Part 2 · Chapter 6

Inductance of Transmission Lines

Every inductance formula in this chapter — for a solid wire, a stranded cable, a single-phase pair, a transposed three-phase line or a double circuit — turns out to be the same expression, \(2\times10^{-7}\ln(\text{GMD}/\text{GMR})\), and the work lies entirely in identifying which distances belong in the numerator and which in the denominator.

Electric Power Systems Prof. Mithun Mondal Reading time ≈ 45 min
i What you'll learn
  • Why the flux inside a conductor contributes exactly \(\tfrac12\times10^{-7}\) H/m whatever the conductor's radius, and why that constant can be absorbed into a fictitious radius \(r' = 0.7788\,r\).
  • How Ampère's law outside the conductor gives \(2\times10^{-7}\ln(D_2/D_1)\), the one integral this whole chapter rests on.
  • The flux linkage of one conductor in a group whose currents sum to zero, and why the remote point of integration disappears from the answer.
  • How that result produces the geometric mean distance and geometric mean radius for a composite conductor — the \(D_s\) tabulated in Chapter 5.
  • Why an equilateral three-phase line is balanced automatically, why a flat one is not, and how transposition restores balance with \(D_{eq} = \sqrt[3]{D_{12}D_{23}D_{31}}\).
  • How a double circuit is handled by treating each phase's two conductors as one composite conductor.
  • What the numbers come to in practice — around \(0.4\;\Omega\)/km of reactance — and how that becomes a per-unit value on Chapter 4's bases.
Section 6-1

Why the Series Reactance Rules the Line

Chapter 4 drew every transmission line as a series impedance \(R + jX\) and then, in the reactance diagram, quietly dropped the \(R\). That was not laziness. For a 132 kV line on Panther conductor the resistance is about \(0.14\;\Omega\)/km and the reactance about \(0.39\;\Omega\)/km; at 400 kV on bundled Moose the ratio widens to ten or more. The series reactance is what limits how much power a line can carry, what sets the voltage drop from one end to the other, what determines the current in a fault, and what appears in the swing equation of Chapter 27. Computing it correctly is therefore the most consequential single calculation in Part 2.

Inductance is defined by flux linkage per ampere,

Definition
\[ L = \frac{\lambda}{I}\quad\text{H}, \qquad \lambda \text{ in weber-turns} \]

and for a coil the flux linkage is unambiguous: a flux \(\phi\) that threads \(N\) turns links \(N\phi\). A transmission line has no turns. What takes their place is a subtler bookkeeping: a tube of flux at radius \(x\) from the conductor axis links only that part of the current which flows inside radius \(x\), so a flux tube inside the conductor is weighted by the fraction \(x^2/r^2\), while one outside is weighted by unity. Getting that weighting right, and then deciding how far out to integrate, is the whole of the calculation.

The plan of the chapter is to build the answer in layers. Sections 6-2 and 6-3 handle a single isolated conductor, inside and outside. Section 6-4 assembles a two-wire line from them and extracts the trick that removes the internal term from every subsequent formula. Section 6-5 generalises to any number of conductors whose currents sum to zero — the condition that a balanced power circuit always satisfies — and Sections 6-6 to 6-9 are that one result applied to stranded conductors, to three-phase lines, and to double circuits.

Two assumptions run through all of it, and both are good ones for a power line at 50 Hz. The conductor material is non-magnetic, so \(\mu = \mu_0 = 4\pi\times10^{-7}\) H/m — true for copper and aluminium, and the reason the steel core of ACSR is excluded from the calculation. And the current density is uniform over the cross-section, which is the statement that skin effect is being neglected; Chapter 5 measured that error and found it to be a few per cent.

The two lengths that matter. Everything below reduces to a ratio of two distances inside a logarithm — a distance characterising how far apart the go and return conductors are, and a distance characterising how big the conductor itself is. Nothing else about the geometry survives. That is why a line's inductance is so insensitive to design changes: doubling the phase spacing adds only \(2\times10^{-7}\ln 2 = 0.139\) mH/km, about a tenth of the total.
Section 6-2

Inductance Due to Internal Flux

Take a long, straight, solid cylindrical conductor of radius \(r\) carrying a current \(I\), and suppose for the moment that the return path is so far away that it disturbs nothing. By symmetry the magnetic field lines are circles concentric with the conductor, and \(H\) is constant in magnitude along any such circle and tangent to it. Ampère's law applied to a circle of radius \(x\) inside the conductor gives

Ampère's law inside the conductor
\[ \oint \mathbf{H}\cdot d\mathbf{s} = I_x \;\Longrightarrow\; H_x\,(2\pi x) = I_x \]
\[ I_x = \frac{\pi x^2}{\pi r^2}\,I = \frac{x^2}{r^2}I \;\Longrightarrow\; H_x = \frac{x I}{2\pi r^2}\;\;\text{A/m} \]

The second line is where the uniform-current-density assumption enters: only the current enclosed by the circle of radius \(x\) counts, and that is the total current scaled by the ratio of the areas. Multiplying by the permeability gives the flux density, and integrating across an annular element of thickness \(dx\) over one metre of length gives the flux in that element:

Flux in an internal tube
\[ B_x = \mu_0 H_x = \frac{\mu_0 x I}{2\pi r^2}\;\;\text{Wb/m}^2, \qquad d\phi = B_x\,dx = \frac{\mu_0 x I}{2\pi r^2}\,dx\;\;\text{Wb/m} \]

Now the weighting. The flux \(d\phi\) forms a closed loop around the axis, but it encircles only the current \(I_x\), not the whole of \(I\). In the language of flux linkage it links a fraction \(x^2/r^2\) of a "turn", so

Internal flux linkage per metre
\[ d\lambda = \frac{x^2}{r^2}\,d\phi = \frac{\mu_0 x^3 I}{2\pi r^4}\,dx \]
\[ \lambda_{\text{int}} = \int_0^{r}\frac{\mu_0 x^3 I}{2\pi r^4}\,dx = \frac{\mu_0 I}{2\pi r^4}\cdot\frac{r^4}{4} = \frac{\mu_0 I}{8\pi}\;\;\text{Wb-t/m} \]
🔑
Internal inductance
\[ L_{\text{int}} = \frac{\lambda_{\text{int}}}{I} = \frac{\mu_0}{8\pi} = \frac{4\pi\times10^{-7}}{8\pi} = \frac{1}{2}\times10^{-7}\;\;\text{H/m} \]

The radius has cancelled. A thin wire and a thick busbar of the same non-magnetic material have exactly the same internal inductance per metre — \(0.05\) mH per kilometre. This is not an approximation; it is exact for uniform current density, and it is the reason the internal contribution can be dealt with once and never mentioned again.

