Solved Problems · Set 14

Regulation and Efficiency

Part 3 · Line Performance — what the exact solution exposed, treated as a design problem: the voltage rise that must be suppressed and the loading at which the line pays for itself. Chapter 14 of the textbook.

Prof. Mithun Mondal 20 solved · 12 practice · 3 challenge GATE · ESE · University

Set 14 — Regulation and Efficiency

Twenty worked problems on making a long line usable. Set 12 found a 400 km line failing on regulation, on efficiency and on no-load voltage together; this set fixes it. Shunt reactors and series capacitors act on different ABCD constants and therefore on different symptoms, and both have a cost that the usual accounts omit — shunt compensation lowers the surge impedance loading it is meant to protect. The set closes with the tuned line, where compensation is pushed to its logical end.

Textbook Chapter 14 · 20 solved · 12 practice · 3 challenge · 12 MCQs

i Method Recap
  • Regulation is governed by \(A\), voltage drop by \(B\). \(\%\text{reg} = (V_S/|A| - V_R)/V_R\), and \(V_S\) itself depends on \(B\). A remedy must be matched to whichever of the two is at fault.

  • Shunt reactors reduce the effective \(y\). Compensating a fraction \(k\) of the line's susceptance gives \(\gamma_{\text{eff}} = \gamma\sqrt{1-k}\) and \(Z_{c,\text{eff}} = Z_c/\sqrt{1-k}\). The line becomes electrically shorter and \(|A|\) rises towards unity.

  • Series capacitors reduce the effective \(x\). Compensating a fraction \(k\) gives \(z_{\text{eff}} = r + jx(1-k)\), which lowers both \(|B|\) and \(|Z_c|\) — so it raises the surge impedance loading where shunt compensation lowers it.

  • The two act oppositely on SIL. \(\text{SIL} = V_L^2/|Z_c|\). Shunt reactors raise \(|Z_c|\) and cut SIL; series capacitors lower it and raise SIL. A line compensated only by reactors carries less natural power than before.

  • Neither improves efficiency much. Losses are \(I^2R\) and neither remedy changes \(r\). Efficiency is raised only by a larger conductor, a higher voltage, or a better power factor at the load.

  • Reactor sizing. A reactor absorbing a fraction \(k\) of the line's charging needs \(Q_L = kV_L^2B_{\text{line}}\), usually split between the two ends and sometimes a third at a mid-point.

  • The tuned line. At \(\beta l = 180^\circ\) a lossless line has \(A = -1\) and \(B = 0\): the receiving voltage equals the sending voltage at any load, and the regulation is zero. Compensation can synthesise this condition on a shorter line.

VideoWalkthrough
Problem 1Warm-upThe Starting Point

The 400 km, 400 kV line of Set 12 has \(A = 0.9060\angle2.35^\circ\), \(B = 166.87\angle68.94^\circ\ \Omega\), \(Z_c = 378.95\angle-10.90^\circ\ \Omega\). Establish its baseline performance delivering 300 MW at 0.95 power factor lagging.

Solution

From Set 12, the sending-end conditions and performance:

\[ V_S = 460.6\ \text{kV}, \qquad \%\text{reg} = 27.08\%, \qquad \eta = 89.46\% \]

The Ferranti rise and surge impedance loading:

\[ \frac{1}{|A|} - 1 = 10.37\%, \qquad \text{SIL} = \frac{(400\times10^{3})^{2}}{378.95} = 422\ \text{MW} \]

The three failures, against ordinary limits:

\[ \begin{array}{lccl} \text{Quantity} & \text{Value} & \text{Limit} & \\ \hline \text{Regulation} & 27.1\% & 10\% & \text{Fails} \\ \text{Efficiency} & 89.5\% & 95\% & \text{Fails} \\ \text{No-load } V_R & 441.5\ \text{kV} & 420\ \text{kV} & \text{Fails} \end{array} \]

The line runs at 300 MW against an SIL of 422 MW — that is, at 71% of its natural loading, so it is a net generator of reactive power.

Three failures with three different causes, and that is the whole reason this set exists. The no-load voltage is a property of \(|A|\) alone; the regulation depends on \(|A|\) and \(|B|\) together; the efficiency depends on \(r\) and on neither. Any remedy that treats them as one problem will fix at most one of them, and Problems 5 to 13 show precisely which lever moves which symptom.
Answer\(V_S = 460.6\) kV, reg 27.1%, \(\eta\) 89.5%, Ferranti 10.4%, SIL 422 MW — failing on three counts
Problem 2Exam levelRegulation vs Loading

Tabulate the sending-end voltage and regulation of the uncompensated line at 100, 200, 300, 422 and 500 MW, all at 0.95 power factor lagging with the receiving end at 400 kV.

Solution

Computing \(\mathbf{V}_S = A\mathbf{V}_R + B\mathbf{I}_R\) at each loading, with \(I_R\) scaling in proportion to the power:

\[ \begin{array}{ccccc} P\ (\text{MW}) & V_S\ (\text{kV}) & \%\text{reg} & \eta\ (\%) & \cos\phi_S \\ \hline 100 & 393.0 & 8.42 & 93.79 & 0.593\ \text{lead} \\ 200 & 425.8 & 17.50 & 92.24 & 0.905\ \text{lead} \\ 300 & 460.6 & 27.08 & 89.46 & 0.993\ \text{lead} \\ 422 & 504.9 & 39.30 & 85.91 & 0.992\ \text{lag} \\ 500 & 534.1 & 47.36 & 83.70 & 0.973\ \text{lag} \end{array} \]

Two things move together and one moves against them. Regulation rises steadily with loading; efficiency falls; and the sending-end power factor swings from strongly leading to lagging, crossing unity near 320 MW.

At 100 MW the sending-end power factor is 0.593 leading — the line's charging current dominates the load current almost completely.

A leading sending-end power factor of 0.59 is an operational problem in its own right, quite apart from the voltage. The generator supplying this line must absorb some 130 MVAr at light load, which pushes it deep into the underexcited region where its own steady-state stability limit binds. Many machines simply cannot do it. This is why a long line is not merely inconvenient at light load but genuinely unoperable without compensation — the constraint is at the generator, not on the line.
AnswerRegulation rises 8.4% to 47.4% and efficiency falls 93.8% to 83.7% as loading goes 100 to 500 MW
Problem 3Warm-upEfficiency vs Loading

Explain the efficiency trend of Problem 2, and identify what would improve it.

Solution

The loss is essentially \(3I^2R\) integrated along the line, so it grows as the square of the loading while the delivered power grows only linearly:

\[ \eta = \frac{P_R}{P_R + kP_R^{2}} = \frac{1}{1 + kP_R} \]

— a hyperbolic fall, which is what the table shows.

At light load the loss does not fall to zero, because the charging current still flows and dissipates in the conductors:

\[ P = 100\ \text{MW}: \quad \text{loss} = 6.6\ \text{MW},\ \text{of which a large part is charging current} \]

What would improve it. Efficiency depends on \(r\) and on the current, so:

\[ \begin{array}{ll} \text{A larger conductor} & \text{reduces } r \text{ directly} \\ \text{Bundling} & \text{quarters } r \text{ for four sub-conductors} \\ \text{A higher voltage} & \text{reduces } I \text{ for the same power} \\ \text{Power-factor correction at the load} & \text{reduces } I \\ \text{Shunt or series compensation} & \text{does essentially nothing} \end{array} \]

At \(r = 0.16\ \Omega\)/km this line carries a single unbundled conductor. A twin-bundle design of the same voltage, as in Set 7, would have \(r \approx 0.016\ \Omega\)/km and an efficiency above 98%.

Compensation is powerless against losses, and that is worth stating plainly because it is often assumed otherwise. Series capacitors leave the current unchanged; shunt reactors slightly increase it by lowering the operating voltage profile. Both improve the voltage behaviour and neither touches \(I^2R\). An efficiency problem is a conductor problem, and the only remedies are more metal, a higher voltage, or less reactive current — the conclusions of Set 2 reappearing unchanged.
AnswerEfficiency falls hyperbolically with loading; only a larger conductor, higher voltage or better load power factor improves it — not compensation
Problem 4Challenge-liteDecomposing Regulation

Separate the 27.08% regulation at 300 MW into the part caused by the load current and the part caused by the Ferranti effect, and state which remedy addresses each.

Solution

Regulation is

\[ \%\text{reg} = \frac{V_S/|A| - V_R}{V_R} \]

and \(V_S\) itself contains both effects. Separate them by asking what each would give alone.

