Set 15 — Complex Power and Line Inductance
Twenty worked problems closing Part 3. Everything so far has been written in volts and amperes; the operator's question is asked in megawatts, and answering it turns the two-port equations into a pair of power relations whose locus is a circle. Out of that circle come the steady-state stability limit, the reactive support a given transfer demands, and the reason a line's capability is quoted as a multiple of its surge impedance loading. The set then goes back to the conductor geometry of Set 5 and asks what actually sets that limit.
Complex power. \(\mathbf{S} = 3\mathbf{V}\mathbf{I}^{*} = P + jQ\) per three phases with \(\mathbf{V}\) a phase voltage, or \(\sqrt{3}V_LI_L\) in magnitude. \(Q > 0\) means lagging — the element absorbs vars.
Receiving-end power from ABCD. \(P_R = \dfrac{|V_S||V_R|}{|B|}\cos(\beta_B-\delta) - \dfrac{|A||V_R|^{2}}{|B|}\cos(\beta_B-\beta_A)\), with \(Q_R\) the same expression in sines and \(\delta\) the angle by which \(\mathbf{V}_S\) leads \(\mathbf{V}_R\).
The circle diagram. As \(\delta\) varies, \((P_R, Q_R)\) traces a circle of radius \(|V_S||V_R|/|B|\) centred at \(-\dfrac{|A||V_R|^{2}}{|B|}\angle(\beta_B-\beta_A)\). Only \(\delta\) moves the operating point along it.
The maximum. \(P_{R,\max}\) occurs at \(\delta = \beta_B\) and equals \(\dfrac{|V_S||V_R|}{|B|} - \dfrac{|A||V_R|^{2}}{|B|}\cos(\beta_B-\beta_A)\) — the steady-state stability limit, and never reached in operation.
The lossless shortcut is optimistic. \(P = V_SV_R\sin\delta/X\) drops the second term entirely, and on a line with \(r/x = 0.4\) it overstates the limit by about 70%.
Inductance from geometry. \(L = 0.2\ln\dfrac{\text{GMD}}{\text{GMR}}\) mH/km. The logarithm makes spacing a weak lever and bundling a strong one, because bundling multiplies the GMR rather than adding to it.
Loadability falls as \(1/l\). Expressed in multiples of SIL, a 100 km line will carry several times its natural loading and a 600 km line barely one — which is why capability is quoted per SIL and not in megawatts.
A three-phase load draws 150 A per phase at 220 kV, the current lagging the phase voltage by 25°. Find the complex power, and state clearly what the sign of each part means. Then repeat with the current leading by 25° and identify what has changed physically.
The definition. With \(\mathbf{V}\) a phase voltage and \(\mathbf{I}\) the line current out of the element:
The conjugate is essential. Without it the angle would be \(\theta_V + \theta_I\), which depends on where the reference was put; with it the angle is \(\theta_V - \theta_I = \phi\), which does not.
Lagging case. Take \(\mathbf{V} = 127.02\angle0^\circ\) kV and \(\mathbf{I} = 150\angle-25^\circ\) A:
Check by the line-quantity form:
The \(\sqrt{3}\) and the 3 are the same statement written with different voltages.
Leading case. With \(\mathbf{I} = 150\angle+25^\circ\):
\(P\) is unchanged; \(Q\) has reversed sign.
What the signs mean. With this convention — current out of the element into the network:
Textbooks differ. The safest habit is to state the current's direction with every result, because the algebra is identical and only the sign convention distinguishes a generator from a load.
The physical change. Both cases move 51.80 MW and both draw 150 A — so both cause identical \(I^2R\) losses in the line feeding them. What differs is where the 24 MVAr comes from: in the lagging case the network supplies it; in the leading case the load supplies it back. That is the whole subject of the previous set expressed in one sign.
The 220 kV, 200 km line of Set 11 has \(A = 0.9760\angle0.564^\circ\) and \(B = 86.16\angle68.20^\circ\ \Omega\). Derive the receiving-end power relations in terms of the ABCD constants and the transmission angle, and evaluate them at \(\delta = 20^\circ\) with both terminal voltages at 220 kV. This line recurs throughout the set.
The derivation. Take \(\mathbf{V}_R\) as reference and let \(\mathbf{V}_S\) lead it by \(\delta\). From \(\mathbf{V}_S = A\mathbf{V}_R + B\mathbf{I}_R\):
Then \(\mathbf{S}_R = 3\mathbf{V}_R\mathbf{I}_R^{*}\) with \(\mathbf{V}_R = |V_R|\angle0\):
Two phasors: one of fixed length that rotates with \(\delta\), and one that is entirely fixed. That structure is the circle diagram of Problem 7, already visible.
Separating real and imaginary parts:
The two coefficients. With \(|V_S| = |V_R| = 220/\sqrt3 = 127.02\) kV:
Both have the dimensions of power. Note that the whole calculation can be done in line quantities as \(V_L^2/|B|\), which gives the same 561.73 MW — the threes cancel again.
The fixed term. \(\beta_B - \beta_A = 68.20 - 0.564 = 67.63^\circ\):
At \(\delta = 20^\circ\):
Reading \(Q_R\). The negative sign says the receiving end must supply 88.3 MVAr into the line to hold its voltage at 220 kV while taking 165.8 MW. A load absorbing vars will not do that; a capacitor bank or a synchronous condenser at the receiving busbar must. Every point on the circle of Problem 7 carries this same requirement.
Derive the corresponding sending-end relations for the same line, evaluate them at \(\delta = 20^\circ\), and confirm that the difference between the two ends is a sensible loss.
The derivation. Invert the two-port to get \(\mathbf{I}_S\) in terms of \(\mathbf{V}_S\) and \(\mathbf{V}_R\). Using \(D = A\) for a symmetrical line:
Then \(\mathbf{S}_S = 3\mathbf{V}_S\mathbf{I}_S^{*}\), with \(\mathbf{V}_S = |V_S|\angle\delta\):
The differences from the receiving-end pair are worth naming, because they are the usual source of error:
Everything is reversed. That is not an accident: it is the same equation viewed from the other terminal, and \(\delta\) changes sign with the viewpoint.
