Part 4 · Chapter 16

Single-Phase Voltage Source Inverters

Part 3 was, in the end, about one number — get the average right and make the ripple small. An inverter's output averages zero, so that whole way of thinking has to be replaced. What matters now is the shape: how closely a waveform assembled from two or three voltage levels can imitate a sine, and what it costs to get closer.

Power Electronics Prof. Mithun Mondal Reading time ≈ 55 min
Where this sits
Part 4 · DC–AC Converters
Chapter 16 of 30 — the first of Part 4
You should already know
The half-bridge leg, dead time and shoot-through from Chapter 11, device switching from Chapter 5, and Fourier series of a periodic waveform.
By the end you can
Derive the harmonic spectrum of a square and quasi-square wave, choose a pulse width to eliminate a chosen harmonic, and work out which device conducts at every instant with an inductive load.
Time
≈ 55 min reading · ≈ 50 min problems
i What you'll learn
  • Why turning DC into AC is a fundamentally different problem from every converter in Part 3 — you must synthesise a shape, not an average.
  • The half-bridge inverter, its two output levels, and why it wastes half the supply.
  • The full-bridge (H-bridge), which doubles the output and unlocks a third level.
  • The Fourier series of a square wave, \( V_1 = \dfrac{4V_s}{\pi\sqrt2} \), and why its THD is 48.3% no matter what you do.
  • Quasi-square-wave control: how one pulse-width choice both regulates the output and annihilates a chosen harmonic.
  • Why an inverter feeding an inductive load needs feedback diodes, and how to work out which of the four devices is conducting at any instant.
  • Why square-wave inverters survive at all, given that Chapter 18's PWM is better in almost every way.
Section 16-1

A Different Kind of Problem

Part 3 was, in the end, about one number. Every converter in it produced a DC output, and the whole design problem was to get the average right and to make the ripple small enough to ignore.

An inverter cannot be described that way. Its output has an average of zero. What matters is the shape: the amplitude, the frequency, and how closely the waveform resembles a sine.

What changes when the output must be AC
QuestionDC–DC converter (Part 3)Inverter (Part 4)
What is controlledOutput averageFundamental amplitude and frequency
What "ripple" meansDeviation from a constantEverything that is not the fundamental — the harmonics
Quality measure\(\Delta V_o / V_o\)Total harmonic distortion
What the filter must doPass DC, block \(f_s\)Pass \(f_1\), block everything above it — a much harder job
Current directionOne way (unless four-quadrant)Reverses every half cycle, always
Device count1 or 2 typical2 minimum, 4 usual, 6 for three phase
Section recap. An inverter's output averages zero, so the design target moves from a number to a shape. Quality is measured as harmonic distortion, the current reverses every half cycle by definition, and the two routes to a clean output are a big filter or faster switching.
Section 16-2

The Half-Bridge and the Full-Bridge

The simplest circuit that can produce AC from DC is one you have already met. It is the half-bridge leg of Chapter 11's Class C chopper, with the load connected to a mid-point instead of to a rail.

HALF-BRIDGE · 2 LEVELS FULL-BRIDGE · 3 LEVELS + 0 S₁ S₂ Z +V/2 −V/2 S₁ S₂ S₃ S₄ Z +V 0 −V
The half-bridge produces \( \pm V_s/2 \); the full bridge produces \( \pm V_s \) and, uniquely, a genuine zero. That third level is what makes pulse-width control possible.
🔑
Square-wave output, half-bridge and full-bridge
\[ \text{Half-bridge: } V_{o(rms)} = \frac{V_s}{2}, \quad V_{1(rms)} = \frac{2V_s}{\pi\sqrt2} = 0.45\,V_s \] \[ \text{Full-bridge: } V_{o(rms)} = V_s, \quad V_{1(rms)} = \frac{4V_s}{\pi\sqrt2} = 0.90\,V_s \]

The full bridge doubles both figures for twice the devices — and since the output power goes as \( V^2 \), it delivers four times the power from the same DC supply.

Section recap. The half-bridge gives \( \pm V_s/2 \) from two switches but forces the load current through the splitter capacitors. The full bridge gives \( \pm V_s \) from four — and, more importantly, a genuine zero level that makes amplitude control, harmonic elimination and freewheeling possible.
Section 16-3

The Harmonics You Cannot Avoid

A square wave is not a sine wave, and Fourier tells us exactly how far short it falls. The result is worth deriving once, because every subsequent improvement in Part 4 is measured against it.

