Part 3 · Chapter 14

Isolated Converters: Flyback, Forward, Push-Pull, and Bridge

Chapters 12 and 13 solved the arithmetic of DC–DC conversion completely, yet almost every mains-connected supply contains a transformer. Two independent reasons explain it: a safety barrier no non-isolated circuit can provide, and a turns ratio that lets the duty ratio stop straining and start regulating. The price is a core whose flux must return to where it started every single cycle — and every topology here is a different answer to that.

Power Electronics Prof. Mithun Mondal Reading time ≈ 55 min
Where this sits
Part 3 · DC–DC Converters
Chapter 14 of 30
You should already know
Volt-second balance, the buck and buck–boost gains, and the direct/indirect distinction from Chapter 12 and Chapter 13.
By the end you can
Choose an isolated topology from power level and input range, size a turns ratio and duty ratio together, and explain what a snubber or a reset winding is actually doing.
Time
≈ 55 min reading · ≈ 50 min problems
i What you'll learn
  • Why galvanic isolation is a safety requirement rather than an engineering preference, and what a converter must do to provide it.
  • How a turns ratio gives voltage gain for free, releasing the duty ratio to do the regulating.
  • The flyback: an isolated buck–boost, \( V_o = \dfrac{N_s}{N_p}\cdot\dfrac{D}{1-D}V_s \), and why it stops at about 150 W.
  • The forward converter: an isolated buck, \( V_o = \dfrac{N_s}{N_p}D\,V_s \), and why it needs a reset winding and \( D < 0.5 \).
  • Push–pull, half-bridge and full-bridge — how using both halves of the B–H loop doubles what a core can carry.
  • Core saturation, flux walking and leakage inductance: the three failure modes that dominate isolated-converter design.
  • How the feedback crosses the isolation barrier without breaking it.
Section 14-1

Two Reasons for a Transformer

Chapters 12 and 13 solved the arithmetic of DC–DC conversion completely: any voltage ratio can be produced, in either direction, with either polarity. Yet almost every mains-connected power supply in existence contains a transformer. There are two reasons, and they are independent.

1 Safety: galvanic isolation
  • A mains-fed converter has a DC link at roughly 325 V (from 230 V AC) or 170 V (from 120 V AC), and its negative rail is connected to the incoming neutral through the rectifier.
  • Without isolation, the output's "ground" is referenced to the mains. Touch it and you are the return path.
  • Safety standards (IEC 60950, IEC 62368-1, IEC 60601 for medical) therefore mandate a barrier between the mains and anything a user can touch, specified in creepage and clearance distances and in the insulation's dielectric withstand — typically 3 kV AC for one minute, and 4 kV for medical.
  • A transformer provides that barrier by construction: energy crosses as a magnetic field, and no conductive path exists at all.
2 Engineering: the turns ratio does the heavy lifting
  • Chapter 12 established that a single boost stage runs out of usefulness above a gain of about 4 or 5, because \( I_o/(1-D) \) and the resistive correction defeat it.
  • A transformer provides any ratio you can wind, at no cost in duty ratio.
  • So the duty ratio is freed to do what it is good at — regulating over a modest range — while the turns ratio does the gross conversion.
  • Multiple secondaries cost almost nothing, which is why one supply can produce +12 V, +5 V and −12 V from a single switch.

There is a cost, and it is worth stating plainly before the topologies: a transformer's core carries flux, and flux cannot go on increasing forever. Every isolated topology in this chapter is, in part, an answer to the question how does the core get reset before the next cycle? Section 14-6 makes that the organising idea.

Section recap. A transformer provides a safety barrier that no non-isolated topology can, and a turns ratio that lets the duty ratio stay in its comfortable range. The price is a core whose flux must be reset every cycle — which is what distinguishes the topologies from one another.
Section 14-2

The Flyback Converter

The flyback is the isolated buck–boost, and the resemblance is exact: take a buck–boost, split its inductor into two windings on the same core, and use the second winding to feed the output.

Because of that origin, its "transformer" is not really a transformer. It is a coupled inductor — an energy-storage device with two windings — and the distinction matters more than it sounds.

