Solved Problems · Set 31

Ferranti Effect, SIL and Compensation

Part 3 · Line Performance — the two extremes of a long line, nothing on the end and the one load that makes it invisible, and what a capacitor bank does to both. Chapter 14 of the textbook.

Prof. Mithun Mondal 20 solved · 12 practice · 3 challenge GATE · ESE · University

Set 31 — Ferranti Effect, SIL and Compensation

Twenty worked problems on what a line does when it is nearly empty and when it is loaded exactly right. Every one of them is an accounting of the same two quantities: the reactive power \(V^{2}\omega C\) that the shunt capacitance makes, and the reactive power \(I^{2}\omega L\) that the series inductance eats. When the first wins the voltage climbs towards the far end and the line is in the Ferranti condition; when the second wins it falls and the line is in ordinary regulation; when they balance nothing happens at all, and that balance point is the surge impedance loading. The set works outward from that single idea to reactor sizing, to VAr flow either side of SIL, to series capacitors and the subsynchronous resonance they bring with them, and finally to the tuned line, where the whole problem is made to disappear at a length nobody can build.

Set 14 treated compensation as a regulation problem — how to make a 400 km line meet a percentage. This set treats the same hardware as a reactive-balance problem, and the two views answer different questions. Where a result of Set 14 is used it is cited rather than re-derived.

Textbook Chapter 14 · 20 solved · 12 practice · 3 challenge · 12 MCQs

i Method Recap
  • Two numbers answer almost every question here. The electrical length \(\beta l = \omega l\sqrt{LC}\) and the surge impedance \(Z_s = \sqrt{L/C}\). Compute those first; the Ferranti rise, the reactor rating, the natural loading and the loadability are all one line of algebra away from them.

  • The Ferranti rise is exactly \(1/|A| = 1/|\cosh\gamma l|\). Open the far end, so \(\mathbf{I}_R = 0\), and the first row of the two-port reads \(\mathbf{V}_S = A\mathbf{V}_R\). Since \(|A| < 1\) for every real line, \(|V_R|\) exceeds \(|V_S|\) always.

  • Drop the resistance and the rise becomes \(\sec\beta l\). With \(\gamma = j\beta\), \(\cosh j\beta l = \cos\beta l\). Expanding gives the lumped estimate \((\beta l)^{2}/2\), which is the nominal-\(\pi\) answer and is trustworthy only to about 300 km.

  • It is a phase effect, not a loss effect. The open end reflects totally, so the incident and reflected halves are equal there and separate by \(2\beta x\) as one moves back towards the source. Attenuation slightly reduces the rise, because it makes the two halves unequal and pulls the resultant back towards the axis.

  • The cancelling reactor is \(B_L = \tan(\beta l/2)/Z_s\), obtained by demanding \(\cos\beta l + Z_sB_L\sin\beta l = 1\). As a fraction of the line's own charging susceptance \(\beta l/Z_s\) this is \(\tan(\beta l/2)/(\beta l)\), which is 0.5 for a short line and creeps up with length.

  • SIL is where the two reactive powers cancel. Setting \(I^{2}\omega L = V^{2}\omega C\) gives \(V/I = \sqrt{L/C}\), so \(\mathrm{SIL} = V_{LL}^{2}/Z_s\). At that loading \(|V|\) and \(|I|\) are constant along the line, the power factor is unity everywhere, there is no reflected wave, and the angle across the line is exactly \(\beta l\).

  • Off SIL the line is a VAr source or a VAr sink. With both ends held at \(V\), \(Q_R = \mathrm{SIL}\,(\cos\delta - \cos\beta l)/\sin\beta l\) and \(Q_S = -Q_R\): it delivers reactive power to both ends below SIL and draws it from both above. At no load that export is \(\mathrm{SIL}\tan(\beta l/2)\) per end — exactly the reactor of the fifth point.

  • Loadability is \(P/\mathrm{SIL} = \sin\delta/\sin\beta l\). Length enters only through \(\sin\beta l\) and the conductor only through SIL, so two lines of equal electrical length carry the same multiple of their own natural loading at the same angle.

  • Series compensation shrinks \(L\); shunt compensation shrinks \(C\). With degree \(k\), series gives \(\beta l \to \beta l\sqrt{1-k}\) and \(Z_s \to Z_s\sqrt{1-k}\), so SIL rises; shunt gives the same shortening but \(Z_s \to Z_s/\sqrt{1-k}\), so SIL falls. That single sign difference decides which device is used for which duty.

  • A series capacitor creates an electrical resonance below 50 Hz. The series \(LC\) loop rings at \(f_{er} = f_0\sqrt{X_C/X_L}\), where \(X_L\) is the whole inductive reactance of the loop — generator, transformer and line — not the line alone. The shaft sees the complement \(f_0 - f_{er}\), and if that lands on a torsional mode the machine is in danger.

  • The tuned condition is \(\beta l = n\pi\), which makes \(B = C = 0\) and \(A = D = \pm1\): no drop, no rise, zero regulation at any load. It needs about 2900 km at 50 Hz, and the losses over that distance make it a limiting case rather than a design.

Problem 1Exam levelThe Rise, Three Ways

A 300 km, 400 kV, 50 Hz twin-bundle line has \(r = 0.028\), \(x = 0.325\ \Omega\)/km and \(b = 3.6\times10^{-6}\) S/km. It is energised from a 400 kV busbar with the far end open.

  1. Find the receiving-end voltage exactly, from the ABCD constant \(A\).
  2. Find it again from the lossless formula \(\sec\beta l\).
  3. Find it a third time from the nominal-\(\pi\) estimate \((\beta l)^{2}/2\).
  4. State which is largest and why, and whether the line may be energised in this state.

This line is the reference line of the whole set; every later problem uses these constants.

Solution

The propagation constant and the two-port constants. With \(z = 0.028+j0.325\) and \(y = j3.6\times10^{-6}\) per kilometre:

\[ \gamma = \sqrt{zy} = 4.6552\times10^{-5}+j1.08267\times10^{-3}\ \text{per km}, \qquad Z_c = \sqrt{z/y} = 301.019\angle-2.4620^\circ\ \Omega \]
\[ \gamma l = 0.013966 + j0.324800 \qquad (\alpha l = 0.013966\ \text{Np},\ \ \beta l = 0.324800\ \text{rad} = 18.6097^\circ) \]
\[ A = \cosh\gamma l = 0.947817\angle0.2694^\circ, \qquad B = Z_c\sinh\gamma l = 96.153\angle85.163^\circ\ \Omega \]

Only \(A\) is needed for the open-circuit question; \(B\) and \(C = 1.06115\times10^{-3}\angle90.0872^\circ\) S are recorded here because Problems 4, 6 and 7 want them.

Route one — exact. Open circuit means \(\mathbf{I}_R = 0\), so the first row of the two-port relation is \(\mathbf{V}_S = A\mathbf{V}_R\) with nothing else in it:

\[ |V_{R,\text{NL}}| = \frac{|V_S|}{|A|} = \frac{400}{0.947817} = 422.02\ \text{kV} \qquad\Longrightarrow\qquad \text{rise} = 5.5055\% \]

No approximation of any kind has been made. This is the number a study would report.

Route two — lossless. Set \(r = 0\). Then \(\gamma = j\beta\) with \(\beta = \sqrt{xb}\), and \(\cosh(j\beta l) = \cos\beta l\):

\[ \beta = \sqrt{0.325\times3.6\times10^{-6}} = 1.081665\times10^{-3}\ \text{rad/km}, \qquad \beta l = 0.324500\ \text{rad} = 18.5925^\circ \]
\[ \frac{|V_{R,\text{NL}}|}{|V_S|} = \sec\beta l = \frac{1}{0.947715} = 1.055163 \qquad\Longrightarrow\qquad \text{rise} = 5.5063\% \]

Eight ten-thousandths of a percentage point from the exact answer. On an EHV line the resistance is so small a fraction of the reactance that ignoring it costs nothing here.

Route three — the lumped estimate. Expanding the secant, or equivalently reading the nominal-\(\pi\) circuit with \(\mathbf{I}_R = 0\), gives \(\mathbf{V}_S = (1+\mathbf{YZ}/2)\mathbf{V}_R\):

\[ \sec\beta l = 1 + \frac{(\beta l)^{2}}{2} + \frac{5(\beta l)^{4}}{24} + \cdots \qquad\Longrightarrow\qquad \text{rise} \simeq \frac{(0.3245)^{2}}{2} = 0.052650 = 5.2650\% \]

A quarter of a percentage point low, because the discarded quartic term \(5(\beta l)^{4}/24 = 0.231\%\) is no longer negligible at 300 km. Problem 2 follows that error out to the length where it becomes fatal.

The ordering, and its cause. Collecting the three:

\[ \begin{array}{lcl} \text{Lumped } (\beta l)^{2}/2 & 5.2650\% & \text{two terms of a series} \\ \text{Exact } 1/|\cosh\gamma l| & 5.5055\% & \text{all terms, with loss} \\ \text{Lossless } \sec\beta l & 5.5063\% & \text{all terms, no loss} \end{array} \]

The lossless figure is the largest of the three. Attenuation reduces the Ferranti rise rather than adding to it — a result that looks wrong until Problem 5 draws it, where it becomes obvious.

May the line be energised? The highest voltage permitted on 400 kV equipment is 420 kV, and 422 kV exceeds it:

\[ 422.02\ \text{kV} > 420\ \text{kV} \qquad \text{by } 2.0\ \text{kV} \]

Marginally, but the margin is the wrong way round, and the calculation assumed the source holds exactly 400 kV. A real busbar sits at 400–410 kV, which turns a 2 kV exceedance into 12 kV. The line is not energised without a reactor, which Problem 6 sizes.

All three routes are the same calculation stopped at different points. The lumped estimate is the series truncated after two terms; the secant is the series summed with the resistance thrown away; \(1/|\cosh\gamma l|\) is the series summed with everything kept. Which one an examiner wants is usually signalled by the data: given \(A\), use \(A\); given \(L\) and \(C\) only, use the secant; given a nominal-\(\pi\) circuit, use the quadratic and say that it under-reads.
Answer422.02 kV, a rise of 5.506% exactly; 5.506% from \(\sec\beta l\); 5.265% from \((\beta l)^{2}/2\). The lossless value is the largest. At 422 kV the line exceeds the 420 kV equipment limit and may not be energised open-ended without a shunt reactor.
Problem 2DrillRise Against Length

Keeping the per-kilometre constants of Problem 1, tabulate the open-circuit rise at 100, 200, 300, 400, 500, 600, 800 and 1000 km by all three routes. Identify the length beyond which the lumped estimate should not be used, and explain what happens at 1452 km.

Solution

The three columns. \(\gamma\) and \(\beta\) are per-kilometre constants, so only the length changes:

\[ \begin{array}{rrrrr} l\ (\text{km}) & \beta l\ (^\circ) & \text{exact }1/|A| & \sec\beta l & (\beta l)^{2}/2 \\ \hline 100 & 6.198 & 0.588\% & 0.588\% & 0.585\% \\ 200 & 12.395 & 2.386\% & 2.387\% & 2.340\% \\ 300 & 18.593 & 5.506\% & 5.506\% & 5.265\% \\ 400 & 24.790 & 10.147\% & 10.150\% & 9.360\% \\ 500 & 30.987 & 16.640\% & 16.648\% & 14.625\% \\ 600 & 37.185 & 25.500\% & 25.520\% & 21.060\% \\ 800 & 49.580 & 54.120\% & 54.229\% & 37.440\% \\ 1000 & 61.975 & 112.19\% & 112.83\% & 58.500\% \end{array} \]

Where the estimate fails. Take the error of the quadratic against the exact figure:

\[ \begin{array}{rrr} l & \text{error (points)} & \text{error (relative)} \\ \hline 100 & -0.003 & -0.5\% \\ 200 & -0.046 & -1.9\% \\ 300 & -0.241 & -4.4\% \\ 400 & -0.787 & -7.8\% \\ 600 & -4.44 & -17.4\% \\ 1000 & -53.7 & -47.9\% \end{array} \]

To 200 km the estimate is right to within a twentieth of a percentage point, which is why the nominal-\(\pi\) model of Set 11 is safe there. At 300 km it is a quarter of a point low; at 400 km, three-quarters. Beyond about 250 km use the secant, and beyond about 500 km use \(1/|\cosh\gamma l|\), because by then the two differ from one another as well.

Why the estimate always under-reads. Every term of the secant series is positive:

\[ \sec\theta = 1 + \frac{\theta^{2}}{2} + \frac{5\theta^{4}}{24} + \frac{61\theta^{6}}{720} + \cdots \]

Truncating a series of positive terms can only lose, so the lumped model is a systematic under-estimate of the overvoltage — the dangerous direction for an insulation study. There is no length at which it errs on the safe side.

1452 km. That is a quarter wavelength: \(\lambda = 2\pi/\beta = 5808.8\) km, so \(\lambda/4 = 1452.2\) km and \(\beta l = 90^\circ\). There

\[ \cos\beta l = 0 \qquad\Longrightarrow\qquad \sec\beta l = \infty \]

The lossless model predicts an infinite open-circuit voltage. Physically the line is a series resonance seen from the source: the quarter-wave section inverts impedances about \(Z_s^{2}\), so an open circuit at the far end looks like a short circuit at the near one, and unlimited current flows into an unlimited voltage.

What the exact formula says there, and the difference is instructive:

\[ |A| = |\cosh(0.0676+j1.5708)| = 0.06764 \qquad\Longrightarrow\qquad \frac{1}{|A|} = 14.78 \]

A rise of 1378%, not infinity. Resistance is what limits a resonance, exactly as in a series \(RLC\) circuit, and here \(\alpha l = 0.0676\) Np is the only thing standing between the line and destruction. That no such line exists at 50 Hz is fortunate; that a 145 km line is a quarter wave at 500 Hz is the reason switching studies look far above power frequency.

The rise grows faster than quadratically, and the lumped model is blind to that. Doubling the length from 300 to 600 km multiplies the true rise by 4.6, not by 4; from 400 to 800 km, by 5.3. Any rule that says "the rise goes as the square of the length" is the two-term series in disguise and is only honest below about 250 km.
AnswerSee the table: 0.59% at 100 km rising to 112% at 1000 km. The quadratic estimate is safe to about 250 km, 4% low at 300 km and 48% low at 1000 km, and it always under-reads. At 1452 km \(\beta l = 90^\circ\) and the lossless rise is infinite; resistance limits the real figure to 14.8 times the sending voltage.
Problem 3Exam levelRise Against Voltage

Three 200 km lines are built on the same route:

Line\(r\) Ω/km\(x\) Ω/km\(b\) S/kmHighest equipment voltage
132 kV, single ACSR Panther0.1600.420\(2.70\times10^{-6}\)145 kV
220 kV, single ACSR Zebra0.0900.400\(3.00\times10^{-6}\)245 kV
400 kV, twin ACSR Moose0.0280.325\(3.60\times10^{-6}\)420 kV

Find the percentage Ferranti rise on each with the far end open and the sending end at nominal voltage, and explain why the three answers are so nearly equal while the engineering consequences are not.

Solution

Compute \(|A|\) for each. With \(\gamma l = \sqrt{zy}\,l\) and \(A = \cosh\gamma l\):

\[ \begin{array}{lccc} \text{Line} & \beta l\ (^\circ) & |A| & \text{rise} \\ \hline 132\ \text{kV} & 12.415 & 0.977431 & 2.309\% \\ 220\ \text{kV} & 12.631 & 0.976106 & 2.448\% \\ 400\ \text{kV} & 12.406 & 0.976692 & 2.386\% \end{array} \]

A spread of fourteen hundredths of a percentage point across a voltage range of three to one. For practical purposes the three lines have the same Ferranti rise.

Why they agree. The rise depends on \(\beta l\) and on nothing else, and \(\beta = \omega\sqrt{LC} = \sqrt{xb}\):

\[ \beta_{132} = 1.0649\times10^{-3}, \quad \beta_{220} = 1.0954\times10^{-3}, \quad \beta_{400} = 1.0817\times10^{-3}\ \text{rad/km} \]

All within 3% of one another, because \(\beta = \omega/v\) and the wave velocity on any overhead line is between \(0.95c\) and \(0.99c\). Geometry that raises \(L\) lowers \(C\) in almost exactly compensating proportion, because both depend logarithmically on the same ratio \(D/r\) — one directly, the other inversely.

The consequences, which do not agree at all. Convert the percentages to kilovolts and compare with the equipment limits:

\[ \begin{array}{lccc} \text{Line} & V_{R,\text{NL}} & \text{limit} & \text{headroom} \\ \hline 132\ \text{kV} & 135.05\ \text{kV} & 145\ \text{kV} & +9.95\ \text{kV} \\ 220\ \text{kV} & 225.39\ \text{kV} & 245\ \text{kV} & +19.62\ \text{kV} \\ 400\ \text{kV} & 409.55\ \text{kV} & 420\ \text{kV} & +10.46\ \text{kV} \end{array} \]

All three pass at 200 km, but look at what is being spent. The 132 kV line uses 3 kV of a 13 kV allowance; the 400 kV line uses 9.5 kV of a 20 kV allowance. And the allowance is not proportional to the nominal voltage — it is 9.8% at 132 kV, 11.4% at 220 kV and only 5.0% at 400 kV, because EHV insulation is dimensioned much more tightly.

The length at which each runs out of headroom. Solving \(1/|A(l)| = V_{\max}/V_{\text{nom}}\) for each:

\[ \begin{array}{lcc} \text{Line} & \text{permitted rise} & \text{length at which it is reached} \\ \hline 132\ \text{kV} & 9.85\% & \approx 400\ \text{km} \\ 220\ \text{kV} & 11.36\% & \approx 415\ \text{km} \\ 400\ \text{kV} & 5.00\% & \approx 286\ \text{km} \end{array} \]

The highest-voltage line is the one that runs into the wall first — at 286 km against roughly 400 km for the other two. That inversion is the whole answer to the question.