  1. Exploit the symmetry before integrating The square wave is an odd function with half-wave symmetry — the second half cycle is the negative of the first. Odd symmetry kills every cosine term; half-wave symmetry kills every even harmonic. So only odd sine terms survive, and we need one integral.
  2. Integrate over the positive half cycle
    Working
    \[ b_n = \frac{2}{\pi}\int_0^{\pi} V_s\sin n\theta\,d\theta = \frac{2V_s}{n\pi}\bigl[-\cos n\theta\bigr]_0^{\pi} = \frac{2V_s}{n\pi}(1 - \cos n\pi) \]
  3. Evaluate for odd and even \(n\) For odd \( n \), \( \cos n\pi = -1 \), so \( b_n = 4V_s/(n\pi) \). For even \( n \), \( \cos n\pi = +1 \), so \( b_n = 0 \), confirming the symmetry argument.
    Result
    \[ v_o(\theta) = \frac{4V_s}{\pi}\left(\sin\theta + \frac{1}{3}\sin3\theta + \frac{1}{5}\sin5\theta + \frac{1}{7}\sin7\theta + \cdots\right) \]
  4. Read off the two facts that matter The fundamental peak is \( 4V_s/\pi = 1.273\,V_s \) — 27% larger than the DC supply, which surprises people. And each harmonic falls only as \( 1/n \), which is a very slow decay.
🔑
Square wave: fundamental and distortion
\[ V_{1(rms)} = \frac{4V_s}{\pi\sqrt2} = 0.900\,V_s, \qquad \text{THD} = \frac{\sqrt{V_{rms}^2 - V_1^2}}{V_1} = \sqrt{\frac{\pi^2}{8} - 1} = 48.3\% \]

That 48.3% is a property of the shape alone. It does not depend on the supply voltage, the frequency, the load or the devices — a square wave is a square wave.

Section recap. A square wave's spectrum is \( 4V_s/n\pi \) for odd \( n \) only: fundamental 27% above the supply, harmonics decaying as \( 1/n \), and a THD of 48.3% fixed by the shape. Removing the 3rd and 5th still leaves 24%.
Section 16-4

Quasi-Square Wave: One Choice, Two Jobs

The full bridge's zero state now earns its keep. Instead of switching straight from \( +V_s \) to \( -V_s \), hold the output at zero for an interval at each end of the half cycle.

Let the output be \( +V_s \) from \( \alpha \) to \( \pi - \alpha \), zero on either side, and \( -V_s \) from \( \pi + \alpha \) to \( 2\pi - \alpha \). The conduction angle is then \( \delta = \pi - 2\alpha \).

  1. Redo the Fourier integral with the new limits
    Working
    \[ b_n = \frac{2}{\pi}\int_{\alpha}^{\pi-\alpha} V_s\sin n\theta\,d\theta = \frac{2V_s}{n\pi}\bigl[\cos n\alpha - \cos n(\pi-\alpha)\bigr] \]
  2. Simplify for odd \(n\) For odd \( n \), \( \cos n(\pi - \alpha) = -\cos n\alpha \), so the bracket becomes \( 2\cos n\alpha \):
    Result
    \[ b_n = \frac{4V_s}{n\pi}\cos n\alpha \]
    At \( \alpha = 0 \) this collapses to the square wave, as it must.
  3. Read what \(\alpha\) now controls The fundamental is \( (4V_s/\pi)\cos\alpha \), so raising \( \alpha \) reduces the output — amplitude control without touching the DC link.
  4. Notice the second, free consequence \( b_n = 0 \) whenever \( \cos n\alpha = 0 \), that is when \( n\alpha = 90^\circ \). So choosing \( \alpha = 90^\circ/n \) annihilates the \(n\)th harmonic completely.
    The classic case
    \[ \alpha = 30^\circ \;\Longrightarrow\; \cos 3\alpha = \cos 90^\circ = 0 \;\Longrightarrow\; \text{no third harmonic} \]
🔑
Quasi-square wave
\[ V_{n(rms)} = \frac{4V_s}{n\pi\sqrt2}\cos n\alpha, \qquad V_{o(rms)} = V_s\sqrt{\frac{\pi - 2\alpha}{\pi}} = V_s\sqrt{\frac{\delta}{\pi}} \]

\( \alpha = 90^\circ/n \) removes the \( n \)th harmonic. \( \alpha = 30^\circ \) removes the third — and, because a 120° conduction angle also improves the shape, it lowers the total distortion from 48.3% to 31.1% at the same time.

Interactive · pulse width, spectrum and distortion

A full-bridge inverter with a zero interval of half-width \( \alpha \) at each end of the half cycle. Watch the waveform and its harmonic spectrum together — and find the angles at which a harmonic disappears entirely.

