Part 5 · Chapter 24

Unsymmetrical Faults

Each kind of unbalanced fault imposes two or three constraints at a single point of the system, and when those constraints are written in sequence quantities they say nothing more complicated than "connect the three sequence networks in series", "connect two of them in parallel", or "connect all three in parallel".

Electric Power Systems Prof. Mithun Mondal Reading time ≈ 52 min
i What you'll learn
  • How the terminal conditions of each fault type transform into relations among sequence quantities, and how those relations dictate a circuit connection.
  • Why the three sequence networks go in series for a line-to-ground fault, in parallel opposition for a line-to-line fault, and all in parallel for a double line-to-ground fault.
  • Where the \(3Z_f\) in the LG formula comes from — the same argument that produced \(3Z_n\) in Chapter 23.
  • How to recover the three phase currents and the three phase voltages once the sequence quantities are known.
  • When an earth fault is more severe than a three-phase fault, and the single ratio \(Z_0/Z_1\) that decides it.
  • What an open conductor does, and why series faults connect the same three networks in the opposite way.
  • How the \(\pm30^\circ\) shift of a delta–star bank turns an earth fault on one side into a two-phase pattern on the other.
Section 24-1

The Fault Point and the Rules of the Game

Chapter 21 solved the symmetrical three-phase fault, and the solution was short because the fault preserved the symmetry of the system: one network, one Thévenin equivalent, one division. Every other fault destroys that symmetry. The three phase currents are unequal, the three phase voltages are unequal, and no per-phase circuit exists in which to work.

Unsymmetrical faults are also the ones that actually happen. Field statistics from transmission systems put single line-to-ground faults at roughly 70 to 80 per cent of all faults, line-to-line at 10 to 15 per cent, double line-to-ground at 5 to 10 per cent, and the balanced three-phase fault — the one that is easiest to calculate — at only 2 to 5 per cent. The chapter that is hardest to write is the one that covers almost everything that occurs.

Chapter 22 supplied the transformation and Chapter 23 supplied the networks. What remains is the connection between them, and it rests on a single observation: a fault is a set of algebraic constraints imposed at one point of an otherwise healthy system. Two conductors intact means two currents are zero. A short to earth means one voltage is fixed by the fault path. Those constraints are statements about phase quantities; transform them, and they become statements about sequence quantities; and statements about sequence quantities are instructions for wiring three circuits together.

abc Z_fZ_fZ_f earth three-phase(Chapter 21) line-to-ground70–80 % of faults line-to-line10–15 % double line-to-ground5–10 %
Four ways of connecting three conductors and the earth — and how often each occurs

Before any algebra, the assumptions must be stated, because every formula in this chapter inherits them. They are the assumptions of Chapter 21, extended to three networks.

🔑
The standing assumptions
The system is balanced before the fault, so only the positive-sequence network is alive; the fault connects the three networks at one point and nowhere else; the pre-fault voltage \(V_f\) at the fault bus is taken as \(1.0\angle0^\circ\) per unit; resistances and line charging are neglected; and rotating machines are represented by an emf behind \(jX_d''\).

The pre-fault voltage is a positive-sequence quantity by definition — a balanced system has no other kind. This is why \(V_f\) appears in one of the three Thévenin equations and not in the other two.

Two notational conventions run through the chapter. The fault is always taken to be on phase \(a\), or on phases \(b\) and \(c\), because the transformation of Chapter 22 is written with phase \(a\) as reference; any real fault is relabelled to fit. And the fault currents flowing out of the system into the fault are written \(I_{fa}, I_{fb}, I_{fc}\), with their sequence components \(I_{a0},I_{a1},I_{a2}\). Older texts, Stevenson among them, write these as \(I_{fa}^{(0)},I_{fa}^{(1)},I_{fa}^{(2)}\); the meaning is identical.

Section 24-2

The Three Thévenin Equivalents

Section 23-8 reduced each sequence network of the system to a Thévenin equivalent at the bus \(k\) where the fault is to occur. Those three equations are the fixed half of every problem in this chapter, and they are worth writing once more, because everything else is added to them.

The network half of the problem
\[ V_{a1} = V_f - Z_1 I_{a1}, \qquad V_{a2} = -\,Z_2 I_{a2}, \qquad V_{a0} = -\,Z_0 I_{a0} \]

Here \(Z_1=Z_{kk}^{(1)}\), \(Z_2=Z_{kk}^{(2)}\) and \(Z_0=Z_{kk}^{(0)}\) are the driving-point impedances of the three sequence networks at the fault bus, obtained either by series–parallel reduction or as diagonal entries of the three bus impedance matrices of Chapter 17. The signs record that positive current is defined as flowing out of the network into the fault, so it produces a drop in each network.

Three equations, six unknowns. The fault supplies the missing three. Whatever the fault type, the procedure is the same, and it is worth stating as a recipe because the four cases differ only in step 2.

StepWhat to doWhere it comes from
1Build the three sequence networks and reduce each to \(Z_1\), \(Z_2\), \(Z_0\) at the fault busChapter 23
2Write the fault's terminal conditions in phase quantities and transform themChapter 22; Sections 24-3 to 24-5
3Read off the network interconnection the transformed conditions demandSeries, parallel, or both
4Solve the connected circuit for \(I_{a0},I_{a1},I_{a2}\)Ohm's law on one loop
5Recover phase currents by \(\mathbf{I}_{abc}=\mathbf{A}\,\mathbf{I}_{012}\), and sequence voltages from the three equations aboveChapter 22
6Find voltages and currents elsewhere in the system from \(Z_{jk}^{(0)},Z_{jk}^{(1)},Z_{jk}^{(2)}\)Chapter 17; Section 24-8
Only step 2 is new. Steps 1, 5 and 6 belong to earlier chapters, and steps 3 and 4 are single-loop circuit analysis. The genuinely new content of this chapter is a page of algebra repeated three times, and once the pattern is seen the three cases stop being three things to memorise.
Section 24-3

The Single Line-to-Ground Fault

A conductor touches a tower, a lightning stroke flashes an insulator string over, a tree grows into a phase — the result is a connection from one phase to earth through whatever impedance \(Z_f\) the arc or the contact provides. Phases \(b\) and \(c\) remain intact, so no current leaves them, and phase \(a\) is tied to earth through \(Z_f\).