At \(\delta = 20^\circ\), with \(|V_S| = |V_R|\) the two coefficients are the same 548.27 and 561.73 MW as before:
The check. The real difference is the line loss:
Verify it independently from the current. \(\mathbf{I}_R = (\mathbf{V}_S - A\mathbf{V}_R)/B\) gives \(|I_R| = 493\) A and \(|I_S| = 521\) A; taking the mean square across the line:
Within 2% of 25.2. The approximation is not exact because the nominal-\(\pi\) puts the whole resistance in one branch that carries neither terminal current, but it confirms that 25 MW is a loss and not an algebraic slip.
The reactive difference is not a loss. \(Q_S - Q_R = -54.4 - (-88.3) = +33.9\) MVAr. The line has generated 33.9 MVAr net — its charging exceeds its \(I^2X\) absorption at this loading, so the line is running below its surge impedance loading. Above SIL the sign reverses.
Tabulate \(P_R\) and \(Q_R\) for the same line at transmission angles from 0 to 68°, both voltages held at 220 kV. Describe the shape of the \(P\)–\(\delta\) curve and say why it is not a sine.
Using \(P_R = 561.73\cos(68.20^\circ - \delta) - 208.62\) and \(Q_R = 561.73\sin(68.20^\circ - \delta) - 507.03\):
The \(\delta = 0\) row is the check. With equal voltage magnitudes and no angle there is no real transfer, and the \(+14.5\) MVAr is the line's own charging arriving at the receiving end — the Ferranti current, seen in power terms.
The shape. Written as a single cosine, \(P_R(\delta) = 561.73\cos(\beta_B - \delta) - 208.62\) is a shifted and displaced cosine:
Both departures from \(P \propto \sin\delta\) come from the same place — the resistance, which drags \(\beta_B\) down from 90° and makes \(\cos(\beta_B-\beta_A)\) non-zero.
The curve is not symmetric about its peak either. Between 0 and 20° it gains 165.8 MW; between 48 and 68° it gains only 33 MW. Power becomes progressively more expensive in angle, which is the mechanical statement of approaching the stability limit.
The reactive column is the real warning. By \(\delta = 30^\circ\) the load bus needs 160 MVAr of support to hold 220 kV; by 50° it needs 332 MVAr — more than the 325 MW being delivered. Long before the angle limit is approached, the reactive requirement has become impossible.
Find the maximum receiving-end power of the line and the angle at which it occurs. Compare it with the value the lossless formula \(P = V_SV_R\sin\delta/X\) would give, and account for the difference.
The maximum. Only the first term depends on \(\delta\), and it is largest when its cosine is unity:
Substituting:
The lossless estimate. With \(X = 80\ \Omega\) and both voltages at 220 kV, \(P = V_L^2\sin\delta/X\) peaks at \(\delta = 90^\circ\):
An overstatement of 71%.
Where the discrepancy sits. Two separate effects, of comparable size:
The first step costs 43 MW; the second costs 209 MW. The dominant error in the lossless formula is not that it ignores \(r\) in the magnitude, but that it throws away a whole term.
Why the fixed term vanishes when \(r = 0\). With no resistance, \(B = jX\) gives \(\beta_B = 90^\circ\), and for a nominal-\(\pi\) line \(A = 1 + ZY/2\) is very nearly real, so \(\beta_A \approx 0\):
The 208.6 MW here is \(548.27\cos67.63^\circ\), and 67.63° is only 22° from 90° — yet that 22° is worth 209 MW.
The limit is never approached in operation. A line run at \(\delta = 68^\circ\) has no margin: a small increase in demand cannot be met by a larger angle, and the system loses synchronism. Practice keeps \(\delta\) below about 30° in normal operation and below 45° after a credible contingency, which caps this line at roughly 230 MW — two-thirds of the theoretical limit.
Find the reactive power required at the receiving end when the line is delivering its maximum 353.1 MW, and the current that flows. Compare both with the values at a normal 200 MW transfer, and say what actually limits the line.
At the limit, \(\delta = \beta_B\), so the sine term vanishes entirely:
The receiving busbar must inject 507 MVAr into the line — 1.44 times the real power it is receiving.
The apparent power and current:
At 200 MW, from the circle relation with \(\delta = 24.87^\circ\):
The comparison:
A 77% increase in delivered power costs a 164% increase in current and a fourfold increase in reactive support.
What binds first. A single ACSR conductor of the class used at 220 kV carries about 600 A continuously:
The conductor melts, the compensator does not exist, and the operator's rule is exceeded — all three long before the mathematical maximum.
Where the vars go. The series branch carries 1653 A at this point, so it absorbs \(3I^{2}X = 3(1653)^{2}(80) = 655.7\) MVAr, against \(V_L^{2}B = 29.0\) MVAr generated by the charging. The net 626.7 MVAr is supplied 507.0 from the receiving end and 119.6 from the sending end — the balance closes exactly. The reactive demand grows as the square of the current, which is why it overtakes the real transfer so abruptly.
Construct the receiving-end circle diagram for the line: find its centre and radius, and verify three points on it from the power relations directly.
The construction. Return to the phasor form of Problem 2:
A fixed phasor plus one of constant length and variable angle. The locus of the sum is a circle — immediately, without any algebra.
The radius is the length of the rotating phasor:
Proportional to the product of the two voltages and inversely to \(|B|\). Raise either voltage and the circle grows.
The centre is the negative of the fixed phasor:
Down and to the left of the origin — which is why the useful part of the circle lies in the fourth quadrant, where \(P > 0\) and \(Q < 0\).
Three verifications. A point at angle \(\theta = \beta_B - \delta\) measured from the positive \(P\) axis:
The three rows are the no-load point, the working point of Problem 2 and the tangent point of Problem 5 — all on one circle.
Reading the geometry. Four features carry the whole of the line's steady-state behaviour:
Where the circle crosses \(Q = 0\) is the transfer this line will carry unaided:
Only 33 MW — under a tenth of the stability limit. Beyond that every megawatt requires reactive support at the load bus.
