are read straight off the diagram, since \(a\) and \(a^2\) are mirror images about the real axis separated vertically by \(\sqrt3\).

Now express each balanced set through its \(a\)-phase member. The positive-sequence set has \(a\)–\(b\)–\(c\) order, so \(b\) lags \(a\) by \(120^\circ\): \(V_{b1}=a^2V_{a1}\) and \(V_{c1}=aV_{a1}\). The negative-sequence set has the reverse order, so \(b\) leads: \(V_{b2}=aV_{a2}\) and \(V_{c2}=a^2V_{a2}\). The zero-sequence set has all three identical: \(V_{b0}=V_{c0}=V_{a0}\). Substituting into the superposition of Section 22-2 gives the three phase quantities in terms of three unknowns.

Synthesis: phase quantities from sequence quantities
\[ \begin{aligned} V_a &= V_{a0} + V_{a1} + V_{a2}\\ V_b &= V_{a0} + a^2V_{a1} + aV_{a2}\\ V_c &= V_{a0} + aV_{a1} + a^2V_{a2} \end{aligned} \]
🔑
The symmetrical component transformation
\[ \mathbf{V}_{abc} = \mathbf{A}\,\mathbf{V}_{012}, \qquad \mathbf{A} = \begin{bmatrix}1&1&1\\ 1&a^2&a\\ 1&a&a^2\end{bmatrix} \]

\(\mathbf{A}\) is symmetric, its first row and first column are all ones, and every entry has unit magnitude. The same matrix transforms currents: \(\mathbf{I}_{abc}=\mathbf{A}\,\mathbf{I}_{012}\). By convention the components are always referred to phase \(a\), and the subscript is often dropped: \(V_0, V_1, V_2\) mean \(V_{a0}, V_{a1}, V_{a2}\).

1 a 120° the three cube roots of unity 1 a start head to tail they close: 1 + a + a² = 0
The identity that makes the transformation invertible
Section 22-4

Inverting the Transformation

Synthesis is not what is needed in practice. Given a measured or computed set of unbalanced phase quantities, the sequence components must be extracted from them, which means inverting \(\mathbf{A}\). There is no need to compute a determinant and a matrix of cofactors; the identity \(1+a+a^2=0\) does the work directly.

Add the three synthesis equations. The \(V_{a1}\) terms carry the factor \(1+a^2+a=0\) and the \(V_{a2}\) terms the factor \(1+a+a^2=0\), so both vanish and only \(3V_{a0}\) survives. Now multiply the second equation by \(a\) and the third by \(a^2\) before adding. Using \(a^3=1\) and \(a^4=a\):

Extracting the positive-sequence component
\[ \begin{aligned} V_a \;&=\; V_{a0} + V_{a1} + V_{a2}\\ aV_b \;&=\; aV_{a0} + a^3V_{a1} + a^2V_{a2} \;=\; aV_{a0} + V_{a1} + a^2V_{a2}\\ a^2V_c \;&=\; a^2V_{a0} + a^3V_{a1} + a^4V_{a2} \;=\; a^2V_{a0} + V_{a1} + aV_{a2} \end{aligned} \]
\[ V_a + aV_b + a^2V_c = \underbrace{(1+a+a^2)}_{0}V_{a0} + 3V_{a1} + \underbrace{(1+a^2+a)}_{0}V_{a2} = 3V_{a1} \]

Multiplying instead by \(a^2\) and \(a\) isolates \(V_{a2}\) by the identical mechanism. The three results together are the analysis equations.

🔑
Analysis: sequence quantities from phase quantities
\[ \mathbf{V}_{012} = \mathbf{A}^{-1}\mathbf{V}_{abc}, \qquad \mathbf{A}^{-1} = \frac13\begin{bmatrix}1&1&1\\ 1&a&a^2\\ 1&a^2&a\end{bmatrix} \]

Written out: \(V_{a0}=\tfrac13(V_a+V_b+V_c)\), \(V_{a1}=\tfrac13(V_a+aV_b+a^2V_c)\), \(V_{a2}=\tfrac13(V_a+a^2V_b+aV_c)\). Since \(a^*=a^2\), the inverse is simply \(\mathbf{A}^{-1}=\tfrac13\mathbf{A}^*\) — the conjugate of the original matrix, divided by three.

That last observation is worth keeping, because it says \(\mathbf{A}\mathbf{A}^*=3\mathbf{I}\). A matrix whose columns are mutually orthogonal and each of squared length three is a scaled unitary matrix, and unitary transformations preserve inner products. Section 22-6 collects the dividend: complex power comes through the transformation almost untouched.