Terminal conditions
\[ I_{fb}=0, \qquad I_{fc}=0, \qquad V_{ka} = Z_f I_{fa} \]

Transform the two current conditions. With \(I_{fb}=I_{fc}=0\), the analysis equations of Chapter 22 read

Sequence currents of an LG fault
\[ \begin{bmatrix}I_{a0}\\I_{a1}\\I_{a2}\end{bmatrix} = \frac13\begin{bmatrix}1&1&1\\1&a&a^2\\1&a^2&a\end{bmatrix}\begin{bmatrix}I_{fa}\\0\\0\end{bmatrix} = \frac13\begin{bmatrix}I_{fa}\\I_{fa}\\I_{fa}\end{bmatrix} \]
\[ \Longrightarrow\quad I_{a0}=I_{a1}=I_{a2}=\frac{I_{fa}}{3} \]

Every entry of the first column of \(\mathbf{A}^{-1}\) is \(\tfrac13\), so a current in phase \(a\) alone splits into three equal thirds. Three networks carrying the same current can only be in series. That is the whole of the topology; what remains is to find what else is in the loop.

Add the three Thévenin equations, using \(I_{a0}=I_{a1}=I_{a2}\):

Summing the three networks
\[ V_{ka}=V_{a0}+V_{a1}+V_{a2} = V_f - \big(Z_0+Z_1+Z_2\big)I_{a0} \]

and equate it to the voltage the fault path imposes. Here the factor of three appears for the second time in two chapters, and for exactly the same reason as in Section 23-2: the physical fault impedance carries the whole fault current \(I_{fa}=3I_{a0}\), while each sequence network carries only \(I_{a0}\).

The fault-path condition
\[ V_{ka} = Z_fI_{fa} = Z_f\big(3I_{a0}\big) = \big(3Z_f\big)I_{a0} \]
🔑
Single line-to-ground fault
\[ I_{a0}=I_{a1}=I_{a2}=\frac{V_f}{Z_0+Z_1+Z_2+3Z_f}, \qquad I_{fa}=3I_{a0}=\frac{3V_f}{Z_0+Z_1+Z_2+3Z_f} \]

The three sequence networks are connected in series with one another and with \(3Z_f\). For a bolted fault set \(Z_f=0\). The other two phase currents are zero, which the reader should confirm by transforming back: \(I_{fb}=I_{a0}+a^2I_{a1}+aI_{a2}=I_{a0}(1+a^2+a)=0\).

The voltages follow at once. Substituting the common current back into the three network equations gives \(V_{a1}=V_f-Z_1I_{a0}\), \(V_{a2}=-Z_2I_{a0}\) and \(V_{a0}=-Z_0I_{a0}\); the synthesis matrix then produces \(V_{ka}\) (which must equal \(3Z_fI_{a0}\), and is zero for a bolted fault) together with \(V_{kb}\) and \(V_{kc}\). The healthy-phase voltages are the interesting ones, and Section 24-6 examines what they do.

One structural point deserves emphasis. Because the three networks are in series, the fault current is limited by the sum of the three impedances, including \(Z_0\). If the zero-sequence network is open at the fault bus — an isolated neutral, or a fault beyond a delta winding — then \(Z_0=\infty\) and the earth-fault current is zero. That is not an artefact of the algebra: with no return path, no earth-fault current can flow.

Section 24-4

The Line-to-Line Fault

Two conductors touch — a bird bridges them, conductors clash in a gale, a jumper swings across — and phases \(b\) and \(c\) are joined through \(Z_f\) with no connection to earth. Phase \(a\) is intact.

Terminal conditions
\[ I_{fa}=0, \qquad I_{fb}=-I_{fc}, \qquad V_{kb}-V_{kc}=Z_fI_{fb} \]

The current conditions transform in two lines:

Sequence currents of an LL fault
\[ I_{a0}=\tfrac13\big(0+I_{fb}-I_{fb}\big)=0 \]
\[ I_{a1}=\tfrac13\big(0+aI_{fb}-a^2I_{fb}\big)=\tfrac{I_{fb}}{3}\big(a-a^2\big)=\frac{jI_{fb}}{\sqrt3}, \qquad I_{a2}=\tfrac{I_{fb}}{3}\big(a^2-a\big)=-\frac{jI_{fb}}{\sqrt3} \]
\[ \Longrightarrow\quad I_{a0}=0, \qquad I_{a1}=-I_{a2} \]

No zero-sequence current at all, and the positive- and negative-sequence currents are equal and opposite. That is the signature of two networks connected in parallel opposition: current leaves the positive-sequence network at the fault point and returns into the negative-sequence network.

The zero-sequence network deserves a sentence of its own. It carries no current, and being passive it contains no source, so every voltage in it is zero. The zero-sequence network is dead throughout an LL fault and plays no part in the calculation whatever the earthing arrangement. This is physically obvious — the fault does not involve earth — but it is worth stating because it means a line-to-line fault current is the same on a solidly earthed system and on an isolated-neutral one.

Now the voltage condition, which must be shown to be satisfied by the parallel connection rather than merely assumed. Expand each side separately. Since \(V_{a0}\) is zero,

Left-hand side
\[ V_{kb}-V_{kc} = \big(a^2V_{a1}+aV_{a2}\big)-\big(aV_{a1}+a^2V_{a2}\big) = \big(a^2-a\big)\big(V_{a1}-V_{a2}\big) \]
Right-hand side
\[ Z_fI_{fb} = Z_f\big(a^2I_{a1}+aI_{a2}\big) = Z_f\big(a^2-a\big)I_{a1} \qquad\text{using } I_{a2}=-I_{a1} \]

The common factor \((a^2-a)\) cancels — it is non-zero, being \(-j\sqrt3\) — and what survives is a statement purely about sequence quantities:

The condition in sequence terms
\[ V_{a1}-V_{a2} = Z_fI_{a1} \]

which is precisely the loop equation of the positive- and negative-sequence Thévenin equivalents joined in opposition through \(Z_f\). Substituting \(V_{a1}=V_f-Z_1I_{a1}\) and \(V_{a2}=-Z_2I_{a2}=+Z_2I_{a1}\) gives the answer.

