By the end of this chapter you should be able to:
Explain why the magnetising current is non-sinusoidal and give its Fourier content.
Show that third harmonics are in phase in all three lines, and hence of zero sequence.
State the sequence rule for harmonics of any order.
Explain the dilemma of distorted current or distorted flux.
Compute the third-harmonic EMF produced by a given flux harmonic.
Describe the behaviour of each connection, earthed and unearthed.
Explain the duties of the tertiary winding.
Compute the neutral current and describe interference effects.
The Non-Sinusoidal Magnetising Current
Chapter 42 established the origin, and it is worth restating exactly.
- The applied voltage is sinusoidal, so from \(v \approx -N\,\mathrm{d}\Phi/\mathrm{d}t\) the flux must be sinusoidal.
- The relation between flux and current is the B-H curve, which is non-linear and hysteretic.
- To force a sinusoidal flux through a non-linear characteristic, the current must be non-sinusoidal — and it comes out peaked, because near the flux peak the core is entering saturation and disproportionately more current is needed.
The waveform has half-wave symmetry — each negative half is the mirror of the positive — so only odd harmonics appear. The third is typically 10 to 40 % of the fundamental, with smaller fifth and seventh.
Note the minus sign on the third harmonic: it is what makes the wave peaked rather than flat-topped.
Contrast this with Chapter 50's inrush current, which is asymmetrical and therefore rich in even harmonics, principally the second. The steady-state magnetising current and the switching transient have opposite harmonic signatures, and protection exploits the difference.
Problem. A magnetising current has harmonic components, relative to a fundamental of 1.00, of \(I_3 = 0.35\), \(I_5 = 0.10\) and \(I_7 = 0.05\). Find the total harmonic distortion and the RMS value, and comment.
Total harmonic distortion.
RMS value.
Comment. The waveform is grossly distorted — over a third of the fundamental in harmonics — yet its RMS value exceeds the fundamental by only 6.5 %.
That is the justification for Chapter 42's equivalent sinusoidal current: a sine wave of the same RMS value gives an answer within 6.5 % for all magnitude calculations, because harmonics add in quadrature and a third of a quantity contributes only a ninth of its square.
The harmonics are therefore negligible for computing magnitudes — but as the rest of this chapter shows, they are not negligible at all for computing what happens at a star point, where they add arithmetically rather than in quadrature.
Why the Third Harmonic Is Special
In a balanced three-phase system the fundamental currents are displaced by \(120^{\circ}\). The third harmonic of each is at three times that displacement.
The fundamentals sum to zero at a star point, which is why no neutral conductor is needed. The third harmonics do not — they add, giving \(3I_3\) in the neutral.
Everything in this chapter follows from that single line. A quantity that is identical in all three phases is called a zero-sequence quantity, and zero-sequence current needs a fourth path — a neutral conductor, an earth connection, or a closed delta — or it cannot flow at all.
Triplens and the Sequence Rule
Repeating the calculation for each harmonic order gives a simple pattern.
| Order \(h\) | Phase a | Phase b | Phase c | Sequence |
|---|---|---|---|---|
| 1 | 0° | −120° | +120° | Positive |
| 2 | 0° | +120° | −120° | Negative |
| 3 | 0° | 0° | 0° | Zero |
| 4 | 0° | −120° | +120° | Positive |
| 5 | 0° | +120° | −120° | Negative |
| 6 | 0° | 0° | 0° | Zero |
| 7 | 0° | −120° | +120° | Positive |
| 9 | 0° | 0° | 0° | Zero |
Multiples of three are called triplen harmonics, and all of them are zero-sequence. Since the magnetising current has odd harmonics only, the triplens that matter are the 3rd, 9th, 15th — with the 3rd dominant by far.
The rule explains why the fifth and seventh, though present, cause none of these difficulties. Being negative- and positive-sequence they sum to zero at a star point exactly as the fundamental does, so they need no special path and simply flow as ordinary balanced currents.
Problem. Determine the sequence of the 11th and 13th harmonics, and state whether either can flow in a three-wire star connection.
Eleventh harmonic. \(11 = 3(3) + 2\), so by the rule it is negative sequence. Checking directly:
Thirteenth harmonic. \(13 = 3(4) + 1\), so positive sequence:
Comment. Both are balanced three-phase sets, merely rotating in opposite directions, and both sum to zero at a star point. Each can therefore flow freely in a three-wire star connection with no neutral — nothing obstructs them.