The zero-sequence line deserves emphasis on its own. It says that \(V_{a0}\) is one third of the sum of the three phase quantities. If the three sum to zero — which for a balanced set they do, by the very identity used above — there is no zero-sequence component at all. Zero sequence is precisely the measure of how far a three-phase set departs from summing to zero, which is why it is intimately tied to earth and neutral paths.

Section 22-5

Sequence Currents, the Neutral and the Delta

Apply the analysis equations to currents in a four-wire system. Kirchhoff's current law at the star point gives the neutral current as the sum of the three line currents, and the zero-sequence equation gives one third of that same sum. The two statements combine into the single most-used result in unbalanced analysis.

🔑
The neutral carries three times the zero-sequence current
\[ I_n = I_a+I_b+I_c = 3I_{a0} \]

Equivalently \(I_{a0}=\tfrac13 I_n\). Zero-sequence current is the component that flows in the same direction in all three phases at once and must therefore return through a fourth path — the neutral conductor, the earth, or both.

Three corollaries follow, and each of them decides the shape of a sequence network in Chapter 23.

If the star point is isolated, there is no fourth path, so \(I_n=0\) and therefore \(I_{a0}=0\). The line currents of an ungrounded star connection contain no zero-sequence component whatever the unbalance. If the star point is earthed through an impedance \(Z_n\), the current \(3I_{a0}\) flows through it and produces a voltage drop \(3I_{a0}Z_n\) between the star point and earth; only the zero-sequence network feels it, and it feels it as an impedance \(3Z_n\) — a factor of three that Section 22-7 derives rather than asserts.

If the load or winding is delta-connected, the line currents are differences of phase currents, \(I_a = I_{ab}-I_{ca}\) and so on, and those differences necessarily sum to zero. So again \(I_{a0}=0\) in the lines. Inside the delta, however, a zero-sequence current may perfectly well circulate: if \(I_{ab}=I_{bc}=I_{ca}=I_0^{\Delta}\), each line current is unaffected but a real current runs round the closed loop. A delta winding is therefore a trap for zero-sequence current — it absorbs it and hides it from the line — which is exactly why delta tertiary windings are fitted to large transformers.

star, earthed through Zn abc Zn In = 3I₀ flows star, isolated neutral abc no path ⇒ I₀ = 0 delta abc I₀ circulates inside line I₀ = 0
Where zero-sequence current can go, and where it cannot

Two further facts are used constantly and are worth stating plainly. A perfectly balanced system in \(a\)–\(b\)–\(c\) sequence contains positive-sequence quantities only; \(I_{a1}\) equals the phase current and \(I_{a2}=I_{a0}=0\). Consequently the appearance of any negative- or zero-sequence current is by itself evidence of an abnormal condition, which is the entire basis of negative-sequence and earth-fault relaying in Chapter 36. And the labelling is a convention with content: if the resultant set rotated in the reverse order, one would name the larger balanced set "positive", so in normal usage \(|I_{a2}|\) does not exceed \(|I_{a1}|\).

Section 22-6

Power in Terms of Symmetrical Components

A change of variables that mangles power would be of limited use, since every engineering answer eventually has to be expressed in megawatts. Fortunately \(\mathbf{A}\) is a scaled unitary matrix, and the calculation is three lines long. Start from the three-phase complex power written as a matrix product:

Complex power through the transformation
\[ S = P_{abc}+jQ_{abc} = V_aI_a^*+V_bI_b^*+V_cI_c^* = \mathbf{V}_{abc}^{T}\,\mathbf{I}_{abc}^{*} = \big(\mathbf{A}\mathbf{V}_{012}\big)^{T}\big(\mathbf{A}\mathbf{I}_{012}\big)^{*} = \mathbf{V}_{012}^{T}\,\mathbf{A}^{T}\mathbf{A}^{*}\,\mathbf{I}_{012}^{*} \]

Everything now hangs on the matrix \(\mathbf{A}^T\mathbf{A}^*\). Since \(\mathbf{A}\) is symmetric, \(\mathbf{A}^T=\mathbf{A}\), and since \(a^*=a^2\), \(\mathbf{A}^*\) is \(\mathbf{A}\) with \(a\) and \(a^2\) interchanged. The diagonal entries of the product are sums like \(1+a^2a+aa^2 = 1+1+1 = 3\); the off-diagonal entries are sums like \(1+a+a^2=0\).

