Solved Problems · Set 32

Speed Control and Braking

Part 4 · Induction Machines — speed is fixed by frequency, poles and slip, so every method of control is an attack on one of the three; and reversing the sense of any of them turns the motor into a brake.

Prof. Mithun Mondal 6 solved problems GATE · ESE · University

Set 32 — Speed Control and Braking

The rotor speed of an induction motor is \(N = (120f/P)(1-s)\), and there is nothing else in the expression. Every method of speed control therefore attacks the frequency, the pole number or the slip, and each has a characteristic price: changing the slip wastes power in the rotor circuit, changing the pole number gives only a few fixed speeds, and changing the frequency requires an inverter and careful attention to the flux. This set works one problem on each, and adds the low-speed voltage boost that constant V/f operation needs.

Braking is the same physics with the sign changed. Drive the rotor faster than the field and the slip goes negative and the machine generates; reverse the field while the rotor still turns forwards and the slip exceeds unity and the machine brakes hard, dissipating in the rotor rather more energy than the load ever stored. The last two problems put numbers to both, including the energy balance that decides whether a rotor can survive being plugged.

Part 4 · Testing and Control · 6 solved problems

i Method Recap
  • Three levers and no others.

    \[ N = \frac{120f}{P}\left(1-s\right) \]

    Frequency control and pole changing act on the synchronous speed; rotor resistance and stator voltage act on the slip. The first two can be efficient; the last two cannot.

  • Rotor resistance control, at constant torque. Constant torque means constant rotor current and constant air-gap power, and the torque expression \(T\propto sE_2^2R/(R^2+(sX_2)^2)\) then reduces, for small slip, to \(s\propto R\):

    \[ \frac{s_2}{s_1} = \frac{R_2+R_{ext}}{R_2} \]

    The rotor circuit's efficiency is \(1-s\), so the loss is paid in full: running at half speed at constant torque throws away half the air-gap power.

  • Stator voltage control. Torque at a given slip goes as \(V^2\), and so does the breakdown torque, so the range is small and the machine stalls if

    \[ \left(\frac{V}{V_{\text{rated}}}\right)^{\!2}T_{\max,\text{rated}} < T_{\text{load}} \]

    It suits fan and pump loads, whose torque falls as \(N^2\) and whose power falls as \(N^3\), and it needs a high-resistance rotor to give any useful range at all.

  • Constant V/f. Air-gap flux is proportional to \(V/f\), so holding that ratio keeps the flux, and hence the torque capability, constant:

    \[ T_{\max} = \frac{3V_{ph}^2}{2\omega_s\left[R_1+\sqrt{R_1^2+X_{01}^2}\right]} \;\xrightarrow[\;R_1\to0\;]{}\; \frac{3V_{ph}^2}{2\omega_sX_{01}} = \text{constant} \]

    At low frequency \(R_1\) is no longer negligible against \(X_{01}\propto f\), so the torque falls away and the voltage must be raised above the straight-line law — the boost.

  • At constant torque the slip speed is constant, not the slip, so a given load holds the same \(sN_s\) at every frequency.

  • Pole changing gives discrete speeds only. A consequent-pole winding doubles the pole number by reconnection; two separate windings give two more; the combination gives four speeds. The two connections are arranged for either constant torque or constant power.

  • The three braking modes, by slip:

    \[ \text{regenerative: } s \lt 0, \qquad \text{motoring: } 0 \lt s \lt 1, \qquad \text{plugging: } 1 \lt s \lt 2 \]

    Reversing two supply leads while running at slip \(s\) makes the slip \(2-s\) instantly. Plugging a pure inertia to rest from synchronous speed dissipates \(3\times\tfrac12J\omega_s^2\) in the rotor.

Problem 1Exam levelRotor Resistance Control

A 400 V, 50 Hz, 6-pole three-phase slip-ring induction motor delivers 20 kW at a slip of 4% with the slip rings short-circuited. The rotor is star-connected with a resistance of 0.05 Ω per phase. The speed is to be reduced to 800 rev/min by inserting external resistance, the load torque remaining constant. Determine

  1. the external resistance required per phase
  2. the rotor current, before and after
  3. the output, the rotor copper loss and the loss in the external bank at the reduced speed
  4. the efficiency of the rotor circuit in each case, and the shaft torque.
Solution

The two operating slips:

\[ N_s = \frac{120\times50}{6} = 1000\ \text{rev/min}, \qquad N_1 = 1000(1-0.04) = 960\ \text{rev/min} \]
\[ s_2 = \frac{1000-800}{1000} = 0.20 \]

Constant torque fixes the rotor current, and that is the key to the whole calculation. Torque is \(3I_2^2R/(s\omega_s)\), so if \(T\) and \(I_2\) are both unchanged then \(R/s\) is unchanged:

\[ \frac{R_2+R_{ext}}{s_2} = \frac{R_2}{s_1} \;\Longrightarrow\; R_2+R_{ext} = R_2\,\frac{s_2}{s_1} = 0.05\times\frac{0.20}{0.04} = 0.25\ \Omega \]
\[ R_{ext} = 0.25-0.05 = 0.20\ \Omega\ \text{per phase} \]

Slip is proportional to total rotor resistance at constant torque — five times the resistance, five times the slip. The relation is exact when \((sX_2)^2\) may be neglected against \(R^2\), and at \(s = 0.2\) with \(R = 0.25\) Ω that is still comfortably true.