Only the triplens are obstructed. This is a useful check on the rule: the harmonics that give trouble in three-phase transformers are exactly 3, 9, 15, …, and no others.
The Dilemma
The core needs a peaked magnetising current to produce a sinusoidal flux. If the circuit refuses to supply the third-harmonic component of that current, something has to give.
The current is peaked as the core demands, and the flux is sinusoidal. The induced EMFs are clean sine waves.
Requires: a closed delta, or an earthed star neutral, or a tertiary.
The current is forced sinusoidal, so the flux becomes flat-topped — it acquires a third-harmonic component of its own.
Result: third-harmonic EMFs are induced in every winding.
The EMF is \(e = -N\,\mathrm{d}\Phi/\mathrm{d}t\). Differentiating \(\Phi_n\sin n\omega t\) brings out a factor \(n\):
A modest 15 % third-harmonic flux produces a 45 % third-harmonic EMF. The distortion is amplified threefold on its way from flux to voltage.
Problem. Third-harmonic current is suppressed, and the flux acquires a third-harmonic component of 15 % of the fundamental. Find the third-harmonic EMF, the peak phase voltage and the RMS phase voltage, and state what happens to the line voltages.
Third-harmonic EMF.
Peak phase voltage. The flux is flat-topped, so its derivative is peaked, and the two peaks coincide:
RMS phase voltage.
Line voltages. The three third-harmonic EMFs are in phase, so in any line voltage they subtract and cancel:
Comment. Two quite different figures describe the same waveform. The RMS rises by under 10 %, but the peak rises by 45 % — and insulation fails on peak voltage, not RMS. A voltmeter would barely notice; the insulation certainly would.
The line-voltage result is the reason the fault can go undetected. Line-to-line voltages remain perfectly sinusoidal, so ordinary measurements at the terminals look normal. The distortion lives entirely between phase and neutral.
Since the third-harmonic EMFs are equal and in phase, they appear as an oscillation of the star point itself at 150 Hz relative to earth — the oscillating neutral of Section 54-5.
Star-Star Without a Neutral
This is the worst case, and it is why the Yy connection is rarely used alone.
There is no path for zero-sequence current — no fourth wire, no delta.
The magnetising current is forced sinusoidal, so the flux becomes flat-topped.
Third-harmonic EMFs of up to 45 % appear in every phase winding, stressing the insulation.
The star point oscillates at three times supply frequency relative to earth.
Line voltages remain sinusoidal, so the trouble is invisible from the terminals.
Because the three third-harmonic EMFs are identical, they cannot appear between lines — they appear between the star point and earth. The neutral is therefore displaced by a voltage at 150 Hz.
The consequences are practical. Phase-to-earth insulation sees the sum of the fundamental phase voltage and this oscillation, and any single-phase load connected between line and neutral receives a distorted supply, even though line-to-line measurements are clean.
Unbalanced loading makes matters worse still, since without a neutral the star point also shifts at fundamental frequency — the second of the two problems named in Chapter 52.
Star-Star With an Earthed Neutral
Earthing the star point, or running a fourth wire, provides the missing path. The third-harmonic current can now flow, the flux stays sinusoidal, and the harmonic EMFs vanish.
Since the three third harmonics are in phase, they add arithmetically. The neutral carries a current at 150 Hz even when the load is perfectly balanced — which surprises anyone expecting a balanced system to need no neutral current.
The cure has its own cost. That neutral current returns through the earth, and a current at 150 Hz flowing through the ground induces voltages in any parallel conductor — which is the origin of the telephone-interference problem of Section 54-9.
Problem. A 100 MVA, 132 kV star-connected winding has an earthed neutral. Its magnetising current is 3 % of rated, of which the third harmonic is 35 %. Find the neutral current, at balanced no load.
Rated current.
Third harmonic per phase.
Neutral current.
Comment. Nearly 14 A flows in the neutral of a transformer that is perfectly balanced and carrying no load at all. The usual rule that a balanced system needs no neutral current applies to the fundamental only; triplen harmonics are exempt from it.
The magnitude is modest as a fraction of rating, and thermally it is unimportant. What matters is where it flows: out through the earth connection and back through the ground, often for a considerable distance, at 150 Hz — a frequency squarely inside the audio band.
Connections Containing a Delta
A delta solves the problem more neatly than an earthed neutral, because the circulating current never leaves the transformer.