The key product
\[ \mathbf{A}^{T}\mathbf{A}^{*} = \begin{bmatrix}1&1&1\\ 1&a^2&a\\ 1&a&a^2\end{bmatrix}\begin{bmatrix}1&1&1\\ 1&a&a^2\\ 1&a^2&a\end{bmatrix} = 3\begin{bmatrix}1&0&0\\ 0&1&0\\ 0&0&1\end{bmatrix} \]
🔑
Power in sequence components
\[ P_{abc}+jQ_{abc} = 3\Big(V_{a0}I_{a0}^{*} + V_{a1}I_{a1}^{*} + V_{a2}I_{a2}^{*}\Big) \]

There are no cross terms: no product of a positive-sequence voltage with a negative-sequence current appears. Each sequence carries its own power independently, and the factor \(3\) is the same factor that appears in \(S=3V_{ph}I_{ph}^*\) for a balanced circuit — as it must, since a balanced circuit has only the middle term.

The absence of cross terms is a genuine physical statement, not bookkeeping. A negative-sequence current in a machine cannot draw power from the positive-sequence voltage; it draws power from the negative-sequence voltage alone, and in a generator that power is a loss, delivered into the rotor surface as double-frequency heating. Section 22-8 returns to the point.

A word on the alternative convention. Some texts define the transformation with a factor \(1/\sqrt3\) built into \(\mathbf{A}\), which makes it exactly unitary and removes the \(3\). That convention makes power literally invariant but destroys the pleasant property that a balanced set has \(V_{a1}\) equal to the actual phase voltage. Power systems practice keeps the convention used here, and pays for it with the factor of three.

Section 22-7

Why the Three Sequences Decouple

Everything so far has been a change of variables applied to phasors. Nothing yet explains why the change is useful, and the explanation is the subject of this section: applied to a balanced network, the transformation diagonalises the impedance matrix.

Take the most general three-phase element that is symmetric in its phases — a transposed line, a symmetrical machine, a static load with equal branches. Its three phases each have the same self impedance \(Z_s\), and each pair has the same mutual impedance \(Z_m\). In phase variables,

A balanced three-phase element
\[ \mathbf{V}_{abc} = \mathbf{Z}_{abc}\mathbf{I}_{abc}, \qquad \mathbf{Z}_{abc} = \begin{bmatrix}Z_s&Z_m&Z_m\\ Z_m&Z_s&Z_m\\ Z_m&Z_m&Z_s\end{bmatrix} \]

The three phases are thoroughly coupled: a current in phase \(a\) produces a voltage in phases \(b\) and \(c\). Substituting the transformation on both sides and premultiplying by \(\mathbf{A}^{-1}\) gives \(\mathbf{V}_{012}=\big(\mathbf{A}^{-1}\mathbf{Z}_{abc}\mathbf{A}\big)\mathbf{I}_{012}\), so the sequence impedance matrix is a similarity transform. To evaluate it, split \(\mathbf{Z}_{abc}\) into a diagonal part and an all-ones part \(\mathbf{J}\):

Diagonalising the balanced impedance matrix
\[ \mathbf{Z}_{abc} = (Z_s-Z_m)\mathbf{I} + Z_m\mathbf{J}, \qquad \mathbf{J}=\begin{bmatrix}1&1&1\\1&1&1\\1&1&1\end{bmatrix} \]
\[ \mathbf{A}^{-1}\mathbf{I}\mathbf{A} = \mathbf{I}, \qquad \mathbf{J}\mathbf{A} = \begin{bmatrix}3&0&0\\3&0&0\\3&0&0\end{bmatrix} \;\Longrightarrow\; \mathbf{A}^{-1}\mathbf{J}\mathbf{A} = \begin{bmatrix}3&0&0\\0&0&0\\0&0&0\end{bmatrix} \]

The middle step is where the identity does its work once more: the columns of \(\mathbf{A}\) sum to \(3\), \(1+a^2+a=0\) and \(1+a+a^2=0\) respectively, so \(\mathbf{J}\mathbf{A}\) has only its first column non-zero. Assembling the two pieces gives a diagonal matrix, and the diagonal entries are the three sequence impedances.

🔑
The sequence impedances of a balanced element
\[ \mathbf{Z}_{012}=\mathbf{A}^{-1}\mathbf{Z}_{abc}\mathbf{A} = \begin{bmatrix}Z_s+2Z_m&0&0\\ 0&Z_s-Z_m&0\\ 0&0&Z_s-Z_m\end{bmatrix} \]

So \(Z_0=Z_s+2Z_m\) and \(Z_1=Z_2=Z_s-Z_m\). The off-diagonal zeros are the whole point: positive-sequence current produces only positive-sequence voltage drop, and likewise for the other two. The three sequences pass through the network without ever meeting.