The line supplies a load of 150 MW at 0.9 lagging with the receiving voltage held at 220 kV. Use the circle diagram to find the transmission angle and the reactive compensation required at the load bus. Repeat for 250 MW and comment on the trend.
Step 1 — locate the operating point on the circle. The circle fixes \(Q\) once \(P\) is chosen:
Step 2 — the reactive power the line will deliver at that point:
Negative: the line takes 74.7 MVAr out of the receiving busbar rather than delivering any.
Step 3 — what the load wants:
Step 4 — the compensator makes up the difference. The busbar must balance:
On the diagram this is the vertical distance from the load point \((150, +72.6)\) down to the circle at \((150, -74.7)\) — which is the whole reason the drawing was made.
At 250 MW, repeating:
The trend across the range:
\(Q_C\) outgrows \(P\) from 100 MW onwards, and by 300 MW it exceeds it.
Two separate causes, and they compound. The load's own demand grows linearly with \(P\) at fixed power factor; the line's absorption grows as \(P^2\) through \(3I^{2}X\). Doubling the transfer from 150 to 300 MW doubles the first from 73 to 145 MVAr and more than triples the second from 75 to 269.
Construct the sending-end circle diagram for the same line and state its relation to the receiving-end one. What does the sending-end operating point tell the generator?
From the relations of Problem 3, written as a phasor sum:
The same radius, the opposite centre. With \(|V_S| = |V_R|\) here:
The sending circle is the receiving circle reflected through the origin — but only when the two voltage magnitudes are equal. In general \(\mathbf{C}_S \propto |V_S|^2\) and \(\mathbf{C}_R \propto |V_R|^2\), and the symmetry is lost.
The direction of travel is also reversed. The receiving-end point sits at angle \(\beta_B - \delta\) and the sending-end point at \(\beta_B + \delta\) measured the other way from the centre — so as the load grows the two points move in opposite senses around their circles.
Operating points at three angles:
All powers in MW and MVAr.
What the generator reads. \(Q_S\) is negative throughout this range, meaning the sending end is absorbing vars from the line — the line is generating more charging than it consumes, below SIL. The machine must run under-excited, which is the condition its capability curve most restricts.
And \(Q_S\) is not monotonic: \(-42.8\), \(-54.4\), \(-49.0\) — it deepens and then recovers. Setting \(\partial Q_S/\partial\delta = 0\) gives \(\beta_B + \delta = 90^\circ\), so the minimum is at \(\delta = 21.80^\circ\):
Beyond that angle the line's own \(I^2X\) absorption begins to overtake its charging, and the generator's under-excitation eases.
Show that when the two terminal voltages are equal the transmission loss of a nominal-\(\pi\) line reduces to a single closed form in \(\delta\), and verify it against the tabulated values.
Subtract the two power relations. Write \(K = 3|V|^{2}/|B|\) and \(K_A = |A|K\) with \(|V_S| = |V_R| = |V|\):
The bracket collapses by the sum-to-product identity:
The two coefficients are equal. This is the step that makes the result clean. Since \(K_A = |A|K\), the claim is \(|A|\cos(\beta_B-\beta_A) = \cos\beta_B\), or equivalently
For the nominal-\(\pi\), \(A = 1 + \mathbf{Z}\mathbf{Y}/2\) and \(\mathbf{B} = \mathbf{Z}\), so \(A^{*} - 1 = \mathbf{Z}^{*}\mathbf{Y}^{*}/2\) and
because \(\mathbf{Y}\) is purely susceptive — the line's leakage conductance is negligible. The identity is exact, not approximate.
The result:
Verification against the values computed the long way:
Exact to every figure carried.
What it says. Expanding for small angles, \(1 - \cos\delta \approx \delta^{2}/2\):
And since \(P_R \approx K\sin\beta_B\,\delta\) for small \(\delta\), the loss grows as the square of the transfer — the \(I^2R\) law, recovered from the circle diagram without ever writing a current.
And the geometric reading: at a common \(\delta\), the sending point sits at angle \(\beta_B+\delta\) from its centre and the receiving point at \(\beta_B-\delta\) from its own — reflections of each other about the \(\delta = 0\) position. Their horizontal separation is the loss, and it opens as \(1-\cos\delta\): zero at \(\delta = 0\) and widening ever faster.
Reduce the receiving-end power relations to the short-line model, and then to the lossless one. Evaluate all three against the exact figures at \(\delta = 10^\circ\), 20° and 30°, and say which simplification actually costs anything.
The short-line reduction. Set \(A = 1\), \(\beta_A = 0\) and \(B = \mathbf{Z}\):
Written in line quantities, which is how it is usually quoted.
The lossless reduction. Set \(r = 0\) as well, so \(\beta_Z = 90^\circ\) and \(|Z| = X\):
The familiar form — and now visibly a double approximation, not one.
The comparison. With \(\mathbf{Z} = 32 + j80 = 86.16\angle68.20^\circ\) and \(X = 80\ \Omega\):
The short-line column is identical to the exact one — to every figure. That is not luck. The nominal-\(\pi\) and the short-line model share \(B = \mathbf{Z}\) exactly, and the identity proved in Problem 10 makes \(|A|\cos(\beta_B-\beta_A) = \cos\beta_B\), so the fixed term is \(V_L^2\cos\beta_Z/|Z|\) in both cases. The shunt admittance drops out of the real power relation altogether when the terminal voltages are equal.
The reactive relation is a different matter. The same comparison for \(Q_R\):
A constant offset of 14.5 MVAr — exactly the charging \(V_L^{2}B/2\) at each end. The short-line model gets the megawatts right and the megavars wrong by a fixed amount.
So the two approximations are not comparable. Dropping the shunt admittance costs nothing in \(P\) and a constant in \(Q\); dropping the resistance costs 20–30% in \(P\) at working angles and 71% at the limit. The one universally taught is the one that does the damage.
The line's conductor is rated at 600 A continuous. Compare the thermal limit, the practical stability limit at \(\delta = 30^\circ\), and the theoretical maximum, and identify which binds. Then repeat the comparison for the same conductor on a 50 km line and a 500 km line.
