Chapter 17 of 30
- Why three legs on one DC link is not three separate inverters — the legs interact through the load's neutral.
- How the eight switching states map to phase and line voltages, and why only seven are distinct.
- The six-step waveform: phase voltage a staircase of \( \pm V_s/3, \pm 2V_s/3 \); line voltage a clean 120° quasi-square.
- Why triplen harmonics cancel between lines, so the line voltage is cleaner than the phase voltage for free.
- The harmonic rule \( n = 6k \pm 1 \) — no 3rd, no 9th, and why the 5th and 7th matter so much in drives.
- 180° versus 120° conduction: 15% more output against immunity from shoot-through.
- What the DC link current looks like, and why the link capacitor is sized by ripple current rather than capacitance.
Three Legs, One Link
A three-phase inverter is three half-bridge legs sharing a DC link, with each leg driving one motor terminal. That is the entire circuit — six transistors, six diodes, one capacitor.
It is tempting to treat it as three independent single-phase inverters. It is not, and the reason is the load's neutral point.
\( S_a, S_b, S_c \in \{0, 1\} \), where 1 means the leg's upper device is on. Note that the line voltage depends on only two legs and takes just three values — while the phase voltage depends on all three and takes four.
Eight States, Seven Vectors
Each leg has two states, so three legs give \( 2^3 = 8 \) combinations. Enumerating them once is worth the effort, because this table is the foundation of both six-step operation and the space vector modulation of Chapter 19.
| State \(S_aS_bS_c\) | Phase \(v_{an}\) | Phase \(v_{bn}\) | Phase \(v_{cn}\) | Line \(v_{ab}\) | Name | Angle |
|---|---|---|---|---|---|---|
| 0 0 0 | 0 | 0 | 0 | 0 | \(V_0\) — zero | — |
| 1 0 0 | \(+2/3\) | \(-1/3\) | \(-1/3\) | \(+1\) | \(V_1\) | 0° |
| 1 1 0 | \(+1/3\) | \(+1/3\) | \(-2/3\) | \(0\) | \(V_2\) | 60° |
| 0 1 0 | \(-1/3\) | \(+2/3\) | \(-1/3\) | \(-1\) | \(V_3\) | 120° |
| 0 1 1 | \(-2/3\) | \(+1/3\) | \(+1/3\) | \(-1\) | \(V_4\) | 180° |
| 0 0 1 | \(-1/3\) | \(-1/3\) | \(+2/3\) | \(0\) | \(V_5\) | 240° |
| 1 0 1 | \(+1/3\) | \(-2/3\) | \(+1/3\) | \(+1\) | \(V_6\) | 300° |
| 1 1 1 | 0 | 0 | 0 | 0 | \(V_7\) — zero | — |
Six-Step Operation
The simplest way to run the inverter is to visit the six active states in order, spending 60° in each. This is six-step or 180° conduction mode — so called because each device is on for a continuous 180° of the cycle.
Reading down the table of Section 17-2 in the order \( V_1 \to V_2 \to V_3 \to V_4 \to V_5 \to V_6 \) gives the two waveforms that define the mode.
Step round one electrical cycle. The bar shows which leg is high; the traces show the resulting phase voltage \( v_{an} \) and line voltage \( v_{ab} \). Notice that the phase voltage has four levels and the line voltage only three.
—
The line voltage is a quasi-square wave of exactly 120° conduction — which is the \( \alpha = 30^\circ \) case of Chapter 16, with its THD of 31.1% and no triplen harmonics at all. The inverter gets that for free, simply from being three-phase.
Where the Triplen Harmonics Went
The phase voltage is a four-level staircase and the line voltage is a three-level quasi-square. The line voltage is visibly cleaner. The reason is one of the more elegant results in power electronics, and it is worth understanding properly rather than accepting as a rule.
- Write the three phase voltages with their phase displacement
Each phase's \( n \)th harmonic is displaced by \( n \times 120^\circ \) from the next, because the fundamental waveforms are displaced by 120°.