  1. Switch on: the primary is across the source
    Working
    \[ v_{Lp,on} = V_s \quad\text{for a time } DT \]
  2. Switch off: the secondary is across the output The secondary sees \( V_o \). Referred to the primary through the turns ratio \( n = N_p/N_s \):
    Working
    \[ v_{Lp,off} = -n\,V_o \quad\text{for a time } (1-D)T \]
  3. Volt-second balance on the primary
    Result
    \[ V_sDT - nV_o(1-D)T = 0 \;\Longrightarrow\; V_o = \frac{1}{n}\cdot\frac{D}{1-D}V_s = \frac{N_s}{N_p}\cdot\frac{D}{1-D}V_s \]
    The buck–boost gain multiplied by the turns ratio — and with the polarity now a matter of how you wind the secondary rather than a constraint.
  4. Find the switch stress With the switch off, the primary sees the reflected output voltage on top of the supply:
    Working
    \[ V_{sw} = V_s + nV_o + V_{spike} \]
    That last term is the leakage-inductance spike of Section 14-6, and it is not small.
🔑
Flyback converter
\[ V_o = \frac{N_s}{N_p}\cdot\frac{D}{1-D}V_s, \qquad V_{sw} = V_s + \frac{N_p}{N_s}V_o + V_{spike}, \qquad P_o = \frac{1}{2}L_pI_{pk}^2 f \]

That last expression is the one that limits the topology. All the transferred power passes through the core as stored energy, so raising the power means raising \( I_{pk} \) — and the core volume rises with it.

Section recap. The flyback is a buck–boost whose inductor has been split into two windings, so it stores all the transferred energy and needs a gapped core. \( V_o = (N_s/N_p)\cdot D/(1-D)\cdot V_s \), the switch blocks \( V_s + nV_o \) plus a leakage spike, and the topology runs out at 100–150 W.
Section 14-3

The Forward Converter

If the flyback is an isolated buck–boost, the forward converter is an isolated buck — and it inherits all the buck's advantages, including the absence of a right-half-plane zero.

The structural difference from the flyback is that the secondary is wound in the same sense as the primary, so the output diode conducts while the switch is on. Energy flows straight through the transformer rather than being stored in it.

FLYBACK FORWARD SWITCH ON source core stores load SWITCH OFF source core releases load SWITCH ON source passes load SWITCH OFF source reset resets load L_o freewheels Store then release, versus pass straight through and reset
The flyback stores energy in the core and releases it during the off-time; the forward passes it straight through during the on-time and uses the off-time to reset the core.
  1. Switch on: the secondary drives the output inductor The secondary voltage is \( V_s N_s/N_p \), and the output inductor sits between it and \( V_o \):
    Working
    \[ v_{Lo,on} = \frac{N_s}{N_p}V_s - V_o \]
  2. Switch off: the output inductor freewheels
    Working
    \[ v_{Lo,off} = -V_o \]
  3. Volt-second balance on the output inductor
    Result
    \[ V_o = \frac{N_s}{N_p}\,D\,V_s \]
    Exactly the buck's \( V_o = DV_s \), scaled by the turns ratio. So the forward converter inherits the buck's continuous output current, small output capacitor, and — crucially — no right-half-plane zero.

But there is a problem the flyback did not have, and it is fundamental.

The primary's magnetising current still builds up during the on-time — a transformer's magnetising inductance is finite, so some current flows into the core regardless of the load. In the flyback that current was the mechanism, and the off-time discharged it into the secondary. In the forward converter the secondary diode blocks during the off-time, so there is nowhere for the magnetising current to go.

Left alone, the flux would ratchet upward a little every cycle until the core saturates, at which point the primary becomes a short across the supply and the switch is destroyed.

🔑
Forward converter, and the constraint the reset imposes
\[ V_o = \frac{N_s}{N_p}D\,V_s, \qquad D_{max} = \frac{N_r/N_p}{1 + N_r/N_p} \;\xrightarrow{\;N_r = N_p\;}\; D < 0.5 \]

With the usual 1:1 reset winding, the core needs as long to reset as it took to magnetise — so the duty ratio can never exceed 0.5, and the switch must block \( 2V_s \).

Section recap. The forward converter is an isolated buck: \( V_o = (N_s/N_p)DV_s \), continuous output current, no RHP zero. The magnetising current has nowhere to go during the off-time, so a reset winding is needed — and with the usual 1:1 winding it caps \( D \) at 0.5 and forces the switch to block \( 2V_s \).
Section 14-4

Push–Pull, Half-Bridge and Full-Bridge

Both topologies so far drive the core in one direction only. The flux goes up during the on-time and returns to zero during the off-time — so only half of the core's available flux swing is ever used.

The remaining three topologies drive the core in both directions, alternately. That doubles the usable flux swing, which for a given core and frequency roughly doubles the power it can handle.

The five isolated topologies compared
TopologySwitchesSwitch blocksGainCore useTypical power
Flyback1\(V_s + nV_o\) \(\dfrac{N_s}{N_p}\dfrac{D}{1-D}\)One quadrant, gappedup to ~150 W
Forward1\(2V_s\) \(\dfrac{N_s}{N_p}D\)One quadrant100–500 W
Push–pull2\(2V_s\) \(2\dfrac{N_s}{N_p}D\)Two quadrants200 W–1 kW
Half-bridge2\(V_s\) \(\dfrac{N_s}{N_p}D\)Two quadrants200 W–2 kW
Full-bridge4\(V_s\) \(2\dfrac{N_s}{N_p}D\)Two quadrants500 W upward
Interactive · turns ratio and duty ratio together

A 12 V output from a rectified mains DC link. Choose the turns ratio and see what duty ratio each topology then needs across the whole universal-input range — and whether it stays inside its legal limits.