🔑
Line-to-line fault
\[ I_{a1}=-I_{a2}=\frac{V_f}{Z_1+Z_2+Z_f}, \qquad I_{a0}=0 \]
\[ I_{fb}=-I_{fc}=\big(a^2-a\big)I_{a1}=-j\sqrt3\,I_{a1} \quad\Longrightarrow\quad \big|I_{fb}\big|=\frac{\sqrt3\,V_f}{\big|Z_1+Z_2+Z_f\big|} \]

The zero-sequence network is not connected. If \(Z_2=Z_1\), which is a good approximation away from generators, the bolted line-to-line fault current is \(\sqrt3/2 = 0.866\) times the three-phase fault current at the same point — always, and independently of every other system parameter.

Section 24-5

The Double Line-to-Ground Fault

Two conductors touch and the pair also reaches earth, through a common impedance \(Z_f\). This is the fault a fallen tower or a flashover of two insulator strings to the structure produces, and it is the one that combines both previous mechanisms.

Terminal conditions
\[ I_{fa}=0, \qquad V_{kb}=V_{kc}=Z_f\big(I_{fb}+I_{fc}\big) \]

Because phase \(a\) carries no current, the sum of the other two is the residual current:

First consequence
\[ I_{fa}+I_{fb}+I_{fc}=3I_{a0} \quad\text{and}\quad I_{fa}=0 \quad\Longrightarrow\quad I_{fb}+I_{fc}=3I_{a0} \]
\[ \Longrightarrow\quad V_{kb}=V_{kc}=3Z_fI_{a0}, \qquad\text{and}\qquad I_{a0}+I_{a1}+I_{a2}=0 \]

Sequence currents that sum to zero are three branches meeting at a node: the networks are all three in parallel. The voltage conditions fix what is in each branch. Transform \(V_{ka},V_{kb},V_{kb}\) — the second and third phase voltages being equal — and take the second and third rows:

Second consequence
\[ V_{a1}=\tfrac13\big(V_{ka}+aV_{kb}+a^2V_{kb}\big)=\tfrac13\big(V_{ka}-V_{kb}\big) \]
\[ V_{a2}=\tfrac13\big(V_{ka}+a^2V_{kb}+aV_{kb}\big)=\tfrac13\big(V_{ka}-V_{kb}\big) \qquad\Longrightarrow\qquad V_{a1}=V_{a2} \]

using \(a+a^2=-1\) in both lines. The first row supplies the link to the zero-sequence branch:

Locating the zero-sequence branch
\[ 3V_{a0}=V_{ka}+2V_{kb} = \big(V_{a0}+V_{a1}+V_{a2}\big)+2\big(3Z_fI_{a0}\big) \]
\[ \Longrightarrow\quad 2V_{a0} = 2V_{a1}+6Z_fI_{a0} \quad\Longrightarrow\quad V_{a1}=V_{a2}=V_{a0}-3Z_fI_{a0} \]

Read the last line as a circuit. The positive- and negative-sequence terminals are at the same potential; the zero-sequence terminal is at that potential plus the drop across \(3Z_f\). So the negative-sequence network and the series combination of the zero-sequence network with \(3Z_f\) hang in parallel from the positive-sequence network's terminals, and the three currents leaving that node sum to zero, as required.

🔑
Double line-to-ground fault
\[ I_{a1}=\frac{V_f}{Z_1+\dfrac{Z_2\big(Z_0+3Z_f\big)}{Z_2+Z_0+3Z_f}} \]
\[ I_{a2}=-I_{a1}\frac{Z_0+3Z_f}{Z_0+Z_2+3Z_f}, \qquad I_{a0}=-I_{a1}\frac{Z_2}{Z_0+Z_2+3Z_f} \]

The last two lines are ordinary current division between the two parallel branches, with the minus signs recording that both currents return into the node. The earth current is \(I_{fb}+I_{fc}=3I_{a0}\).

Two limits check the result. Setting \(Z_f=0\) gives the bolted double line-to-ground fault. Letting \(Z_f\to\infty\) opens the zero-sequence branch, so \(I_{a0}\to0\) and \(I_{a1}\to V_f/(Z_1+Z_2)\) — the line-to-line fault of Section 24-4, which is what a double line-to-ground fault becomes when the path to earth is removed. The formulas of the three fault types are not independent results; they are one family.

positiveV_f , Z₁ negative Z₂ zero Z₀ 3Z_f F I_a0 = I_a1 = I_a2
LG fault — three networks in series
positiveV_fZ₁ negativeZ₂ Z_f zero-sequence network not connected — dead I_a1 = −I_a2 , I_a0 = 0
LL fault — positive against negative
positiveV_fZ₁ negativeZ₂ zeroZ₀ 3Z_f F I_a0 + I_a1 + I_a2 = 0
LLG fault — all three in parallel
Section 24-6

Which Fault Is Worst, and What Earthing Decides

A switchgear engineer sizing a circuit breaker, and a protection engineer setting a relay, both need to know which fault at a given bus produces the largest current. The formulas of the last three sections answer the question, and the answer turns out to depend on a single ratio.

Take the common approximation \(Z_2=Z_1\), write \(k=Z_0/Z_1\), and set \(Z_f=0\). Then the three bolted fault currents, all measured as the largest phase current, are

The three faults compared, with \(Z_2=Z_1\)
\[ \big|I_{3\phi}\big| = \frac{V_f}{Z_1}, \qquad \big|I_{LG}\big| = \frac{3V_f}{2Z_1+Z_0} = \frac{V_f}{Z_1}\cdot\frac{3}{2+k}, \qquad \big|I_{LL}\big| = \frac{\sqrt3\,V_f}{2Z_1} = \frac{V_f}{Z_1}\cdot\frac{\sqrt3}{2} \]
🔑
The severity rule
\[ \frac{I_{LG}}{I_{3\phi}} = \frac{3}{2+k} \;>\;1 \quad\Longleftrightarrow\quad k=\frac{Z_0}{Z_1}\;<\;1 \qquad\text{and}\qquad \frac{I_{LL}}{I_{3\phi}}=\frac{\sqrt3}{2}=0.866 \;\;\text{always} \]

A line-to-line fault is never the worst case. An earth fault exceeds the three-phase fault exactly when \(Z_0 < Z_1\), which is the normal situation at the terminals of a solidly earthed generator (where \(X_0\) is a fraction of \(X_d''\)) and the abnormal one out on a transmission line (where line \(Z_0\) is two to five times \(Z_1\)).