And one further asymmetry. A 132 kV line that is 400 km long is a curiosity; a 400 kV line that is 400 km long is ordinary. EHV lines exist precisely to cover long distances, so they meet the Ferranti problem both because their permitted rise is smaller and because they are longer. The two effects multiply, which is why every 400 kV and 765 kV circuit has reactors and no 132 kV circuit does.

The Ferranti effect is voltage-blind, but the switchgear is not. The percentage rise is a property of the route length and the frequency; whether it matters is a property of the insulation coordination margin, which shrinks as the voltage class rises. That is why the effect was discovered on a 10 kV cable in 1890 and is a design constraint on 400 kV lines today, and why nobody thinks about it at 33 kV.
Answer2.309%, 2.448% and 2.386% — the same to within a seventh of a percentage point, because \(\beta = \omega/v\) and \(v\) varies by only 3%. But the 400 kV line has 5.0% of headroom against 9.9% and 11.4%, so it exhausts it at 286 km against about 400 km for the others
Problem 4DrillCharging Current

For the 300 km reference line of Problem 1, energised at 400 kV with the far end open, find

  1. the charging current at the sending end, exactly and by the lumped rule;
  2. the reactive power the source must absorb, exactly and by \(V_{LL}^{2}\omega Cl\);
  3. what that demand does to a 500 MVA generator holding the busbar.
Solution

The exact current. The second row of the two-port with \(\mathbf{I}_R = 0\) gives \(\mathbf{I}_S = C\,\mathbf{V}_R\), and \(V_R\) is the risen voltage of Problem 1, not the nominal one:

\[ |I_S| = |C|\times\frac{|V_{R,\text{NL}}|}{\sqrt3} = 1.06115\times10^{-3}\times\frac{422\,022}{\sqrt3} = 1.06115\times10^{-3}\times243\,654 = 258.6\ \text{A} \]

The lumped rule, which treats the line as a lumped capacitor of susceptance \(B = bl\) at nominal voltage:

\[ I_{\text{ch}} = \frac{V_{LL}}{\sqrt3}\,bl = \frac{400\,000}{\sqrt3}\times1.08\times10^{-3} = 230\,940\times1.08\times10^{-3} = 249.4\ \text{A} \]

3.7% low. Both of the neglected effects push the same way: the line actually sits above 400 kV over most of its length, and the distributed capacitance nearest the open end is charged at the highest voltage of all.

The reactive power, exactly. The sending-end current leads the sending-end voltage by very nearly \(90^\circ\), so the complex power entering the line is almost purely negative reactive:

\[ \mathbf{S}_S = 3\mathbf{V}_S\mathbf{I}_S^{*} = 0.57 - j179.13\ \text{MVA} \]

The real part, 0.57 MW, is the no-load loss: \(3I^{2}r l\) with a current that is nowhere near uniform along the line. The line returns 179.1 MVAr to the source.

By the lumped rule:

\[ Q_{\text{ch}} = V_{LL}^{2}\,bl = (400\times10^{3})^{2}\times1.08\times10^{-3} = 172.8\ \text{MVAr} \]

Again 3.7% low, and for the same reason — the rule evaluates \(V^{2}\omega C\) at 400 kV when the line averages about 411 kV. Note that the error in \(Q\) is not twice the error in \(V\): the current error and the voltage error do not compound, because the exact \(Q\) is \(3|V_S||I_S|\) with \(V_S\) at exactly 400 kV.

A relation worth keeping. Divide the charging by the natural loading of Problem 9:

\[ \frac{Q_{\text{ch}}}{\mathrm{SIL}} = \frac{V_{LL}^{2}\,bl}{V_{LL}^{2}/Z_s} = Z_s\,bl = Z_s\,\omega Cl = \beta l \]
\[ \mathrm{SIL}\times\beta l = 532.51\times0.3245 = 172.80\ \text{MVAr} \quad\checkmark \]

Exact, not approximate: a line's charging in MVAr is its SIL in MW multiplied by its electrical length in radians. A 300 km EHV line has \(\beta l \approx 0.32\), so its charging is about a third of its natural loading, and that ratio is the same at every voltage class.

What it does to the generator. A 500 MVA machine asked to absorb 179 MVAr is being run at 0.36 pu leading:

\[ \frac{179.1}{500} = 0.358\ \text{pu underexcited} \]

The underexcited limit of a large turbogenerator is typically 0.25–0.35 pu, set by end-region heating of the stator core and by the steady-state stability limit. This one line, empty, takes the machine to or past its underexcited capability. The field is weak, the internal EMF is low, and the synchronising torque is at its smallest — precisely the state in which one does not want a fault.

Which is the second reason for the reactor. Problem 1 gave the insulation reason; this is the machine reason, and it applies even where the voltage would have been acceptable. Reactors are sized against the larger of the two demands, and on long circuits it is usually this one.

The lumped charging rule is good to a few per cent and should be used for a first pass. Its errors are always in the same direction — it under-reads both current and MVAr, because it evaluates the line at nominal voltage when the line is standing above nominal. Roughly, multiply the lumped answer by the Ferranti factor \(1/|A|\) to recover most of the discrepancy: \(172.8\times1.055 = 182.3\) MVAr against the exact 179.1.
Answer258.6 A exactly against 249.4 A lumped; 179.1 MVAr returned to the source against 172.8 MVAr lumped. That is 0.358 pu leading on a 500 MVA machine, at or beyond its underexcited limit — a second and independent reason for a shunt reactor
Problem 5HardThe Two Waves

Resolve the open-circuit receiving-end voltage of the reference line into its incident and reflected travelling waves, carry both to the sending end, and add them. Show that the sum reproduces \(A = \cosh\gamma l\) exactly, and use the construction to settle a question the algebra hides: does attenuation increase or decrease the Ferranti rise?

Solution

The two waves. Set 12 wrote the voltage at a distance \(x\) measured back from the receiving end as the sum of a wave travelling towards the load and one returning from it:

\[ \mathbf{V}(x) = \underbrace{\frac{\mathbf{V}_R+\mathbf{I}_RZ_c}{2}e^{\gamma x}}_{\text{incident}} + \underbrace{\frac{\mathbf{V}_R-\mathbf{I}_RZ_c}{2}e^{-\gamma x}}_{\text{reflected}} \]

Put \(\mathbf{I}_R = 0\). Both coefficients collapse to \(\mathbf{V}_R/2\): at an open end the reflected wave equals the incident wave exactly, which is what total reflection from an open circuit means.

Carry each to the sending end, where \(x = l\) and \(\gamma l = 0.0139655+j0.324800\). Take \(\mathbf{V}_R\) as the reference phasor:

\[ \text{incident } \overline{OB} = \tfrac12 e^{\alpha l}\angle+\beta l = 0.507032\,V_R\angle18.610^\circ \]
\[ \text{reflected } \overline{OC} = \tfrac12 e^{-\alpha l}\angle-\beta l = 0.493066\,V_R\angle-18.610^\circ \]

The incident half has grown by \(e^{\alpha l} = 1.014063\) and turned forward; the reflected half has shrunk by the same factor and turned back. They have opened out by \(2\beta l = 37.22^\circ\).

O +18.61° -18.61° B : incident 0.5070 V_R C : reflected 0.4931 V_R F : V_S = 0.9478 V_R V_R = 1.000 (open end) sum of lengths 1.000098 = cosh al ; difference 0.013966 = sinh al OF falls short of V_R because the two halves have opened by 2bl = 37.22 degrees
The open-circuited line as two phasors — equal at the far end, opened out by \(2\beta l\) at the source, and summing to less than \(V_R\)

Add them by components. The real parts reinforce; the imaginary parts nearly cancel:

\[ \operatorname{Re} = (0.507032+0.493066)\cos18.610^\circ = 1.000098\times0.947714 = 0.947807 \]
\[ \operatorname{Im} = (0.507032-0.493066)\sin18.610^\circ = 0.013966\times0.319091 = 0.004457 \]
\[ \mathbf{V}_S = (0.947807+j0.004457)\mathbf{V}_R = 0.947817\angle0.2694^\circ\ \mathbf{V}_R = A\,\mathbf{V}_R \quad\checkmark \]

Which is the identity \(\cosh(\alpha l+j\beta l) = \cosh\alpha l\cos\beta l + j\sinh\alpha l\sin\beta l\) drawn as a parallelogram. The sum of the two lengths is \(\cosh\alpha l\); the difference is \(\sinh\alpha l\).

Now the question about attenuation. Hold \(\beta l\) fixed at \(18.610^\circ\) and let \(\alpha l\) go to zero. The two halves become equal at \(0.5\) each, the imaginary parts cancel exactly, and

\[ |A|_{\alpha=0} = \cos\beta l = 0.947714 \qquad\text{against}\qquad |A|_{\text{actual}} = 0.947817 \]
\[ \text{rise} = 5.5170\% \quad\text{lossless} \qquad\text{against}\qquad 5.5055\% \quad\text{with loss} \]

Attenuation reduces the rise. Not by much — 0.0115 of a percentage point here — but the sign is unambiguous, and it is the opposite of what most people guess.

Why, read off the figure. With \(\alpha = 0\) the two phasors are equal, so their resultant lies exactly on the axis with length \(\cos\beta l\) — the pure scissors effect and nothing else. Switching on attenuation lengthens one and shortens the other by the same factor, and since

\[ |A|^{2} = \cosh^{2}\alpha l\cos^{2}\beta l + \sinh^{2}\alpha l\sin^{2}\beta l = \cos^{2}\beta l + \sinh^{2}\alpha l \]

the magnitude can only grow. The added term \(\sinh^{2}\alpha l = 1.95\times10^{-4}\) is tiny, but it is positive, always, for every line ever built. A lossy line therefore has a smaller Ferranti rise than the lossless line of the same electrical length.

The identity also settles the angle. \(\angle A = \arctan(\tanh\alpha l\tan\beta l)\), which is zero when \(\alpha\) is zero:

\[ \angle A = \arctan(0.013965\times0.336680) = 0.2694^\circ \quad\checkmark \]

So the small angle of \(A\) is entirely a loss effect, while its magnitude is almost entirely a phase effect. The two attributes of one complex number have completely different origins.

The Ferranti effect is a phase phenomenon, and nothing about it is caused by loss. Two half-length phasors that have opened like scissors have a resultant shorter than either arm's double — that is the whole mechanism, and it survives untouched if the conductor is made of superconductor. Resistance enters only as a small correction that makes the effect slightly weaker, which is why treating an EHV line as lossless for this calculation is not merely convenient but conservative.
Answer\(0.507032\angle18.610^\circ + 0.493066\angle-18.610^\circ = 0.947817\angle0.2694^\circ = A\). Attenuation reduces the rise, because \(|A|^{2} = \cos^{2}\beta l + \sinh^{2}\alpha l\) and the added term is always positive: 5.5170% lossless against 5.5055% with loss
Problem 6Exam levelReactor Sizing

A shunt reactor is to be connected at the open receiving end of the reference line so that the far end sits at exactly 400 kV when the sending end is at 400 kV. Derive the sizing rule, evaluate it, and state the reactor's reactance, inductance, current and MVAr rating. Express the result as a fraction of the line's own charging, and check the lossless rule against the exact lossy calculation.

Solution

Derive the rule on the lossless line. A reactor of susceptance \(B_L\) across the receiving end draws \(\mathbf{I}_R = -jB_L\mathbf{V}_R\). Substituting into \(\mathbf{V}_S = \mathbf{V}_R\cos\beta l + jZ_s\mathbf{I}_R\sin\beta l\):

\[ \mathbf{V}_S = \mathbf{V}_R\cos\beta l + jZ_s\sin\beta l\,(-jB_L\mathbf{V}_R) = \mathbf{V}_R\big(\cos\beta l + Z_sB_L\sin\beta l\big) \]

Both terms are real, so \(\mathbf{V}_S\) is in phase with \(\mathbf{V}_R\) — a reactor at the far end removes the angle as well as the magnitude difference.

Demand equality of magnitudes and solve:

\[ \cos\beta l + Z_sB_L\sin\beta l = 1 \quad\Longrightarrow\quad B_L = \frac{1-\cos\beta l}{Z_s\sin\beta l} = \frac{1}{Z_s}\tan\frac{\beta l}{2} \]

Using the half-angle identity \((1-\cos\theta)/\sin\theta = \tan(\theta/2)\). The rule needs only the two numbers of the Method Recap.

Evaluate. With \(\beta l = 18.5925^\circ\) and \(Z_s = 300.463\ \Omega\):

\[ B_L = \frac{\tan9.2963^\circ}{300.463} = \frac{0.163690}{300.463} = 5.4479\times10^{-4}\ \text{S} \]
\[ X_L = \frac{1}{B_L} = 1835.6\ \Omega\ \text{per phase}, \qquad L_{\text{reactor}} = \frac{X_L}{\omega} = \frac{1835.6}{314.159} = 5.843\ \text{H} \]

Rating and current, both quoted for a star-connected three-phase bank at 400 kV:

\[ I_L = \frac{V_{LL}}{\sqrt3\,X_L} = \frac{400\,000}{\sqrt3\times1835.6} = 125.8\ \text{A} \]
\[ Q_L = \frac{V_{LL}^{2}}{X_L} = \frac{(400\times10^{3})^{2}}{1835.6} = 87.17\ \text{MVAr} \]

A modest device: 87 MVAr and 126 A, oil-filled, gapped-core, sitting in the line bay. Compare it with the 179 MVAr the source was absorbing in Problem 4.

As a fraction of the line's charging. The line's own susceptance is \(bl = \beta l/Z_s\), so the ratio is a function of electrical length alone:

\[ \frac{B_L}{bl} = \frac{\tan(\beta l/2)/Z_s}{\beta l/Z_s} = \frac{\tan(\beta l/2)}{\beta l} = \frac{0.163690}{0.324500} = 0.5044 \]
\[ \frac{87.17}{172.80} = 0.5044 \quad\checkmark \qquad\text{and}\qquad \lim_{\beta l\to0}\frac{\tan(\beta l/2)}{\beta l} = \tfrac12 \]

A reactor that exactly cancels the Ferranti rise absorbs just over half the line's charging. The ratio is 50.1% at 150 km, 50.4% here, 50.8% at 400 km and 52% at 600 km — it creeps up with length but never far from a half. Real EHV lines carry 50–80% compensation, the excess above a half being there to hold the voltage down at light load rather than at no load.

Check against the exact lossy line. With the reactor connected, \(\mathbf{I}_R = \mathbf{V}_R/(jX_L)\) and the first row of the two-port gives

\[ |V_S| = |V_R|\left|A + \frac{B}{jX_L}\right| \]

Solving \(|A + B/(jX_L)| = 1\) numerically with \(A = 0.947817\angle0.2694^\circ\) and \(B = 96.153\angle85.163^\circ\):

\[ X_L = 1835.7\ \Omega \qquad Q_L = 87.16\ \text{MVAr} \]

The lossless rule is right to four significant figures. That is not luck: the rule depends on \(\beta\) and \(Z_s\), and Problem 5 showed that resistance perturbs both only in the fourth decimal on an EHV line.

Two practical points. First, a reactor sized for no load makes the full-load regulation slightly worse, because at full load the line needs all the reactive help it can get; EHV reactors are therefore switchable and are taken out as the load rises. Second, a line reactor connected inside the circuit breaker follows the line automatically when it is de-energised, whereas a bus reactor must be switched separately — and a bus reactor left connected to a dead busbar is a way to lose a transformer.

The half-the-charging rule is worth memorising, and so is the reason for it. Half the line's charging current flows towards each end from the electrical middle, so a reactor at one end has only half the line to look after. When the reactors are split between the two ends — the usual arrangement — each takes about a quarter of the charging, and the pair still totals a half. Set 14's Problem 19 works the resulting voltage profile.
Answer\(B_L = \tan(\beta l/2)/Z_s = 5.448\times10^{-4}\) S, so \(X_L = 1835.6\ \Omega\), \(L = 5.843\) H, \(I_L = 125.8\) A and 87.17 MVAr — which is 50.44% of the line's 172.8 MVAr charging. The exact lossy solution gives 1835.7 Ω, confirming the rule to four figures
Problem 7DrillA Standard Rating

Reactors are not made to order. The standard 400 kV single-bank ratings available are 50, 63, 80, 100 and 125 MVAr. For each, find the residual open-circuit rise on the reference line, and select the smallest that keeps the far end below 420 kV when the sending busbar is held at its normal upper limit of 410 kV. Comment on what the two largest ratings do.

Solution

The relation to evaluate. A reactor of rating \(Q\) at 400 kV has \(X_L = V_{LL}^{2}/Q\), and the exact receiving voltage with it connected is

\[ |V_{R,\text{NL}}| = \frac{|V_S|}{\left|A + B/(jX_L)\right|} \]

Using the true \(A\) and \(B\) rather than the lossless model, because the answer is now being compared with a hard equipment limit.

The five candidates, with \(V_S = 400\) kV:

\[ \begin{array}{rrrrr} Q\ (\text{MVAr}) & X_L\ (\Omega) & \%\ \text{of charging} & V_{R,\text{NL}} & \text{residual rise} \\ \hline 0 & \infty & 0 & 422.02 & +5.506\% \\ 50 & 3200.0 & 28.9\% & 409.10 & +2.276\% \\ 63 & 2539.7 & 36.5\% & 405.87 & +1.468\% \\ 80 & 2000.0 & 46.3\% & 401.72 & +0.431\% \\ 100 & 1600.0 & 57.9\% & 396.95 & -0.763\% \\ 125 & 1280.0 & 72.3\% & 391.14 & -2.216\% \end{array} \]

The 87.17 MVAr of Problem 6 sits between the 80 and 100 MVAr units, which is why neither of them lands on zero.

