Solved Problems · Set 31

Starting Methods and Starter Calculations

Part 4 · Induction Machines — the standstill impedance is small and the standstill torque is not, so every starter is a bargain struck between the current the supply will tolerate and the torque the load demands.

Prof. Mithun Mondal 6 solved problems GATE · ESE · University

Set 31 — Starting Methods and Starter Calculations

An induction motor at standstill is a short-circuited transformer. The only impedance limiting the current is the leakage impedance, and Set 30's circle diagram put the starting point four to seven times further out than the full-load point. The torque available there, by contrast, is rarely more than the full-load value, because at unit slip most of the air-gap power goes into rotor copper loss rather than into the shaft. Every starting method is an attempt to improve that exchange.

Three of the four methods work on the stator, reducing the voltage at start, and all three obey the same arithmetic: current falls as the voltage and torque as its square. The fourth works on the rotor and is the only one that changes the exchange rate itself — adding resistance to a slip-ring rotor raises the torque while lowering the current. These six problems establish each method on realistic machines, derive the star–delta factor of one-third rather than quoting it, and end with the four side by side on one table.

Part 4 · Testing and Control · 6 solved problems

i Method Recap
  • The starting current is fixed by the standstill impedance, which is exactly what the blocked-rotor test of Set 29 measured:

    \[ I_{st} = \frac{V_{ph}}{|Z_{01}|} = I_{sc}, \qquad \frac{I_{sc}}{I_{FL}} \approx 5\text{ to }7 \]
  • The starting torque follows from the torque law at unit slip. Since \(T \propto I_2'^2R_2'/s\) at constant voltage,

    \[ \frac{T_{st}}{T_{FL}} = \left(\frac{I_{sc}}{I_{FL}}\right)^{\!2}s_{FL} \]

    This single relation converts a current ratio into a torque ratio and is used in every problem on this page.

  • Every stator-side method scales the same way. Applying a fraction \(x\) of rated voltage gives

    \[ I_{\text{motor}} = xI_{sc}, \qquad T_{st} = x^2T_{st,\text{DOL}} \]

    and with an autotransformer the supply current is reduced once more, to \(x^2I_{sc}\), because the starter transforms it. A stator resistance or reactance does not: the supply current stays at \(xI_{sc}\).

  • Star–delta gives one-third of both, for a machine wound to run in delta:

    \[ \frac{I_{st,Y}}{I_{st,\Delta}} = \frac13, \qquad \frac{T_{st,Y}}{T_{st,\Delta}} = \frac13 \]

    It is exactly equivalent to an autotransformer set to \(x = 1/\sqrt3 = 57.7\%\), and its ratio cannot be adjusted.

  • Rotor resistance moves the torque peak. For a slip-ring machine the maximum torque occurs at

    \[ s_{\max T} = \frac{R_2+R_{ext}}{X_2}, \qquad T_{\max} = \frac{3E_2^2}{2\omega_sX_2}\ \text{(unchanged)} \]

    so \(R_2+R_{ext} = X_2\) puts the full breakdown torque at standstill. The value of the maximum never changes; only the slip at which it appears.

  • The rotor current falls as the resistance rises, which is why this is the only method that buys torque without buying current:

    \[ I_2 = \frac{sE_2}{\sqrt{(R_2+R_{ext})^2+(sX_2)^2}} \]
  • A figure of merit that settles the argument. For every stator-side method the ratio of starting torque to supply current is the same as it is direct on line; only rotor resistance improves it:

    \[ \frac{T_{st}}{I_{\text{supply}}}\bigg|_{\text{autotransformer, }Y\text{-}\Delta} = \frac{T_{st}}{I_{\text{supply}}}\bigg|_{\text{DOL}} \]
Problem 1CoreDirect-On-Line Starting

A 15 kW, 400 V, 50 Hz, 4-pole, three-phase delta-connected squirrel-cage induction motor takes a full-load line current of 30 A at 0.85 power factor lagging and runs at 4% slip. Switched direct on to a 400 V supply at standstill it draws 150 A. Find

  1. the full-load speed, torque and efficiency
  2. the starting torque, as a value and as a multiple of full-load torque
  3. the starting kVA, and the starting kVA per kW of rating.
Solution