The thermal limit depends only on the conductor, not on the length:
At 0.9 power factor that is 206 MW; at unity, 229 MW.
The three limits at 200 km:
Thermal and practical-stability limits are within 2% of each other. This line is well matched to its conductor — which is what a competent design looks like.
At other lengths, keeping the same conductor and both voltages at 220 kV. These use the exact hyperbolic constants rather than the nominal-\(\pi\), so the 200 km row runs about 1% above the figures used elsewhere in the set:
Powers in MW.
The crossover. At 50 km the conductor is the constraint and stability is irrelevant — the line could carry four times its thermal rating before angle became an issue. At 500 km the position is reversed: the stability limit of 99 MW is well under half the conductor's 229 MW, and the extra copper is wasted.
Why the boundary sits near 200 km. The thermal limit is independent of length; the stability limit falls roughly as \(1/l\). They cross at whatever length makes \(V_L^{2}/|B|\) comparable to \(\sqrt3V_LI_{\text{rated}}\) — for a 220 kV single-conductor line, about 200 km. Raising the voltage to 400 kV moves the crossover out to roughly 400 km, which is why the two voltage classes have the route lengths they do.
The 0.40 Ω/km used throughout Part 3 has been taken on trust. Recover it: the line is horizontally configured with 6 m between adjacent phases, transposed, and the conductor has a GMR of 11.4 mm. Find \(L\) and \(X\), and identify what the answer is sensitive to.
The geometric mean distance. For a transposed horizontal line with spacings \(D\), \(D\) and \(2D\):
The inductance from the standard result of Set 5:
The reactance:
The 0.40 Ω/km assumed since Set 9, recovered from the tower drawing.
What the answer is sensitive to. Differentiate the logarithm:
A 10% change in either geometric quantity changes \(L\) by only 1.5%. The logarithm suppresses everything.
Which is why every overhead line has almost the same reactance. Across the whole range of transmission practice:
The single-conductor lines are all near 0.4 Ω/km regardless of voltage. Only bundling moves the number appreciably — and it moves the GMR, not the GMD.
The corresponding capacitance uses the physical radius instead of the GMR:
With \(r \approx 14.3\) mm this gives 0.0089 µF/km and \(b = 2.8\) µS/km — close to the 3.0 used throughout. The two logarithms differ only in the denominator, which is why \(Z_c = \sqrt{x/b}\) is so nearly the same for all overhead lines.
Replace the single conductor by bundles of two, three and four sub-conductors at 0.45 m spacing, keeping the tower geometry. Find the reactance in each case and the resulting power limit, remembering that the resistance falls too.
The bundle GMRs from the standard expressions, with \(d = 0.45\) m and \(D_s = 0.0114\) m:
A four-bundle has seventeen times the GMR of one conductor — the geometric mean radius of an object 0.45 m across, not of a wire 23 mm across.
The reactances, with GMD unchanged at 7.560 m:
Diminishing returns, and sharply. The first sub-conductor added buys 28%; the second buys a further 10%; the third a further 6%. The logarithm again: doubling the GMR subtracts \(0.2\ln2 = 0.139\) mH/km whatever the starting point, and each added sub-conductor doubles it less than the last.
The resistance falls in proportion to \(n\) — \(n\) conductors in parallel — and this matters as much as the reactance:
For the 200 km line with both voltages at 220 kV.
The limit rises by 2.45 times while the reactance falls by only 44%. The extra gain comes from the falling \(r/x\), which pushes \(\beta_B\) towards 90° and shrinks the subtracted term of Problem 5 — exactly the mechanism that made heavy series compensation counterproductive in Set 14, running the other way.
But the thermal limit rises faster. \(n\) conductors carry \(n\) times the current:
The four-bundle has crossed over: its stability limit is now below its thermal rating, and further conductor buys nothing on a 200 km route.
Vary the phase spacing of the single-conductor line from 4 m to 12 m and find the effect on the reactance and the power limit. Compare the leverage with that of bundling, and explain why towers are not built narrower.
The calculation, with GMD \(= D\sqrt[3]{2}\) and GMR fixed at 11.4 mm:
Tripling the spacing costs 18% in reactance and 6% in power limit. Set that against the bundling result:
Bundling is the larger lever by an order of magnitude, and it acts in the useful direction.
Why the logarithm makes this so. The GMD enters as \(\ln(\text{GMD})\) and the ratio inside is already 663, so:
Matching the table. Any change of spacing is divided by about 6 before it reaches the inductance. Changing the GMR is divided by the same 6 — but bundling changes the GMR by a factor of 17, not 3.
Why towers are not built narrower. Nothing in this table is what sets the spacing. Four separate constraints do:
At 220 kV these fix the spacing at 5–7 m regardless of what the reactance would prefer, and at 400 kV at 9–12 m.
And a narrower tower has a second cost. Reducing the GMD reduces the capacitance denominator as well, so \(b\) rises with \(x\) falling — which lowers \(Z_c\) and raises SIL. A compact line therefore genuinely does carry more natural power, and compact-line designs exist for exactly this reason; but they buy it with insulation technology, not by simply moving the phases closer on a conventional tower.
The same route carries a double-circuit tower: two vertical circuits 9 m apart, phases at 0, 7 and 14 m, with the second circuit's phase order reversed. Find the equivalent reactance per phase, and the power limit with both circuits and with one out of service.
The self-GMDs. Each phase is now a group of two conductors, one on each circuit. With the reversed order, phase \(a\) sits at \((0, 14)\) and \((9, 0)\):
Reversing the second circuit is what puts \(a\) diagonally opposite \(a\). Keeping the same order would give three separations of 9 m and a higher reactance — this is the low-reactance arrangement.
The equivalent GMR of each phase group, then their geometric mean:
The mutual GMDs, each the fourth root of four separations:
The reactance per phase for the pair of circuits together:
49.2% of the single circuit's 0.4082 — slightly less than half, which two independent circuits in parallel would give. The reversed phasing turns the mutual coupling to advantage.