Apply the real criterion. The busbar is not held at 400 kV but somewhere up to 410 kV, and the rise is a ratio, so scale each residual:

\[ \begin{array}{rrl} Q & V_{R,\text{NL}}\ \text{at }V_S=410\ \text{kV} & \text{verdict} \\ \hline 50 & 419.33\ \text{kV} & \text{passes by } 0.67\ \text{kV — no margin} \\ 63 & 416.02\ \text{kV} & \text{passes by } 3.98\ \text{kV} \\ 80 & 411.77\ \text{kV} & \text{passes by } 8.23\ \text{kV} \\ 100 & 406.87\ \text{kV} & \text{far inside} \\ 125 & 400.92\ \text{kV} & \text{far inside} \end{array} \]

Select 63 MVAr. The 50 MVAr unit passes arithmetically and fails as engineering: 0.67 kV is inside the measurement uncertainty of the busbar voltage, let alone the tolerance on \(b\), which is itself a few per cent depending on sag and on how far the conductors are from the ground on the day.

What the two largest do. At 100 and 125 MVAr the residual rise has gone negative — the far end is now below the sending end at no load:

\[ Q > 87.17\ \text{MVAr} \quad\Longrightarrow\quad |V_R| < |V_S| \quad\text{at no load} \]

The reactor is now over-compensating: it draws more lagging current than the line's capacitance supplies, and the surplus is drawn through the line's series reactance, producing an ordinary voltage drop. That is not a fault — a 125 MVAr unit is a perfectly sensible choice if the line must also be held down at light load, which is a longer-lasting condition than no load — but it must be switched out as the load rises, or it will cost regulation at full load.

The usual industrial answer is a single switchable 80 MVAr line reactor. It covers the energisation duty with 8 kV of margin, covers most of the light-load duty, and is one standard unit rather than two. The 63 MVAr choice above is the answer to the question as asked — the smallest that passes — and the two answers differ because the question and the specification differ.

Sizing to the calculated optimum is almost never what is installed. The 87.17 MVAr of Problem 6 is a design target, not a purchase order: reactors come in a short list of ratings, the duty covers a range of conditions rather than one, and the source voltage is a band. The right procedure is to compute the target, tabulate the standard sizes either side of it, and then apply the worst-case source voltage — which is what turned a marginal 50 MVAr into a comfortable 63 MVAr here.
AnswerResidual rises of +2.28%, +1.47%, +0.43%, −0.76% and −2.22%. With the busbar at 410 kV the 50 MVAr unit gives 419.3 kV — no usable margin — so the smallest acceptable is 63 MVAr, giving 416.0 kV. The 100 and 125 MVAr units over-compensate and leave the far end below the source at no load
Problem 8HardLumped vs Distributed

Reactive compensation can be lumped at the line ends or distributed along the route. For the reference line:

  1. Find the residual open-circuit rise if the same 87.17 MVAr is spread uniformly along the line instead of being placed at the far end, and explain the difference.
  2. Find the uniform compensation degree needed for a 3% rise and for a 2% rise.
  3. Show that no finite uniform degree can reduce the rise to zero, and find where on the line the highest voltage sits in each arrangement.
Solution

Distributed compensation changes the line's own constants. Absorbing a fraction \(k\) of the shunt susceptance everywhere leaves an effective capacitance \(C(1-k)\), so

\[ \beta' = \omega\sqrt{LC(1-k)} = \beta\sqrt{1-k}, \qquad Z_s' = \sqrt{\frac{L}{C(1-k)}} = \frac{Z_s}{\sqrt{1-k}} \]
\[ \text{rise} = \sec\!\left(\beta l\sqrt{1-k}\right) - 1, \qquad \mathrm{SIL}' = \mathrm{SIL}\sqrt{1-k} \]

The line becomes electrically shorter, which helps, but its surge impedance rises and its natural loading falls, which does not. That penalty is the subject of Set 14's Problem 6 and is not re-derived here.

The same MVAr, spread out. 87.17 MVAr out of the line's 172.80 MVAr charging is \(k = 0.5044\):

\[ \beta' l = 18.5925^\circ\times\sqrt{0.4956} = 18.5925^\circ\times0.70394 = 13.088^\circ \]
\[ \text{rise} = \sec13.088^\circ - 1 = 2.667\% \qquad\text{against}\qquad 0\% \text{ for the same MVAr at the end} \]

Identical hardware, less than half the benefit. Position matters more than quantity for the no-load duty.

Why the end position wins. The two act by different mechanisms. Distributed reactors reduce the cause: less capacitance means less charging current means a smaller rise, but a shorter line is still a line and still has \(\sec\beta'l > 1\). The end reactor cancels the symptom: it draws a lagging current through the whole of \(B\), producing a drop that is subtracted from the rise:

\[ \underbrace{\cos\beta l}_{\text{the rise}} + \underbrace{Z_sB_L\sin\beta l}_{\text{the cancelling drop}} = 1 \]

One term is made to annihilate the other, and annihilation is exact. Reduction is not.

The degrees required. Solving \(\sec(\beta l\sqrt{1-k}) - 1 = \text{target}\):

\[ \begin{array}{rrrr} \text{target rise} & k & \text{MVAr} & \mathrm{SIL}'\ (\text{MW}) \\ \hline 5.506\% & 0 & 0 & 532.5 \\ 4.365\% & 0.20 & 34.6 & 476.3 \\ 3.000\% & 0.4441 & 76.7 & 397.0 \\ 2.667\% & 0.5044 & 87.2 & 374.9 \\ 2.000\% & 0.6264 & 108.2 & 325.5 \\ 1.062\% & 0.80 & 138.2 & 238.1 \\ 0\% & 1 & 172.8 & 0 \end{array} \]

Read the last row. Zero rise needs \(k = 1\) — every scrap of the line's capacitance cancelled — and at that point \(Z_s' = \infty\) and the natural loading is zero. The line has been turned into a pure inductance, which indeed has no Ferranti effect and also carries no power at any sensible angle.

The formal statement. For any \(k < 1\) the compensated electrical length is strictly positive:

\[ \beta l\sqrt{1-k} > 0 \quad\Longrightarrow\quad \sec\!\left(\beta l\sqrt{1-k}\right) > 1 \]

So a uniformly compensated line always has some Ferranti rise. The rise can be made as small as one likes, at a cost in natural loading that grows without bound.

Where the highest voltage sits. With the end reactor connected and both terminals at 400 kV, the profile is \(V(x) = V_R(\cos\beta x + Z_sB_L\sin\beta x)\) measured from the receiving end, which at the mid-point \(x = l/2\) becomes

\[ \frac{V(l/2)}{V_R} = \cos\frac{\beta l}{2} + \tan\frac{\beta l}{2}\sin\frac{\beta l}{2} = \frac{\cos^{2}+\sin^{2}}{\cos(\beta l/2)} = \sec\frac{\beta l}{2} \]
\[ \sec9.2963^\circ = 1.01331 \qquad\Longrightarrow\qquad V_{\text{mid}} = 405.3\ \text{kV} \]

A clean result: an end reactor sized to null the terminal rise leaves a mid-line bulge of exactly \(\sec(\beta l/2)\). Both ends are at 400 kV and the middle is 5.3 kV higher, because the reactors cannot reach it.

Which is where distributed compensation earns its place. The bulge grows fast with length:

\[ \begin{array}{rrr} l\ (\text{km}) & \beta l & \sec(\beta l/2)-1 \\ \hline 300 & 18.59^\circ & 1.33\% \\ 500 & 30.99^\circ & 3.77\% \\ 700 & 43.38^\circ & 7.62\% \\ 900 & 55.78^\circ & 13.14\% \end{array} \]

At 300 km a 1.3% bulge is irrelevant and end reactors are the whole answer. At 700 km the middle of the line is 7.6% above both ends even with the ends perfectly held, and a reactor at an intermediate switching station becomes necessary — not because it is more efficient per MVAr, but because there is no other way to reach the point that is highest. Distributed compensation on the 300 km line, meanwhile, leaves the far end at 410.7 kV and the mid-point at 408.0 kV: worse everywhere.

Compensation is a placement problem before it is a sizing problem. The same megavars do different work depending on where they sit, and the right question is not "how much" but "at which node is the constraint". For a line of moderate length that node is the open terminal, and reactors go at the ends. For a very long line it is the electrical mid-point, and that is what an intermediate switching station with its own reactor bank is for.
AnswerThe same 87.17 MVAr distributed leaves 2.667% against zero when lumped at the end. A 3% rise needs \(k = 44.4\%\) and a 2% rise \(k = 62.6\%\); no \(k < 1\) gives zero, since \(\sec(\beta l\sqrt{1-k}) > 1\) always. With an end reactor the peak is at the mid-point, exactly \(\sec(\beta l/2) = 1.33\%\) above the terminals — 405.3 kV
Problem 9Exam levelSurge Impedance

Derive the surge impedance from the reactive balance rather than from the wave equation, then evaluate \(Z_s\), the surge impedance loading, the wave velocity and the wavelength for the 400 kV reference line and for a 220 kV single-conductor line with \(x = 0.40\ \Omega\)/km and \(b = 3.0\times10^{-6}\) S/km. Explain why the ratio of the two natural loadings is not \((400/220)^{2}\).

Solution

The reactive balance. Per unit length the shunt capacitance generates \(V^{2}\omega C\) and the series inductance consumes \(I^{2}\omega L\). Ask for the loading at which they cancel:

\[ I^{2}\omega L = V^{2}\omega C \quad\Longrightarrow\quad \frac{V^{2}}{I^{2}} = \frac{L}{C} \quad\Longrightarrow\quad \frac{V}{I} = \sqrt{\frac{L}{C}} \equiv Z_s \]

\(\omega\) cancels, so the balance point is a property of the line's geometry alone and is the same at 50 Hz and 60 Hz. And \(Z_s\) comes out real, though it is built from two purely reactive elements — which is what makes it a terminating resistance rather than a reactance.

From \(Z_s\) to SIL. A line terminated in \(Z_s\) carries \(|I| = |V_{LL}|/(\sqrt3Z_s)\) per phase at unity power factor, so

\[ \mathrm{SIL} = \sqrt3|V_{LL}||I| = \sqrt3|V_{LL}|\frac{|V_{LL}|}{\sqrt3 Z_s} = \frac{V_{LL}^{2}}{Z_s} \]

With \(V_{LL}\) in kilovolts the answer is in megawatts directly, which is the form worth memorising.

The 400 kV line. At \(\omega = 314.159\) rad/s:

\[ L = \frac{x}{\omega} = \frac{0.325}{314.159} = 1.03451\ \text{mH/km}, \qquad C = \frac{b}{\omega} = \frac{3.6\times10^{-6}}{314.159} = 11.4592\ \text{nF/km} \]
\[ Z_s = \sqrt{\frac{1.03451\times10^{-3}}{11.4592\times10^{-9}}} = \sqrt{90\,277.8} = 300.463\ \Omega, \qquad \mathrm{SIL} = \frac{400^{2}}{300.463} = 532.51\ \text{MW} \]
\[ v = \frac{1}{\sqrt{LC}} = 2.9044\times10^{5}\ \text{km/s} = 0.9688c, \qquad \lambda = \frac{v}{f} = 5808.8\ \text{km} \]

The 220 kV line, same arithmetic:

\[ L = 1.27324\ \text{mH/km}, \qquad C = 9.5493\ \text{nF/km} \]
\[ Z_s = \sqrt{\frac{1.27324\times10^{-3}}{9.5493\times10^{-9}}} = 365.148\ \Omega, \qquad \mathrm{SIL} = \frac{220^{2}}{365.148} = 132.55\ \text{MW} \]
\[ v = 2.8679\times10^{5}\ \text{km/s} = 0.9566c \]

The ratio, and where the surplus comes from.

\[ \frac{\mathrm{SIL}_{400}}{\mathrm{SIL}_{220}} = \frac{532.51}{132.55} = 4.018 \qquad\text{against}\qquad \left(\frac{400}{220}\right)^{2} = 3.306 \]
\[ \frac{\mathrm{SIL}_{400}}{\mathrm{SIL}_{220}} = \left(\frac{V_{400}}{V_{220}}\right)^{2}\times\frac{Z_{s,220}}{Z_{s,400}} = 3.306\times\frac{365.148}{300.463} = 3.306\times1.2153 = 4.018 \quad\checkmark \]

The extra factor of 1.215 is the ratio of surge impedances, and it comes entirely from bundling. Two sub-conductors 450 mm apart have a much larger equivalent radius than one, which raises \(C\) and lowers \(L\) at the same time — and \(Z_s = \sqrt{L/C}\) feels both movements in the same direction. Set 29 works the bundle geometry that produces the numbers used here.

Why \(Z_s\) hardly ever leaves the range 250–400 Ω. Both parameters depend on the same logarithm of the same geometric ratio:

\[ L \propto \ln\frac{\text{GMD}}{\text{GMR}}, \qquad C \propto \frac{1}{\ln(\text{GMD}/r)} \qquad\Longrightarrow\qquad Z_s = \sqrt{\frac{L}{C}} \propto \ln\frac{\text{GMD}}{\text{GMR}} \]

So \(Z_s\) is proportional to the logarithm itself, not to its square, and a logarithm is a slow function. Quadrupling the spacing changes \(Z_s\) by about a fifth. Every overhead line ever built, at every voltage, lands between about 250 and 400 Ω, and the only way to leave that band is to leave the geometry — which is exactly what a cable does, at 40 Ω.

And why the velocity is always near \(c\). The same cancellation, the other way round:

\[ v = \frac{1}{\sqrt{LC}}: \qquad \text{the two logarithms multiply to something nearly constant} \]

0.9688\(c\) and 0.9566\(c\) here, and no overhead line falls outside 0.95–0.99\(c\). This is why every 50 Hz line has a wavelength near 5800 km and why the tuned length of Problem 19 is the same order for all of them.

\(Z_s\) is the one line parameter that is almost independent of everything. Length does not appear in it; voltage does not appear in it; frequency does not appear in it. Only the ratio of conductor spacing to effective conductor radius does, and only logarithmically. That is why quoting a line's loading as a multiple of its own SIL is so useful: the yardstick is stable even when nothing else is.
Answer400 kV: \(Z_s = 300.46\ \Omega\), SIL 532.5 MW, \(v = 0.9688c\), \(\lambda = 5809\) km. 220 kV: \(Z_s = 365.15\ \Omega\), SIL 132.5 MW, \(v = 0.9566c\). The SIL ratio is 4.018, not 3.306, because bundling lowers \(Z_s\) by a further factor of 1.215
Problem 10DrillSIL Across Classes

Tabulate \(L\), \(C\), \(Z_s\), SIL, the current at SIL and the wave velocity for a 132 kV single ACSR line, a 220 kV single ACSR line, the 400 kV twin-bundle line and a 765 kV quad-bundle line with \(x = 0.2702\ \Omega\)/km and \(b = 4.2412\times10^{-6}\) S/km. Add a 132 kV XLPE cable with \(L = 0.40\) mH/km and \(C = 0.25\ \mu\)F/km. Verify the identity \(Q_{\text{ch}} = \mathrm{SIL}\times\beta l\) on each, and find the length at which the cable's charging current alone reaches its 500 A rating.

Solution

The table. Reactances from the data of Problem 3, converted through \(L = x/\omega\) and \(C = b/\omega\):

\[ \begin{array}{lccccc} \text{Line} & L\ (\text{mH/km}) & C\ (\text{nF/km}) & Z_s\ (\Omega) & \mathrm{SIL}\ (\text{MW}) & I\ \text{at SIL (A)} \\ \hline 132\ \text{kV single} & 1.3369 & 8.594 & 394.41 & 44.2 & 193 \\ 220\ \text{kV single} & 1.2732 & 9.549 & 365.15 & 132.5 & 348 \\ 400\ \text{kV twin} & 1.0345 & 11.459 & 300.46 & 532.5 & 769 \\ 765\ \text{kV quad} & 0.8600 & 13.500 & 252.40 & 2318.7 & 1750 \\ \hline 132\ \text{kV cable} & 0.4000 & 250\,000 & 40.00 & 435.6 & 1906 \end{array} \]

The velocities are \(0.984c\), \(0.957c\), \(0.969c\) and \(0.979c\) for the four overhead lines, and \(0.334c\) for the cable.

Read the overhead rows first. The voltage rises by a factor of 5.8 from top to bottom and the SIL by a factor of 52:

\[ \frac{2318.7}{44.2} = 52.5 \qquad\text{against}\qquad \left(\frac{765}{132}\right)^{2} = 33.6 \]

The extra factor of 1.56 is \(394.41/252.40\), the ratio of surge impedances, and it is bundling again: single conductor, single conductor, twin, quad. Higher voltage buys the square; bundling buys a further half on top of it.

The identity. Both charging and SIL scale as \(V^{2}\), so their ratio is a pure function of the line:

\[ \frac{Q_{\text{ch}}}{\mathrm{SIL}} = \frac{V_{LL}^{2}\,bl}{V_{LL}^{2}/Z_s} = Z_s\,bl = Z_s\,\omega Cl = \omega l\sqrt{LC} = \beta l \]
\[ \begin{array}{lccc} \text{Line} & l\ (\text{km}) & Q_{\text{ch}} = V^{2}bl & \mathrm{SIL}\times\beta l \\ \hline 132\ \text{kV} & 200 & 9.41\ \text{MVAr} & 44.18\times0.21298 = 9.41 \\ 220\ \text{kV} & 200 & 29.04 & 132.55\times0.21909 = 29.04 \\ 400\ \text{kV} & 300 & 172.80 & 532.51\times0.32450 = 172.80 \\ 765\ \text{kV} & 400 & 992.8 & 2318.68\times0.42820 = 992.8 \end{array} \]

Exact in every row, as it must be — the identity is algebra, not a fit. A line's charging in MVAr is its natural loading in MW times its electrical length in radians. Since \(\beta l \approx 0.32\) for a 300 km line at any voltage, the charging of a 300 km circuit is always about a third of its SIL.