Full-load conditions first, since everything on this page is quoted against them:

\[ N_s = \frac{120\times50}{4} = 1500\ \text{rev/min}, \qquad N = 1500(1-0.04) = 1440\ \text{rev/min} \]
\[ T_{FL} = \frac{P_{\text{out}}}{\omega_m} = \frac{15000}{2\pi(1440)/60} = \frac{15000}{150.80} = 99.5\ \text{N·m} \]

The efficiency, as a check that the data are self-consistent:

\[ P_{\text{in}} = \sqrt3\,V_LI_L\cos\phi = \sqrt3\times400\times30\times0.85 = 17667\ \text{W} \]
\[ \eta = \frac{15000}{17667} = 0.849 = 84.9\% \]

Reasonable for a 15 kW machine. Note that \(I_{FL}\) is the line current; the delta-connected windings each carry \(30/\sqrt3 = 17.3\) A.

The starting torque from the current ratio. Torque is proportional to \(I_2'^2R_2'/s\), and the rotor resistance is the same at both conditions, so the ratio is

\[ \frac{T_{st}}{T_{FL}} = \left(\frac{I_{sc}}{I_{FL}}\right)^{\!2}s_{FL} = \left(\frac{150}{30}\right)^{\!2}(0.04) = 25\times0.04 = 1.00 \]
\[ T_{st} = 1.00\times99.5 = 99.5\ \text{N·m} \]

Exactly full-load torque — which sounds satisfactory until the current is looked at. Note also how the slip enters: a machine with a low-resistance rotor has a small \(s_{FL}\) and therefore a poor starting torque, and vice versa.

The starting kVA, which is what the supply actually sees:

\[ S_{st} = \sqrt3\times400\times150 = 103.9\ \text{kVA} \]
\[ \frac{S_{st}}{P_{\text{rated}}} = \frac{103.9}{15} = 6.9\ \text{kVA per kW} \]

Against a full-load input of \(\sqrt3(400)(30) = 20.8\) kVA. Supply authorities set limits in exactly this form — a typical rule permits direct-on-line starting only up to a few kW on a domestic supply and a few tens of kW on an industrial one.

Why the exchange is so poor. At standstill the power crossing the air gap is \(P_g\) and all of it becomes rotor copper loss, since \(P_m = (1-s)P_g = 0\). Five times the current produces twenty-five times the heat in the rotor, and the shaft sees no more torque than at full load. A motor started direct on line spends the whole run-up dumping into the rotor an energy equal to the kinetic energy it finally acquires.

The number that decides everything is \((I_{sc}/I_{FL})^2s_{FL}\), and it is a property of the machine, not of the starter. This motor offers 1.00 pu of torque for 5.0 pu of current. No stator-side starter can change that exchange rate — the following two problems only move along it, trading torque away in the same proportion as current. Changing the exchange rate requires access to the rotor, which is Problem 4.
Answer(a) 1440 rev/min, 99.5 N·m, 84.9%   (b) \(T_{st} = 99.5\ \text{N·m} = 1.00\,T_{FL}\)   (c) 103.9 kVA, 6.9 kVA/kW
Problem 2CoreThe Star–Delta One-Third Factor

The motor of Problem 1 is started with a star–delta starter: the stator is connected in star for starting and switched to delta when the machine is near full speed.

  1. Derive from first principles the ratio of the starting line current in star to that in delta, and the corresponding torque ratio.
  2. Evaluate both for this machine.
  3. State the autotransformer tapping to which a star–delta starter is equivalent.
Solution

Fix what does not change. The starter reconnects the windings but does not alter them, so the standstill impedance per phase, \(Z\), is the same in both connections. The supply line voltage \(V_L\) is also the same. Only the voltage across each winding changes.

Delta connection. Each winding sees the full line voltage, and the line current is \(\sqrt3\) times the winding current:

\[ I_{ph,\Delta} = \frac{V_L}{Z}, \qquad I_{L,\Delta} = \sqrt3\,\frac{V_L}{Z} \]

Star connection. Each winding sees \(V_L/\sqrt3\), and the line current is the winding current:

\[ I_{ph,Y} = \frac{V_L}{\sqrt3\,Z}, \qquad I_{L,Y} = \frac{V_L}{\sqrt3\,Z} \]

Divide, and the factor of three appears as two separate factors of \(\sqrt3\):

\[ \frac{I_{L,Y}}{I_{L,\Delta}} = \frac{V_L/(\sqrt3Z)}{\sqrt3\,V_L/Z} = \frac{1}{3} \]

One \(\sqrt3\) comes from the reduced winding voltage and the other from the change in the line-to-phase current relation. Both act in the same direction, which is why the reduction is three and not \(\sqrt3\).