The cancellation has a physical reading. Making the conductor fatter spreads the current over a larger area, which weakens the internal field at any given fraction of the radius; but it also provides more volume in which that field can store energy. The two effects are exactly equal and opposite.

Section 6-3

Inductance Due to External Flux

Outside the conductor the same argument is simpler, because every flux tube encircles the entire current. Take two points \(P_1\) and \(P_2\) at distances \(D_1\) and \(D_2\) from the conductor axis, with \(D_1 \ge r\), and ask for the flux linkage produced between them.

r x inside: links Iₓ = (x²/r²)·I L_int = ½ × 10⁻⁷ H/m internal flux P₁ P₂ D₁ D₂ outside: every tube links all of I λ₁₂ = 2 × 10⁻⁷ I ln(D₂/D₁) external flux
The two regions and the different weight each flux tube carries
Ampère's law outside the conductor
\[ H_x(2\pi x) = I \;\Longrightarrow\; B_x = \frac{\mu_0 I}{2\pi x}, \qquad d\lambda = d\phi = \frac{\mu_0 I}{2\pi x}\,dx \]
\[ \lambda_{12} = \int_{D_1}^{D_2}\frac{\mu_0 I}{2\pi x}\,dx = \frac{\mu_0 I}{2\pi}\ln\frac{D_2}{D_1} = 2\times10^{-7}\,I\,\ln\frac{D_2}{D_1}\;\;\text{Wb-t/m} \]
🔑
The integral the chapter is built on
\[ L_{12} = 2\times10^{-7}\ln\frac{D_2}{D_1}\;\;\text{H/m} \]

Every formula that follows is this expression with different distances substituted into it. The logarithm is the reason all line inductances land in the same narrow band: a distance ratio has to change by a factor of \(e = 2.718\) to move the inductance by \(0.2\) mH/km.

One caution about \(D_2 \to \infty\). Taken alone, the integral diverges: a single isolated conductor carrying a steady current has infinite inductance per metre. That is not a defect of the analysis but a statement that a single conductor carrying current with no return path does not exist. In every real circuit there is a return, its flux opposes this one, and the divergence cancels. Section 6-5 shows the cancellation happening explicitly.

Section 6-4

The Single-Phase Line and the Radius \(r'\)

Consider two parallel conductors of radii \(r_1\) and \(r_2\), their axes a distance \(D\) apart, one carrying \(+I\) and the other \(-I\). Ask for the inductance associated with conductor 1.

Flux produced by conductor 1's own current links conductor 1's circuit out to the location of conductor 2, and no further: a flux tube at a distance greater than \(D+r_2\) encircles both \(+I\) and \(-I\), a net zero, and links nothing. A tube between \(D-r_2\) and \(D+r_2\) links a part of conductor 2's current and is awkward to treat exactly, but the conductors of a power line are centimetres thick and metres apart, so \(r_2 \ll D\) and it is entirely legitimate to integrate out to \(D\) and stop. With that, the flux linkage of conductor 1 is the internal term of Section 6-2 plus the external term of Section 6-3 taken from \(r_1\) to \(D\):

Inductance of conductor 1
\[ L_1 = \underbrace{\tfrac12\times10^{-7}}_{\text{internal}} + \underbrace{2\times10^{-7}\ln\frac{D}{r_1}}_{\text{external}} = 2\times10^{-7}\left(\frac14 + \ln\frac{D}{r_1}\right) \]

The bracket can be tidied by noticing that \(\tfrac14 = \ln e^{1/4}\), and that adding a logarithm is multiplying inside it:

Absorbing the internal flux into the radius
\[ L_1 = 2\times10^{-7}\left(\ln e^{1/4} + \ln\frac{D}{r_1}\right) = 2\times10^{-7}\ln\frac{D}{r_1 e^{-1/4}} = 2\times10^{-7}\ln\frac{D}{r_1'} \]
\[ r' \equiv e^{-1/4}\,r = 0.7788\,r \]
🔑
The fictitious radius
\(r' = 0.7788\,r\) is the radius of a hypothetical thin-walled tube which, carrying the same current, has no internal flux and yet exactly the same total inductance as the real solid conductor.

From this point forward, internal flux never appears again. Every formula is written with \(r'\) — or, for a stranded conductor, with the \(D_s\) of Chapter 5 that plays the same role — and the external integral is taken from that radius outward.

Conductor 2 carries \(-I\), so the flux it produces around itself circulates the opposite way; but conductor 2's circuit is also traversed the opposite way, and the two reversals cancel. Its flux linkage adds to conductor 1's rather than subtracting from it, and the two inductances simply sum. For constant permeability that superposition is exact.