16 : 1
325 V
Duty ratio required at this operating point, and whether it is legal
TopologyGain lawRequired DLimitVerdict
Flyback\(\frac{1}{n}\frac{D}{1-D}\)\(D < 0.75\)
Forward\(\frac{1}{n}D\)\(D < 0.5\)
Half-bridge\(\frac{1}{n}D\)\(D < 0.5\)
Full-bridge\(\frac{2}{n}D\)\(D < 0.5\)
Reflected Vo192 V
Flyback switch517 V
Forward switch650 V
Bridge switch325 V

Section recap. Driving the core in both directions doubles the usable flux swing and removes the need for a reset winding. Push–pull is best at low input voltage; half-bridge halves the switch voltage at the cost of doubled current; full-bridge gives both advantages for four switches, and dominates above about 500 W.
Section 14-5

Feedback Across the Barrier

An isolated converter has a controller on the primary side, at mains potential, and an output on the secondary side that a user may touch. The controller needs to know the output voltage. Connecting a wire between them would defeat the entire purpose.

There are three standard answers, and the choice affects accuracy, cost and safety certification.

Getting the feedback signal across the isolation barrier
MethodHow it worksAccuracyCostUsed in
Optocoupler + shunt reference A TL431 on the secondary compares \(V_o\) with a reference and drives an LED; a phototransistor on the primary receives it ±1% or better Low The overwhelming majority of supplies
Auxiliary winding (primary-side regulation) A third winding reflects the output voltage during the off-time; the controller samples it ±5% Lowest — no optocoupler at all Low-cost chargers, LED drivers
Signal transformer or digital isolator A small pulse transformer or capacitive/magnetic isolator carries a modulated signal Excellent Highest Digitally controlled and high-reliability supplies
Section recap. An optocoupler with a shunt reference is the default and gives ±1%. Primary-side regulation removes it at the cost of ±5%, a slower loop and sampling difficulties. Digital isolators are used where a digital loop or long-term reliability justifies the cost.
Section 14-6

Three Ways an Isolated Converter Fails

Non-isolated converters fail in fairly obvious ways — a device over-rated, a loop unstable, a capacitor cooked. Isolated converters add three failure modes that come from the magnetics, and all three destroy hardware rather than merely degrading performance.

1 Core saturation
  • What happens: the flux density reaches \( B_{sat} \). Above it, permeability collapses, so inductance collapses, so \( di/dt = v/L \) becomes enormous. The primary is effectively a short across the supply.
  • How fast: microseconds. Faster than most over-current protection, which is why cycle-by-cycle current limiting is standard.
  • What causes it: too many volt-seconds — excessive \( D \), excessive \( V_s \), a failed reset, or a core running too hot (\( B_{sat} \) falls with temperature, typically 30% from 25 °C to 100 °C).
  • Design margin: operate at \( B_{max} \approx 0.6\,B_{sat} \) at the highest temperature and worst-case volt-seconds.
2 Flux walking
  • What happens: in a symmetric topology, a small imbalance between the two half-cycles leaves a little residual flux. Next cycle it happens again. The operating point creeps toward one end of the B–H loop until it saturates.
  • What causes it: unequal on-times (gate-drive propagation mismatch), unequal device voltage drops, unequal winding resistances. Differences of a few percent are enough.
  • The classic remedy: a DC blocking capacitor in series with the primary. Any DC component of the applied voltage charges it, and it self-corrects. Standard on half-bridges, where it also serves as one of the splitter capacitors.
  • The better remedy: current-mode control. The controller terminates each pulse on peak current rather than on time, so an asymmetry that would increase the flux automatically shortens that pulse. This is the main reason current-mode control dominates isolated converter design.
3 Leakage inductance
  • What it is: the fraction of the primary's flux that does not link the secondary — typically 1–3% of the magnetising inductance. It is not coupled, so at turn-off its energy has nowhere to go.
  • What happens: \( \tfrac12 L_{lk}I_{pk}^2 \) is dumped into the switch's output capacitance, producing a voltage spike that can exceed the supply several times over, plus severe ringing.
  • The remedy: a snubber or clamp. An RCD clamp catches the spike and dissipates the energy in a resistor. An active clamp recovers it. Either way, the clamp voltage must be set above the reflected output voltage or it will conduct continuously and waste real power.
  • The prevention: winding technique. Interleaving the primary and secondary (half the primary, the secondary, then the other half) can cut leakage by a factor of four — at the cost of higher interwinding capacitance, which worsens common-mode EMI. The two goals oppose each other, and the resolution is one of the genuinely skilled parts of transformer design.
Section recap. Core saturation kills in microseconds and is prevented by volt-second margin; flux walking creeps up over many cycles and is cured by a DC blocking capacitor or current-mode control; leakage inductance produces a turn-off spike that must be clamped above the reflected output voltage, not below it.
Section 14-7

Worked Examples

1 A universal-input flyback

Problem. Design the turns ratio and duty range for a 12 V, 3 A flyback from universal mains (85–265 V AC, so 120–375 V DC), switching at 65 kHz. Then find the switch voltage rating required.

