Part 3 · Chapter 14

Ferranti Effect, Surge Impedance Loading and Tuned Lines

A long line has a reactive power of its own, and everything distinctive about its behaviour — the voltage that rises when nothing is connected, the one loading at which the profile goes perfectly flat, the mythical length at which the drop vanishes entirely — is a statement about whether that reactive power is in balance.

Electric Power Systems Prof. Mithun Mondal Reading time ≈ 50 min
i What you'll learn
  • Why an open-circuited line has \(|V_r| > |V_s|\), and why the exact rise is \(1/|\cosh\gamma l|\), or \(\sec\beta l\) on a lossless line.
  • How the same rise appears as an incident wave growing and a reflected wave shrinking, and how to draw the phasor construction.
  • Why the surge impedance \(Z_s=\sqrt{L/C}\) is the impedance at which the line's own reactive generation and absorption cancel exactly.
  • Why loading at SIL gives a flat voltage profile, unity power factor everywhere, and no reflected wave.
  • How SIL and \(\beta l\) together give the loadability curve \(P/\mathrm{SIL} = \sin\delta/\sin\beta l\), and where the thermal limit hands over to the angle limit.
  • Why a tuned line needs \(\beta l = n\pi\), why that means 3000 km at 50 Hz, and what series and shunt compensation achieve instead.
Section 14-1

The Line With Nothing on the End

In 1890 the Deptford station of the London Electric Supply Corporation was sending power into the city over a 10 kV cable, and Sebastian Ziani de Ferranti found the voltage at the far end of a lightly loaded circuit standing above the voltage at the generator. That is not what a circuit made of resistance and inductance can do. Every intuition built on Ohm's law says a load pulls the voltage down, and the further away it is, the further down.

The resolution is that a transmission line is not only resistance and inductance. Chapter 7 gave every metre of it a capacitance to earth, and Chapter 12 spread that capacitance uniformly along the length rather than parking it in a lump. The current that flows into that distributed capacitance does not vanish when the load is switched off — it is drawn by the line itself. And because it is a capacitive current, it leads the voltage by very nearly \(90^\circ\), so when it passes through the line's series inductive reactance it produces a drop that is very nearly \(180^\circ\) out of phase with the voltage. A negative drop is a rise.

Chapter 13 already met the result in a different guise. Regulation was written \(\big(|V_s|/|A| - |V_r|\big)/|V_r|\), with the no-load voltage \(|V_s|/|A|\); and \(A = \cosh\gamma l\), whose magnitude is less than one for every real line. Every line therefore has a no-load voltage above its sending-end voltage. This chapter asks how large, why, and what to do about it — and then follows the same reactive-power argument to its two other consequences: the loading at which the effect exactly disappears, and the length at which it would disappear on its own.

The organising question. A line's series inductance absorbs reactive power at a rate \(I^{2}\omega L\) per unit length; its shunt capacitance generates reactive power at a rate \(V^{2}\omega C\). Whether the voltage rises or falls along the line is decided entirely by which of the two is larger. Light load: capacitance wins, voltage rises, and that is Ferranti. Heavy load: inductance wins, voltage falls, and that is ordinary regulation. Exactly balanced: nothing happens at all, and that is surge impedance loading.
Section 14-2

The Ferranti Effect, Exactly

Open the far end of the line, so \(\mathbf{I}_r = 0\), and read the first row of the two-port relation of Chapter 12:

The open-circuited line
\[ \mathbf{V}_s = A\,\mathbf{V}_r = \mathbf{V}_r\cosh\gamma l \quad\Longrightarrow\quad \frac{|V_{r,\text{NL}}|}{|V_s|} = \frac{1}{|\cosh\gamma l|} \]

That is the whole effect, stated exactly and with no approximation whatever. To see why the ratio exceeds unity, drop the resistance — legitimate on an EHV line, where Chapter 8's bundling has already made \(r\) small — so that \(\gamma = j\beta\) with \(\beta = \omega\sqrt{LC}\). The hyperbolic cosine of an imaginary argument is a circular cosine:

🔑
The Ferranti rise on a lossless line
\[ \frac{|V_{r,\text{NL}}|}{|V_s|} = \frac{1}{\cos\beta l} = \sec\beta l \;>\; 1 \qquad\text{for } 0 < \beta l < \tfrac{\pi}{2} \]

The rise depends on nothing but the electrical length \(\beta l\) — not on the voltage class, not on the conductor size, and not on the resistance except as a small second-order correction. Since \(\beta \simeq \omega/c\), electrical length is very nearly proportional to physical length, and the rise grows with it without limit: at \(\beta l = 90^\circ\), a quarter wavelength, \(\sec\beta l\) is infinite.

Expanding the secant for a moderate line recovers the estimate used in Chapter 11, where the shunt admittance was still a lump:

The lumped estimate, and where it comes from
\[ \sec\beta l = 1 + \frac{(\beta l)^{2}}{2} + \frac{5(\beta l)^{4}}{24}+\cdots \quad\Longrightarrow\quad \text{rise} \simeq \frac{(\beta l)^{2}}{2} = \frac{\omega^{2}LC\,l^{2}}{2} \]

The same result falls out of the nominal-π circuit directly. With \(\mathbf{I}_r=0\), that circuit gives \(\mathbf{V}_s = (1+\mathbf{YZ}/2)\mathbf{V}_r\); putting \(r=0\) so that \(\mathbf{Z}=j\omega Ll\) and \(\mathbf{Y}=j\omega Cl\),

Ferranti from the nominal-π circuit
\[ \mathbf{V}_s = \left(1 + \frac{(j\omega Cl)(j\omega Ll)}{2}\right)\mathbf{V}_r = \left(1 - \frac{\omega^{2}LC\,l^{2}}{2}\right)\mathbf{V}_r \;\Longrightarrow\; V_r = \frac{V_s}{1-(\beta l)^{2}/2} \]

Three routes, one answer. The nominal circuit is the two-term expansion, the secant is the exact lossless result, and \(1/|\cosh\gamma l|\) is exact for a real line. How much the routes differ is a fair measure of when a lumped model may be trusted, and the table says: not far.

Length (400 kV line, \(\lambda = 5854\) km)\(\beta l\)Exact \(\sec\beta l - 1\)Estimate \((\beta l)^{2}/2\)
100 km6.15°0.58%0.58%
200 km12.30°2.35%2.30%
300 km18.45°5.42%5.18%
400 km24.60°9.98%9.22%
600 km36.90°25.05%20.74%
800 km49.20°53.03%36.86%
1463 km (\(\lambda/4\))90°123%

Up to 200 km the estimate is good to a twentieth of a percentage point. At 400 km it is three-quarters of a point low, which is already enough to matter when an insulation margin is being checked. Beyond 600 km it collapses entirely, because the quartic term it discarded has become comparable with the quadratic one it kept.