Working\[ v_{an,n} = V_n\sin n\theta, \quad v_{bn,n} = V_n\sin n(\theta - 120^\circ), \quad v_{cn,n} = V_n\sin n(\theta - 240^\circ) \]
- Ask what happens when \(n\) is a multiple of 3
For \( n = 3, 9, 15, \ldots \), the displacement \( n \times 120^\circ \) is a whole multiple of 360°:
So the third harmonic is identical in all three phases — in phase, not displaced.Working\[ n = 3: \quad 3 \times 120^\circ = 360^\circ \equiv 0^\circ \]
- Take the difference to get the line voltage
The triplen harmonics subtract to exactly zero between any two lines.Result\[ v_{ab,3} = v_{an,3} - v_{bn,3} = V_3\sin3\theta - V_3\sin3\theta = 0 \]
- Confirm what survives For \( n \) not a multiple of 3, the displacement is a genuine 120° or 240°, so the difference is non-zero — and scaled by \( \sqrt3 \), like the fundamental. Combined with the even-harmonic cancellation from half-wave symmetry, only \( n = 6k \pm 1 \) remains: 5, 7, 11, 13, 17, 19, …
No even harmonics (half-wave symmetry), no triplens (three-phase cancellation). Whatever the modulation scheme, a three-phase inverter with an isolated neutral produces only these.
180° or 120° Conduction
Six-step operation runs each device for 180° of the cycle. The alternative is to run each for 120°, leaving a 60° gap before its complement turns on. Both modes are used, for quite different reasons.
| Property | 180° conduction | 120° conduction |
|---|---|---|
| Devices on at once | 3 (one per leg) | 2 |
| Fundamental phase voltage | \(0.450\,V_s\) | \(0.390\,V_s\) |
| Output relative to 180° | 100% | 86.6% |
| Phase voltage shape | Four-level staircase | Quasi-square, \(\pm V_s/2\) |
| Shoot-through risk | Present — needs dead time | Impossible by construction |
| Terminal voltage during the gap | Always defined | Set by the load's back-EMF |
| Device utilisation | Better | Each device idle a third of the time |
| Typical use | Nearly all AC drives, PWM inverters | BLDC drives, older thyristor inverters |
What the DC Link Sees
Everything so far has looked outward, at the load. Looking inward, at the DC link, reveals the component that most often determines an inverter's size, cost and lifetime.
The link current is whatever the three legs demand: \( i_{dc} = S_a i_a + S_b i_b + S_c i_c \). Because the \( S \) values are switching functions, this is a chopped combination of three sinusoids — and its shape is nothing like DC.
Worked Examples
Problem. A three-phase six-step inverter runs from a 540 V DC link into a star-connected load of \( R = 8\ \Omega \), \( L = 30 \) mH per phase at 50 Hz. Find the line and phase voltages, the fundamental current, and the 5th and 7th harmonic currents.
Compare the two distortion figures. The phase voltage THD is about 31% for the line and higher for the phase, but the current THD is
\[ \text{THD}_i \approx \frac{\sqrt{1.02^2 + 0.52^2 + \cdots}}{19.6} \approx 6\% \]
The load has done most of the filtering, exactly as in Chapter 16. A six-step drive therefore produces reasonably smooth current despite a visibly poor voltage waveform — which is why the mode was viable for decades before PWM became affordable.
Problem. A 400 V, 50 Hz induction motor must be driven at rated voltage by a six-step inverter. What DC link voltage is needed, and what does a standard three-phase rectifier from a 400 V supply actually provide?
So six-step operation works comfortably — 540 V available against 513 V needed, a 5% margin.
Now ask the same question for a PWM inverter, which is what would actually be built:
653 V needed against 540 V available — a 21% shortfall. Plain sinusoidal PWM cannot produce rated motor voltage from a standard rectifier, which is a genuinely awkward result and one that catches people out.
How real drives resolve it, and both methods are standard:
- Third-harmonic injection or space vector modulation, which raise the limit to \( 0.707V_s \) — giving 382 V from a 540 V link, close enough that a small rectifier margin covers it. This is the usual answer, and Chapters 18 and 19 explain why adding a harmonic increases the usable output.
- Over-modulation at the top of the speed range, accepting some low-order harmonics in exchange for amplitude — converging on six-step at maximum speed.
This example is worth remembering, because it explains why every serious drive uses SVM rather than plain sinusoidal PWM: not for elegance, but because plain SPWM simply cannot reach rated voltage.
Problem. A 30 kW drive runs from a 540 V link at 0.85 power factor. Find the phase current, the device peak current, and the ratings for the transistors and diodes. Compare with a single-phase inverter of the same power.
Ratings. Blocking voltage is the full link plus overshoot — specify 1200 V devices for a 540 V link, which is standard practice. Peak current 65.4 A, so a 100 A module gives sensible margin.