Step 1 — choose the reflected voltage. The usual guideline is \( nV_o \approx 0.5\,V_{s(max)} \), balancing duty ratio against switch stress:

Working
\[ nV_o \approx 0.5(375) = 188\ \text{V} \;\Longrightarrow\; n = \frac{188}{12} \approx 16 \]

Step 2 — find the duty range.

Working
\[ D = \frac{nV_o}{nV_o + V_s} = \frac{192}{192 + V_s} \]
\[ V_s = 120\ \text{V}: \; D = 0.615 \qquad V_s = 375\ \text{V}: \; D = 0.339 \]

Both comfortable — well inside the 0.75 practical ceiling, with margin for transients.

Step 3 — the switch rating.

Working
\[ V_{clamp} = V_{s(max)} + 1.5\,nV_o = 375 + 1.5(192) = 663\ \text{V} \]
\[ V_{rating} \ge 1.2(663) = 796\ \text{V} \;\Longrightarrow\; \text{specify an 800 V MOSFET} \]

Sanity check. 36 W output at 65 kHz means 0.55 mJ per cycle. With \( P_o = \tfrac12 L_pI_{pk}^2f \) and a typical \( I_{pk} \) of 1.5 A, \( L_p \approx 490\ \mu\text{H} \) — an entirely ordinary value for an EF25 core, which confirms the design is in sensible territory.

2 A forward converter and its reset constraint

Problem. A forward converter produces 5 V at 20 A from a 48 V telecom bus (42–56 V), at 200 kHz, with a 1:1 reset winding. Find the turns ratio, the duty range, and the switch rating.

The reset winding caps \( D \) at 0.5, so design the maximum duty ratio at the minimum input, leaving margin — say \( D_{max} = 0.45 \) at \( V_s = 42 \) V.

Working
\[ V_o = \frac{N_s}{N_p}DV_s \;\Longrightarrow\; \frac{N_s}{N_p} = \frac{V_o}{D_{max}V_{s(min)}} = \frac{5}{0.45(42)} = 0.265 \]
\[ \text{Choose } N_p{:}N_s = 4{:}1 \;\Longrightarrow\; N_s/N_p = 0.25 \]
\[ D = \frac{V_o}{(N_s/N_p)V_s} = \frac{5}{0.25\,V_s} = \frac{20}{V_s} \]
\[ V_s = 42\ \text{V}: \; D = 0.476 \qquad V_s = 56\ \text{V}: \; D = 0.357 \]

The low-line case is uncomfortably close to the limit. 0.476 against a hard ceiling of 0.5 leaves only 5% margin — and any transient dip below 42 V, or any extra drop in the diode and windings, will push it over. Two fixes:

  • Use \( N_p{:}N_s = 3.5{:}1 \), giving \( D = 0.42 \) at low line. More margin, at the cost of higher secondary voltage and so a higher-rated output diode.
  • Use an active-clamp forward, which recycles the magnetising energy and permits \( D > 0.5 \). More parts, better efficiency, and the standard answer in modern telecom supplies.

Switch rating. With a 1:1 reset, \( V_{sw} = 2V_{s(max)} = 112 \) V. Add 30% for the leakage spike and ringing and specify a 150 V MOSFET.

3 Why the same supply changes topology at 500 W

Problem. A 12 V supply from a 325 V DC link is required at 100 W, then at 500 W, then at 2 kW. Recommend a topology for each and justify the changes.

100 W — flyback.

  • Fewest parts, no output inductor, cheapest by a clear margin.
  • \( P = \tfrac12 L_pI_{pk}^2f \) with \( I_{pk} \approx 2 \) A is manageable, and the core is small.
  • The output capacitor sees roughly \( I_o\sqrt{D/(1-D)} \approx 6 \) A RMS at 8.3 A output — high but survivable with parallel ceramics.

500 W — two-switch forward, or half-bridge.

  • A flyback here would need \( I_{pk} \approx 10 \) A and store 6 mJ per cycle — a large gapped core, and an output capacitor bank sized by ripple current rather than capacitance.
  • A forward converter passes energy straight through, so the transformer is a genuine transformer: smaller core, no gap, much lower peak currents.
  • The output inductor makes the output current continuous, cutting the capacitor's ripple burden by roughly a factor of five.
  • Two-switch rather than single-switch, because each device then blocks only \( V_s = 325 \) V instead of 650 V — cheaper, faster devices and no reset winding.

