Set 21 — Parallel Operation and Load Sharing
A substation almost never runs one transformer. Units are banked in parallel so that any one of them can be taken out for maintenance, so that the plant can be extended as the load grows, and so that light loads can be carried by a single machine at good efficiency. The moment two transformers share a busbar, however, nobody decides how the load divides between them: the impedances do, and the designer's only control is the choice of machines.
This set takes the percentage impedance of Set 19 and the efficiency of Set 20 and asks what they mean for two machines working together. Six problems cover the division of load between unequal units, the extra kVA that appears when the impedance angles differ, the capacity lost when the percentage impedances do not match, the current that circulates when the ratios do not match, and the vector-group rule that decides which three-phase transformers may be paralleled at all.
What must match, and what merely should. Same polarity and same phase sequence are absolute — getting either wrong short-circuits the bank. Equal voltage ratios and, for three-phase units, equal phase displacement are next: a mismatch drives a circulating current with no load connected. Equal per-unit impedance and equal \(X/R\) only affect how well the load divides.
With equal ratios the two impedances are simply in parallel across the load, so the current divides inversely as the impedance and the volt-amperes follow the conjugate:
\[ I_A = I\,\frac{Z_B}{Z_A+Z_B}, \qquad S_A = S\left(\frac{Z_B}{Z_A+Z_B}\right)^{\!*} \]In percentage terms the rule reads off the nameplates. Working on a common kVA base, the share of a unit is proportional to its rating divided by its percentage impedance:
\[ S_A = S\;\frac{S_{A,\text{rated}}/Z_A\%}{\sum_k S_{k,\text{rated}}/Z_k\%} \]Equivalently, convert every impedance to one base with \(Z\%_{\text{new}} = Z\%_{\text{old}}\times S_{\text{base,new}}/S_{\text{base,old}}\) and divide inversely.
Only kW and kvar add; kVA does not. If the impedance angles differ, the two units deliver at different power factors and
\[ |S_A| + |S_B| \;>\; |S|, \qquad P_A+P_B = P, \qquad Q_A+Q_B = Q \]The bank's usable capacity is set by whichever unit saturates first. The most heavily worked machine, relative to its own rating, is the one with the smallest percentage impedance. Full combined capacity is available only when every \(Z\%\) is the same.
Unequal ratios drive a circulating current round the loop formed by the two windings, present at no load and superimposed on the load-division current when a load is connected:
\[ I_c = \frac{E_A-E_B}{Z_A+Z_B}, \qquad I_A = \frac{(E_A-E_B) + I\,Z_B}{Z_A+Z_B} \]Three-phase units are grouped by phase displacement, 0°, 180°, −30° and +30°. Two transformers of the same group parallel directly; a −30° unit and a +30° unit can be made to match by interchanging two phases on both sides of one of them. No relabelling can bridge 0° and 180°.
Two single-phase transformers of identical voltage ratio are connected in parallel on the same busbars and supply a common load of 600 kVA at 0.8 power factor lagging. Their nameplates read:
| Transformer | Rating | Percentage impedance |
|---|---|---|
| A | 500 kVA | 4.0% |
| B | 250 kVA | 5.0% |
The two impedances have the same \(X/R\) ratio. Determine
- the kVA delivered by each transformer
- the percentage of its own rating at which each is working.
A percentage impedance is only meaningful against its own base, so before the two can be compared they must be referred to one common kVA base. Take 500 kVA:
The 250 kVA machine is electrically the stiffer of the two by a factor of 2.5 — it is 5% impedant at 250 kVA, which is 10% at 500 kVA.
Equal ratios mean the two windings sit across the same terminal voltage, so on the common base the current, and hence the kVA, divides inversely as the impedance:
Divide the 600 kVA in that ratio. The base cancels if the shares are written straight from the nameplates as rating divided by percentage impedance:
The two add to 600 kVA exactly, which they may do here only because the impedance angles are equal — Problem 2 shows what happens when they are not.
Express each share as a fraction of its own rating:
The unit with the lower percentage impedance is the harder worked of the two, whatever their ratings. With 600 kVA drawn from a bank rated 750 kVA in total, one machine is at 86% and the other loafing at 69%.