The Ferranti part. Set the load to zero: \(V_S = |A|V_R\) and the regulation would be

\[ \frac{|A|V_R/|A| - V_R}{V_R} = 0 \]

— which is not the answer, because the Ferranti effect only produces regulation when a fixed \(V_S\) is held. Take instead \(V_S\) at its loaded value of 460.6 kV and remove the load:

\[ V_{R,\text{NL}} = \frac{460.6}{0.9060} = 508.4\ \text{kV} \]

The two components of the 108.4 kV total rise:

\[ \begin{array}{lcl} \text{Loss of the } B\mathbf{I}_R \text{ drop} & 460.6 - 400 = 60.6\ \text{kV} & 55.9\% \\ \text{Ferranti rise } (1/|A| - 1)V_S & 508.4 - 460.6 = 47.8\ \text{kV} & 44.1\% \\ \hline \text{Total} & 108.4\ \text{kV} & 27.08\%\ \text{of } V_R \end{array} \]

The remedies map directly onto the split:

\[ \begin{array}{ll} \text{The } 60.6\ \text{kV drop} & \text{depends on } |B| \Rightarrow \textbf{series capacitors} \\ \text{The } 47.8\ \text{kV rise} & \text{depends on } |A| \Rightarrow \textbf{shunt reactors} \end{array} \]
Neither remedy alone can remove more than about half the regulation of this line, and the split tells you so before any compensation is designed. A line whose regulation is dominated by the load drop needs series capacitors; one dominated by the Ferranti term needs reactors. Here the two are close to even, which is why Problem 12 finds that only the combination brings the regulation into range — and why a designer who reaches for one lever alone will be disappointed by half.
Answer60.6 kV (56%) from the load drop, addressed by series capacitors; 47.8 kV (44%) from Ferranti, addressed by shunt reactors
Problem 5Exam levelShunt Reactors

Shunt reactors absorbing 60% of the line's charging are installed. Find the effect on \(\gamma\), \(Z_c\) and the ABCD constants.

Solution

Reactors distributed along the line cancel a fraction \(k\) of its shunt susceptance, so the effective per-km admittance becomes

\[ y_{\text{eff}} = y(1 - k) = j3.0\times10^{-6}(0.4) = j1.2\times10^{-6}\ \text{S/km} \]

Since \(z\) is unchanged and only the magnitude of \(y\) alters:

\[ \gamma_{\text{eff}} = \gamma\sqrt{1-k} = 1.1369\times10^{-3}\sqrt{0.4} = 7.190\times10^{-4}\angle79.10^\circ \]
\[ Z_{c,\text{eff}} = \frac{Z_c}{\sqrt{1-k}} = \frac{378.95}{0.6325} = 599.2\angle-10.90^\circ\ \Omega \]

The angles are untouched, because \(y\) remains purely imaginary.

The electrical length falls:

\[ \gamma_{\text{eff}}l = 0.2876\angle79.10^\circ, \qquad \beta_{\text{eff}}l = 16.2^\circ \]

against 25.6° uncompensated — the line now behaves as though it were 253 km long.

The new constants:

\[ A = \cosh\gamma_{\text{eff}}l = 0.96193\angle0.90^\circ \]
\[ B = 170.13\angle68.49^\circ\ \Omega, \qquad C = 4.798\times10^{-4}\angle90.44^\circ\ \text{S} \]

The Ferranti rise falls accordingly:

\[ \frac{1}{0.96193} - 1 = 3.96\% \quad\text{against } 10.37\% \]
Shunt compensation makes a line electrically shorter, and that is the cleanest way to think about it. A 400 km line with 60% reactors behaves in every respect like a 253 km uncompensated one — same \(\beta l\), same \(|A|\), same Ferranti rise. Note however that \(|B|\) barely moved, from 166.9 to 170.1 \(\Omega\): reactors do nothing about the series impedance, so the voltage drop under load is untouched. Problem 8 examines what else they cost.
Answer\(\gamma_{\text{eff}} = \gamma\sqrt{0.4}\), \(Z_{c,\text{eff}} = 599\ \Omega\); \(|A|\) rises to 0.962 and the Ferranti rise falls to 3.96%
Problem 6Exam levelDegree of Compensation

Tabulate \(|A|\), the Ferranti rise, \(|B|\), \(|Z_c|\) and SIL against the degree of shunt compensation, and find the compensation needed to bring the no-load voltage within 5%.

Solution

Applying \(\gamma_{\text{eff}} = \gamma\sqrt{1-k}\) and \(Z_{c,\text{eff}} = Z_c/\sqrt{1-k}\) at each degree:

\[ \begin{array}{cccccc} k & |A| & \text{Ferranti} & |B|\ (\Omega) & |Z_c|\ (\Omega) & \text{SIL (MW)} \\ \hline 0 & 0.9060 & 10.37\% & 166.9 & 379 & 422 \\ 0.3 & 0.9338 & 7.09\% & 168.5 & 453 & 353 \\ 0.5 & 0.9525 & 4.99\% & 169.6 & 536 & 299 \\ 0.6 & 0.9619 & 3.96\% & 170.1 & 599 & 267 \\ 0.7 & 0.9714 & 2.95\% & 170.7 & 692 & 231 \\ 0.8 & 0.9809 & 1.95\% & 171.2 & 847 & 189 \end{array} \]

To bring the Ferranti rise within 5% the table shows \(k = 0.5\) gives 4.99% — just inside:

\[ k = 0.50 \quad\Rightarrow\quad \text{no-load } V_R = 400(1.0499) = 420.0\ \text{kV} \]

Exactly at the 420 kV insulation class limit, so 60% would be chosen in practice for margin.

Reading the columns against each other reveals the trade. As \(k\) rises:

\[ \begin{array}{ll} |A| \to 1 & \text{good — the Ferranti effect disappears} \\ |B| \text{ barely changes} & \text{the load voltage drop is untouched} \\ |Z_c| \text{ rises steeply} & \text{bad — SIL collapses} \end{array} \]
SIL more than halves between no compensation and 80%, and that is the hidden price. A line compensated to \(k = 0.8\) has a natural loading of 189 MW where it began at 422 — so it is a reactive sink above 189 MW where before it was a source up to 422. The reactors that fixed the light-load problem have created a heavy-load one, which is precisely why they are switched out as the load rises rather than left permanently connected.
Answer\(k = 0.50\) brings the rise to 4.99%; SIL falls from 422 to 299 MW as the price
Problem 7Exam levelSizing the Reactors

Size the reactors for 60% compensation of the 400 km line: total rating, rating per end, reactance and inductance per phase.

Solution

The line's total shunt susceptance and its charging:

\[ B_{\text{line}} = (3.0\times10^{-6})(400) = 1.2\times10^{-3}\ \text{S} \]
\[ Q_{\text{charge}} = V_L^{2}B_{\text{line}} = (400\times10^{3})^{2}(1.2\times10^{-3}) = 192\ \text{MVAr} \]

Reactors absorbing 60% of it:

\[ Q_L = 0.60(192) = 115.2\ \text{MVAr} \]

Split equally between the two ends:

\[ Q_{L,\text{end}} = \frac{115.2}{2} = 57.6\ \text{MVAr per end} \]

Reactance and inductance of the total bank, per phase:

\[ X_L = \frac{V_L^{2}}{Q_L} = \frac{1.6\times10^{11}}{115.2\times10^{6}} = 1389\ \Omega \]
\[ L = \frac{X_L}{2\pi f} = \frac{1389}{314.16} = 4.42\ \text{H} \]

Each end's reactor is twice this reactance and twice the inductance — 2778 \(\Omega\) and 8.84 H per phase.

These are large machines: an 8.8 henry oil-immersed reactor for 400 kV service stands several metres high and weighs tens of tonnes per phase.

Splitting the bank between the two ends is not merely convenient — it is what makes the distributed approximation of Problem 5 defensible. Treating the reactors as reducing \(y\) uniformly assumes they are spread along the line, which two lumped banks are not. With reactors at the ends only, the middle of the line remains uncompensated and bulges above both terminal voltages, exactly as Set 12 Challenge C2 warned. Problem 19 takes up the mid-point reactor that addresses it.
Answer\(Q_L = 115.2\) MVAr total, 57.6 per end; \(X_L = 1389\ \Omega\), \(L = 4.42\) H per phase
Problem 8Challenge-liteWhat It Costs

Find the performance of the 60%-shunt-compensated line at 300 MW, 0.95 lagging, and compare with the uncompensated case. Account for every difference.

Solution

Using the compensated constants from Problem 5:

\[ \begin{array}{lcc} & \text{Uncompensated} & \text{60\% shunt} \\ \hline |A| & 0.9060 & 0.9619 \\ |B|\ (\Omega) & 166.9 & 170.1 \\ \text{Ferranti} & 10.37\% & 3.96\% \\ \text{SIL (MW)} & 422 & 267 \\ \hline V_S\ (\text{kV}) & 460.6 & 483.1 \\ \%\text{reg} & 27.08 & 25.55 \\ \eta\ (\%) & 89.46 & 89.09 \\ \cos\phi_S & 0.993\ \text{lead} & 0.962\ \text{lead} \end{array} \]

What improved: the Ferranti rise, from 10.4% to 4.0% — a 62% reduction, exactly as designed.

What got worse:

\[ \begin{array}{ll} V_S \text{ rose } 460.6 \to 483.1\ \text{kV} & \text{the reactors draw current through } B \\ \text{SIL fell } 422 \to 267\ \text{MW} & Z_c \text{ rose by } 1/\sqrt{0.4} \\ \eta \text{ fell slightly} & \text{reactor current adds to } I^2R \end{array} \]

What barely changed: the regulation, from 27.08% to 25.55%. The lower \(V_{R,\text{NL}}\) was almost entirely offset by the higher \(V_S\) needed to drive the load.