Loop inductance of a single-phase line
\[ L = L_1 + L_2 = 2\times10^{-7}\left(\ln\frac{D}{r_1'} + \ln\frac{D}{r_2'}\right) = 4\times10^{-7}\ln\frac{D}{\sqrt{r_1'r_2'}} \]
\[ \text{if } r_1 = r_2 = r: \qquad L = 4\times10^{-7}\ln\frac{D}{r'}\;\;\text{H/m} \]
Per conductor or per loop — say which. \(L_1 = 2\times10^{-7}\ln(D/r')\) is the inductance of one conductor; the loop formed by both has twice that. In three-phase work the useful quantity is always the per-phase (that is, per-conductor) value, because per-phase analysis of Chapter 3 treats one phase against a fictitious neutral. Mixing the two is the commonest factor-of-two error in this subject.
Section 6-5

Flux Linkages of One Conductor in a Group

A three-phase line has three conductors, a double circuit has six, a stranded conductor has dozens of filaments. All of them are handled by one general result, and the only condition it needs is the one every balanced power circuit satisfies: the currents sum to zero.

Let \(n\) parallel conductors carry currents \(I_1, I_2, \dots, I_n\) with \(\sum I_k = 0\). Choose a remote point \(P\) and, using Section 6-3, write the flux linkage of conductor 1 caused by each current in turn out to that point. The contribution of \(I_1\) starts at conductor 1's own surface, so it uses \(r_1'\); the contribution of \(I_k\) starts at the distance \(D_{1k}\) between the conductors, because flux from \(I_k\) closer to conductor \(k\) than that does not encircle conductor 1 at all.

1 2 3 n I₁ + I₂ + ⋯ + Iₙ = 0 D₁₂ D₁₃ D₁ₙ P D₁P DₙP as P recedes, D₁P / DₙP → 1 and every P-term vanishes
The remote point is a scaffold: it must appear during the derivation and be gone from the answer
Total flux linkage of conductor 1 out to \(P\)
\[ \lambda_{1P} = 2\times10^{-7}\left(I_1\ln\frac{D_{1P}}{r_1'} + I_2\ln\frac{D_{2P}}{D_{12}} + I_3\ln\frac{D_{3P}}{D_{13}} + \cdots + I_n\ln\frac{D_{nP}}{D_{1n}}\right) \]

Split every logarithm of a quotient into a difference and collect the two kinds of term:

Separating the near terms from the far terms
\[ \lambda_{1P} = 2\times10^{-7}\Bigg(I_1\ln\frac{1}{r_1'} + I_2\ln\frac{1}{D_{12}} + \cdots + I_n\ln\frac{1}{D_{1n}} \Bigg) \]
\[ \qquad\qquad +\; 2\times10^{-7}\Big(I_1\ln D_{1P} + I_2\ln D_{2P} + \cdots + I_n\ln D_{nP}\Big) \]

The first bracket contains only the geometry of the conductor group. The second contains the remote point, and it is the one that must be made to disappear. Use the condition \(\sum I_k = 0\) in the form \(I_n = -(I_1+I_2+\cdots+I_{n-1})\) and substitute it into the last term of the second bracket:

Eliminating \(I_n\) from the far terms
\[ \sum_{k=1}^{n} I_k \ln D_{kP} = I_1\ln\frac{D_{1P}}{D_{nP}} + I_2\ln\frac{D_{2P}}{D_{nP}} + \cdots + I_{n-1}\ln\frac{D_{(n-1)P}}{D_{nP}} \]

Every surviving term is now a logarithm of a ratio of distances to \(P\). As \(P\) recedes, those distances become more and more nearly equal — the conductors are metres apart and \(P\) is kilometres away — so each ratio tends to \(1\) and each logarithm to \(0\). The divergence noted at the end of Section 6-3 has cancelled, exactly as promised, and it did so because the currents sum to zero.

🔑
Flux linkage of one conductor in a group
\[ \lambda_1 = 2\times10^{-7}\left(I_1\ln\frac{1}{r_1'} + I_2\ln\frac{1}{D_{12}} + I_3\ln\frac{1}{D_{13}} + \cdots + I_n\ln\frac{1}{D_{1n}}\right)\;\;\text{Wb-t/m} \]

Valid whenever \(I_1+I_2+\cdots+I_n=0\). Each current is weighted by the logarithm of the reciprocal of its distance from the conductor in question, with the conductor's own current weighted by \(1/r_1'\). Everything in the remaining seven sections is an application of this single line.

Section 6-6

Composite Conductors: GMD and GMR

Chapter 5 established that every practical conductor is stranded, and that magnetically it must be treated as a bundle of parallel filaments rather than a solid rod. Section 6-5 now supplies the machinery.

Let a single-phase line consist of two composite conductors. Conductor \(X\) is made of \(n\) identical filaments \(a, b, \dots, n\), each carrying \(I/n\); conductor \(Y\) is the return, made of \(m\) identical filaments \(a', b', \dots, m\), each carrying \(-I/m\). The currents sum to zero, so the group formula applies. Applying it to filament \(a\):

Flux linkage of one filament
\[ \lambda_a = 2\times10^{-7}\frac{I}{n}\left(\ln\frac{1}{r_a'}+\ln\frac{1}{D_{ab}}+\cdots+\ln\frac{1}{D_{an}}\right) - 2\times10^{-7}\frac{I}{m}\left(\ln\frac{1}{D_{aa'}}+\cdots+\ln\frac{1}{D_{am}}\right) \]
\[ = 2\times10^{-7}\,I\,\ln\frac{\sqrt[m]{D_{aa'}D_{ab'}\cdots D_{am}}}{\sqrt[n]{r_a'\,D_{ab}\,D_{ac}\cdots D_{an}}} \]

The second line is worth pausing over, because it is where the roots come from. A sum of logarithms divided by \(n\) is the logarithm of an \(n\)-th root of a product; the minus sign turns the \(Y\)-filament product into a numerator. Filament \(a\) carries \(I/n\), so its inductance is

Inductance of one filament
\[ L_a = \frac{\lambda_a}{I/n} = 2n\times10^{-7}\ln\frac{\sqrt[m]{D_{aa'}D_{ab'}\cdots D_{am}}}{\sqrt[n]{r_a'\,D_{ab}\cdots D_{an}}} \]

Each filament has a different \(L\), because each sits in a different position. The filaments are in parallel and share the current, so the inductance of conductor \(X\) as a whole is the average of the filament inductances divided by the number in parallel:

Combining the filaments
\[ L_{av} = \frac{L_a+L_b+\cdots+L_n}{n}, \qquad L_X = \frac{L_{av}}{n} = \frac{L_a+L_b+\cdots+L_n}{n^2} \]

Substituting the filament expressions and collecting the \(mn\) distances that appear in every numerator and the \(n^2\) that appear in every denominator gives the result in a form that is nothing but two geometric means.