The torque ratio uses winding current, not line current. Torque comes from the ampere-turns of each winding, so \(T \propto I_{ph}^2\) at a given slip:

\[ \frac{T_{st,Y}}{T_{st,\Delta}} = \left(\frac{I_{ph,Y}}{I_{ph,\Delta}}\right)^{\!2} = \left(\frac{1}{\sqrt3}\right)^{\!2} = \frac{1}{3} \]

The two ratios come out equal, but by different routes: the current ratio is \(1/3\) because of the two \(\sqrt3\) factors, and the torque ratio is \(1/3\) because a single \(\sqrt3\) is squared. Confusing the two is the classic error here.

Now the numbers for this machine:

\[ I_{L,\Delta} = 150\ \text{A} \;\Longrightarrow\; I_{ph,\Delta} = \frac{150}{\sqrt3} = 86.6\ \text{A}, \qquad \frac{V_L}{Z} = 86.6\ \text{A} \]
\[ I_{L,Y} = I_{ph,Y} = \frac{86.6}{\sqrt3} = 50.0\ \text{A} = \frac{150}{3}\;\checkmark \]
\[ T_{st,Y} = \frac{99.5}{3} = 33.2\ \text{N·m} = 0.333\,T_{FL} \]
QuantityDelta (DOL)Star (starting)Ratio
Winding voltage400 V231 V\(1/\sqrt3\)
Winding current86.6 A50.0 A\(1/\sqrt3\)
Line current150.0 A50.0 A1/3
Starting torque99.5 N·m33.2 N·m1/3
As multiple of full load5.00 and 1.001.67 and 0.333

The equivalent tapping. A star connection puts \(1/\sqrt3\) of the line voltage across each winding, so it does exactly what an autotransformer set to

\[ x = \frac{1}{\sqrt3} = 0.577 = 57.7\% \]

would do, and the arithmetic agrees: \(x^2 = 1/3\) for the torque and \(x^2 = 1/3\) for the supply current. The star–delta starter is an autotransformer starter with one fixed tap and no autotransformer.

Two practical points the arithmetic does not show. First, the machine must be designed to run in delta at the supply voltage, and all six winding ends must be brought out. Second, the changeover from star to delta briefly disconnects the motor; when delta is re-made the machine is running but the currents are not in step with the supply, and a transient of several times full-load current can occur. Closed-transition starters exist to suppress it.

The one-third factor is two \(\sqrt3\) factors for the current and one squared \(\sqrt3\) for the torque — a coincidence of value, not of mechanism. Because both fall by the same factor, star–delta preserves the torque-per-ampere of direct-on-line starting exactly. That it costs nothing but a contactor is why it remains the commonest starter for medium cage motors, and the fixed 57.7% is why it is often not enough.
Answer(a) both ratios \(=1/3\)   (b) 50.0 A and 33.2 N·m \((0.333\,T_{FL})\)   (c) equivalent to a 57.7% tapping
Problem 3Exam levelAutotransformer Tappings

The same 15 kW motor is to be started through a three-phase autotransformer starter.

  1. Show that with a tapping \(x\) the motor current is \(xI_{sc}\) but the supply current is only \(x^2I_{sc}\).
  2. Find the motor current, supply current and starting torque at the 60% tapping.
  3. Find the tapping needed for a starting torque of half the full-load torque, and the supply current it draws.
  4. Compare with a stator-resistance starter set to give the same starting torque.
Solution

The motor side. The motor sees \(xV\) across an unchanged standstill impedance, so

\[ I_{\text{motor}} = \frac{xV_{ph}}{|Z_{01}|} = xI_{sc}, \qquad T_{st} = x^2T_{st,\text{DOL}} \]

Torque goes as the square because it goes as the square of the current at a fixed slip.

The supply side, and the reason for the second factor of \(x\). The autotransformer steps the voltage down by \(x\), so it steps the current down by \(x\) as well. Neglecting the starter's own losses and exciting current, volt-amperes in equal volt-amperes out:

\[ V\,I_{\text{supply}} = xV\times I_{\text{motor}} \;\Longrightarrow\; I_{\text{supply}} = x\,I_{\text{motor}} = x^2I_{sc} \]

This is the whole case for the autotransformer starter. A series resistance or reactance in the stator also gives \(xV\) at the motor, but the supply current then equals the motor current, \(xI_{sc}\), and none of the second reduction is obtained.