The capacitance rises correspondingly. Using the physical radius 14.3 mm in place of the GMR:
Against 122 MW for one circuit. The natural loading has slightly more than doubled.
The limits, at 200 km with \(r = 0.08\ \Omega\)/km for the two conductors in parallel:
And the contingency governs. A double-circuit line on one tower is exposed to common-mode failure — a tower collapse, a wide fire, a lightning flashover across both circuits. Planning practice requires the surviving circuit to carry the load:
The real capability of this double circuit is 229 MVA — the same as one circuit alone — unless load can be shed on the contingency.
Hold the sending voltage of the single-circuit 200 km line at 220 kV and let the receiving end take a constant-power load at 0.95 lagging with no compensation. Trace the receiving voltage against the load, find the maximum load that can be served, and compare it with the 353 MW of Problem 5.
The equation to solve. A constant-power load fixes \(\mathbf{S}_R\) and lets \(|V_R|\) float:
Multiplying through by \(|V_R|\) gives a quadratic in \(|V_R|^{2}\) — hence two roots for every load, not one.
The two branches. Solving at a series of loads:
The upper branch is the operating point; the lower is a mathematically valid solution at high current and low voltage that no protection would permit and no load would sustain.
The nose. The two roots merge at
Beyond it there is no solution. The load cannot be served at any voltage — the system does not settle at a lower voltage, it collapses.
Against the angle limit of 353 MW. The difference is entirely in what was assumed:
Problem 5's 353 MW required 507 MVAr at the load bus. Withdraw that assumption and the same line manages 166 MW — a factor of 2.1.
The power factor moves the nose sharply:
Correcting the load's power factor raises the collapse point by 54%. This is the same lever as Problem 20 of Set 14, seen from the stability side rather than the regulation side.
The knee is the operating constraint, not the nose. At 140 MW the voltage is already 167 kV — 76% of nominal, far below anything a network would tolerate. A 0.95 pu voltage criterion caps this line at 54 MW uncompensated, and it is compensation, not the nose, that makes the line usable at all.
Set out the difference between the angle limit of Problem 5 and the voltage limit of Problem 17: what each assumes, what each measures, and which arrives first in practice.
The assumptions are the whole difference. Both are steady-state maxima of the same two-port:
What each measures. The angle limit measures the ability of the machines to stay in step: beyond \(\delta = \beta_B\) an increase in mechanical power cannot be exported, the rotor accelerates and synchronism is lost. The voltage limit measures the ability of the network to supply reactive power: beyond the nose, no voltage exists at which the load's demand and the line's delivery agree.
The numbers for this line:
In descending order — and the two most restrictive are both reactive in origin.
Which arrives first depends on the var plan, and only on that. With a compensator at the load bus the voltage limit disappears and the thermal or angle limit binds; without one the voltage limit binds at less than half. The transfer capability of a corridor is therefore not a property of the line. It is a property of the line plus the reactive plant at its ends.
The historical pattern follows this. Angle instability dominated the mid-20th-century record because networks were sparse, machines slow and lines long relative to their loads. As systems grew denser and loads grew — especially induction-motor loads, which restore their power draw as voltage falls and so behave as the constant-power model assumes — the binding constraint moved to reactive support. Most large blackouts since 1980 have had a voltage-collapse mechanism rather than an angle one.
The two are coupled, not independent. Every megavar of support that raises the voltage limit also holds \(|V_R|\) up, which raises the angle limit through the \(|V_S||V_R|/|B|\) term. And a falling voltage raises the current for a given power, deepening the \(I^{2}X\) absorption — the feedback that makes the collapse fast.
Compute the steady-state limit of the single-circuit line at lengths from 50 to 800 km, express it as a multiple of the surge impedance loading, and explain why capability is quoted this way.
The reference. With \(z = 0.16 + j0.40\) and \(y = j3.0\ \mu\)S/km:
Independent of length — which is exactly what makes it a useful yardstick.
The limits, from the exact hyperbolic constants with both voltages at 220 kV:
Powers in MW.
The shape. The limit falls almost exactly as \(1/l\) over the middle of the range, because \(|B| \approx |Z|\) is nearly proportional to length. It falls faster beyond 500 km, where \(\sinh\gamma l\) begins to outgrow its argument.
Why express it per SIL. The SIL absorbs the voltage class:
The \(V_L^{2}\) cancels. Since every overhead line has \(Z_c \approx 380\ \Omega\) and \(\beta \approx 1.1\times10^{-3}\), the ratio depends on the length alone — so one curve serves every voltage class. That is the St Clair curve, drawn in 1953 and still used.
The three regimes it exposes:
Read against the practical column, a 400 km line carries about 1 SIL and a 600 km line about two-thirds — which is why long AC corridors are always compensated and very long ones are built as HVDC instead.
The 30° column is the honest one. Its ratios are 63% of the theoretical maxima throughout, because \(\cos(\beta_B - 30^\circ)\) is a nearly constant fraction of 1 over the range of \(\beta_B\) that overhead lines span. That constancy is why a single rule of thumb — about 1 SIL at 400 km — survives across the whole of transmission practice.
State the transfer capability of the 200 km double-circuit 220 kV corridor for a load at 0.95 lagging: apply every limit in this set, identify the binding one, and say what would have to change to raise it.
The corridor, from Problem 16: \(r = 0.08\), \(x = 0.2010\ \Omega\)/km, \(b = 5.66\ \mu\)S/km, \(Z_c = 195.5\ \Omega\), SIL 248 MW, \(|B| = 42.9\ \Omega\), \(|A| = 0.9774\), two 600 A conductors per phase.
Limit 1 — thermal. Independent of everything else:
Limit 2 — angle, normal state. At \(\delta \le 30^\circ\) with both voltages held at 220 kV:
320 MVAr of support at the receiving bus — which must be installed for this limit to mean anything.
Limit 3 — voltage stability, no support:
And applying a \(0.95\) pu voltage criterion instead of the nose itself brings this down to 106 MW.
Limit 4 — the N−1 contingency. With one circuit out, the surviving circuit has \(|B| = 87.0\ \Omega\):
The complete picture:
All in MW.
