By the end of this chapter you should be able to:
Explain why a DC motor cannot be switched directly on to the supply.
Calculate the starting resistance needed to limit the current to a stated value.
Explain why the resistance must be removed in steps.
Determine the number of steps and the resistance of each section.
Describe the three-point starter and the function of each terminal.
Explain the no-volt and overload releases and what each protects against.
State the defect of the three-point starter and how the four-point starter cures it.
Describe the two-point starter and why a series motor needs a different arrangement.
Why a Starter Is Needed
Chapter 34 established the relation that governs everything here:
In normal running \(E_b\) absorbs almost the whole supply voltage, leaving only a few volts to drive the current. At the instant of switching on, the armature is stationary, so \(E_b = 0\) and the full supply appears across the armature resistance alone.
The consequences are all bad at once:
The armature winding overheats — the loss goes as \(I_a^{2}\), so 25 times the current is 625 times the loss.
Commutation fails: Chapter 31's reactance voltage is proportional to \(I_a\), so the machine sparks violently.
The torque is enormous, giving a mechanical shock to the coupling, gearing and load.
The supply voltage dips, disturbing every other consumer on the same feeder.
Only very small machines — a fraction of a kilowatt, where \(R_a\) is relatively large — may be switched directly on. Everything else needs a starter.
The Starting Resistance
The remedy is to insert resistance in series with the armature and remove it as the motor gains speed.
The limiting value \(I_{\max}\) is chosen at 1.5 to 2 times the full-load current — enough to give a useful accelerating torque, low enough that the winding and commutator survive the few seconds involved.
Problem. A 230 V shunt motor has an armature resistance of 0.25 \(\Omega\) and a full-load armature current of 40 A. Find the current if it were switched directly on, and the starting resistance needed to limit the starting current to 1.5 times full load.
Direct on line.
With a starter. Limiting to \(I_{\max} = 60\) A:
Comment. The starter resistance is fourteen times the armature resistance, which is why a starter is a substantial piece of equipment rather than a small component.
Note the loss it must dissipate. At 60 A the starter absorbs \((60)^{2}(3.583) = 12.9\) kW at the first stud — briefly, but the grids must be sized for it. Compare the 211.6 kW that would be dissipated in the armature alone on direct switching, in a winding designed to lose 400 W.
Why the Resistance Is Cut Out in Steps
The starting resistance cannot simply be removed all at once, nor left in until the motor reaches full speed.
- At the first stud the full resistance limits the current to \(I_{\max}\).
- The motor accelerates, so \(E_b\) rises and the current falls.
- When the current has fallen to a chosen lower value \(I_{\min}\), a section of resistance is cut out, and the current jumps back up to \(I_{\max}\).
- The process repeats until all the resistance is out and the motor runs on \(R_a\) alone.
The current therefore oscillates between two limits, and the accelerating torque with it. More steps means a narrower band, smoother acceleration and a more expensive starter — the design trade-off of Section 36-4.
Design of a Multi-Step Starter
Let \(R_1, R_2, \ldots\) be the total circuit resistance at successive studs, so that \(R_1\) includes all the sections and \(R_{n+1} = R_a\).
At stud 1 the current starts at \(I_{\max}\) and falls to \(I_{\min}\). The back EMF at that moment is the same immediately before and after the switch, so
The same argument applies at every stud, so the total resistances form a geometric progression with common ratio \(k\).
Since the last total resistance must be the armature resistance itself,
and the individual sections are the differences
\(n\) rarely comes out a whole number. It is rounded up, and then \(k\) is recomputed from \(k = (R_a/R_1)^{1/n}\) so that the progression lands exactly on \(R_a\). Rounding up raises \(k\), which narrows the current band — the design becomes gentler than specified, never harsher.
Problem. For the motor of Example 36.1, the current is to be held between 60 A and the full-load 40 A. Find the number of starter steps required and the corrected value of \(k\).
Ratio and first resistance.
Number of steps.