This is why solidly earthed generators are rare. Earthing the machine neutral through even a modest impedance adds \(3Z_n\) to \(Z_0\), pushes \(k\) above unity, and brings the earth-fault current below the three-phase value, which is what the machine's bracing and the breaker's rating were designed for. Example 5 sizes such a reactor.

The same ratio governs the other half of the earthing question — what happens to the two healthy phases. For a bolted LG fault on phase \(a\) with \(Z_2=Z_1\), substituting the sequence voltages into the synthesis equation and simplifying gives a compact result:

Healthy-phase voltage during an earth fault
\[ V_{a1}=V_f\frac{1+k}{2+k}, \qquad V_{a2}=\frac{-V_f}{2+k}, \qquad V_{a0}=\frac{-kV_f}{2+k} \]
\[ \big|V_{kb}\big|=\big|V_{kc}\big| = V_f\,\frac{\sqrt3\,\sqrt{k^2+k+1}}{2+k} \]

The quantity on the left, divided by \(V_f\), is the earth-fault factor, and it is what insulation and surge-arrester ratings are chosen against. Evaluating it:

\(k=Z_0/Z_1\)Earth-fault factor \(|V_{kb}|/V_f\)\(I_{LG}/I_{3\phi}\)Typical arrangement
00.8661.50Ideal solid earth at the machine terminals
0.50.9171.20Solidly earthed generator
11.0001.00Healthy phases unaffected — the crossover
21.1460.75Typical transmission bus
31.2490.60Limit of "effectively earthed"
51.3780.43Resistance- or reactance-earthed system
\(\infty\)1.7320Isolated neutral — full line voltage on the healthy phases

The two columns move in opposite directions, and that is the whole of the earthing dilemma. Raising \(Z_0\) reduces earth-fault current — good for equipment damage, for step-and-touch potentials, and for breaker duty — but raises the voltage the healthy phases must withstand, so the insulation and the arresters must be rated higher. A system is called effectively earthed when \(X_0/X_1\le3\) and \(R_0/X_1\le1\), which keeps the earth-fault factor below about 1.4, or 80 per cent of the \(\sqrt3\) that an isolated neutral would give. That threshold is why transmission systems at 132 kV and above, where insulation is the dominant cost, are almost always solidly or effectively earthed, while distribution and industrial systems, where continuity of supply matters more, are often resistance-earthed. Chapter 37 works through the choice in full.

Why the earth-fault factor is exactly 1 when \(Z_0=Z_1\). With all three sequence impedances equal, the fault sees the same impedance in each network, the sequence voltages combine so that the phasor of the faulted phase collapses to the origin while the other two are merely rotated — the neutral point moves to the tip of the faulted phasor, and the two healthy phasors keep their length. Any departure from \(Z_0=Z_1\) distorts that picture, one way below unity, the other way up towards \(\sqrt3\).
V_a (pre-fault) V_b V_c V_ka = 0 V_kb = 0.974∠−103.4° V_kc = 0.974∠+103.4° V_kbc = 1.895 pu (was 1.732 pu) Example 1 data: X₁=0.20 X₂=0.25 X₀=0.08 Z_f=0
The faulted phasor collapses to the origin; the other two shift but barely change length
Section 24-7

Open Conductors: Faults in Series

Everything so far has been a shunt fault: a connection made between conductors, or between a conductor and earth, that did not exist before. The other family of unbalance is the series fault, in which a connection that should exist is broken. A conductor snaps; a fuse in one phase clears while the other two hold; a circuit breaker's three poles fail to close together and one contact stays open. The system is then unbalanced not at a point on the line but across a gap in it, and the sequence method handles it with the same machinery, applied to the two ends of the gap instead of to a bus and earth.

Let \(V_{aa'},V_{bb'},V_{cc'}\) be the voltages across the break in each phase, and \(I_a,I_b,I_c\) the currents through it. For one conductor open — phase \(a\) broken, phases \(b\) and \(c\) continuous — the conditions are that no current flows in \(a\) and no voltage appears across the unbroken conductors:

One conductor open
\[ I_a=0, \qquad V_{bb'}=V_{cc'}=0 \]
\[ \Longrightarrow\quad I_{a0}+I_{a1}+I_{a2}=0, \qquad V_{0}=V_{1}=V_{2}=\tfrac13 V_{aa'} \]

Equal voltages across three branches whose currents sum to zero: the three sequence networks are connected in parallel across the break. For two conductors open — phases \(b\) and \(c\) broken, phase \(a\) continuous — the conditions are the mirror image:

Two conductors open
\[ I_b=I_c=0, \qquad V_{aa'}=0 \]
\[ \Longrightarrow\quad I_{a0}=I_{a1}=I_{a2}=\tfrac13 I_a, \qquad V_{0}+V_{1}+V_{2}=0 \]

Equal currents in three branches whose voltages sum to zero: the three networks are connected in series across the break. Laid beside the shunt faults, a duality appears that is worth tabulating, because it halves the amount to be remembered.

FaultConditionsSequence relationsConnection of the three networks
Three-phase (shunt)\(V_a=V_b=V_c=0\)\(I_{a0}=I_{a2}=0\)Positive-sequence network alone (Chapter 21)
Line-to-ground (shunt)\(I_b=I_c=0,\;V_a=Z_fI_a\)\(I_{a0}=I_{a1}=I_{a2}\)All three in series, with \(3Z_f\)
Line-to-line (shunt)\(I_a=0,\;I_b=-I_c\)\(I_{a0}=0,\;I_{a1}=-I_{a2}\)Positive against negative, through \(Z_f\)
Double line-to-ground (shunt)\(I_a=0,\;V_b=V_c\)\(I_{a0}+I_{a1}+I_{a2}=0,\;V_{a1}=V_{a2}\)Negative and (zero \(+\,3Z_f\)) in parallel across positive
One conductor open (series)\(I_a=0,\;V_{bb'}=V_{cc'}=0\)\(V_0=V_1=V_2,\;\sum I=0\)All three in parallel across the break
Two conductors open (series)\(I_b=I_c=0,\;V_{aa'}=0\)\(I_{a0}=I_{a1}=I_{a2},\;\sum V=0\)All three in series across the break

The impedances used are different, though. For a series fault the relevant quantities are the Thévenin impedances seen looking into the two ends of the gap in each sequence network, with the broken branch removed — not the driving-point impedances to the reference bus. The driving quantity is supplied by the compensation theorem: if the branch carried a pre-fault current \(I^{\text{pre}}\), then opening it leaves an open-circuit voltage \(V_{th}=I^{\text{pre}}Z_1^{\,pp'}\) across the gap in the positive-sequence network, and none in the other two.