The engineering consequence is severe and immediate. A 400 km, 400 kV line energised from one end with its far end open settles at 440 kV — a 40 kV overvoltage on equipment specified for a maximum of 420 kV. No 400 kV line is ever switched in without shunt reactors already connected, and the switching sequence at commissioning is written around exactly this number.

Section 14-3

Two Travelling Waves, and the Phasor Construction

The formula \(\sec\beta l\) is correct but not yet an explanation. Chapter 12 gave the physical picture: the voltage anywhere on a line is the sum of an incident wave travelling toward the load and a reflected wave travelling back from it,

The two waves, from Chapter 12
\[ \mathbf{V}(x) = \underbrace{\frac{\mathbf{V}_r+\mathbf{I}_rZ_c}{2}\,e^{\gamma x}}_{\text{incident}} \;+\; \underbrace{\frac{\mathbf{V}_r-\mathbf{I}_rZ_c}{2}\,e^{-\gamma x}}_{\text{reflected}}, \qquad x \text{ measured from the receiving end} \]

Set \(\mathbf{I}_r = 0\). Both coefficients collapse to \(\mathbf{V}_r/2\): at the open end the reflected wave equals the incident wave exactly, which is what "total reflection from an open circuit" means. Writing \(\gamma = \alpha+j\beta\),

The open-circuited line as two waves
\[ \mathbf{V}(x) = \frac{\mathbf{V}_r}{2}e^{\alpha x}e^{\,j\beta x} + \frac{\mathbf{V}_r}{2}e^{-\alpha x}e^{-j\beta x} \]

Follow the two terms as \(x\) grows from the open end toward the source. The incident term grows in magnitude as \(e^{\alpha x}\) and rotates forward through \(+\beta x\). The reflected term shrinks as \(e^{-\alpha x}\) and rotates backward through \(-\beta x\). At \(x=0\) they are two equal, co-linear phasors that add to \(\mathbf{V}_r\). At any \(x>0\) they have separated by an angle \(2\beta x\), and two phasors of nearly equal length that have opened out like scissors have a resultant shorter than their arithmetic sum. The sending-end voltage is therefore smaller than \(V_r\), which is the Ferranti effect drawn rather than calculated.

O Vᵣ (no load) Vᵣ/2 incident Vᵣ/2 reflected at x = 0 the two halves are collinear OB = (Vᵣ/2)e^{αl} B OC = (Vᵣ/2)e^{−αl} C OF = Vₛ F βl −βl |OF| = |Vᵣ||cosh γl| = 0.909 |Vᵣ| βl = 24.6° (400 km) so |Vᵣ| = 1.100 |Vₛ|
OB grows and turns forward, OC shrinks and turns back — their sum OF falls short of Vᵣ

The construction also shows why attenuation is not the cause. If \(\alpha\) were zero, the two halves would keep their length exactly and the resultant would be \(V_r\cos\beta l\) — still less than \(V_r\), and by more than the lossy case. Attenuation slightly reduces the Ferranti rise, because it makes the incident half longer than the reflected half and so brings the parallelogram back toward the axis. The rise is a phase phenomenon, not an amplitude one.

Why the effect grows with length and not with voltage. The scissors open at a rate set by \(\beta\), which is \(\omega\sqrt{LC}\) — geometry and frequency only. Two lines of the same length at 132 kV and 400 kV have nearly the same \(\beta\) and therefore nearly the same percentage rise. What differs is the consequence: 2.4% on a 132 kV line is 3 kV, and nobody notices; 10% on a 400 kV line is 40 kV, and the insulation coordination study of Chapter 37 is rewritten around it.
Section 14-4

Charging Current and the Reactive Balance

The current that produces all this deserves its own accounting. With the far end open, the second row of the two-port gives \(\mathbf{I}_s = C\,\mathbf{V}_{r,\text{NL}}\), and since \(C=\sinh\gamma l/Z_c\), which for a lossless line is \(j\sin\beta l/Z_s\), the sending-end current is purely capacitive. For a short enough line the whole calculation collapses to something one can do in the head: the line looks like a capacitor of total susceptance \(B = \omega C l\), and

Charging current and charging reactive power
\[ I_{\text{ch}} = \frac{V_{LL}}{\sqrt3}\,\omega C l \quad\text{per phase}, \qquad Q_{\text{ch}} = 3\left(\frac{V_{LL}}{\sqrt3}\right)^{2}\omega Cl = V_{LL}^{2}\,\omega Cl \]

For the 400 km, 400 kV line of Chapter 12, with \(b = \omega C = 3.6\times10^{-6}\) S/km, that is \(Q_{\text{ch}} = (400\times10^{3})^{2}\times1.44\times10^{-3} = 230\) MVAr — nearly half the line's own natural loading, produced by the line whether anyone wants it or not. That reactive power has to go somewhere. At no load it flows back into the source, which must be able to absorb it; at light load the generators are pushed toward the underexcited region of their capability curve, where Chapter 26 will show their stability margin is smallest.

The remedy is a shunt reactor, and its size follows from a short calculation that is worth doing properly rather than guessing. Connect a reactor of susceptance \(B_L\) across the open receiving end, so \(\mathbf{I}_r = -jB_L\mathbf{V}_r\), and demand that the receiving voltage come back to the sending value. On a lossless line:

Sizing the shunt reactor
\[ \mathbf{V}_s = \mathbf{V}_r\cos\beta l + jZ_s\sin\beta l\;(-jB_L\mathbf{V}_r) = \mathbf{V}_r\big(\cos\beta l + Z_sB_L\sin\beta l\big) \]
\[ |V_r|=|V_s| \;\Longrightarrow\; \cos\beta l + Z_sB_L\sin\beta l = 1 \;\Longrightarrow\; B_L = \frac{1-\cos\beta l}{Z_s\sin\beta l} = \frac{1}{Z_s}\tan\frac{\beta l}{2} \]
🔑
A reactor that cancels the Ferranti rise is half the line's charging
\[ \frac{B_L}{B_{\text{line}}} = \frac{\tan(\beta l/2)/Z_s}{\beta l/Z_s} = \frac{\tan(\beta l/2)}{\beta l} \;\xrightarrow[\;\beta l \to 0\;]{}\; \frac12 \]

using \(B_{\text{line}} = \omega Cl = \beta l/Z_s\). The ratio is 50.2% for a 200 km line and 50.8% for a 400 km one, creeping upward with length. Reactive compensation of roughly 50% to 80% of line charging is therefore what one finds on real EHV circuits — the excess above 50% being there to hold the voltage down at light load as well as at no load.