Corrected \(k\). With \(n = 7\) exactly:
Comment. The lower limit has risen slightly, from 40 A to 40.6 A. That is the right direction: with seven steps rather than the fractional 6.73, each cut removes slightly less resistance, so the current falls slightly less far before the next step.
Had \(n\) been rounded down to 6, \(k\) would have fallen to 0.6344 and \(I_{\min}\) to 38.1 A — a wider swing, and the last stud would not land on \(R_a\). Always round up.
Problem. Complete the design of Example 36.2 by tabulating the total resistance at each stud and the resistance of each section. Verify that the sections sum to the starter resistance found in Example 36.1.
| Stud \(m\) | Total \(R_m = k^{m-1}R_1\) | Section \(r_m = R_m - R_{m+1}\) |
|---|---|---|
| 1 | 3.8333 \(\Omega\) | 1.2380 \(\Omega\) |
| 2 | 2.5954 | 0.8382 |
| 3 | 1.7572 | 0.5675 |
| 4 | 1.1897 | 0.3842 |
| 5 | 0.8055 | 0.2601 |
| 6 | 0.5454 | 0.1761 |
| 7 | 0.3692 | 0.1192 |
| 8 (running) | 0.2500 = \(R_a\) | — |
| Sum of sections | 3.5833 \(\Omega\) | |
Sample calculation, stud 2.
Checks. The eighth total resistance is 0.2500 \(\Omega\), exactly \(R_a\), and the sections sum to 3.5833 \(\Omega\) — the starter resistance of Example 36.1 \(\checkmark\)
Comment. Notice how unequal the sections are. The first removes 1.238 \(\Omega\) and the last only 0.119 \(\Omega\) — a ratio of more than ten to one. Each section is \(k\) times the one before, because each must produce the same proportional jump in current from a progressively smaller total.
A starter built with equal sections would give large current surges at the first studs and negligible ones at the last — which is why the resistance grids of a real starter are visibly graded in size.
The Three-Point Starter
The commonest starter for shunt and compound motors. Its three terminals are marked L (line), F (field) and A (armature).
- The handle is moved from the off position to the first stud, putting the whole starting resistance in series with the armature.
- The shunt field is connected across the supply through the no-volt coil, so it receives full excitation from the outset — giving maximum torque per ampere.
- The handle is moved slowly across the studs as the motor accelerates, cutting out one section at a time.
- At the last stud the handle is held by the no-volt coil against the pull of a spring, and the starting resistance is entirely out of the armature circuit.
The field is energised before any armature current flows, and this is deliberate. From Chapter 34, \(T_a = K_a\Phi I_a\), so full flux gives the greatest possible torque for the limited starting current.
It also means the speed \(N \propto E_b/\Phi\) starts from its lowest value, so the motor accelerates under control rather than racing. Any field rheostat should be at minimum resistance — that is, maximum flux — during starting.
Protective Devices
An electromagnet in series with the shunt field. It holds the handle at the running position.
If the supply fails, or the field circuit opens, the coil de-energises and a spring returns the handle to the off position.
It therefore protects against two distinct faults:
Supply failure: the motor is disconnected, so it cannot be restarted directly on line when the supply returns.
Field failure: the runaway of Chapter 34's P34.10 is prevented, because the coil is in the same circuit as the field.
An electromagnet carrying the line current, with an armature held down by gravity.
If the current exceeds a preset value, the electromagnet lifts the armature, which short-circuits the no-volt coil.
The holding coil is thereby de-energised, the spring returns the handle, and the motor is disconnected.
The setting is adjustable, usually by altering the air gap or the counterweight.
The Four-Point Starter
The no-volt coil is in series with the shunt field. Chapter 37 will show that the principal method of raising a shunt motor's speed is to increase the field-circuit resistance with a rheostat.
But that same rheostat is in series with the holding coil. Weakening the field to raise the speed also weakens the holding coil, and at high speed settings the coil may release the handle and stop the motor for no reason at all.
