Line Performance: Regulation and Efficiency
A line is judged by two numbers — how far the receiving-end voltage moves when the load is thrown off, and what fraction of the power sent actually arrives — and both of them follow from the four ABCD constants that Chapters 10 to 12 spent their length constructing.
- Why voltage regulation is defined against the no-load receiving voltage \(|V_s|/|A|\), and why the short-line shortcut \(|V_s|-|V_r|\) is only a special case of it.
- How regulation varies with load power factor, and the exact condition \(\cos(\theta+\phi) = -I|Z|/2V_r\) for zero regulation at a leading power factor.
- Why the loss on a line with distributed shunt admittance is \(P_s-P_r\) and never \(3I_r^{2}R\) — and how far wrong the shortcut goes.
- The scaling law \(\text{loss}/P = PR/(V^{2}\cos^{2}\phi)\), which is the whole argument for high voltage and for power-factor correction in one line.
- The maximum-efficiency condition, and why a lightly loaded EHV line breaks it.
- How the receiving-end circle diagram turns regulation, power transfer and reactive support into one picture.
What "Performance" Actually Asks
Part 2 of this book computed the parameters of a line: resistance from the conductor, inductance from the geometry in Chapter 6, capacitance in Chapter 7, both modified by bundling in Chapter 8. Part 3 has been turning those parameters into a circuit. Chapter 10 kept only the series impedance and got a model good to 80 km. Chapter 11 lumped the shunt admittance at one or two points and reached 250 km. Chapter 12 distributed it properly, solved the wave equation, and produced constants that are exact at any length.
All three chapters ended with the same two-port relation, differing only in what was put into the four constants:
Everything a planner or an operator wants to know about a transmission line is a question about that matrix and the load hung on its right-hand terminals. There are three such questions, and they are not independent.
How much does the voltage move? Consumers' equipment is designed for a nominal voltage and tolerates perhaps \(\pm 5\%\) around it. If the receiving-end voltage sags when the load comes on and soars when it goes off, either the load suffers or a tap-changer and a capacitor bank must be bought to hide the problem. The measure of that movement is voltage regulation.
How much power is thrown away? Every ampere in the conductor heats it. That heat is bought fuel that never reaches a customer, and on a 400 kV interconnector carrying 600 MW for twenty years its cumulative value is comparable to the cost of the line itself. The measure is transmission efficiency.
How much can be sent at all? Chapter 10 showed that a short line is limited by conductor heating, Chapter 12 that a long one is limited by the angle \(\delta\) long before the conductor is warm. That is the loadability question, and Chapter 14 takes it up with the surge impedance as its yardstick.
This chapter answers the first two exactly, for any line, from the ABCD constants alone. The reference line of Chapters 11 and 12 — 200 km, 220 kV, 50 Hz, \(z = 0.16+j0.40\ \Omega\)/km, \(y = j3.0\times10^{-6}\) S/km, delivering 60 MW at 0.9 power factor lagging — runs through the whole discussion so that every new formula can be checked against a number already known.
Voltage Regulation and the No-Load Voltage
Regulation is defined by a thought experiment. Hold the sending-end voltage at whatever value delivers rated voltage to the load at full load. Now disconnect the load, leaving the sending-end voltage untouched. The receiving-end voltage will move. Regulation is that movement, expressed as a fraction of the full-load value.
with \(|V_s|\) held constant between the two conditions. The definition uses magnitudes only: the phase of the receiving-end voltage is nobody's concern at the load terminals.
To evaluate it we need the no-load receiving voltage. Set \(\mathbf{I}_r = 0\) in the two-port relation. The first row collapses immediately:
The constant \(A\) alone decides the no-load voltage. That is worth pausing over, because \(A\) is the one constant of the four that the short-line model of Chapter 10 discarded — there \(A=1\) exactly, and the no-load voltage is simply the sending-end voltage. Every departure of \(|A|\) from unity is a statement about the shunt capacitance, and Chapter 12 showed that \(A=\cosh\gamma l\), which for a real line has a magnitude less than one. A line therefore always ends up with a no-load voltage higher than its sending-end voltage. That is the Ferranti effect, and Chapter 14 is devoted to it.
where \(V_r\) and \(I_r\) are the full-load receiving-end quantities. For a short line \(A=1\) and this reduces to the familiar \(\big(|V_s|-|V_r|\big)/|V_r|\); for a medium or long line it does not, and using the short-line form on a long line quietly hides the Ferranti rise inside the answer.