Add a neutral earthing impedance \(Z_n\) and the same machinery delivers the factor of three promised in Section 22-5. With the star point returned to earth through \(Z_n\), the phase equation gains the neutral drop \(Z_nI_n = Z_n(I_a+I_b+I_c)\) in every row, which is precisely \(Z_n\mathbf{J}\mathbf{I}_{abc}\). Transforming, that adds \(Z_n\,\text{diag}(3,0,0)\) to \(\mathbf{Z}_{012}\):

The neutral impedance appears tripled, and only in the zero-sequence network
\[ Z_0 = Z_s+2Z_m+3Z_n, \qquad Z_1 = Z_2 = Z_s-Z_m \]
Three networks, not one. Because the transformation diagonalises every balanced element in the system, it diagonalises the whole system: an \(n\)-bus network becomes three independent \(n\)-bus networks, one per sequence, each an ordinary single-phase circuit to which \(\mathbf{Y}_{bus}\), \(\mathbf{Z}_{bus}\) and everything else from Part 4 applies unchanged. Chapter 23 builds those three networks element by element — and shows that they are genuinely different, because \(Z_0\) depends on the return path through earth while \(Z_1\) and \(Z_2\) do not. Chapter 24 connects them at the fault point, which is the single place where the three are allowed to meet.
Section 22-8

What Each Sequence Does Physically

The components are not merely algebraic conveniences; each corresponds to something a machine or an instrument can feel.

Positive sequence is the normal system. Applied to the stator of a machine it produces a magnetic field rotating forward at synchronous speed, in step with the rotor. It carries essentially all the useful power, and it is the only sequence present when nothing is wrong. Its impedance is the ordinary impedance used throughout Parts 3 and 4 — a generator's positive-sequence reactance is exactly the \(X_d''\), \(X_d'\) or \(X_d\) of Chapter 21, according to the instant of interest.

Negative sequence produces a field rotating backwards at synchronous speed. Relative to a rotor turning forwards at synchronous speed, that field sweeps past at twice synchronous speed, inducing double-frequency currents in the rotor body, the damper bars and the wedges. The consequences are a braking torque of no use to anyone and, far more seriously, concentrated surface heating that can damage a large turbo-alternator within seconds. This is why negative-sequence overcurrent relays exist and why continuous negative-sequence current is limited to a few per cent of rating.

Zero sequence produces no rotating field at all: three identical currents in three windings spaced \(120^\circ\) apart give three mmf contributions that cancel in the air gap. It produces only leakage flux, so a machine's zero-sequence reactance is small — typically below its subtransient reactance. What zero sequence does instead is flow in earth and neutral paths, and its magnitude depends entirely on how the system is earthed. That dependence, not the winding, dominates \(Z_0\) in practice.

PropertyPositive (1)Negative (2)Zero (0)
Phase sequence\(a\)–\(b\)–\(c\)\(a\)–\(c\)–\(b\)all in phase
Air-gap fieldforward, synchronousbackward, synchronousnone (leakage only)
Present in a healthy systemyes, alonenono
Needs a neutral or earth pathnonoyes
Typical generator reactance\(X_d''\approx 0.15\) pu\(X_2\approx X_d''\)\(X_0\approx 0.05\) pu
Effect on a machineuseful torquedouble-frequency rotor heatingheating, no torque
Section 22-9

Reading Fault Conditions in Sequence Terms

The transformation earns its place only if the fault conditions themselves become simple in the new variables, and they do. Each fault type imposes two or three constraints on the phase quantities at the fault point; transforming those constraints yields relations among the sequence quantities that dictate how the three networks are to be interconnected. This section states the constraints and their transforms; Chapter 24 turns them into circuit connections.

Take a single line-to-ground fault on phase \(a\) through an impedance \(Z_f\). Two currents are zero because those conductors are intact, and the third is fixed by the fault path: \(I_b=I_c=0\) and \(V_a=Z_fI_a\). Substituting the first pair into the analysis equations,

Single line-to-ground fault
\[ I_{a0}=\tfrac13(I_a+0+0)=\tfrac{I_a}{3}, \quad I_{a1}=\tfrac13(I_a+0+0)=\tfrac{I_a}{3}, \quad I_{a2}=\tfrac13(I_a+0+0)=\tfrac{I_a}{3} \]
\[ \Longrightarrow\quad I_{a0}=I_{a1}=I_{a2}=\frac{I_f}{3} \]

Three equal sequence currents flowing in three networks: that is the signature of elements connected in series, and it is why the three sequence networks are joined in series for an LG fault. Now a line-to-line fault between phases \(b\) and \(c\), where \(I_a=0\) and \(I_b=-I_c\):

Line-to-line fault
\[ I_{a0}=\tfrac13(0+I_b-I_b)=0 \]
\[ I_{a1}=\tfrac13\big(0+aI_b+a^2(-I_b)\big)=\tfrac{I_b}{3}(a-a^2)=\frac{jI_b}{\sqrt3}, \qquad I_{a2}=\tfrac{I_b}{3}(a^2-a)=-\frac{jI_b}{\sqrt3} \]

so \(I_{a1}=-I_{a2}\) with no zero sequence at all — which is the signature of two elements connected in parallel (or, more precisely, in opposition), and the zero-sequence network takes no part because the fault does not involve earth. The remaining cases follow the same pattern, and the table below is the summary Chapter 24 works from.