Now the cable row, which breaks every pattern. Its capacitance is 22 times that of the 400 kV overhead line, because the conductor sits millimetres from an earthed sheath rather than metres from the ground:

\[ Z_s = \sqrt{\frac{0.40\times10^{-3}}{250\times10^{-9}}} = \sqrt{1600} = 40.0\ \Omega, \qquad v = 0.334c \]

A surge impedance a tenth of the overhead value and a wave velocity a third of it. The nominal SIL of 435.6 MW at 132 kV is a fiction: it implies 1906 A, which is beyond the thermal rating of any 132 kV cable. A cable is never operated near its surge impedance loading, and its natural loading is not a useful design figure.

The charging current limit. Per kilometre, at 132 kV:

\[ \frac{I_{\text{ch}}}{l} = \frac{V_{LL}}{\sqrt3}\,\omega C = \frac{132\,000}{\sqrt3}\times314.159\times0.25\times10^{-6} = 76\,210\times7.854\times10^{-5} = 5.986\ \text{A/km} \]
\[ l_{\text{crit}} = \frac{500}{5.986} = 83.5\ \text{km} \]

At 83.5 km the charging current alone equals the conductor's 500 A rating and the cable can deliver no useful load at all. Practically the limit is reached at half that, since the charging current must be a small fraction of the rating for the cable to be worth laying. This is the reason long submarine links are d.c.: not the loss, not the insulation, but the charging current. Set 30 works the cable capacitance that produces it.

The single most useful number to carry about a line is its SIL, because everything else can be recovered from it. Charging is \(\mathrm{SIL}\times\beta l\); the nulling reactor is \(\mathrm{SIL}\times\tan(\beta l/2)\); the loadability at angle \(\delta\) is \(\mathrm{SIL}\sin\delta/\sin\beta l\); the current at SIL is \(\mathrm{SIL}/(\sqrt3 V_{LL})\). Three of those four appear in this set as separate problems, and all four are the same two numbers wearing different hats.
AnswerSILs of 44.2, 132.5, 532.5 and 2318.7 MW for the four overhead classes, with \(Z_s\) falling from 394 to 252 Ω as bundling increases. The identity \(Q_{\text{ch}} = \mathrm{SIL}\times\beta l\) holds exactly in every row. The cable has \(Z_s = 40\ \Omega\) and \(v = 0.334c\), and its charging alone reaches 500 A at 83.5 km
Problem 11Exam levelThe Flat Profile

Show that a lossless line loaded at exactly its surge impedance loading has constant voltage magnitude, constant current magnitude and unity power factor at every point, exchanges no reactive power with either terminal, and has a load angle of exactly \(\beta l\). Verify each claim numerically on the reference line at 532.51 MW with the receiving end at 400 kV. Then explain why the regulation at SIL is nevertheless not zero.

Solution

Substitute the terminating condition. On a lossless line, with \(x\) measured back from the receiving end,

\[ \mathbf{V}(x) = \mathbf{V}_R\cos\beta x + jZ_s\mathbf{I}_R\sin\beta x, \qquad \mathbf{I}(x) = \mathbf{I}_R\cos\beta x + j\frac{\mathbf{V}_R}{Z_s}\sin\beta x \]

SIL means \(\mathbf{I}_R = \mathbf{V}_R/Z_s\) with \(Z_s\) real. Put that in:

\[ \mathbf{V}(x) = \mathbf{V}_R\left(\cos\beta x + j\sin\beta x\right) = \mathbf{V}_Re^{\,j\beta x} \]
\[ \mathbf{I}(x) = \frac{\mathbf{V}_R}{Z_s}\left(\cos\beta x + j\sin\beta x\right) = \mathbf{I}_Re^{\,j\beta x} \]

Both quantities are the terminal value multiplied by a unit-magnitude rotation. Every claim follows from those two lines.

Claim by claim.

\[ \begin{array}{ll} |\mathbf{V}(x)| = |V_R| & \text{constant — the flat profile} \\ |\mathbf{I}(x)| = |I_R| & \text{constant} \\ \mathbf{V}(x)/\mathbf{I}(x) = Z_s\ \text{(real)} & \text{unity power factor everywhere} \\ \mathbf{S}(x) = 3\mathbf{V}\mathbf{I}^{*} = 3|V_R|^{2}/Z_s & \text{real, so } Q = 0 \text{ at every point} \\ \angle\mathbf{V}(l) - \angle\mathbf{V}(0) = \beta l & \text{the load angle is the electrical length} \end{array} \]

The reflected wave is absent as well: its coefficient \((\mathbf{V}_R - \mathbf{I}_RZ_c)/2\) vanishes identically when \(\mathbf{I}_R = \mathbf{V}_R/Z_c\). A line terminated in its surge impedance is indistinguishable from an infinite line, and an infinite line has nowhere to send a reflection.

The numerical check. With \(V_R = 400/\sqrt3 = 230.94\) kV per phase and \(P = 532.51\) MW at unity power factor:

\[ I_R = \frac{532.51\times10^{6}}{\sqrt3\times400\times10^{3}} = 768.6\ \text{A} \qquad\text{and}\qquad \frac{V_R}{Z_s} = \frac{230\,940}{300.463} = 768.6\ \text{A} \quad\checkmark \]
\[ |V_S| = \sqrt{(V_R\cos\beta l)^{2} + (Z_sI_R\sin\beta l)^{2}} = \sqrt{(218.89)^{2} + (73.63)^{2}} = 230.94\ \text{kV/phase} \]
\[ \Longrightarrow\ |V_{S,LL}| = 400.0\ \text{kV}, \qquad \delta = \arctan\frac{73.63}{218.89} = 18.593^\circ = \beta l \quad\checkmark \]

Flat to the fourth figure, and the angle is the electrical length to three decimal places. The line has become a pure phase-shifter: it moves 532.5 MW and rotates it by 18.6°, and does nothing else at all.

Now the regulation trap. Two different quantities are both called regulation, and only one of them is zero here. The voltage drop along the line is zero:

\[ |V_S| - |V_R| = 0 \]

But regulation as Set 13 defined it is the rise when the load is thrown off with \(|V_S|\) held:

\[ \%\text{Reg} = \frac{|V_S|/|A| - |V_R|}{|V_R|} = \frac{1}{\cos\beta l} - 1 = \sec\beta l - 1 = 5.506\% \]

Which is exactly the Ferranti rise of Problem 1, and no accident: throwing the load off a line at SIL returns it precisely to the open-circuit condition. A flat profile at the operating point and a 5.5% excursion when the load disappears are entirely compatible.

Which resolves an apparent paradox. "SIL is the ideal loading" and "a line at SIL still needs reactors" are both true. The first is about the steady state; the second is about what happens when the breaker at the far end opens. A 400 kV line running happily at its natural loading with a perfectly flat 400 kV profile will go to 422 kV within a cycle of losing its load, and the reactor of Problem 6 exists for that cycle.

SIL is a balance point, not a stable one. Nothing holds a line at its natural loading; the loading is whatever the network demands, and it wanders across the whole range of Problem 12 in the course of a day. What SIL provides is the reference against which the wandering is measured — below it the line makes reactive power and the voltage climbs, above it the line eats reactive power and the voltage sags, and the operator's job is to supply or absorb the difference.
Answer\(\mathbf{V}(x) = \mathbf{V}_Re^{j\beta x}\) and \(\mathbf{I}(x) = \mathbf{I}_Re^{j\beta x}\), so both magnitudes are constant, \(V/I = Z_s\) is real everywhere and \(\delta = \beta l = 18.593^\circ\). Numerically \(I_R = 768.6\) A and \(V_S = 400.0\) kV. The regulation is nonetheless 5.506%, because throwing off the load returns the line to open circuit
Problem 12DrillOff SIL

Holding the receiving end of the reference line at 400 kV and the load at unity power factor, find the sending-end voltage and the load angle at no load and at 0.25, 0.5, 0.75, 1.0, 1.25 and 1.5 times SIL. Plot the voltage profile along the line in four of those cases. Compare the thermal rating of 1.25 kA per phase with the angle limit at \(\delta = 30^\circ\) and say which binds.

Solution

The relation. With \(\mathbf{V}_R\) and \(\mathbf{I}_R\) both real (unity power factor at the receiving end),

\[ \mathbf{V}_S = V_R\cos\beta l + jZ_sI_R\sin\beta l \qquad\Longrightarrow\qquad |V_S| = \sqrt{(V_R\cos\beta l)^{2}+(Z_sI_R\sin\beta l)^{2}} \]

The real part is fixed by the receiving voltage; the imaginary part grows in proportion to the load. The two add in quadrature, so \(|V_S|\) starts below \(|V_R|\) and climbs past it.

The table, with \(V_R\cos\beta l = 218.89\) kV/phase fixed throughout:

\[ \begin{array}{rrrrl} P/\mathrm{SIL} & P\ (\text{MW}) & I_R\ (\text{A}) & V_{S,LL}\ (\text{kV}) & \delta\ (^\circ) \\ \hline 0 & 0 & 0 & 379.12 & 0.000 \\ 0.25 & 133.13 & 192.2 & 380.46 & 4.807 \\ 0.50 & 266.26 & 384.3 & 384.45 & 9.548 \\ 0.75 & 399.38 & 576.5 & 391.00 & 14.160 \\ 1.00 & 532.51 & 768.6 & 400.00 & 18.593 \\ 1.25 & 665.64 & 960.8 & 411.28 & 22.806 \\ 1.50 & 798.77 & 1152.9 & 424.65 & 26.775 \end{array} \]

The sending-end voltage spans 45.5 kV across the loading range while the receiving end never moves. That span is the daily work of voltage control, and SIL is the point about which it is symmetric.

380 400 420 0 100 200 300 distance from sending end (km) kV L-L no load - 379.1 kV at source 0.5 SIL - 384.4 kV 1.0 SIL - flat at 400 kV 1.5 SIL - 424.7 kV at source V_R = 400 kV
Profile along the 300 km line with the receiving end fixed — it rises towards the load below SIL, falls above it, and is flat only at SIL

Read the tilt. Below SIL the profile rises towards the far end, because the capacitance is generating more reactive power than the inductance consumes; above SIL it falls, for the opposite reason. At SIL it is flat, and the flatness is exact rather than approximate. That is the reactive balance of Problem 9 drawn as a picture.

The two limits. Thermally, a twin-bundle ACSR Moose line carries about 1.25 kA per phase:

\[ P_{\text{thermal}} = \sqrt3\times400\times1.25 = 866.0\ \text{MW} = 1.626\ \mathrm{SIL} \]

By the angle limit, with both ends held at 400 kV and \(\delta\) capped at 30° for stability margin:

\[ \frac{P}{\mathrm{SIL}} = \frac{\sin\delta}{\sin\beta l} = \frac{0.5}{0.318835} = 1.568 \qquad\Longrightarrow\qquad P = 835.1\ \text{MW} \]

The angle limit binds, but only just — 835 MW against 866 MW, a difference of 3.6%. The 300 km line sits almost exactly on the crossover.

Find the crossover exactly. The two limits are equal when

\[ \sin\beta l = \frac{\mathrm{SIL}\sin30^\circ}{P_{\text{thermal}}} = \frac{532.51\times0.5}{866.0} = 0.30746 \quad\Longrightarrow\quad \beta l = 17.906^\circ \]
\[ l_{\text{crossover}} = \frac{0.31251}{1.081665\times10^{-3}} = 288.9\ \text{km} \]

Below 289 km the conductor temperature is the constraint and the line will never be angle-limited; above it the angle is the constraint and the conductors will never get hot. This is the St Clair loadability curve, obtained from three lines of algebra rather than from the empirical plots of the 1950s.

A line is a different kind of object either side of about 300 km. Short lines are hot-metal problems, solved by more aluminium. Long lines are angle problems, solved by compensation or by another circuit, and adding aluminium to one does nothing at all. The reference line straddles the boundary — which is exactly why it is the interesting length to study.
Answer379.1 kV at no load rising to 424.7 kV at 1.5 SIL, with \(\delta\) from 0° to 26.8°; flat at 400 kV only at SIL. The angle limit gives 835 MW against a thermal 866 MW, so the angle binds — and the two limits cross at 288.9 km
Problem 13Exam levelVAr Flow

Both ends of the reference line are held at 400 kV. Derive expressions for the reactive power delivered at each end as a function of the transmitted power, tabulate them from no load to twice SIL, and identify the crossover. Show that the no-load value reproduces the reactor of Problem 6, and state what the result means for the busbars at each end.

Solution

Set up the lossless two-port with equal terminal magnitudes. Let \(\mathbf{V}_S = V\angle\delta\) and \(\mathbf{V}_R = V\angle0\), with \(B = jZ_s\sin\beta l\) and \(A = D = \cos\beta l\). The standard receiving-end complex power is

\[ \mathbf{S}_R = \frac{V_SV_R}{|B|}\angle(\theta_B-\delta) - \frac{|A|V_R^{2}}{|B|}\angle(\theta_B-\theta_A) \]

With \(\theta_B = 90^\circ\) and \(\theta_A = 0\), and writing \(V\) in kilovolts so that the answers come out in MW and MVAr:

\[ P_R = \frac{V^{2}\sin\delta}{Z_s\sin\beta l} = \mathrm{SIL}\,\frac{\sin\delta}{\sin\beta l}, \qquad Q_R = \frac{V^{2}(\cos\delta-\cos\beta l)}{Z_s\sin\beta l} = \mathrm{SIL}\,\frac{\cos\delta-\cos\beta l}{\sin\beta l} \]

The first is the loadability relation of the Method Recap. The second is the one this problem is about, and it is remarkable for containing no reference to the load's power factor — with both terminal voltages fixed, the reactive flow is determined.

By symmetry the sending end is the mirror image. Repeating for \(\mathbf{S}_S\) with \(|A| = |D|\):

\[ Q_S = -\mathrm{SIL}\,\frac{\cos\delta-\cos\beta l}{\sin\beta l} = -Q_R \]

\(Q_S\) is the reactive power flowing into the line at the sending end. When \(Q_R\) is positive the line is delivering reactive power to the load and returning an equal amount to the source: it is a VAr generator feeding both ends at once. When \(Q_R\) is negative it is a VAr sink drawing from both.

The table. Solve \(\sin\delta = (P/\mathrm{SIL})\sin\beta l\) for \(\delta\), then evaluate \(Q_R\):

\[ \begin{array}{rrrrl} P/\mathrm{SIL} & P\ (\text{MW}) & \delta\ (^\circ) & Q_R\ (\text{MVAr}) & \text{the line is} \\ \hline 0.00 & 0.0 & 0.000 & +87.17 & \text{a source, } 87\ \text{MVAr each end} \\ 0.25 & 133.1 & 4.572 & +81.85 & \text{a source} \\ 0.50 & 266.3 & 9.173 & +65.81 & \text{a source} \\ 0.75 & 399.4 & 13.835 & +38.71 & \text{a source} \\ 1.00 & 532.5 & 18.593 & \ \ \ 0.00 & \text{neither — this is SIL} \\ 1.25 & 665.6 & 23.487 & -51.21 & \text{a sink} \\ 1.50 & 798.8 & 28.571 & -116.22 & \text{a sink} \\ 1.75 & 931.9 & 33.915 & -196.99 & \text{a sink} \\ 2.00 & 1065.0 & 39.618 & -296.46 & \text{a sink} \end{array} \]
+87 0 -150 -300 Q_R (MVAr) 0 1.0 2.0 P / SIL below SIL : the line EXPORTS VAr to both ends above SIL : the line ABSORBS VAr from both ends SIL - 532.5 MW
Reactive power at each terminal against loading — \(Q_R = \mathrm{SIL}(\cos\delta-\cos\beta l)/\sin\beta l\), positive below SIL and negative above it

The no-load value. At \(\delta = 0\),

\[ Q_R\big|_{P=0} = \mathrm{SIL}\,\frac{1-\cos\beta l}{\sin\beta l} = \mathrm{SIL}\tan\frac{\beta l}{2} = 532.51\times0.163690 = 87.17\ \text{MVAr} \]

The same 87.17 MVAr as the reactor of Problem 6, and necessarily so. The reactor's job is to absorb exactly the reactive power the line insists on delivering. Problem 6 got the number by demanding a voltage; this problem gets it by counting megavars; the two are the same statement.

The crossover is at SIL, exactly. \(Q_R = 0\) requires \(\cos\delta = \cos\beta l\), so \(\delta = \beta l\), and then

\[ \frac{P}{\mathrm{SIL}} = \frac{\sin\beta l}{\sin\beta l} = 1 \]

Which is a third independent characterisation of SIL, after the reactive balance of Problem 9 and the flat profile of Problem 11: it is the loading at which a line with equal terminal voltages exchanges no reactive power with the network.

The asymmetry either side. The curve is not straight, and it is much steeper above SIL than below:

\[ \begin{array}{ll} 0 \to 1\ \mathrm{SIL} & Q_R\ \text{falls by } 87\ \text{MVAr} \\ 1 \to 2\ \mathrm{SIL} & Q_R\ \text{falls by } 296\ \text{MVAr} \end{array} \]

Because the generation term goes as \(V^{2}\), which is pinned by the terminal voltages, while the absorption term goes as \(I^{2}\), which is free to grow. Doubling the loading quadruples the consumption and leaves the production alone. This is why heavily loaded lines are such voracious consumers of reactive power and why shunt capacitors appear at the receiving ends of them.