A single numerical case shows the scale of the effect. Suppose a line carries a pre-fault current of \(1.0\angle{-20^\circ}\) per unit and that, with the phase-\(a\) conductor removed, the impedances across the gap are \(Z_1^{\,pp'}=Z_2^{\,pp'}=j0.50\) and \(Z_0^{\,pp'}=j1.20\) per unit. With the three networks in parallel,

One conductor open — worked
\[ V_{th}=I^{\text{pre}}Z_1^{\,pp'} = \big(1.0\angle{-20^\circ}\big)\big(j0.50\big) = 0.500\angle70^\circ \]
\[ V = \frac{V_{th}}{Z_1\left(\dfrac{1}{Z_1}+\dfrac{1}{Z_2}+\dfrac{1}{Z_0}\right)} = \frac{0.500\angle70^\circ}{2.4167}=0.2069\angle70^\circ \]
\[ I_{a1}=\frac{V_{th}-V}{Z_1}=0.5862\angle{-20^\circ}, \quad I_{a2}=\frac{-V}{Z_2}=0.4138\angle160^\circ, \quad I_{a0}=\frac{-V}{Z_0}=0.1724\angle160^\circ \]
\[ \big|I_b\big|=\big|I_c\big| = 0.904\ \text{pu}, \qquad 3I_{a0}=0.517\ \text{pu of residual current} \]

The load current in the two surviving phases has fallen only from 1.000 to 0.904 per unit, which no overcurrent relay would notice. But half a per unit of residual current now circulates, and every earth-fault relay in the vicinity sees it. This is why a broken conductor lying on dry ground — drawing almost no fault current, yet lethal to anyone who touches it — is detected by unbalance rather than by magnitude, and why negative-sequence and broken-conductor relays exist at all. Chapter 36 sets them.

Section 24-8

Voltages and Currents Away from the Fault

The sequence currents at the fault bus are only the first answer. A protection study needs the current in every line and the voltage at every bus, because those are the quantities the relays and the instrument transformers actually measure. Chapter 17 supplies the machinery: the off-diagonal entries of the three bus impedance matrices.

🔑
Sequence voltage at any bus \(j\) during a fault at bus \(k\)
\[ V_{j1}=V_f-Z_{jk}^{(1)}I_{a1}, \qquad V_{j2}=-Z_{jk}^{(2)}I_{a2}, \qquad V_{j0}=-Z_{jk}^{(0)}I_{a0} \]

Then \(\mathbf{V}_{j,abc}=\mathbf{A}\,\mathbf{V}_{j,012}\) gives the three line-to-ground voltages at bus \(j\). Setting \(j=k\) recovers the equations of Section 24-2, as it must.

Line currents follow from the sequence voltage differences. In a branch between buses \(p\) and \(q\) with sequence impedances \(z_1^{pq}\), \(z_2^{pq}\), \(z_0^{pq}\),

Branch currents by sequence
\[ I_{pq,1}=\frac{V_{p1}-V_{q1}}{z_1^{pq}}, \qquad I_{pq,2}=\frac{V_{p2}-V_{q2}}{z_2^{pq}}, \qquad I_{pq,0}=\frac{V_{p0}-V_{q0}}{z_0^{pq}} \]

and the three phase currents in that branch are recovered by \(\mathbf{A}\) in the usual way. One warning applies to the zero-sequence part: because delta windings break the zero-sequence network into islands, \(V_{j0}\) is identically zero at every bus outside the island containing the fault, and no residual current flows there at all.

Crossing a delta–star transformer requires care of a different kind. Chapter 23 recorded that the positive-sequence quantities on the high-voltage side lead those on the low-voltage side by \(30^\circ\) while the negative-sequence quantities lag by \(30^\circ\). The two shifts are equal and opposite, so they do not cancel when the sequence components are recombined — they rotate the positive- and negative-sequence phasors in opposite directions, and the phase pattern that emerges on the far side is quite different from the one that went in.

🔑
Crossing a Δ–Y bank
\[ I_{1,\text{HV}} = I_{1,\text{LV}}\,e^{\,j30^\circ}, \qquad I_{2,\text{HV}} = I_{2,\text{LV}}\,e^{-j30^\circ}, \qquad I_{0,\text{HV}} = 0 \]

The zero-sequence current does not cross at all — it circulates in the delta. Example 6 works out the consequence: an earth fault on the star side appears on the delta side as equal and opposite currents in two lines and nothing in the third, which is the current pattern of a line-to-line fault.

Finally, a practical note on measurement. The three line current transformers of a feeder are almost always connected in residual, so that the relay in the common return receives \(I_a+I_b+I_c=3I_{a0}\). That single connection is the reason zero-sequence current is the workhorse quantity of earth-fault protection: it is available directly, without any computation, and it is zero in a healthy balanced circuit no matter how heavily loaded. Everything this chapter computes about \(I_{a0}\) is a prediction about what that one relay will see.

Section 24-9

Worked Examples

1 Line-to-ground fault at generator terminals

Problem. A 20 MVA, 13.8 kV generator with \(X_1=0.20\), \(X_2=0.25\) and \(X_0=0.08\) per unit is running unloaded at rated voltage with its neutral solidly earthed. A bolted line-to-ground fault occurs on phase \(a\) at its terminals. Find the fault current in per unit and in amperes, and the three line-to-ground voltages at the fault.