At the 60% tapping, with \(I_{sc} = 150\) A and \(T_{st,\text{DOL}} = 99.5\) N·m:

\[ I_{\text{motor}} = 0.60\times150 = 90.0\ \text{A}, \qquad I_{\text{supply}} = 0.36\times150 = 54.0\ \text{A} \]
\[ T_{st} = 0.36\times99.5 = 35.8\ \text{N·m} = 0.360\,T_{FL} \]

1.8 times full-load current from the supply for 36% of full-load torque. The motor terminals are at \(0.6\times400 = 240\) V during this period.

The tapping for half full-load torque:

\[ x^2T_{st,\text{DOL}} = 0.5\,T_{FL} \;\Longrightarrow\; x^2 = \frac{0.5\times99.5}{99.5} = 0.5 \;\Longrightarrow\; x = 0.707 \]
\[ I_{\text{motor}} = 0.707\times150 = 106.1\ \text{A}, \qquad I_{\text{supply}} = 0.5\times150 = 75.0\ \text{A} = 2.5\,I_{FL} \]

The tapping is the square root of the torque ratio required, a relation worth remembering: to double the starting torque, multiply the tapping by \(\sqrt2\).

The stator-resistance alternative. To get the same torque it must also apply \(x = 0.707\) at the motor, so the motor current is again 106.1 A — but that current now comes straight from the supply:

Starter for \(0.5\,T_{FL}\)Motor voltageMotor currentSupply currentLoss in starter
Autotransformer, 70.7% tap283 V106.1 A75.0 ASmall (transformer losses)
Stator resistance283 V106.1 A106.1 ALarge (\(I^2R\) in the resistors)

41% more supply current for the same torque, and the difference is burnt as heat in the starting resistors. The autotransformer costs more to buy and is worth it on any machine large enough for the question to arise.

The starter's own rating. During starting the autotransformer carries 106.1 A at 283 V on the motor side, which is \(\sqrt3(283)(106.1) = 52\) kVA — but only for a few seconds. Starting autotransformers are therefore rated for a short-time duty and a stated number of starts per hour, and are physically far smaller than a 52 kVA continuous unit.

The autotransformer is the only stator-side starter that reduces the supply current twice. Once because the motor voltage is lower, and again because the starter transforms. That gives it the same torque per supply ampere as direct-on-line starting — no better, but no worse — while a series resistance is a factor \(x\) worse and wastes energy doing it. Its second advantage is adjustability: taps at 50%, 65% and 80% are standard, where star–delta offers only 57.7%.
Answer(b) 90.0 A motor, 54.0 A supply, 35.8 N·m   (c) \(x = 70.7\%\), 75.0 A supply   (d) a stator resistance would draw 106.1 A for the same torque
Problem 4Exam levelRotor Resistance Starting

A three-phase, 50 Hz, 8-pole slip-ring induction motor has a star-connected rotor whose standstill emf is 200 V per phase, resistance 0.12 Ω per phase and standstill leakage reactance 0.6 Ω per phase. The full-load slip is 3%. Determine

  1. the slip and speed at which maximum torque occurs with the slip rings short-circuited
  2. the external resistance per phase that gives maximum torque at starting
  3. the starting torque with and without that resistance, each as a multiple of full-load torque
  4. the rotor current at starting in each case, as a multiple of the full-load rotor current
  5. the external resistance that would place maximum torque at 50% slip, as a starter step.
Solution

Set up the two working expressions. With \(R\) the total rotor resistance per phase,

\[ I_2 = \frac{sE_2}{\sqrt{R^2+(sX_2)^2}}, \qquad T \propto \frac{sE_2^2R}{R^2+(sX_2)^2} \]

Differentiating the torque with respect to \(s\) gives the standard condition \(R = sX_2\) at the maximum.