2 kW — full-bridge, phase-shifted.

  • The core is driven in both directions, so it carries twice the power of a single-ended design of the same size.
  • Each switch blocks only \( V_s \), and the primary sees the full \( \pm V_s \) — the best combination available.
  • 167 A on the secondary demands synchronous rectification; Schottky diodes would dissipate over 80 W.
  • Phase-shifted control allows zero-voltage switching by using the leakage inductance to resonate with the device capacitance, so switching loss largely disappears — the difference between 92% and 96% efficiency, which at 2 kW is 80 W of heat.

The pattern. Each change is forced by a quantity that grew faster than the topology could accommodate: stored energy first, then device voltage stress, then switching loss. Recognising which one binds is how topology selection is actually done.

4 Diagnosing a saturating transformer

Problem. A push–pull converter works at low power but fails within seconds at full load. The primary current waveform shows a normal ramp that suddenly turns almost vertical near the end of each pulse. What is happening, and what are the candidate causes?

Diagnosis: the core is saturating. The signature is unmistakable — \( di/dt = v/L \), so when \( L \) collapses at \( B_{sat} \), the current rises almost without limit. The "hockey stick" current waveform means saturation and essentially nothing else.

Why it appears only at full load narrows the cause considerably:

  1. Flux walking — the most likely cause in a push–pull. A small asymmetry between the half-cycles biases the operating point, and at high current there is no longer room for the bias. Check by comparing the two switches' on-times on an oscilloscope, and their \( V_{DS(on)} \) drops.
  2. Insufficient volt-second margin. At full load the duty ratio is largest and \( B_{max} \) with it. Verify \( B_{max} = V_sD T/(2N_pA_e) \) against the datasheet \( B_{sat} \) at operating temperature, not at 25 °C.
  3. Thermal. \( B_{sat} \) for ferrite falls roughly 30% from 25 °C to 100 °C. A design with 20% margin on a cold core has none on a hot one — and full load is when it is hot.
  4. Turns count wrong. Worth eliminating early: measure the primary inductance and compare with \( A_L N^2 \).

The fixes, in the order to try them:

  • Add a DC blocking capacitor in series with the primary. Cheapest, and cures flux walking directly.
  • Switch to current-mode control, which terminates each pulse on peak current and so self-corrects asymmetry cycle by cycle.
  • Add turns or a larger core to increase the volt-second capability.

What not to do: raise the current limit so the protection stops tripping. It is reporting a real fault.

Section 14-8

Summary & Formula Sheet

Chapter 14 in five sentences:

  1. A transformer provides a safety barrier no non-isolated topology can, and a turns ratio that frees the duty ratio to regulate rather than to convert.
  2. The flyback is an isolated buck–boost — it stores all the energy, needs a gapped core, and runs out at 100–150 W.
  3. The forward is an isolated buck — energy passes straight through, so no RHP zero and small magnetics, but the magnetising current must be reset, which caps \( D \) at 0.5 with a 1:1 winding.
  4. Driving the core in both directions doubles what it can carry: push–pull for low input voltage, half-bridge and full-bridge for mains.
  5. Three magnetics failure modes dominate: saturation (microseconds), flux walking (many cycles), and the leakage spike (every turn-off).
Formula sheet · Chapter 14
Flyback gainisolated buck–boost
\( V_o = \dfrac{N_s}{N_p}\cdot\dfrac{D}{1-D}V_s \)
Flyback duty ratio\(n = N_p/N_s\)
\( D = \dfrac{nV_o}{nV_o + V_s} \)
Flyback switch stressclamp above \(V_s + nV_o\)
\( V_{sw} = V_s + nV_o + V_{spike} \)
Flyback powerwhy it caps out near 150 W
\( P_o = \tfrac12 L_p I_{pk}^2 f \)
Forward gainisolated buck; no RHP zero
\( V_o = \dfrac{N_s}{N_p}D\,V_s \)
Forward reset limit\(N_r = N_p \Rightarrow D < 0.5\)
\( D_{max} = \dfrac{N_r/N_p}{1 + N_r/N_p} \)
Forward switch stress1:1 reset winding
\( V_{sw} = V_s\left(1 + \dfrac{N_p}{N_r}\right) = 2V_s \)
Push–pull gain\(D\) per switch, \(<0.5\)
\( V_o = 2\dfrac{N_s}{N_p}D\,V_s \)
Half-bridge gainprimary sees \(\pm V_s/2\)
\( V_o = \dfrac{N_s}{N_p}D\,V_s \)
Full-bridge gainprimary sees \(\pm V_s\)
\( V_o = 2\dfrac{N_s}{N_p}D\,V_s \)
Peak flux densitykeep \(\le 0.6B_{sat}\) when hot
\( B_{max} = \dfrac{V_s\,DT}{N_p A_e} \)
Leakage spike energywhat the clamp must absorb
\( W_{lk} = \tfrac12 L_{lk}I_{pk}^2 \)
Optimum flyback turns ratiobalances \(D\) against switch cost
\( nV_o \approx 0.5\,V_{s(max)} \)