Quasi-square waveform and its harmonic spectrum Above, one cycle of the inverter output: it sits at zero for the angle alpha, rises to plus the supply voltage until 180 degrees minus alpha, returns to zero, then repeats negatively in the second half cycle. A dashed sine shows the fundamental component for comparison. Below, a bar chart of the harmonic amplitudes relative to the fundamental for harmonics 1, 3, 5, 7, 9, 11 and 13. As alpha increases the fundamental shrinks and individual harmonics pass through zero: the third vanishes at 30 degrees, the fifth at 18 degrees, and the seventh at about 12.9 degrees. +V_s −V_s ωt one cycle · dashed = fundamental 100% 0
Fundamental V10.900 Vs
Total RMS1.000 Vs
THD48.3%
Harmonic nullednone

Section recap. Holding the output at zero for \( \alpha \) at each end of the half cycle gives \( b_n = (4V_s/n\pi)\cos n\alpha \). One angle does two jobs: it scales the fundamental by \( \cos\alpha \) and nulls the \( n \)th harmonic when \( \alpha = 90^\circ/n \). More angles null more harmonics — selective harmonic elimination.
Section 16-5

Which Device Is Actually Conducting

Everything above concerned the output voltage, which the switching pattern sets directly. The current is set by the load, and with an inductive load it lags — which means that for part of every half cycle, the voltage and current have opposite signs.

During those intervals the load is returning energy to the DC link, and the transistors cannot carry it. Something else must.

Device conduction over one cycle, lagging load, full bridge
IntervalOutput voltageLoad currentConductingPower flow
\(0\) to \(\varphi\)\(+V_s\)Negative\(D_1, D_4\)Load → DC link
\(\varphi\) to \(\pi\)\(+V_s\)Positive\(T_1, T_4\)DC link → load
\(\pi\) to \(\pi+\varphi\)\(-V_s\)Positive\(D_2, D_3\)Load → DC link
\(\pi+\varphi\) to \(2\pi\)\(-V_s\)Negative\(T_2, T_3\)DC link → load
Section recap. With a lagging load the current and voltage disagree in sign for \( \varphi \) radians of each half cycle, and the feedback diodes carry that current back into the DC link. They need the same ratings as the transistors plus fast recovery. Dead time, harmless in a chopper, produces 5th and 7th harmonics and low-speed torque ripple here.
Section 16-6

Why Square-Wave Inverters Still Exist

Chapter 18's PWM is better on distortion, better on filter size and better on control. It would be reasonable to conclude that square-wave inversion is a historical curiosity. It is not, and the reasons are worth stating because they recur throughout Parts 4 to 7.

Square wave against PWM
CriterionSquare / quasi-squarePWM (Ch. 18)
Switchings per cycle22 × (carrier ratio), often 100–400
Switching lossNegligibleOften the dominant loss
DC link utilisation\(4V_s/\pi = 1.27V_s\) peak\(V_s\) peak (linear region)
THD before filtering48.3%Low-order harmonics near zero
Harmonic frequencies3rd, 5th, 7th — near the fundamentalNear \(f_c\), easy to filter
Output filter sizeLargeSmall
Amplitude controlVia \(\alpha\), limited rangeContinuous and fast
Control complexityTrivialRequires a modulator
Section recap. Square-wave operation loses on every quality measure and wins on two — switching loss and DC link utilisation. That keeps it alive at the very top of the power range, where switching cannot be afforded, and at the very bottom, where the 27% extra output is worth more than the waveform.
Section 16-7

Worked Examples

1 Square-wave inverter feeding an RL load

Problem. A single-phase full-bridge inverter with \( V_s = 200 \) V feeds \( R = 10\ \Omega \), \( L = 25 \) mH at 50 Hz. Find the fundamental output voltage, the fundamental current, the third and fifth harmonic currents, and the total RMS current.

Voltage harmonics
\[ V_{n(rms)} = \frac{4V_s}{n\pi\sqrt2} \;\Longrightarrow\; V_1 = 180.0\ \text{V}, \quad V_3 = 60.0\ \text{V}, \quad V_5 = 36.0\ \text{V} \]
Impedance at each harmonic
\[ Z_n = \sqrt{R^2 + (n\omega L)^2}, \qquad \omega L = 2\pi(50)(0.025) = 7.854\ \Omega \]
\[ Z_1 = \sqrt{100 + 61.7} = 12.72\ \Omega, \quad Z_3 = \sqrt{100 + 555} = 25.6\ \Omega, \quad Z_5 = \sqrt{100 + 1542} = 40.5\ \Omega \]
Harmonic currents
\[ I_1 = \frac{180}{12.72} = 14.15\ \text{A}, \quad I_3 = \frac{60}{25.6} = 2.34\ \text{A}, \quad I_5 = \frac{36}{40.5} = 0.89\ \text{A} \]

Total RMS current, including harmonics up to the 13th:

Working
\[ I_{rms} = \sqrt{14.15^2 + 2.34^2 + 0.89^2 + 0.45^2 + 0.27^2 + 0.18^2 + 0.13^2} = 14.37\ \text{A} \]

Read the result carefully. The voltage THD is 48.3%, but the current THD is only \( \sqrt{14.37^2 - 14.15^2}/14.15 = 17.7\% \).