The air-gap power is also unchanged, because \(P_g = T\omega_s\) and both factors are fixed:

\[ P_g = \frac{P_m}{1-s_1} = \frac{20000}{0.96} = 20833\ \text{W} \]
\[ T = \frac{P_g}{\omega_s} = \frac{20833}{2\pi(1000)/60} = \frac{20833}{104.72} = 198.9\ \text{N·m} \]

The rotor current, from the copper loss at the original operating point:

\[ P_{cu2} = s_1P_g = 0.04\times20833 = 833\ \text{W} = 3I_2^2R_2 \]
\[ I_2 = \sqrt{\frac{833}{3\times0.05}} = 74.5\ \text{A} \]
\[ \text{After: } I_2 = \sqrt{\frac{s_2P_g}{3(R_2+R_{ext})}} = \sqrt{\frac{4167}{3\times0.25}} = 74.5\ \text{A}\;\checkmark \]

Identical, as constant torque requires. The stator current is essentially unchanged too, so the machine is drawing the same input while delivering less — which is exactly where the loss appears.

The new power balance:

\[ P_m = (1-s_2)P_g = 0.80\times20833 = 16667\ \text{W} \]
\[ P_{cu2,\text{total}} = s_2P_g = 0.20\times20833 = 4167\ \text{W} \]
\[ \text{in the rotor: } 4167\times\frac{0.05}{0.25} = 833\ \text{W}, \qquad \text{in the bank: } 4167\times\frac{0.20}{0.25} = 3333\ \text{W} \]

The rotor itself is no hotter than before — same current, same resistance — and all the extra loss is in the external resistors, where it can be got rid of. That is the one redeeming feature of the method.

Set the two conditions side by side:

QuantityRings shortedWith 0.20 Ω added
Speed960 rev/min800 rev/min
Slip0.040.20
Torque198.9 N·m198.9 N·m
Rotor current74.5 A74.5 A
Air-gap power20833 W20833 W
Output20000 W16667 W
Rotor-circuit loss833 W4167 W
Rotor-circuit efficiency \((1-s)\)96%80%

A 17% speed reduction has cost 3.3 kW — a sixth of the machine's output — burnt in a resistor bank. Take the speed down to half and the rotor circuit would be 50% efficient.

Rotor resistance control is a torque-preserving, power-wasting method, and its loss is not incidental but structural. The air-gap power is set by the torque and the synchronous speed, neither of which the resistance touches; the shaft takes \((1-s)\) of it and the rotor circuit must take the rest. Simple, smooth and cheap to build; unacceptable for anything running continuously below about 80% speed. The alternative that recovers the slip power instead of burning it is the slip-power-recovery scheme, of which this problem is the crude ancestor.
Answer(a) \(R_{ext} = 0.20\ \Omega\)   (b) 74.5 A in both cases   (c) 16.67 kW output, 833 W in the rotor, 3333 W in the bank   (d) 96% falling to 80%; \(T = 198.9\ \text{N·m}\)
Problem 2Exam levelStator Voltage on a Fan Load

A 400 V, 50 Hz, 4-pole cage induction motor with a high-resistance rotor runs at a slip of 10% when driving a fan that absorbs 15 kW at that speed. Its breakdown torque at rated voltage is 2.2 times full-load torque. The fan torque varies as the square of the speed and its power as the cube. The stator voltage is reduced to 70% of rated by a solid-state controller.

  1. Find the new slip and speed.
  2. Find the new shaft power and the rotor copper loss, before and after.
  3. Find the lowest voltage at which the machine could drive a constant-torque load of full-load torque, and use it to explain why voltage control is offered for fans and not for conveyors.
Solution

Write the two characteristics that must intersect. On the working part of its curve the motor's torque is proportional to the slip and to the square of the applied voltage; the fan's torque is proportional to the square of the speed:

\[ T_{\text{motor}} = k\,V^2s, \qquad T_{\text{fan}} = c\,N^2 = cN_s^2(1-s)^2 \]

The first is the low-slip linear approximation of the torque–slip curve, valid while \((sX_2)^2 \ll R_2^2\) — which is why the machine must have a high-resistance rotor for this method to work over any range.