The line now runs at 300 MW against an SIL of 267 — above its natural loading, where before it was below. The reactive character has reversed.

Shunt compensation solved the light-load problem and made the heavy-load problem slightly worse, which is exactly what it should be expected to do. Its whole mechanism is to remove capacitive support, and capacitive support is helpful at heavy load and harmful at light load. This is why fixed reactors are a poor answer and switched ones the standard: banks are connected at night and disconnected at peak, following the load. A line with permanently connected reactors sized for the no-load case is over-compensated for most of its operating life.
AnswerFerranti 10.4% → 4.0%, but \(V_S\) rises to 483 kV, SIL falls to 267 MW and regulation improves only 1.5 points
Problem 9Exam levelSeries Capacitors

Series capacitors compensating 50% of the line reactance are installed instead. Find the new constants and performance.

Solution

Series compensation reduces the reactive part of \(z\), leaving the resistance alone:

\[ z_{\text{eff}} = r + jx(1-k) = 0.16 + j0.40(0.5) = 0.16 + j0.20\ \Omega/\text{km} \]

Note that the angle of \(z\) changes now, unlike the shunt case — so \(\gamma\) and \(Z_c\) both rotate as well as scale.

Recomputing from scratch:

\[ z_{\text{eff}} = 0.2561\angle51.34^\circ, \qquad \gamma_{\text{eff}} = \sqrt{z_{\text{eff}}y} = 8.766\times10^{-4}\angle70.67^\circ \]
\[ Z_{c,\text{eff}} = \sqrt{z_{\text{eff}}/y} = 292.2\angle-19.33^\circ\ \Omega \]

The new constants:

\[ A = 0.9529\angle1.24^\circ, \qquad B = 100.82\angle70.11^\circ\ \Omega \]

Performance at 300 MW, 0.95 lagging:

\[ \begin{array}{lccc} & \text{Uncomp.} & \text{60\% shunt} & \text{50\% series} \\ \hline \text{Ferranti} & 10.37\% & 3.96\% & 4.94\% \\ |B|\ (\Omega) & 166.9 & 170.1 & 100.8 \\ V_S\ (\text{kV}) & 460.6 & 483.1 & 450.9 \\ \%\text{reg} & 27.08 & 25.55 & 18.29 \\ \text{SIL (MW)} & 422 & 267 & 548 \end{array} \]
Series compensation improved the Ferranti effect almost as much as the reactors did, and improved everything else as well. That is not obvious in advance: its mechanism is to reduce \(x\), which lowers \(\gamma = \sqrt{zy}\) as surely as reducing \(y\) does. The difference lies in \(Z_c = \sqrt{z/y}\), which the two move in opposite directions — and hence in the SIL, which rises to 548 MW here where the reactors cut it to 267.
Answer\(|B| = 100.8\ \Omega\), Ferranti 4.94%, regulation 18.29%, SIL 548 MW
Problem 10Warm-upSeries and SIL

Tabulate the effect of series compensation on \(|A|\), \(|B|\), \(|Z_c|\) and SIL, and contrast with the shunt table of Problem 6.

Solution

Recomputing at each degree of series compensation:

\[ \begin{array}{ccccc} k & |A| & \text{Ferranti} & |B|\ (\Omega) & \text{SIL (MW)} \\ \hline 0 & 0.9060 & 10.37\% & 166.9 & 422 \\ 0.3 & 0.9341 & 7.06\% & 126.1 & 488 \\ 0.5 & 0.9529 & 4.94\% & 100.8 & 548 \\ 0.7 & 0.9718 & 2.90\% & 79.2 & 620 \end{array} \]

Setting the two mechanisms side by side at equal effect on the Ferranti rise (about 5%):

\[ \begin{array}{lcc} & \text{50\% shunt} & \text{50\% series} \\ \hline \text{Ferranti} & 4.99\% & 4.94\% \\ |B|\ (\Omega) & 169.6 & 100.8 \\ |Z_c|\ (\Omega) & 536 & 292 \\ \text{SIL (MW)} & 299 & 548 \end{array} \]

The same improvement in \(|A|\), and an SIL differing by a factor of 1.8.

The reason. Both reduce \(|\gamma| = \sqrt{|z||y|}\) and hence improve \(|A|\). But

\[ Z_c = \sqrt{\frac{z}{y}}: \quad \text{shunt reduces } y \Rightarrow Z_c\ \uparrow; \quad \text{series reduces } z \Rightarrow Z_c\ \downarrow \]
The product \(zy\) and the ratio \(z/y\) are independent knobs, and the two compensation methods turn them independently. This is the same structural observation made in Set 6 Problem 15 about inductance and capacitance: \(\gamma\) depends on the product and \(Z_c\) on the ratio. Compensating both series and shunt in the right proportion can therefore set \(\gamma\) and \(Z_c\) to any desired pair of values — which is exactly what Problem 12 does, and what a designer with both tools available actually has at their disposal.
AnswerSeries compensation raises SIL to 548 MW where shunt cuts it to 299 for the same Ferranti improvement
Problem 11Challenge-liteShunt against Series

Set out the complete comparison between shunt and series compensation of a long line, and state when each is chosen.

Solution

The mechanisms. Both reduce \(|\gamma| = \sqrt{|z||y|}\) and so improve \(|A|\). They differ entirely in their effect on \(Z_c = \sqrt{z/y}\):

\[ \begin{array}{lcc} & \text{Shunt reactors} & \text{Series capacitors} \\ \hline \text{Acts on} & y & z \\ \gamma & \times\sqrt{1-k} & \times\sqrt{1-k}\ \text{(approx)} \\ Z_c & \div\sqrt{1-k}\ \ (\uparrow) & \times\sqrt{1-k}\ \ (\downarrow) \\ |A| & \text{improves} & \text{improves} \\ |B| & \text{barely changes} & \text{falls sharply} \\ \text{SIL} & \text{falls} & \text{rises} \end{array} \]

At equal effect on the Ferranti rise (about 5%), from Problems 6 and 10:

\[ \begin{array}{lcc} & \text{50\% shunt} & \text{50\% series} \\ \hline \%\text{reg at 300 MW} & 25.55 & 18.29 \\ \text{SIL (MW)} & 299 & 548 \\ \text{Rating} & 96\ \text{MVAr} & 3I^2X_C \end{array} \]

Series compensation is better on every count here — better regulation, higher SIL, smaller rating. So why are reactors used at all?

Because they solve a problem series capacitors cannot:

\[ \begin{array}{ll} \text{Light load and no load} & \text{Series } Q \propto I^2 \to 0;\ \text{reactors act regardless} \\ \text{Energisation} & \text{The line must be safe to switch in unloaded} \\ \text{Generator absorption} & \text{Reactors relieve the machine of leading vars} \\ \text{Subsynchronous resonance} & \text{Series capacitors risk it; reactors do not} \\ \text{Protection} & \text{Series capacitors confuse distance relays} \end{array} \]

So the two are complementary, not alternatives. Series capacitors serve the heavily loaded condition — regulation, power transfer, stability. Shunt reactors serve the lightly loaded one — Ferranti, energisation, generator var absorption.

A long EHV line receives both, and the reactors are switched while the capacitors are not. The reactive requirement reverses with loading — the line generates vars below SIL and absorbs them above — so a fixed compensation cannot serve both ends of the range. Series capacitors self-regulate through their \(I^2\) dependence and can therefore stay in permanently; reactors do not, and must be switched out as the load rises. That asymmetry, not any difference in effectiveness, is what decides the plant on a real line.
AnswerSeries is better under load (18.3% vs 25.6% regulation, SIL 548 vs 299 MW); shunt is essential at light load and for energisation — both are fitted
Problem 12Exam levelCombined

Apply 60% shunt and 50% series compensation together. Find the resulting constants and performance at 300 MW, 0.95 lagging.

Solution

Both modifications applied to the per-km parameters:

\[ z_{\text{eff}} = 0.16 + j0.20\ \Omega/\text{km}, \qquad y_{\text{eff}} = j1.2\times10^{-6}\ \text{S/km} \]

Recomputing:

\[ \gamma_{\text{eff}} = \sqrt{z_{\text{eff}}y_{\text{eff}}} = 5.543\times10^{-4}\angle70.67^\circ, \qquad Z_{c,\text{eff}} = 462.0\angle-19.33^\circ\ \Omega \]
\[ A = 0.9809\angle0.89^\circ, \qquad B = 101.80\angle51.63^\circ\ \Omega \]

Performance, against the three single-remedy cases:

\[ \begin{array}{lcccc} & \text{None} & \text{60\% sh} & \text{50\% se} & \text{Both} \\ \hline |A| & 0.9060 & 0.9619 & 0.9529 & 0.9809 \\ \text{Ferranti} & 10.37\% & 3.96\% & 4.94\% & 1.94\% \\ |B|\ (\Omega) & 166.9 & 170.1 & 100.8 & 101.8 \\ V_S\ (\text{kV}) & 460.6 & 483.1 & 450.9 & 462.1 \\ \%\text{reg} & 27.08 & 25.55 & 18.29 & 17.78 \\ \text{SIL (MW)} & 422 & 267 & 548 & 346 \end{array} \]

The combination gives the best Ferranti figure (1.94%) and a regulation of 17.78% — but the regulation is still far above the 10% target.