Why the current is so much cleaner. The inductive load's impedance rises with frequency, so it attenuates each harmonic by roughly \( n \) — and the harmonic voltages were already falling as \( 1/n \). The two effects compound, so harmonic currents fall roughly as \( 1/n^2 \). An inductive load is itself a low-pass filter, and in a motor drive it does most of the filtering for free. This is why motors tolerate inverter output that no measuring instrument would.

2 Choosing a pulse width for two purposes at once

Problem. The inverter of Example 1 must deliver a fundamental of 150 V RMS and eliminate the third harmonic. Can both be done? If not, what would you change?

Take each requirement in turn.

Eliminating the third harmonic
\[ \cos3\alpha = 0 \;\Longrightarrow\; \alpha = 30^\circ \]
The fundamental this forces
\[ V_1 = 0.900\,V_s\cos30^\circ = 0.900(200)(0.866) = 155.9\ \text{V} \]
The angle 150 V would require
\[ \cos\alpha = \frac{150}{180} = 0.833 \;\Longrightarrow\; \alpha = 33.6^\circ \]

So no — one angle cannot serve two masters. \( \alpha = 30^\circ \) gives 155.9 V with no third harmonic; \( \alpha = 33.6^\circ \) gives exactly 150 V but leaves \( \cos(3 \times 33.6^\circ) = -0.174 \), so 17% of the third harmonic returns.

Three ways out, in ascending order of cost:

  1. Accept 155.9 V. A 4% overshoot is often within tolerance, and the clean spectrum is worth more.
  2. Lower the DC link to 192.5 V. Then \( \alpha = 30^\circ \) gives exactly 150 V with no third harmonic. Both requirements met — but only if the DC link is adjustable, which means an extra converter stage.
  3. Use three switching angles. Selective harmonic elimination with \( \alpha_1, \alpha_2, \alpha_3 \) can set the fundamental to 150 V and null two harmonics. More switchings, more loss, and a lookup table — but complete control.

The general lesson. With \( k \) switching angles you have \( k \) degrees of freedom and can impose \( k \) conditions. Counting them before you start saves a great deal of algebra.

3 Rating the devices and the diodes

Problem. A 5 kW single-phase inverter runs from a 400 V link into a load at 0.8 power factor lagging. Find the RMS and peak load current, the fraction of each cycle the diodes conduct, and the ratings for the transistors and diodes.

Load current
\[ V_1 = 0.900(400) = 360\ \text{V (rms)}, \qquad S = \frac{P}{\text{pf}} = \frac{5000}{0.8} = 6250\ \text{VA} \]
\[ I_{rms} = \frac{6250}{360} = 17.4\ \text{A}, \qquad I_{pk} = \sqrt2(17.4) = 24.6\ \text{A} \]
Diode conduction fraction
\[ \varphi = \cos^{-1}(0.8) = 36.9^\circ \;\Longrightarrow\; \frac{\varphi}{180^\circ} = 20.5\% \text{ of every cycle} \]

Ratings.

  • Blocking voltage: the full link, 400 V, plus overshoot from stray inductance at turn-off. Allow 50% and specify 600 V devices.
  • Transistor current: 24.6 A peak, conducting for 79.5% of the cycle. An RMS rating of about 15.5 A per device; specify 30 A parts for thermal margin.
  • Diode current: the same 24.6 A peak, conducting 20.5% of the cycle — an RMS of about 7.9 A. Do not under-rate them: they carry a fifth of the total conduction duty continuously.

Now vary the power factor and watch the split move. At unity power factor the diodes never conduct at all. At 0.5 lagging, \( \varphi = 60^\circ \) so they conduct a third of the time. A drive that must run a lightly loaded motor — where the power factor collapses towards zero — puts nearly half the conduction duty on the diodes, and that is precisely the condition many drives spend most of their life in. Rating the diodes from the full-load power factor is a common and expensive error.

4 How big must the output filter be?

Problem. A 50 Hz square-wave inverter must meet 5% voltage THD at its terminals. Design an \( LC \) filter, and comment on the result.

The third harmonic dominates at 33% of the fundamental, so it must be attenuated to about 4% — a factor of roughly 8 at 150 Hz, while 50 Hz passes essentially unchanged.