Now the comparison that matters. A single-phase inverter delivering the same 30 kW from the same link:
The three-phase inverter needs six devices at 65 A; the single-phase needs four at 103 A. Total device current rating is 392 A against 412 A — almost identical. The three-phase version is not cheaper in silicon.
Where it wins is everywhere else:
- Constant instantaneous power. A balanced three-phase load draws steady power, so the DC link sees no 2nd-harmonic ripple. A single-phase inverter's power pulsates at \( 2f_1 \), forcing a link capacitor several times larger.
- Smaller devices individually, so cheaper packages, easier gate drive and simpler thermal management.
- Better waveform for free — no triplens, as Section 17-4 showed.
- It matches the machine. Three-phase motors dominate above a few kilowatts, so the alternative barely exists.
Problem. An inverter is observed cycling through the states 100, 110, 010, 011, 001, 101 with equal dwell times. Identify the mode, find \( v_{an} \) and \( v_{ab} \) in each interval, and determine the phase sequence.
Step 1 — identify the mode. Six active states in sequence with equal dwell and no zero states is six-step, 180° conduction. Each state lasts 60°.
Step 2 — read the phase voltage. \( +2/3, +1/3, -1/3, -2/3, -1/3, +1/3 \) — the classic six-step staircase, positive for 180° and negative for 180°.
Step 3 — read the line voltage. \( +1, 0, -1, -1, 0, +1 \). Grouping across the cycle boundary, that is \( +1 \) for 120°, \( 0 \) for 60°, \( -1 \) for 120°, \( 0 \) for 60° — a 120° quasi-square wave, as Section 17-3 predicted.
Step 4 — the phase sequence. Leg \( a \) goes high at 0°, leg \( b \) at 60°, leg \( c \) at 180°... but the sequence to check is when each phase voltage peaks. \( v_{an} \) peaks in state 100 (0°–60°), \( v_{bn} \) peaks in 010 (120°–180°), \( v_{cn} \) peaks in 001 (240°–300°). So the order is a, b, c — positive sequence, and the motor turns forwards.
To reverse it, run the state sequence backwards: 100, 101, 001, 011, 010, 110. No hardware change, no contactor — a software decision. This is one of the quiet advantages of an inverter drive over a direct-on-line starter, and it costs nothing.
Summary & Formula Sheet
Chapter 17 in five sentences:
- Three legs share one DC link, and because the load's neutral floats, each phase voltage is its own terminal minus the average of all three.
- Eight switching states give six active vectors 60° apart plus a zero vector reachable two ways — the picture Chapter 19 builds on.
- Six-step operation makes a four-level phase voltage and a three-level line voltage of 0.816 \( V_s \) RMS with 31.1% THD.
- Triplen harmonics are in phase in all three legs and cancel between lines, leaving only \( n = 6k \pm 1 \).
- 180° conduction gives 15.5% more output; 120° conduction cannot shoot through and leaves a phase free for back-EMF sensing.
Key terms
- Six-step operation
- Visiting the six active switching vectors in turn for 60° each. Also called 180° conduction.
- Switching state
- The triple \(S_aS_bS_c\) recording which leg has its upper device on. Eight exist; six are active.
- Zero state / zero vector
- States 000 and 111, in which all three terminals share a rail so no phase sees voltage.
- Floating neutral
- A star point not connected to the inverter. Its potential is the average of the three terminal voltages.
- Triplen harmonics
- Multiples of three. In phase in all three legs, so they cancel between lines and never reach the load.
- Positive / negative sequence
- Whether a harmonic's field rotates with or against the fundamental. 5th is negative, 7th positive, alternating thereafter.
- Sixth-harmonic torque ripple
- The pulsation produced when the 5th and 7th harmonics beat against the fundamental. Worst at low speed.
- 120° conduction
- Each device on for 120° with a 60° gap before its complement. Shoot-through impossible; suits trapezoidal BLDC machines.
- DC link capacitor
- The energy buffer between rectifier and inverter. Selected on RMS ripple current; usually the life-limiting component.
- DC link utilisation
- Fundamental output per volt of link. Six-step 0.780; SVM 0.707; sinusoidal PWM 0.612.
Test Yourself
Each leg produces only two voltage levels. Where do the phase voltage's four levels come from?
From the floating neutral, which makes each phase voltage depend on all three legs rather than one.