The operator is thus prevented from using the full speed range — the starter interferes with the speed control.
A fourth terminal N is added. The no-volt coil is taken directly across the supply through its own protective resistance, in parallel with the field circuit rather than in series with it.
The line current now divides three ways at the handle:
through the armature and the starting resistance,
through the shunt field and its rheostat,
through the holding coil and its series resistance.
The coil current is now independent of the field rheostat setting, so the full speed range is available.
The gain comes at a price. Because the holding coil is no longer in the field circuit, it does not release on field failure. A broken shunt field leaves the coil energised, the handle held, and the motor free to race.
A four-point starter therefore needs a separate field-failure relay if that protection is required. The three-point starter gets it free; the four-point starter must pay for it.
Problem. A three-point starter has a no-volt coil of 50 \(\Omega\) in series with a 200 \(\Omega\) shunt field on a 230 V supply. The coil needs at least 0.70 A to hold. Find the coil current with no field rheostat, and with 150 \(\Omega\) of rheostat inserted for speed control. Will the starter hold?
With no rheostat.
Comfortably above the 0.70 A holding value.
With 150 \(\Omega\) of rheostat.
Below 0.70 A, so the coil releases and the motor stops — even though nothing is wrong.
The maximum usable rheostat setting.
Comment. The operator can use only 79 \(\Omega\) of the 150 \(\Omega\) rheostat, so roughly half the intended speed range is unavailable. This is the whole case for the four-point starter, in which the coil current would have stayed at its design value however far the rheostat was turned.
Note also the incidental cost of the series coil: without it the field would draw \(230/200 = 1.15\) A, so the coil is weakening the field by 20 % even at the minimum setting, and consuming \((0.92)^{2}(50) = 42\) W continuously.
Two-Point Starters for Series Motors
A series motor has no separate field circuit, so there is nothing to connect a third terminal to. Its starter has only two terminals and the holding coil carries the full line current.
Because the holding coil carries the armature current, it doubles as a no-load release. If the load is removed the current falls, the coil weakens, and the handle springs back — disconnecting the motor before it can run away.
This is precisely the protection Chapter 35 showed a series motor needs, and it comes free from the series connection, exactly as the three-point starter's field-failure protection did.
The same coil still serves as a no-volt release on supply failure, since a lost supply also means lost current. One coil, two protections — but no overload protection from it, so a separate device is fitted.
Problem. For the motor of Example 36.1, compare the starting torque and the armature heating with and without the starter. Take the full-load torque as 100 N·m.
Torque. For a shunt motor \(T_a \propto I_a\):
Armature heating at the instant of starting.
Comparison with the full-load armature loss.
Comment. With the starter the armature dissipates 2.25 times its normal loss for a few seconds — entirely survivable. Without it, 529 times, in a winding designed for 400 W. The insulation would char before the motor completed one revolution.
The 150 N·m available with the starter is 1.5 times full-load torque, which accelerates any normal load perfectly well. The 2300 N·m of direct starting is not a benefit but a hazard — it would shear couplings and strip gear teeth. The starter limits the torque as usefully as it limits the current.
Note where the energy goes instead: at the first stud the starter grids absorb \((60)^{2}(3.583) = 12.9\) kW, which is why they are open wire grids in a ventilated box rather than enclosed components.
Comparison
| Two-point | Three-point | Four-point | |
|---|---|---|---|
| Used for | Series motors | Shunt and compound | Shunt and compound |
| Terminals | L, A | L, F, A | L, F, A, N |
| Holding coil in series with | Armature (line current) | Shunt field | Its own resistance |
| Protects on supply failure | Yes | Yes | Yes |
| Protects on field failure | n/a | Yes | No |
| Protects on loss of load | Yes | No | No |
| Full field-control range | n/a | No | Yes |
Summary and Key Formulas
At rest \(E_b = 0\), so a motor switched directly on would draw \(V/R_a\) — 20 to 30 times rated, damaging the winding, the commutation, the coupling and the supply.