Second-order filter response
\[ \left|\frac{V_o}{V_i}\right| = \frac{1}{|1 - (f/f_0)^2|} \;\Longrightarrow\; 8 = \frac{1}{(150/f_0)^2 - 1} \;\Longrightarrow\; f_0 = 141\ \text{Hz} \]
Check the fundamental is not amplified
\[ \text{At } 50\ \text{Hz}: \quad \frac{1}{|1 - (50/141)^2|} = 1.14 \quad\text{— a 14\% rise, acceptable but not negligible} \]
Component values for a 10 Ω load
\[ f_0 = \frac{1}{2\pi\sqrt{LC}} = 141\ \text{Hz} \;\text{with}\; L = 20\ \text{mH} \;\Longrightarrow\; C = 64\ \mu\text{F} \]

Now look at what that means physically. A 20 mH inductor carrying 15 A is a substantial iron-cored component — several kilograms, and comparable in size to the rest of the inverter. The 64 μF capacitor must withstand the full AC output voltage continuously.

And two problems the arithmetic hides:

  1. The cutoff is uncomfortably close to the fundamental. At \( f_0/f_1 = 2.8 \) there is very little margin. Component tolerance or a frequency change could push the resonance towards 50 Hz, where the filter would amplify rather than attenuate.
  2. The resonance needs damping. At \( f_0 = 141 \) Hz, an undamped \( LC \) filter has a sharp peak — and a load transient will ring at that frequency for many cycles.

Compare with PWM. At a 10 kHz carrier the lowest significant harmonic is near 10 kHz, so \( f_0 \) can be 1 kHz — a ratio of 20 to the fundamental, with enormous margin. The inductor becomes about 0.2 mH: a hundred times smaller, a small ferrite part instead of an iron lump.

This single comparison is the strongest argument for PWM, and it is worth carrying into Chapter 18: the filter shrinks roughly as the square of the frequency ratio you push the harmonics to.

Section 16-8

Summary & Formula Sheet

Chapter 16 in five sentences:

  1. An inverter's output averages zero, so the design target is a shape — measured by harmonic distortion rather than ripple.
  2. The full bridge gives twice the half-bridge's output and, more importantly, a third level at zero.
  3. A square wave has a fundamental of \( 4V_s/\pi \) peak, harmonics falling only as \( 1/n \), and a THD of 48.3% fixed by its shape.
  4. A quasi-square wave's angle \( \alpha \) both scales the fundamental by \( \cos\alpha \) and nulls the \( n \)th harmonic at \( \alpha = 90^\circ/n \).
  5. With a lagging load the feedback diodes conduct for \( \varphi/\pi \) of every cycle and need full ratings plus fast recovery.
Formula sheet · Chapter 16
Square wave, harmonic \(n\)odd \(n\) only; peak value
\( V_{n(pk)} = \dfrac{4V_s}{n\pi} \)
Fundamental, full bridgeRMS; note it exceeds \(V_s\)
\( V_1 = \dfrac{4V_s}{\pi\sqrt2} = 0.900\,V_s \)
Fundamental, half bridgeexactly half the full bridge
\( V_1 = \dfrac{2V_s}{\pi\sqrt2} = 0.450\,V_s \)
Square-wave THDa property of the shape alone
\( \text{THD} = \sqrt{\dfrac{\pi^2}{8} - 1} = 48.3\% \)
Quasi-square, harmonic \(n\)\(\alpha\) = zero half-width
\( V_{n(pk)} = \dfrac{4V_s}{n\pi}\cos n\alpha \)
Quasi-square RMS\(\delta = \pi - 2\alpha\) is the conduction angle
\( V_{o(rms)} = V_s\sqrt{\dfrac{\delta}{\pi}} \)
Harmonic elimination angle\(\alpha = 30^\circ\) removes the 3rd
\( \alpha = \dfrac{90^\circ}{n} \)
Harmonic current, RL loadfalls roughly as \(1/n^2\)
\( I_n = \dfrac{V_n}{\sqrt{R^2 + (n\omega L)^2}} \)
Total harmonic distortionvoltage or current
\( \text{THD} = \dfrac{\sqrt{X_{rms}^2 - X_1^2}}{X_1} \)
Diode conduction fraction\(\varphi\) = load phase angle
\( \dfrac{t_{diode}}{T/2} = \dfrac{\varphi}{\pi} \)
Dead-time voltage errorproduces 5th and 7th harmonics
\( \Delta V \approx V_s\dfrac{t_{dead}}{T_s} \)
SHE Fourier coefficient\(k\) angles null \(k-1\) harmonics
\( b_n = \dfrac{4V_s}{n\pi}\Bigl(1 + 2\sum_{i=1}^{k}(-1)^i\cos n\alpha_i\Bigr) \)