🔑
The master formula
\[ L_X = 2\times10^{-7}\ln\frac{D_m}{D_s}\;\;\text{H/m} \]
\[ D_m = \sqrt[mn]{\prod_{i\in X}\prod_{j\in Y} D_{ij}}, \qquad D_s = \sqrt[n^2]{\prod_{i\in X}\prod_{j\in X} D_{ij}}\;\;(D_{ii}=r_i') \]

\(D_m\), the mutual geometric mean distance or GMD, is the \(mn\)-th root of the product of every distance from a filament of \(X\) to a filament of \(Y\). \(D_s\), the self GMD or geometric mean radius, is the \(n^2\)-th root of the product of every distance from a filament of \(X\) to a filament of \(X\), the self-distances being \(r'\). The inductance of the complete line is \(L = L_X + L_Y\), with \(D_m\) the same for both and \(D_s\) computed separately for each.

Three consequences deserve to be drawn out. First, the formula contains the results of Section 6-4 as a special case: for two solid conductors \(n=m=1\), \(D_m = D\), \(D_s = r'\), and \(L_X = 2\times10^{-7}\ln(D/r')\) as before. Second, \(D_s\) is a property of the conductor alone — it can be computed once by the manufacturer and printed in a catalogue, which is exactly what the \(D_s\) column of Chapter 5's ACSR table is. Third, \(D_m\) is a property of the spacing alone, and when the conductors are far apart compared with their own size, \(D_m\) is very nearly the centre-to-centre distance, which is why hand calculations on ordinary lines use the spacing directly and lose nothing.

Two averages, two roles. \(D_m\) measures how far the go and return circuits are from one another and sits in the numerator, so wider spacing means more inductance. \(D_s\) measures how spread out the conductor's own metal is and sits in the denominator, so a fatter — or a bundled — conductor means less inductance. Chapter 8 exploits the second half of that sentence deliberately: splitting one conductor into a bundle of four raises \(D_s\) by a factor of several and cuts the reactance by around 30%.
Section 6-7

Three-Phase Lines with Equilateral Spacing

Put three conductors at the vertices of an equilateral triangle of side \(D\), each with geometric mean radius \(D_s\), carrying balanced currents \(I_a+I_b+I_c=0\). The group formula of Section 6-5 applied to conductor \(a\) gives

Flux linkage of phase \(a\)
\[ \lambda_a = 2\times10^{-7}\left(I_a\ln\frac{1}{D_s} + I_b\ln\frac{1}{D} + I_c\ln\frac{1}{D}\right) \]

The last two terms carry the same coefficient because \(b\) and \(c\) are equidistant from \(a\). Replace \(I_b + I_c\) by \(-I_a\):

The balance condition does the work
\[ \lambda_a = 2\times10^{-7}\left(I_a\ln\frac{1}{D_s} - I_a\ln\frac{1}{D}\right) = 2\times10^{-7}\,I_a\ln\frac{D}{D_s} \]
🔑
Inductance per phase, equilateral spacing
\[ L_a = L_b = L_c = 2\times10^{-7}\ln\frac{D}{D_s}\;\;\text{H/m per phase} \]

Identical in form to the per-conductor inductance of a single-phase line. The symmetry of the triangle makes the three phases identical without any further intervention, so an equilateral line needs no transposition and behaves as three independent single-phase circuits — which is exactly the assumption per-phase analysis in Chapter 3 was built on.

Two features of this result are worth noticing. The flux linkage of phase \(a\) came out proportional to \(I_a\) alone, with the other two currents having vanished into the balance condition; that is what allows a single per-phase inductance to be quoted at all. And the answer is the same whether the line has a neutral conductor or not, because a balanced set draws no neutral current and a conductor carrying no current produces no flux.

The trouble is that nobody builds equilateral lines. Three conductors at the corners of a triangle require a tower with an awkward outline; horizontal (flat) and vertical configurations are cheaper to build, easier to string and easier to maintain. So the practical case is the unsymmetrical one.

Section 6-8

Unsymmetrical Spacing and Transposition

Let the three conductors sit at three positions with mutual distances \(D_{12}\), \(D_{23}\) and \(D_{31}\), not all equal. Writing out \(\lambda_a\), \(\lambda_b\) and \(\lambda_c\) from the group formula now produces three different expressions, because the middle conductor is closer to both its neighbours than the two outer conductors are to each other. The consequence is real and troublesome: the three phases have different inductances, so equal applied voltages produce unequal currents, and balanced currents produce unequal voltage drops. A line built this way delivers an unbalanced supply even to a perfectly balanced load, and the residual unbalance drives current into the neutral and the earth and induces voltages in nearby telephone circuits.