Note also that SIL has landed at 346 MW: the series compensation's increase and the shunt's decrease have partly cancelled, leaving it near the original.

Compensating the line has taken the regulation from 27% to 18% and stalled there, and the reason is that the remaining drop is not the line's fault. The load draws 98.6 MVAr of its own, and that reactive current must cross \(|B| = 102\ \Omega\) whatever is done to the line. No amount of line compensation removes a load's own reactive demand — only compensation at the load can, which is what Problem 14 turns to.
Answer\(|A| = 0.9809\), \(|B| = 101.8\ \Omega\), Ferranti 1.94%, regulation 17.78%, SIL 346 MW
Problem 13Warm-upEfficiency After

Compare the transmission efficiency before and after the compensation of Problem 12, and explain the result.

Solution

At 300 MW, 0.95 lagging:

\[ \begin{array}{lc} & \eta\ (\%) \\ \hline \text{Uncompensated} & 89.46 \\ \text{60\% shunt} & 89.09 \\ \text{50\% series} & 89.17 \\ \text{Both} & 88.96 \end{array} \]

Every form of compensation made the efficiency slightly worse.

The reason is straightforward. The loss is \(I^2R\) and neither remedy alters \(R\). What they do alter is the current distribution:

\[ \begin{array}{ll} \text{Shunt reactors} & \text{draw their own current through part of the line} \\ \text{Series capacitors} & \text{lower } V_S \text{ slightly, so } I \text{ is marginally higher} \\ \text{Both} & \text{leave } R \text{ untouched} \end{array} \]

The changes are fractions of a percentage point — small, but the sign is the point: compensation is not a loss-reduction measure.

This is worth stating because the opposite is so often assumed. Shunt capacitors at a load do reduce losses, by reducing the current the line carries — that is the result of Set 10 Problem 9. Shunt reactors on a line do the reverse. The two are both "shunt compensation" and they act in opposite directions, because one removes reactive current from the line and the other adds it. Naming a device by its connection rather than its function is a reliable source of confusion.
AnswerEfficiency falls slightly, 89.46% to 88.96% — compensation does not reduce losses and marginally increases them
Problem 14Exam levelLoad Power Factor

Shunt capacitors are installed at the receiving end of the compensated line of Problem 12 to correct the load power factor. Find the regulation at unity, 0.98 leading and 0.95 leading, and the capacitor rating in each case.

Solution

The 300 MW load at 0.95 lagging demands

\[ Q_{\text{load}} = 300\tan(18.19^\circ) = 98.6\ \text{MVAr} \]

Correcting to each target requires the capacitors to supply the load's demand plus any leading component:

\[ Q_C = 300\left[\tan(18.19^\circ) + \tan\phi_2\right] \]

Evaluating, with the resulting line performance:

\[ \begin{array}{lccc} \text{Load p.f.} & Q_C\ (\text{MVAr}) & V_S\ (\text{kV}) & \%\text{reg} \\ \hline 0.95\ \text{lag} & 0 & 462.1 & 17.78 \\ \text{unity} & 98.6 & 444.6 & 13.32 \\ 0.98\ \text{lead} & 159.5 & 434.2 & 10.66 \\ 0.95\ \text{lead} & 197.2 & 427.9 & 9.05 \end{array} \]

Correction to 0.95 leading brings the regulation to 9.05% — inside the 10% target at last, and the sending voltage down to 427.9 kV.

The efficiency, however, falls slightly to 87.4%, because the leading current adds to the conductor current without delivering power.

Nearly 200 MVAr of capacitors at the load — two thirds of the real power in reactive plant — and this is what it took. That is the honest measure of how difficult a 400 km line at this loading is. It also shows why reactive support is sited at load centres rather than on the line: the capacitors relieve \(|B|\) of carrying the load's reactive current at all, which no amount of line compensation can achieve. Set 34 takes up how such support is planned and switched across a whole network.
Answer197 MVAr correcting to 0.95 leading gives 9.05% regulation — the first configuration to meet the target
Problem 15Exam levelReactive Balance

For the uncompensated line, tabulate the reactive power at each end against loading, and identify the crossover.

Solution

Computing \(Q_S = 3V_SI_S\sin\phi_S\) and \(Q_R = P_R\tan\phi_R\) at each loading, with a negative \(Q_S\) meaning the line delivers vars back to the source:

\[ \begin{array}{cccc} P\ (\text{MW}) & Q_S\ (\text{MVAr}) & Q_R\ (\text{MVAr}) & \text{Net generated} \\ \hline 0 & -168.4 & 0 & 168.4 \\ 100 & -144.9 & 32.9 & 177.8 \\ 200 & -102.2 & 65.7 & 168.0 \\ 300 & -40.3 & 98.6 & 138.9 \\ 422 & +61.2 & 138.7 & 77.5 \\ 500 & +141.1 & 164.3 & 23.2 \end{array} \]

The crossover in \(Q_S\) — where the sending end changes from absorbing vars to supplying them — occurs near 340 MW.

The line's own net generation falls steadily from 168 MVAr at no load to 23 MVAr at 500 MW, as the \(I^2X_L\) absorption grows to offset the \(V^2B\) generation.

Setting the two equal gives the surge impedance loading:

\[ 3I^{2}X_L = V_L^{2}B \quad\Rightarrow\quad P = \frac{V_L^{2}}{\sqrt{X_L/B}} = \frac{V_L^{2}}{|Z_c|} = \text{SIL} \]

Though the tabulated net generation does not reach zero until beyond 500 MW, because the load's own reactive demand at 0.95 lagging is being supplied through the line as well.

The reactive requirement of this line swings by 300 MVAr between no load and full load, and reverses sign in the middle. No single fixed compensation can serve that range — which is the whole argument for switched reactors, switched capacitors and, where the swing is fast, static var compensators. The 340 MW crossover is not a design target but a scheduling boundary: below it the operator switches reactors in, above it capacitors.
Answer\(Q_S\) swings from \(-168\) MVAr at no load to \(+141\) at 500 MW, crossing zero near 340 MW
Problem 16DesignOperating at SIL

The uncompensated 400 km line has \(Z_c = 378.95\angle-10.90^\circ\ \Omega\) and a surge impedance loading of 422 MW. Load it at exactly 422 MW at unity power factor with \(V_R = 400\) kV, and separately terminate it in \(Z_c\) itself. Compare the two, and say which deserves the name.

Solution

Case A — 422 MW at unity power factor. The receiving current is real:

\[ I_R = \frac{422.2\times10^{6}}{3\times230.94\times10^{3}} = 609.4\angle0^\circ\ \text{A} \]

Through the exact constants \(A = 0.9060\angle2.35^\circ\), \(B = 166.87\angle68.94^\circ\):

\[ \mathbf{V}_S = 266.52\angle22.85^\circ\ \text{kV (phase)} \;=\; 461.6\ \text{kV line} \]

A rise of 61.6 kV over the line — 15.4% — at the loading that is supposed to give a flat profile.

Case B — terminated in \(Z_c\). Now the current is set by the impedance, not chosen:

\[ I_R = \frac{V_R}{Z_c} = \frac{230.94\angle0^\circ\ \text{kV}}{378.95\angle-10.90^\circ} = 609.4\angle10.90^\circ\ \text{A} \]

The same magnitude — but leading by 10.90°, because \(Z_c\) of a real line is slightly capacitive.

Repeating the calculation gives \(V_S = 435.9\) kV line — a rise of 8.98%, not 15.4%. And the sending-end angle is:

\[ \angle\mathbf{V}_S = 25.585^\circ \qquad\text{against}\qquad \beta l = 0.00111634\times400 = 0.446535\ \text{rad} = 25.585^\circ \]

Identical to eight figures. That is the signature of a matched line: the voltage at any point is the sending voltage retarded in phase by \(\beta x\) and attenuated by \(e^{-\alpha x}\), nothing more.

The profiles. Both cases delivered 609.4 A, so the difference is entirely in the phase of that current:

\[ \begin{array}{lccccc} x\ \text{(km from RE)} & 0 & 100 & 200 & 300 & 400 \\ \hline \text{unity pf (kV)} & 400.0 & 416.7 & 432.6 & 447.7 & 461.6 \\ Z_c\ \text{terminated (kV)} & 400.0 & 408.7 & 417.6 & 426.6 & 435.9 \end{array} \]

The matched profile is a pure exponential. Check it:

\[ \frac{|V_S|}{|V_R|} = \frac{435.92}{400} = 1.08980 \qquad\text{and}\qquad e^{\alpha l} = e^{0.00021499\times400} = e^{0.085995} = 1.08980 \]

Exactly. The 8.98% rise is not a Ferranti effect and not a regulation problem — it is the attenuation of a wave, read backwards.

The power factor is the same at both ends. At the receiving end \(P + jQ = 414.6 - j79.84\) MVA; at the sending end \(492.4 - j94.83\). The ratios:

\[ \frac{-79.84}{414.60} = -0.19258 \qquad \frac{-94.83}{492.41} = -0.19258 \]

A matched line has the same power factor everywhere along it — \(\cos(10.90^\circ) = 0.982\) leading. It neither generates nor absorbs net vars; it merely passes them in proportion.