Key terms

Inverter
A converter producing AC of controllable amplitude and frequency from a DC source.
Voltage source inverter (VSI)
An inverter fed from a stiff DC voltage — a capacitor-supported link. The output voltage is imposed; the current follows the load.
Half-bridge / full-bridge
Two switches producing \(\pm V_s/2\), or four producing \(\pm V_s\) and zero.
Quasi-square wave
A three-level output with a zero interval of half-width \(\alpha\) at each end of the half cycle. Also sold as "modified sine wave".
Total harmonic distortion (THD)
The RMS of everything that is not the fundamental, divided by the fundamental.
Triplen harmonics
The 3rd, 9th, 15th and so on. In phase in all three legs of a three-phase system, so they cancel between lines.
Selective harmonic elimination (SHE)
Choosing several switching angles to null several chosen harmonics while setting the fundamental. Solved offline and tabulated.
Feedback (antiparallel) diode
The diode across each switch that returns reactive load current to the DC link. Needs full ratings and fast recovery.
Dead time
The interval when both devices of a leg are off. Prevents shoot-through; distorts the inverter output.
DC link utilisation
How much fundamental output a modulation scheme extracts from a given DC voltage. Square wave is the best at \(1.27V_s\) peak.
Check yourself

Test Yourself

Chapter 16 · six questions answers hidden until you ask
A square-wave inverter's fundamental is 1.27 times the DC supply. Where does the extra voltage come from — is this not free energy?

No. The fundamental component exceeds the supply, but the waveform never does. There is no violation because the two are different quantities.

What Fourier is actually saying. The square wave equals a sum of sinusoids:

\[ v_o = \frac{4V_s}{\pi}\left(\sin\theta + \frac{1}{3}\sin3\theta + \frac{1}{5}\sin5\theta + \cdots\right) \]

The first term has a peak of \( 1.273V_s \) — but the higher terms, at \( \theta = 90^\circ \), are negative and subtract from it. The sum is exactly \( V_s \), as it must be. Evaluate: \( 1.273(1 - 1/3 + 1/5 - 1/7 + \cdots) = 1.273 \times \pi/4 = 1.000 \). ✓

Check the energy too. The total RMS is \( V_s \), so the total power into a resistor is \( V_s^2/R \). The fundamental alone would give \( (0.9V_s)^2/R = 0.81V_s^2/R \), so the harmonics carry the remaining 19%. Nothing has been created.

Why the 27% is nevertheless a genuine engineering advantage. If the load responds only to the fundamental — a motor, a transformer, a filtered supply — then that is the component that does the work. From a fixed battery, square-wave operation delivers 27% more useful fundamental than sinusoidal PWM can in its linear region.

And this is why over-modulation exists. A PWM drive that needs more output than the linear region allows is deliberately pushed towards square wave, gaining amplitude at the cost of low-order harmonics. Every field-weakening motor drive does this at high speed. Chapter 18 treats it properly.

Why can a half-bridge inverter not produce zero volts across its load, when a full bridge can?

Because one leg has only two states, and the load is referenced to a fixed point.

The half-bridge. The load sits between the leg's mid-point and the capacitor mid-point. The capacitor mid-point is fixed at \( V_s/2 \). The leg's output is either \( V_s \) or 0. So the load sees either \( +V_s/2 \) or \( -V_s/2 \) — two values, and neither is zero. Turning both switches off does not help: the load current then flows through a diode, which still clamps the output to one rail or the other.

The full bridge. The load sits between two leg mid-points, each of which can be \( V_s \) or 0. Four combinations, three distinct differences: \( +V_s \), \( 0 \) (twice), \( -V_s \).

The general rule this illustrates: a converter's output levels come from the number of distinct differences its switching states can produce, not from the number of states. Two legs of two states give three levels, not four, because two of the states are degenerate.

Why the degeneracy is useful rather than wasteful. The two zero states — both legs high, or both legs low — are electrically identical at the load but use different devices. A modulator can alternate between them to share the conduction duty and equalise device temperatures. Space vector modulation (Chapter 19) makes this choice explicitly, and it is one of the things that makes SVM better than naive carrier PWM.

And the extension. Three legs of two states give \( 2^3 = 8 \) states but only 7 distinct vectors, because two are zero. That is the basis of the entire three-phase inverter of Chapter 17.

Why does eliminating the third harmonic also reduce total distortion, when the theory only promised to remove one component?

Because the third harmonic was by far the largest, and because a 120° conduction angle happens to be a better shape overall.

The dominant term is removed. In a square wave the third carries 33% of the fundamental — more than every harmonic above the ninth combined. Removing it takes the THD from 48.3% down to about 35% on that account alone.