Maximum torque with the rings shorted:

\[ s_{\max T} = \frac{R_2}{X_2} = \frac{0.12}{0.6} = 0.20 \]
\[ N_s = \frac{120\times50}{8} = 750\ \text{rev/min}, \qquad N = 750(1-0.20) = 600\ \text{rev/min} \]

To bring that peak to standstill, put \(s_{\max T} = 1\):

\[ R_2+R_{ext} = X_2 = 0.6\ \Omega \;\Longrightarrow\; R_{ext} = 0.6-0.12 = 0.48\ \Omega\ \text{per phase} \]

Evaluate the three torques from \(T \propto sR/(R^2+(sX_2)^2)\), working in units of \(E_2^2\) which cancel in the ratios:

\[ T_{FL} \propto \frac{0.03(0.12)}{0.12^2+(0.03\times0.6)^2} = \frac{0.00360}{0.014724} = 0.2445 \]
\[ T_{st}\big|_{R=0.12} \propto \frac{1(0.12)}{0.12^2+0.6^2} = \frac{0.12}{0.3744} = 0.3205 \]
\[ T_{st}\big|_{R=0.60} \propto \frac{1(0.60)}{0.60^2+0.6^2} = \frac{0.60}{0.72} = 0.8333 \]
\[ \frac{T_{st}}{T_{FL}} = \frac{0.3205}{0.2445} = 1.31 \qquad\text{and}\qquad \frac{T_{st,\max}}{T_{FL}} = \frac{0.8333}{0.2445} = 3.41 \]

The rotor currents, which is where the method earns its reputation:

\[ I_{2,FL} = \frac{0.03(200)}{\sqrt{0.12^2+(0.018)^2}} = \frac{6.00}{0.12134} = 49.5\ \text{A} \]
\[ I_{2,st}\big|_{R=0.12} = \frac{200}{\sqrt{0.12^2+0.6^2}} = \frac{200}{0.6119} = 326.9\ \text{A} = 6.61\,I_{2,FL} \]
\[ I_{2,st}\big|_{R=0.60} = \frac{200}{\sqrt{0.6^2+0.6^2}} = \frac{200}{0.8485} = 235.7\ \text{A} = 4.77\,I_{2,FL} \]

Adding the resistance raised the torque from 1.31 to 3.41 times full load and at the same time lowered the current from 6.61 to 4.77 times full load. No stator-side starter can do that.

Put the two together:

Rotor circuit\(R\) per phase\(s_{\max T}\)Starting torqueStarting rotor currentTorque per ampere
Rings shorted0.12 Ω0.201.31 pu6.61 pu0.198
With 0.48 Ω added0.60 Ω1.003.41 pu4.77 pu0.715

A factor of 3.6 improvement in torque per ampere. It comes from the power factor: at \(R = X_2\) the rotor circuit is at 0.707 lagging instead of 0.196, so far more of the rotor current is in phase with the rotor emf and therefore producing torque.

A starter step at 50% slip. As the machine accelerates the resistance is cut out in stages, each stage chosen so the torque stays high. For the peak to sit at \(s = 0.5\):

\[ R_2+R_{ext} = 0.5X_2 = 0.30\ \Omega \;\Longrightarrow\; R_{ext} = 0.18\ \Omega\ \text{per phase} \]

And the torque there is \(0.5(0.30)/(0.09+0.09) = 0.8333\) in the same units — identical to the standstill maximum, as it must be. The peak value of the torque is \(3E_2^2/(2\omega_sX_2)\) and does not contain \(R\) at all; the resistance only chooses where the peak sits.

Rotor resistance is the only starting method that changes the machine rather than the supply to it. Every stator-side starter moves the operating point down a fixed characteristic; adding rotor resistance draws a new characteristic with the same peak in a different place. The cost is a wound rotor with slip rings, brushes and an external resistance bank — which is why cage motors dominate wherever the load will start on 0.3 pu of torque, and slip-ring machines survive on crushers, hoists and mills where it will not.
Answer(a) \(s = 0.20\), 600 rev/min   (b) \(R_{ext} = 0.48\ \Omega\)   (c) 1.31 pu rising to 3.41 pu   (d) 326.9 A (6.61 pu) falling to 235.7 A (4.77 pu)   (e) \(R_{ext} = 0.18\ \Omega\)
Problem 5Exam levelWill a Star–Delta Starter Do?

A 22 kW, 400 V, 50 Hz, 6-pole delta-connected cage induction motor has a full-load line current of 42 A and a full-load slip of 4%. Its standstill current at rated voltage is six times full load. It is to drive a compressor that requires 40% of full-load torque to break away, and the supply authority limits the starting current to 2.5 times full load.