A starter inserts \(R_{st} = V/I_{\max} - R_a\) and removes it as \(E_b\) builds up. \(I_{\max}\) is chosen at 1.5 to 2 times full load.
The resistance is removed in steps, keeping the current between \(I_{\max}\) and \(I_{\min}\).
The total resistances form a geometric progression of ratio \(k = I_{\min}/I_{\max}\), with \(R_1 = V/I_{\max}\) and \(R_{n+1} = R_a\).
\(n = \ln(R_aI_{\max}/V)/\ln k\), always rounded up, after which \(k\) is recomputed as \((R_a/R_1)^{1/n}\).
Sections are \(r_m = R_m(1 - k)\) and are graded, the first being the largest.
The three-point starter has its no-volt coil in series with the shunt field, so it protects against supply failure and field failure. Its defect is that field-rheostat resistance also weakens the holding coil.
The four-point starter gives the coil its own circuit, restoring the full speed range but losing field-failure protection.
The overload release short-circuits the no-volt coil rather than breaking the main circuit directly.
A two-point starter serves a series motor; its coil carries the line current and so doubles as a no-load release.
| Quantity | Formula | Notes |
|---|---|---|
| Direct starting current | \(V/R_a\) | 20–30× rated |
| Starter resistance | \(R_{st} = \dfrac{V}{I_{\max}} - R_a\) | — |
| Step ratio | \(k = I_{\min}/I_{\max}\) | — |
| Total at stud \(m\) | \(R_m = k^{m-1}R_1\) | \(R_1 = V/I_{\max}\) |
| Number of steps | \(n = \dfrac{\ln\left(R_aI_{\max}/V\right)}{\ln k}\) | round up |
| Corrected ratio | \(k = \left(R_a/R_1\right)^{1/n}\) | after rounding |
| Section resistance | \(r_m = R_m\left(1 - k\right)\) | graded, largest first |
| Check | \(\sum r_m = R_{st}\) and \(R_{n+1} = R_a\) | always verify both |
| Starting torque | \(T \propto I_{\max}\) (shunt) | 1.5–2× full load |
Common Mistakes
Forgetting to subtract \(R_a\). The starter resistance is \(V/I_{\max} - R_a\), not \(V/I_{\max}\).
Rounding \(n\) down. Round up; the last stud must land on \(R_a\), and rounding down widens the current swing.
Forgetting to recompute \(k\) after rounding. The progression will otherwise miss \(R_a\).
Making the sections equal. They form a geometric progression; the first is the largest by a wide margin.
Confusing \(R_m\) with \(r_m\). \(R_m\) is the total circuit resistance at that stud, including \(R_a\); \(r_m\) is one section.
Starting with the field rheostat at maximum. Full flux gives maximum torque per ampere and the lowest starting speed.
Thinking the overload release breaks the main circuit. It short-circuits the no-volt coil, which then releases the handle.
Believing the four-point starter is simply better. It gains the speed range and loses field-failure protection.
Using a three-point starter on a series motor. There is no shunt field to connect to F.
Leaving the starter resistance in circuit while running. It is a starting device, not a speed controller — that is Chapter 37.
Chapter Review
For design problems find \(R_1\) and \(k\) first, then \(n\), then recompute \(k\) before working out the sections.
P36.1 A 250 V motor has \(R_a = 0.20~\Omega\) and full-load current 50 A. Find the direct starting current and the starter resistance to limit it to twice full load.
Show answer
\[I = \frac{250}{0.20} = 1250~\mathrm{A} = 25\ \text{times rated}\]\[R_1 = \frac{250}{100} = 2.50~\Omega, \qquad R_{st} = 2.50 - 0.20 = 2.30~\Omega\]P36.2 For P36.1, the current is to be held between 100 A and 60 A. Find the number of steps.