But the measured figure is 31.1%, which is better still. The extra improvement comes from the shape change. At \( \alpha = 30^\circ \), every harmonic is scaled by \( \cos n\alpha \), and several of those factors are small:

  • 3rd: \( \cos 90^\circ = 0 \) — eliminated.
  • 5th: \( \cos 150^\circ = -0.866 \) — barely reduced.
  • 7th: \( \cos 210^\circ = -0.866 \) — barely reduced.
  • 9th: \( \cos 270^\circ = 0 \) — also eliminated.
  • 15th, 21st: also nulled, since \( \cos n\alpha = 0 \) whenever \( n \) is an odd multiple of 3.

So \( \alpha = 30^\circ \) removes the entire triplen family, not just the third. That is why it does so much better than one elimination would suggest.

The catch, stated fairly. The fundamental also fell, from \( 0.900V_s \) to \( 0.779V_s \) — 13.4% less output. THD is a ratio, so part of the improvement is the denominator shrinking rather than the numerator. Judged on absolute harmonic content the gain is real but smaller than the headline suggests.

Which is the honest way to state the trade: \( \alpha = 30^\circ \) buys a much cleaner spectrum at the cost of 13% of the output. Whether that is a good bargain depends on whether you have DC link voltage to spare.

An inverter drives a motor whose voltage THD measures 48% but whose current THD is under 10%. Is the instrument faulty?

No — both readings are correct, and the difference is one of the most useful facts in drive engineering.

The load filters the harmonics. A motor is essentially \( R + j\omega L \), so its impedance rises with frequency:

\[ I_n = \frac{V_n}{\sqrt{R^2 + (n\omega L)^2}} \]

At high \( n \) this is approximately \( V_n/(n\omega L) \). The harmonic voltages already fall as \( 1/n \), so the currents fall as \( 1/n^2 \).

Put numbers on it. With \( R = 2\ \Omega \) and \( \omega L = 10\ \Omega \):

  • Fundamental: \( V_1 = 100\% \), \( Z_1 = 10.2\ \Omega \), \( I_1 = 9.8 \) units.
  • 5th: \( V_5 = 20\% \), \( Z_5 = 50\ \Omega \), \( I_5 = 0.40 \) units — 4% of the fundamental current, not 20%.
  • 7th: \( V_7 = 14\% \), \( Z_7 = 70\ \Omega \), \( I_7 = 0.20 \) units — 2%.

Summing gives a current THD around 5%, against a voltage THD of 48%.

Why this matters practically. Torque is produced by current, not voltage, so a motor fed a square wave produces torque that is much smoother than the voltage waveform implies. It is the main reason square-wave and six-step drives were viable for decades.

And the three caveats that stop this being a free pass:

  1. Harmonic currents still cause \( I^2R \) heating without producing useful torque. A 5% current THD is about 0.25% extra loss — small, but it accumulates.
  2. The 5th harmonic produces a negative-sequence field, so it makes a braking torque that pulsates at six times the fundamental. Audible, and hard on gearboxes.
  3. The voltage harmonics still stress the insulation, regardless of how little current flows. Fast switching edges on long motor cables cause reflections that can double the terminal voltage — a well-known cause of premature winding failure.
A designer sets the dead time to 5 μs "for safety" in a 20 kHz inverter. What have they done?

Given away 10% of the output voltage and introduced serious low-order distortion, in exchange for margin they almost certainly did not need.

The arithmetic. At 20 kHz the switching period is 50 μs. Dead time occurs at every transition, twice per period, so 10 μs of every 50 is lost — 20% of the switching period, and a voltage error of up to 10% of the DC link.

What that does to the output:

  • Lost amplitude. The maximum achievable fundamental falls by about 10%, so the DC link must be raised or the drive derated.
  • 5th and 7th harmonics. The error's sign follows the current's sign, so it is a square wave at the fundamental frequency — whose spectrum is exactly the low-order harmonics that PWM existed to avoid. Typical figures are 3–5% each.
  • Low-speed torque ripple. At 10% of rated speed the commanded voltage is about 10% of the link, so a 10% error is a 100% error. Motors run visibly roughly, and some will not start at all.
  • Zero-crossing clamping. Near a current zero the sign is ambiguous, so the compensation cannot decide and the current flattens — a distinctive distortion that shows up clearly on a current probe.

What the dead time should actually have been. Set it from the devices: turn-off delay plus fall time plus the gate-driver's propagation mismatch, with perhaps 50% margin. A modern 600 V IGBT needs 1–2 μs; a SiC MOSFET needs 100–200 ns. 5 μs is appropriate for a large, slow, high-voltage IGBT and nothing else.

Why the mistake is so common. Excess dead time never causes a visible failure — it causes a slightly weak, slightly rough drive that passes every functional test. Shoot-through, by contrast, destroys the module instantly. The asymmetry of consequences pushes designers towards excess, and only measurement corrects it.

The right approach: measure the actual device turn-off at the worst-case temperature and current, set the dead time from that, and add dead-time compensation in the modulator to cancel the residue.