Two practical points follow. A reactor sized for no load makes the full-load regulation slightly worse, because at full load the line needs all the reactive help it can get; EHV reactors are therefore switchable, and are taken out as the load rises. And a reactor connected permanently at the line end — a bus reactor — must be disconnected before the line is de-energised on that side, whereas a line reactor connected inside the circuit breaker follows the line automatically. Chapter 34 develops the switching philosophy; here it is enough to know that the size comes from \(\tan(\beta l/2)/Z_s\).

Section 14-5

Surge Impedance and Natural Loading

Sections 14-1 to 14-4 have been about the case where the line's capacitance dominates. Turn the question round: is there a load at which the two reactive effects cancel, so that the line neither generates nor absorbs?

Write the balance directly. Per unit length, the shunt capacitance produces \(V^{2}\omega C\) and the series inductance consumes \(I^{2}\omega L\). Setting them equal:

The reactive balance
\[ I^{2}\omega L = V^{2}\omega C \quad\Longrightarrow\quad \frac{V^{2}}{I^{2}} = \frac{L}{C} \quad\Longrightarrow\quad \frac{V}{I} = \sqrt{\frac{L}{C}} \equiv Z_s \]

The ratio of voltage to current at which the balance holds is exactly the surge impedance that Chapter 12 obtained by an entirely different route — solving the wave equation and taking the ratio of the two solution constants. That the reactive-balance argument and the wave argument give the same number is not a coincidence: both are statements that a line terminated in \(Z_s\) is indistinguishable from an infinitely long line, and an infinite line has nowhere to store a reactive imbalance.

🔑
Surge impedance and surge impedance loading
\[ Z_s = \sqrt{\frac{L}{C}}\ \ (\text{pure resistance}), \qquad \mathrm{SIL} = \frac{V_{LL}^{2}}{Z_s}\ \ \text{three-phase watts} \]

Derivation of the second: a line at \(Z_s\) carries \(|I_L| = |V_{LL}|/(\sqrt3 Z_s)\) per phase at unity power factor, so \(P = \sqrt3|V_{LL}||I_L| = |V_{LL}|^{2}/Z_s\). Because \(Z_s\) is real, the power factor along the line is unity everywhere.

Two things about \(Z_s\) deserve emphasis. First, it is resistive, even though it is built entirely from two reactive elements. That is what makes it a natural terminating load: a resistor of \(Z_s\) ohms absorbs the incident wave completely and reflects nothing, which is why Chapter 12 called such a line "infinite" and why surge impedance is the impedance that matters for the lightning and switching surges of Chapter 38.

Second, it is remarkably insensitive to everything. Both \(L\) and \(C\) depend logarithmically on the ratio \(D/r\) of Chapters 6 and 7 — \(L\) proportional to \(\ln(D/r')\) and \(C\) inversely proportional to \(\ln(D/r)\) — so their ratio depends on the square of that logarithm and moves very little as the geometry changes. Every overhead line, at every voltage, ends up with a surge impedance between about 250 and 400 Ω. Bundling reduces it, because it raises \(C\) and lowers \(L\) together, and that is the reason a bundled 400 kV line has a natural loading four times that of a single-conductor 220 kV line rather than the \((400/220)^{2}=3.3\) that voltage alone would give.

Line\(L\) (mH/km)\(C\) (nF/km)\(Z_s\) (Ω)SIL (MW)\(v = 1/\sqrt{LC}\)
132 kV, single ACSR1.3009.0038045.80.975 c
220 kV, single ACSR1.2739.55365132.60.956 c
400 kV, twin bundle1.01911.46298536.70.976 c
765 kV, quad bundle0.86013.5025223190.978 c
Underground cable (Ch 9)0.40250400.33 c

The cable row is the exception that proves the rule, and it is the reason a.c. cables cannot be run over long distances. Its capacitance is thirty times that of an overhead line, because the conductor sits millimetres from an earthed sheath rather than metres from the ground. Its surge impedance is a tenth as large, its charging current per kilometre is enormous, and beyond a few tens of kilometres the charging current alone reaches the conductor's thermal rating with no room left for load. Long submarine links are therefore d.c., which is where Chapter 38 begins.

Section 14-6

The Flat Profile at SIL — and Off It

Chapter 12 substituted \(\mathbf{I}_r = \mathbf{V}_r/Z_s\) into the lossless solution and obtained \(\mathbf{V}(x) = \mathbf{V}_re^{\,j\beta x}\) and \(\mathbf{I}(x) = \mathbf{I}_re^{\,j\beta x}\). Both magnitudes are constant along the entire line; only the phase advances. Everything else follows from those two lines of algebra.

🔑
A lossless line loaded at SIL
\(|V|\) and \(|I|\) are the same at every point; the power factor is unity at every point; no reflected wave exists; the line exchanges no reactive power with either end.

The angle between the two ends is \(\delta = \beta l\) exactly — the line is a pure phase-shifter carrying real power and nothing else.

A caution about vocabulary is needed here, because two different quantities both get called "regulation". At SIL there is no voltage drop: \(|V_s| = |V_r|\), and the profile between them is flat. But the regulation as Chapter 13 defined it — the rise when the load is thrown off with \(|V_s|\) held — is not zero at SIL. Throwing off the load returns the line to the open-circuit condition of Section 14-2, so

Regulation of a lossless line at SIL
\[ \%\text{Reg}\big|_{\mathrm{SIL}} = \frac{|V_s|/|A| - |V_r|}{|V_r|} = \frac{1}{\cos\beta l} - 1 = \sec\beta l - 1 \]

which for the 400 km line is 9.98% — precisely the Ferranti rise. A flat profile at the operating point and a large excursion when the load disappears are entirely compatible, and confusing the two is a reliable way to lose marks.