Two conventions must be kept straight, because textbooks and examination papers use both. The definition above holds \(|V_s|\) fixed and asks what \(|V_r|\) does; this is the physical statement, since the sending end is normally a generator bus held at a set voltage. The alternative holds \(|V_r|\) fixed at rated value and computes the \(|V_s|\) required — which is what the worked examples of Chapters 10 to 12 did, because it needs no iteration. The two give the same regulation figure provided the same load is used, because the ratio \(|V_s|/(|A||V_r|)\) is what the formula actually contains. Working from a fixed \(|V_r|\) is therefore the practical route, and the "hold \(V_s\) fixed" language is simply how the answer is interpreted.
Regulation Against Load Power Factor
Regulation is not a property of the line. It is a property of the line and the load it is carrying, and the load's power factor matters as much as its magnitude. Chapter 10 derived the approximate drop for a short line by projecting the impedance drop onto the receiving voltage; with \(\mathbf{V}_r\) as reference and \(\mathbf{I}_r = I\angle-\phi\) for a lagging load,
The in-phase part of the drop dominates the magnitude; the quadrature part contributes only at second order and is why the approximation is good to a fraction of a percent for any realistic line. Read the bracket. The resistive term \(R\cos\phi\) is always positive: real power always costs voltage. The reactive term \(X\sin\phi\) changes sign with the power factor, and since \(X\) is two to ten times \(R\) on an overhead line, it is the term that decides the outcome.
At a lagging power factor the load draws reactive power through the line's reactance and the drop is large. At unity power factor only the resistive term survives. At a leading power factor the reactive term subtracts, and if the load leads strongly enough the two terms cancel exactly.
The cancellation can be made exact. Write \(Z = R+jX = |Z|\angle\theta\), take \(\mathbf{V}_r\) as reference and let the current lead by \(\phi\), so \(\mathbf{I}_r = I\angle\phi\). Then \(\mathbf{V}_s = V_r + I|Z|\angle(\theta+\phi)\) and
Since \(I|Z|/2V_r\) is small — a few per cent — the inverse cosine is a little more than \(90^\circ\), so \(\phi \simeq 90^\circ - \theta\) and \(\cos\phi \simeq \sin\theta = X/|Z|\). A line whose impedance angle is \(68^\circ\) has zero regulation at a leading power factor of about \(0.93\); load it any more capacitively and the receiving voltage exceeds the sending voltage even at full load.
Regulation can therefore be negative, and on a line serving a capacitor-compensated industrial load it routinely is. Negative regulation is not automatically a virtue: it means that throwing the load off makes the voltage fall, which is just as much a disturbance as a rise. The design target is a small regulation of either sign, not a large negative one.
Transmission Efficiency and the Loss Budget
Efficiency has the definition one would expect,
and the whole difficulty is in getting \(P_{\text{loss}}\) right. On a short line it is easy, because the same current flows in every element of the conductor: \(P_{\text{loss}} = 3I^{2}R\), and there is nothing else. That single formula, pushed a little, produces the most useful scaling law in transmission engineering. Substitute \(I = P_r/(\sqrt3\,V_{LL}\cos\phi)\):
Doubling the voltage divides the loss fraction by four. Improving the power factor from 0.8 to unity divides it by \(1/0.64 = 1.56\). Halving the resistance — a bigger conductor, or the bundle of Chapter 8 — halves it. And the loss fraction grows in proportion to the power carried, so a line that is 2% lossy at half load is 4% lossy at full load. The first of these exponents is the entire economic case for extra-high voltage, made in Chapter 2 and now quantified.