Show answer
\[k = \frac{60}{100} = 0.60, \qquad \frac{R_a}{R_1} = \frac{0.20}{2.50} = 0.080\]\[n = \frac{\ln 0.080}{\ln 0.60} = \frac{-2.526}{-0.5108} = 4.945 \quad\Longrightarrow\quad 5\ \text{steps}\]P36.3 For P36.2, find the corrected \(k\) and the new lower current limit.
Show answer
\[k = (0.080)^{1/5} = 0.6034\]Barely changed, because \(n\) was already close to a whole number.\[I_{\min} = (0.6034)(100) = 60.3~\mathrm{A}\]P36.4 For P36.3, find the total resistance at each stud and the first two sections.
Show answer
\[R_1 = 2.500, \ R_2 = 1.509, \ R_3 = 0.9102, \ R_4 = 0.5492, \ R_5 = 0.3314, \ R_6 = 0.2000 = R_a \ \checkmark\]Sections sum to \(2.500 - 0.200 = 2.300~\Omega\) \(\checkmark\)\[r_1 = 2.500 - 1.509 = 0.991~\Omega, \qquad r_2 = 1.509 - 0.910 = 0.599~\Omega\]P36.5 A three-point starter has a 40 \(\Omega\) holding coil and a 160 \(\Omega\) field on 200 V. The coil needs 0.80 A. What is the largest usable field rheostat?
Show answer
Only 50 \(\Omega\) may be inserted before the handle drops out.\[\frac{200}{200 + R} \ge 0.80 \quad\Longrightarrow\quad R \le \frac{200}{0.80} - 200 = 250 - 200 = 50~\Omega\]P36.6 A motor's armature dissipates 500 W at full load. What does it dissipate at the first stud if \(I_{\max}\) is 1.8 times full load, and on direct starting at 25 times full load?
Show answer
\[\text{with starter: } (500)(1.8)^{2} = (500)(3.24) = 1620~\mathrm{W}\]\[\text{direct: } (500)(25)^{2} = (500)(625) = 312\,500~\mathrm{W} = 313~\mathrm{kW}\]P36.7 Why must the field rheostat be at minimum resistance during starting?
Show answer
Minimum rheostat resistance means maximum field current and maximum flux. Since \(T_a = K_a\Phi I_a\) and the starting current is deliberately limited, maximum flux gives the greatest possible torque from that limited current.It also gives the lowest speed for a given \(E_b\), since \(N \propto E_b/\Phi\), so the motor accelerates under control instead of racing.
On a three-point starter there is a third reason: the holding coil is in the same circuit, and minimum rheostat resistance gives it maximum current.
P36.8 Explain how the overload release works, and why it does not break the main circuit itself.
Show answer
The overload release is an electromagnet carrying the line current. On overload it lifts a pivoted armature which short-circuits the no-volt holding coil.The holding coil, deprived of current, releases the handle, and the spring returns it to the off position — disconnecting the motor and simultaneously reinserting the full starting resistance ready for the next start.
Why not break the circuit directly? A contact interrupting the full armature current would arc badly and need to be substantial. Short-circuiting a small coil is a much lighter duty, and it reuses the disconnecting mechanism that already exists for the no-volt function.
P36.9 Compare the three-point and four-point starters, stating what each gains and loses.
Show answer
Three-point: the holding coil is in series with the shunt field. It therefore protects against both supply failure and field failure. But any field rheostat inserted for speed control also weakens the coil, so the speed range is limited — Example 36.4 found only half the rheostat usable.Four-point: the coil has its own circuit across the supply through terminal N. Its current is independent of the field rheostat, so the full speed range is available. But it no longer releases on field failure, and a separate field-failure relay is needed.
Neither is simply better. The choice depends on whether wide field control is wanted.
P36.10 Why does a series motor's two-point starter give protection that a shunt motor's does not?
Show answer
Because its holding coil carries the armature current rather than the field current. If the mechanical load is removed, the current falls, the coil weakens, and the handle springs back — disconnecting the motor before it can run away.This is exactly the protection a series motor needs (Chapter 35), and it comes free from the series connection.