Away from SIL the profile tilts, and the direction of the tilt is the reactive balance again. Below SIL the capacitance wins and the voltage rises toward the far end; above SIL the inductance wins and it falls. The figure shows all four cases on the same 400 km line, with the receiving end held at 400 kV.

distance from sending end (km) |V| line-to-line (kV) 400 360 440 0 200 400 no load (364 kV at source) 0.5 SIL 1.0 SIL — flat 1.5 SIL (441 kV at source) Vᵣ = 400
Voltage along a 400 km line with Vᵣ fixed — the profile is flat only at surge impedance loading

Read the sending-end values off the left edge: 364 kV at no load, 373 kV at half SIL, 400 kV at SIL, 441 kV at one and a half SIL. The same physical line requires a source voltage spanning 77 kV, purely because of what is hanging on its far end. Managing that span is the daily work of voltage control, and the SIL is the point about which the whole problem is symmetric.

Section 14-7

Loadability: SIL as the Yardstick

Because SIL is a natural unit, line loading is quoted in multiples of it throughout the industry, and the practice is not merely convenient — the loading limit itself turns out to have a clean expression in those units. Take the lossless line, whose \(B = jZ_s\sin\beta l\) has magnitude \(Z_s\sin\beta l\) and angle \(90^\circ\), and put it into the power-transfer formula of Chapter 11:

Power transfer on a lossless line, in SIL units
\[ P = \frac{|V_s||V_r|}{|B|}\sin\delta = \frac{|V_s||V_r|\sin\delta}{Z_s\sin\beta l} \quad\xrightarrow[\;|V_s|=|V_r|=V_{LL}\;]{}\quad \frac{P}{\mathrm{SIL}} = \frac{\sin\delta}{\sin\beta l} \]
🔑
The loadability relation
\[ \frac{P}{\mathrm{SIL}} = \frac{\sin\delta}{\sin\beta l} \]

Everything about the length has been absorbed into \(\sin\beta l\); everything about the voltage class and the conductor into SIL. Two lines of the same electrical length carry the same multiple of their own SIL at the same load angle, whatever their voltage.

A practical operating limit needs an angle limit, since \(\delta\) cannot be pushed to \(90^\circ\) without losing all stability margin. Chapter 28 will justify \(\delta \le 30^\circ\) for a line that must survive a fault; adopting that here gives a loadability curve.

Length\(\beta l\)\(P/\mathrm{SIL}\) at \(\delta=30^\circ\)Limited by
100 km6.15°4.67Conductor temperature
200 km12.30°2.35Conductor temperature
300 km18.45°1.58Crossover (≈ 294 km)
400 km24.60°1.20Angle
600 km36.90°0.83Angle
800 km49.20°0.66Angle
1000 km61.50°0.57Angle

This is the St Clair curve of line loadability, obtained here from three lines of algebra rather than from the empirical plots of the 1950s. A twin-bundle 400 kV line can carry about 1.25 kA per phase thermally, which is \(\sqrt3\times400\times1.25 = 866\) MW, or 1.61 SIL. Comparing that with the table: the two limits are equal where \(\sin\beta l = 0.5/1.61 = 0.311\), that is at \(\beta l = 18.1^\circ\) or 294 km. Below that length the conductor temperature binds; above it the angle does. That crossover is the answer to the question Chapter 10 first raised — when does a line stop being limited by how hot the conductor gets? — and for a 400 kV circuit the answer is: at about 290 km, sooner if the permitted angle is smaller.

Three regimes, one curve. Short lines are thermally limited and their loadability falls as \(1/l\) once the drop starts to bite. Medium lines are limited by the acceptable voltage drop. Long lines are limited by the angle, and their loadability tends to \(\sin\delta/\sin\beta l\), which for a half-wavelength line is nominally infinite — a fact that Section 14-8 turns into the idea of the tuned line before explaining why nobody builds one.
Section 14-8

Tuned Power Lines

Take the lossless ABCD matrix and ask what would make the line perfect — no voltage drop, no rise, no regulation at all, for any load whatever. With \(\gamma = j\beta\), Chapter 12's constants are

The lossless line, once more
\[ \begin{bmatrix}\mathbf{V}_s\\ \mathbf{I}_s\end{bmatrix} = \begin{bmatrix} \cos\beta l & jZ_s\sin\beta l\\ \dfrac{j\sin\beta l}{Z_s} & \cos\beta l \end{bmatrix} \begin{bmatrix}\mathbf{V}_r\\ \mathbf{I}_r\end{bmatrix} \]

The off-diagonal terms are what couple the voltage to the current and therefore what create the drop. Kill them: set \(\sin\beta l = 0\), which happens whenever \(\beta l = n\pi\). Then \(\cos\beta l = \pm1\) and the matrix becomes \(\pm\) the identity.

🔑
The tuned line
\[ \beta l = n\pi \;\Longrightarrow\; \mathbf{V}_s = \pm\mathbf{V}_r, \quad \mathbf{I}_s = \pm\mathbf{I}_r \;\Longrightarrow\; |V_s| = |V_r|,\; |I_s| = |I_r| \]

at every load and every power factor. There is no voltage drop, no Ferranti rise, and the regulation is exactly zero. The sign alternates: an odd \(n\) reverses the phase by \(180^\circ\), an even \(n\) reproduces it.

How long is such a line? The wavelength of Chapter 12 is \(\lambda = 2\pi/\beta = v/f\), where \(v = 1/\sqrt{LC}\) is between \(0.95c\) and \(0.98c\) for any overhead line. So

Tuned lengths at power frequency
\[ \beta l = n\pi \;\Longleftrightarrow\; l = \frac{n\lambda}{2}, \qquad \lambda = \frac{v}{f} \simeq \frac{2.93\times10^{5}\ \text{km/s}}{50\ \text{Hz}} \simeq 5900\ \text{km} \]
\[ l = 2950\ \text{km},\; 5900\ \text{km},\; 8850\ \text{km},\dots \qquad(\text{at }60\ \text{Hz}: \;2440\ \text{km},\;4880\ \text{km},\dots) \]

Three thousand kilometres. No transmission line of that length has ever been built as a single a.c. circuit, and there is no economic reason to build one: the loss over 3000 km at any useful loading would be a quarter of the power sent, and the right-of-way cost alone would pay for an HVDC link several times over. The tuned line is a limiting case, not a design.

Could a shorter line be made tuned? Since \(\beta = \omega\sqrt{LC}\), tuning a 400 km line at 50 Hz needs \(\beta = \pi/400 = 7.854\times10^{-3}\) rad/km against the natural \(1.073\times10^{-3}\) — a factor of 7.3, which means the product \(LC\) must be raised 53-fold by adding series inductance or shunt capacitance along the route. That is absurd for a power line, and it also destroys the thing one wanted: raising \(LC\) at fixed \(L/C\) leaves \(Z_s\) alone but multiplies the loss and the cost. The technique is used at high frequency in telephony, where the required \(\lambda/2\) is metres rather than megametres, and Heaviside's loading coils are exactly this idea applied to a telephone cable. At power frequency it is a curiosity.