Three other loss mechanisms exist and must at least be named. Leakage across insulator strings is represented by the conductance \(g\) of Chapter 12's line model; on a clean, dry overhead line it is negligible, on a salt-polluted coastal line it is not. Dielectric loss in the insulation is negligible overhead but significant in the cables of Chapter 9, where it grows as \(V^{2}\omega C\tan\delta\) and sets the practical length limit of an a.c. cable. Corona loss, the subject of Chapter 15, is zero below a threshold voltage and then rises steeply; on an EHV line in foul weather it can exceed the \(I^{2}R\) loss at light load. All three share a property that matters for Section 13-6: they depend on the voltage, not on the current, and so are roughly constant while the load varies.
Where the Loss Really Sits
On a medium or long line the sending-end and receiving-end currents are not equal, because the shunt capacitance injects current all along the way. Chapter 12 wrote the current at a distance \(x\) from the receiving end as
and the true loss is the integral of \(3r|I(x)|^{2}\) over the length, plus \(3g|V(x)|^{2}\) if leakage is modelled:
This integral is never evaluated in practice, and it does not have to be. Conservation of energy already supplies the answer: whatever is dissipated inside the line is exactly the difference between what enters and what leaves.
Both terminal quantities come straight out of the two-port relation, so no integration and no assumption about the current profile is required. Example 3 verifies that this equals the integral above to five significant figures for the reference line.
The tempting shortcuts are all wrong, and it is worth knowing by how much. Using \(3I_r^{2}R\) on the reference line at its 60 MW load gives 2.94 MW against a true 2.53 MW — sixteen per cent high, because the receiving-end current is the largest current anywhere on the line. Using \(3I_s^{2}R\) gives 2.28 MW, ten per cent low. Averaging the squares, \(\tfrac32 R\big(|I_s|^{2}+|I_r|^{2}\big)\), gives 2.61 MW, three per cent high, and this is the best of the shortcuts because the current profile is close to linear over 200 km. None of them is a substitute for \(P_s - P_r\).
The current profile itself repays a glance. At 0.9 lagging the reference line carries 175.0 A at the receiving end and only 154.2 A at the sending end, falling monotonically along the way — the charging current, which leads the voltage by roughly \(90^\circ\), partially cancels the lagging load current, and the cancellation is most complete near the sending end where the accumulated charging current is largest. At unity power factor the opposite happens: the charging current adds in quadrature to a load current that has no reactive component, and the profile rises from 157.5 A at the load to 171.7 A at the source.
Efficiency as the Load Varies
A line does not run at one load. It follows the daily and seasonal demand curve of Chapter 30, and its efficiency changes as it does. Split the loss into the part that varies with current and the part that does not:
Efficiency is then \(\eta = P_r/(P_r + P_0 + kP_r^{2})\). Differentiate with respect to \(P_r\) and set the derivative to zero. The numerator of \(d\eta/dP_r\) is proportional to \(P_0 - kP_r^{2}\), so:
At that load \(\eta_{\max} = P_r^{*}/(P_r^{*}+2P_0)\). Because \(P_0\) on an overhead line is small, \(P_r^{*}\) usually falls well below the rated load — which is deliberate, since the line spends most of the year below rating.
The rule holds cleanly whenever the fixed loss is genuinely independent of the load current, as corona and leakage are. It fails in an instructive way when the "fixed" loss is itself an \(I^{2}R\) loss in the same conductor, which is what the charging current produces. On the reference line the no-load loss is 184 kW of \(I^{2}R\) caused by 77 A of charging current. Adding a lagging load does not simply add to that current, it partly cancels it, so the loss initially falls: at 5 MW the total loss is 159 kW, below the no-load figure. The efficiency peak, at 15.1 MW and 98.50%, therefore does not satisfy "variable equals fixed" at all. The lesson is not that the rule is wrong but that it applies to independent loss terms, and the charging loss is not independent.
For planning, a single instantaneous efficiency is less useful than the energy lost over a year. If the line's peak loss is \(P_{\text{loss,max}}\), the annual energy loss is
where LF is the load factor of Chapter 30 and LSF the loss-load factor. The quadratic dominance in that empirical relation is the \(I^{2}\) again: a line with a load factor of 0.6 has a loss factor of only 0.43, because it spends most of its time well below peak, where the loss falls quadratically. Example 5 puts a rupee figure on it.