The mechanism. With no connection between the load's star point and the inverter, the star point settles wherever the three phase currents sum to zero — for a balanced load, at the average of the three terminal voltages. So
\[ v_{an} = V_s\left(S_a - \frac{S_a + S_b + S_c}{3}\right) \]
Enumerate what that expression can produce. \( S_a \) is 0 or 1, and the sum \( S_a + S_b + S_c \) is 0, 1, 2 or 3:
- \( S_a = 1 \), sum = 1 (only phase a high): \( 1 - 1/3 = +2/3 \)
- \( S_a = 1 \), sum = 2 (a and one other high): \( 1 - 2/3 = +1/3 \)
- \( S_a = 0 \), sum = 1 (a low, one other high): \( 0 - 1/3 = -1/3 \)
- \( S_a = 0 \), sum = 2 (a low, two others high): \( 0 - 2/3 = -2/3 \)
- Sum = 0 or 3 (all agree): \( 0 \) — the zero states
Four non-zero levels plus zero, from legs that have two. The extra levels come from the relationships between legs, not from any leg's own capability.
Test the claim by connecting the neutral. Tie the star point to the DC link's mid-point and \( v_{an} \) becomes simply \( \pm V_s/2 \) — back to two levels, and each phase is now an independent single-phase half-bridge. The four-level behaviour vanishes, and with it the triplen cancellation.
Which is why drives never connect the neutral. Doing so would forfeit the extra levels, forfeit the triplen cancellation, forfeit the ability to inject a third harmonic for extra DC link utilisation (Chapter 18), and add a wire that would carry substantial triplen current. It is a rare case where leaving something unconnected is the whole design.
Why is the line voltage cleaner than the phase voltage, when it is made from the same switching?
Because subtraction removes everything the two phases have in common — and the triplen harmonics are entirely common.
The phase voltage is a four-level staircase containing the fundamental, the 5th, 7th, 11th, 13th and the triplens (3rd, 9th, 15th). It looks stepped and irregular.
The line voltage is \( v_{an} - v_{bn} \). For any harmonic displaced by \( n \times 120^\circ \):
- If \( n \) is a multiple of 3, the displacement is a whole number of full turns, so the two are identical and subtract to zero.
- Otherwise the displacement is a real 120° or 240°, and the difference is \( \sqrt3 \) times either — the same factor as the fundamental.
So the line voltage keeps the useful part and discards the triplens, arriving at a clean three-level 120° quasi-square wave with 31.1% THD against the phase voltage's higher figure.
An important consequence for measurement. If you probe a drive's output phase-to-neutral using the inverter's negative rail as your reference, you will see a two-level square wave with an enormous common-mode component — nothing like what the motor experiences. The motor sees phase-to-its own floating star point, which no oscilloscope terminal is connected to. Always measure line-to-line on a drive output; phase measurements referenced to the DC link are misleading.
And where the triplens actually go. They do not disappear — they appear between the load's star point and the DC link, as a common-mode voltage stepping at the switching frequency. That common-mode voltage drives current through the motor's parasitic capacitance to its frame, and thence through the bearings. Bearing currents are a well-known cause of premature motor failure in inverter drives, and they are exactly the triplens that the line voltage was so pleased to be rid of.
A standard 400 V drive uses a 540 V DC link. Why can plain sinusoidal PWM not produce 400 V from it, when six-step operation can?
Because sinusoidal PWM confines each leg to a sine wave that must fit inside the link voltage, while six-step lets each leg swing fully square.
The two limits.
- Six-step: \( V_{L1} = (\sqrt6/\pi)V_s = 0.780V_s \). From 540 V, that is 421 V — more than enough.
- Sinusoidal PWM, linear region: each leg's reference is a sine of peak at most \( V_s/2 \) about the mid-point, giving \( V_{L1} = (\sqrt3/2\sqrt2)V_s = 0.612V_s \). From 540 V, that is 331 V — a 17% shortfall.
Why square wave beats sine here. A square wave's fundamental is \( 4/\pi = 1.27 \) times its own amplitude, because Fourier packs more fundamental into a square than into a sine of the same peak. SPWM deliberately throws that away in exchange for a clean spectrum.
The two standard resolutions:
- Third-harmonic injection or SVM. Add a triplen component common to all three legs. It flattens each leg's reference so a larger fundamental fits inside the same link — and because it is common to all three, the load never sees it (Section 17-4). The limit rises to \( 0.707V_s \), giving 382 V from 540 V. Essentially free, which is why every commercial drive does it. Chapters 18 and 19.