Key terms

Galvanic isolation
No conductive path between input and output. Required by safety standards for mains-connected equipment.
Creepage and clearance
The minimum distances across a surface and through air between isolated conductors. Set by standards from the working voltage and pollution degree.
Flyback converter
Isolated buck–boost. Stores energy in a gapped coupled inductor; windings never conduct simultaneously.
Forward converter
Isolated buck. Energy passes straight through an ungapped transformer during the on-time; needs a reset mechanism.
Reset winding
A third winding that returns the magnetising energy to the source during the off-time. With \(N_r = N_p\) it caps \(D\) at 0.5.
Magnetising current
The current that establishes flux in the core, independent of load. Useful in a flyback; pure overhead in a forward converter.
Flux walking
Progressive drift of the core's operating point caused by asymmetry between half-cycles in a push–pull or bridge converter.
Leakage inductance
Primary flux that does not link the secondary. Its stored energy produces the turn-off voltage spike.
RCD clamp
Resistor, capacitor and diode network that catches the leakage spike and dissipates its energy. Must clamp above \(V_s + nV_o\).
Active clamp
A clamp that recycles the leakage and magnetising energy instead of dissipating it, and allows \(D > 0.5\) in a forward converter.
Primary-side regulation
Sensing the output through an auxiliary winding, removing the optocoupler at the cost of accuracy and loop speed.
Phase-shifted full bridge
A full bridge whose two legs are shifted in phase, using leakage inductance to achieve zero-voltage switching.
Check yourself

Test Yourself

Chapter 14 · six questions answers hidden until you ask
Why does a flyback transformer need an air gap when a forward transformer must not have one?

Because they are storing entirely different amounts of energy, on purpose.

Where magnetic energy is actually stored. Energy density is \( \tfrac12 BH \), and \( H = B/\mu \). Ferrite has \( \mu_r \) of a few thousand, so for the same \( B \), \( H \) in the air gap is thousands of times larger than in the core. Essentially all the energy is in the gap, even though the gap is a fraction of a millimetre.

The flyback must store energy. Every joule delivered to the output is first held in the core during the on-time — \( P_o = \tfrac12 L_pI_{pk}^2f \). Without a gap the core saturates at a small current and can hold almost nothing. The gap is what makes the topology possible.

The forward converter must not. Its transformer conducts on both sides at once, so power passes straight through. Any energy it stores is magnetising current — current that produces flux but delivers nothing to the load, and that must then be reset. Adding a gap lowers \( L_m \), which raises the magnetising current, which makes reset harder and wastes conduction loss for no return.

The two components are therefore specified differently:

  • Flyback: specify primary inductance and saturation current, like an inductor. Gapped, with \( L_p \) chosen from the required stored energy.
  • Forward: specify turns ratio, volt-second product and leakage. Ungapped, with \( L_m \) as high as the core allows.

The general rule: indirect converters store, so they gap. Direct converters transfer, so they do not.

A forward converter's duty ratio is limited to 0.5. Why can a flyback happily run at 0.6, when both are single-switch isolated converters?

Because the two use the off-time for different purposes, and only one of them has a separate reset to fit in.

The forward converter's off-time has two jobs: the output inductor freewheels, and the transformer's magnetising current must be reset through the reset winding. With \( N_r = N_p \), resetting takes exactly as long as magnetising did, so \( t_{reset} = t_{on} \), and \( t_{on} + t_{reset} \le T \) gives \( D \le 0.5 \) immediately.

The flyback's off-time has one job, and it is the reset. Delivering the stored energy to the secondary is resetting the core — the flux falls from its peak back to its starting value while the output diode conducts. The two are the same event, so there is no separate reset interval to accommodate.

What limits the flyback instead:

  • The energy must be fully delivered within \( (1-D)T \), or the converter enters continuous conduction mode — legal and common, but it changes the dynamics and introduces an RHP zero.
  • The switch stress \( V_s + nV_o \) rises with the turns ratio needed for a high \( D \).
  • Practical designs stop around \( D = 0.7 \) to \( 0.75 \), and it is a soft economic limit rather than a hard physical one.

The way to remember it: ask what the core is doing during the off-time. In a flyback it is delivering power. In a forward converter it is doing nothing useful — just resetting — which is precisely why that topology feels wasteful of duty ratio, and why active-clamp variants exist to recover it.

A half-bridge and a push–pull both use two switches on the same core. Why is the half-bridge preferred for mains input and the push–pull for a 48 V bus?