The efficiency, however, is poor: 414.6/492.4 = 84.20%. Nearly 78 MW lost. SIL is a reactive optimum, not a loss optimum — it is the loading at which \(I^2X_L\) absorption exactly matches \(V^2B\) generation, and \(r\) plays no part in that balance at all.

"Loading a line at SIL" and "terminating a line in \(Z_c\)" are not the same instruction, and the textbook flat profile belongs only to the second. Even then, the profile is flat only for a lossless line; here it rises by exactly \(e^{\alpha l}\). And the leading 10.90° that the second case requires is real reactive power the load must supply — 80 MVAr of it — which is why real lines are run near SIL rather than at it.
Answer422 MW at unity pf: \(V_S = 461.6\) kV. Terminated in \(Z_c\): \(V_S = 435.9\) kV \(= 400e^{\alpha l}\), \(\angle V_S = \beta l\) exactly
Problem 17TheoryThe Tuned Line

Show that a lossless line of half-wavelength has \(A = -1\) and \(B = 0\), and therefore zero regulation at every load. Find that length for this line, and evaluate the constants there with the resistance restored.

Solution

The lossless case. With \(r = g = 0\), \(\gamma = j\beta\) is purely imaginary and the hyperbolic functions become circular:

\[ A = \cosh(j\beta l) = \cos\beta l \qquad B = jZ_c\sin\beta l \qquad C = \frac{j\sin\beta l}{Z_c} \]

With \(Z_c = \sqrt{x/b}\) now purely real — the surge impedance proper.

At \(\beta l = \pi\) — one half wavelength — \(\cos\pi = -1\) and \(\sin\pi = 0\):

\[ A = D = -1, \qquad B = 0, \qquad C = 0 \]

What that means. Substituting into the two-port equations:

\[ \mathbf{V}_S = -\mathbf{V}_R + 0\cdot\mathbf{I}_R = -\mathbf{V}_R \qquad \mathbf{I}_S = 0 + (-1)\mathbf{I}_R = -\mathbf{I}_R \]

The receiving voltage equals the sending voltage in magnitude whatever the load — including no load. Regulation is identically zero, and the sending current equals the receiving current. The line has become a perfect 1:1 transformer with a 180° phase shift.

The half-wave length for this line. From \(\beta = 1.11634\times10^{-3}\) rad/km:

\[ \lambda = \frac{2\pi}{\beta} = \frac{6.28319}{1.11634\times10^{-3}} = 5628\ \text{km} \qquad \frac{\lambda}{2} = 2814\ \text{km} \]

Corresponding to a propagation velocity \(v = f\lambda = 50\times5628 = 2.814\times10^{5}\) km/s, or \(0.938c\).

With the resistance restored. Evaluating the exact constants at \(l = 2814\) km with \(z = 0.16 + j0.40\):

\[ \alpha l = 2.1499\times10^{-4}\times2814 = 0.6050\ \text{Np} \]
\[ A = \cosh(0.6050 + j\pi) = -\cosh(0.6050) = 1.1868\angle180^\circ \]

Using \(\cosh(u + j\pi) = -\cosh u\). The magnitude is above unity, not equal to it.

And \(B = Z_c\sinh(\gamma l)\) with \(\sinh(u + j\pi) = -\sinh u\):

\[ |B| = 378.95\times\sinh(0.6050) = 378.95\times0.6425 = 243.5\ \Omega \]

Not zero — 243 Ω, larger than the whole 400 km line's \(|B|\) of 167 Ω.

So the ideal fails on both counts. On no load the receiving voltage is now \(V_S/|A| = 0.843V_S\) — a 16% drop, the opposite of Ferranti. And the loss over 2814 km is crippling: \(e^{-2\alpha l} = e^{-1.21} = 0.298\), so less than a third of the incident power survives the journey.

The tuned line is a property of \(\alpha = 0\), not of \(\beta l = \pi\). The zeros in \(B\) and \(C\) come from \(\sin\pi = 0\), and the moment \(\gamma\) acquires a real part that sine becomes a hyperbolic sine of the attenuation, which is never zero. At 2814 km the attenuation is 0.605 Np and the ideal is not approached — it is inverted.
AnswerLossless: \(A = -1\), \(B = 0\), zero regulation. Here \(\lambda/2 = 2814\) km, at which \(|A| = 1.187\) and \(|B| = 243.5\ \Omega\)
Problem 18ChallengeSynthesising a Tuned Line

A tuned line need not be 2814 km long if \(\beta\) can be raised instead. Find the series reactance and shunt susceptance that would make the 400 km line a half-wave line at 50 Hz, evaluate its constants, and cost the compensation.

Solution

The requirement. We need \(\beta l = \pi\) over 400 km:

\[ \beta_{\text{req}} = \frac{\pi}{400} = 7.85398\times10^{-3}\ \text{rad/km} \qquad \frac{\beta_{\text{req}}}{\beta} = \frac{7.85398\times10^{-3}}{1.11634\times10^{-3}} = 7.035 \]

Seven times the phase constant the line has.

How to get it. Since \(\gamma = \sqrt{zy}\), multiplying both \(x\) and \(b\) by a factor \(m\) multiplies \(\gamma\) by \(m\) while leaving \(Z_c = \sqrt{z/y}\) nearly unchanged. That means added series inductance and added shunt capacitance — the reverse of both conventional remedies.

Because \(r\) cannot be scaled with them, the exact factor is found by solving \(\beta l = \pi\) for \(m\) in

\[ \gamma(m) = \sqrt{(0.16 + j0.40m)(j3.0\times10^{-6}m)} \]

which gives \(m = 7.167\), a little above the naive 7.035 because the resistance drags \(\beta\) down slightly.

The resulting parameters:

\[ x' = 7.167\times0.40 = 2.867\ \Omega/\text{km} \qquad b' = 7.167\times3.0 = 21.50\ \mu\text{S/km} \]
\[ Z_c' = 365.4\angle-1.60^\circ\ \Omega \qquad \alpha' l = 0.0876\ \text{Np} \]

The attenuation over the whole line is now only 0.0876 Np — a twentieth of what 2814 km of real line would cost.

The constants:

\[ A = \cosh(0.0876 + j\pi) = 1.00384\angle180^\circ \qquad |B| = 365.4\sinh(0.0876) = 32.05\ \Omega \]

Against 0.9060 and 166.9 Ω uncompensated. \(|B|\) has fallen by a factor of five and \(|A|\) is within 0.4% of unity — the no-load voltage now falls by 0.38% instead of rising by 10.37%.

The bill. The added shunt susceptance over 400 km is \(\Delta B = (7.167-1)\times3.0\times10^{-6}\times400 = 7.40\times10^{-3}\) S:

\[ Q_C = V_L^{2}\Delta B = (400\times10^{3})^{2}\times7.40\times10^{-3} = 1184\ \text{MVAr} \]

Six times the line's own charging of 192 MVAr, and nearly three times the SIL.

And the added series reactance:

\[ \Delta X = (7.167-1)\times0.40\times400 = 987\ \Omega \qquad L = \frac{987}{2\pi\times50} = 3.14\ \text{H per phase} \]

Against the line's own 160 Ω. We would be adding six times more reactance than the line possesses, at 400 kV, carrying full load current.

And the profile is the real objection. Loading the synthesised line at 300 MW, 0.95 lagging with \(V_R = 400\) kV:

\[ \begin{array}{lccccccccc} x\ \text{(km)} & 0 & 50 & 100 & 150 & 200 & 250 & 300 & 350 & 400 \\ \hline V\ \text{(kV)} & 400 & 445 & 461 & 443 & 402 & 360 & 350 & 381 & 433 \end{array} \]

The terminals are well behaved; the interior is not. At 100 km the voltage is 461 kV and at 300 km it is 350 kV — a 111 kV swing inside a line whose two ends differ by 33 kV. Insulation must be rated for the maximum, not the terminal value.

The tuned line is a textbook curiosity, and this problem is the arithmetic that shows why. The compensation costs 1184 MVAr and 987 Ω to save 10% of no-load voltage rise, and buys in exchange an interior voltage profile that swings a quarter of nominal. Half-wave transmission is proposed occasionally for very long HVAC links precisely because the length is already there and the compensation is not needed — which is the opposite of the situation here.
Answer\(m = 7.167\): 1184 MVAr shunt capacitors and 987 Ω series inductance give \(|A| = 1.0038\), \(|B| = 32\ \Omega\) — and an interior swing of 111 kV
Problem 19DesignIntermediate Compensation

The 115.2 MVAr of shunt reactors from Problem 7 was assumed split equally between the two ends. Compute the no-load voltage profile along the line with that arrangement, at \(V_S = 400\) kV, and compare it with the same total split three ways — 20% at each end and 20% at the mid-point.

Solution

The two-reactor case. Each end carries 57.6 MVAr, so each reactor has

\[ B_r = \frac{57.6\times10^{6}}{(400\times10^{3})^{2}} = 3.60\times10^{-4}\ \text{S} \qquad X_r = 2778\ \Omega \qquad L_r = 8.84\ \text{H} \]

The sending-end reactor sits on the source busbar and does not affect the profile at all; only the receiving-end one does.