Solution. The three networks are single branches, so \(Z_1=j0.20\), \(Z_2=j0.25\), \(Z_0=j0.08\) with \(V_f=1.0\angle0^\circ\). Connect them in series:

Sequence and fault currents
\[ I_{a0}=I_{a1}=I_{a2}=\frac{1.0}{j(0.20+0.25+0.08)}=\frac{1.0}{j0.53}=-j1.8868\ \text{pu} \]
\[ I_{fa}=3I_{a0}=-j5.6604\ \text{pu} \]
Conversion to amperes
\[ I_{\text{base}}=\frac{20\times10^{6}}{\sqrt3\times13\,800}=\frac{20\times10^{6}}{23\,903}=836.7\ \text{A} \]
\[ \big|I_{fa}\big| = 5.6604\times836.7 = 4737\ \text{A} \]

For the voltages, substitute the common current into the three network equations:

Sequence voltages at the fault bus
\[ V_{a1}=1.0-(j0.20)(-j1.8868)=1.0-0.3774=0.6226 \]
\[ V_{a2}=-(j0.25)(-j1.8868)=-0.4717, \qquad V_{a0}=-(j0.08)(-j1.8868)=-0.1509 \]
\[ V_{ka}=V_{a0}+V_{a1}+V_{a2}=-0.1509+0.6226-0.4717=0 \;\;\checkmark \]

The faulted phase voltage comes out as zero, which is the check that the bolted condition has been satisfied. Now the healthy phases:

Healthy-phase voltages
\[ V_{kb}=V_{a0}+a^2V_{a1}+aV_{a2} = -0.1509+0.6226\angle240^\circ+0.4717\angle300^\circ \]
\[ = \big(-0.1509-0.3113+0.2358\big)+j\big(-0.5392-0.4085\big) = -0.2264-j0.9477 \]
\[ \big|V_{kb}\big| = \sqrt{0.0513+0.8982}=0.9744\ \text{pu} \quad\text{at}\quad -103.4^\circ \]

By the conjugate symmetry of the whole calculation, \(V_{kc}=0.9744\angle{+103.4^\circ}\). The two healthy phases have fallen slightly, from 1.000 to 0.974 per unit, which the table of Section 24-6 predicts: here \(k=Z_0/Z_1=0.40\), well below the crossover value of unity. In volts, with a base line-to-neutral value of \(13\,800/\sqrt3 = 7967\) V, they stand at 7763 V. The voltage between the two healthy phases, however, has risen: \(|V_{kb}-V_{kc}|=1.895\) pu against the pre-fault \(\sqrt3=1.732\).

2 Line-to-line fault on the same machine

Problem. The generator of Example 1 now suffers a bolted line-to-line fault between phases \(b\) and \(c\). Find the fault current and the three line-to-ground voltages, and compare with the three-phase fault current at the same point.

Solution. The zero-sequence network takes no part. Connect positive against negative:

Sequence currents
\[ I_{a1}=-I_{a2}=\frac{1.0}{j(0.20+0.25)}=\frac{1.0}{j0.45}=-j2.2222\ \text{pu} \]
Phase currents
\[ I_{fb}=\big(a^2-a\big)I_{a1}=\big(-j\sqrt3\big)\big(-j2.2222\big)=-3.8490\ \text{pu} \]
\[ I_{fc}=+3.8490\ \text{pu}, \qquad I_{fa}=0 \]
\[ \big|I_{fb}\big| = 3.8490\times836.7 = 3221\ \text{A} \]

The voltages are unusually clean in this case:

Sequence and phase voltages
\[ V_{a1}=1.0-(j0.20)(-j2.2222)=0.5556, \qquad V_{a2}=-(j0.25)(+j2.2222)=0.5556 \]
\[ V_{ka}=V_{a1}+V_{a2}=1.1111, \qquad V_{kb}=V_{kc}=\big(a^2+a\big)V_{a1}=-V_{a1}=-0.5556 \]

The two faulted phases sit at the same potential, as a bolted short between them requires, so \(V_{kbc}=0\); and the healthy phase has risen to 1.111 per unit. The three-phase fault current at the same terminals is \(1.0/0.20=5.000\) pu, so the ratio is \(3.849/5.000=0.770\). That is below the \(0.866\) of the severity rule because \(X_2\) here exceeds \(X_1\); with \(X_2=X_1\) the ratio would be exactly \(\sqrt3/2\).

3 Double line-to-ground fault, and the full comparison

Problem. The same generator now suffers a bolted double line-to-ground fault on phases \(b\) and \(c\). Find all three sequence currents, the current in each faulted phase, the current into earth, and tabulate all four fault types.

Solution. With \(Z_f=0\) the negative-sequence branch \(j0.25\) and the zero-sequence branch \(j0.08\) hang in parallel across the positive-sequence network:

The parallel combination and the positive-sequence current
\[ \frac{Z_2Z_0}{Z_2+Z_0}=\frac{(j0.25)(j0.08)}{j0.33}=j\frac{0.0200}{0.33}=j0.06061 \]
\[ I_{a1}=\frac{1.0}{j(0.20+0.06061)}=\frac{1.0}{j0.26061}=-j3.8372\ \text{pu} \]
Current division into the two branches
\[ I_{a2}=-I_{a1}\frac{Z_0}{Z_0+Z_2}=j3.8372\times\frac{0.08}{0.33}=j0.9302\ \text{pu} \]
\[ I_{a0}=-I_{a1}\frac{Z_2}{Z_0+Z_2}=j3.8372\times\frac{0.25}{0.33}=j2.9070\ \text{pu} \]
\[ \text{check:}\quad -3.8372+0.9302+2.9070 = 0 \;\;\checkmark \]
Phase and earth currents
\[ I_{fb}=I_{a0}+a^2I_{a1}+aI_{a2} = -4.1287+j4.3605 = 6.005\angle133.4^\circ\ \text{pu} \]
\[ I_{fc}= 4.1287+j4.3605 = 6.005\angle46.6^\circ\ \text{pu} \]
\[ I_{fb}+I_{fc}=3I_{a0}=j8.7209\ \text{pu} \quad\Longrightarrow\quad 8.7209\times836.7=7297\ \text{A into earth} \]

Collecting all four faults at these terminals:

FaultLargest phase current (pu)AmperesEarth current (pu)
Three-phase5.00041840
Line-to-ground5.66047375.660
Line-to-line3.84932210
Double line-to-ground6.00550258.721

At the terminals of a solidly earthed machine — where \(X_0\) is much the smallest of the three sequence reactances — every earth fault exceeds the three-phase fault, and the double line-to-ground fault is the most severe of all, both in phase current and, by a wide margin, in earth current. This is the calculation that sends a designer looking for a neutral earthing impedance, which Example 5 supplies.