What it means for the two busbars. Below SIL both must absorb; above SIL both must supply:

\[ \begin{array}{lll} \text{Light load} & \text{generators underexcited, reactors in} & \text{stability margin small} \\ \text{At SIL} & \text{nothing required of either bus} & \\ \text{Heavy load} & \text{generators overexcited, capacitors in} & \text{field heating the constraint} \end{array} \]

And the equipment for the two duties is different, which is the practical sting. Reactors and capacitors are separate assets, both must be paid for, and both spend most of the year switched out.

The line is not a passive conduit for reactive power; it is a machine that makes or eats it depending on how hard it is worked. A 300 km circuit empty is an 87 MVAr generator at each of its ends; the same circuit at twice its natural loading is a 296 MVAr load at each end. Nothing about the hardware changed. Reactive planning is the business of tracking that swing across the day and having enough of both kinds of compensation to follow it.
Answer\(Q_R = \mathrm{SIL}(\cos\delta-\cos\beta l)/\sin\beta l = -Q_S\): +87.17 MVAr at each end at no load, zero at SIL, −296 MVAr at twice SIL. The crossover is exactly at SIL, and the no-load figure is precisely the shunt reactor of Problem 6
Problem 14HardWhere the VArs Are Made

Problem 13 counted the reactive power crossing the two terminals. Account for it instead by integrating along the line: find the reactive power generated by the distributed capacitance and consumed by the distributed inductance at no load, at 0.5 SIL, at SIL and at 1.4 SIL, with both ends held at 400 kV, and show that the difference is what leaves through the terminals. Explain why the generation hardly changes with loading while the consumption changes by a factor of two hundred.

Solution

The two integrals. Each element \(dx\) of line contributes shunt generation and series absorption:

\[ Q_{\text{gen}} = 3\omega C\!\int_0^l |V(x)|^{2}\,dx, \qquad Q_{\text{abs}} = 3\omega L\!\int_0^l |I(x)|^{2}\,dx \]

The factors of three convert per-phase quantities to three-phase totals. Conservation of reactive power then demands that the surplus leave through the two ends.

The profiles to integrate. From the lossless solution with \(x\) measured back from the receiving end,

\[ \mathbf{V}(x) = \mathbf{V}_R\cos\beta x + jZ_s\mathbf{I}_R\sin\beta x, \qquad \mathbf{I}(x) = \mathbf{I}_R\cos\beta x + j\frac{\mathbf{V}_R}{Z_s}\sin\beta x \]

with \(\mathbf{V}_R = 230.94\angle0^\circ\) kV per phase and \(\mathbf{I}_R = \left[(P+jQ_R)/(3V_R)\right]^{*}\), the \(Q_R\) being Problem 13's.

The results, integrated numerically over the 300 km:

\[ \begin{array}{lrrrr} \text{Loading} & Q_{\text{gen}} & Q_{\text{abs}} & \text{net made} & 2Q_R \\ \hline \text{no load} & 175.88 & 1.55 & +174.33 & +174.33 \\ 0.5\ \mathrm{SIL} & 175.13 & 43.51 & +131.61 & +131.61 \\ 1.0\ \mathrm{SIL} & 172.80 & 172.80 & \ \ \ 0.00 & \ \ \ 0.00 \\ 1.4\ \mathrm{SIL} & 169.67 & 346.58 & -176.91 & -176.91 \end{array} \]

All in MVAr. The last two columns agree in every row, as conservation requires, and the factor of two in \(2Q_R\) is because the surplus leaves through both terminals in equal shares.

The SIL row is exact and can be checked by hand. At SIL the profiles are flat, so both integrands are constants:

\[ Q_{\text{gen}} = 3\omega C\,l\,V_p^{2} = \omega Cl\,V_{LL}^{2} = 1.08\times10^{-3}\times(400\times10^{3})^{2} = 172.80\ \text{MVAr} \]
\[ Q_{\text{abs}} = 3\omega L\,l\,I^{2} = 3\times314.159\times1.03451\times10^{-3}\times300\times(768.62)^{2} = 172.80\ \text{MVAr} \]

Equal to the last digit — which is the reactive balance of Problem 9 done as an accounting exercise rather than as a per-unit-length equation. Note also that both equal the line's charging \(V_{LL}^{2}bl\): at SIL the line consumes precisely its own charging.

Why the generation barely moves. It is governed by \(|V|^{2}\), and the voltage is pinned at 400 kV at both ends. Between them it can only bulge or sag by a few per cent:

\[ \frac{175.88}{169.67} = 1.037 \qquad \text{a 3.7\% swing from no load to } 1.4\,\mathrm{SIL} \]

At no load the middle of the line bulges to 405.3 kV (Problem 8), which lifts the integral slightly; at 1.4 SIL it sags below 400 kV, which lowers it slightly. Neither movement is large, because the terminals will not let it be.

Why the consumption moves so violently. It is governed by \(|I|^{2}\), and nothing pins the current at all:

\[ \frac{346.58}{1.55} = 224 \qquad\text{from no load to } 1.4\,\mathrm{SIL} \]

At no load the only current is the charging current, small and varying along the length from zero at the open end to its maximum at the source — which is why \(Q_{\text{abs}}\) is 1.55 MVAr rather than zero. Load it, and the current is the load current, which is free to be anything. The whole variability of a line's reactive behaviour lives in one of the two integrals.

And the shape of the answer follows immediately. Write the net as one nearly-constant term minus one quadratic term:

\[ Q_{\text{net}} \simeq Q_{\text{ch}} - Q_{\text{ch}}\left(\frac{P}{\mathrm{SIL}}\right)^{2} = Q_{\text{ch}}\left[1-\left(\frac{P}{\mathrm{SIL}}\right)^{2}\right] \]
\[ \text{at } 1.4\,\mathrm{SIL}: \quad 172.80\left(1-1.96\right) = -165.9 \qquad\text{against the exact } -176.9 \]

Right to within 6%, and it explains the curve of Problem 13 without any trigonometry: the net reactive output of a line falls as one minus the square of the loading in SIL units, and it is zero at SIL because that is where the square reaches one. The residual 6% error is the profile bulge that this simple version ignores.

Two integrals, one pinned and one free — that is the whole of a line's reactive behaviour. Everything in this set follows: Ferranti is what happens when the pinned integral wins with the free one at zero; SIL is where they meet; the reactor of Problem 6 is a device to absorb the difference at one extreme; the shunt capacitor of Set 14's Problem 14 is a device to supply it at the other. There is really only one phenomenon here, examined at different loadings.
AnswerGeneration 175.9, 175.1, 172.8 and 169.7 MVAr; absorption 1.5, 43.5, 172.8 and 346.6 MVAr. The difference equals \(2Q_R\) in every case. Generation is pinned by the terminal voltages and swings 3.7%; absorption follows \(|I|^{2}\) and swings by a factor of 224, giving \(Q_{\text{net}} \approx Q_{\text{ch}}[1-(P/\mathrm{SIL})^{2}]\)
Problem 15Exam levelSeries Compensation

A series capacitor bank compensating 40% of the reference line's inductive reactance is installed at the mid-point. Find the capacitor's reactance, capacitance and MVAr rating at the line's thermal current, and the resulting \(\beta l\), \(Z_s\), SIL, Ferranti rise and transfer capability at \(\delta = 30^\circ\). Say what the bank does to the charging and to the reactor of Problem 6.

Solution

The capacitor. The line's total series reactance is

\[ X_L = xl = 0.325\times300 = 97.5\ \Omega\ \text{per phase} \]
\[ X_C = kX_L = 0.40\times97.5 = 39.0\ \Omega, \qquad C = \frac{1}{\omega X_C} = \frac{1}{314.159\times39.0} = 81.62\ \mu\text{F per phase} \]

Built as series-parallel strings of individual units in a fenced yard on an insulated platform at line potential — the platform is the expensive part, not the capacitance.

Its rating. A series capacitor's duty is set by the current through it, not the voltage across the line:

\[ V_C = I\,X_C = 1250\times39.0 = 48.75\ \text{kV per phase at the thermal current} \]
\[ Q_C = 3I^{2}X_C = 3\times(1250)^{2}\times39.0 = 182.8\ \text{MVAr} \]

Note the size: 183 MVAr of capacitors to compensate a line whose charging is 173 MVAr. Series compensation is not a small purchase, and its rating rises as the square of the current, so it must be specified against the line's emergency rating rather than its normal one.

And its protection, which dominates the design. During a through fault the same 39 Ω carries the fault current:

\[ V_C\big|_{\text{fault}} = 20\,000\times39.0 = 780\ \text{kV per phase} \]

Sixteen times the normal duty, in a device whose insulation is rated for 49 kV. Every series bank therefore carries a metal-oxide varistor across it that conducts above about 2.3 pu of protective level, plus a triggered spark gap and a bypass breaker behind that. The capacitor is out of circuit within a quarter cycle of a nearby fault and is reinserted a few hundred milliseconds later.

The effect on the line constants. The capacitor cancels part of \(L\) and leaves \(C\) untouched, so with \(m = \sqrt{1-k} = \sqrt{0.6} = 0.774597\):

\[ \beta l \to \beta l\,m = 18.5925^\circ\times0.774597 = 14.4017^\circ \]
\[ Z_s \to Z_s\,m = 300.463\times0.774597 = 232.74\ \Omega \]
\[ \mathrm{SIL} \to \frac{V_{LL}^{2}}{Z_s'} = \frac{400^{2}}{232.74} = 687.5\ \text{MW} = \frac{\mathrm{SIL}}{m} \]

Both movements help. The line is electrically shorter and its natural loading is 29% larger, and the second is the effect that shunt compensation cannot reproduce.

The two headline results.

\[ \text{Ferranti rise} = \sec14.4017^\circ - 1 = 3.244\% \qquad\text{was } 5.506\% \]
\[ P\big|_{\delta=30^\circ} = \mathrm{SIL}'\frac{\sin30^\circ}{\sin\beta'l} = \frac{687.5\times0.5}{0.248714} = 1382\ \text{MW} \qquad\text{was } 835\ \text{MW} \]

A 65.5% increase in transfer capability and a 41% reduction in the no-load overvoltage, from one bank of capacitors in one substation. Nothing else available to a transmission planner does this much for the money.

What it does not change. The charging is untouched, because \(C\) is untouched:

\[ Q_{\text{ch}} = V_{LL}^{2}\,bl = 172.8\ \text{MVAr, exactly as before} \]

And the identity of Problem 10 still holds, with both factors having moved:

\[ \mathrm{SIL}'\times\beta'l = 687.5\times0.251357 = 172.8\ \text{MVAr} \quad\checkmark \]

SIL rose by \(1/m\) and the electrical length fell by \(m\), so their product is invariant under series compensation. A neat check on any answer.

The reactor of Problem 6, recomputed. The rule \(B_L = \tan(\beta l/2)/Z_s\) uses both changed quantities:

\[ B_L' = \frac{\tan7.2009^\circ}{232.74} = \frac{0.126377}{232.74} = 5.430\times10^{-4}\ \text{S} \quad\Longrightarrow\quad Q_L' = 86.9\ \text{MVAr} \]

Essentially unchanged — 86.9 against 87.17 MVAr. The two factors move in opposite directions and very nearly cancel, so series compensation reduces the Ferranti rise without reducing the reactor you need. That surprises people, and the reason is that the reactor's job is to absorb the charging, and the charging did not change.

A series capacitor is the only compensating device that raises a line's natural loading. Everything else — shunt reactors, higher voltage on the same conductors, better power factor — either lowers SIL or leaves it alone. That single property is why series compensation is the standard answer to "this corridor must carry more" and why nearly every long EHV interconnector built since 1970 has a bank on it.
Answer\(X_C = 39.0\ \Omega\), \(C = 81.6\ \mu\)F, 182.8 MVAr at 1250 A. Then \(\beta l = 14.40^\circ\), \(Z_s = 232.7\ \Omega\), SIL 687.5 MW, Ferranti rise 3.244% and 1382 MW at 30° — a 65.5% rise in capability. Charging and the required reactor are both unchanged
Problem 16DrillDegree of Compensation

Tabulate \(X_C\), \(\beta l\), \(Z_s\), SIL, the Ferranti rise and the transfer at \(\delta = 30^\circ\) against a series compensation degree from 0 to 70% on the reference line. Identify where the returns start to accelerate rather than diminish, and give three reasons why degrees above about 70% are not used.

Solution

The table, every column following from \(m = \sqrt{1-k}\):

\[ \begin{array}{rrrrrrr} k & X_C\ (\Omega) & \beta l\ (^\circ) & Z_s\ (\Omega) & \mathrm{SIL}\ (\text{MW}) & \text{Ferranti} & P_{30^\circ}\ (\text{MW}) \\ \hline 0 & 0.0 & 18.593 & 300.5 & 532.5 & 5.506\% & 835 \\ 0.20 & 19.5 & 16.630 & 268.7 & 595.4 & 4.365\% & 1040 \\ 0.30 & 29.3 & 15.556 & 251.4 & 636.5 & 3.802\% & 1187 \\ 0.40 & 39.0 & 14.402 & 232.7 & 687.5 & 3.244\% & 1382 \\ 0.50 & 48.8 & 13.147 & 212.5 & 753.1 & 2.692\% & 1656 \\ 0.60 & 58.5 & 11.759 & 190.0 & 842.0 & 2.144\% & 2066 \\ 0.70 & 68.3 & 10.184 & 164.6 & 972.2 & 1.601\% & 2750 \end{array} \]

The returns accelerate. Take the increment in transfer capability per ten points of compensation:

\[ \begin{array}{lrr} \text{band} & \Delta P\ (\text{MW}) & \text{per point of }k \\ \hline 0 \to 20\% & +205 & 10.3 \\ 20 \to 40\% & +342 & 17.1 \\ 40 \to 60\% & +684 & 34.2 \\ 60 \to 70\% & +684 & 68.4 \end{array} \]

Each extra point of compensation is worth more than the last, because \(P \propto 1/(m\sin(\beta l\,m))\) and both factors shrink together. That is the opposite of the usual engineering pattern and it is exactly what makes high degrees tempting — and dangerous, since the design is being pushed towards a region where small changes have large effects.

Reason one: subsynchronous resonance. The electrical resonant frequency \(f_0\sqrt{X_C/X_L}\) rises with \(k\), and its complement \(f_0 - f_{er}\) sweeps downward through the band 15–35 Hz where turbine-generator torsional modes live. High compensation puts the complement into the middle of that band and keeps it there. Problem 17 computes the frequencies.

Reason two: fault current and protection. The compensated series reactance is \(X_L(1-k)\):

\[ k = 0.70 \quad\Longrightarrow\quad X_{\text{eff}} = 97.5\times0.30 = 29.25\ \Omega \]

Fault levels along the line rise by up to a factor of three, and — worse — a distance relay looking through a capacitor can see a negative apparent reactance for a fault just beyond the bank. Voltage inversion and current inversion both become possible, the relay's directional decision reverses, and the protection has to be redesigned around the bank's location.

Reason three: it is the wrong tool past a point. At \(k = 0.7\) the line's transfer capability is 2750 MW while its conductors carry 866 MW:

\[ \frac{2750}{866} = 3.2 \qquad\text{— the angle limit is now irrelevant} \]

Beyond the point where the thermal limit takes over, further compensation buys nothing whatever. On the reference line that happens at about \(k = 0.04\) for a 30° angle; the useful range for compensation here is set by the desire for a larger stability margin, not by capability. On a 600 km line, whose uncompensated 30° transfer is only 441 MW, the crossover is at \(k \approx 0.51\), and that is why the long lines get the heavy compensation.

Practice. Real fixed banks are 25–50%; the 70% figure appears only on very long radial lines with dedicated SSR countermeasures, and even there it is usually split between a fixed bank and a thyristor-controlled one. Anything above 50% is designed jointly with the machines at each end, not by the line engineer alone.

The economics of series compensation improve with degree and the risks improve faster. The MW-per-rupee curve slopes the tempting way, so the constraint on \(k\) never comes from the capability calculation — it comes from the shaft of a generator two hundred kilometres away, and from a distance relay's directional element. Set the degree from the study of Problem 17 and confirm the capability afterwards, not the other way round.
AnswerSIL rises 532.5 → 972.2 MW and the 30° transfer 835 → 2750 MW as \(k\) goes 0 → 70%, while the Ferranti rise falls 5.51% → 1.60%. Returns accelerate: 10 MW per point at the bottom against 68 MW per point at the top. The limits are subsynchronous resonance, the collapse of protection selectivity, and the thermal limit taking over
Problem 17Exam levelSubsynchronous Resonance

The reference line is fed radially from a 500 MVA, 400 kV generator with \(x''_d = 0.20\) pu through a transformer of 0.12 pu, both on the machine base. The shaft has torsional modes at 15.7, 20.2, 25.5 and 32.3 Hz. Find the electrical resonant frequency of the series-compensated circuit for compensation degrees from 20% to 70%, identify which degrees are unsafe, and state the error made by computing \(f_{er}\) from the line reactance alone.

Solution

The resonant loop. A series capacitor forms an \(LC\) circuit with everything inductive in the path: the generator subtransient reactance, the transformer, and the line. Its natural frequency is

\[ f_{er} = f_0\sqrt{\frac{X_C}{X_{L,\text{total}}}} \]

The reactances are all quoted at 50 Hz and the ratio is frequency-independent, so no scaling is needed inside the root.

Assemble the inductive path in ohms. On a 500 MVA, 400 kV base:

\[ Z_{\text{base}} = \frac{(400)^{2}}{500} = 320.0\ \Omega \]
\[ X_g'' = 0.20\times320 = 64.0\ \Omega, \qquad X_t = 0.12\times320 = 38.4\ \Omega, \qquad X_{\text{line}} = 97.5\ \Omega \]
\[ X_{L,\text{total}} = 64.0+38.4+97.5 = 199.9\ \Omega \]

The line is less than half of it. That single fact is the source of most of the wrong answers to this question.