Two special lengths are worth carrying away even so, because they occur in problems and in surge analysis. At \(\beta l = \pi\), a half wavelength, \(A=D=-1\) and \(B=C=0\): the line is a perfect repeater with a phase reversal. At \(\beta l = \pi/2\), a quarter wavelength, \(A=D=0\), \(B = jZ_s\), \(C = j/Z_s\), and the line inverts impedances:

The quarter-wave line as an impedance inverter
\[ Z_{\text{in}} = \frac{\mathbf{V}_s}{\mathbf{I}_s} = \frac{jZ_s\mathbf{I}_r}{j\mathbf{V}_r/Z_s} = \frac{Z_s^{2}}{Z_R} \]

An open circuit at the far end appears as a short at the near end and vice versa, which is why \(\sec\beta l\) blew up at \(90^\circ\) in Section 14-2: a quarter-wave line on open circuit is a series resonance seen from the source. At 50 Hz that length is about 1460 km, comfortably beyond anything built, but a switching surge contains frequencies of several hundred hertz, and at 500 Hz the quarter wavelength is only 146 km. Resonant overvoltages on a line of ordinary length are therefore entirely possible during switching — which is why Chapter 37's insulation coordination study looks at frequencies far above 50 Hz.

Section 14-9

Making a Real Line Behave

Tuning is out of reach, but its two ingredients — the electrical length \(\beta l = \omega l\sqrt{LC}\) and the surge impedance \(Z_s = \sqrt{L/C}\) — can each be moved, and moving them is what compensation does.

A series capacitor cancels part of the line's inductive reactance. With a compensation degree \(k = X_C/X_L\), the effective inductance becomes \(L(1-k)\) while \(C\) is untouched, so

Effect of series compensation
\[ \beta l \to \beta l\sqrt{1-k}, \qquad Z_s \to Z_s\sqrt{1-k}, \qquad \mathrm{SIL} \to \frac{\mathrm{SIL}}{\sqrt{1-k}} \]

Both changes help. The line becomes electrically shorter, so \(\sin\beta l\) falls and loadability rises; and the surge impedance falls, so the natural loading itself rises. The two multiply: at 40% compensation the 400 km line's \(\beta l\) falls from 24.6° to 19.1°, its \(Z_s\) from 298 to 231 Ω, its SIL from 537 to 693 MW, and its transfer at \(\delta=30^\circ\) from 645 MW to 1061 MW — a 65% increase for a device that sits in one substation. The Ferranti rise falls too, from 9.98% to 5.80%. This is the most cost-effective single measure available for a long line, and its price is the subsynchronous resonance risk and the protection complexity that Chapter 38 examines.

A shunt reactor cancels part of the line's capacitance. With a degree \(k_{sh}\) of the charging susceptance absorbed, the effective capacitance is \(C(1-k_{sh})\), so

Effect of shunt reactive compensation
\[ \beta l \to \beta l\sqrt{1-k_{sh}}, \qquad Z_s \to \frac{Z_s}{\sqrt{1-k_{sh}}}, \qquad \mathrm{SIL} \to \mathrm{SIL}\sqrt{1-k_{sh}} \]

Here the two effects pull against each other. The line is shortened electrically, which helps, but its surge impedance rises and its natural loading falls, which does not. Shunt reactors are therefore a light-load measure: they exist to hold the voltage down when the line is nearly empty, and they are switched out as soon as it fills. That is the opposite duty from a series capacitor, and a well-designed EHV corridor has both.

sending bus receiving bus series capacitor βl → βl√(1−k) Zₛ → Zₛ√(1−k) SIL rises switched shunt reactor ≈ 50–80% of charging shunt reactor holds no-load V down shunt capacitor (full load)
Series capacitor shortens the line electrically; shunt reactors tame it empty, shunt capacitors tame it full

Which brings Part 3 to a close. Chapter 10 modelled a line as a series impedance and got the voltage drop. Chapter 11 lumped its shunt admittance and met the charging current. Chapter 12 distributed that admittance and found waves, a characteristic impedance and a wavelength. Chapter 13 turned the resulting two-port into performance figures. This chapter has read the same two-port at its two extremes — nothing on the end, and the one load that makes the line invisible — and found the Ferranti effect and the surge impedance loading waiting there. Chapter 15 leaves the circuit model entirely and asks what happens when the electric field at the conductor surface becomes strong enough to ionise the air around it.

Section 14-10

Worked Examples

1 The Ferranti rise on the reference line, three ways

Problem. The 200 km, 220 kV, 50 Hz reference line has \(\gamma l = 0.042998+j0.223268\), \(A = 0.97613\angle0.559^\circ\) and \(C = 5.9521\times10^{-4}\angle90.184^\circ\) S. With the sending end held at 220 kV and the far end open, find the receiving-end voltage exactly, by the lossless secant formula, and by the lumped estimate. Find the charging current and the reactor needed to cancel the rise.

Solution. Exactly, the rise is governed by \(|A|\) alone:

Exact
\[ |V_{r,\text{NL}}| = \frac{220}{0.97613} = 225.38\ \text{kV}, \qquad \text{rise} = \frac{225.38-220}{220}\times100 = 2.446\% \]

By the lossless formula, with \(\beta l = 0.223268\) rad \(= 12.792^\circ\):

Lossless and lumped
\[ \sec\beta l - 1 = \frac{1}{\cos12.792^\circ}-1 = \frac{1}{0.975179}-1 = 2.545\% \]
\[ \frac{(\beta l)^{2}}{2} = \frac{0.223268^{2}}{2} = 0.024924 = 2.492\% \]

Three estimates within a tenth of a percentage point of each other, and the exact one is the smallest — attenuation reduces the rise, as Section 14-3 argued from the phasor construction. The charging current follows from the second row of the two-port with \(\mathbf{I}_r=0\):

Charging current and reactive power
\[ |I_s| = |C|\,|V_{r,\text{NL}}| = 5.9521\times10^{-4}\times\frac{225\,380}{\sqrt3} = 5.9521\times10^{-4}\times130\,124 = 77.45\ \text{A} \]
\[ Q_s = -3|V_s||I_s|\sin\phi_s = -29.51\ \text{MVAr} \quad\text{(the line returns 29.5 MVAr to the source)} \]

Compare with the rule-of-thumb charging \(V_{LL}^{2}B = (220\times10^{3})^{2}\times6\times10^{-4} = 29.04\) MVAr. The exact figure is 1.6% larger because the line is sitting at 225 kV, not 220 kV, over most of its length.