  1. Decide whether a star–delta starter is acceptable on both counts.
  2. Find the lowest full-load slip a motor of this current ratio could have and still start the load on a star–delta starter.
  3. If the compressor were changed for one needing 60% of full-load torque, find the autotransformer tapping required and the resulting supply current.
Solution

Full-load quantities:

\[ N_s = \frac{120\times50}{6} = 1000\ \text{rev/min}, \qquad N = 960\ \text{rev/min} \]
\[ T_{FL} = \frac{22000}{2\pi(960)/60} = \frac{22000}{100.53} = 218.8\ \text{N·m} \]

Direct-on-line figures, from the current ratio:

\[ \frac{T_{st}}{T_{FL}}\bigg|_{\text{DOL}} = 6^2\times0.04 = 1.44 \qquad\Longrightarrow\qquad T_{st} = 315.1\ \text{N·m} \]
\[ I_{st,\text{DOL}} = 6\times42 = 252\ \text{A} \]

Apply the one-third factor to both:

\[ \frac{T_{st}}{T_{FL}}\bigg|_{Y\text{-}\Delta} = \frac{1.44}{3} = 0.48, \qquad I_{st,Y} = \frac{252}{3} = 84\ \text{A} = 2.0\,I_{FL} \]

Test both requirements:

RequirementLimitStar–delta givesVerdict
Breakaway torque≥ 0.40 \(T_{FL}\) = 87.5 N·m0.48 \(T_{FL}\) = 105.0 N·mPasses, 20% margin
Starting current≤ 2.5 \(I_{FL}\) = 105 A2.0 \(I_{FL}\) = 84 APasses, 20% margin

Acceptable on both counts — but the torque margin is thin. A 20% margin over breakaway torque means the machine accelerates slowly, and the starter must be timed to hold star long enough for the motor to reach a speed at which the transition to delta does not produce a large current surge.

The limiting slip. Setting the star–delta torque exactly equal to the requirement:

\[ \frac13\left(\frac{I_{sc}}{I_{FL}}\right)^{\!2}s_{FL} = 0.40 \;\Longrightarrow\; s_{FL} = \frac{3\times0.40}{36} = 0.0333 \]

A motor of the same current ratio but 3% slip — a slightly more efficient design — would not start this load on a star–delta starter. The better machine is the worse starter, because low slip means low rotor resistance and low rotor resistance means poor standstill torque.

The heavier compressor. With 0.60 pu of torque needed and 1.44 pu available direct on line:

\[ x^2 = \frac{0.60}{1.44} = 0.4167 \;\Longrightarrow\; x = 0.645 = 64.5\% \]
\[ I_{\text{supply}} = x^2I_{sc} = 0.4167\times252 = 105\ \text{A} = 2.5\,I_{FL} \]

Exactly at the supply limit, and it had to be: the torque and the supply current both scale as \(x^2\), so their ratio is a constant of the machine. Asking for \(0.60/0.48 = 1.25\) times the star–delta torque necessarily costs 1.25 times the star–delta current, and \(1.25\times2.0 = 2.5\).

Where that leaves the design. The 65% tapping is standard, so the job can be done — but there is now no margin at all on current. Any further increase in breakaway torque forces a change of machine: a higher-slip cage design, a deep-bar or double-cage rotor with better standstill torque, or a slip-ring motor with rotor resistance as in Problem 4.

Every stator-side starting question reduces to one number, and it is not adjustable. Torque and supply current both scale as \(x^2\), so \(T_{st}/I_{\text{supply}}\) is fixed at \(1.44/6 = 0.24\) per unit for this machine no matter which starter is chosen. Specifying a starter is therefore only ever a choice of where to sit on that line — and if no point on it satisfies both the load and the supply, the answer is a different motor.
Answer(a) yes — 0.48 pu torque against 0.40 required, 84 A against 105 A allowed   (b) \(s_{FL} = 3.33\%\)   (c) 64.5% tapping, 105 A
Problem 6CoreThe Four Methods Compared

Draw up a comparison of the starting methods for the 15 kW machine of Problems 1 to 3 — direct on line, star–delta, autotransformer at two tappings, and stator resistance — giving for each the motor voltage, motor current, supply current and starting torque. Add the rotor-resistance figures from the slip-ring machine of Problem 4 for comparison, and identify the figure of merit that separates the methods.

Solution

Recall the base quantities for the cage machine: \(I_{FL} = 30\) A, \(I_{sc} = 150\) A, \(T_{FL} = 99.5\) N·m and \(T_{st,\text{DOL}} = 99.5\) N·m, so \(I_{sc}/I_{FL} = 5.0\) and \(T_{st}/T_{FL} = 1.00\).