The Four Models on One Line
Chapters 10, 11 and 12 offered four models of the same 200 km line. Now that regulation and efficiency have precise definitions, the four can be put side by side on the same load and the cost of each simplification read directly. The load throughout is 60 MW at 220 kV, 0.9 lagging, so \(\mathbf{I}_r = 174.95\angle-25.842^\circ\) A and \(V_r = 127\,017\) V per phase.
| Model | \(A\) | \(B\) (Ω) | \(V_{s(LL)}\) | \(I_s\) | % Reg | Loss | \(\eta\) |
|---|---|---|---|---|---|---|---|
| Short line (Ch 10) | \(1\angle0^\circ\) | \(86.16\angle68.20^\circ\) | 239.94 kV | 174.95 A | 9.06% | 2.939 MW | 95.33% |
| Nominal-T (Ch 11) | \(0.97605\angle0.564^\circ\) | \(85.13\angle68.48^\circ\) | 234.52 kV | 154.45 A | 9.22% | 2.614 MW | 95.83% |
| Nominal-π (Ch 11) | \(0.97605\angle0.564^\circ\) | \(86.16\angle68.20^\circ\) | 234.84 kV | 154.06 A | 9.37% | 2.520 MW | 95.97% |
| Exact hyperbolic (Ch 12) | \(0.97613\angle0.559^\circ\) | \(85.47\angle68.38^\circ\) | 234.64 kV | 154.20 A | 9.26% | 2.531 MW | 95.95% |
Three observations survive the arithmetic. First, the two nominal circuits bracket the exact answer in every column, the T underestimating and the π overestimating — exactly as Section 11-5 predicted from the signs of the neglected series terms. Averaging them would give 234.68 kV against a true 234.64 kV.
Second, the short-line model happens to get the regulation nearly right, at 9.06% against 9.26%, and this is luck rather than merit. It errs twice in opposite directions: it overstates \(|V_s|\) by 2.3% because it lets the full load current flow through the whole reactance, and it takes \(|A|=1\) instead of 0.976, which understates the no-load voltage by the same order. The two mistakes very nearly cancel in the ratio.
Third, no such cancellation protects the efficiency. The short-line model gives 95.33% against 95.95%, and its 2.94 MW loss is 16% too large, because it puts the receiving-end current — the largest current on the line — into every metre of conductor. Regulation forgives a bad model; efficiency does not. A quantity that depends on the square of a current is far less tolerant of a wrong current profile than one that depends on a ratio of voltages.
The Receiving-End Power Circle Diagram
Everything so far has taken the load as given and computed the sending end. The operator's question is usually the reverse: both bus voltages are held at rated value by generators and tap-changers, and what is wanted is the range of real and reactive power the line can then deliver, and what reactive support the receiving bus needs. The circle diagram answers all of that in one figure.
Solve the two-port relation for the receiving-end current and form the complex power. Write \(A = |A|\angle\alpha\), \(B = |B|\angle\beta\), take \(\mathbf{V}_r = |V_r|\angle0\) as reference and let the sending-end voltage lead by the load angle, \(\mathbf{V}_s = |V_s|\angle\delta\):
Read this as geometry in the \(P\)–\(Q\) plane. The second term is a fixed vector: it does not contain \(\delta\), so with both voltages held it never moves. The first term has fixed length and an angle that sweeps as \(\delta\) changes. A fixed point plus a vector of constant length turning about it traces a circle.
The centre depends only on the receiving voltage and the line; the radius is proportional to the product of the two terminal voltages. Raising \(|V_s|\) inflates the circle without moving its centre — which is precisely how a generator's excitation buys reactive support at the far end.
Separating real and imaginary parts gives the two working formulas, which are just Chapter 11's power-transfer expressions written in a new order:
Four readings come off the diagram at once. The horizontal coordinate of any point on the circle is the real power delivered; the vertical coordinate is the reactive power delivered to the line's receiving terminals. The topmost point of the circle is the maximum real power that can be pushed through with those two voltages, reached at \(\delta = \beta\). The vertical gap between the circle and the load's actual reactive demand is the reactive power that a capacitor bank or synchronous condenser must supply if the receiving voltage is to be held at the assumed value. And the load angle at any operating point is \(\beta\) minus the angle subtended at the centre — Chapter 28 will use exactly that angle as the state variable of the stability problem.