4 Faults on a transmission bus, where the ordering reverses

Problem. Use the three Thévenin impedances found in Example 5 of Chapter 23 for bus 2 of the generator–transformer–line system: \(Z_1=j0.3948\), \(Z_2=j0.4448\), \(Z_0=j0.4244\) per unit on a 25 MVA, 66 kV base, with \(V_f=1.0\angle0^\circ\). Find the current for each of the four bolted fault types.

Solution. The base current at 66 kV is

Base current
\[ I_{\text{base}}=\frac{25\times10^{6}}{\sqrt3\times66\,000}=\frac{25\times10^{6}}{114\,315}=218.7\ \text{A} \]
Three-phase and line-to-ground
\[ I_{3\phi}=\frac{1.0}{0.3948}=2.5329\ \text{pu} = 554\ \text{A} \]
\[ I_{LG}=\frac{3.0}{0.3948+0.4448+0.4244}=\frac{3.0}{1.2640}=2.3734\ \text{pu}=519\ \text{A} \]
Line-to-line
\[ \big|I_{LL}\big|=\frac{\sqrt3\times1.0}{0.3948+0.4448}=\frac{1.7321}{0.8396}=2.0629\ \text{pu}=451\ \text{A} \]
Double line-to-ground
\[ \frac{Z_2Z_0}{Z_2+Z_0}=\frac{0.4448\times0.4244}{0.8692}=0.21718 \quad\Longrightarrow\quad I_{a1}=\frac{1.0}{j0.61198}=-j1.6340 \]
\[ I_{a2}=j1.6340\times\frac{0.4244}{0.8692}=j0.7978, \qquad I_{a0}=j1.6340\times\frac{0.4448}{0.8692}=j0.8362 \]
\[ \big|I_{fb}\big|=\big|I_{fc}\big|=2.451\ \text{pu}=536\ \text{A}, \qquad 3I_{a0}=2.509\ \text{pu}=549\ \text{A} \]

The ordering has reversed. Here \(Z_0=j0.4244\) slightly exceeds \(Z_1=j0.3948\), so \(k=1.075\) and the earth fault falls just below the three-phase fault, exactly as the severity rule of Section 24-6 requires. At this bus the breaker must be rated on the three-phase fault; at the generator terminals of Example 3 it must be rated on the double line-to-ground fault. Both calculations are needed, and which one governs is not obvious until \(k\) is computed.

5 Sizing a neutral earthing reactor

Problem. For the generator of Examples 1 to 3 (\(X_1=0.20\), \(X_2=0.25\), \(X_0=0.08\) per unit; 20 MVA, 13.8 kV), find the neutral reactance \(X_n\) that limits the line-to-ground fault current to the three-phase value, and then the value that limits it to 1000 A.

Solution. Earthing the neutral through \(X_n\) adds \(3X_n\) to the zero-sequence branch and leaves \(X_1\) and \(X_2\) untouched, so the three-phase fault current is unchanged at \(1.0/0.20=5.000\) pu. Setting the earth-fault current equal to it,

Matching the three-phase level
\[ \frac{3.0}{0.20+0.25+0.08+3X_n}=5.000 \;\Longrightarrow\; 0.53+3X_n=0.60 \;\Longrightarrow\; X_n=0.02333\ \text{pu} \]
\[ Z_{\text{base}}=\frac{13.8^2}{20}=\frac{190.44}{20}=9.522\ \Omega \;\Longrightarrow\; X_n=0.02333\times9.522=0.222\ \Omega \]

A reactor of a fifth of an ohm is enough to remove the excess. To go further and hold the earth-fault current to 1000 A, first express that limit in per unit using the base current of 836.7 A from Example 1:

Limiting to 1000 A
\[ I_{\text{limit}}=\frac{1000}{836.7}=1.1951\ \text{pu} \]
\[ \frac{3.0}{0.53+3X_n}=1.1951 \;\Longrightarrow\; 0.53+3X_n=2.5102 \;\Longrightarrow\; X_n=0.6601\ \text{pu}=6.285\ \Omega \]

The second reactor is nearly thirty times the first, and it raises \(k=Z_0/Z_1\) from 0.40 to \((0.08+1.980)/0.20=10.3\). The table of Section 24-6 then warns of the price: an earth-fault factor of about 1.53, so the healthy phases will sit at more than half again their normal voltage during an earth fault, and the machine's insulation and surge arresters must be chosen accordingly. Limiting earth-fault current and limiting overvoltage are opposing requirements, and the reactor is where the compromise is struck.

6 An earth fault seen from the other side of a delta–star bank

Problem. A 20 MVA, 33/11 kV transformer is connected \(\Delta\) on the 33 kV side and \(Y\) solidly earthed on the 11 kV side, with a leakage reactance of \(j0.09\) per unit. The 33 kV system behind it has \(Z_1=Z_2=j0.06\) per unit on the same base. A bolted line-to-ground fault occurs on phase \(a\) of the 11 kV bus. Find the fault current on the 11 kV side and the currents in the three 33 kV lines.

Solution. The positive- and negative-sequence paths run from the 33 kV source through the transformer to the 11 kV bus. The zero-sequence path stops at the delta, so it consists of the transformer alone:

Thévenin impedances at the 11 kV bus
\[ Z_1=Z_2=j(0.06+0.09)=j0.15, \qquad Z_0=j0.09 \]
The earth fault on the 11 kV side
\[ I_{a0}=I_{a1}=I_{a2}=\frac{1.0}{j(0.15+0.15+0.09)}=\frac{1.0}{j0.39}=-j2.5641\ \text{pu} \]
\[ I_{fa}=3I_{a0}=-j7.6923\ \text{pu} \]
\[ I_{\text{base},11}=\frac{20\times10^{6}}{\sqrt3\times11\,000}=1049.7\ \text{A} \;\Longrightarrow\; \big|I_{fa}\big|=7.6923\times1049.7=8075\ \text{A} \]

Now cross the transformer. The zero-sequence current circulates in the delta and never reaches a 33 kV line, so \(I_{0,\text{HV}}=0\). The positive-sequence current is advanced by \(30^\circ\) and the negative-sequence current retarded by \(30^\circ\). Writing \(I=2.5641\angle{-90^\circ}\) for the common magnitude,