The power factor is the same for both and equal to the load's, because the two impedances have the same angle. Each machine therefore delivers 0.8 of its share as kW:
Two single-phase transformers, both 2000/400 V and of exactly equal ratio, are paralleled on a 400 V busbar. Their equivalent impedances referred to the secondary are
| Transformer | Rating | Equivalent impedance (secondary) |
|---|---|---|
| A | 200 kVA | 0.010 + j0.040 Ω |
| B | 150 kVA | 0.030 + j0.036 Ω |
The bank supplies 300 kVA at 0.8 power factor lagging at 400 V. Find the kVA and the power factor of each transformer, and comment on the sum of the two kVA figures.
Put the impedances in polar form, because it is the angles that make this problem different from Problem 1:
A ratio \(X/R\) of 4.0 for the larger unit and 1.2 for the smaller is entirely normal: leakage reactance grows with size faster than winding resistance falls.
The load current, with the busbar voltage as reference:
Divide it inversely as the impedances, keeping the angles:
Transformer A, the more reactive of the two, carries a current lagging by nearly 49°; transformer B carries one lagging by only 23°. Neither is at the load's 36.87°.
Convert to volt-amperes at the busbar voltage. Each machine's power factor is the cosine of its own current angle:
Now the point of the problem. Add the two kVA figures arithmetically and compare with the load:
Nothing has been created. The two currents are not in phase, so their magnitudes cannot be added; only their components can.
Check by resolving into kW and kvar, which must add:
| Unit | kVA | p.f. | kW | kvar | % of rating |
|---|---|---|---|---|---|
| A | 163.7 | 0.657 | 107.6 | 123.4 | 81.8% |
| B | 144.0 | 0.920 | 132.4 | 56.6 | 96.0% |
| Total | 307.7 | 0.800 | 240.0 | 180.0 | — |
240 kW and 180 kvar are exactly the load's \(300\times0.8\) and \(300\times0.6\). The kVA column is the only one that does not balance.
What the nameplate rule of Problem 1 would have predicted. The percentage impedances are \(0.04123/(400^2/200000) = 5.15\%\) and \(0.04690/(400^2/150000) = 4.40\%\), giving shares of 159.7 kVA and 140.3 kVA.
The ratio it predicts, \(|Z_B|/|Z_A| = 1.138\), is exactly right — current division by magnitude is unaffected by the angles. What is wrong is the assumption that the two shares add to 300.
Three single-phase transformers of the same voltage ratio and the same \(X/R\) ratio are to be operated in parallel:
| Transformer | Rating | Percentage impedance |
|---|---|---|
| P | 250 kVA | 4.0% |
| Q | 500 kVA | 5.0% |
| R | 750 kVA | 6.0% |
Find the largest total load the bank may carry if no transformer is to exceed its own rating, and state the percentage of the installed 1500 kVA that this represents. What single change would allow the full 1500 kVA to be used?
Form the sharing weights as rating over percentage impedance, exactly as in Problem 1 but for three units:
Ask which unit reaches its rating first. Divide each share fraction by the machine's own rating — or, more directly, note that the fractional loading of a unit is proportional to \(1/Z\%\), so the smallest percentage impedance is always the first to saturate. Here that is P, at 4.0%.
Scale the total until P is exactly full. P carries 0.2174 of whatever the bank carries, so
Check the other two at that load:
| Unit | Share of 1150 kVA | Rating | Loading |
|---|---|---|---|
| P | 250.0 kVA | 250 kVA | 100% |
| Q | 400.0 kVA | 500 kVA | 80% |
| R | 500.0 kVA | 750 kVA | 66.7% |
Nearly 350 kVA of perfectly good transformer is unusable, and the reason is entirely a mismatch of percentage impedance.
The single change that recovers it. Every unit reaches 100% together only if the loading fractions are equal, and since loading \(\propto 1/Z\%\) that requires
Making all three 6% (the largest present) would divide 1500 kVA as 250 : 500 : 750 — exactly in proportion to the ratings. In practice the 4% and 5% units would be re-specified, or a series reactor fitted, to bring them up to 6%; nothing can be done to the 6% machine to help.