- Over-modulation. Push the reference beyond the linear region, accepting some low-order harmonics for amplitude, converging on six-step at the extreme. Used at the top of the speed range, where the motor is field-weakened and waveform quality matters less.
Why this is worth remembering. It is the practical reason SVM displaced carrier PWM in drives — not elegance, but the 15% of output voltage that plain SPWM cannot reach. A drive built with naive SPWM would be unable to run a standard motor at rated speed.
Why do the 5th and 7th harmonics both produce torque ripple at six times the fundamental, when they are different frequencies?
Because torque comes from the interaction of two fields, and both harmonics are six times the fundamental away from it — one below, one above.
Set up the rotation. The fundamental field rotates forwards at \( \omega_1 \). Working out each harmonic's sequence from its \( n \times 120^\circ \) displacement:
- 5th: \( 5 \times 120^\circ = 600^\circ \equiv 240^\circ \) — negative sequence, so it rotates backwards at \( 5\omega_1 \).
- 7th: \( 7 \times 120^\circ = 840^\circ \equiv 120^\circ \) — positive sequence, rotating forwards at \( 7\omega_1 \).
Now take the relative speeds seen from the fundamental field:
- 5th relative to fundamental: \( -5\omega_1 - \omega_1 = -6\omega_1 \).
- 7th relative to fundamental: \( +7\omega_1 - \omega_1 = +6\omega_1 \).
Both are \( 6\omega_1 \) — one leading, one lagging. Torque is proportional to the product of the two fields, and a product of components separated by \( 6\omega_1 \) pulsates at exactly that frequency. So both contribute a 6th-harmonic torque ripple, and they add.
The pattern continues. The 11th (negative) and 13th (positive) both sit \( 12\omega_1 \) from the fundamental, giving a 12th-harmonic ripple; the 17th and 19th give an 18th. This is why the ripple spectrum of any three-phase drive is at multiples of six — a direct consequence of the \( 6k \pm 1 \) rule.
Why it matters at low speed. At 5 Hz fundamental the ripple is at 30 Hz, which is slow enough that the rotor's inertia cannot smooth it and squarely inside the mechanical resonance band of many drivetrains. At 50 Hz the ripple is at 300 Hz, where inertia filters it almost completely. Six-step drives are therefore acceptable at speed and unacceptable near standstill — which is precisely the operating region most modern applications care about.
State 000 and state 111 both produce zero output. Does the choice between them matter?
Electrically at the load, no. In every other respect, yes — and modulators exploit the choice deliberately.
1. Switching count, which is the biggest effect. Getting to a zero state from an active state requires switching however many legs disagree:
- From 100 to 000: only leg a changes. One switching.
- From 100 to 111: legs b and c change. Two switchings.
Always choosing the nearer zero state roughly halves the switching loss, for no cost. This is the single largest advantage of space vector modulation over naive carrier PWM.
2. Device thermal balance. In 111 the load current freewheels through the three upper devices; in 000 through the three lower ones. Always choosing one would leave half the module hotter than the other. Alternating shares the duty.
3. Common-mode voltage. The star point relative to the negative rail sits at 0 in state 000 and at \( V_s \) in state 111. Each transition between them is a full-amplitude common-mode step — which drives current through the motor's stray capacitance to the frame and thence through the bearings. Some modulation schemes deliberately restrict which zero states they use to reduce common-mode stepping, at the cost of more switchings. Trading bearing life against efficiency is a real decision in large drives.
4. Neutral-point balance in multilevel converters. In a three-level NPC inverter (Chapter 20), the redundant states charge and discharge the mid-point capacitors differently, so the choice becomes an active control input rather than an optimisation.
The general point. Redundancy in a switching table is not waste. It is a free degree of freedom, and good modulators spend it on switching loss, thermal balance or common-mode voltage — whichever the application is short of.
A drive's DC link capacitor runs hot even though the inverter and motor are correctly sized. Why is the capacitor the component under stress?
Because it absorbs the difference between two currents that neither the rectifier nor the inverter wants to smooth — and it does so continuously, from the inside.
What it is absorbing. The rectifier supplies current in six pulses per mains cycle; the inverter draws current in a pattern set by the switching states and the motor current. The capacitor takes the difference, which contains:
- Switching-frequency ripple from the inverter's commutations — kilohertz, and largely handled by a small film capacitor in parallel.