Set the two equal at each voltage and divide, so that \(k\), \(c\) and \(N_s\) all cancel:

\[ \frac{(0.7V)^2s_2}{V^2s_1} = \frac{(1-s_2)^2}{(1-s_1)^2} \;\Longrightarrow\; \frac{0.49\,s_2}{0.10} = \frac{(1-s_2)^2}{0.81} \]
\[ 3.969\,s_2 = 1-2s_2+s_2^2 \;\Longrightarrow\; s_2^2 - 5.969\,s_2 + 1 = 0 \]
\[ s_2 = \frac{5.969-\sqrt{35.629-4}}{2} = \frac{5.969-5.624}{2} = 0.1725 \]

The other root, 5.797, is outside the physical range and is discarded.

The speeds:

\[ N_s = 1500\ \text{rev/min}, \qquad N_1 = 1500(0.90) = 1350\ \text{rev/min} \]
\[ N_2 = 1500(1-0.1725) = 1241\ \text{rev/min} \]

A 30% voltage reduction has bought an 8% speed reduction. That is the fundamental limitation of the method: slip is a poor lever because it only has the range 0 to \(s_{\max T}\) to work in.

The fan power falls as the cube of speed:

\[ P_2 = 15000\left(\frac{1241}{1350}\right)^{\!3} = 15000\times0.7771 = 11657\ \text{W} \]

The rotor copper loss, before and after:

\[ P_{cu2,1} = \frac{s_1}{1-s_1}P_1 = \frac{0.10}{0.90}\times15000 = 1667\ \text{W} \]
\[ P_{cu2,2} = \frac{s_2}{1-s_2}P_2 = \frac{0.1725}{0.8275}\times11657 = 2430\ \text{W} \]
VoltageSlipSpeedShaft powerAir-gap powerRotor copper loss
400 V (100%)0.1001350 rev/min15.00 kW16.67 kW1667 W
280 V (70%)0.17251241 rev/min11.66 kW14.09 kW2430 W

The rotor loss went up while the output went down — that is what slip control always does. But it went up by only 763 W. Had the load been a constant-torque one, the air-gap power would have stayed at 16.67 kW and the rotor loss would have been \(0.1725\times16667 = 2875\) W. The falling torque demand is what keeps the fan case tolerable.

The stalling limit for a constant-torque load. Breakdown torque scales as \(V^2\), so the motor can hold full-load torque only while

\[ \left(\frac{V}{V_{\text{rated}}}\right)^{\!2}\times2.2\,T_{FL} \ge T_{FL} \;\Longrightarrow\; \frac{V}{V_{\text{rated}}} \ge \sqrt{\frac{1}{2.2}} = 0.674 \]

At 67.4% of rated voltage the peak of the torque curve has fallen to exactly the load torque, and the slightest further reduction makes the machine stall. And 67.4% of voltage on a constant-torque load buys a speed reduction of only a few per cent before the curve becomes unstable.

Why the fan is different. As the fan slows it asks for less torque, so the operating point moves down the load curve as well as down the motor curve, and the intersection remains on the stable side. A conveyor or a hoist demands the same torque at every speed, so the motor curve must be pushed down while the load line stays put — and the two lose contact at 67.4% voltage. Fans and centrifugal pumps are the only loads for which stator-voltage control gives a usable range, and even then the range is modest and the rotor loss real.

Voltage control does not change what the machine can do; it changes how much of it the machine will do. The whole torque–slip curve is scaled vertically by \(V^2\), so both the useful torque and the stability margin shrink together. It is cheap, it is smooth, it needs no access to the rotor, and it is only ever right for a load whose own torque falls with speed at least as fast as the motor's ability to supply it.
Answer(a) \(s = 0.1725\), 1241 rev/min   (b) 11.66 kW; rotor loss 1667 W → 2430 W   (c) 67.4% of rated voltage
Problem 3ChallengeConstant V/f and the Boost

A 400 V, 50 Hz, 4-pole star-connected cage induction motor has a stator resistance of 0.5 Ω per phase and a total standstill leakage reactance of 3.0 Ω per phase at 50 Hz. It is supplied from an inverter operating on the constant V/f law. The full-load slip at 50 Hz is 4%.

  1. State the V/f ratio and the applied voltage and synchronous speed at 25 Hz and at 10 Hz.
  2. Show that the maximum torque would be independent of frequency if the stator resistance were negligible, and evaluate it on that assumption.
  3. Evaluate the maximum torque at 50, 25 and 10 Hz with the stator resistance included.
  4. Find the voltage that must be applied at 10 Hz to restore the 50 Hz maximum torque, and hence the boost.
  5. Find the speed at 25 Hz when the machine drives its rated torque.
Solution

The V/f law and its consequences:

\[ \frac{V}{f} = \frac{400}{50} = 8.0\ \text{V per Hz} \]
FrequencyLine voltagePhase voltage\(N_s\)\(\omega_s\)\(X_{01}\)
50 Hz400 V230.94 V1500 rev/min157.08 rad/s3.00 Ω
25 Hz200 V115.47 V750 rev/min78.54 rad/s1.50 Ω
10 Hz80 V46.19 V300 rev/min31.42 rad/s0.60 Ω

Both the synchronous speed and the reactance are proportional to frequency; the resistance is not, and that single fact is the whole of parts (c) and (d).