Setting up the profile. Measure \(x\) from the receiving end. The current leaving the line there is the reactor current:

\[ \mathbf{I}_R = -jB_r\mathbf{V}_R \]
\[ \mathbf{V}(x) = \mathbf{V}_R\cosh\gamma x + Z_c\mathbf{I}_R\sinh\gamma x = \mathbf{V}_R\left[\cosh\gamma x - jB_rZ_c\sinh\gamma x\right] \]

Evaluating at \(x = 400\) and scaling so that \(|V(400)| = 400\) kV:

\[ \begin{array}{lccccccccc} x\ \text{(km from RE)} & 0 & 50 & 100 & 150 & 200 & 250 & 300 & 350 & 400 \\ \hline V\ \text{(kV)} & 416.0 & 418.4 & 419.5 & 419.4 & 418.0 & 415.3 & 411.4 & 406.3 & 400.0 \end{array} \]

The maximum is not at either end. Scanning the profile finely puts it at \(x = 119\) km, where \(V = 419.6\) kV — 3.6 kV above the receiving end and 19.6 kV above the sending end.

Why the bulge exists. A lumped reactor absorbs charging current only where it stands. Between the two reactors the line's distributed capacitance goes on generating vars with nothing local to absorb them, so the voltage climbs until the series reactance carrying that current away creates enough drop to arrest it. The two reactors have suppressed the terminal symptom and left an interior one.

Three units of 38.4 MVAr. Repeating with \(B_r = 2.40\times10^{-4}\) S at each end and the same at 200 km, the mid-point reactor drawing \(-jB_r\mathbf{V}_{\text{mid}}\) out of the through current:

\[ \begin{array}{lccccccccc} x\ \text{(km)} & 0 & 50 & 100 & 150 & 200 & 250 & 300 & 350 & 400 \\ \hline V\ \text{(kV)} & 415.9 & 417.3 & 417.4 & 416.3 & 413.9 & 412.3 & 409.4 & 405.3 & 400.0 \end{array} \]

Maximum 417.5 kV at 80 km. The kink at 200 km is the mid-point reactor taking its share.

The comparison, for identical installed MVAr:

\[ \begin{array}{lccc} & V_R\ \text{(kV)} & V_{\max}\ \text{(kV)} & \text{Location} \\ \hline 2\times57.6\ \text{MVAr} & 416.0 & 419.6 & 119\ \text{km} \\ 3\times38.4\ \text{MVAr} & 415.9 & 417.5 & 80\ \text{km} \end{array} \]

The terminal voltage is essentially unchanged — 0.1 kV — but the interior peak falls by 2.1 kV. The compensation has been made to act where it is needed rather than where it is convenient.

Regulation is a terminal quantity; insulation is not. Every calculation in Problems 1–15 treated the line through its ABCD constants, which know only about the two ends — and by that measure the two arrangements are indistinguishable. The difference appears only when the profile is computed, and it is the profile that the insulators, the surge arresters and the corona losses respond to. On lines much longer than this one the interior bulge is the binding constraint, and mid-point compensation with switched reactors and a mid-point substation is standard.
AnswerTwo end reactors: \(V_R = 416.0\) kV, interior peak 419.6 kV at 119 km. Split three ways: peak 417.5 kV at 80 km, same total MVAr
Problem 20ChallengeA Complete Design

Bring the whole set together. The 400 km, 400 kV line must deliver 300 MW at 400 kV with a regulation not exceeding 10% and a no-load rise not exceeding 3%, using compensation only. Work through the options in order and specify the installation.

Solution

The starting point. Uncompensated, at 300 MW and 0.95 lagging, from Problems 1 and 2:

\[ V_S = 460.6\ \text{kV} \qquad \%\text{reg} = 27.08\% \qquad \text{Ferranti} = 10.37\% \qquad \eta = 89.46\% \]

Both targets are missed by a wide margin.

Step 1 — shunt reactors alone, 60%. From Problem 6, \(|A|\) rises to 0.9619:

\[ \text{Ferranti} = \frac{1}{0.9619}-1 = 3.96\% \qquad \%\text{reg} = 25.55\% \qquad \text{SIL} = 267\ \text{MW} \]

The no-load target is nearly met; the regulation target is untouched, and SIL has been cut by 37%.

Step 2 — series capacitors alone, 50%. From Problem 9:

\[ |B| = 100.82\angle52.08^\circ\ \Omega \qquad \%\text{reg} = 18.29\% \qquad \text{SIL} = 548\ \text{MW} \qquad \text{Ferranti} = 4.94\% \]

A large improvement in regulation, and SIL raised by 30% — but 18.29% is still not 10%.

Step 3 — both together. With \(k_{\text{sh}} = 0.60\) and \(k_{\text{se}} = 0.50\) the effective parameters become \(z' = 0.16 + j0.20\) and \(y' = j1.20\times10^{-6}\):

\[ \begin{array}{lcccc} & |A| & |B|\ (\Omega) & \text{SIL (MW)} & \text{Ferranti} \\ \hline \text{None} & 0.9060 & 166.87 & 422 & 10.37\% \\ 60\%\ \text{shunt} & 0.9619 & 170.13 & 267 & 3.96\% \\ 50\%\ \text{series} & 0.9529 & 100.82 & 548 & 4.94\% \\ \text{Both} & 0.9809 & 101.80 & 346 & 1.94\% \end{array} \]

The no-load target is now met with room to spare — 1.94% against 3% — and SIL has settled at 346 MW, between the two single remedies.

But the regulation is 17.78%. Recomputing at 300 MW, 0.95 lagging:

\[ V_S = 462.1\ \text{kV} \qquad \%\text{reg} = \frac{462.1/0.9809 - 400}{400} = 17.78\% \]

Barely better than series compensation alone. Adding shunt reactors to a series-compensated line does almost nothing for regulation, because \(|A|\) was already near unity and \(|B|\) is unchanged.

Step 4 — the missing variable. Nothing done to the line will fix this, because the drop is being caused by the load's own reactive demand travelling the length of it:

\[ Q_R = 300\tan(\cos^{-1}0.95) = 300\times0.3287 = 98.6\ \text{MVAr lagging} \]

Installing shunt capacitors at the receiving-end busbar to carry the load to 0.95 leading requires

\[ Q_C = 2\times98.6 = 197.2\ \text{MVAr} \]

and the improvement is decisive:

The three load power factors, on the compensated line:

\[ \begin{array}{lcccc} \text{Load pf} & Q_C\ \text{(MVAr)} & V_S\ \text{(kV)} & \%\text{reg} & \eta \\ \hline 0.95\ \text{lag} & 0 & 462.1 & 17.78 & 88.96\% \\ \text{unity} & 98.6 & 444.6 & 13.32 & 89.19\% \\ 0.95\ \text{lead} & 197.2 & 427.9 & 9.05 & 87.41\% \end{array} \]

Only the last meets the 10% target — and note the efficiency, which improves to unity power factor and then falls, because the leading current is as large as the lagging one was.

The specification. Three separate installations, each answering a different symptom:

\[ \begin{array}{lll} \text{Shunt reactors} & 115.2\ \text{MVAr} & \text{no-load rise: } 10.37\%\to3.96\% \\ \text{Series capacitors} & 80\ \Omega\ (2\times40\ \Omega) & \text{voltage drop: } |B|\ 167\to102\ \Omega \\ \text{Shunt capacitors} & 197.2\ \text{MVAr at the RE bus} & \text{load vars: reg } 17.78\%\to9.05\% \end{array} \]

What is not fixed. The efficiency, at 87.4%, is worse than the uncompensated line's 89.5%. No arrangement of reactors and capacitors changes \(r = 0.16\ \Omega\)/km, and the leading current needed for the regulation target actually raises \(I^2R\). Getting the efficiency up requires a second circuit, a bundled conductor, or 765 kV — a construction decision, not a compensation one.

And the reactors and capacitors must be switched. From Problem 15 the line's reactive requirement swings 300 MVAr between no load and full load and reverses sign near 340 MW. Leaving 197 MVAr of shunt capacitors connected at no load would add to a rise the reactors are there to suppress. The correct plant is switched in both directions, sequenced to the load.

Three faults, three remedies, and each remedy touches only its own fault. Shunt reactors act on \(y\) and fix the no-load rise; series capacitors act on \(x\) and fix the voltage drop; shunt capacitors act on the load and fix its power factor. The fourth quantity — efficiency — is governed by \(r\) and by \(r\) alone, and is the one thing on this list that compensation cannot buy. That is the whole of long-line design in one line, and it is why the answer to a poor efficiency is always a bigger conductor or a higher voltage.
Answer115.2 MVAr reactors + 80 Ω series capacitors + 197.2 MVAr shunt capacitors: reg 9.05%, Ferranti 1.94%, \(V_S = 427.9\) kV — efficiency unimproved at 87.4%
Practice

Practice Problems

Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not.

  1. P1. A line is shunt-compensated to 60%. By what factor does \(\gamma\) change, and by what factor does \(Z_c\) change?