Given that PWM is better in almost every way, why are millions of square-wave inverters still sold each year?

Because "better" is measured against requirements, and two of the square wave's properties are exactly what some applications need.

1. DC link utilisation — the argument at the bottom of the market. A square wave produces \( 4V_s/\pi = 1.27V_s \) peak. Sinusoidal PWM in its linear region produces \( V_s \). For a 12 V battery inverter that is the difference between 15.3 V and 12 V of fundamental peak — 27% more output from the same battery. For a camping inverter running a fan and some lights, that is worth more than waveform purity, and the bill of materials is a fraction of a PWM design's.

2. Switching loss — the argument at the top. Switching energy scales with \( VI \). At 3 kV and 2 kA, one switching event costs several joules. Square wave at 50 Hz costs 100 events per second; PWM at 5 kHz costs 10,000. At those ratings the second is thermally impossible.

This is why HVDC valves, large traction converters and grid-scale equipment do not use conventional PWM. They use square wave with many series levels, or selective harmonic elimination with a handful of angles — getting a good waveform from a very small switching budget. That is precisely what Chapter 20's multilevel inverters are for.

The shape of the market that results:

  • Below ~1 kW: quasi-square, because cost and battery utilisation dominate.
  • 1 kW to ~1 MW: PWM, because switching is cheap and waveform quality matters.
  • Above ~1 MW: multilevel with low switching frequency, because switching is expensive again.

The engineering lesson generalises well beyond inverters. A technique that is superior across most of a specification can still lose at the extremes, where a single constraint dominates everything else. Recognising which constraint binds — before choosing the technique — is most of what topology selection is.

Practice

Problems

Three habits for Part 4:

  1. Work in harmonics, not instantaneous values. Find \( V_n \), divide by \( Z_n \), then recombine. It is faster and it shows you where the problem is.
  2. Count your degrees of freedom. \( k \) switching angles impose \( k \) conditions — no more.
  3. Check the current's sign against the voltage's before deciding which device conducts.

Problems 1–5 are direct application; 6–9 need judgement; 10–12 are design questions worth discussing in a tutorial.

  1. A single-phase full-bridge inverter with \( V_s = 300 \) V feeds \( R = 15\ \Omega \), \( L = 40 \) mH at 50 Hz. Find \( V_1 \), \( V_3 \), \( V_5 \), the corresponding currents, and the total RMS current including harmonics to the 11th.
  2. For the inverter of Problem 1, compute the voltage THD and the current THD, and explain the difference in one sentence.
  3. A quasi-square-wave inverter runs at \( \alpha = 20^\circ \) from a 240 V link. Find the RMS output voltage, the fundamental, and the amplitude of the 3rd, 5th and 7th harmonics relative to the fundamental.
  4. Find the value of \( \alpha \) that eliminates the fifth harmonic, and state the fundamental output it gives from a 400 V link. Which other harmonics are nulled at the same angle?
  5. A half-bridge inverter delivers 2 kW at 230 V from a split 650 V link. Find the fundamental, the load current, and the RMS current in each splitter capacitor.
  6. An inverter feeds a load at 0.6 power factor lagging. Sketch the output voltage and current over one cycle and identify which of \( T_1 \)–\( T_4 \), \( D_1 \)–\( D_4 \) conducts in each interval. Hence find the RMS current in one transistor and one diode if the load current is 20 A RMS.
  7. Show that a quasi-square wave with \( \alpha = 30^\circ \) eliminates all triplen harmonics, and explain why this matters less in a three-phase system than in a single-phase one.
  8. A 20 kHz inverter has 3 μs of dead time. Estimate the fractional voltage loss, and the amplitude of the resulting 5th harmonic as a fraction of the fundamental at 10% of rated speed.
  9. Design an \( LC \) output filter for a 400 Hz, 115 V aircraft inverter running quasi-square at \( \alpha = 30^\circ \), to achieve 5% THD. Compare the inductor size with that required for a 50 Hz inverter of the same rating and comment.
  10. A "modified sine wave" inverter is sold as suitable for all appliances. Analyse its suitability for (a) an incandescent lamp, (b) an induction motor, (c) a laptop charger with a capacitor-input rectifier, and (d) a mains transformer. Justify each answer from the harmonic content.
  11. Selective harmonic elimination with three angles is to null the 5th and 7th harmonics while setting the fundamental to 0.8 of its maximum. Write the three equations that must be solved, explain why they have no closed-form solution, and describe how a controller uses the result at run time.
  12. A 5 MW inverter must choose between square-wave operation at 50 Hz and PWM at 2 kHz. Estimate the switching loss for each given 3.3 kV devices carrying 1.5 kA with 3 μs transitions, and comment on what this implies for the choice of topology at this power level.