Two 100 kVA single-phase transformers are supplied from a common 2200 V busbar and their secondaries are paralleled. On open circuit transformer A gives 220 V and transformer B, whose tap setting differs, gives 216 V. Their equivalent impedances referred to the secondary are
| Transformer | No-load secondary emf | Equivalent impedance (secondary) |
|---|---|---|
| A | 220 V | 0.008 + j0.023 Ω |
| B | 216 V | 0.010 + j0.028 Ω |
Determine
- the current circulating between the two transformers with no load connected, and its value as a percentage of rated secondary current
- the current and the kVA delivered by each when a load of 150 kVA at 0.8 power factor lagging is connected to the 220 V busbar.
On open circuit the two secondaries form a closed loop. The 4 V difference between the induced emfs is impressed on the two impedances in series — there is nowhere else for it to act:
Judge it against the rating. Rated secondary current is
A ratio error of 4 V in 220 V — 1.8% — produces a permanent 16% current. The reason is visible in per unit: the driving voltage is 1.8% while the impedance opposing it is only \(5.03\% + 6.14\% = 11.2\%\), so \(0.0182/0.1117 = 0.163\) pu.
This current does no useful work at all. It leaves transformer A, passes through transformer B against its emf, and returns — heating both windings and consuming part of the thermal rating that the load should have had. It is present whenever the transformers are energised, load or no load.
Now connect the load. Its current, referred to the 220 V busbar:
Superpose the two effects. Writing \(E_A = I_AZ_A+V\) and \(E_B = I_BZ_B+V\) with \(I_A+I_B = I\) and eliminating \(V\):
Note the two impedances are almost parallel in angle here (70.82° and 70.35°), so the load-division term barely rotates the current; it is the circulating term that skews everything.
Convert to volt-amperes at the 220 V busbar:
| Unit | Current | kVA | p.f. | Loading |
|---|---|---|---|---|
| A | 438.4 A | 96.5 | 0.738 | 96.5% |
| B | 249.1 A | 54.8 | 0.891 | 54.8% |
| Total | 681.8 A | 151.3 | 0.800 | — |
A 150 kVA load on a 200 kVA bank, and transformer A is already at 96.5% of rating. Had the ratios matched, the division term alone would have given 82.5 kVA and 67.5 kVA — still unequal, because \(|Z_A| < |Z_B|\), but nothing like as lopsided. The extra 14 kVA on A and the 13 kVA missing from B are the circulating current at work.
A distribution substation contains two three-phase transformers, both 11 kV/433 V and both of vector group Dyn11, connected to the same LV board:
| Transformer | Rating | Percentage impedance |
|---|---|---|
| T1 | 1600 kVA | 6.0% |
| T2 | 1000 kVA | 4.5% |
The board carries 2000 kVA at 0.85 power factor lagging. Assuming equal \(X/R\) ratios, find
- the kVA and the secondary line current of each transformer
- the maximum total load the bank can carry without overloading either unit
- the percentage impedance T2 would need for the pair to share in proportion to their ratings.
Being three-phase changes nothing about the sharing rule. Both nameplate kVA figures are three-phase totals and both percentage impedances are already per-unit quantities, so the weights are formed exactly as before:
Divide the 2000 kVA:
The smaller machine, being the stiffer one, is carrying almost its full rating while the larger sits at two-thirds.
Secondary line currents from the three-phase kVA at 433 V:
The currents add arithmetically here only because the impedance angles were taken equal, so all three phasors are collinear.
Maximum bank load. T2 saturates first, at 45.45% of whatever the board carries:
2200 kVA out of an installed 2600 kVA, or 84.6%. The 400 kVA shortfall is the price of the 1.5-point impedance mismatch.
The matched impedance. Proportional sharing needs equal loading fractions, hence equal percentage impedances:
With that value the shares at 2600 kVA would be 1600 kVA and 1000 kVA, both units exactly full. It is worth noting that raising T2's impedance increases the bank's capacity — the opposite of what intuition suggests about impedance.
State the conditions to be satisfied before two three-phase transformers may be operated in parallel, and set out which vector groups may be paralleled with which.