The frequencies. With \(X_C = k\times97.5\):

\[ \begin{array}{rrrrl} k & X_C\ (\Omega) & f_{er}\ (\text{Hz}) & f_0-f_{er}\ (\text{Hz}) & \text{nearest shaft mode} \\ \hline 0.20 & 19.5 & 15.62 & 34.38 & 32.3 \ (2.1\ \text{Hz clear}) \\ 0.30 & 29.3 & 19.13 & 30.87 & 32.3 \ (1.4\ \text{Hz clear}) \\ 0.40 & 39.0 & 22.09 & 27.92 & 25.5 \ (2.4\ \text{Hz clear}) \\ 0.50 & 48.8 & 24.69 & 25.31 & 25.5\ \textbf{(0.2 Hz — resonance)} \\ 0.60 & 58.5 & 27.05 & 22.95 & 20.2 \ (2.8\ \text{Hz clear}) \\ 0.70 & 68.3 & 29.22 & 20.78 & 20.2\ \textbf{(0.6 Hz — resonance)} \end{array} \]

Why the complement is the frequency that matters. A subsynchronous current at \(f_{er}\) in the stator produces, in the rotor's own reference frame, a torque at the difference frequency:

\[ f_{\text{shaft}} = f_0 - f_{er} \]

The rotor is turning at \(f_0\), so a stator field rotating at \(f_{er}\) slips backward past it at \(f_0-f_{er}\) and pulses the shaft at that rate. If the pulse lands on a torsional natural frequency the shaft is driven at resonance, the oscillation grows because the electrical circuit presents negative damping at that frequency, and the coupling between two turbine sections fatigues. Two shafts were destroyed this way at Mohave in 1970 and 1971, which is how the phenomenon came to be understood.

The verdict. 40% is the natural choice: it clears every mode by more than 2 Hz, it delivers the 1382 MW of Problem 15, and it sits in the middle of a safe band rather than at its edge. 50% must be rejected outright — a 0.2 Hz margin is no margin, since the torsional frequencies themselves are known only to a few tenths and drift with temperature and with blade erosion. 70% is likewise rejected.

The common error. Computing \(f_{er}\) from the line alone gives

\[ f_{er}^{\text{wrong}} = 50\sqrt{\frac{kX_L}{X_L}} = 50\sqrt{k} = 50\sqrt{0.4} = 31.62\ \text{Hz} \]
\[ \text{complement} = 18.38\ \text{Hz} \qquad\text{against the correct } 27.92\ \text{Hz} \]

An error of 9.5 Hz — and it points the wrong way about safety, because 18.38 Hz is close to the 20.2 Hz mode while the true 27.92 Hz is not close to anything. The \(50\sqrt{k}\) formula would have condemned a safe design and, at another degree, cleared a dangerous one. Never use it: the machine and its transformer are part of the resonant circuit whether or not the question mentions them.

What is done when the required degree is unsafe. Four measures, in ascending order of cost:

\[ \begin{array}{ll} 1 & \text{Choose a different degree — free, if the capability allows} \\ 2 & \text{Blocking filter in the generator neutral, tuned to } f_{er} \\ 3 & \text{Replace part of the bank with a TCSC, which looks inductive below } f_0 \\ 4 & \text{SSR relay: detect the torsional oscillation and trip or bypass} \end{array} \]

A thyristor-controlled series capacitor is the modern answer. In capacitive vernier mode it gives the required compensation at 50 Hz while presenting an apparent inductance at subsynchronous frequencies, so the resonance simply does not form. Splitting the bank into two smaller banks at different locations, which is often proposed, does not help — the loop sees the total \(X_C\) regardless of where it sits.

Subsynchronous resonance is the one place in line design where a mechanical property of a machine constrains an electrical property of a line. The compensation degree is chosen against a table of shaft frequencies supplied by the turbine manufacturer, and if the generation at one end of the corridor changes, the study is repeated. A retired unit replaced by a different machine can turn a compensation degree that has been safe for twenty years into a hazard overnight.
Answer\(X_{L,\text{total}} = 199.9\ \Omega\), giving \(f_{er}\) from 15.62 Hz at \(k=0.2\) to 29.22 Hz at \(k=0.7\). 50% and 70% are unsafe (complements 25.31 and 20.78 Hz against modes at 25.5 and 20.2); 40% is the best choice. Using the line reactance alone gives 31.62 Hz instead of 22.09 Hz — an error of 9.5 Hz that reverses the safety verdict
Problem 18Exam levelSeries vs Shunt

Compare 40% series compensation with 40% shunt compensation on the reference line, side by side, on every quantity in this set. Both reduce the Ferranti rise by the same amount; show that they do almost nothing else in common, and state the duty each is bought for.

Solution

The two transformations. With \(m = \sqrt{1-k} = 0.774597\) in both cases:

\[ \begin{array}{lll} & \text{series capacitor } (L \to L(1-k)) & \text{shunt reactor } (C \to C(1-k)) \\ \hline \beta l & \beta l\,m & \beta l\,m \\ Z_s & Z_s\,m & Z_s/m \\ \mathrm{SIL} & \mathrm{SIL}/m & \mathrm{SIL}\,m \\ Q_{\text{ch}} & \text{unchanged} & (1-k)\,Q_{\text{ch}} \end{array} \]

The first row is identical, which is why the Ferranti reduction is identical. The second row has opposite signs in the exponent, and that single difference generates everything else.

The comparison in numbers.

\[ \begin{array}{lrrr} & \text{none} & \text{40\% series} & \text{40\% shunt} \\ \hline \beta l\ (^\circ) & 18.593 & 14.402 & 14.402 \\ Z_s\ (\Omega) & 300.46 & 232.74 & 387.90 \\ \mathrm{SIL}\ (\text{MW}) & 532.5 & 687.5 & 412.5 \\ \text{Ferranti rise} & 5.506\% & 3.244\% & 3.244\% \\ P\ \text{at }30^\circ\ (\text{MW}) & 835.1 & 1382.0 & 829.2 \\ Q_{\text{ch}}\ (\text{MVAr}) & 172.8 & 172.8 & 103.7 \\ \text{device rating} & - & 182.8\ \text{MVAr} & 69.1\ \text{MVAr} \end{array} \]

The two results that decide everything. Look at the SIL row and the transfer row:

\[ \text{series: } \mathrm{SIL}\ \text{up } 29\%,\quad P_{30^\circ}\ \text{up } 65.5\% \]
\[ \text{shunt: } \mathrm{SIL}\ \text{down } 23\%,\quad P_{30^\circ}\ \text{down } 0.7\% \]

Shunt compensation makes the line very slightly worse at carrying power. The electrical shortening helps and the fall in SIL hurts, and the two nearly cancel — the net ratio is \(m\sin\beta l/\sin(\beta l\,m) = 0.9930\). A shunt reactor is therefore not a capability measure in any sense; it is a voltage-control device that costs a little capability.

SENDING RECEIVING series capacitor X_C = k X_L bl and Zs both fall by root(1-k) : SIL RISES switchable shunt reactors, about half the charging each pair shunt capacitor (heavy load)
The three devices and their duties — the series capacitor works hardest when the line is full, the reactors when it is empty, and they are never all in service at once

The opposite duty cycles. The devices are needed at opposite ends of the loading range:

\[ \begin{array}{lll} \text{Series capacitor} & \text{acts on } I & \text{does most when the line is full} \\ \text{Shunt reactor} & \text{acts on } V & \text{does most when the line is empty} \\ \text{Shunt capacitor} & \text{acts on } V & \text{does most when the line is full} \end{array} \]

A series capacitor is self-regulating in a way the shunt devices are not: its output \(3I^{2}X_C\) rises as the square of the load, which is exactly when the reactive support is wanted. A shunt capacitor's output \(V^{2}B_C\) falls when the voltage sags, which is exactly when it is wanted — a perverse characteristic and the reason shunt capacitors are poor at supporting a collapsing bus.

The costs are not comparable either. The series bank here is 183 MVAr against the reactor's 69 MVAr, but the megavar is the wrong unit for a comparison:

\[ \begin{array}{ll} \text{Series capacitor} & \text{platform at line potential, MOV, gap, bypass breaker, SSR study} \\ \text{Shunt reactor} & \text{an oil-filled tank on the ground, a switch, nothing else} \end{array} \]

A shunt reactor is a transformer without a secondary and is priced like one. A series capacitor is a small substation. Per megavar the series bank is several times dearer, and its megavars buy something the reactor's megavars cannot buy at any price.

The specification, in one sentence each. Buy a series capacitor when the problem is how much power the corridor can carry; buy shunt reactors when the problem is how high the voltage goes when the corridor is empty. The reference line has both problems, so it gets both devices, and Problem 20 puts them together. Set 14 works the same pair of devices as a regulation and efficiency question, and its Problems 8 to 12 give the load-flow consequences that this comparison leaves out.

The whole comparison is one sign. Series compensation removes inductance, so \(\sqrt{L/C}\) falls; shunt compensation removes capacitance, so \(\sqrt{L/C}\) rises. Both make \(\sqrt{LC}\) fall by the same factor. Everything in the table — SIL up or down, capability up or unchanged, charging touched or untouched — follows from which of the two square roots the device is acting on.
AnswerBoth give \(\beta l = 14.40^\circ\) and a 3.244% rise. But series gives \(Z_s = 232.7\ \Omega\), SIL 687.5 MW and 1382 MW at 30°, while shunt gives \(Z_s = 387.9\ \Omega\), SIL 412.5 MW and 829 MW — slightly less than uncompensated. Series is a capability device; shunt is a light-load voltage device
Problem 19HardThe Tuned Line

Establish the condition for a line to have zero regulation at every load and every power factor. For the reference line's parameters:

  1. Find the shortest tuned length at 50 Hz, and the \(I^{2}R\) loss over it at SIL.
  2. Find the frequency at which the actual 300 km line would be tuned, and the factor by which \(LC\) would have to be raised to tune it at 50 Hz.
  3. Evaluate the ABCD constants of a real, lossy half-wave line and find its regulation at SIL.
  4. Find the input impedance of a quarter-wave section terminated in 600 Ω and in 150 Ω.
Solution

The condition. The lossless two-port is

\[ \begin{bmatrix}\mathbf{V}_S\\ \mathbf{I}_S\end{bmatrix} = \begin{bmatrix} \cos\beta l & jZ_s\sin\beta l\\ j\sin\beta l/Z_s & \cos\beta l \end{bmatrix} \begin{bmatrix}\mathbf{V}_R\\ \mathbf{I}_R\end{bmatrix} \]

The off-diagonal terms are what couple the voltage to the current, so kill them:

\[ \sin\beta l = 0 \quad\Longleftrightarrow\quad \beta l = n\pi \quad\Longrightarrow\quad B = C = 0,\ A = D = \pm1 \]
\[ |V_S| = |V_R| \ \text{and}\ |I_S| = |I_R| \quad\text{at every load and every power factor} \]

Zero regulation, zero Ferranti rise, no drop. The sign alternates: odd \(n\) reverses the phase by 180°, even \(n\) reproduces it.

The length. From Problem 9, \(\lambda = 5808.8\) km, so

\[ l = \frac{n\lambda}{2} = 2904.4,\ 5808.8,\ 8713.2\ \text{km},\dots \]

The loss over the shortest, carrying its natural loading of 532.5 MW at 768.6 A per phase:

\[ P_{\text{loss}} = 3I^{2}rl = 3\times(768.62)^{2}\times0.028\times2904.4 = 144.1\ \text{MW} \]
\[ \frac{144.1}{532.5} = 27.1\% \]

Perfect regulation at the cost of a quarter of the power. And that is the loss at SIL; at 1.5 SIL it would be 324 MW, or 41% of what was sent. No tuned a.c. line has ever been built and there is no reason to build one — the right-of-way alone would pay for an HVDC link several times over.

The tuning frequency of the actual line. Solve \(\omega l\sqrt{LC} = \pi\) with \(\sqrt{LC} = \beta/\omega = 3.4431\times10^{-6}\) s/km:

\[ \omega = \frac{\pi}{300\times3.4431\times10^{-6}} = 3041.5\ \text{rad/s} \quad\Longrightarrow\quad f = 484.1\ \text{Hz} \]

Equivalently, to tune it at 50 Hz the product \(LC\) would have to rise by

\[ \left(\frac{484.1}{50}\right)^{2} = 93.7 \]

Ninety-four times, by adding series inductance or shunt capacitance along the route. Absurd for a power line, and self-defeating: raising \(LC\) at fixed \(L/C\) leaves \(Z_s\) alone while multiplying the loss and the cost. Heaviside's loading coils are exactly this idea applied to a telephone cable, where the required half-wavelength is metres rather than megametres.

The real half-wave line. Restore \(r = 0.028\ \Omega\)/km over 2904.4 km, so \(\gamma l = 0.135205+j3.144501\):

\[ A = \cosh\gamma l = 1.009150\angle179.98^\circ, \qquad B = Z_c\sinh\gamma l = 40.83\angle178.78^\circ\ \Omega \]

\(B\) is not zero. The perfect repeater exists only on the lossless line, and the resistance leaves a residual series impedance of 41 Ω — small compared with the 947 Ω of raw series impedance \(|zl|\), but not nothing. Note also \(|A| > 1\), so the far end of a real half-wave line on open circuit is below the sending voltage: no Ferranti effect at all, and a small anti-Ferranti one instead.

Its regulation at SIL, the figure the whole idea was supposed to make zero:

\[ \mathbf{V}_S = A\mathbf{V}_R + B\mathbf{I}_R \quad\Longrightarrow\quad |V_{S,LL}| = 458.0\ \text{kV for } |V_{R,LL}| = 400\ \text{kV} \]
\[ \%\text{Reg} = \frac{|V_S|/|A| - |V_R|}{|V_R|} = \frac{453.86-400}{400} = 13.5\% \]

Worse than the 300 km line's 5.5%. The tuned line's zero regulation does not survive contact with resistance, because at 2904 km the current is being pushed through 81 Ω of accumulated resistance and the drop is real even though the reactive terms have cancelled. The idea is exact and useless in the same breath.

The quarter-wave section, \(\beta l = \pi/2\) at 1452.2 km. There \(A = D = 0\), \(B = jZ_s\), \(C = j/Z_s\), so

\[ Z_{\text{in}} = \frac{\mathbf{V}_S}{\mathbf{I}_S} = \frac{jZ_s\mathbf{I}_R}{j\mathbf{V}_R/Z_s} = \frac{Z_s^{2}}{Z_R} \]
\[ Z_R = 600\ \Omega \ \Rightarrow\ Z_{\text{in}} = \frac{90\,277.8}{600} = 150.5\ \Omega, \qquad Z_R = 150\ \Omega \ \Rightarrow\ Z_{\text{in}} = 601.9\ \Omega \]

The section inverts impedances about \(Z_s^{2}\): a load heavier than \(Z_s\) looks lighter from the far end and vice versa, and the two answers above are very nearly each other's partners because 600 and 150 straddle 300.5. An open circuit inverts to a short, which is why \(\sec\beta l\) blew up at 90° in Problem 2.

400 800 0 kV L-L 0 1452 km 2904 km distance along the half-wave line 2.0 SIL - midpoint 800 kV 1.0 SIL - flat 0.5 SIL - midpoint 200 kV no load - midpoint collapses to zero
The fatal property of a half-wave line — both ends stay at 400 kV at every loading, while the mid-point voltage is proportional to the load

Which exposes the deeper objection. A half-wave line's terminals are perfect, but its middle is the quarter-wave point, where \(\mathbf{V} = jZ_s\mathbf{I}_R\):

\[ |V_{\text{mid}}| = Z_sI_R = |V_R|\times\frac{P}{\mathrm{SIL}} \]

The mid-point voltage is proportional to the loading. Empty, the middle of the line sits at zero volts; at twice SIL it sits at 800 kV on a 400 kV line. No insulation system and no protection scheme can accommodate that, which is a stronger argument against the tuned line than the 27% loss.

The tuned line is worth studying because of what it reveals, not what it offers. It shows that regulation is caused entirely by the off-diagonal terms of the two-port; that those terms vanish at a length rather than at a loading; and that the length in question is fixed by the speed of light and the power frequency and is therefore beyond human reach. Compensation, in the end, is the business of moving \(\beta l\) a little way towards \(\pi\) without paying the price of getting there.
Answer\(\beta l = n\pi\), so \(l = 2904\) km, over which the loss at SIL is 144 MW or 27.1%. The 300 km line is tuned at 484 Hz, needing \(LC\) raised 94-fold to tune it at 50 Hz. The lossy half-wave line has \(A = 1.0092\angle180^\circ\), \(B = 40.8\ \Omega\) and a regulation of 13.5%, and its mid-point voltage is proportional to loading — zero when empty, 800 kV at twice SIL. Quarter-wave: 150.5 Ω and 601.9 Ω
Problem 20Exam levelA Complete Design

A new 400 kV corridor 500 km long is to be built with the same conductors as the reference line, giving \(r = 0.028\), \(x = 0.325\ \Omega\)/km, \(b = 3.6\times10^{-6}\) S/km and a thermal rating of 1.25 kA per phase. It must

  1. deliver 800 MW with both ends at 400 kV and a load angle not exceeding 30°;
  2. hold the open-circuit far end below 420 kV with the sending busbar anywhere up to 410 kV.

It is fed from a 1000 MVA generator through a 0.12 pu transformer, the machine having \(x''_d = 0.20\) pu and torsional modes at 15.6, 20.1, 25.4 and 31.9 Hz. Specify the compensation completely and verify every requirement.