The answer: 217 MW with reactive support installed, 166 MW without. Both are set by the contingency, not by the normal state — and the corridor's headroom in normal operation (434 MW thermal) is twice its declared capability. That gap is not waste; it is the margin that makes the contingency survivable.
What would raise it, in order of cost:
Note that series compensation — the remedy of Set 14 — is nearly useless here. It attacks \(|B|\), and \(|B|\) is not what binds.
Practice Problems
Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not.
P1. A line has \(|B| = 86.16\ \Omega\) and both terminal voltages at 220 kV. What is the radius of its receiving-end circle?
Show answer
\(V_L^2/|B| = (220\times10^3)^2/86.16 = \mathbf{561.7}\) MW.P2. For the same line, \(|A| = 0.976\) and \(\beta_B - \beta_A = 67.63^\circ\). Where is the centre?
Show answer
\(-0.976\times561.7\angle67.63^\circ\), i.e. \(\mathbf{(-208.6,\ -507.0)}\) MW/MVAr.P3. At what transmission angle does that line reach its maximum receiving-end power?
Show answer
\(\delta = \beta_B = \mathbf{68.20^\circ}\) — not 90°.P4. What is that maximum?
Show answer
\(561.7 - 208.6 = \mathbf{353.1}\) MW — the rightmost point of the circle.P5. The same line has \(X = 80\ \Omega\). What does \(P = V_SV_R/X\) give, and by how much is it wrong?
Show answer
\((220\times10^3)^2/80 = \mathbf{605}\) MW — an overstatement of 71%.P6. A transposed horizontal line has 7 m between adjacent phases. Find the GMD.
Show answer
\(\sqrt[3]{7\times7\times14} = 7\sqrt[3]{2} = \mathbf{8.82}\) m.P7. Its conductor has GMR 12 mm. Find \(L\) and \(X\) at 50 Hz.
Show answer
\(L = 0.2\ln(8.82/0.012) = 0.2\ln735 = \mathbf{1.320}\) mH/km; \(X = \mathbf{0.4147}\ \Omega\)/km.P8. Replace it by a two-conductor bundle at 0.4 m. What are the new GMR and \(X\)?
Show answer
\(\sqrt{0.012\times0.4} = \mathbf{69.3}\) mm; \(X = 0.2\ln(8.82/0.0693)\times2\pi f = \mathbf{0.3045}\ \Omega\)/km — a 27% reduction.P9. A 400 kV line has \(Z_c = 300\ \Omega\). What is its SIL?
Show answer
\((400\times10^3)^2/300 = \mathbf{533}\) MW.P10. A 300 km line has a loadability of 1.90 SIL and an SIL of 127.7 MW. What is its steady-state limit?
Show answer
\(1.90\times127.7 = \mathbf{243}\) MW.P11. Use \(P_{\text{loss}} = 2K\cos\beta_B(1-\cos\delta)\) with \(K = 561.7\) MW and \(\beta_B = 68.20^\circ\) to find the loss at \(\delta = 25^\circ\).
Show answer
\(2(561.7)(0.37142)(1-0.90631) = \mathbf{39.1}\) MW.P12. Bundling four ways cuts \(X\) by 44% but raises \(P_{\max}\) by 145%. Why the mismatch?
Show answer
Because \(r\) falls as \(1/n\) as well. The falling \(r/x\) pushes \(\beta_B\) towards 90°, shrinking the subtracted term in \(P_{\max}\) — Problem 14.
Challenge Problems
Three problems that generalise the set rather than applying it. The first two produce results worth remembering in their own right.
C1 — The loss formula, generalised. Problem 10 obtained \(P_{\text{loss}} = 2K\cos\beta_B(1-\cos\delta)\) for equal terminal voltages. Repeat the derivation with \(|V_S| \ne |V_R|\), simplify as far as it will go, and identify what the result actually is. Check it numerically at \(|V_S| = 231\) kV, \(|V_R| = 220\) kV, \(\delta = 20^\circ\).
Show answer
Subtracting the two power relations without assuming equal magnitudes:
\[ P_{\text{loss}} = \frac{3|A|}{|B|}\left(|V_S|^{2}+|V_R|^{2}\right)\cos(\beta_B-\beta_A) - \frac{6|V_S||V_R|}{|B|}\cos\beta_B\cos\delta \]Applying the identity \(|A|\cos(\beta_B-\beta_A) = \cos\beta_B\) proved in Problem 10, the common factor comes out:
\[ P_{\text{loss}} = \frac{3\cos\beta_B}{|B|}\left(|V_S|^{2}+|V_R|^{2}-2|V_S||V_R|\cos\delta\right) \]The bracket is the cosine rule — it is \(|\mathbf{V}_S - \mathbf{V}_R|^{2}\). And \(\cos\beta_B = R/|B|\), so
\[ P_{\text{loss}} = \frac{3R\,|\mathbf{V}_S-\mathbf{V}_R|^{2}}{|B|^{2}} = 3R\left|\frac{\mathbf{V}_S-\mathbf{V}_R}{\mathbf{B}}\right|^{2} = 3I^{2}R \]It is Joule's law. The whole circle-diagram apparatus, subtracted from itself, returns the elementary result — and identifies \((\mathbf{V}_S-\mathbf{V}_R)/\mathbf{B}\) as the current in the series branch.
The check: with \(V_S = 133.37\), \(V_R = 127.02\) kV per phase and \(\delta = 20^\circ\), the bracket is \(2.0847\times10^{9}\) V\(^2\), giving \(P_{\text{loss}} = 26.942\) MW. Computing \(P_S\) and \(P_R\) separately gives 211.463 and 184.521 MW — a difference of 26.942 MW, and the series current is 529.76 A, for which \(3I^{2}R = 26.942\) MW. All three agree to five figures.
C2 — Where to put 200 MVAr. A fixed 200 MVAr of shunt capacitors is available for the 200 km single-circuit line. Compare siting it at the sending busbar, at the mid-point, and at the receiving busbar, judging by the load that can be served at 0.95 lagging with the receiving voltage at or above 0.95 pu. Then compare by the voltage-collapse point instead, and explain why the two comparisons rank the options differently.