Because they trade voltage stress against current stress in opposite directions, and which trade is favourable depends entirely on the input voltage.

Push–pull: centre-tapped primary, tap at \( +V_s \). Each switch blocks \( 2V_s \). The primary half-winding sees the full \( V_s \).

Half-bridge: split-capacitor mid-point. Each switch blocks only \( V_s \). The primary sees \( \pm V_s/2 \) — half the volt-seconds, so twice the primary current for the same power.

At 48 V input:

  • Push–pull switches block 96 V. A 150 V MOSFET is cheap, fast and has very low \( R_{DS(on)} \).
  • Half-bridge switches block 48 V but carry twice the current, and \( I^2R \) doubles the conduction loss.
  • Push–pull wins: the voltage stress is trivial to accommodate and the lower current is worth having.

At 325 V input:

  • Push–pull switches block 650 V, plus a leakage spike — so 800 V or 900 V devices, which are markedly more expensive and have \( R_{DS(on)} \) several times higher for the same die.
  • Half-bridge switches block 325 V, so 500 V or 600 V devices — a mature, cheap, high-performance category.
  • Half-bridge wins, and comfortably.

The underlying reason: \( R_{DS(on)} \) scales roughly as \( V_{BR}^{2.5} \). Doubling the required blocking voltage costs about 5.7 times the on-resistance for the same die area. That is a steep penalty, and it is why the crossover between the two topologies sits somewhere around 100 V input.

The bonus for the half-bridge: the splitter capacitors block DC, so flux walking is cured by construction rather than by an added component.

Why does a flyback stop being sensible above about 150 W, when the equations contain no such limit?

Because \( P_o = \tfrac12 L_pI_{pk}^2 f \) forces every quantity in the converter upward together, and each of them hits a practical wall.

1. Core size. Stored energy sets core volume. Doubling the power doubles the energy per cycle, and the core grows with it. At a few hundred watts a flyback transformer becomes larger and more expensive than a forward transformer of the same rating — often by a factor of two or three.

2. Peak currents. Because energy is stored and released rather than passed through, the peak current is roughly twice the average, and the RMS is about \( 1.15 \times \) the CCM equivalent. Conduction losses rise as the square. At 500 W the primary peak might be 10 A where a forward converter would need 4 A.

3. Output capacitor ripple. This is often the binding constraint and the least anticipated. The flyback has no output inductor, so the capacitor absorbs the entire pulsed secondary current. Its RMS ripple is approximately \( I_o\sqrt{D/(1-D)} \) — at 12 V, 40 A and \( D = 0.4 \), that is 33 A RMS. No reasonable capacitor bank handles that.

4. Leakage energy. \( \tfrac12 L_{lk}I_{pk}^2 \) scales with the square of the peak current. At high power the clamp dissipates tens of watts, and efficiency falls several points.

What a forward converter changes. Energy passes straight through, so the core is smaller; the output inductor makes the output current continuous, so the capacitor's ripple burden falls by roughly a factor of five; the peak currents are lower; and the leakage energy is smaller in proportion.

The boundary is economic, not physical. Kilowatt flybacks exist — some traction and welding supplies use them — but they are chosen for specific reasons (multiple outputs, wide input range, tolerance of short circuits) that outweigh the penalties. For a general-purpose supply, 150 W is where the arithmetic turns.

A designer sets a flyback's RCD clamp to catch at 400 V, with a 325 V link and a 192 V reflected voltage. What happens?

The clamp conducts during normal operation and dissipates a large fraction of the converter's output power.

Where the numbers go wrong. During the off-time the primary legitimately sits at

\[ V_s + nV_o = 325 + 192 = 517\ \text{V} \]

for the whole of the energy-transfer interval. That is not a spike; it is the reflected output voltage, and it is exactly how the energy gets to the secondary. A clamp set at 400 V conducts throughout that interval.

How much power it wastes. The clamp diverts current whenever the primary tries to exceed 400 V, which is essentially all of the off-time. Rather than catching a brief spike, it becomes a parallel load taking a substantial share of the transferred energy — comfortably tens of watts in a 36 W supply, which is to say the converter cannot regulate at all.

The symptoms on the bench are unmistakable once you know them: the clamp resistor is far too hot to touch, the output cannot reach its set voltage at full load, efficiency is dismal, and the drain waveform shows a flat plateau at the clamp level for the whole off-time rather than a brief spike decaying to a plateau at 517 V.

The correct setting:

\[ V_{clamp} = V_s + 1.5\,nV_o = 325 + 288 = 613\ \text{V} \]

and the switch is then rated at \( 1.2 \times 613 \approx 740 \) V, so an 800 V part.

The principle to carry: a clamp must sit above every voltage the circuit produces legitimately, and catch only what it produces parasitically. Setting it from the supply voltage alone, without adding the reflected output, is one of the most common flyback design errors — and the one that most reliably produces a converter that appears to work at no load and collapses under it.