The ideal argument. With \(R_1\) neglected the maximum torque is

\[ T_{\max} = \frac{3V_{ph}^2}{2\omega_sX_{01}} \]

and every symbol on the right carries a factor of frequency: \(V \propto f\), \(\omega_s \propto f\), \(X_{01}\propto f\). So \(T_{\max} \propto f^2/(f\cdot f)\), a constant. Evaluating at 50 Hz:

\[ T_{\max} = \frac{3(230.94)^2}{2(157.08)(3.00)} = \frac{160000}{942.5} = 169.8\ \text{N·m} \]

This is the promise of constant V/f: constant flux, and therefore the machine's full torque capability available all the way down to zero speed.

Now include the stator resistance, which changes the denominator to \(R_1+\sqrt{R_1^2+X_{01}^2}\):

\[ T_{\max} = \frac{3V_{ph}^2}{2\omega_s\left[R_1+\sqrt{R_1^2+X_{01}^2}\right]} \]
\[ 50\ \text{Hz}:\quad \frac{3(230.94)^2}{2(157.08)\left[0.5+\sqrt{0.25+9.00}\right]} = \frac{160000}{314.16\times3.5414} = 143.8\ \text{N·m} \]
\[ 25\ \text{Hz}:\quad \frac{3(115.47)^2}{2(78.54)\left[0.5+\sqrt{0.25+2.25}\right]} = \frac{40000}{157.08\times2.0811} = 122.4\ \text{N·m} \]
\[ 10\ \text{Hz}:\quad \frac{3(46.19)^2}{2(31.42)\left[0.5+\sqrt{0.25+0.36}\right]} = \frac{6400}{62.83\times1.2810} = 79.5\ \text{N·m} \]

Read what has happened. The constant-flux promise fails progressively as the frequency falls:

Frequency\(X_{01}/R_1\)\(T_{\max}\) ideal\(T_{\max}\) actualFraction retained
50 Hz6.0169.8 N·m143.8 N·m100% (reference)
25 Hz3.0169.8 N·m122.4 N·m85%
10 Hz1.2169.8 N·m79.5 N·m55%

The cause is visible in the second column. At 50 Hz the resistance is a sixth of the reactance and barely matters; at 10 Hz it is comparable with it, and a fixed 0.5 Ω is now taking a serious fraction of a phase voltage that has fallen to 46 V.

The boost. Solve the same expression for the voltage that restores 143.8 N·m at 10 Hz:

\[ V_{ph}^2 = \frac{2\omega_s\left[R_1+\sqrt{R_1^2+X_{01}^2}\right]T_{\max}}{3} = \frac{62.83\times1.2810\times143.8}{3} = 3858 \]
\[ V_{ph} = 62.1\ \text{V} \qquad\Longrightarrow\qquad V_L = 62.1\sqrt3 = 107.6\ \text{V} \]
\[ \text{boost} = 107.6-80.0 = 27.6\ \text{V},\ \text{i.e. }34\%\text{ above the straight-line law} \]

In practice the inverter's V/f characteristic is given a fixed offset at zero frequency rather than a curve — the "IR compensation" or "torque boost" setting — chosen to be roughly the stator resistance drop at rated current. Here \(I_{ph}R_1\) at a current of the order of 40 A would be about 20 V per phase, which is the right order.

Speed at 25 Hz on rated torque. At constant torque the machine holds the same slip speed, not the same slip, because the torque depends on the rotor frequency rather than on the slip alone:

\[ \Delta N = s\,N_s\Big|_{50\ \text{Hz}} = 0.04\times1500 = 60\ \text{rev/min} \]
\[ N\Big|_{25\ \text{Hz}} = 750-60 = 690\ \text{rev/min}, \qquad s = \frac{60}{750} = 0.08 \]

The slip has doubled while the slip speed and the rotor frequency (2 Hz) are unchanged. This is the practical signature of V/f control: the speed error caused by loading is a fixed number of rev/min at every setting, which is why open-loop V/f drives hold speed poorly at low frequency and a slip-compensation term is added.

Constant V/f keeps the flux constant, and the flux is what the torque capability is made of — but only while the resistance can be ignored. Below roughly a tenth of rated frequency the stator resistance drop is no longer a rounding error on the applied voltage, and the law must be corrected. Everything characteristic of a modern inverter drive — the boost setting, the minimum-frequency limit, the move to vector control for full torque at zero speed — follows from the two lines of this problem.
Answer(a) 8 V/Hz; 200 V at 750 rev/min, 80 V at 300 rev/min   (b) 169.8 N·m   (c) 143.8, 122.4 and 79.5 N·m   (d) 107.6 V, a boost of 27.6 V   (e) 690 rev/min at \(s = 0.08\)
Problem 4CorePole Changing

A three-phase, 50 Hz cage induction motor has a stator winding that can be reconnected by the consequent-pole method from 4 poles to 8 poles. On 4 poles it delivers 22 kW at a slip of 4%; on 8 poles the slip at the same torque is 5%.