Improving Both at Once: Compensation
The formulas of this chapter identify the levers precisely. Regulation is driven by \(I\big(R\cos\phi + X\sin\phi\big)\); efficiency by \(P_rR/(V^{2}\cos^{2}\phi)\). Only three quantities appear in both: the current, the reactance, and the power factor. Each can be attacked.
Shunt capacitors at the receiving end. A capacitor bank supplies the load's reactive demand locally, so the line no longer carries it. The current falls from \(P/(\sqrt3 V\cos\phi)\) toward \(P/(\sqrt3 V)\), which cuts the \(I^{2}R\) loss by \(\cos^{2}\phi\) and removes the \(IX\sin\phi\) term from the drop simultaneously. This is the cheapest and commonest remedy, and Chapter 34 sizes it properly. Its weakness is that the reactive output falls as \(V^{2}\), so it delivers least support exactly when the voltage has collapsed and support is most needed.
Series capacitors. Inserting \(-jX_C\) in series cancels part of \(X\). With a compensation degree \(k = X_C/X\), the effective reactance becomes \(X(1-k)\), and both the reactive term of the drop and the denominator of the power-transfer formula shrink together. Chapter 14 shows that this also shortens the line electrically and raises its natural loading. The risks — subsynchronous resonance, and the fault current that must be bypassed around the capacitor — belong to Chapter 38.
Shunt reactors. These do the opposite: they absorb the charging reactive power of a lightly loaded line and suppress the Ferranti rise. They improve the no-load voltage at the cost of a slightly worse full-load one, and on an EHV line they are switched in and out as the load follows the daily curve.
Higher voltage, or a bundle. Both attack the problem at its root. Doubling \(V\) at constant power quarters the loss fraction and halves the current, and hence halves the drop. Bundling reduces \(X\) by about 30% and \(R\) in proportion to the number of subconductors — the whole argument of Chapter 8, now with a performance number attached.
| Measure | Acts on | Regulation | Efficiency | Cost / risk |
|---|---|---|---|---|
| Shunt capacitor at load | \(\cos\phi\), \(I\) | Improves strongly | Improves as \(\cos^{2}\phi\) | Cheap; output falls as \(V^{2}\) |
| Series capacitor | \(X\) | Improves strongly | Little direct effect | SSR, protection complexity |
| Shunt reactor | Line \(C\) | Fixes no-load rise | Slight loss increase | Must be switchable |
| Synchronous condenser / SVC | \(Q\) at either sign | Improves, both directions | Improves | Expensive; needs control |
| Larger conductor or bundle | \(R\), \(X\) | Improves | Improves in proportion | Tower and right-of-way cost |
| Higher transmission voltage | \(V^{2}\) | Improves | Improves as \(1/V^{2}\) | Insulation, corona (Ch 15) |
Worked Examples
Problem. The 200 km, 220 kV, 50 Hz reference line has exact constants \(A = D = 0.976081+j0.009523\), \(B = 31.49+j79.46\ \Omega\) and \(C = -1.911\times10^{-6}+j5.9521\times10^{-4}\) S. It delivers 60 MW at 220 kV, 0.9 power factor lagging. Find the regulation and the efficiency, and state the no-load receiving voltage.
Solution. Per phase, \(V_r = 220\,000/\sqrt3 = 127\,017\) V taken as reference. The load current is
Apply the two-port relation term by term:
Now the two performance figures. Remove the load with \(|V_s|\) held at 135 471 V per phase; the open-circuit receiving voltage is \(|V_s|/|A|\):
For the efficiency, the sending-end power factor angle is the angle between \(\mathbf{V}_s\) and \(\mathbf{I}_s\):
Note how nearly unity the sending-end power factor is. The line's own charging current, leading by almost exactly \(90^\circ\), has supplied most of the load's 29.1 MVAr demand from within the line itself, leaving the source to provide only a small reactive component. That is the same cancellation that flattens the current profile in Section 13-5, seen from the other end.