A shunt motor's three-point starter has its coil in the field circuit, so it releases on field failure instead — which is the fault a shunt motor is vulnerable to. In each case the coil is placed in the circuit whose failure is most dangerous for that machine.
MCQ 1. A DC motor needs a starter because at rest:
(a) the flux is zero (b) the back EMF is zero (c) the resistance is zero (d) the torque is zeroShow answer
(b) the back EMF is zero, so the full supply appears across \(R_a\).MCQ 2. Starting current is typically limited to:
(a) 0.5× full load (b) 1.5–2× full load (c) 10× full load (d) 25× full loadShow answer
(b) 1.5–2× full load — enough torque to accelerate, low enough to survive.MCQ 3. The total resistances at successive studs form:
(a) an arithmetic progression (b) a geometric progression (c) equal steps (d) a random setShow answer
(b) a geometric progression of common ratio \(k = I_{\min}/I_{\max}\).MCQ 4. The last total resistance \(R_{n+1}\) must equal:
(a) zero (b) \(R_a\) (c) \(R_{st}\) (d) \(V/I_{\max}\)Show answer
(b) \(R_a\) — all the starter resistance is out and the armature runs alone.MCQ 5. The sections of a starter are:
(a) all equal (b) largest first (c) smallest first (d) arbitraryShow answer
(b) largest first, each being \(k\) times the one before.MCQ 6. In a three-point starter, the no-volt coil is in series with the:
(a) armature (b) shunt field (c) starting resistance (d) supply onlyShow answer
(b) shunt field — which gives it field-failure protection and also its defect.MCQ 7. The overload release operates by:
(a) breaking the armature circuit (b) short-circuiting the no-volt coil (c) opening the field (d) blowing a fuseShow answer
(b) short-circuiting the no-volt coil, which then releases the handle.MCQ 8. The four-point starter's advantage is that:
(a) it is cheaper (b) the coil current is independent of the field rheostat (c) it protects on field failure (d) it needs no overload releaseShow answer
(b) the coil current is independent of the field rheostat, so the full speed range is available.MCQ 9. The four-point starter loses:
(a) supply-failure protection (b) field-failure protection (c) overload protection (d) nothingShow answer
(b) field-failure protection, since the coil is no longer in the field circuit.MCQ 10. A two-point starter's holding coil also acts as a:
(a) no-load release (b) field-failure release (c) speed regulator (d) brakeShow answer
(a) no-load release, because it carries the armature current — the protection a series motor needs.
Explain why a DC motor cannot be switched directly on to the supply, listing the consequences.
Derive the starting resistance required for a stated current limit.
Explain why the starting resistance must be removed in steps rather than all at once.
Derive the geometric progression of stud resistances and the expression for the number of steps.
Describe the three-point starter and the function of each of its terminals.
Explain the operation of the no-volt and overload releases, and the three faults they cover between them.
State the defect of the three-point starter and explain how the four-point starter cures it and at what cost.
Explain why a series motor uses a two-point starter and what protection this affords.
The starting resistance of this chapter is removed once the motor is running. Chapter 37 asks what happens if resistance is kept in circuit deliberately — and finds that it is one of three ways to control the speed. From \(N \propto (V - I_aR_a)/\Phi\) the three handles are the flux, the armature-circuit resistance and the applied voltage, and each gives a distinct method with its own range, cost and efficiency.
Field control raises the speed above rated and is efficient, since the field current is small — but it is limited by the holding-coil problem of Example 36.4 unless a four-point starter is fitted. Armature-resistance control lowers the speed below rated and is very inefficient, for exactly the reason Example 36.5 gave: the resistance dissipates real power. Voltage control, the Ward-Leonard method, avoids both objections at the cost of a second machine.
Chapter 38 then covers braking — making the motor act as a generator to bring its load to rest — and Chapter 39 the testing methods that measure Chapter 33's losses without loading the machine fully.