The remedy is transposition: exchange the physical positions of the conductors at regular intervals along the route, so that each conductor occupies each of the three positions for one third of the length. The line is then geometrically identical as seen from any of the three phases, and the inductance per phase is the average of the three.

pos 1 pos 2 pos 3 a b c b c a ℓ/3 ℓ/3 ℓ/3 one full transposition cycle — every conductor occupies every position once Dₑq = ∛(D₁₂ D₂₃ D₃₁)
Transposition makes three unequal geometries into one average geometry

Carry out that averaging. In the first section \(a\) occupies position 1, \(b\) position 2 and \(c\) position 3; in the second, \(a\) moves to position 2, \(b\) to 3, \(c\) to 1; in the third, \(a\) is at 3, \(b\) at 1, \(c\) at 2. Writing the group formula for phase \(a\) in each section,

Phase \(a\) in the three sections
\[ \lambda_{a1} = 2\times10^{-7}\left(I_a\ln\frac{1}{D_s}+I_b\ln\frac{1}{D_{12}}+I_c\ln\frac{1}{D_{31}}\right) \]
\[ \lambda_{a2} = 2\times10^{-7}\left(I_a\ln\frac{1}{D_s}+I_b\ln\frac{1}{D_{23}}+I_c\ln\frac{1}{D_{12}}\right) \]
\[ \lambda_{a3} = 2\times10^{-7}\left(I_a\ln\frac{1}{D_s}+I_b\ln\frac{1}{D_{31}}+I_c\ln\frac{1}{D_{23}}\right) \]

Average the three. The \(I_b\) terms collect the same three distances as the \(I_c\) terms, so both acquire the coefficient \(\tfrac13\ln\big[1/(D_{12}D_{23}D_{31})\big]\), and \(I_b + I_c = -I_a\) once more:

The average over a transposition cycle
\[ \lambda_a = \frac{\lambda_{a1}+\lambda_{a2}+\lambda_{a3}}{3} = 2\times10^{-7}\left(I_a\ln\frac{1}{D_s} - \frac{I_a}{3}\ln\frac{1}{D_{12}D_{23}D_{31}}\right) \]
\[ = 2\times10^{-7}\,I_a\,\ln\frac{\sqrt[3]{D_{12}D_{23}D_{31}}}{D_s} \]
🔑
The working formula for a three-phase line
\[ L = 2\times10^{-7}\ln\frac{D_{eq}}{D_s}\;\;\text{H/m per phase}, \qquad D_{eq} = \sqrt[3]{D_{12}D_{23}D_{31}} \]

\(D_{eq}\) is the equivalent equilateral spacing: the side of the equilateral triangle that would give the same inductance. Setting \(D_{12}=D_{23}=D_{31}=D\) recovers Section 6-7, so the equilateral case is contained in this one and only the equilateral formula need be remembered.

For the common flat configuration with adjacent spacing \(D\) and outer spacing \(2D\), \(D_{eq} = \sqrt[3]{D\cdot D\cdot 2D} = D\sqrt[3]{2} = 1.26\,D\). A flat line therefore has slightly more inductance than an equilateral line of the same adjacent spacing, and slightly less than one of the same overall width — the geometric mean sitting, as always, between the extremes.

Modern practice frequently omits physical transposition altogether. Full transposition requires a special tower and a costly interruption of the conductor, and on a line of moderate length the resulting unbalance is a fraction of a per cent — small enough to be absorbed. The formula is used anyway, because the assumption of a transposed line is what makes a single per-phase impedance meaningful, and every method from Chapter 16 onward depends on there being one. Where the unbalance genuinely matters — very long EHV lines, or lines feeding sensitive loads — transposition is provided, or the phases of a double circuit are arranged so that the two circuits' unbalances oppose.

Section 6-9

Double-Circuit Lines and Practical Values

A double-circuit line carries two three-phase circuits on one set of towers. Electrically the two circuits are in parallel, but they are close enough to be magnetically coupled, so the inductance is not simply half of one circuit's value; the mutual flux must be accounted for. The machinery of Section 6-6 does it without any new ideas: treat the two conductors belonging to phase \(a\) — call them \(a\) and \(a'\) — as the two filaments of a single composite conductor, and likewise for \(b\) and \(c\).

Composite treatment of a double circuit
\[ D_{S}^{A} = \sqrt{D_s\,D_{aa'}}, \qquad D_{AB} = \sqrt[4]{D_{ab}D_{ab'}D_{a'b}D_{a'b'}} \]
\[ L = 2\times10^{-7}\ln\frac{D_{eq}}{D_S^{\,b}}, \qquad D_{eq} = \sqrt[3]{D_{AB}D_{BC}D_{CA}}, \quad D_S^{\,b} = \sqrt[3]{D_S^AD_S^BD_S^C} \]

The self GMD of the phase-\(a\) group is the geometric mean of the two conductors' own \(D_s\) values and the distance between them; since \(D_{aa'}\) is metres and \(D_s\) is centimetres, the composite \(D_S^A\) is far larger than \(D_s\), and the inductance correspondingly smaller. That is the whole benefit of a double circuit beyond simple redundancy — and it is maximised by placing the two conductors of a phase as far apart as the tower allows, which means the two circuits should be arranged with their phase sequences reversed relative to one another, \(a\,b\,c\) down one side and \(c\,b\,a\) down the other.

R a a' b b' c' c R √3 R 2R hexagonal double circuit Dₑq = 3^(1/4) R D_S = √(2 R Dₛ) same phase at opposite vertices
The hexagonal arrangement, where the algebra closes in one line

The hexagonal arrangement makes the point cleanly. Six conductors sit at the vertices of a regular hexagon of circumradius \(R\), with the two conductors of a phase at opposite vertices. In a regular hexagon the chord subtending \(60^\circ\) equals \(R\), the chord subtending \(120^\circ\) is \(\sqrt3 R\), and the diameter is \(2R\). Taking phases \(a\) and \(b\), one pair of conductors is separated by \(R\) at each of two vertex pairs and by \(\sqrt3 R\) at the other two, so

The hexagonal double circuit
\[ D_{AB} = \sqrt[4]{(\sqrt3R)(R)(R)(\sqrt3R)} = \sqrt[4]{3R^4} = 3^{1/4}R = 1.316\,R \]
\[ D_{eq} = 3^{1/4}R \quad\text{(by symmetry)}, \qquad D_S^{\,b} = \sqrt{D_s\cdot 2R} \]
\[ L = 2\times10^{-7}\ln\frac{3^{1/4}R}{\sqrt{2RD_s}}\;\;\text{H/m per phase} \]

Example 5 puts numbers to it and finds that the double circuit gives less than half the inductance of a single circuit of the same \(D_{eq}\) — the mutual coupling, arranged this way, helps rather than hinders.