Problem. Repeat Example 1 for power factors from 0.7 lagging to 0.7 leading and account for the shape of both curves. At what power factor is the regulation zero, and at what power factor is the efficiency greatest?
Solution. The load current magnitude is \(60\times10^{6}/(\sqrt3\times220\times10^{3}\cos\phi)\), which itself grows as the power factor worsens, so both effects act together. Repeating the computation of Example 1 at each angle gives:
| Power factor | \(|I_r|\) (A) | \(V_{s(LL)}\) (kV) | % Reg | \(\eta\) |
|---|---|---|---|---|
| 0.70 lagging | 224.94 | 245.89 | 14.50% | 94.03% |
| 0.80 lagging | 196.82 | 240.20 | 11.85% | 95.24% |
| 0.90 lagging | 174.95 | 234.64 | 9.26% | 95.95% |
| 0.972 lagging | 162.00 | 229.59 | 6.91% | 96.16% |
| 1.00 | 157.46 | 224.59 | 4.58% | 95.95% |
| 0.95 leading | 165.75 | 217.83 | 1.44% | 95.00% |
| 0.902 leading | 174.64 | 214.75 | 0.00% | 94.32% |
| 0.80 leading | 196.82 | 209.26 | −2.55% | 92.74% |
| 0.70 leading | 224.94 | 203.83 | −5.08% | 90.74% |
Regulation falls monotonically as the power factor swings from lagging to leading, passing through zero at 0.902 leading and going negative beyond. Check that against the closed form of Section 13-3, using the short-line impedance \(Z = 32+j80 = 86.16\angle68.199^\circ\ \Omega\) and \(I = 174.6\) A:
The short-line formula predicts 0.905 leading against the exact 0.902 — close, because at 200 km the shunt admittance shifts the answer by only a third of a percent.
The efficiency curve is the surprise. It does not peak at unity power factor, where the short-line law \(P_{\text{loss}}\propto1/\cos^{2}\phi\) says it should. It peaks at 0.972 lagging, at 96.16%. The reason is the one given in Section 13-5: the line's own charging current leads by \(90^\circ\), and a slightly lagging load current cancels part of it along the whole length, minimising \(\int|I(x)|^{2}dx\). At unity power factor nothing cancels and the loss rises again. The optimum lag is small because the load current here is more than twice the charging current; on a lightly loaded 400 kV line, where they are comparable, the effect is much larger.
Problem. For the reference line at the load of Example 1, compute the loss by integrating \(3r|I(x)|^{2}\) along the line and compare it with \(P_s-P_r\) and with the three usual shortcuts. Where along the line is the loss density greatest?
Solution. With \(\gamma = 2.1499\times10^{-4}+j1.11634\times10^{-3}\) per km and \(Z_c = 378.95\angle-10.900^\circ\ \Omega\), the current at a distance \(x\) from the load is \(\mathbf{I}(x) = \mathbf{I}_r\cosh\gamma x + (\mathbf{V}_r/Z_c)\sinh\gamma x\). Evaluating its magnitude:
| \(x\) from receiving end | 0 km | 50 km | 100 km | 150 km | 200 km |
|---|---|---|---|---|---|
| \(|I(x)|\), A | 174.95 | 167.28 | 161.07 | 156.62 | 154.20 |
The two agree to five figures, which is the check that the ABCD constants and the wave solution describe the same line. Now the shortcuts:
| Estimate | Expression | Value | Error |
|---|---|---|---|
| Receiving-end current | \(3I_r^{2}R = 3(174.95)^{2}(32)\) | 2.939 MW | +16.1% |
| Sending-end current | \(3I_s^{2}R = 3(154.20)^{2}(32)\) | 2.283 MW | −9.8% |
| Mean of squares | \(\tfrac32R\big(I_s^{2}+I_r^{2}\big)\) | 2.611 MW | +3.2% |
| Exact | \(P_s-P_r\) | 2.531 MW | — |
The loss density \(3r|I|^{2}\) is greatest at the receiving end, where the current is largest, and falls by 22% along the line: the receiving half of the line dissipates 1.348 MW against the sending half's 1.183 MW. That asymmetry is the physical reason \(3I_r^{2}R\) overestimates and \(3I_s^{2}R\) underestimates, and it also explains why the mean-of-squares estimate does best — the current profile is nearly linear, so its mean square is nearly the average of the end values.