  1. Find the synchronous and running speeds on both connections.
  2. Find the torque on 4 poles, and the output on 8 poles if the changeover is arranged for constant torque.
  3. State what would be obtained instead if the changeover were arranged for constant power.
  4. State how four speeds could be obtained from one machine, and give them.
Solution

The two synchronous speeds:

\[ N_s\big|_{4} = \frac{120\times50}{4} = 1500\ \text{rev/min}, \qquad N_s\big|_{8} = \frac{120\times50}{8} = 750\ \text{rev/min} \]
\[ N\big|_{4} = 1500(0.96) = 1440\ \text{rev/min}, \qquad N\big|_{8} = 750(0.95) = 712.5\ \text{rev/min} \]

Doubling the poles halves the speed exactly; the difference in slip makes the running speeds not quite a factor of two apart.

The 4-pole torque:

\[ T = \frac{22000}{2\pi(1440)/60} = \frac{22000}{150.80} = 145.9\ \text{N·m} \]

Constant-torque changeover. If the reconnection is arranged so the machine develops the same torque on both connections, the output follows the speed:

\[ P\big|_{8} = T\,\omega_m = 145.9\times\frac{2\pi(712.5)}{60} = 145.9\times74.61 = 10885\ \text{W} \]
\[ \frac{P_8}{P_4} = \frac{10885}{22000} = 0.495 \approx \frac{N_8}{N_4} \]

Half the speed, half the power, same torque. This is the connection used for conveyors, hoists and any load whose torque demand does not change with speed. In winding terms it is the series-delta to parallel-star change.

Constant-power changeover is the other standard arrangement (parallel-star to series-delta). It holds the output at 22 kW on both connections, so the torque on 8 poles becomes

\[ T\big|_{8} = \frac{22000}{74.61} = 294.9\ \text{N·m} = 2.02\,T_4 \]

Double the torque at half the speed. Machine tools use it, because the cutting power required is roughly the same at every spindle speed.

Four speeds from one machine. A single consequent-pole winding gives two speeds in the ratio 2 : 1 and nothing else. Two independent windings, each pole-changeable, give four:

WindingConnectionPoles\(N_s\) at 50 Hz
ANormal61000 rev/min
BNormal8750 rev/min
AConsequent pole12500 rev/min
BConsequent pole16375 rev/min

The second winding sits in the same slots as the first and is idle whenever the other is energised, so a four-speed machine is physically larger and dearer than a single-speed one of the same rating. Pole-amplitude modulation is the refinement that obtains two speeds in a ratio other than 2 : 1 from a single winding.

What pole changing is and is not good for. The speeds are discrete, so no continuous adjustment is possible — but each of them is a synchronous speed, so the machine runs at a low slip and full efficiency at every setting. Nothing is wasted, which is precisely what rotor-resistance and voltage control cannot claim. It remains common on fans, pumps, lifts and machine tools where two or four fixed speeds are all that is wanted, and it is confined to cage machines, since a wound rotor would have to be re-poled as well.

Pole changing is the only method on this page that costs nothing in efficiency. It moves the synchronous speed rather than the slip, so the machine still runs a few per cent below whatever speed it is set to, and the rotor loss stays at a few per cent of the air-gap power. Its price is paid in copper and switchgear rather than in heat, and it buys a handful of fixed speeds rather than a range.
Answer(a) 1500/1440 and 750/712.5 rev/min   (b) \(T = 145.9\ \text{N·m}\), output 10.89 kW   (c) 22 kW at 294.9 N·m   (d) 1000, 750, 500, 375 rev/min
Problem 5Exam levelPlugging

A 30 kW, 400 V, 50 Hz, 4-pole cage induction motor runs at 1440 rev/min on full load. Referred to the stator, its rotor resistance is 0.4 Ω and the total standstill leakage reactance is 2.0 Ω per phase. Two supply leads are interchanged while the machine is running at full load, in order to bring it rapidly to rest. The total inertia referred to the shaft is 8 kg·m² and the load torque may be neglected during braking.

  1. Find the slip and the rotor frequency immediately after the reversal.
  2. Find the braking torque at that instant, as a multiple of full-load torque.
  3. Find the energy dissipated in the rotor in bringing the machine to rest, and how it divides between the supply and the stored kinetic energy.
  4. Find the rotor resistance that would give maximum braking torque at the instant of reversal.
Solution

Reversing two leads reverses the direction of the rotating field. The rotor, still turning forwards at 1440 rev/min, now runs against a field going backwards at 1500 rev/min, so the relative speed is the sum:

\[ s' = \frac{-1500-1440}{-1500} = \frac{2940}{1500} = 1.96 = 2-s \]
\[ f_2 = s'f = 1.96\times50 = 98\ \text{Hz} \]

Nearly twice line frequency in the rotor bars, and it falls to 50 Hz only when the machine reaches standstill. Deep-bar effects are therefore pronounced during plugging.