What do all these formulas actually produce? Remarkably little variety. The logarithm compresses everything, and for overhead lines the answer always lands near the same figure.

LineConductor\(D_{eq}\)\(D_s\)\(L\) (mH/km)\(X\) at 50 Hz (Ω/km)
33 kV, flat 1.5 mDog1.89 m0.00473 m1.1980.376
132 kV, flat 3 mPanther3.78 m0.00821 m1.2260.385
220 kV, flat 6 mZebra7.56 m0.01151 m1.2970.408
400 kV, flat 11 m, twin bundle at 0.45 m2 × Moose13.86 m0.0758 m1.0420.327
400 kV hexagonal double circuitZebra, \(R=4\) m5.26 m0.303 m0.5710.179
Every overhead line has about 0.4 Ω/km of reactance. Across four voltage levels and a fifteen-fold change in spacing, the single-circuit values in that table vary by less than ten per cent. Only the two devices that raise \(D_s\) substantially — bundling and paralleling a second circuit — move the number appreciably, and both do so by tens of per cent rather than by factors. This is why \(0.4\;\Omega\)/km is a legitimate first estimate for any overhead line whose data you do not have, and why Chapter 8's bundling and Chapter 38's series compensation are the two serious ways to make a line electrically shorter.
Section 6-10

Worked Examples

1 A single-phase two-wire line

Problem. A single-phase 50 Hz line consists of two solid round conductors each of radius 0.5 cm, spaced 1 m between centres. Find the loop inductance and reactance per kilometre, and the fraction of the inductance contributed by flux inside the conductors.

Solution. The fictitious radius comes first, and after it nothing else refers to the internal flux.

Loop inductance
\[ r' = 0.7788\times0.005 = 3.894\times10^{-3}\;\text{m}, \qquad \frac{D}{r'} = \frac{1}{3.894\times10^{-3}} = 256.8 \]
\[ L = 4\times10^{-7}\ln(256.8) = 4\times10^{-7}\times5.5483 = 2.219\times10^{-6}\;\text{H/m} = 2.219\;\text{mH/km} \]
\[ X = 2\pi(50)(2.219\times10^{-3}) = 0.697\;\Omega/\text{km} \]

The internal contribution is \(\tfrac12\times10^{-7}\) H/m per conductor, so \(1.0\times10^{-7}\) H/m for the loop:

Share of the internal flux
\[ \frac{1.0\times10^{-7}}{2.219\times10^{-6}} = 0.0451 = 4.5\% \]

Small, but not negligible — dropping it would understate the reactance by 4.5%, and a designer who used \(r\) in place of \(r'\) would make exactly that error. Notice also how large the reactance of this line is compared with the \(0.4\;\Omega\)/km of Section 6-9: the loop value is twice the per-conductor value, and the ratio \(D/r'\) is larger here than in a three-phase line of the same physical size.

2 A composite-conductor line

Problem. One side of a single-phase line consists of three solid conductors of radius 0.25 cm, arranged in a vertical line at \((0,0)\), \((0,6)\) and \((0,12)\) metres. The return consists of two solid conductors of radius 0.5 cm at \((9,3)\) and \((9,9)\) metres. Find the inductance of each side and of the complete line.

Solution. Label the first side \(a,b,c\) from the bottom and the return \(d,e\). The mutual GMD needs all six cross distances:

The six distances between the sides
\[ D_{ad}=D_{bd}=D_{be}=D_{ce}=\sqrt{9^2+3^2}=\sqrt{90}=9.487\;\text{m} \]
\[ D_{ae}=D_{cd}=\sqrt{9^2+9^2}=\sqrt{162}=12.728\;\text{m} \]
\[ D_m = \sqrt[6]{(9.487)^4(12.728)^2} = \exp\!\left(\frac{4(2.2500)+2(2.5440)}{6}\right) = e^{2.3480} = 10.463\;\text{m} \]

The self GMD of side \(X\) uses the nine distances among \(a,b,c\), with \(r_X' = 0.7788\times0.0025 = 1.947\times10^{-3}\) m and \(D_{ab}=D_{bc}=6\), \(D_{ac}=12\):

Self GMD of the three-conductor side
\[ D_{sX} = \sqrt[9]{(r_X')^3\,(6)^4\,(12)^2} = \exp\!\left(\frac{3(-6.2417)+4(1.7918)+2(2.4849)}{9}\right) \]
\[ = \exp\!\left(\frac{-6.5883}{9}\right) = e^{-0.7320} = 0.4810\;\text{m} \]

For side \(Y\), with \(r_Y' = 0.7788\times0.005 = 3.894\times10^{-3}\) m and \(D_{de}=6\) m, only four distances arise and the fourth root collapses to a square root:

Self GMD of the two-conductor side
\[ D_{sY} = \sqrt[4]{(r_Y')^2(6)^2} = \sqrt{r_Y'\times6} = \sqrt{0.023364} = 0.1529\;\text{m} \]
Inductance of each side and of the line
\[ L_X = 2\times10^{-7}\ln\frac{10.463}{0.4810} = 2\times10^{-7}\ln(21.75) = 6.160\times10^{-7}\;\text{H/m} \]
\[ L_Y = 2\times10^{-7}\ln\frac{10.463}{0.1529} = 2\times10^{-7}\ln(68.45) = 8.452\times10^{-7}\;\text{H/m} \]
\[ L = L_X + L_Y = 1.461\times10^{-6}\;\text{H/m} = 1.461\;\text{mH/km} \]

Side \(Y\) has the larger inductance although its individual conductors are the fatter ones, because it has only two of them and they are closer together: its self GMD is a third of side \(X\)'s. Spreading the metal out is worth far more than making each piece thicker — which is the argument for bundling, stated a chapter early.