For the reactor, use \(B_L = \tan(\beta l/2)/Z_s\) with \(Z_s = 365\ \Omega\):

Reactor
\[ L = \frac{0.40}{314.159} = 1.2732\ \text{mH/km},\quad C = \frac{3.0\times10^{-6}}{314.159} = 9.549\ \text{nF/km},\quad \beta = \omega\sqrt{LC} = 1.0955\times10^{-3}\ \text{rad/km} \]
\[ \beta l = 0.21910\ \text{rad} = 12.554^\circ, \qquad B_L = \frac{\tan 6.277^\circ}{365.1} = \frac{0.11000}{365.1} = 3.013\times10^{-4}\ \text{S} \]
\[ X_L = 3319\ \Omega, \qquad Q_L = \frac{V_{LL}^{2}}{X_L} = \frac{(220\times10^{3})^{2}}{3319} = 14.58\ \text{MVAr} \quad (50.2\% \text{ of the line's charging}) \]

Solving the exact lossy relation \(|V_s| = |V_r|\,\big|A + B/(jX_L)\big|\) numerically gives \(X_L = 3322\ \Omega\) and \(Q_L = 14.57\) MVAr, so the lossless rule is good to a fifth of a percent. A 15 MVAr reactor holds the open end at 220 kV. On a 220 kV line the rise it corrects is only 5 kV, and most utilities would not fit one; the same calculation on a 400 kV line, in Example 2, gives an answer nobody can ignore.

2 A 400 km, 400 kV line switched onto an open end

Problem. The 400 km line of Chapter 12 has \(z = 0.03+j0.32\ \Omega\)/km, \(y = j3.6\times10^{-6}\) S/km, \(A = 0.90927\angle0.528^\circ\), \(B = 124.65\angle84.811^\circ\ \Omega\), \(C = 1.39617\times10^{-3}\angle90.167^\circ\) S and \(Z_s = 298\ \Omega\). It is energised at 400 kV with the far end open. Find the receiving voltage, the charging current and reactive power, and the reactor that returns the far end to 400 kV. What does an 80 MVAr reactor achieve instead?

Solution. The rise:

Open-circuit voltage
\[ |V_{r,\text{NL}}| = \frac{400}{0.90927} = 439.91\ \text{kV} \;\Longrightarrow\; \text{rise } 9.98\% \]
\[ |I_s| = |C|\,\frac{439\,910}{\sqrt3} = 1.39617\times10^{-3}\times253\,983 = 354.6\ \text{A} \]
\[ Q_{\text{ch}} \simeq V_{LL}^{2}\,\omega Cl = (400\times10^{3})^{2}\times1.44\times10^{-3} = 230.4\ \text{MVAr at rated voltage} \]

A 40 kV overvoltage on a system whose highest permitted equipment voltage is 420 kV. The line cannot be energised in this state at all. Size the reactor from the tuned-reactor rule, with \(\beta l = 24.60^\circ\):

Reactor sizing
\[ B_L = \frac{\tan(12.30^\circ)}{298} = \frac{0.21801}{298} = 7.316\times10^{-4}\ \text{S} \;\Longrightarrow\; X_L = 1367\ \Omega \]
\[ Q_L = \frac{(400\times10^{3})^{2}}{1367} = 117.0\ \text{MVAr} \quad = 50.8\%\ \text{of the line charging} \]

Solving the exact lossy relation \(|V_s| = |V_r|\,|A + B/(jX_L)|\) numerically gives \(X_L = 1367.5\ \Omega\), confirming the lossless rule to four figures. A 117 MVAr reactor brings the open end back to exactly 400 kV.

With a standard 80 MVAr unit instead, \(X_L = (400\times10^{3})^{2}/80\times10^{6} = 2000\ \Omega\) and

80 MVAr reactor
\[ |V_{r,\text{NL}}| = \frac{400}{\big|A + B/(j2000)\big|} = 411.8\ \text{kV} \quad\text{— a residual rise of }2.95\% \]

Within the 420 kV limit with room to spare, at two-thirds the reactor cost. The full 117 MVAr would only be justified if the line also had to be held at 400 kV at light load, and in practice a 125 MVAr switchable reactor is the usual choice because it covers both duties with one unit.

3 The rise built from its two waves

Problem. For the 400 km line of Example 2 on open circuit, resolve the receiving-end voltage into its incident and reflected components, follow both to the sending end, and show that their sum reproduces \(A = \cosh\gamma l\).

Solution. With \(\mathbf{I}_r = 0\) both components are \(\mathbf{V}_r/2\) at the open end. Taking \(\mathbf{V}_r\) as reference and using \(\gamma l = 0.020103+j0.429795\), so \(\alpha l = 0.020103\) Np and \(\beta l = 0.429795\) rad \(=24.625^\circ\):

The two components at the sending end
\[ \text{incident } OB = \tfrac12 e^{\alpha l}\,V_r\angle+\beta l = 0.510153\,V_r\angle24.625^\circ \]
\[ \text{reflected } OC = \tfrac12 e^{-\alpha l}\,V_r\angle-\beta l = 0.490049\,V_r\angle-24.625^\circ \]

Add them by components. The real parts reinforce and the imaginary parts almost cancel:

The resultant
\[ \operatorname{Re} = (0.510153+0.490049)\cos24.625^\circ = 1.000202\times0.909051 = 0.909235 \]
\[ \operatorname{Im} = (0.510153-0.490049)\sin24.625^\circ = 0.020104\times0.416685 = 0.008377 \]
\[ \mathbf{V}_s = (0.909235+j0.008377)\mathbf{V}_r = 0.90927\angle0.528^\circ\;\mathbf{V}_r = A\,\mathbf{V}_r\;\checkmark \]

The construction makes two things visible that the formula hides. The real part of the sum is \((\text{sum of lengths})\times\cos\beta l\), so if there were no attenuation at all the answer would be exactly \(V_r\cos\beta l\) — the pure Ferranti factor. The tiny imaginary part is entirely due to the difference in the two lengths, and therefore entirely due to attenuation; it is what makes \(\angle A\) a fraction of a degree instead of zero. And since the sum of the two lengths, \(\cosh\alpha l = 1.00021\), exceeds unity only in the fourth decimal, attenuation makes almost no difference to the magnitude — confirming that the Ferranti effect is a matter of phase, not of loss.