The full-load torque, for reference:

\[ T_{FL} = \frac{30000}{2\pi(1440)/60} = \frac{30000}{150.80} = 198.9\ \text{N·m} \]

Compare the two torques using \(T \propto sR_2'/\left[R_2'^2+(sX)^2\right]\) at constant applied voltage:

\[ s = 0.04:\quad \frac{0.04(0.4)}{0.16+(0.08)^2} = \frac{0.0160}{0.1664} = 0.09615 \]
\[ s' = 1.96:\quad \frac{1.96(0.4)}{0.16+(3.92)^2} = \frac{0.7840}{15.5264} = 0.05049 \]
\[ \frac{T_{\text{brake}}}{T_{FL}} = \frac{0.05049}{0.09615} = 0.525 \qquad\Longrightarrow\qquad T_{\text{brake}} = 104.4\ \text{N·m} \]

Only about half full-load torque, because at \(s' = 1.96\) the rotor reactance \(s'X = 7.84\) Ω swamps the 0.4 Ω of resistance and the rotor power factor collapses to 0.051. Plugging a cage motor gives a modest braking torque and a very large current.

The energy balance. With the field reversed, the air-gap power flows into the rotor from the supply while the kinetic energy also flows into it from the shaft; both end up as rotor copper loss. Writing \(J\,d\omega_m/dt = T\) and integrating from \(\omega_{m0}\) to zero:

\[ W_{cu2} = \int T\left(\omega_s+\omega_m\right)dt = J\int_{0}^{\omega_{m0}}\left(\omega_s+\omega_m\right)d\omega_m = J\left(\omega_s\omega_{m0}+\tfrac12\omega_{m0}^2\right) \]
\[ \omega_s = 157.08\ \text{rad/s}, \qquad \omega_{m0} = \frac{2\pi(1440)}{60} = 150.80\ \text{rad/s} \]
\[ W_{cu2} = 8\left(157.08\times150.80 + \tfrac12(150.80)^2\right) = 8(23687+11370) = 280.5\ \text{kJ} \]

Split it into its two sources:

SourceExpressionEnergyShare
Drawn from the supply\(J\omega_s\omega_{m0}\)189.5 kJ68%
Kinetic energy of the drive\(\tfrac12J\omega_{m0}^2\)91.0 kJ32%
Total in the rotor280.5 kJ100%

The supply supplies twice as much energy as the load gives up, and every joule of it is dissipated in the rotor. For a machine plugged from very nearly synchronous speed the total is \(3\times\tfrac12J\omega_s^2\) — three times the stored kinetic energy, and three times the energy that a free run-up from rest would dissipate.

Why the supply must be opened at standstill. Nothing in the physics stops the machine at zero speed — the reversed field continues to produce torque and the machine simply accelerates the other way. A zero-speed relay or a plugging switch is therefore an essential part of the scheme.

Maximum braking torque. The condition is the same as for maximum motoring torque, \(R = sX\), applied at \(s' = 1.96\):

\[ R_2'+R_{ext}' = 1.96\times2.0 = 3.92\ \Omega \;\Longrightarrow\; R_{ext}' = 3.52\ \Omega\ \text{referred to the stator} \]
\[ T \propto \frac{1.96(3.92)}{3.92^2+3.92^2} = \frac{7.683}{30.73} = 0.2500 \;\Longrightarrow\; \frac{T}{T_{FL}} = \frac{0.2500}{0.09615} = 2.60 \]

2.60 times full-load torque instead of 0.525 — a fivefold improvement, obtained by making the rotor circuit resistive at 98 Hz. It requires a slip-ring machine, which is why heavy plugging duty is a slip-ring application.

Plugging is fast, crude and expensive in energy. Its slip lies between 1 and 2, its rotor frequency is nearly double line frequency, and it dumps three times the drive's kinetic energy into the rotor for every stop. On a cage machine the torque it delivers is poor as well, because the rotor power factor at \(s \approx 2\) is dreadful. It is used where stopping time matters more than anything else — machine tools, cranes, mill drives — and always with a means of removing the supply at zero speed.
Answer(a) \(s' = 1.96\), \(f_2 = 98\ \text{Hz}\)   (b) \(0.525\,T_{FL} = 104.4\ \text{N·m}\)   (c) 280.5 kJ, being 189.5 kJ from the supply and 91.0 kJ of kinetic energy   (d) \(R_{ext}' = 3.52\ \Omega\), giving \(2.60\,T_{FL}\)
Problem 6Exam levelRegenerative Braking

The 30 kW, 4-pole, 50 Hz machine of Problem 5 drives a hoist. While a load is being lowered the hoist drives the motor at 1560 rev/min against a torque of 198.9 N·m. The stator copper and core losses total 1.5 kW.