3 A transposed three-phase line

Problem. A 132 kV, 50 Hz, three-phase line 100 km long is strung with Panther ACSR (\(D_s = 0.00821\) m) in a horizontal configuration with 3 m between adjacent conductors. The line is fully transposed. Find the equivalent spacing, the inductance per phase per kilometre, the reactance per kilometre and the total series reactance.

Solution. The three mutual distances are 3 m, 3 m and 6 m.

Equivalent spacing and inductance
\[ D_{eq} = \sqrt[3]{3\times3\times6} = \sqrt[3]{54} = 3.780\;\text{m} \]
\[ \frac{D_{eq}}{D_s} = \frac{3.780}{0.00821} = 460.4, \qquad \ln(460.4) = 6.1321 \]
\[ L = 2\times10^{-7}(6.1321) = 1.2264\times10^{-6}\;\text{H/m} = 1.2264\;\text{mH/km} \]
Reactance
\[ X = 2\pi(50)(1.2264\times10^{-3}) = 0.3853\;\Omega/\text{km} \]
\[ X_{\text{total}} = 0.3853\times100 = 38.53\;\Omega \]

Note how modest the effect of the geometry is. Had the conductors been at the corners of an equilateral triangle of side 3 m, \(D_{eq}\) would be 3 m instead of 3.78 m and \(L\) would fall to \(2\times10^{-7}\ln(365.4) = 1.180\) mH/km — a change of under 4% for a completely different tower. The two-thirds power of the outer spacing that \(D_{eq}\) contains, sitting inside a logarithm, is a very weak lever.

4 What actually changes the inductance

Problem. For the line of Example 3, find the effect on \(L\) of (a) doubling every spacing, (b) halving \(D_s\), and (c) computing the inductance of a solid conductor of radius 10.5 mm at the same \(D_{eq}\) while wrongly neglecting the internal flux.

Solution. Because the geometry enters through a logarithm, each change contributes an additive term rather than a multiplicative one.

(a) Doubling the spacing
\[ L' = 2\times10^{-7}\ln\frac{2D_{eq}}{D_s} = L + 2\times10^{-7}\ln 2 = 1.2264 + 0.1386 = 1.3650\;\text{mH/km} \]

An 11.3% increase for a tower twice as wide — the reason phase spacing is set by insulation clearance and mechanical swing, never by inductance.

(b) Halving the geometric mean radius
\[ L'' = 2\times10^{-7}\ln\frac{D_{eq}}{D_s/2} = L + 2\times10^{-7}\ln 2 = 1.3650\;\text{mH/km} \]

Identical to (a), and necessarily so: only the ratio \(D_{eq}/D_s\) exists in the formula, and doubling the numerator is indistinguishable from halving the denominator.

(c) The cost of forgetting the internal flux
\[ \text{correct: } 2\times10^{-7}\ln\frac{3.780}{0.7788\times0.0105} = 2\times10^{-7}\ln(462.3) = 1.2272\;\text{mH/km} \]
\[ \text{wrong: } 2\times10^{-7}\ln\frac{3.780}{0.0105} = 2\times10^{-7}\ln(360.0) = 1.1772\;\text{mH/km} \]
\[ \text{error} = \frac{1.2272-1.1772}{1.2272} = 4.07\% \]

The error is \(2\times10^{-7}\ln(1/0.7788) = 0.0500\) mH/km, which is precisely the \(\tfrac12\times10^{-7}\) H/m of Section 6-2 — the same absolute quantity for every line, and therefore a larger percentage error for the lines with the smallest total inductance.

5 A hexagonal double circuit

Problem. Six conductors of \(D_s = 0.012\) m are arranged at the vertices of a regular hexagon of circumradius 4 m, with the two conductors of each phase at opposite vertices. Find the inductance per phase, and compare it with a single circuit of the same equivalent spacing.

Solution. Using the hexagon results of Section 6-9:

The two geometric means
\[ D_{eq} = 3^{1/4}\times4 = 1.3161\times4 = 5.264\;\text{m} \]
\[ D_S^{\,b} = \sqrt{D_s\times2R} = \sqrt{0.012\times8} = \sqrt{0.096} = 0.3098\;\text{m} \]
\[ L = 2\times10^{-7}\ln\frac{5.264}{0.3098} = 2\times10^{-7}\ln(16.99) = 5.665\times10^{-7}\;\text{H/m} \]
\[ = 0.5665\;\text{mH/km}, \qquad X = 2\pi(50)(0.5665\times10^{-3}) = 0.1780\;\Omega/\text{km} \]

A single circuit with the same \(D_{eq}\) and the same conductor would have

The single-circuit comparison
\[ L_{\text{single}} = 2\times10^{-7}\ln\frac{5.264}{0.012} = 2\times10^{-7}\ln(438.7) = 1.2168\;\text{mH/km} \]
\[ \tfrac12 L_{\text{single}} = 0.6084\;\text{mH/km} \quad\text{against}\quad L_{\text{double}} = 0.5665\;\text{mH/km} \]

Two independent circuits in parallel would give 0.6084 mH/km; the coupled hexagonal pair gives 0.5665, seven per cent better. The gain comes entirely from \(D_{aa'} = 2R = 8\) m being as large as the arrangement permits. Had the two circuits been strung with the same phase sequence on both sides — so that \(a\) and \(a'\) sat at adjacent vertices, \(D_{aa'} = R = 4\) m — then \(D_S^{\,b} = \sqrt{0.048} = 0.2191\) m and \(L\) would rise to \(2\times10^{-7}\ln(24.02) = 0.6359\) mH/km, worse than two uncoupled circuits. Reversing the sequence on the second circuit costs nothing and is always done.

6 Back to per unit

Problem. Express the series impedance of the 100 km Panther line of Example 3 in per unit on a base of 100 MVA and 132 kV, taking the conductor resistance as 0.139 Ω/km at 20 °C and an operating temperature of 75 °C. Comment on the \(X/R\) ratio.