The comparison, every entry obtained from \(I_{\text{motor}} = xI_{sc}\) and \(T = x^2T_{st,\text{DOL}}\), with the supply current \(x^2I_{sc}\) for the transforming starters and \(xI_{sc}\) for the resistance starter:

MethodMotor voltageMotor currentSupply currentStarting torque\(T_{st}/I_{\text{supply}}\) (pu)
Direct on line400 V150.0 A150.0 A (5.00 pu)99.5 N·m (1.00 pu)0.200
Star–delta231 V50.0 A (line)50.0 A (1.67 pu)33.2 N·m (0.333 pu)0.200
Autotransformer, 60%240 V90.0 A54.0 A (1.80 pu)35.8 N·m (0.360 pu)0.200
Autotransformer, 70.7%283 V106.1 A75.0 A (2.50 pu)49.7 N·m (0.500 pu)0.200
Stator resistance, 70.7%283 V106.1 A106.1 A (3.54 pu)49.7 N·m (0.500 pu)0.141
Rotor resistance \(^\dagger\)full voltage4.77 pu4.77 pu3.41 pu0.715

\(^\dagger\) Figures for the slip-ring machine of Problem 4, quoted in per unit of its own full-load values; a cage motor cannot be started this way at all.

Read the last column. The four stator-side transforming methods give identical torque per supply ampere, 0.200 pu, because both quantities scale as \(x^2\):

\[ \frac{T_{st}}{I_{\text{supply}}} = \frac{x^2T_{st,\text{DOL}}}{x^2I_{sc}} = \frac{T_{st,\text{DOL}}}{I_{sc}} \qquad\text{independent of }x \]

The stator-resistance starter is worse by exactly the factor \(x\), and the rotor-resistance method is in a different class altogether.

The other considerations, which the table of numbers cannot show:

MethodCostAdjustable?Main drawback
Direct on lineLowestNoSupply disturbance; heavy rotor heating
Star–deltaLowNo — fixed at 57.7%Needs six leads and delta running; transition surge
AutotransformerModerateYes — typically 50/65/80%Bulky; short-time rated; more contactors
Stator resistanceLowYes, continuouslyEnergy wasted; poor torque per supply ampere
Rotor resistanceHighestYes, in stepsRequires a slip-ring machine with brushgear

Choosing for this machine. Suppose the load needs 0.35 pu of breakaway torque and the supply allows 2 pu of current. Star–delta gives 0.333 pu — just short. The 60% autotransformer tap gives 0.360 pu at 1.80 pu of current, and is the correct answer. The 70.7% tap would work too but at 2.50 pu, over the limit; direct on line is far over it; and a stator resistance set for 0.36 pu of torque would draw \(0.6\times5.0 = 3.0\) pu.

That is the whole design procedure: convert the load's torque requirement to a value of \(x\), read off the supply current, and check it against the limit. If no \(x\) satisfies both, the machine is wrong for the duty.

Four methods, one line, and one escape from it. Direct-on-line, star–delta and autotransformer starting all sit on the same straight line of torque against supply current — they differ only in where, in cost, and in adjustability. Stator resistance sits below the line and wastes energy. Rotor resistance is not on the line at all, because it acts on the rotor's power factor rather than on the applied voltage, and it is the reason slip-ring machines are still built.
AnswerAll transforming stator-side methods give \(T_{st}/I_{\text{supply}} = 0.200\) pu; stator resistance 0.141 pu; rotor resistance 0.715 pu
Formulas