  1. Find the slip, the rotor frequency and the direction of power flow.
  2. Find the mechanical input, the air-gap power, the rotor copper loss and the power returned to the supply.
  3. Find the slip if the machine, running at 1440 rev/min on 4 poles, were suddenly reconnected to 8 poles, and comment.
  4. Tabulate the three braking modes with their slip ranges and state what limits each.
Solution

Above synchronous speed the slip is negative:

\[ s = \frac{N_s-N}{N_s} = \frac{1500-1560}{1500} = -0.04 \]
\[ f_2 = |s|f = 0.04\times50 = 2\ \text{Hz} \]

The rotor now cuts the field in the opposite sense, so the rotor emf, the rotor current and the torque all reverse: the machine develops a torque opposing rotation, and power flows from shaft to supply. It has become an induction generator.

The power balance, taken in the direction of flow. Mechanical input first:

\[ \omega_m = \frac{2\pi(1560)}{60} = 163.36\ \text{rad/s}, \qquad P_m = T\omega_m = 198.9\times163.36 = 32493\ \text{W} \]
\[ P_g = T\omega_s = 198.9\times157.08 = 31243\ \text{W} \]
\[ P_{cu2} = P_m-P_g = 32493-31243 = 1250\ \text{W} = |s|P_g\;\checkmark \]

What reaches the line:

\[ P_{\text{returned}} = P_g - \left(P_{cu1}+P_i\right) = 31243-1500 = 29743\ \text{W} \]
StagePowerNote
Mechanical input at the shaft32493 WThe descending load
Rotor copper loss1250 W\(|s|P_g\), small because \(|s|\) is small
Across the air gap to the stator31243 WDirection reversed
Stator copper and core loss1500 WUnchanged in sign
Returned to the supply29743 W91.5% of the mechanical input

Compare Problem 5: plugging dissipated 280 kJ to stop the same machine, while regeneration returns 91.5% of what it receives. That difference is the whole argument for regenerative braking wherever the duty allows it.

The machine still needs the supply. The magnetising current comes from the line, so the stator must stay connected and the line must be live: an induction machine cannot regenerate into a dead network without capacitors to supply the reactive power. It also draws lagging reactive power while exporting real power — the current reverses in phase but not in quadrature.

Regeneration by pole changing. Switching the machine of Problem 4 from 4 poles to 8 while it runs at 1440 rev/min drops the synchronous speed to 750, so

\[ s = \frac{750-1440}{750} = -0.92, \qquad f_2 = 0.92\times50 = 46\ \text{Hz} \]

A very large negative slip, so a heavy braking torque and a large current — the machine regenerates strongly while decelerating from 1440 to about 712 rev/min, after which it motors again. This is the standard way of obtaining a fast, efficient deceleration between two speeds on a multi-speed drive, and it is why lift motors are often pole-changing machines.

The three modes together:

ModeSpeedSlipRotor frequencyPower flowLimitation
Motoring\(0 < N < N_s\)\(0 < s < 1\)\(sf\), 0 to 50 HzSupply → shaft
Regenerative\(N > N_s\)\(s < 0\)\(|s|f\), 2 Hz hereShaft → supplyCannot brake below \(N_s\); needs a live supply
Plugging\(N > 0\), field reversed\(1 < s < 2\)\(sf\), 98 down to 50 HzSupply and shaft → rotorHuge rotor loss; must trip at zero speed
Dynamic (DC injection)AnyField stationaryProportional to \(N\)Shaft → rotorTorque falls to zero at rest; no holding torque

Dynamic braking is included for completeness: the stator is disconnected from the AC supply and fed with direct current, so the field is stationary and the machine behaves as a synchronous generator feeding its own rotor resistance. It is efficient in the sense that the supply contributes almost nothing, but all the kinetic energy still ends up in the rotor.

The sign of the slip settles everything. Positive and less than one, the machine takes power from the supply and gives it to the shaft; negative, it does the reverse; greater than one, it takes from both and gives to neither, heating its own rotor. A single machine occupies all three regions in the course of one hoisting cycle — motoring while lifting, regenerating while lowering, and plugging or DC-injecting to stop — and the equivalent circuit of Set 28 describes all three without alteration.
Answer(a) \(s = -0.04\), \(f_2 = 2\ \text{Hz}\), shaft to supply   (b) 32.49 kW in, 1.25 kW rotor loss, 29.74 kW returned   (c) \(s = -0.92\) at \(f_2 = 46\ \text{Hz}\)
Formulas