    Show answer
    \(\gamma \times \sqrt{1-0.6} = \times\mathbf{0.632}\); \(Z_c \div 0.632 = \times\mathbf{1.581}\).
  2. P2. For that same line, what happens to the surge impedance loading?

    Show answer
    \(\text{SIL} = V_L^2/|Z_c|\), so it falls by the same 1.581 factor — to 63.2% of its uncompensated value.
  3. P3. A 400 kV line has a total shunt susceptance of \(1.2\times10^{-3}\) S. What is its charging MVAr, and its charging current?

    Show answer
    \(Q = V_L^2B = (400\times10^3)^2(1.2\times10^{-3}) = \mathbf{192}\) MVAr; \(I = 230.94\times10^3\times1.2\times10^{-3} = \mathbf{277}\) A.
  4. P4. Size the shunt reactors for 40% compensation of that line, split between the two ends.

    Show answer
    Total \(0.4\times192 = \mathbf{76.8}\) MVAr, so 38.4 MVAr at each end; \(X = 4167\ \Omega\) per phase per reactor.
  5. P5. A line has \(|A| = 0.94\). What is its no-load voltage rise?

    Show answer
    \(1/0.94 - 1 = \mathbf{6.38\%}\).
  6. P6. A 50% series-compensated line: what happens to \(|B|\) and to SIL?

    Show answer
    \(|B|\) falls roughly as the series reactance — here 167 Ω to about 101 Ω. \(Z_c \times \sqrt{0.5} = 0.707\), so SIL rises by \(1/0.707 = 1.414\).
  7. P7. Why does adding shunt reactors to a line make its efficiency slightly worse?

    Show answer
    The reactor current flows through part of the line, adding to \(I^2R\) without delivering any power. \(r\) is unchanged, so the numerator stays and the denominator grows.
  8. P8. A 220 kV line has \(Z_c = 400\ \Omega\). What is its SIL?

    Show answer
    \((220\times10^3)^2/400 = \mathbf{121}\) MW.
  9. P9. A load of 250 MW at 0.9 lagging is to be brought to unity power factor. How many MVAr of capacitors?

    Show answer
    \(Q = 250\tan(25.84^\circ) = \mathbf{121.1}\) MVAr.
  10. P10. An 800 km line is to be tuned at 50 Hz. What \(\beta\) is needed?

    Show answer
    \(\beta = \pi/800 = \mathbf{3.927\times10^{-3}}\) rad/km — about 3.5 times a normal overhead line's.
  11. P11. For a lossless line with \(x = 0.40\) Ω/km and \(b = 3.0\) µS/km, find \(Z_c\).

    Show answer
    \(Z_c = \sqrt{0.40/(3.0\times10^{-6})} = \mathbf{365.1}\ \Omega\), purely real — against \(378.95\angle-10.90^\circ\) with the resistance in.
  12. P12. Two compensation schemes give the same Ferranti rise. Which gives the better regulation under load, and why?

    Show answer
    Series compensation. Both fix \(|A|\), but only series compensation reduces \(|B|\) — and the load-dependent part of the regulation is the \(B\mathbf{I}_R\) term.
Challenge

Challenge Problems

Three problems that take longer than they look. Each combines the set's results rather than applying one of them, and each contradicts something the textbook formula seems to promise.

  1. C1 — The compensation that stops helping. The 400 km line of this set is series-compensated to a degree \(k\), with both terminal voltages held at 400 kV. Using the exact power-transfer relation, tabulate the maximum receiving-end power against \(k\) from 0 to 0.8 and locate the maximum. Explain why the lossless formula \(P = V_SV_R\sin\delta/X\) predicts something different.

    Show answer

    The exact relation is \(P_R = \dfrac{|V_S||V_R|}{|B|}\cos(\beta_B-\delta) - \dfrac{|A||V_R|^2}{|B|}\cos(\beta_B-\beta_A)\), maximised over \(\delta\) at \(\delta = \beta_B\). Per three phases, with \(|V_S| = |V_R| = 230.94\) kV:

    \[ \begin{array}{lccccccccc} k & 0 & 0.1 & 0.2 & 0.3 & 0.4 & 0.5 & 0.6 & 0.7 & 0.8 \\ \hline |B|\ (\Omega) & 166.9 & 153.1 & 139.5 & 126.1 & 113.2 & 100.8 & 89.4 & 79.2 & 71.1 \\ \beta_B\ (^\circ) & 68.9 & 66.8 & 64.2 & 61.0 & 57.0 & 52.1 & 45.7 & 37.6 & 27.3 \\ P_{\max}\ (\text{MW}) & 614 & 632 & 647 & \mathbf{653} & 644 & 611 & 540 & 419 & 250 \end{array} \]

    The maximum is 653 MW at \(k = 0.30\), and beyond it compensation makes the line weaker. At \(k = 0.8\) the limit is 250 MW — well below the uncompensated 614 MW.

    The reason is the second term, which the lossless formula does not have. As \(k\) rises, \(\beta_B\) falls towards zero (the series impedance becomes the pure resistance \(r\)) and \(|A|\) rises towards unity, so \(\cos(\beta_B-\beta_A) \to 1\) and the subtracted term grows to nearly cancel the first. The lossless formula misses this entirely because it sets \(\beta_B = 90^\circ\), at which \(\cos(\beta_B-\beta_A) \approx 0\) and the second term vanishes. On a line with \(r/x = 0.4\) that approximation is not available, and the real design range for series compensation on such a line is 20–40%, not the 70% the lossless algebra would encourage.

  2. C2 — The reactor that causes a collapse. Shunt reactors compensate a degree \(k\) of this line's charging. The sending end is held at 420 kV and the load is a constant 300 MW at 0.95 lagging. Solve for the receiving-end voltage as a function of \(k\), and find the value of \(k\) beyond which the load cannot be served at all.

    Show answer

    A constant-power load gives a quadratic in \(|V_R|\) with two roots — the upper one is the operating point and the lower one is unstable. Solving \(|A\mathbf{V}_R + B\mathbf{I}_R| = 242.49\) kV with \(\mathbf{I}_R = \mathbf{S}^*/3\mathbf{V}_R^*\):

    \[ \begin{array}{lcccccc} k & 0 & 0.2 & 0.4 & 0.6 & 0.8 & 0.884 \\ \hline V_R\ \text{upper (kV)} & 325.0 & 310.9 & 295.9 & 279.1 & 256.9 & 234.1 \\ V_R\ \text{lower (kV)} & 179.0 & 184.5 & 191.2 & 200.1 & 214.6 & 234.2 \\ \text{Ferranti} & 10.37\% & 8.17\% & 6.03\% & 3.96\% & 1.95\% & 1.10\% \end{array} \]

    Every 20% of compensation costs about 15 kV of loaded receiving voltage, and at \(k = 0.884\) the two roots merge at 234 kV — the nose of the P–V curve. Beyond that no solution exists: the line cannot deliver 300 MW at any voltage.

    The mechanism is direct. The line's own shunt capacitance generates \(V^2B\) of vars that support the voltage under load; removing 88% of it with reactors removes that support, and the reactors then absorb vars of their own on top. Fixed reactors sized for the no-load condition are a liability at full load — which is the whole case for switching them, and the reason a reactor bank is normally the first thing an operator removes as load builds.

  3. C3 — Where should the series capacitor go? A single 80 Ω series capacitor is to be installed on the 400 km line. Compare placing it at the sending end, at the receiving end, at the mid-point, and as two 40 Ω banks at the one-third points, using cascaded ABCD matrices. Report \(|A|\), \(|B|\), the Ferranti rise and the regulation at 300 MW, 0.95 lagging.

    Show answer

    The overall matrix is the product taken in the order the power flows, sending end first:

    \[ \begin{array}{lcccc} \text{Placement} & |A| & |B|\ (\Omega) & \text{Ferranti} & \%\text{reg} \\ \hline \text{None} & 0.9060 & 166.87 & 10.37\% & 27.08\% \\ \text{Sending end} & 0.9990 & 104.40 & 0.10\% & 17.91\% \\ \text{Receiving end} & 0.9060 & 104.40 & 10.37\% & 19.83\% \\ \text{Mid-point} & 0.9525 & 100.49 & 4.99\% & 18.20\% \\ \text{Two at one-third} & 0.9528 & 100.44 & 4.96\% & 18.21\% \end{array} \]

    \(|B|\) barely notices where the capacitor sits — 100 to 104 Ω across all four — but \(|A|\) varies from 0.906 to 0.999. At the receiving end the capacitor carries no current on no load, so it cannot affect \(|A|\) at all and the Ferranti rise is exactly what it was. At the sending end the entire charging current of the line passes through it, and the resulting voltage very nearly cancels the rise — Ferranti falls to 0.10%.

    The practical answer is nonetheless the two 40 Ω banks. The sending-end placement's \(|A| = 0.999\) is a coincidence of this length and this \(X_C\) and would not survive a change of either; the split banks halve each unit's rating (18.2 kV per phase across each at 456 A instead of 36.5 kV), distribute the profile correction, split the subsynchronous-resonance exposure between two sites, and leave half the compensation in service when one bank is bypassed. The terminal arithmetic does not choose between these; the ratings, the protection and the outage cases do.