FaultTerminal conditionsSequence relationsNetwork connection
Three-phase\(V_a=V_b=V_c=0\)\(I_{a0}=I_{a2}=0\)positive-sequence network only (Chapter 21)
Line-to-ground (a–g)\(I_b=I_c=0,\;V_a=Z_fI_a\)\(I_{a0}=I_{a1}=I_{a2}\)all three in series
Line-to-line (b–c)\(I_a=0,\;I_b=-I_c\)\(I_{a0}=0,\;I_{a1}=-I_{a2}\)positive against negative
Double line-to-ground (b–c–g)\(I_a=0,\;V_b=V_c\)\(I_{a0}+I_{a1}+I_{a2}=0\)negative and zero in parallel across positive

One row of that table is a useful sanity check on everything in this chapter. A bolted three-phase fault sets all three phase voltages to zero; three zeros sum to zero and have no unbalance, so \(V_{a0}=V_{a1}=V_{a2}=0\) and the currents contain positive sequence only. Symmetrical components applied to a symmetrical fault return exactly the single-network calculation of Chapter 21, as any correct generalisation must.

A second consequence is worth noting for Chapter 30. A single-phase load connected between one line and neutral of a three-phase supply satisfies \(I_b=I_c=0\) — mathematically identical to the LG fault condition — and therefore draws equal positive-, negative- and zero-sequence currents. Every single-phase traction load or domestic feeder is, in this precise sense, a permanent low-level unsymmetrical fault on the system that feeds it.

Section 22-10

Worked Examples

1 An open conductor on a four-wire feeder

Problem. A four-wire feeder carries \(I_a=10\angle0^\circ\) A and \(I_b=10\angle-120^\circ\) A when the conductor of phase \(c\) breaks, so \(I_c=0\). Find the three sequence components of the line current and the neutral current.

Solution. Apply the analysis equations directly. For the zero-sequence component,

Zero sequence
\[ I_{a0}=\tfrac13\big(10\angle0^\circ + 10\angle{-120^\circ} + 0\big)=\tfrac13\big(10-5-j8.660\big)=\tfrac13\big(5-j8.660\big)=3.333\angle{-60^\circ}\;\text{A} \]

For the positive sequence, multiply \(I_b\) by \(a\), which adds \(120^\circ\) to its angle:

Positive sequence
\[ I_{a1}=\tfrac13\big(10\angle0^\circ + 10\angle(-120^\circ+120^\circ) + 0\big)=\tfrac13(10+10)=6.667\angle0^\circ\;\text{A} \]

For the negative sequence, multiply \(I_b\) by \(a^2\), adding \(240^\circ\):

Negative sequence
\[ I_{a2}=\tfrac13\big(10\angle0^\circ + 10\angle120^\circ\big)=\tfrac13\big(10-5+j8.660\big)=\tfrac13\big(5+j8.660\big)=3.333\angle60^\circ\;\text{A} \]

Check by synthesis: \(I_a=I_{a0}+I_{a1}+I_{a2}=(1.667-j2.887)+6.667+(1.667+j2.887)=10\angle0^\circ\), and \(I_c=I_{a0}+aI_{a1}+a^2I_{a2}=(1.667-j2.887)+6.667\angle120^\circ+3.333\angle(60^\circ+240^\circ)=(1.667-j2.887)+(-3.333+j5.774)+(1.667-j2.887)=0\) as required.

The neutral current is \(I_n = I_a+I_b+I_c = 5-j8.660 = 10\angle-60^\circ\) A, and \(3I_{a0}=3\times3.333\angle-60^\circ = 10\angle-60^\circ\) A. The two agree, as Section 22-5 requires. This is the set drawn in the figure of Section 22-2.

2 A general unbalanced set, resolved and reassembled

Problem. The line currents of a four-wire system are \(I_a=10\angle0^\circ\) A, \(I_b=12\angle-150^\circ\) A and \(I_c=8\angle100^\circ\) A. Resolve them into symmetrical components and verify the result by reconstructing \(I_b\).