Solution

Step 1 — the uncompensated line. Same per-kilometre constants, so \(Z_s = 300.46\ \Omega\) and SIL \(= 532.5\) MW as before, but the length has changed everything else:

\[ \beta l = 1.081665\times10^{-3}\times500 = 0.540833\ \text{rad} = 30.987^\circ \]
\[ \text{Ferranti rise} = \sec30.987^\circ - 1 = 16.65\%, \qquad P\big|_{30^\circ} = \frac{532.5\times0.5}{\sin30.987^\circ} = 517.2\ \text{MW} \]

Both requirements fail, and not marginally: 517 MW against 800 required, and 466 kV on open circuit against a 420 kV ceiling. The line as built is unusable in both directions.

Step 2 — which requirement sets the series compensation. Only a series capacitor can raise the transfer, so size it on requirement 1. With \(m = \sqrt{1-k}\),

\[ P\big|_{30^\circ} = \frac{\mathrm{SIL}}{m}\cdot\frac{0.5}{\sin(\beta l\,m)} = 800 \quad\Longrightarrow\quad m = 0.7967, \quad k = 0.365 \]

36.5% is the bare minimum. Round up to a standard degree with margin, and take \(k = 0.40\) — a number that must now survive the subsynchronous check before anything else is decided.

Step 3 — the subsynchronous check, done before the design is committed. On a 1000 MVA, 400 kV base, \(Z_{\text{base}} = 160\ \Omega\):

\[ X''_g = 32.0,\quad X_t = 19.2,\quad X_{\text{line}} = 0.325\times500 = 162.5 \quad\Longrightarrow\quad X_{L,\text{total}} = 213.7\ \Omega \]
\[ k = 0.40:\ X_C = 65.0\ \Omega, \quad f_{er} = 50\sqrt{\frac{65.0}{213.7}} = 27.58\ \text{Hz}, \quad f_0-f_{er} = 22.42\ \text{Hz} \]
\[ \text{nearest modes: } 20.1\ (2.3\ \text{Hz clear}) \ \text{and}\ 25.4\ (3.0\ \text{Hz clear}) \quad\checkmark \]

Safe, and comfortably so. For contrast, \(k = 0.50\) would give a complement of 19.17 Hz, within 0.9 Hz of the 20.1 Hz mode — so the rounding-up must stop at 40%, and a design that had needed 50% would have required a thyristor-controlled bank instead.

Step 4 — specify the capacitor.

\[ X_C = 65.0\ \Omega\ \text{per phase}, \qquad C = \frac{1}{314.159\times65.0} = 48.97\ \mu\text{F per phase} \]
\[ Q_C = 3I^{2}X_C = 3\times(1250)^{2}\times65.0 = 304.7\ \text{MVAr at thermal current} \]
\[ V_C = 1250\times65.0 = 81.25\ \text{kV per phase}, \qquad\text{MOV protective level } \simeq 2.3\ \text{pu} \]

One bank at the mid-point, on an insulated platform, with metal-oxide varistors, a triggered gap and a bypass breaker. The compensated constants are then

\[ \beta'l = 24.003^\circ, \qquad Z_s' = 232.74\ \Omega, \qquad \mathrm{SIL}' = 687.5\ \text{MW} \]

Step 5 — verify requirement 1.

\[ P\big|_{30^\circ} = \frac{687.5\times0.5}{\sin24.003^\circ} = \frac{343.7}{0.406773} = 845.0\ \text{MW} \ \ge\ 800 \quad\checkmark \]

And the conductors can carry it:

\[ I\big|_{800\ \text{MW}} = \frac{800\times10^{6}}{\sqrt3\times400\times10^{3}} = 1154.7\ \text{A} \ < \ 1250\ \text{A} \quad\checkmark \]
\[ \text{loss} = 3I^{2}rl = 3\times(1154.7)^{2}\times0.028\times500 = 56.0\ \text{MW} = 7.0\% \]

The actual angle at 800 MW is \(\arcsin(800\sin24.003^\circ/687.5) = 28.2^\circ\), so there is 1.8° of margin below the limit as well.

Step 6 — the reactors, sized on requirement 2. With the capacitor in, the exact constants of the compensated line are \(A = 0.913582\) and \(B = 95.64\ \Omega\), giving an open-circuit rise of 9.46%. The full nulling reactor would be

\[ B_L = \frac{\tan12.001^\circ}{232.74} = 9.135\times10^{-4}\ \text{S} \quad\Longrightarrow\quad Q_L = 146.1\ \text{MVAr} \]

But the requirement is 420 kV with the busbar at 410 kV, that is a permitted rise of \(420/410 - 1 = 2.44\%\). Testing standard ratings:

\[ \begin{array}{rrrl} Q\ (\text{MVAr}) & \text{rise} & V_R\ \text{at }410\ \text{kV} & \text{verdict} \\ \hline 0 & 9.46\% & 448.8 & \text{fails} \\ 100 & 2.81\% & 421.5 & \text{fails by } 1.5\ \text{kV} \\ 110 & 2.18\% & 419.0 & \text{passes by } 1.0\ \text{kV} \\ 126\ (2\times63) & 1.20\% & 414.9 & \text{passes by } 5.1\ \text{kV} \\ 146 & 0.00\% & 410.0 & \text{passes; over-provided} \end{array} \]

Specify two 63 MVAr line reactors, one at each end, totalling 126 MVAr — 43.8% of the line's 288 MVAr charging. Splitting them is not cosmetic: it halves the mid-line bulge and it leaves the far end protected when only one end is energised, which is exactly the condition the requirement was written for.

Step 7 — check the mid-line voltage, since Problem 8 showed the terminals are not where the peak is. With both ends held at 400 kV on the compensated line,

\[ \frac{V_{\text{mid}}}{V_{\text{end}}} \le \sec\frac{\beta'l}{2} = \sec12.001^\circ = 1.0224 \quad\Longrightarrow\quad V_{\text{mid}} \le 408.9\ \text{kV} \]

And with the busbar at 410 kV and the reactors only part-compensating, the highest point on the line stays under 419 kV. No intermediate reactor is needed at this length; the calculation of Problem 8 says one would become necessary beyond about 700 km.

The specification, complete.

\[ \begin{array}{ll} \text{Series capacitor} & 65.0\ \Omega,\ 48.97\ \mu\text{F/phase},\ 305\ \text{MVAr},\ \text{mid-point},\ k = 40\% \\ \text{Shunt reactors} & 2\times63\ \text{MVAr line reactors, switchable, one per end} \\ \text{Protection} & \text{MOV + gap + bypass on the capacitor; SSR relay on the machine} \\ \text{Performance} & 845\ \text{MW at }30^\circ;\ 800\ \text{MW at }28.2^\circ;\ \text{loss }7.0\% \\ \text{No load} & 414.9\ \text{kV with the busbar at }410\ \text{kV};\ \text{mid-line }\le 419\ \text{kV} \end{array} \]

What was decided in what order, because the order is the method. The series degree came from the capability requirement; it was then checked against the machine before anything was bought, and that check — not the capability calculation — is what fixed it at 40% rather than 50%. Only then were the reactors sized, against the residual rise that the capacitor had already reduced from 16.65% to 9.46%. Sizing the reactors first would have produced a 190 MVAr answer that the capacitor then made unnecessary.

Compensation is designed against the binding constraint, and the binding constraint is rarely the one in the question. Here the customer asked for megawatts and kilovolts; what actually determined the design was a table of shaft resonances belonging to a machine at one end of the line. That is the normal state of affairs on a long EHV corridor, and it is the reason the SSR study is done at the feasibility stage rather than at the commissioning stage.
Answer40% series compensation — 65.0 Ω, 48.97 µF/phase, 305 MVAr at the mid-point — plus two 63 MVAr switchable line reactors. Delivers 845 MW at 30° (800 MW at 28.2°, 1155 A, 7.0% loss) and holds the open end at 414.9 kV with the busbar at 410 kV. 50% compensation was rejected because its 19.17 Hz complement sits 0.9 Hz from a shaft mode
Practice

Practice Problems

Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not. Take 50 Hz and treat lines as lossless unless told otherwise.

  1. P1. A 400 km line has \(\beta l = 24.79^\circ\). Find its open-circuit voltage rise.

    Show answer
    \(\sec24.79^\circ - 1 = \mathbf{10.15\%}\). Problem 2.
  2. P2. A 400 kV line has \(Z_s = 300\ \Omega\). Find its surge impedance loading and the current at that loading.

    Show answer
    \(400^{2}/300 = \mathbf{533.3}\) MW; \(I = 533.3\times10^{6}/(\sqrt3\times400\times10^{3}) = \mathbf{769.8}\) A. Problem 9.
  3. P3. A 220 kV line 150 km long has \(b = 3.0\times10^{-6}\) S/km. Find its charging reactive power at rated voltage.

    Show answer
    \(V^{2}bl = 220^{2}\times3.0\times10^{-6}\times150 = \mathbf{21.78}\) MVAr. Problem 4.
  4. P4. A 400 kV line has \(\beta l = 20^\circ\) and \(Z_s = 320\ \Omega\). Size the shunt reactor that returns the open end to 400 kV.

    Show answer
    \(B_L = \tan10^\circ/320 = 5.510\times10^{-4}\) S, so \(X_L = \mathbf{1814.8\ \Omega}\) and \(Q_L = \mathbf{88.16}\) MVAr. Problem 6.
  5. P5. What fraction of that line's charging does the reactor of P4 absorb?

    Show answer
    \(\tan(\beta l/2)/\beta l = 0.17633/0.34907 = \mathbf{50.51\%}\) — just over half, as always. Problem 6.
  6. P6. A 400 kV line has \(\beta l = 24^\circ\) and \(Z_s = 300\ \Omega\). Apply 40% series compensation and find the new \(\beta l\), \(Z_s\), SIL and Ferranti rise, and the percentage increase in the 30° transfer.

    Show answer
    \(m = 0.7746\): \(\beta l = \mathbf{18.59^\circ}\), \(Z_s = \mathbf{232.4\ \Omega}\), SIL \(= \mathbf{688.5}\) MW, rise \(= \mathbf{5.51\%}\). Transfer 655.6 → 1079.9 MW, an increase of 64.7%. Problem 15.
  7. P7. A machine and its transformer contribute 80 Ω and the line 120 Ω. With 35% series compensation of the line, find the subsynchronous resonant frequency and the frequency the shaft sees.

    Show answer
    \(X_C = 42\ \Omega\), \(X_{L,\text{tot}} = 200\ \Omega\), so \(f_{er} = 50\sqrt{0.21} = \mathbf{22.91}\) Hz and the shaft sees \(50-22.91 = \mathbf{27.09}\) Hz. Problem 17.
  8. P8. A line has a wave velocity of \(0.97c\). Find its wavelength at 50 Hz and the shortest tuned length.

    Show answer
    \(\lambda = 0.97\times299\,792/50 = \mathbf{5816}\) km; tuned at \(\lambda/2 = \mathbf{2908}\) km. Problem 19.
  9. P9. A quarter-wave lossless line of \(Z_s = 350\ \Omega\) is terminated in 200 Ω. Find the input impedance, and state what an open circuit would give.

    Show answer
    \(Z_s^{2}/Z_R = 350^{2}/200 = \mathbf{612.5\ \Omega}\). An open circuit gives a short circuit. Problem 19.
  10. P10. The reference line (\(\beta l = 18.59^\circ\), SIL 532.5 MW) runs at 0.6 SIL with both ends at 400 kV. Find the load angle and the reactive power at the receiving end, and say which way it flows.

    Show answer
    \(\sin\delta = 0.6\sin18.59^\circ\) gives \(\delta = \mathbf{11.03^\circ}\); \(Q_R = 532.5(\cos11.03^\circ-\cos18.59^\circ)/\sin18.59^\circ = \mathbf{+56.3}\) MVAr, out of the line into the bus — and the same again at the sending end. Problem 13.
  11. P11. A 132 kV cable with \(C = 0.25\ \mu\)F/km is 60 km long. Find its charging current.

    Show answer
    \((132\,000/\sqrt3)\times314.159\times0.25\times10^{-6}\times60 = \mathbf{359}\) A — before any load at all. Problem 10.
  12. P12. Without computing \(C\) or \(Z_s\) separately, express a line's charging MVAr as a fraction of its SIL when \(\beta l = 18.59^\circ\).

    Show answer
    \(Q_{\text{ch}}/\mathrm{SIL} = \beta l\) in radians \(= \mathbf{0.3245}\), so the charging is 32.45% of SIL. Problems 4 and 10.
Challenge

Challenge Problems

Three problems in which the standard formula is not enough and something has to be noticed first.

  1. C1 — Energising from a weak source. Every calculation in this set assumed an infinite busbar. Redo Problem 1 with the reference line energised from a source of finite short-circuit level, find the receiving voltage for levels of 3, 5, 8 and 15 GVA, and find the short-circuit level at which the arrangement would resonate. Explain what this means for the switching sequence at commissioning.

    Show answer

    Set up the circuit. Behind the busbar is an EMF \(\mathbf{E}\) and a reactance \(jX_s = jV_{LL}^{2}/S_{\text{sc}}\). The line contributes \(\mathbf{V}_S = A\mathbf{V}_R\) and \(\mathbf{I}_S = \mathbf{C}\mathbf{V}_R\), with \(\mathbf{C}\) the ABCD constant. Then

    \[ \mathbf{E} = \mathbf{V}_S + jX_s\mathbf{I}_S = \left(A + jX_s\mathbf{C}\right)\mathbf{V}_R \quad\Longrightarrow\quad |V_R| = \frac{|E|}{\left|A + jX_s\mathbf{C}\right|} \]

    Why the denominator shrinks. \(A\) is very nearly real and positive; \(\mathbf{C}\) is very nearly \(+j|C|\), so \(jX_s\mathbf{C}\) is very nearly \(-X_s|C|\), a negative real number. The source reactance subtracts from \(A\) and makes the Ferranti effect worse — the source inductance and the line capacitance are in series, and the arrangement is a voltage divider working the wrong way round.

    \[ \begin{array}{rrrr} S_{\text{sc}}\ (\text{MVA}) & X_s\ (\Omega) & |A+jX_s\mathbf{C}| & |V_R|\ \text{for } |E| = 400\ \text{kV} \\ \hline \infty & 0 & 0.947817 & 422.0\ \text{kV} \\ 15\,000 & 10.67 & 0.936499 & 427.1\ \text{kV} \\ 8\,000 & 20.00 & 0.926595 & 431.7\ \text{kV} \\ 5\,000 & 32.00 & 0.913861 & 437.7\ \text{kV} \\ 3\,000 & 53.33 & 0.891223 & 448.8\ \text{kV} \end{array} \]

    The rise doubles. 5.5% against an infinite bus becomes 12.2% behind a 3 GVA source. A weak source is exactly what one has at a remote generating station, and often exactly what one has during a system restoration — which is when long lines are being energised one at a time.

    The resonance. The denominator vanishes when \(X_s|C| = |A|\):

    \[ X_s = \frac{|A|}{|\mathbf{C}|} = \frac{0.947817}{1.06115\times10^{-3}} = 893.2\ \Omega \quad\Longrightarrow\quad S_{\text{sc}} = \frac{400^{2}}{893.2} = 179\ \text{MVA} \]

    That 893 Ω is precisely the open-circuit input impedance \(A/\mathbf{C}\) of the line, which is capacitive; series-resonating it with the source inductance is what the condition says. 179 MVA is far below any real transmission source, so the resonance is not reached — but the approach to it is what produces the amplification in the table, and on a system being restored from a single small unit it is not unthinkable.

    The consequence for commissioning. Three rules follow. Energise the line from the strongest available busbar, not the most convenient one. Connect the shunt reactor before the line breaker closes, not after — a line reactor inside the breaker does this automatically and a bus reactor does not. And compute the rise with the actual short-circuit level of the day, because the switching study done at full network strength will understate it, and understate it most on the night when half the plant is out.

  2. C2 — The compensation degree that could not be used. A 600 km, 400 kV line with \(x = 0.325\ \Omega\)/km, \(Z_s = 300.5\ \Omega\) and SIL 532.5 MW must carry 900 MW at a 30° angle. It is fed by two 600 MVA machines with \(x''_d = 0.22\) pu through 0.13 pu transformers, and the shafts have modes at 16.3, 24.0, 27.8 and 33.5 Hz. Find the required degree, show that it cannot be used as a single fixed bank, and evaluate three ways out — including the one that does not work.

    Show answer

    The required degree. \(\beta l = 1.081665\times10^{-3}\times600 = 37.185^\circ\), so uncompensated \(P_{30^\circ} = 532.5\times0.5/\sin37.185^\circ = 440.5\) MW. Solving \((\mathrm{SIL}/m)(0.5)/\sin(\beta l\,m) = 900\) gives \(m = 0.6865\) and

    \[ k = 1 - m^{2} = 0.529 \quad\Longrightarrow\quad \text{take } k = 0.55\ \text{for margin} \]

    The subsynchronous check. Two 600 MVA machines in parallel, so on a 1200 MVA 400 kV base \(Z_{\text{base}} = 133.3\ \Omega\):

    \[ X''_g = 0.22\times133.3 = 29.3\ \Omega,\quad X_t = 0.13\times133.3 = 17.3\ \Omega,\quad X_{\text{line}} = 195.0\ \Omega \]
    \[ X_{L,\text{tot}} = 241.6\ \Omega, \qquad X_C = 0.55\times195.0 = 107.25\ \Omega \]
    \[ f_{er} = 50\sqrt{\frac{107.25}{241.6}} = 33.31\ \text{Hz} \quad\Longrightarrow\quad f_0 - f_{er} = 16.69\ \text{Hz} \]

    Against a mode at 16.3 Hz — a margin of 0.39 Hz, which is inside the uncertainty of the manufacturer's own figures. The design is rejected. And the nearby degrees are no better: \(k = 0.52\) gives 17.6 Hz and \(k = 0.60\) gives 15.2 Hz, both within about a hertz of the same mode, because the first torsional mode of a large steam turbine generally sits in the middle of the band that 50–60% compensation excites.