Sequence currents on the 33 kV side
\[ I_{1,\text{HV}}=I\,e^{\,j30^\circ}=2.5641\angle{-60^\circ}, \qquad I_{2,\text{HV}}=I\,e^{-j30^\circ}=2.5641\angle{-120^\circ}, \qquad I_{0,\text{HV}}=0 \]
Line currents on the 33 kV side
\[ I_A = I_{1,\text{HV}}+I_{2,\text{HV}} = 2.5641\big(\angle{-60^\circ}+\angle{-120^\circ}\big)=2.5641\times2\cos30^\circ\;\angle{-90^\circ}=4.4412\angle{-90^\circ} \]
\[ I_B = a^2I_{1,\text{HV}}+aI_{2,\text{HV}} = 2.5641\big(\angle180^\circ+\angle0^\circ\big)=0 \]
\[ I_C = aI_{1,\text{HV}}+a^2I_{2,\text{HV}} = 2.5641\big(\angle60^\circ+\angle120^\circ\big)=4.4412\angle{+90^\circ}=-I_A \]
In amperes
\[ I_{\text{base},33}=\frac{20\times10^{6}}{\sqrt3\times33\,000}=349.9\ \text{A} \;\Longrightarrow\; \big|I_A\big|=\big|I_C\big|=4.4412\times349.9=1554\ \text{A}, \quad I_B=0 \]

A single-phase earth fault on the star side has produced, on the delta side, equal and opposite currents in two lines and nothing at all in the third — the current signature of a line-to-line fault. In per unit the delta-side current is \(1/\sqrt3\) of the star-side fault current, since \(4.4412/7.6923=0.5774\). A relay on the 33 kV side, seeing no residual current and a two-phase pattern, has no way of telling from magnitudes alone that the fault beyond the transformer involves earth. This is why earth-fault protection must be provided on the earthed side of every delta–star bank, and why transformer differential schemes require the phase compensation that Chapter 36 describes.

Review

Chapter Summary

The method

Transform the fault's terminal conditions; the sequence relations that result are wiring instructions for the three networks.

LG fault

\(I_{a0}=I_{a1}=I_{a2}=V_f/(Z_0+Z_1+Z_2+3Z_f)\); three networks in series; \(I_f=3I_{a0}\).

LL fault

\(I_{a1}=-I_{a2}=V_f/(Z_1+Z_2+Z_f)\); zero-sequence network dead; \(|I_{fb}|=\sqrt3|I_{a1}|\).

LLG fault

\(Z_2\) and \((Z_0+3Z_f)\) in parallel across \(Z_1\); \(I_{a0}+I_{a1}+I_{a2}=0\); earth current \(3I_{a0}\).

The factor 3

\(3Z_f\) and \(3Z_n\) appear because the physical path carries \(3I_{a0}\) while each network carries \(I_{a0}\).

Severity

\(I_{LG}>I_{3\phi}\) exactly when \(Z_0<Z_1\); \(I_{LL}=0.866\,I_{3\phi}\) whenever \(Z_2=Z_1\).

Earthing

Raising \(Z_0\) cuts earth-fault current but raises healthy-phase voltage towards \(\sqrt3\) — the earthing compromise.

Series faults

One conductor open puts the networks in parallel across the break; two open puts them in series.

Practice

Practice Problems

Take \(V_f=1.0\angle0^\circ\) per unit and neglect pre-fault load current unless a problem says otherwise. In every case draw the network interconnection before computing anything, and check at the end that the sequence currents recombine to the phase currents the fault type demands.

  1. A 30 MVA, 11 kV generator has \(X_1=0.22\), \(X_2=0.26\) and \(X_0=0.07\) per unit with its neutral solidly earthed. Find the current for a bolted line-to-ground fault at its terminals, in per unit and in amperes, and the two healthy-phase voltages.
  2. Repeat Problem 1 for a bolted line-to-line fault and for a bolted double line-to-ground fault, and tabulate all four fault currents including the three-phase value. Which fault governs the breaker rating?
  3. The line-to-ground fault of Problem 1 occurs through an arc resistance of \(0.5\ \Omega\). Recompute the fault current, and state the percentage by which the arc reduces it.
  4. At a 132 kV bus the sequence Thévenin impedances are \(Z_1=j0.18\), \(Z_2=j0.20\) and \(Z_0=j0.55\) per unit on 100 MVA. Compute all four bolted fault currents in per unit and in amperes, and verify the severity rule of Section 24-6.
  5. For the generator of Problem 1, find the neutral earthing resistance in ohms that limits the line-to-ground fault current to 500 A, and estimate the resulting earth-fault factor.
  6. A \(\Delta\)–\(Y_g\) transformer, \(j0.10\) per unit, connects a 132 kV system (\(Z_1=Z_2=j0.05\) per unit) to a 33 kV bus. A bolted line-to-ground fault occurs on the 33 kV bus. Find the 33 kV fault current and the three 132 kV line currents, and explain why one of them is zero.
  7. A double line-to-ground fault occurs through \(Z_f=j0.05\) per unit at a bus where \(Z_1=j0.25\), \(Z_2=j0.30\) and \(Z_0=j0.20\). Find the three sequence currents, the two faulted-phase currents, and the earth current. Then let \(Z_f\to\infty\) and confirm that the result becomes the line-to-line fault at the same bus.
  8. A line carries \(0.8\angle{-25^\circ}\) per unit before one of its conductors breaks. Across the resulting gap the sequence Thévenin impedances are \(Z_1=Z_2=j0.40\) and \(Z_0=j1.00\) per unit. Find the currents in the two surviving phases and the residual current \(3I_{a0}\), and comment on whether an overcurrent relay would detect the condition.
Tip: every answer in this chapter can be checked without repeating the algebra. Recombine the sequence currents and confirm that the phases the fault did not involve carry zero; add the sequence voltages and confirm that the faulted phase satisfies its own terminal condition; and compare the magnitude against the three-phase fault current, which should be within a factor of \(0.7\) to \(1.5\) of it for any realistic \(Z_0/Z_1\). A result that fails one of those three tests is wrong, and finding out which one it fails usually identifies the error.