Then take two 11 kV/433 V transformers, each of 6% impedance on a common base, and estimate the per-unit circulating current that would flow if their secondaries were paralleled while their phase displacements differed by
- 30° — for example a Yy0 unit against a Dy11 unit
- 60° — a Dy1 unit against a Dy11 unit
The conditions, in order of severity. The first three cannot be violated at all; the last two govern only how well the bank performs:
| Condition | Consequence if violated | Status |
|---|---|---|
| Same polarity / terminal marking | Dead short across the secondaries | Essential |
| Same phase sequence | Two phases short-circuited through the windings | Essential |
| Same phase displacement (vector group) | Large permanent circulating current | Essential |
| Same voltage ratio, on the same tap | Circulating current at no load — Problem 4 | Strongly desirable |
| Equal percentage impedance | Unequal loading, capacity lost — Problems 3 and 5 | Desirable |
| Equal \(X/R\) ratio | Different power factors, kVA sum exceeds load — Problem 2 | Desirable |
The four displacement groups. Every standard three-phase connection puts the secondary line voltage at one of four angles relative to the primary, and the group number is that angle in units of 30° measured clockwise:
| Group | Displacement | Connections | May be paralleled with |
|---|---|---|---|
| 1 | 0° | Yy0, Dd0, Dz0 | Group 1 only |
| 2 | 180° | Yy6, Dd6, Dz6 | Group 2 only |
| 3 | −30° (lag) | Dy1, Yd1, Yz1 | Group 3, and Group 4 after interchanging two phases on both sides |
| 4 | +30° (lead) | Dy11, Yd11, Yz11 | Group 4, and Group 3 by the same device |
The reason groups 3 and 4 can be bridged is that interchanging two phases on the primary and the secondary reverses the phase sequence through the transformer, which negates the displacement: \(-30^\circ\) becomes \(+30^\circ\). Relabelling terminals can only rotate a set of phasors by \(\pm120^\circ\), so it can never turn 0° into 180°, and groups 1 and 2 stay apart.
The circulating voltage produced by a displacement. Two secondary phasors of equal magnitude \(E\) separated by an angle \(\theta\) leave a difference
Unlike the ratio error of Problem 4, this difference is not a small trim — it is a fixed fraction of the whole secondary voltage.
Thirty degrees. In per unit, with \(E = 1.0\) and the two 6% impedances in series:
Over four times full-load current, permanently, with no load connected. The bank would trip on overcurrent within seconds, and would burn out if it did not.
Sixty degrees — a group 3 unit paralleled with a group 4 unit without the phase interchange:
The full secondary voltage now appears across the loop impedance. For comparison, 180° would give \(2.0/0.12 = 16.7\) pu, which is simply a short circuit fed from both ends.
Put the three cases side by side against the 16.3% of Problem 4:
| Mismatch | Driving voltage | Circulating current |
|---|---|---|
| Ratio, 4 V in 220 V | 0.018 pu | 0.163 pu |
| Displacement 30° | 0.518 pu | 4.31 pu |
| Displacement 60° | 1.000 pu | 8.33 pu |
| Displacement 180° | 2.000 pu | 16.7 pu |
A tap mismatch wastes capacity; a group mismatch destroys the transformers. The two faults differ by two orders of magnitude.