Why does current-mode control cure flux walking, when voltage-mode control does not?

Because current-mode control terminates each pulse on a measurement of the flux, while voltage-mode control terminates it on a clock.

What flux walking is. In a push–pull or bridge converter, half-cycle A magnetises the core one way and half-cycle B the other. If A applies slightly more volt-seconds than B — a few nanoseconds of extra on-time, or a slightly lower device drop — the core does not return to where it started. The offset accumulates every cycle until the core saturates.

Voltage-mode control cannot see it. The pulse ends when the sawtooth crosses the error voltage — a timing decision that knows nothing about the core. If half-cycle A is systematically longer, it stays longer, and the drift continues unopposed.

Current-mode control does see it, because in a transformer the primary current is proportional to the flux (plus the reflected load current). The pulse ends when the sensed current reaches a threshold. So:

  • If half-cycle A pushed the flux too far positive, the next A half-cycle starts from a higher flux, so its current reaches the threshold sooner, and the pulse is shorter.
  • The correction is automatic, cycle by cycle, with no additional components.

This is negative feedback on the flux itself, and it is the main reason current-mode control dominates isolated converter design — not the loop-shaping advantages usually cited first.

Two caveats worth knowing:

  1. Current-mode control is unstable above \( D = 0.5 \) without slope compensation — a ramp added to the sensed current. This is why every current-mode controller IC has a slope-compensation pin or an internal ramp.
  2. It corrects volt-second asymmetry but not asymmetry in the sensing path itself. A current-sense transformer with different behaviour on the two half-cycles will introduce its own walk.

The belt-and-braces approach, used in most production designs, is current-mode control and a DC blocking capacitor in series with the primary. Neither is expensive, and the failure they prevent is catastrophic.

Practice

Problems

Three habits for isolated converter problems:

  1. Choose the turns ratio first, from the worst-case duty ratio you are willing to run at. Everything else follows.
  2. Check the switch stress at the highest input voltage, and remember to add the reflected output and the leakage spike.
  3. Ask what resets the core. If you cannot answer, the design is not finished.

Problems 1–5 are direct application; 6–9 need judgement; 10–12 are design questions worth discussing in a tutorial.

  1. A flyback produces 15 V at 2 A from a 300 V DC link with \( N_p{:}N_s = 20{:}1 \), at 100 kHz. Find \( D \), the switch blocking voltage before the spike, and the primary inductance if the peak primary current is 1.2 A.
  2. A forward converter with \( N_p{:}N_s = 6{:}1 \) and a 1:1 reset winding runs from 400 V. Find the output voltage at \( D = 0.4 \), the switch rating, and the maximum output voltage the topology permits.
  3. A push–pull converter produces 24 V at 10 A from 48 V with \( N_p{:}N_s = 1{:}1 \). Find the duty ratio per switch and the blocking voltage each device must withstand.
  4. A half-bridge produces 12 V from 325 V at \( D = 0.4 \). Find the required turns ratio, and compare it with the ratio a full bridge would need for the same output and duty ratio.
  5. A flyback transformer has \( L_p = 600\ \mu\text{H} \) and \( L_{lk} = 12\ \mu\text{H} \), with \( I_{pk} = 2 \) A at 65 kHz. Find the leakage energy per cycle and the power the clamp must dissipate.
  6. A universal-input flyback (120–375 V DC) delivers 20 V at 3 A. Choose a turns ratio, justify it, find the duty range, and specify the switch voltage rating with reasons.
  7. Explain why a forward converter has no right-half-plane zero while a flyback in continuous conduction does, and state what that means for the two converters' achievable loop bandwidths.
  8. A 500 W supply is to be built from a 325 V link. Compare a two-switch forward and a half-bridge on device count, device ratings, transformer utilisation, control complexity and cost. Recommend one.
  9. A push–pull converter saturates at full load but not at half load. List four candidate causes, state the measurement that would distinguish each, and give the remedy for each.
  10. Design a 60 W flyback for 12 V output from universal mains at 65 kHz. Specify the turns ratio, duty range, primary inductance, peak current, switch voltage rating and clamp level. State the output capacitor's RMS ripple current and comment on what type of capacitor is required.
  11. A telecom supply must produce 3.3 V at 30 A from a 36–72 V bus with better than ±2% regulation and fast transient response. Compare an active-clamp forward converter with a phase-shifted full bridge, and recommend one with reasons covering efficiency, part count, transformer utilisation and control.
  12. An engineer proposes replacing a flyback's optocoupler feedback with primary-side regulation to save cost in a 5 V, 2 A charger. Analyse the consequences for regulation accuracy, transient response, no-load behaviour and cable-drop compensation, and state under what output specification the change would be acceptable.