Key Formulas

QuantityRelationNotes
Synchronous speed\(N_s = 120f/P\)Problems 1, 4, 5
Full-load torque\(T_{FL} = P_{\text{out}}/\omega_m\), \(\omega_m = 2\pi N/60\)Problems 1, 5
Starting torque ratio\(\dfrac{T_{st}}{T_{FL}} = \left(\dfrac{I_{sc}}{I_{FL}}\right)^{2}s_{FL}\)The key relation — Problems 1, 5
Reduced voltage\(I_{\text{motor}} = xI_{sc},\quad T_{st} = x^2T_{st,\text{DOL}}\)Problems 3, 5, 6
Autotransformer supply current\(I_{\text{supply}} = x^2I_{sc}\)Two reductions — Problem 3
Stator-resistance supply current\(I_{\text{supply}} = xI_{sc}\)One reduction only — Problems 3, 6
Tapping for a given torque\(x = \sqrt{T_{\text{required}}/T_{st,\text{DOL}}}\)Problems 3, 5
Star–delta\(\dfrac{I_{L,Y}}{I_{L,\Delta}} = \dfrac{T_{st,Y}}{T_{st,\Delta}} = \dfrac13\)Equivalent to \(x = 57.7\%\) — Problems 2, 5
Rotor current\(I_2 = \dfrac{sE_2}{\sqrt{R^2+(sX_2)^2}}\)\(R = R_2+R_{ext}\) — Problem 4
Torque–slip law\(T \propto \dfrac{sE_2^2R}{R^2+(sX_2)^2}\)Problem 4
Slip for maximum torque\(s_{\max T} = \dfrac{R_2+R_{ext}}{X_2}\)Problem 4
Resistance for maximum starting torque\(R_2+R_{ext} = X_2\)Problem 4
Maximum torque\(T_{\max} = \dfrac{3E_2^2}{2\omega_sX_2}\)Independent of \(R\) — Problem 4
Starting kVA\(S_{st} = \sqrt3\,V_LI_{st}\)Quoted per kW of rating — Problem 1
Figure of merit\(T_{st}/I_{\text{supply}}\)Constant for all transforming starters — Problem 6
Pitfalls

Common Mistakes

  1. Taking the star–delta current reduction as \(1/\sqrt3\). It is \(1/3\): one \(\sqrt3\) from the winding voltage and a second from the line-to-phase relation — Problem 2.

  2. Squaring the line-current ratio to get the star–delta torque ratio. That would give \(1/9\). Torque follows the winding current, whose ratio is \(1/\sqrt3\), so the torque ratio is \(1/3\) — Problem 2.

  3. Using \(xI_{sc}\) for the supply current with an autotransformer. The starter transforms the current as well as the voltage, so the supply sees \(x^2I_{sc}\) — 54 A, not 90 A, at the 60% tap — Problem 3.

  4. Using \(x^2I_{sc}\) for a stator-resistance starter. A series element passes the motor current straight through; there is no second reduction — Problems 3 and 6.

  5. Forgetting the slip in \((I_{sc}/I_{FL})^2s_{FL}\). Without it the starting torque of Problem 1 comes out 25 times full load instead of once — Problems 1 and 5.

  6. Assuming a low-slip motor is the better starter. Low slip means low rotor resistance and therefore low standstill torque; the 3.33% machine of Problem 5 fails on a load the 4% machine starts.

  7. Believing rotor resistance raises the maximum torque. \(T_{\max} = 3E_2^2/2\omega_sX_2\) contains no \(R\). The resistance moves the peak to a higher slip; it does not make it taller — Problem 4.

  8. Expecting the rotor current to rise when resistance is added. It falls, from 6.61 to 4.77 pu, while the torque rises — which is the entire point of the method — Problem 4.

  9. Applying rotor-resistance starting to a cage motor. There is no external rotor circuit to connect to. The nearest cage equivalent is a deep-bar or double-cage rotor, whose effective resistance is high at standstill by design — Problems 4 and 6.

  10. Sizing a starting autotransformer for continuous duty. It carries 52 kVA for a few seconds in Problem 3 and nothing thereafter; it is rated for a stated number of starts per hour, not continuously.

  11. Quoting a tapping without saying whether it refers to voltage or torque. A "50% tap" applies half the voltage and gives a quarter of the torque — Problems 3 and 5.

  12. Ignoring the star-to-delta transition. The changeover briefly opens the supply and can produce a current transient larger than the star starting current itself — Problem 2.

Looking Ahead

Set 30 put the starting point on the circle diagram at four times rated current for 86% of rated torque, and this set has shown what can and cannot be done about it. Everything acting on the stator moves along one fixed line: torque and supply current both scale as the square of the applied voltage, so the ratio between them is a property of the machine that no starter can improve. Only the rotor circuit offers a way off that line, and it does so by improving the rotor's power factor at standstill — more torque for less current, at the price of slip rings.

The external resistance of Problem 4, however, is not switched out and forgotten. Left in place it holds the machine at a higher slip and a lower speed, which is the oldest method of speed control there is. The same three levers — rotor resistance, stator voltage, and supply frequency — that a starter uses for a few seconds can be used continuously, and reversing the phase sequence or driving the rotor above synchronism turns the motor into a brake.

Next: Set 32 — Speed Control and Braking, where rotor resistance, stator voltage, constant V/f and pole changing are worked through, and plugging and regenerative braking are given their slips.