The three third-harmonic EMFs are equal and in phase. Round a closed delta they therefore add, giving a driving voltage of \(3E_3\) round the loop.
That drives a circulating third-harmonic current within the delta, which supplies exactly the magnetising harmonic the core requires.
The flux stays sinusoidal, no harmonic EMF appears at any terminal, and no harmonic current reaches the external system.
| Connection | Path for \(I_3\) | Flux | Harmonic EMF | Verdict |
|---|---|---|---|---|
| Yy, no neutral | None | Flat-topped | Up to 45 % | Unacceptable alone |
| Yy, neutral earthed | Through earth | Sinusoidal | None | Works; causes interference |
| Yy with tertiary delta | In the tertiary | Sinusoidal | None | Preferred remedy |
| Yd | In the delta | Sinusoidal | None | Good |
| Dy | In the delta | Sinusoidal | None | Good |
| Dd | In both deltas | Sinusoidal | None | Good |
This is the harmonic half of the case for Dyn11 made in Chapter 53. The HV delta contains the circulating harmonic entirely within the transformer, while the LV star supplies the four-wire neutral — and neither function interferes with the other.
The Tertiary Winding
Where both main windings must be star — usually because neutrals are wanted on both sides for earthing at two voltage levels — a third winding is added in delta purely to provide the harmonic path.
Harmonic path. Circulates the third-harmonic magnetising current, keeping the flux sinusoidal.
Earth-fault current. Provides a zero-sequence path, so that earth-fault current is large enough to operate protection.
Auxiliary supply. Often brought out at 11 kV to feed station auxiliaries.
Reactive compensation. Reactors or capacitors can be connected to it.
A tertiary is conventionally rated at about one third of the main winding. That rating is not set by the harmonic duty at all — the circulating harmonic is only about 1 % of rated current, which is thermally trivial. It is set by the fault and auxiliary duties, and by the mechanical forces a through-fault imposes.
Problem. A 100 MVA, 400/132 kV star-star transformer is fitted with an 11 kV delta tertiary. Estimate the circulating third-harmonic current, compare it with a conventional one-third rating, and comment.
Conventional tertiary rating.
Circulating harmonic current, referred to the tertiary and taking the same 1.05 % of rated as in Example 54.4:
Expressed on the transformer's own base this is about 1 % of rated current — a current the winding would carry without any measurable temperature rise.
Comment. The harmonic duty alone would justify a tertiary of perhaps a few percent of the main rating. The one-third convention is set by the other three duties: supplying earth-fault current large enough to operate protection, feeding auxiliaries, and withstanding the mechanical forces of a through-fault.
There is a design consequence worth noting. Because the tertiary is a closed delta, it carries circulating current whenever any zero-sequence condition exists — a harmonic, an unbalanced load, or an earth fault elsewhere on the system. Its rating must cover the worst of these, not the mildest.
And it cannot simply be omitted from a star-star transformer to save money. Without it the machine has no zero-sequence path at all, so earth faults on either side draw little current, protection may not operate, and the flux distortion of Section 54-5 returns in full.
Practical Consequences
Insulation stress from a phase-voltage peak up to 45 % high.
Oscillating neutral at 150 Hz relative to earth.
Distorted phase voltages supplied to any line-to-neutral load.
Increased iron loss, since the flat-topped flux wave contains harmonic components that the core must carry.
Neutral and earth currents at 150 Hz even at balanced no load.
Telephone interference, since 150 Hz and its multiples fall in the audio band and earth-return current couples into parallel lines.
Protection nuisance: standing zero-sequence current can bias sensitive earth-fault relays.
Additional loss in the neutral and earth path.
Summary and Key Formulas
A sinusoidal voltage forces sinusoidal flux; the non-linear B-H curve then forces a peaked, non-sinusoidal magnetising current containing odd harmonics, the third being 10 to 40 %.
The distortion barely affects the RMS value — 36.7 % THD raises it by only 6.5 % — which justifies the equivalent sinusoidal current.
Third harmonics are at \(3\times120^{\circ} = 360^{\circ} \equiv 0^{\circ}\), so they are in phase in all three lines — zero sequence.
Sequence rule: \(h = 3k\) zero, \(3k+1\) positive, \(3k+2\) negative. Only triplens cause difficulty.
Zero-sequence current needs a fourth path: a neutral, an earth, or a closed delta. Without one it cannot flow.
The dilemma: allow the harmonic current and the flux is sinusoidal; block it and the flux flat-tops.