Solution. Convert to rectangular form first: \(I_a=10+j0\), \(I_b=-10.392-j6.000\), \(I_c=-1.389+j7.879\). Then

Zero sequence
\[ I_{a0}=\tfrac13\big(10 - 10.392 - 1.389 + j(0-6.000+7.879)\big)=\tfrac13\big(-1.781+j1.879\big)=0.863\angle133.5^\circ\;\text{A} \]

Multiplying by \(a\) and \(a^2\) is done on the polar forms — add \(120^\circ\) and \(240^\circ\) respectively — and the results converted back:

Positive sequence
\[ I_{a1}=\tfrac13\big(10\angle0^\circ + 12\angle{-30^\circ} + 8\angle340^\circ\big) = \tfrac13\big(10+(10.392-j6.000)+(7.518-j2.736)\big) \]
\[ = \tfrac13\big(27.910-j8.736\big)=\tfrac13\big(29.245\angle{-17.4^\circ}\big)=9.748\angle{-17.4^\circ}\;\text{A} \]
Negative sequence
\[ I_{a2}=\tfrac13\big(10\angle0^\circ + 12\angle90^\circ + 8\angle220^\circ\big)=\tfrac13\big(10+j12+(-6.128-j5.142)\big) \]
\[ = \tfrac13\big(3.872+j6.858\big)=\tfrac13\big(7.875\angle60.6^\circ\big)=2.625\angle60.6^\circ\;\text{A} \]

Reconstruct \(I_b = I_{a0}+a^2I_{a1}+aI_{a2}\):

Check
\[ I_b = 0.863\angle133.5^\circ + 9.748\angle(-17.4^\circ+240^\circ) + 2.625\angle(60.6^\circ+120^\circ) \]
\[ = (-0.594+j0.626)+(-7.176-j6.598)+(-2.625-j0.028) = -10.395-j6.000 = 12\angle{-150^\circ}\;\checkmark \]

The neutral carries \(3I_{a0}=2.589\angle133.5^\circ\) A. Notice the proportions: the positive-sequence component is \(9.75\) A against a negative-sequence component of \(2.63\) A and a zero-sequence component of \(0.86\) A. A set that looks badly unbalanced is in fact a strong positive-sequence set with modest contamination — which is exactly the situation a protection engineer must be able to quantify.

3 The single line-to-ground condition

Problem. A bolted single line-to-ground fault on phase \(a\) at a bus draws \(I_f=-j5.0\) per unit. Phases \(b\) and \(c\) carry no current. Find the sequence currents, and state what the same conditions imply about the sequence voltages if the system is earthed.

Solution. With \(I_b=I_c=0\), every one of the three analysis equations reduces to the same single term, because whatever multiplies \(I_b\) and \(I_c\) multiplies zero:

All three components are equal
\[ I_{a0}=I_{a1}=I_{a2}=\frac{I_a}{3}=\frac{-j5.0}{3}=-j1.667\;\text{pu} \]

The fault current is \(I_f = 3I_{a0} = -j5.0\) pu, so the useful working form is \(I_f = 3I_{a1}\): the fault current is three times the positive-sequence current, not equal to it. The magnitude of each sequence component is only a third of the total, which is a common source of error when a computed \(I_{a1}\) is mistaken for the answer.

On the voltage side the remaining terminal condition is \(V_a=0\) for a bolted fault, and since \(V_a=V_{a0}+V_{a1}+V_{a2}\),

Voltage constraint
\[ V_{a0}+V_{a1}+V_{a2}=0 \]

Three networks carrying the same current whose voltages sum to zero is the description of three impedances in series across a source. Chapter 24 draws that connection and solves it as \(I_{a1}=E/(Z_1+Z_2+Z_0+3Z_f)\), where the \(3Z_f\) arises because the fault impedance carries \(I_f=3I_{a1}\) while appearing in a network that carries only \(I_{a1}\).

4 The line-to-line condition, and the absence of zero sequence

Problem. A bolted fault between phases \(b\) and \(c\) causes \(I_b=8.66\angle-90^\circ\) A and \(I_c=8.66\angle90^\circ\) A, with \(I_a=0\). Find the sequence currents, and confirm that no earth current flows.

Solution. Write \(I_b=-j8.66\) and \(I_c=+j8.66=-I_b\). The zero sequence goes first:

Zero sequence vanishes
\[ I_{a0}=\tfrac13\big(0+I_b+(-I_b)\big)=0 \]

and since \(I_n=3I_{a0}\), no current returns through earth or neutral — correct, because the fault never touched earth. For the other two, factor \(I_b\) out:

Positive and negative sequence
\[ I_{a1}=\tfrac13\big(0+aI_b+a^2(-I_b)\big)=\frac{I_b}{3}\big(a-a^2\big)=\frac{I_b}{3}\big(j\sqrt3\big)=\frac{jI_b}{\sqrt3} = \frac{j(-j8.66)}{1.732}=5.0\angle0^\circ\;\text{A} \]
\[ I_{a2}=\frac{I_b}{3}\big(a^2-a\big)=-\frac{jI_b}{\sqrt3}=5.0\angle180^\circ\;\text{A} \]

So \(I_{a1}=-I_{a2}\), with \(|I_b|=\sqrt3\,|I_{a1}|\). Check by synthesis: \(I_a=0+5.0+(-5.0)=0\;\checkmark\), and \(I_b=0+a^2(5.0)+a(-5.0)=5.0(a^2-a)=5.0(-j\sqrt3)=-j8.66\;\checkmark\). Two networks carrying equal and opposite currents, with no third network involved, is the description of two impedances connected in opposition — the sequence-network connection Chapter 24 uses for this fault.