Key Formulas

QuantityRelationNotes
Speed\(N = \dfrac{120f}{P}(1-s)\)The three levers — all problems
Rotor resistance control\(\dfrac{R_2+R_{ext}}{s_2} = \dfrac{R_2}{s_1}\) at constant torqueProblem 1
Air-gap power\(P_g = T\omega_s = \dfrac{P_m}{1-s}\)Unchanged by rotor resistance — Problem 1
Rotor copper loss\(P_{cu2} = sP_g = 3I_2^2R\)Problems 1, 2, 5, 6
Rotor-circuit efficiency\(\eta_{\text{rotor}} = 1-s\)Problem 1
Voltage control\(T \propto V^2s\) (low slip), \(T_{\max}\propto V^2\)Problem 2
Fan load\(T_L \propto N^2,\quad P_L\propto N^3\)Problem 2
Stalling limit\(V/V_{\text{rated}} \ge \sqrt{T_L/T_{\max,\text{rated}}}\)Problem 2
Constant V/f\(V/f\) constant keeps the flux constantProblem 3
Maximum torque\(T_{\max} = \dfrac{3V_{ph}^2}{2\omega_s\left[R_1+\sqrt{R_1^2+X_{01}^2}\right]}\)Problem 3
Slip speed at constant torque\(sN_s = \text{constant}\)Problem 3
Pole change\(N_s\propto 1/P\); constant torque \(\Rightarrow P_{\text{out}}\propto N\)Problem 4
Plugging slip\(s' = 2-s\), \(f_2 = s'f\)Problem 5
Plugging energy\(W_{cu2} = J\left(\omega_s\omega_{m0}+\tfrac12\omega_{m0}^2\right)\)\(\to 3\times\tfrac12J\omega_s^2\) from \(\omega_s\) — Problem 5
Regenerative braking\(s<0\); returned \(= P_g-(P_{cu1}+P_i)\)Problem 6
Pitfalls

Common Mistakes

  1. Believing rotor resistance changes the torque at a given slip permanently. It changes the slip at which a given torque appears. At constant torque the rotor current, the air-gap power and the stator current are all unchanged — Problem 1.

  2. Charging the extra slip loss to the rotor. The rotor's own \(3I_2^2R_2\) stays at 833 W; the additional 3333 W appears in the external bank, which is why the machine does not overheat — Problem 1.

  3. Taking the output as unchanged when the speed is reduced at constant torque. Output follows the speed: 20 kW at 960 rev/min becomes 16.67 kW at 800 — Problem 1.

  4. Assuming the slip varies as \(1/V^2\) under voltage control. That holds only for a constant-torque load. With a fan the load torque falls too, and the slip equation becomes quadratic — Problem 2.

  5. Expecting a large speed range from voltage control. 30% off the voltage bought 8% off the speed here, and the machine stalls entirely at 67.4% on a constant-torque load — Problem 2.

  6. Holding \(V\) constant while reducing \(f\). The flux would rise as \(1/f\) and the core would saturate. Above rated frequency the reverse applies: \(V\) cannot be raised further, so the flux falls and the machine enters constant-power operation — Problem 3.

  7. Quoting maximum torque as exactly constant under V/f control. It is constant only if \(R_1\) is neglected; here it falls to 55% of its 50 Hz value by 10 Hz — Problem 3.

  8. Holding the slip constant instead of the slip speed when the frequency changes. A given torque needs a given rotor frequency, so 4% at 50 Hz becomes 8% at 25 Hz — Problem 3.

  9. Taking the new slip after a pole change as the old one. Both \(N_s\) and the operating point change; on 8 poles the machine runs at 712.5 rev/min, not at 720 — Problem 4.

  10. Writing the plugging slip as \(s+1\) or as \(-s\). It is \(2-s\): the rotor turns forwards while the field turns backwards, so the relative speed is \(N_s+N\) — Problem 5.

  11. Equating the plugging energy to the kinetic energy. It is three times as much, because the supply continues to deliver \(T\omega_s\) into the rotor throughout the deceleration — Problem 5.

  12. Leaving the supply connected after a plugging stop. The machine does not stop at zero speed; it reverses — Problem 5.

  13. Expecting regenerative braking to bring a machine to rest. It works only above synchronous speed, so it cannot hold or stop a load; something else must finish the job — Problem 6.

  14. Assuming an induction machine regenerating on a negative slip supplies its own excitation. The magnetising current still comes from the line, and the machine still absorbs lagging reactive power while exporting real power — Problem 6.

Looking Ahead

Six problems have exhausted \(N = (120f/P)(1-s)\). Slip control by rotor resistance or stator voltage is simple and lossy, and the loss is not a defect of the equipment but a consequence of \(P_{cu2} = sP_g\). Pole changing is lossless but discrete. Frequency control is the only method that is both continuous and efficient, and Problem 3 showed the one thing that spoils it — a stator resistance that does not scale with frequency, and the voltage boost that answers it. On the braking side the same equation, read with a different sign of slip, gave regeneration above synchronism, plugging between slips of one and two, and an energy bill for plugging of three times the drive's kinetic energy.

That closes the induction machine. Its defining feature has been the slip: torque exists only because the rotor runs slower than the field, and every calculation from Set 25 onwards has turned on that difference. The next family of machines gives it up. Excite the rotor with direct current and it locks to the field exactly, at a speed set by the supply frequency and nothing else — no slip, no rotor copper loss from slip, and a machine whose reactive power can be commanded at will by its field current.

Next: Set 33 — Alternator Fundamentals and the EMF Equation, where synchronous speed, frequency, flux per pole and the generated emf are put together.