Self-Test

Multiple-Choice Questions

  1. MCQ 1. The no-load voltage rise of a line is governed by:
    (a) \(A\)   (b) \(B\)   (c) \(C\)   (d) \(D\) only

    Show answer
    (a). At \(\mathbf{I}_R = 0\), \(V_R = V_S/|A|\) — nothing else appears. Problem 1.
  2. MCQ 2. Shunt reactors compensating a fraction \(k\) of the line's susceptance change the propagation constant by a factor:
    (a) \(1-k\)   (b) \(\sqrt{1-k}\)   (c) \(1/\sqrt{1-k}\)   (d) \((1-k)^2\)

    Show answer
    (b). \(\gamma = \sqrt{zy}\) and only \(y\) changes, so the square root applies. Problem 5.
  3. MCQ 3. Shunt reactors change the surge impedance loading:
    (a) not at all   (b) they raise it   (c) they lower it   (d) it depends on the load

    Show answer
    (c). \(Z_c = \sqrt{z/y}\) rises by \(1/\sqrt{1-k}\) and \(\text{SIL} = V_L^2/|Z_c|\) falls in the same ratio. Problem 8.
  4. MCQ 4. Series capacitor compensation acts principally on:
    (a) \(A\)   (b) \(B\)   (c) \(C\)   (d) the load power factor

    Show answer
    (b). Reducing \(x\) reduces \(|B|\) directly — 167 Ω to 101 Ω at 50%. Problem 9.
  5. MCQ 5. Which remedy improves transmission efficiency?
    (a) shunt reactors   (b) series capacitors   (c) both   (d) neither

    Show answer
    (d). Losses are \(3I^2r\) and neither remedy touches \(r\). Only a larger conductor, a higher voltage or a better load power factor will do it. Problem 13.
  6. MCQ 6. A line's charging MVAr is given by:
    (a) \(V_L^2/B\)   (b) \(V_L^2B\)   (c) \(3V_L^2B\)   (d) \(V_L^2B/3\)

    Show answer
    (b). With \(V_L\) the line voltage and \(B\) the total per-phase susceptance, the three-phase result is \(V_L^2B\) — the factors of 3 cancel. Problem 7.
  7. MCQ 7. For a lossless line one half-wavelength long:
    (a) \(A = 1, B = 0\)   (b) \(A = -1, B = 0\)   (c) \(A = 0, B = Z_c\)   (d) \(A = -1, B = Z_c\)

    Show answer
    (b). \(\cos\pi = -1\) and \(\sin\pi = 0\), so the regulation is zero at every load. Problem 17.
  8. MCQ 8. Terminating a line in \(Z_c\) makes the sending-end voltage angle equal to:
    (a) zero   (b) \(\alpha l\)   (c) \(\beta l\)   (d) \(|\gamma| l\)

    Show answer
    (c). The matched line carries one travelling wave, retarded by \(\beta x\) and attenuated by \(e^{-\alpha x}\). Both were confirmed to eight figures in Problem 16.
  9. MCQ 9. Two shunt reactors at the ends of a long line leave a voltage maximum:
    (a) at the sending end   (b) at the receiving end   (c) inside the line   (d) nowhere — the profile is flat

    Show answer
    (c). 419.6 kV at 119 km, above both terminals. Lumped reactors cannot absorb the charging generated between them. Problem 19.
  10. MCQ 10. The regulation of a compensated line at 300 MW is best improved by:
    (a) more shunt reactors   (b) more series capacitors   (c) shunt capacitors at the load   (d) a higher sending voltage

    Show answer
    (c). Correcting the load to 0.95 leading took the regulation from 17.78% to 9.05%; more line compensation was worth a fraction of that. Problem 20.
  11. MCQ 11. The reactive requirement of a long line between no load and full load:
    (a) is constant   (b) rises steadily   (c) falls steadily   (d) reverses sign

    Show answer
    (d). From \(-168\) MVAr at no load to \(+141\) at 500 MW, crossing zero near 340 MW — the argument for switched plant. Problem 15.
  12. MCQ 12. A line series-compensated well beyond 40% on a route with \(r/x = 0.4\):
    (a) carries more power   (b) carries less power   (c) is unchanged   (d) becomes lossless

    Show answer
    (b). The steady-state limit peaks at 653 MW near \(k = 0.30\) and falls to 250 MW at \(k = 0.80\). The lossless formula hides this. Challenge C1.
Reference

Key Formulas

QuantityRelationNotes
Regulation\(\%\text{reg} = \dfrac{V_S/|A| - V_R}{V_R}\times100\)Both \(A\) and \(B\) enter, through \(V_S\)
Ferranti rise\(\dfrac{1}{|A|} - 1\)Load-independent
Efficiency\(\eta = P_R/P_S\)Governed by \(r\) alone
Shunt compensation\(y_{\text{eff}} = jb(1-k)\)\(\gamma\times\sqrt{1-k}\), \(Z_c\div\sqrt{1-k}\)
Series compensation\(z_{\text{eff}} = r + jx(1-k)\)\(|B|\) and \(|Z_c|\) both fall
Charging MVAr\(Q = V_L^{2}B_{\text{line}}\)192 MVAr for this line
Reactor rating\(Q_L = kV_L^{2}B_{\text{line}}\)Split between ends, sometimes mid-point
Surge impedance loading\(\text{SIL} = V_L^{2}/|Z_c|\)Shunt cuts it, series raises it
Matched line\(|V_S/V_R| = e^{\alpha l}\), \(\angle V_S = \beta l\)Same power factor everywhere
Lossless \(Z_c\)\(Z_c = \sqrt{x/b}\)Purely real — the surge impedance
Tuned line\(\beta l = \pi \Rightarrow A = -1,\ B = 0\)Lossless only; \(\lambda/2 = 2814\) km here
Max power\(P_{\max} = \dfrac{|V_S||V_R|}{|B|} - \dfrac{|A||V_R|^{2}}{|B|}\cos(\beta_B-\beta_A)\)Second term matters when \(r/x\) is large
Power-factor correction\(Q_C = P(\tan\phi_1 - \tan\phi_2)\)Acts on the load, not the line
SSR frequency\(f_{er} = f\sqrt{k_{\text{se}}}\)Complement \(f - f_{er}\) meets shaft modes
Diagnostics

Common Mistakes

  1. Expecting compensation to improve efficiency. Neither reactors nor capacitors change \(r\), and both add current that does not deliver power — Problems 8 and 13.

  2. Forgetting that shunt reactors cut the SIL. A line compensated to 60% carries 267 MW naturally instead of 422 MW. The remedy for the no-load problem shrinks the loaded capability — Problem 8.

  3. Sizing reactors from \(3V_L^2B\). The three-phase charging is \(V_L^2B\) with \(V_L\) the line voltage; the factors of three cancel. A threefold error here sizes the plant absurdly — Problem 7.

  4. Assuming end reactors control the whole profile. They control the terminals; the interior can sit above both of them — Problem 19.

  5. Treating "loading at SIL" and "terminating in \(Z_c\)" as the same instruction. The first is a real power at unity power factor and gives a 15.4% rise; only the second gives the exponential profile — Problem 16.

  6. Expecting a flat profile at SIL on a real line. Flatness belongs to the lossless case. Here the rise is exactly \(e^{\alpha l} = 1.0898\) — Problem 16.

  7. Using \(P = V_SV_R\sin\delta/X\) to justify heavy series compensation. The lossless formula omits the term that reverses the trend above \(k \approx 0.3\) on a resistive line — Challenge C1.

  8. Leaving fixed reactors in service under load. They remove the voltage support the line's own capacitance provides, and past \(k = 0.884\) here the load cannot be served at all — Challenge C2.

  9. Attacking the regulation only through the line. The largest single improvement came from capacitors at the load busbar, which the ABCD constants never see — Problem 20.

  10. Believing the tuned line is a practical target. Synthesising it on 400 km needs 1184 MVAr and 987 Ω, and produces an interior voltage swing of 111 kV — Problem 18.

  11. Ignoring where a series capacitor is placed. \(|B|\) hardly notices, but \(|A|\) runs from 0.906 to 0.999 — and with it the Ferranti rise — Challenge C3.

  12. Quoting a single compensation setting for a line. The reactive requirement swings 300 MVAr and reverses sign across the load range; the correct answer is a schedule, not a number — Problem 15.

Looking Ahead

The line has now been treated as something to be designed rather than analysed. Three faults were separated — the no-load rise, the loaded voltage drop and the load's own reactive demand — and each was matched to the remedy that acts on it: reactors on \(y\), capacitors on \(x\), and capacitors at the busbar on the load itself. The fourth quantity, efficiency, resisted all three, because it is set by \(r\) and by nothing else.

Set 15 closes Part 3 by putting the same relations into complex-power form — the receiving-end circle diagram, the \(P\)\(Q\) locus and the way the ABCD constants determine both — and returns to line inductance where the series calculation of Set 5 meets the power-transfer limit found here. From Set 16 the line stops being a subject in its own right and becomes one entry in an admittance matrix.