Key Formulas
| Quantity | Relation | Notes |
|---|---|---|
| Base change | \(Z\%_{\text{new}} = Z\%_{\text{old}}\dfrac{S_{\text{base,new}}}{S_{\text{base,old}}}\) | Same voltage base — Problem 1 |
| Current division | \(\mathbf{I}_A = \mathbf{I}\dfrac{Z_B}{Z_A+Z_B}\) | Equal ratios — Problems 2, 4 |
| kVA division | \(\mathbf{S}_A = \mathbf{S}\left(\dfrac{Z_B}{Z_A+Z_B}\right)^{\!*}\) | Conjugate, because \(S = VI^*\) — Problem 2 |
| Nameplate sharing rule | \(S_k = S\,\dfrac{S_{k,\text{rated}}/Z_k\%}{\sum S_{k,\text{rated}}/Z_k\%}\) | Equal \(X/R\) assumed — Problems 1, 3, 5 |
| Fractional loading | \(\dfrac{S_k}{S_{k,\text{rated}}} \propto \dfrac{1}{Z_k\%}\) | Smallest \(Z\%\) saturates first — Problems 3, 5 |
| Maximum bank load | \(S_{\max} = S_{k,\text{rated}}\big/ f_k\) for the critical unit | \(f_k\) = that unit's share fraction — Problems 3, 5 |
| Power balance | \(\sum P_k = P,\quad \sum Q_k = Q,\quad \sum|S_k| \ge |S|\) | Equality only for equal angles — Problem 2 |
| Circulating current | \(I_c = \dfrac{E_A-E_B}{Z_A+Z_B}\) | Present at no load — Problem 4 |
| Loaded, unequal ratios | \(\mathbf{I}_A = \dfrac{(E_A-E_B)+\mathbf{I}Z_B}{Z_A+Z_B}\) | Circulating plus division — Problem 4 |
| Circulating current, per unit | \(I_{c,\text{pu}} = \dfrac{\Delta E_{\text{pu}}}{Z_{A,\text{pu}}+Z_{B,\text{pu}}}\) | Fast check — Problems 4, 6 |
| Displacement mismatch | \(\Delta E = 2E\sin(\theta/2)\) | \(\theta\) = angle between groups — Problem 6 |
| Percentage impedance | \(Z\% = \dfrac{I_{\text{rated}}|Z|}{V_{\text{rated}}}\times100 = \dfrac{|Z|}{Z_{\text{base}}}\times100\) | Per phase — Problems 2, 4 |
| Three-phase line current | \(I_L = \dfrac{S}{\sqrt3\,V_L}\) | Total kVA, not per phase — Problem 5 |
Common Mistakes
Comparing percentage impedances without a common base. 4% on 500 kVA and 5% on 250 kVA are not in the ratio 4 : 5 but 4 : 10, and the sharing is 2.5 : 1, not 1.25 : 1 — Problem 1.
Dividing the load in proportion to the impedances instead of inversely. The low-impedance unit takes the larger share; it is the stiff machine that gets worked hardest — Problems 1 and 3.
Adding the two kVA figures and expecting the load. With unequal impedance angles they sum to 307.7 kVA for a 300 kVA load. Only kW and kvar add — Problem 2.
Forgetting the conjugate in \(S_A = S(Z_B/(Z_A+Z_B))^*\). Dropping it swaps which transformer carries the reactive load and reverses both power factors — Problem 2.
Assuming the largest transformer limits the bank. The limit belongs to the unit with the smallest percentage impedance, regardless of size — the 250 kVA unit stops the 1500 kVA bank at 1150 kVA in Problem 3.
Believing that a lower impedance is always better. Raising T2 from 4.5% to 6% raises the bank's usable capacity from 2200 kVA to 2600 kVA — Problem 5.
Using the load impedance in the circulating-current formula. The circulating current flows in the loop formed by the two transformers alone, so only \(Z_A+Z_B\) limits it — Problem 4.
Treating a small ratio error as a small effect. 1.8% of voltage difference against 11.2% of loop impedance gives 16.3% of rated current — Problem 4.
Adding the circulating and load currents arithmetically. They are phasors at 70.6° and 37.1°; adding magnitudes gives 448.8 A instead of the correct 438.4 A — Problem 4.
Assuming any two star–delta transformers will parallel. Dy1 and Dy11 are 60° apart and would circulate 8.3 pu; they must first be brought to the same group by interchanging two phases on both sides — Problem 6.
Treating polarity and phase sequence as matters of degree. They are switching conditions: get either wrong and the bank is short-circuited the instant the breaker closes — Problem 6.
The percentage impedance that Set 19 introduced as a voltage drop and Set 20 used as a loss has now become the quantity that decides how a substation divides its work. Six problems have turned on it: two units share inversely as it, the bank's capacity is limited by the smallest of it, and the current that circulates when the ratios disagree is a voltage difference divided by it. Where the impedance angles disagree as well, the two kVA figures no longer add to the load — a reminder that kVA is a magnitude and magnitudes do not superpose.
Every transformer so far has had two electrically separate windings, and Problem 6 leaned on that separation when it counted the phase displacement between them. Joining the two windings at one point gives up the isolation but changes the economics completely: part of the load then reaches the output without being transformed at all, and the same iron and copper can carry several times the nameplate power.
Next: Set 22 — Autotransformers, where the conductive and inductive parts of the transferred power are separated and the copper saving is worked out.