Since \(E_n \propto n\Phi_n\), a 15 % flux harmonic gives a 45 % EMF harmonic — peak phase voltage 1.45 pu though RMS rises under 10 %.
Third-harmonic EMFs cancel in the line voltages and appear between phase and neutral, giving the oscillating neutral.
An earthed star neutral carries \(3I_3\) at 150 Hz even at balanced no load, causing telephone interference.
A delta confines the circulating harmonic within the transformer and is the clean solution; a tertiary delta supplies it where both mains are star.
| Quantity | Formula | Notes |
|---|---|---|
| Magnetising current | \(i_\mu = I_1\sin\omega t - I_3\sin3\omega t + \dots\) | minus sign gives the peak |
| Total harmonic distortion | \(\text{THD} = \dfrac{\sqrt{\sum_{h\gt 1}I_h^{2}}}{I_1}\) | 36.7 % typical |
| RMS value | \(I_{rms} = \sqrt{\sum_h I_h^{2}}\) | only 6.5 % above \(I_1\) |
| Third-harmonic phase | \(3\times120^{\circ} \equiv 0^{\circ}\) | all three in phase |
| Sequence rule | \(3k\) zero, \(3k{+}1\) pos, \(3k{+}2\) neg | triplens are zero-seq |
| Sum at a star point | \(i_{3a}+i_{3b}+i_{3c} = 3I_3\) | not zero |
| Neutral current | \(I_N = 3I_3\) | at 150 Hz, balanced |
| EMF from flux harmonic | \(E_n \propto n\Phi_n\) | threefold amplification |
| Peak phase voltage | \(\hat{V} = 1 + E_3/E_1\) | 1.45 pu at \(\Phi_3 = 0.15\) |
| Line voltage harmonic | \(V_{AB,3} = E_{A3} - E_{B3} = 0\) | lines stay clean |
| Delta driving voltage | \(3E_3\) round the loop | drives the circulation |
Common Mistakes
Saying third harmonics are 120° apart. Three times 120° is 360°, so they are in phase.
Assuming a balanced system needs no neutral current. True for the fundamental; false for triplens.
Expecting the fifth and seventh to cause the same trouble. They are negative and positive sequence and sum to zero normally.
Adding the third harmonic to get a peaked wave. It must be subtracted; adding it flat-tops the wave.
Taking \(E_3/E_1 = \Phi_3/\Phi_1\). Differentiation multiplies by the order, so it is three times as large.
Judging the overvoltage by RMS. RMS rises under 10 % while the peak rises 45 %, and insulation responds to the peak.
Expecting to see the distortion in the line voltages. It cancels there; look between phase and neutral.
Thinking the delta current reaches the external system. It circulates inside the closed loop and never leaves.
Sizing the tertiary from the harmonic duty. That needs only a few percent; the one-third rating comes from fault and auxiliary duties.
Omitting the tertiary from a star-star transformer. It also provides the zero-sequence path that earth-fault protection depends on.
Chapter Review
For any harmonic question, first classify the order by the sequence rule — that decides at once whether a path is needed.
P54.1 A magnetising current has \(I_1 = 1.00\), \(I_3 = 0.30\), \(I_5 = 0.12\). Find the THD and the RMS value.
Show answer
\[\text{THD} = \frac{\sqrt{0.0900 + 0.0144}}{1.00} = \sqrt{0.1044} = 0.3231 = 32.31\,\%\]Only 5.09 % above the fundamental despite 32 % distortion.\[I_{rms} = \sqrt{1 + 0.1044} = \sqrt{1.1044} = 1.05090\]P54.2 Classify the 15th and 17th harmonics by sequence, and state which needs a special path.
Show answer
\[15 = 3(5) \Rightarrow \text{zero sequence (a triplen)}\]The 15th needs a neutral, earth or delta; the 17th flows as an ordinary balanced set.\[17 = 3(5) + 2 \Rightarrow \text{negative sequence}\]P54.3 A flat-topped flux contains a third harmonic of 12 % of the fundamental. Find the third-harmonic EMF and the peak phase voltage.
Show answer
\[\frac{E_3}{E_1} = (3)(0.12) = 0.36\]\[\hat{V}_{ph} = 1 + 0.36 = 1.36~\mathrm{pu} \quad (36\,\%\ \text{overvoltage})\]\[V_{rms} = \sqrt{1 + (0.36)^{2}} = 1.06283~\mathrm{pu} \quad (6.28\,\%\ \text{up})\]P54.4 A 50 MVA, 66 kV earthed star winding has a magnetising current of 2.5 % of rated, of which 30 % is third harmonic. Find the neutral current.