5 Power computed both ways

Problem. At an unbalanced bus the phase voltages are \(V_a=1.00\angle0^\circ\), \(V_b=0.90\angle-115^\circ\), \(V_c=1.10\angle110^\circ\) per unit and the line currents are \(I_a=1.00\angle0^\circ\), \(I_b=1.20\angle-150^\circ\), \(I_c=0.80\angle100^\circ\) per unit. Compute the complex power in phase quantities and again in sequence quantities.

Solution. In phase quantities, term by term:

Direct summation
\[ V_aI_a^*=1.000\angle0^\circ, \qquad V_bI_b^*=1.080\angle35^\circ, \qquad V_cI_c^*=0.880\angle10^\circ \]
\[ S = 1.000+(0.885+j0.619)+(0.867+j0.153) = 2.751+j0.772 = 2.858\angle15.7^\circ\;\text{pu} \]

Now resolve both sets. The currents are one tenth of Example 2's, so their components are \(I_{a0}=0.0863\angle133.5^\circ\), \(I_{a1}=0.9748\angle-17.4^\circ\), \(I_{a2}=0.2625\angle60.6^\circ\). Resolving the voltages the same way gives

Sequence voltages
\[ V_{a0}=0.1089\angle41.8^\circ, \qquad V_{a1}=0.9940\angle{-2.2^\circ}, \qquad V_{a2}=0.0823\angle{-154.7^\circ}\;\text{pu} \]
Summation over the sequences
\[ 3V_{a0}I_{a0}^*=0.0282\angle{-91.6^\circ}, \qquad 3V_{a1}I_{a1}^*=2.9070\angle15.2^\circ, \qquad 3V_{a2}I_{a2}^*=0.0648\angle144.7^\circ \]
\[ S = (-0.001-j0.028)+(2.805+j0.763)+(-0.053+j0.037)=2.751+j0.772\;\checkmark \]

The two routes agree to three decimals. The breakdown is more informative than the total: the positive-sequence term alone is \(2.907\) per unit, against \(0.065\) for the negative sequence and \(0.028\) for the zero sequence. The three are phasors and partly cancel, which is why they sum to \(2.858\) per unit rather than to \(3.000\). Both minor terms deliver almost no real power — the zero-sequence contribution is very nearly \(-j0.028\), pure reactive — and in a machine they are the heating discussed in Section 22-8 rather than useful output.

6 Sequence impedances of an earthed line

Problem. A transposed three-phase line has a self impedance of \(0.5+j3.0\) per unit per phase and a mutual impedance of \(0.1+j1.0\) per unit between each pair of phases. Find \(Z_0\), \(Z_1\) and \(Z_2\). Then find \(Z_0\) if the star point at the receiving end is earthed through a reactor of \(j0.5\) per unit.

Solution. The line is balanced, so the result of Section 22-7 applies without further work:

Sequence impedances
\[ Z_0 = Z_s+2Z_m = (0.5+j3.0)+2(0.1+j1.0) = 0.7+j5.0\;\text{pu} \]
\[ Z_1 = Z_2 = Z_s-Z_m = (0.5+j3.0)-(0.1+j1.0) = 0.4+j2.0\;\text{pu} \]

The zero-sequence impedance is two and a half times the positive-sequence value. The reason is visible in the algebra: positive- and negative-sequence currents sum to zero across the three phases, so the mutual coupling opposes the self impedance and is subtracted; zero-sequence currents are identical in all three phases, so the couplings reinforce and are added twice over. For real overhead lines the ratio \(Z_0/Z_1\) is typically between \(2\) and \(3.5\), and Chapter 23 shows that the earth return path adds further to it.

With the star point earthed through \(Z_n=j0.5\) pu, the neutral drop enters every phase equation and appears tripled in the zero-sequence network alone:

Effect of the earthing reactor
\[ Z_0 = Z_s+2Z_m+3Z_n = 0.7+j5.0+3(j0.5) = 0.7+j6.5\;\text{pu}, \qquad Z_1=Z_2=0.4+j2.0\;\text{pu unchanged} \]

The earthing reactor has raised \(Z_0\) by \(30\,\%\) and left the other two sequences untouched. Since Example 3 showed that an LG fault current is \(3E/(Z_1+Z_2+Z_0+3Z_f)\), raising \(Z_0\) is a direct and selective way of limiting earth-fault current without affecting three-phase fault levels or normal operation at all — which is precisely why neutral earthing reactors and resistors are used. Chapter 37 takes up the choice of earthing method in full.