- Six-times-fundamental ripple from the inverter — 300 Hz at 50 Hz output, and much harder to filter.
- Six-times-mains ripple from the rectifier — also 300 Hz at 50 Hz mains.
The two 300 Hz components beat whenever the motor is not running at exactly mains frequency, producing a low-frequency envelope that raises the RMS ripple well above a naive calculation.
Why heating is the failure mode. The loss is \( I_{ripple}^2 R_{ESR} \), dissipated inside a sealed aluminium can with poor internal conduction. The core runs far hotter than the case, the electrolyte dries out, ESR rises, and the heating accelerates. Life halves for roughly every 10 °C.
Typical magnitude. For a drive delivering \( I_{phase} \), the link ripple current is roughly \( 0.5\,I_{phase} \) — about 25 A RMS for a 50 A machine, continuously.
The remedies, and what each actually buys:
- Parallel more capacitors. Ripple divides between them and \( I^2R \) divides as the square, so doubling the count quarters the heating per unit.
- Add a DC link choke. Reduces the rectifier-side contribution substantially and improves the input power factor at the same time — often the best value change.
- Move to film capacitors. Far better ripple rating and life; larger and dearer per microfarad. Standard in traction.
- Improve cooling. Frequently the cheapest fix, and often overlooked because nobody expects the capacitor to be the hot component.
The lesson worth generalising: the component that fails first is rarely the one handling the most power. It is the one whose life depends most sharply on a stress that was estimated rather than measured.
Problems
Three habits for three-phase inverter problems:
- Start from the switching states, not from a memorised waveform. \( v_{an} = V_s(S_a - \bar S) \) and \( v_{ab} = V_s(S_a - S_b) \) give everything.
- Work line-to-line where you can. The triplens are already gone and the arithmetic is simpler.
- Check the DC link requirement against what a rectifier provides before assuming a modulation scheme will fit.
Problems 1–5 are direct application; 6–9 need judgement; 10–12 are design questions worth discussing in a tutorial.
- A six-step inverter runs from a 600 V link. Find the RMS and fundamental values of the phase and line voltages, and the amplitudes of the 5th, 7th and 11th harmonics relative to the fundamental.
- For the inverter of Problem 1 feeding a star load of \( R = 10\ \Omega \), \( L = 25 \) mH at 50 Hz, find the fundamental, 5th and 7th harmonic currents and the current THD.
- Using \( v_{an} = V_s(S_a - \bar S) \), tabulate all eight switching states and verify that exactly two produce zero output.
- A 415 V, 50 Hz motor is to be driven at rated voltage. Find the DC link required for (a) six-step, (b) sinusoidal PWM, (c) space vector modulation, and state which are achievable from a 415 V diode bridge.
- A 45 kW drive runs from a 650 V link at 0.88 power factor. Find the phase current, the device peak current, and the fraction of each cycle the feedback diodes conduct.
- Show that the 5th harmonic is negative sequence and the 7th positive, and hence explain why both produce torque pulsation at six times the fundamental frequency.
- Explain why a three-phase inverter's DC link needs no second-harmonic filtering while a single-phase inverter of the same power does. Quantify the difference for a 10 kW converter.
- A drive is switched from 180° to 120° conduction with the DC link unchanged. Find the change in fundamental output voltage and in the current each device must carry, and state one application in which the change would be worthwhile.
- The common-mode voltage between a motor's star point and the DC link's negative rail is \( (v_{aN}+v_{bN}+v_{cN})/3 \). Evaluate it for all eight switching states, and explain why transitions between 000 and 111 are the worst case for bearing currents.
- Design the DC link for a 55 kW, 400 V drive: find the link voltage, estimate the capacitor's RMS ripple current, and specify a capacitor bank. State what you would measure to confirm the design in service.
- A six-step drive produces audible 300 Hz noise and measurable torque ripple at 50 Hz output, but runs smoothly at 5 Hz output when a PWM inverter is substituted. Explain both observations from the harmonic analysis of this chapter, and estimate the ripple frequency in each case.
- An engineer proposes connecting the motor's star point to the DC link mid-point "to give a stable reference". Analyse the consequences for phase voltage levels, harmonic content, neutral current, DC link capacitor stress and the achievable output voltage. Recommend for or against with reasons.