Show answer
\[I_{rated} = \frac{50\times10^{6}}{\sqrt3\,(66\times10^{3})} = 437.39~\mathrm{A}\]\[I_3 = (0.30)(0.025)(437.39) = 3.280~\mathrm{A}\]\[I_N = 3I_3 = 9.841~\mathrm{A}\ \text{at }150~\mathrm{Hz} = 2.25\,\%\ \text{of rated}\]P54.5 Why does a 15 % third-harmonic flux not raise the RMS phase voltage by 45 %?
Show answer
Because harmonics add in quadrature for RMS purposes but arithmetically at the instant their peaks coincide.A 45 % component contributes only \((0.45)^{2} = 0.2025\) to the sum of squares, hence under 10 % on the RMS. Insulation responds to the peak, so the 45 % figure is the one that matters.\[V_{rms} = \sqrt{1 + (0.45)^{2}} = 1.0966 \quad\text{vs}\quad \hat{V} = 1 + 0.45 = 1.45\]P54.6 A star-star transformer has its neutral earthed on the primary only. Does this cure the harmonic problem?
Show answer
Yes. The magnetising current is drawn on the primary side, so a zero-sequence path on that side is sufficient — the third harmonic flows out through the earthed neutral and the flux stays sinusoidal.The secondary neutral is irrelevant to this particular problem, since the harmonic is a magnetising current and never needed to appear in the secondary at all.
But the cure brings the earth-return current of Section 54-9, with its interference risk, which is why a tertiary delta is usually preferred.
P54.7 Explain why third-harmonic currents in the three phases are in phase, and what follows.
Show answer
The fundamentals are displaced by 120°. The third harmonic of each is at three times that displacement:All three therefore coincide — the third harmonic is a zero-sequence quantity.\[3\times0^{\circ} = 0^{\circ}, \quad 3\times\left(-120^{\circ}\right) = -360^{\circ} \equiv 0^{\circ}, \quad 3\times\left(-240^{\circ}\right) = -720^{\circ} \equiv 0^{\circ}\]What follows. At a star point the fundamentals cancel but the third harmonics add, giving \(3I_3\). Since a three-wire star offers nowhere for that current to go, it cannot flow at all, and the magnetising current is forced sinusoidal.
The core then cannot produce a sinusoidal flux, so the flux flat-tops and induces third-harmonic EMFs instead. The trouble is transferred from the current to the voltage.
A neutral, an earth connection or a closed delta gives the current a path and restores the sinusoidal flux.
P54.8 Show that third-harmonic EMFs do not appear in the line voltages, and say where they do appear.
Show answer
Any line voltage is the difference of two phase EMFs. Since the third harmonics are equal and in phase,and the same for the other two lines. Line-to-line voltages therefore remain sinusoidal.\[V_{AB,3} = E_{A3} - E_{B3} = 0\]Where they appear. Being common to all three phases, they act between the star point and earth, displacing the neutral by a voltage at three times supply frequency — the oscillating neutral.
Two practical consequences follow. Phase-to-earth insulation is stressed by the sum of the fundamental and this oscillation; and any single-phase load between line and neutral receives a distorted supply. Since terminal line-voltage measurements look perfectly clean, the condition is easily missed.
P54.9 Explain how a delta winding solves the harmonic problem, and why it is preferable to earthing the neutral.
Show answer
The three third-harmonic EMFs are equal and in phase, so round a closed delta they add rather than cancel, giving a driving voltage of \(3E_3\) round the loop. This drives a circulating third-harmonic current inside the delta, which supplies exactly the magnetising harmonic the core requires.The flux therefore stays sinusoidal, no harmonic EMF appears at any terminal, and the phase voltages are clean.
Why it is preferable. An earthed neutral also provides a path, but the current then leaves the transformer, flows through the earth at 150 Hz and returns through the ground — inducing voltages in parallel conductors and causing telephone interference, as well as biasing sensitive earth-fault relays.
The delta current never leaves the transformer. It circulates in a closed loop within the tank, so the harmonic is dealt with entirely internally — which is why almost every large transformer has a delta winding somewhere, buried if not brought out.