4 Surge impedance and natural loading across the voltage classes

Problem. A 400 kV twin-bundle line has \(x = 0.32\ \Omega\)/km and \(b = 3.6\times10^{-6}\) S/km at 50 Hz. Find \(L\), \(C\), \(Z_s\), the SIL, the wave velocity and the wavelength. Then compare with a single-conductor 220 kV line having \(x = 0.40\ \Omega\)/km and \(b = 3.0\times10^{-6}\) S/km, and explain why the ratio of the two SILs is not \((400/220)^{2}\).

Solution. At \(\omega = 2\pi\times50 = 314.159\) rad/s:

400 kV line
\[ L = \frac{x}{\omega} = \frac{0.32}{314.159} = 1.0186\ \text{mH/km}, \qquad C = \frac{b}{\omega} = \frac{3.6\times10^{-6}}{314.159} = 11.459\ \text{nF/km} \]
\[ Z_s = \sqrt{\frac{1.0186\times10^{-3}}{11.459\times10^{-9}}} = \sqrt{88\,891} = 298.1\ \Omega, \qquad \mathrm{SIL} = \frac{(400)^{2}}{298.1} = 536.7\ \text{MW} \]
\[ v = \frac{1}{\sqrt{LC}} = 2.927\times10^{5}\ \text{km/s} = 0.976c, \qquad \lambda = \frac{v}{f} = 5854\ \text{km} \]
220 kV line
\[ L = \frac{0.40}{314.159} = 1.2732\ \text{mH/km}, \qquad C = \frac{3.0\times10^{-6}}{314.159} = 9.549\ \text{nF/km} \]
\[ Z_s = \sqrt{\frac{1.2732\times10^{-3}}{9.549\times10^{-9}}} = 365.1\ \Omega, \qquad \mathrm{SIL} = \frac{(220)^{2}}{365.1} = 132.6\ \text{MW} \]

The ratio of the SILs is \(536.7/132.6 = 4.05\), against \((400/220)^{2} = 3.31\) from the voltage alone. The extra factor of \(1.22\) is the ratio of surge impedances, \(365.1/298.1\), and it comes entirely from bundling: two subconductors spaced 450 mm apart have a larger equivalent radius, which raises \(C\) and lowers \(L\) simultaneously. Chapter 8's geometric mean radius argument, made there to reduce corona and reactance, is here worth an extra 22% of transmission capability at no additional voltage.

The two velocities, \(0.976c\) and \(0.956c\), differ by only 2%, which is the reason both lines have a wavelength near 5800 km and why the tuned length of Section 14-8 is the same order for every overhead line ever built.

5 The voltage profile, and where the thermal limit hands over

Problem. For the 400 km, 400 kV line, treated as lossless with \(Z_s = 298.14\ \Omega\) and \(\beta = 1.0733\times10^{-3}\) rad/km, find the sending-end voltage needed to hold the receiving end at 400 kV at no load, at 0.5, 1.0 and 1.5 times SIL, all at unity power factor. Then find the load angle and the loadability at \(\delta = 30^\circ\), and compare with the thermal rating of 1.25 kA per phase.

Solution. \(\beta l = 0.42933\) rad \(= 24.599^\circ\), so \(\cos\beta l = 0.90914\) and \(\sin\beta l = 0.41625\). With \(V_r = 400/\sqrt3 = 230.94\) kV per phase and \(\mathbf{I}_r = P/(\sqrt3\times400)\) at unity power factor, the lossless relation gives \(\mathbf{V}_s = V_r\cos\beta l + jZ_s I_r\sin\beta l\), whose magnitude is \(\sqrt{(V_r\cos\beta l)^{2}+(Z_sI_r\sin\beta l)^{2}}\):

Loading\(P\) (MW)\(I_r\) (A)\(V_{s(LL)}\) (kV)Profile
No load00363.7rises 10.0% to the load
0.5 SIL268.4387.4373.1rises 7.2%
1.0 SIL536.7774.8400.0flat
1.5 SIL805.11162.2441.2falls 9.3%

Check the SIL row by hand: \(I_r = 230\,940/298.14 = 774.6\) A, so \(V_r\cos\beta l = 209.94\) kV and \(Z_sI_r\sin\beta l = 298.14\times774.6\times0.41625 = 96.12\) kV per phase; the magnitude is \(\sqrt{209.94^{2}+96.12^{2}} = 230.9\) kV per phase, or 400.0 kV line to line. Flat, as promised.

Now the loadability. With both ends at 400 kV,

Loadability at a 30° angle
\[ \frac{P}{\mathrm{SIL}} = \frac{\sin\delta}{\sin\beta l} = \frac{\sin30^\circ}{0.41625} = 1.201 \;\Longrightarrow\; P = 1.201\times536.7 = 644.6\ \text{MW} \]
Thermal rating
\[ P_{\text{thermal}} = \sqrt3\times400\times1.25 = 866\ \text{MW} = 1.61\ \mathrm{SIL} \]

The angle limit bites first: 645 MW against a conductor capable of 866 MW. The line will be run at about 1.2 SIL and its conductors will never get hot. Repeating the calculation at 200 km gives \(P/\mathrm{SIL} = 2.35\), or 1260 MW, which now exceeds the thermal figure — so at 200 km the conductor is the constraint and at 400 km the angle is. The two swap over at 294 km, which is where the loadability table of Section 14-7 changes its right-hand column.

6 Tuning, and what compensation buys instead

Problem. For the same 400 kV line with \(L = 1.0186\) mH/km and \(C = 11.459\) nF/km: (a) find the length that would be tuned at 50 Hz; (b) find the frequency at which the existing 400 km would be tuned; (c) find the input impedance of a quarter-wave section terminated in 600 Ω; (d) find what 40% series compensation does to \(\beta l\), \(Z_s\), the SIL, the Ferranti rise and the transfer at \(\delta = 30^\circ\).

Solution. (a) Tuning needs \(\beta l = n\pi\), and \(\lambda = 5854\) km from Example 4:

Tuned lengths
\[ l = \frac{n\lambda}{2} = 2927\ \text{km},\; 5854\ \text{km},\; 8781\ \text{km},\dots \]

Nearly 3000 km for the shortest. At the line's own resistance of 0.03 Ω/km the \(I^{2}R\) loss over that distance at SIL would be \(3(774.8)^{2}(0.03)(2927) = 158\) MW out of 537 MW sent, or 29%. The tuned line delivers perfect voltage regulation and throws away a third of the power to do it.