Problem. Tabulate the efficiency of the reference line at 0.9 lagging from no load to 160 MW with \(V_r\) held at 220 kV. Then suppose the line also suffers 300 kW of corona and leakage loss independent of load; find the load of maximum efficiency and the efficiency there.
Solution. Repeating the two-port computation at each load:
| \(P_r\) (MW) | 0 | 20 | 40 | 60 | 100 | 132.6 | 160 |
|---|---|---|---|---|---|---|---|
| Loss (MW) | 0.184 | 0.324 | 1.106 | 2.531 | 7.308 | 13.10 | 19.29 |
| \(\eta\) (%) | — | 98.41 | 97.31 | 95.95 | 93.19 | 91.01 | 89.24 |
| % Reg | 0 | 3.02 | 6.11 | 9.26 | 15.73 | 21.13 | 25.76 |
The 184 kW at zero load is not corona: it is genuine \(I^{2}R\) produced by the 77.5 A of charging current that flows even with the far end open. Between no load and about 5 MW the loss actually falls, to 159 kW, because the lagging load current begins cancelling that charging current; the efficiency peaks at 98.50% near 15 MW and declines thereafter. The final column, 132.6 MW, is the line's surge impedance loading, the natural loading Chapter 14 will show it was designed around.
Now add 300 kW of load-independent loss. Fit the variable term from the 60 MW point, where the current-dependent loss is 2.531 MW:
Maximum efficiency occurs at 20.7 MW, one-sixth of the natural loading. Every real transmission line is like this: it is at its most efficient far below the load it is built to carry, because it is sized for the peak and lives most of its life well below it.
Problem. A three-phase 50 Hz, 132 kV, 160 km line has \(r = 0.16\ \Omega\)/km, \(x = 0.42\ \Omega\)/km and \(b = 2.7\times10^{-6}\) S/km. It delivers 40 MW at 132 kV, 0.85 power factor lagging. Using the nominal-π model, find the sending-end voltage and current, the regulation and the efficiency. If the line runs at a load factor of 0.6 all year, what is the annual energy loss and its value at ₹4 per kWh?
Solution. Total parameters: \(\mathbf{Z} = 25.6+j67.2 = 71.911\angle69.146^\circ\ \Omega\) and \(\mathbf{Y} = j4.32\times10^{-4}\) S. The nominal-π constants follow from Chapter 11:
With \(V_r = 132\,000/\sqrt3 = 76\,210\) V and \(|I_r| = 40\times10^{6}/(\sqrt3\times132\times10^{3}\times0.85) = 205.83\) A at \(-31.788^\circ\), so \(\mathbf{I}_r = 174.95-j108.43\) A:
A regulation of 16% is unacceptable — the load would sit at 132 kV under full load and be pushed to 153 kV when it was thrown off. The cure is either a capacitor bank at the load or a tap-changing transformer, and the fact that the poor power factor of 0.85 is responsible for most of it points at the capacitor bank first.
For the energy loss, the peak loss is \(43.000-40 = 3.000\) MW. With a load factor of 0.6 the loss-load factor is
Four and a half crore rupees a year, for one 160 km circuit. Capitalised over the life of the line at any reasonable discount rate, that is a sum comparable to the cost of the conductor itself, which is why conductor size is chosen by an economic optimum — Kelvin's law — and not by thermal rating alone.
Problem. Both ends of the reference line are held at 220 kV. Construct the receiving-end circle. What real power can the line deliver at most? For a 60 MW, 0.9 lagging load at the receiving bus, what load angle is required and what capacitor rating must be installed to hold the receiving voltage at 220 kV?