Review

Chapter Summary

Fortescue's theorem

Any three phasors resolve uniquely into a positive-, a negative- and a zero-sequence balanced set.

The transformation

\(\mathbf{V}_{abc}=\mathbf{A}\mathbf{V}_{012}\) with rows \((1,1,1)\), \((1,a^2,a)\), \((1,a,a^2)\).

Its inverse

\(\mathbf{A}^{-1}=\tfrac13\mathbf{A}^*\), because \(1+a+a^2=0\) kills every unwanted term.

Neutral current

\(I_n=3I_{a0}\). No neutral, no earth, or a delta connection means no zero-sequence line current.

Power

\(S=3(V_{a0}I_{a0}^*+V_{a1}I_{a1}^*+V_{a2}I_{a2}^*)\) — no cross terms between sequences.

Decoupling

\(\mathbf{A}\) diagonalises any balanced \(\mathbf{Z}_{abc}\): \(Z_0=Z_s+2Z_m\), \(Z_1=Z_2=Z_s-Z_m\).

The factor 3Zn

A neutral earthing impedance appears as \(3Z_n\), and only in the zero-sequence network.

Fault signatures

LG gives \(I_{a0}=I_{a1}=I_{a2}\) (series); LL gives \(I_{a0}=0\), \(I_{a1}=-I_{a2}\) (opposition).

Practice

Practice Problems

Refer every set of components to phase \(a\), and check each answer by synthesising at least one phase quantity back from the components. Difficulty rises down the list.

  1. The line currents in a four-wire system are \(I_a=15\angle0^\circ\) A, \(I_b=15\angle-90^\circ\) A and \(I_c=15\angle150^\circ\) A. Find the three sequence components and the neutral current, and verify that \(I_n=3I_{a0}\).
  2. A three-phase set has \(V_{a0}=0.2\angle90^\circ\), \(V_{a1}=1.0\angle0^\circ\) and \(V_{a2}=0.3\angle-60^\circ\) per unit. Construct \(V_a\), \(V_b\) and \(V_c\), and state whether the resulting set could exist on the lines of a delta-connected load.
  3. Show from the analysis equations that a balanced \(a\)–\(b\)–\(c\) set has \(I_{a1}\) equal to the phase current and \(I_{a2}=I_{a0}=0\), and that a balanced \(a\)–\(c\)–\(b\) set has \(I_{a2}\) equal to the phase current and \(I_{a1}=I_{a0}=0\).
  4. Prove that \(\mathbf{A}^{-1}=\tfrac13\mathbf{A}^*\) by evaluating \(\mathbf{A}\mathbf{A}^*\) entry by entry, using only \(a^3=1\) and \(1+a+a^2=0\).
  5. A single-phase load of 500 kVA at unity power factor is connected between line \(a\) and neutral of an 11 kV, four-wire system. Find the three sequence components of the line current, and the current in the neutral conductor.
  6. A star-connected load of \(10+j5\;\Omega\) per phase has its star point earthed through \(2+j3\;\Omega\). Write \(\mathbf{Z}_{abc}\) including the neutral term and hence obtain \(Z_0\), \(Z_1\) and \(Z_2\). Comment on why only one of the three changed.
  7. For the currents of Problem 1 and phase voltages \(V_a=1.0\angle0^\circ\), \(V_b=1.0\angle-120^\circ\), \(V_c=1.0\angle120^\circ\) per unit, compute the complex power both directly and from the sequence components, and explain which sequence terms are non-zero and why.
  8. A generator supplies a load whose currents contain \(4\,\%\) negative sequence. Using \(P=3\,\text{Re}(V_{a2}I_{a2}^*)\) for that term alone and \(X_2=X_d''\), estimate the fraction of rated power appearing as double-frequency rotor loss, and explain why the manufacturer's continuous limit on \(|I_{a2}|\) is stated as an \(I_2^2t\) figure rather than a current.
Tip: the transformation is arithmetic, and the arithmetic is where marks are lost. Multiplying by \(a\) means adding \(120^\circ\) to an angle, so do it in polar form; adding phasors means converting to rectangular form, so do that separately. Keep the two operations apart on the page and the calculation becomes mechanical. Two checks catch almost every slip: the three components must synthesise back to the original phase quantities, and \(I_a+I_b+I_c\) must equal \(3I_{a0}\) exactly. Neither takes more than a minute, and one of them will find the error.