P54.10 Why is a tertiary rated at a third of the main winding when the harmonic current is only about 1 %?
Show answer
Because the harmonic duty is the least demanding of its four functions.Harmonic path — needs only a few percent of rated current, thermally trivial.
Earth-fault current — must provide a zero-sequence path carrying enough current to operate protection, and must withstand it.
Auxiliary supply — often brought out at 11 kV to feed station services, a real continuous load.
Reactive compensation — reactors or capacitors may be connected to it.
The rating must also cover the mechanical forces of a through-fault, since the tertiary carries circulating current whenever any zero-sequence condition exists anywhere on the system.
The one-third convention is set by the worst of these duties, not the mildest. A tertiary sized for the harmonic alone would fail the first time an earth fault occurred.
MCQ 1. The magnetising current is non-sinusoidal because:
(a) the supply is distorted (b) the B-H curve is non-linear (c) of leakage flux (d) of copper lossShow answer
(b) the B-H curve is non-linear, and a sinusoidal flux is required.MCQ 2. Third-harmonic currents in the three phases are:
(a) 120° apart (b) 60° apart (c) in phase (d) in antiphaseShow answer
(c) in phase, since \(3\times120^{\circ} = 360^{\circ}\).MCQ 3. The 9th harmonic is of which sequence?
(a) positive (b) negative (c) zero (d) noneShow answer
(c) zero — it is a triplen.MCQ 4. The 5th harmonic is of which sequence?
(a) positive (b) negative (c) zero (d) noneShow answer
(b) negative, since \(5 = 3(1) + 2\).MCQ 5. If third-harmonic current is blocked, the flux becomes:
(a) sinusoidal (b) peaked (c) flat-topped (d) zeroShow answer
(c) flat-topped, and it induces harmonic EMFs.MCQ 6. A 15 % third-harmonic flux induces a third-harmonic EMF of:
(a) 5 % (b) 15 % (c) 45 % (d) 150 %Show answer
(c) 45 %, since \(E_n \propto n\Phi_n\).MCQ 7. Third-harmonic EMFs appear:
(a) in the line voltages (b) between phase and neutral (c) nowhere (d) only on loadShow answer
(b) between phase and neutral — they cancel in every line voltage.MCQ 8. The neutral of an earthed star winding carries, at balanced no load:
(a) zero (b) \(I_3\) (c) \(3I_3\) (d) \(\sqrt3I_3\)Show answer
(c) \(3I_3\), at 150 Hz.MCQ 9. A delta winding deals with the harmonic by:
(a) blocking it (b) circulating it internally (c) passing it to earth (d) filtering itShow answer
(b) circulating it internally, so it never leaves the transformer.MCQ 10. A tertiary winding is conventionally rated at about:
(a) 1 % (b) 10 % (c) one third (d) full ratingShow answer
(c) one third, set by its fault and auxiliary duties rather than the harmonic.
Explain why the magnetising current is non-sinusoidal and give its harmonic content.
Show that third harmonics are in phase in all three lines, and define zero sequence.
State and justify the sequence rule for harmonics of any order.
Explain the dilemma between distorted current and distorted flux.
Derive the relation between a flux harmonic and the EMF it induces.
Compare the harmonic behaviour of Yy, Yd, Dy and Dd connections.
Explain how a delta winding resolves the problem and why it is preferred to earthing.
Give the duties of a tertiary winding and explain its conventional rating.
Two chapters remain in Part 3. Chapter 55 takes up the Scott or T-T connection, which converts a three-phase supply into two-phase and back. It uses a main transformer with a centre tap and a teaser tapped at the \(\sqrt3/2 = 0.866\) point — the same figure met in Chapter 53 as the open-delta utilisation factor, arriving here from a quite different direction. Its classic application is the electric furnace and the single-phase railway supply, where a large single-phase load must be drawn from a three-phase system without unbalancing it.
Chapter 56 then closes Part 3 with instrument transformers — the current and potential transformers on which every measurement and every protective relay depends. Their theory is the ordinary transformer theory of Chapters 41 to 46, but the design priority is inverted: accuracy of ratio and of phase angle matters more than efficiency or regulation, and a current transformer must never be open-circuited while its primary carries current, for reasons that follow directly from the magnetising curve of Chapter 42.
Part 4 then opens on induction motors, where the rotating magnetic field of Chapter 22 meets the transformer action of Part 3 — an induction motor being, in essence, a transformer whose secondary is free to turn.