Solution. With \(|A| = 0.97613\), \(\alpha = 0.559^\circ\), \(|B| = 85.472\ \Omega\), \(\beta = 68.382^\circ\), and \(|V_s| = |V_r| = 127\,017\) V per phase:
The maximum real power is the horizontal extreme, reached when \(\delta=\beta\) so that the rotating vector points along \(+P\):
For 60 MW, solve the real-power equation for the angle:
The negative sign is the whole point. With both ends at 220 kV and only 60 MW flowing, the line's own charging capacitance produces more reactive power than its reactance consumes, and 13.37 MVAr must be absorbed at the receiving bus. The load, however, wants to draw \(60\tan(25.842^\circ) = 29.06\) MVAr. The shortfall is made up by a capacitor bank:
A 42.4 MVAr bank at the receiving bus holds 220 kV at both ends with 60 MW flowing, and the sending end then sees a load angle of only \(6.70^\circ\). Compare this with Example 1, where no capacitor was fitted and the sending end had to be raised to 234.6 kV instead. The circle diagram gives both answers, and the choice between them — raise the source voltage, or install reactive support at the load — is the central trade-off of Chapter 34.
Chapter Summary
\(\%\text{Reg} = \big(|V_s|/|A| - |V_r|\big)/|V_r|\). The constant \(A\) alone fixes the no-load voltage.
Drop \(\simeq I(R\cos\phi + X\sin\phi)\); since \(X \gg R\), the reactive term decides the answer.
At a leading \(\phi\) with \(\cos(\theta+\phi) = -I|Z|/2V_r\); beyond it the regulation goes negative.
Never \(3I_r^{2}R\) on a line with shunt admittance — that overstates the loss by 16% at 200 km.
\(P_{\text{loss}}/P_r = P_rR/(V^{2}\cos^{2}\phi)\) — four levers, with voltage the strongest.
Where variable loss equals fixed loss — normally far below the rated load.
Centre \(3|A||V_r|^{2}/|B|\angle(\beta-\alpha)\) reversed, radius \(3|V_s||V_r|/|B|\); \(P_{\max}\) at \(\delta=\beta\).
Shunt capacitors cut \(I\) and the drop together; series capacitors cut \(X\); reactors fix no load.
Practice Problems
Take 50 Hz throughout, use the model appropriate to the stated length, and quote regulation and efficiency to two decimal places. Problems 6 to 8 are of GATE standard.
- A 50 km, 33 kV line has \(R = 8\ \Omega\) and \(X = 12\ \Omega\) per phase and delivers 5 MW at 0.8 power factor lagging. Find the sending-end voltage, the regulation and the efficiency. Repeat with the power factor corrected to 0.95 lagging and state the reduction in loss.
- Show from the approximate drop formula that the regulation of a short line is zero when \(\tan\phi \simeq R/X\) with the current leading, and explain why the exact condition of Section 13-3 gives a slightly larger leading angle.
- A 150 km, 132 kV line has \(z = 0.12+j0.40\ \Omega\)/km and \(y = j3.2\times10^{-6}\) S/km. Using the nominal-π model, find \(A\), \(B\), \(C\), \(D\), and then the regulation and efficiency for a load of 30 MW at 0.9 lagging.
- For the line of Problem 3, find the no-load receiving-end voltage when the sending end is held at 132 kV, and the charging current that flows in that condition. Comment on whether a shunt reactor is needed.
- A line has a constant loss of 250 kW and an \(I^{2}R\) loss of 1.8 MW when delivering 45 MW. Determine the load at which its efficiency is greatest, and the efficiency there. Sketch \(\eta\) against \(P_r\).
- A 220 kV line has \(A = 0.94\angle1.2^\circ\) and \(B = 130\angle74^\circ\ \Omega\). Both ends are held at 220 kV. Find the radius and centre of the receiving-end circle, the maximum receiving-end power, and the reactive power that must be supplied at the receiving bus for a 150 MW load at 0.9 lagging.
- The same 220 kV line of Problem 6 supplies 150 MW at unity power factor with the receiving end at rated voltage. Find the required sending-end voltage and the regulation, and then find the shunt capacitor rating that would allow the sending end to remain at 220 kV.
- A 400 km, 400 kV line has \(A = 0.909\angle0.53^\circ\), \(B = 124.6\angle84.8^\circ\ \Omega\) and a surge impedance of 298 Ω. Compute its regulation and efficiency at 0.5, 1.0 and 1.5 times its surge impedance loading, all at unity power factor and 400 kV at the receiving end, and explain the trend in the regulation column.