(b) Solve \(\omega l\sqrt{LC} = \pi\) for \(\omega\) with \(l = 400\) km and \(\sqrt{LC} = 3.4165\times10^{-6}\) s/km:

The tuning frequency of a 400 km line
\[ \omega = \frac{\pi}{400\times3.4165\times10^{-6}} = 2299\ \text{rad/s} \;\Longrightarrow\; f = 366\ \text{Hz} \]

Which is precisely why the idea belongs to telephony and not to power: at carrier frequencies the required half-wavelength is short enough to build.

(c) A quarter-wave section is \(\lambda/4 = 1463\) km and inverts impedances about \(Z_s^{2}\):

Impedance inversion
\[ Z_{\text{in}} = \frac{Z_s^{2}}{Z_R} = \frac{298.14^{2}}{600} = \frac{88\,887}{600} = 148.1\ \Omega \]

A load heavier than \(Z_s\) looks lighter than \(Z_s\) from the far end, and vice versa; an open circuit looks like a short. That inversion is the reason \(\sec\beta l\) diverges at \(90^\circ\).

(d) With \(k = 0.4\), the factor is \(\sqrt{1-k} = \sqrt{0.6} = 0.7746\):

40% series compensation
\[ \beta l' = 24.599^\circ\times0.7746 = 19.054^\circ, \qquad Z_s' = 298.14\times0.7746 = 230.9\ \Omega \]
\[ \mathrm{SIL}' = \frac{400^{2}}{230.9} = 692.8\ \text{MW}, \qquad \text{Ferranti} = \sec19.054^\circ-1 = 5.80\% \]
\[ P\big|_{\delta=30^\circ} = \frac{400^{2}\times\sin30^\circ}{230.9\times\sin19.054^\circ} = \frac{80\,000}{230.9\times0.32649} = 1061\ \text{MW} \]

Transfer at a 30° angle rises from 645 MW to 1061 MW, an increase of 65%; the natural loading rises 29%; and the no-load overvoltage falls from 10.0% to 5.8%. One series capacitor bank, sitting in a single substation, has done more for this line than a second circuit would have done for two-thirds of the price of a second circuit. That is why every long EHV corridor built since the 1970s has one — and why Chapter 38 must then deal with the subsynchronous resonance it introduces.

Review

Chapter Summary

Ferranti, exactly

\(|V_{r,\text{NL}}|/|V_s| = 1/|\cosh\gamma l|\), which is \(\sec\beta l\) on a lossless line.

It is a phase effect

Incident and reflected halves open out by \(2\beta x\); attenuation slightly reduces the rise.

Charging

\(Q_{\text{ch}} = V_{LL}^{2}\omega Cl\) — 230 MVAr on a 400 km, 400 kV line, whether wanted or not.

The reactor rule

\(B_L = \tan(\beta l/2)/Z_s\), which is close to half the line's charging susceptance.

Surge impedance

\(Z_s=\sqrt{L/C}\) is where \(I^{2}\omega L = V^{2}\omega C\) — reactive generation equals absorption.

SIL

\(V_{LL}^{2}/Z_s\): flat profile, unity power factor everywhere, no reflected wave.

Loadability

\(P/\mathrm{SIL} = \sin\delta/\sin\beta l\) — thermal below ~250 km, angle-limited above it.

Tuned line

\(\beta l = n\pi\) gives \(|V_s|=|V_r|\) at any load, but needs 3000 km at 50 Hz.

Practice

Practice Problems

Take 50 Hz unless told otherwise, treat lines as lossless where the problem says so, and quote voltages line-to-line. Problems 5 to 8 are of GATE standard.

  1. A 300 km, 220 kV line has \(L = 1.25\) mH/km and \(C = 9.6\) nF/km. Treating it as lossless, find \(\beta\), \(\beta l\), \(Z_s\), the SIL, and the no-load receiving voltage when the sending end is held at 220 kV.
  2. For the line of Problem 1, find the shunt reactor rating that returns the open-circuit receiving voltage to 220 kV, and express it as a percentage of the line's charging reactive power. Verify the \(\tan(\beta l/2)\) rule against a direct calculation.
  3. Show that on a lossless line loaded at exactly SIL, the current magnitude is constant along the line and the reactive power exchanged with either terminal is zero. Then show that the load angle between the two ends is exactly \(\beta l\).
  4. A 500 kV line 500 km long has \(Z_s = 270\ \Omega\) and \(\lambda = 5900\) km. Find its SIL, the Ferranti rise on open circuit, and the power it can transfer with both ends at 500 kV and a load angle of 30°, in MW and in multiples of SIL.
  5. An overhead line has \(x = 0.35\ \Omega\)/km and \(b = 3.3\times10^{-6}\) S/km at 50 Hz. Determine \(Z_s\), the wave velocity as a fraction of the speed of light, and the wavelength. What length would be tuned at 50 Hz, and what at 60 Hz?
  6. A 400 km line has \(\beta l = 24^\circ\) and \(Z_s = 300\ \Omega\) at 400 kV. Thirty-five per cent series compensation is installed. Find the new \(\beta l\), \(Z_s\), SIL and Ferranti rise, and the percentage increase in the power transferable at a 30° load angle.
  7. A quarter-wave lossless line of surge impedance 400 Ω is terminated in (a) an open circuit, (b) a short circuit, (c) 400 Ω, (d) 1000 Ω. State the input impedance in each case and explain the pattern in terms of \(Z_{\text{in}} = Z_s^{2}/Z_R\).
  8. A 250 km, 400 kV line with \(Z_s = 300\ \Omega\) and \(\lambda = 5900\) km supplies 900 MW at unity power factor with the receiving end at 400 kV. Find the loading in multiples of SIL, the sending-end voltage on the lossless model, and the reactive power that must be supplied at the receiving bus to bring the sending end back to 400 kV.
Tip: almost every problem in this chapter is answered by first computing two numbers and nothing else — the electrical length \(\beta l\) and the surge impedance \(Z_s\). The Ferranti rise is \(\sec\beta l - 1\); the reactor is \(\tan(\beta l/2)/Z_s\); the natural loading is \(V^{2}/Z_s\); the loadability is \(\sin\delta/\sin\beta l\); the tuned length is where \(\beta l\) reaches \(\pi\). If an answer cannot be written in terms of those two, it is probably the wrong answer.