Solution. Chapter 4 gives the base impedance from the two chosen bases:

Base impedance
\[ Z_{\text{base}} = \frac{(kV_{\text{base}})^2}{MVA_{\text{base}}} = \frac{132^2}{100} = 174.24\;\Omega \]

The resistance is corrected to operating temperature by the rule of Chapter 5, with \(T = 228\) °C for aluminium:

Resistance at 75 °C
\[ R_{75} = 0.139\times\frac{228+75}{228+20} = 0.139\times1.2218 = 0.1698\;\Omega/\text{km} \]
\[ R_{\text{total}} = 16.98\;\Omega, \qquad X_{\text{total}} = 38.53\;\Omega \]
Per-unit impedance
\[ R_{pu} = \frac{16.98}{174.24} = 0.0975, \qquad X_{pu} = \frac{38.53}{174.24} = 0.2211 \]
\[ Z_{pu} = 0.0975 + j0.2211 = 0.2416\,\angle 66.2^\circ \]

The \(X/R\) ratio is \(38.53/16.98 = 2.27\). At 132 kV that is low enough that dropping the resistance — as the reactance diagram of Chapter 4 does — would be a real approximation, acceptable for a fault-current estimate but not for a load-flow or a loss calculation. On a 400 kV line with a twin Moose bundle the resistance per phase falls to about \(0.028\;\Omega\)/km while the reactance stays near \(0.33\), so \(X/R\) rises to roughly ten and the reactance diagram becomes almost exact. The higher the voltage, the more nearly a transmission line is a pure inductor — which is the assumption every stability result in Part 6 rests on.

Review

Chapter Summary

Internal flux

\(L_{\text{int}} = \tfrac12\times10^{-7}\) H/m, independent of radius, because a flux tube at \(x\) links only \(x^2/r^2\) of the current.

External flux

\(L_{12} = 2\times10^{-7}\ln(D_2/D_1)\) — the one integral every other formula is built from.

The radius \(r'\)

\(r' = e^{-1/4}r = 0.7788r\) absorbs the internal term, so it never appears again.

One conductor in a group

\(\lambda_1 = 2\times10^{-7}\sum_k I_k\ln(1/D_{1k})\), valid whenever \(\sum I_k = 0\); the remote point cancels.

The master formula

\(L = 2\times10^{-7}\ln(D_m/D_s)\) — mutual GMD over self GMD, for every configuration in this chapter.

Equilateral spacing

\(L = 2\times10^{-7}\ln(D/D_s)\) per phase, balanced automatically, no transposition needed.

Transposition

\(D_{eq} = \sqrt[3]{D_{12}D_{23}D_{31}}\) makes an unsymmetrical line behave as an equilateral one of that side.

Double circuits

Treat each phase's pair as one composite conductor: \(D_S^A = \sqrt{D_sD_{aa'}}\), and reverse the second circuit's sequence.

The number to remember

About \(0.4\;\Omega\)/km at 50 Hz for any single-circuit overhead line; only bundling and paralleling move it much.

Practice

Practice Problems

Take \(\mu_r = 1\) and 50 Hz throughout, and assume full transposition unless told otherwise. Where a conductor is described by its physical radius, remember to convert to \(r'\).

  1. A single-phase line has two solid conductors of radius 0.8 cm spaced 1.5 m apart. Find the inductance and reactance per kilometre of the loop, and the percentage by which the answer would change if the internal flux were ignored.
  2. Show from the derivation of Section 6-2 that the internal inductance of a hollow conductor with inner radius \(r_1\) and outer radius \(r_2\) is less than \(\tfrac12\times10^{-7}\) H/m, and explain physically why a tubular conductor is used in some extra-high-voltage substations.
  3. A three-phase line has conductors of GMR 0.0095 m at the corners of a triangle with sides 4 m, 5 m and 6 m. Find \(D_{eq}\), the inductance per phase per kilometre, and the reactance of a 220 km line.
  4. The same conductors are arranged flat with 5 m between adjacent conductors. Compare \(D_{eq}\) and the reactance with the previous answer, and state which arrangement gives the lower reactance and by what percentage.
  5. A single-phase line has one side made of two conductors of radius 1 cm separated by 4 m, and the other side made of a single conductor of radius 1 cm placed 10 m from the midpoint of the first pair, on the perpendicular bisector. Find \(D_m\), the self GMD of each side, and the total inductance per kilometre.
  6. A three-phase line is not transposed: conductors of GMR 0.01 m sit flat with 4 m adjacent spacing. Using the group formula of Section 6-5, write the flux linkage of each phase for balanced currents \(I_a = I\angle0^\circ\), \(I_b = I\angle{-120}^\circ\), \(I_c = I\angle120^\circ\), and show that the three per-phase inductances are unequal. Identify which phase has the largest.
  7. For a hexagonal double circuit of circumradius \(R\) and conductor GMR \(D_s\), show that the per-phase inductance is always less than half that of a single circuit of the same \(D_{eq}\), for every \(R\) and every \(D_s\). Reduce the comparison to a single inequality between \(3^{1/4}R\) and \(2R\), and say in one sentence what physical fact that inequality expresses.
  8. A 400 kV line uses a twin bundle of Zebra conductors (\(D_s = 0.01151\) m) with 0.45 m between sub-conductors, arranged flat with 11 m between phases. Treating each bundle as a two-filament composite conductor, find the bundle's geometric mean radius, the line's \(D_{eq}\), and the reactance per kilometre. Repeat with a single Zebra conductor per phase at the same spacing, and quantify the percentage saving bundling has bought.
Tip: every problem in this chapter is answered by deciding what goes in the numerator and what goes in the denominator of one logarithm. Ask two questions in order: which distances separate the current from its return, and which distances describe the metal carrying that current? The first set gives \(D_m\) or \(D_{eq}\), the second gives \(D_s\), and no further physics is needed. When a conductor is composite, the only change is that both quantities become geometric means over more distances — never a new formula.