Show answer
\[ \begin{array}{lrr} \text{Siting} & P\ \text{at}\ V_R \ge 0.95\ \text{pu} & P\ \text{at the nose} \\ \hline \text{None} & 54 & 165 \\ \text{Sending busbar} & 54 & 165 \\ \text{Mid-point} & 164 & 213 \\ \text{Receiving busbar} & 216 & 225 \end{array} \]All in MW, with \(B_C = 200/220^{2} = 4.132\) mS.
The sending busbar is worthless. It is held at 220 kV by the source; injecting vars there changes nothing downstream and merely relieves the generator of some excitation duty.
The receiving busbar wins on both counts, but by very different margins — 32% over the mid-point on the voltage criterion and only 6% at the nose. The reason is that the two criteria ask different questions. The nose is reached when the network can no longer supply the reactive demand anywhere, and a mid-point capacitor supports the whole second half of the line, so it delays collapse almost as well. The 0.95 pu criterion asks specifically about the voltage at the load bus, and only a capacitor at that bus holds it directly.
The practical reading: mid-point compensation is a stability measure and busbar compensation is a voltage-regulation measure. A line that is long enough to need both usually gets both, at different ratings — and this is why a mid-point substation on a long corridor carries switched capacitors as well as the reactors of Set 14.
C3 — Four ways to double a corridor. A 500 km, 220 kV single-circuit line delivers 97 MW at a 30° angle limit. Evaluate four upgrades — 50% series compensation, a second circuit, rebuilding at 400 kV with a two-bundle, and rebuilding at 400 kV with a four-bundle — and find the single quantity that predicts all four results.
Show answer
\[ \begin{array}{lrrrr} \text{Option} & |Z_c|\ (\Omega) & \text{SIL} & P_{30^\circ} & P_{30}/\text{SIL} \\ \hline \text{220 kV base} & 397 & 122 & 97 & 0.80 \\ \text{+ 50\% series} & 305 & 159 & 121 & 0.77 \\ \text{Double circuit} & 196 & 248 & 197 & 0.80 \\ \text{400 kV, 2-bundle} & 301 & 532 & 468 & 0.88 \\ \text{400 kV, 4-bundle} & 241 & 663 & 621 & 0.94 \end{array} \]Powers in MW.
The last column is nearly constant. Every option delivers between 0.77 and 0.94 SIL at 500 km, whatever is done to the conductor or the voltage. The loadability in SIL is a function of the electrical length, and none of these upgrades changes the electrical length appreciably — \(\beta = \omega\sqrt{lc}\) is nearly invariant across all overhead construction.
So the only quantity that matters is the SIL, and \(\text{SIL} = V_L^{2}/|Z_c|\) with \(|Z_c|\) confined to a narrow band. Doubling the megawatts therefore means doubling \(V_L^{2}/|Z_c|\), and the four options do it in four ways: series compensation lowers \(Z_c\) by 23%, a second circuit halves it, and the voltage step raises \(V_L^{2}\) by 3.3 times. Only the last is a step change, and it is the only one that also improves the ratio — because a bundled 400 kV line has a lower \(r/x\), which is the effect of Problem 14 reappearing.
The corollary is the planning rule: at a fixed voltage a corridor's capability can be roughly doubled but not transformed, and a demand for several times the transfer is a demand for a higher voltage class or for HVDC.
Multiple-Choice Questions
MCQ 1. In \(\mathbf{S} = 3\mathbf{V}\mathbf{I}^{*}\), the conjugate is needed because:
(a) it makes \(P\) positive (b) the angle becomes \(\theta_V-\theta_I\), independent of reference (c) it cancels the 3 (d) convention onlyShow answer
(b). Without it the result would depend on where the phase reference was placed. Problem 1.MCQ 2. The receiving-end circle has radius:
(a) \(|V_S||V_R|/|B|\) (b) \(|A||V_R|^2/|B|\) (c) \(|V_R|^2/|B|\) (d) \(|V_S|^2/|B|\)Show answer
(a) — the rotating phasor. Option (b) is the distance from the origin to the centre. Problem 7.MCQ 3. Maximum receiving-end power occurs at:
(a) \(\delta = 90^\circ\) (b) \(\delta = \beta_A\) (c) \(\delta = \beta_B\) (d) \(\delta = \beta_B - \beta_A\)Show answer
(c). 90° only for a lossless line, where \(\beta_B = 90^\circ\). Problem 5.MCQ 4. For a 220 kV line with \(r/x = 0.4\), the lossless formula \(P = V_SV_R\sin\delta/X\) overstates the limit by roughly:
(a) 5% (b) 20% (c) 70% (d) not at allShow answer
(c) — 605 MW against 353 MW. The dominant error is the term it drops, not the \(X\) it uses. Problems 5 and 11.MCQ 5. Dropping the shunt admittance from the receiving-end real power relation (equal terminal voltages) costs:
(a) nothing (b) about 1% (c) about 10% (d) it cannot be droppedShow answer
(a). The short-line and nominal-\(\pi\) models give identical \(P_R\); only \(Q_R\) differs, by the constant charging. Problem 11.MCQ 6. A transposed horizontal line with spacing \(D\) has GMD:
(a) \(D\) (b) \(1.26D\) (c) \(1.5D\) (d) \(2D\)Show answer
(b). \(\sqrt[3]{D\cdot D\cdot 2D} = D\sqrt[3]{2} = 1.26D\). Problem 13.MCQ 7. Tripling the phase spacing of a line changes its reactance by about:
(a) +200% (b) +50% (c) +18% (d) it fallsShow answer
(c). The logarithm divides the change by about 6. Problem 15.MCQ 8. A four-conductor bundle at 0.45 m has a GMR about how many times the single conductor's?
(a) 4 (b) 8 (c) 17 (d) 40Show answer
(c) — 0.196 m against 0.0114 m. That is the whole reason bundling works. Problem 14.MCQ 9. In a double-circuit line, reversing the second circuit's phase order:
(a) raises the reactance (b) lowers it (c) has no effect (d) affects only the capacitanceShow answer
(b). It puts like phases diagonally opposite, raising the self-GMD of each phase group — the low-reactance arrangement. Problem 16.MCQ 10. Voltage collapse occurs when:
(a) the voltage falls below 0.9 pu (b) \(\delta\) exceeds 90° (c) the load-flow equation has no real solution (d) a generator tripsShow answer
(c). Two roots merge and then vanish — the system does not settle lower, it collapses. Problem 17.MCQ 11. A line's loadability expressed in multiples of SIL depends principally on:
(a) the voltage class (b) the conductor size (c) the length (d) the load power factorShow answer
(c). The \(V_L^2\) cancels and \(Z_c\) is nearly universal, leaving one curve in length — the St Clair curve. Problem 19.MCQ 12. The transfer capability of a corridor is:
(a) its thermal rating (b) its steady-state stability limit (c) the smallest of several limits, contingency included (d) its SILShow answer
(c). For the double circuit of Problem 20 it was 217 MW — set by the N−1 case, against 434 MW of normal thermal headroom.
Key Formulas
| Quantity | Relation | Notes |
|---|---|---|
| Complex power | \(\mathbf{S} = 3\mathbf{V}\mathbf{I}^{*} = P + jQ\) | \(|S| = \sqrt3V_LI_L\) |
| Receiving-end \(P\) | \(\dfrac{V_SV_R}{|B|}\cos(\beta_B-\delta) - \dfrac{|A|V_R^{2}}{|B|}\cos(\beta_B-\beta_A)\) | Line quantities; threes cancel |
| Receiving-end \(Q\) | The same with sines | Sets the var support needed |
| Sending-end \(P\) | \(\dfrac{|A|V_S^{2}}{|B|}\cos(\beta_B-\beta_A) - \dfrac{V_SV_R}{|B|}\cos(\beta_B+\delta)\) | Signs and arguments both reverse |
| Circle radius | \(V_SV_R/|B|\) | Same for both diagrams |
| Receiving centre | \(-\dfrac{|A|V_R^{2}}{|B|}\angle(\beta_B-\beta_A)\) | Sending centre is \(+\) with \(V_S^{2}\) |
| Maximum power | \(\dfrac{V_SV_R}{|B|} - \dfrac{|A|V_R^{2}}{|B|}\cos(\beta_B-\beta_A)\) | At \(\delta = \beta_B\) |
| Loss identity | \(|A|\cos(\beta_B-\beta_A) = \cos\beta_B\) | Exact for any lossless shunt |
| Transmission loss | \(\dfrac{3\cos\beta_B}{|B|}\left(V_S^{2}+V_R^{2}-2V_SV_R\cos\delta\right)\) | Reduces to \(3I^{2}R\) |
| Inductance | \(L = 0.2\ln(\text{GMD}/\text{GMR})\) mH/km | GMD \(= 1.26D\) horizontal |
| Capacitance | \(C = 0.0556/\ln(\text{GMD}/r)\) µF/km | Physical radius, not GMR |
| Bundle GMR | \(\sqrt{D_sd}\), \(\sqrt[3]{D_sd^{2}}\), \(1.09\sqrt[4]{D_sd^{3}}\) | \(n = 2, 3, 4\) |
| Surge impedance loading | \(\text{SIL} = V_L^{2}/|Z_c|\) | Length-independent yardstick |
| Loadability | \(P_{\max}/\text{SIL} \approx |Z_c|/|B|\) | Function of length alone |
| Voltage-collapse point | Where the two roots of the load-flow quadratic merge | No solution beyond it |
Common Mistakes
Omitting the conjugate in \(\mathbf{S} = 3\mathbf{V}\mathbf{I}^{*}\). The result then depends on the phase reference, which no physical quantity may — Problem 1.
Quoting \(P\) without stating the current direction. The algebra of a generator and a load is identical; only the sign convention distinguishes them — Problem 1.
Taking the maximum at \(\delta = 90^\circ\). It is at \(\delta = \beta_B\), which is 68° here and 45° on a feeder with \(r/x = 1\) — Problem 5.
Using \(P = V_SV_R\sin\delta/X\) outside stability studies. It overstates a resistive line's limit by 71% — Problems 5 and 11.
Reporting the steady-state limit as a capability. It assumes unlimited var support and offers no operating margin — Problems 5, 6 and 18.
Treating \(P_R\) and \(Q_R\) as independent. Fix the two voltages and the constants, and \(\delta\) alone sets both — Problem 2.
Reflecting the receiving circle through the origin to get the sending one. True only when \(|V_S| = |V_R|\); the two centres scale as different squares — Problem 9.
Using the GMR in the capacitance formula. Capacitance uses the physical radius; inductance uses the GMR — Problem 13.
Expecting spacing to be a useful reactance lever. The logarithm divides any spacing change by about six, and clearances fix the spacing anyway — Problem 15.
Forgetting that bundling lowers \(r\) as well as \(x\). The resistance reduction is half the benefit and all of the surprise — Problem 14.
Keeping the same phase order on both circuits of a double-circuit tower. Reversing it lowers the reactance for nothing — Problem 16.
Confusing the voltage limit with the angle limit. One assumes unlimited support and the other none; on this line they differ by a factor of 2.1 — Problem 18.
Part 3 closes here. A transmission line has been built up from its conductor geometry in Set 5, lumped in Sets 9 and 11, solved exactly in Set 12, compensated in Set 14, and finally read as a power relation whose locus is a circle. The four ABCD constants have carried all of it, and the last two problems returned the analysis to the tower drawing it started from — the logarithm in \(L = 0.2\ln(\text{GMD}/\text{GMR})\) being, in the end, the reason every overhead line in the world behaves so nearly alike.
From Set 16 the line stops being a subject. It becomes one off-diagonal entry in a bus admittance matrix, and the questions change from "what does this line do" to "what does this network do". Sets 16 to 18 build \(Y_{\text{bus}}\) and \(Z_{\text{bus}}\); Sets 19 and 20 solve the load flow that the circle diagram of this set was invented to avoid.