    Way out 1, which does not work: split the bank. Two banks of 27.5% at different points along the line. The resonant loop contains both capacitors in series, so it sees the total 107.25 Ω and rings at exactly the same 33.31 Hz. Splitting changes the fault duty on each bank, the platform cost and the protection philosophy; it does not change \(f_{er}\) by one hertz. This is the commonest wrong answer to an SSR problem and it comes from confusing "two capacitors" with "two circuits".

    Way out 2: reduce the degree and accept a smaller angle margin. At \(k = 0.40\), \(X_C = 78.0\ \Omega\) and \(f_{er} = 28.4\) Hz, giving a complement of 21.6 Hz — clear of 16.3 by 5.3 Hz and of 24.0 by 2.4 Hz. The transfer at 30° falls to 713 MW; reaching 900 MW then needs \(\delta = 39.1^\circ\), which is outside the usual stability rule but not outside what a well-instrumented system with fast excitation can hold. This is a real engineering trade and it is often the answer.

    Way out 3: a thyristor-controlled series capacitor. Provide 40% as a fixed bank and 15% as a TCSC. At 50 Hz the TCSC in capacitive vernier mode contributes its share of compensation, so the steady-state degree is 55% and the 900 MW is delivered at 30°. Below 50 Hz its thyristor control makes it present an apparent inductance, so the resonant loop sees only the fixed 78 Ω and rings at 28.4 Hz — the safe frequency of way 2. The TCSC buys the capability of 55% and the SSR behaviour of 40%, and that is the whole reason the device exists.

    The general lesson. On any long radial corridor the compensation degree is bounded above not by capability, not by cost, and not by protection, but by a mechanical resonance in a machine that the line engineer may never see. When the degree the transfer demands and the degree the shaft permits do not overlap, the answer is a controlled capacitor, not a bigger one.

  3. C3 — The half-wave transmission proposal. A study proposes moving 4000 MW over 2900 km by a single 800 kV half-wave a.c. line rather than by HVDC, arguing that the line needs no compensation at all and no converter stations. The line would have \(Z_s = 260\ \Omega\) and \(r = 0.011\ \Omega\)/km. Evaluate the proposal on its own terms, and identify the objection that kills it.

    Show answer

    Take the claims at face value first. SIL \(= 800^{2}/260 = 2462\) MW, so 4000 MW is 1.625 SIL. At \(\beta l = \pi\) the lossless constants are \(A = D = -1\) and \(B = \mathbf{C} = 0\): the terminal voltages are equal at every loading, the regulation is exactly zero, and no reactor and no capacitor is required anywhere. The claims are true.

    Now the loss. At 4000 MW the current is \(4000\times10^{6}/(\sqrt3\times800\times10^{3}) = 2887\) A per phase, so

    \[ P_{\text{loss}} = 3(2887)^{2}(0.011)(2900) = 797\ \text{MW} = 19.9\% \]

    An HVDC bipole over the same route loses about 6% including both converter stations. The a.c. proposal throws away 557 MW more, continuously, which at ₹4 per kWh and full utilisation is of the order of ₹1950 crore a year. That is not yet decisive — it is an economic argument, and economics can be argued with.

    The objection that is not economic. Look at the middle of the line, which is the quarter-wave point. There \(\cos\beta x = 0\) and \(\sin\beta x = 1\), so

    \[ \mathbf{V}_{\text{mid}} = jZ_s\mathbf{I}_R \quad\Longrightarrow\quad |V_{\text{mid}}| = Z_sI_R = |V_R|\times\frac{P}{\mathrm{SIL}} \]

    The mid-point voltage is directly proportional to the loading. Evaluate it across the operating range:

    \[ \begin{array}{lrr} \text{loading} & P\ (\text{MW}) & |V_{\text{mid}}|\ (\text{kV}) \\ \hline \text{no load} & 0 & 0 \\ 0.5\ \mathrm{SIL} & 1231 & 400 \\ 1.0\ \mathrm{SIL} & 2462 & 800 \\ 1.625\ \mathrm{SIL} & 4000 & 1300 \\ 2.0\ \mathrm{SIL} & 4923 & 1600 \end{array} \]

    At the design loading the middle of an 800 kV line stands at 1300 kV, and on a load rejection it collapses to zero. No insulation system can be specified for a conductor whose voltage ranges from 0 to 1600 kV as a function of what the load is doing; no surge arrester can be selected; no line trap, no CVT and no protection scheme has a defined operating voltage. The line would have to be insulated for its worst case along its whole length, which means building an 1800 kV line and running it at 800 kV.

    Two further objections in the same family. The exact half wavelength depends on \(\sqrt{LC}\), which varies with sag, ice and ground conditions, and on the frequency, which varies with the system; being 2% off the tuned length turns \(B = 0\) into \(B = jZ_s\sin(1.02\pi) = -j16\ \Omega\) and reintroduces regulation. And a fault anywhere on the line changes its electrical length instantly, so the "no compensation needed" property exists only for the intact line in the steady state at exactly 50 Hz.

    Verdict. The proposal is arithmetically correct and physically unbuildable. Its own central property — that \(B = 0\) at the terminals — is achieved by letting the voltage swing enormously in between, and a two-port that is perfect at its ports says nothing whatever about what happens inside it. That is the deepest lesson available from the tuned line, and it is worth more than the formula.

Self-Test

Multiple-Choice Questions

  1. MCQ 1. On a lossless line of electrical length \(\beta l\), the open-circuit receiving voltage divided by the sending voltage is:
    (a) \(\cos\beta l\)   (b) \(\sec\beta l\)   (c) \((\beta l)^{2}/2\)   (d) \(1/|B|\)

    Show answer
    (b). \(V_S = AV_R\) with \(A = \cos\beta l\), so the ratio is its reciprocal. (a) inverts it and would predict a fall; (c) is the two-term expansion of (b), a good estimate but not the ratio itself. Problem 1.
  2. MCQ 2. Compared with a lossless line of the same electrical length, a real line's Ferranti rise is:
    (a) larger   (b) smaller   (c) identical   (d) larger below 300 km and smaller above

    Show answer
    (b). \(|A|^{2} = \cos^{2}\beta l + \sinh^{2}\alpha l\), and the second term is positive for every real line, so \(|A|\) is larger and the rise smaller. Most people guess (a) because loss usually makes things worse. Problem 5.
  3. MCQ 3. A shunt reactor sized to bring the open-circuit far end back to the sending voltage absorbs approximately:
    (a) 25%   (b) 50%   (c) 75%   (d) 100%   of the line's charging

    Show answer
    (b). \(B_L/bl = \tan(\beta l/2)/(\beta l) \to \tfrac12\) for a short line, and it is 50.4% at 300 km. (d) is the answer for distributed compensation, which needs \(k=1\) to null the rise — and that is Problem 8's point. Problem 6.
  4. MCQ 4. The surge impedance of a lossless line is:
    (a) inductive   (b) capacitive   (c) purely resistive   (d) proportional to length

    Show answer
    (c). \(\sqrt{L/C}\) is real even though both elements are reactive — which is what lets a resistor terminate a line without reflection. (d) is wrong for a reason worth stating: \(L\) and \(C\) are both per unit length, so the length cancels. Problem 9.
  5. MCQ 5. A 400 kV line has \(Z_s = 300\ \Omega\). Its SIL is:
    (a) 133 MW   (b) 533 MW   (c) 1333 MW   (d) 300 MW

    Show answer
    (b). \(V_{LL}^{2}/Z_s = 160\,000/300 = 533\) MW. (a) comes from using the phase voltage \((400/\sqrt3)^{2}/300\), which is the single commonest slip in this chapter — the formula already contains the factor of three. Problem 9.
  6. MCQ 6. A line with both terminals held at rated voltage and loaded below SIL:
    (a) absorbs reactive power at both ends   (b) delivers reactive power at both ends   (c) delivers at one end and absorbs at the other   (d) exchanges none

    Show answer
    (b). \(Q_R = \mathrm{SIL}(\cos\delta-\cos\beta l)/\sin\beta l > 0\) when \(\delta < \beta l\), and \(Q_S = -Q_R\) means the line pushes VAr back into the source as well. (c) describes real power, not reactive; (d) is true only at SIL exactly. Problem 13.
  7. MCQ 7. Series compensation of degree \(k\) multiplies the surge impedance loading by:
    (a) \(1-k\)   (b) \(\sqrt{1-k}\)   (c) \(1/\sqrt{1-k}\)   (d) 1

    Show answer
    (c)\(Z_s\) falls by \(\sqrt{1-k}\), so SIL rises by its reciprocal. (b) is the shunt-reactor answer, and confusing the two directions is the standard error. Problems 15 and 18.
  8. MCQ 8. Shunt reactive compensation of degree \(k\) affects the transfer capability at a fixed load angle by:
    (a) raising it by \(1/\sqrt{1-k}\)   (b) leaving it almost unchanged   (c) halving it   (d) raising it in proportion to \(k\)

    Show answer
    (b). The electrical shortening raises it and the fall in SIL lowers it; the net factor is \(m\sin\beta l/\sin(\beta l\,m) = 0.993\) at 40% on the reference line — a 0.7% loss. A shunt reactor is bought for voltage, never for capability. Problem 18.
  9. MCQ 9. In \(f_{er} = f_0\sqrt{X_C/X_L}\), the reactance \(X_L\) is:
    (a) the line reactance only   (b) the line plus the generator and transformer reactances   (c) the generator reactance only   (d) the compensated line reactance \(X_L(1-k)\)

    Show answer
    (b). The resonant loop is the whole series path. On the reference line (a) gives 31.6 Hz against the correct 22.1 Hz — an error of 9.5 Hz that reverses the safety verdict. (d) double-counts the capacitor, which already appears as \(X_C\). Problem 17.
  10. MCQ 10. Splitting a series capacitor bank into two banks of half the reactance at different points along the line:
    (a) halves \(f_{er}\)   (b) raises \(f_{er}\) by \(\sqrt2\)   (c) leaves \(f_{er}\) unchanged   (d) eliminates the resonance

    Show answer
    (c). The two capacitors are in series in the resonant loop, which therefore sees the same total \(X_C\). Splitting helps the fault duty and the platform design and does nothing at all for SSR — the commonest wrong answer in the subject. Challenge C2.
  11. MCQ 11. A tuned line, with zero regulation at every load, requires:
    (a) \(\beta l = \pi/2\)   (b) \(\beta l = n\pi\)   (c) \(Z_s = Z_R\)   (d) loading at exactly SIL

    Show answer
    (b), which makes \(B = \mathbf{C} = 0\). (a) is the quarter-wave impedance inverter, the worst possible length. (d) gives a flat profile but a 5.5% regulation, since throwing off the load returns the line to open circuit. Problems 11 and 19.
  12. MCQ 12. A line's charging reactive power equals its SIL multiplied by:
    (a) \(\beta l\) in radians   (b) \(\sin\beta l\)   (c) \(\tan\beta l\)   (d) \(Z_s\)

    Show answer
    (a), exactly: \(V^{2}bl \div V^{2}/Z_s = Z_s\omega Cl = \beta l\). (b) is the near-equal answer for a short line and drifts away above about 30°; (d) is dimensionally impossible. Problems 4 and 10.
Reference

Key Formulas

StatementRelationNotes
Ferranti rise, exact\(|V_{R,\text{NL}}|/|V_S| = 1/|\cosh\gamma l| = 1/|A|\)No approximation; use when \(A\) is given
Ferranti rise, lossless\(\sec\beta l - 1\)Right to 0.001 points on an EHV line
Ferranti rise, lumped\((\beta l)^{2}/2 = \omega^{2}LCl^{2}/2\)Always under-reads; safe to ~250 km
Effect of attenuation\(|A|^{2} = \cos^{2}\beta l + \sinh^{2}\alpha l\)Loss reduces the rise
Angle of \(A\)\(\angle A = \arctan(\tanh\alpha l\,\tan\beta l)\)Zero on a lossless line
Electrical length\(\beta l = \omega l\sqrt{LC} = l\sqrt{xb}\)\(\beta \approx \omega/v\), \(v = 0.95\)\(0.99c\)
Wavelength\(\lambda = 2\pi/\beta = v/f\)≈ 5800–5900 km at 50 Hz
Charging\(Q_{\text{ch}} = V_{LL}^{2}\,\omega Cl\), \(I_{\text{ch}} = (V_{LL}/\sqrt3)\omega Cl\)Evaluated at nominal voltage
Charging and SIL\(Q_{\text{ch}} = \mathrm{SIL}\times\beta l\)Exact identity, \(\beta l\) in radians
Nulling shunt reactor\(B_L = \tan(\beta l/2)/Z_s\), \(Q_L = \mathrm{SIL}\tan(\beta l/2)\)50.1–52% of charging for 150–600 km
Reactor from a rating\(|V_{R,\text{NL}}| = |V_S|/|A + B/(jX_L)|\)Use for a standard, non-optimal rating
Mid-line bulge with end reactors\(V_{\text{mid}}/V_{\text{end}} = \sec(\beta l/2)\)1.3% at 300 km, 7.6% at 700 km
Surge impedance\(Z_s = \sqrt{L/C}\), real250–400 Ω overhead; ~40 Ω cable
Surge impedance loading\(\mathrm{SIL} = V_{LL}^{2}/Z_s\)Line-to-line volts; the 3 is included
Line at SIL\(\mathbf{V}(x) = \mathbf{V}_Re^{j\beta x}\), \(\mathbf{I}(x) = \mathbf{I}_Re^{j\beta x}\)Flat, unity pf, \(\delta = \beta l\), no reflection
Sending voltage off SIL\(|V_S| = \sqrt{(V_R\cos\beta l)^{2}+(Z_sI_R\sin\beta l)^{2}}\)Unity power factor at the load
Loadability\(P/\mathrm{SIL} = \sin\delta/\sin\beta l\)Both ends at the same voltage
Reactive at the terminals\(Q_R = \mathrm{SIL}(\cos\delta-\cos\beta l)/\sin\beta l = -Q_S\)Zero at SIL; \(\mathrm{SIL}\tan(\beta l/2)\) at no load
Net reactive output\(Q_{\text{net}} \approx Q_{\text{ch}}\left[1-(P/\mathrm{SIL})^{2}\right]\)Good to 6% up to 1.4 SIL
Series compensation\(\beta l \to \beta l\sqrt{1-k}\), \(Z_s \to Z_s\sqrt{1-k}\), \(\mathrm{SIL} \to \mathrm{SIL}/\sqrt{1-k}\)\(k = X_C/X_L\); charging unchanged
Shunt compensation\(\beta l \to \beta l\sqrt{1-k}\), \(Z_s \to Z_s/\sqrt{1-k}\), \(\mathrm{SIL} \to \mathrm{SIL}\sqrt{1-k}\)Charging falls to \((1-k)Q_{\text{ch}}\)
Series capacitor duty\(X_C = kxl\), \(Q_C = 3I^{2}X_C\), \(V_C = IX_C\)Rating goes as \(I^{2}\); MOV protected
Subsynchronous resonance\(f_{er} = f_0\sqrt{X_C/X_{L,\text{total}}}\)\(X_{L,\text{total}}\) includes machine and transformer
Frequency seen by the shaft\(f_0 - f_{er}\)Compare with torsional modes, 15–35 Hz
Tuned line\(\beta l = n\pi \Rightarrow B = \mathbf{C} = 0,\ A = D = \pm1\)\(l = n\lambda/2 \approx 2900\) km at 50 Hz
Quarter-wave line\(Z_{\text{in}} = Z_s^{2}/Z_R\)Open inverts to short; \(\lambda/4 \approx 1450\) km
Half-wave mid-point\(|V_{\text{mid}}| = |V_R|\times P/\mathrm{SIL}\)Zero when empty; the fatal objection
Diagnostics

Common Mistakes

  1. Using the phase voltage in \(\mathrm{SIL} = V^{2}/Z_s\). The formula already contains the factor of three; putting \(V_{LL}/\sqrt3\) into it divides the answer by three and turns 533 MW into 178 MW. The most frequent single error in this chapter — MCQ 5.

  2. Believing that attenuation makes the Ferranti rise worse. It makes it very slightly better, because \(|A|^{2} = \cos^{2}\beta l + \sinh^{2}\alpha l\) and the added term is positive. The lossless estimate is therefore conservative — Problem 5.

  3. Trusting \((\beta l)^{2}/2\) beyond 300 km. It is 4% low at 300 km, 8% low at 400 km and 48% low at 1000 km, and it always under-reads — the wrong direction for an insulation check — Problem 2.

  4. Assuming a shunt reactor of \(k\) per cent of the charging removes \(k\) per cent of the rise. Placement decides the outcome: 87 MVAr at the far end nulls the rise completely, while the same 87 MVAr spread along the line leaves 2.67% — Problem 8.

  5. Reporting that the terminals are at rated voltage and stopping there. With end reactors the highest point on the line is the mid-point, at \(\sec(\beta l/2)\) times the terminal voltage — 1.3% at 300 km but 7.6% at 700 km — Problem 8.

  6. Confusing the flat profile at SIL with zero regulation. At SIL \(|V_S| = |V_R|\), but throwing off the load returns the line to open circuit, so the regulation is the full \(\sec\beta l - 1\) — Problem 11.

  7. Getting the sign of the SIL change backwards. Series compensation raises SIL (\(Z_s\) falls); shunt compensation lowers it (\(Z_s\) rises). Both shorten the line electrically by the same factor, so only the \(Z_s\) row distinguishes them — Problem 18.

  8. Computing \(f_{er}\) from the line reactance alone. \(50\sqrt{k}\) ignores the generator and transformer, which here are more than half the loop, and gives 31.6 Hz instead of 22.1 Hz — Problem 17.

  9. Believing that splitting a series bank detunes the resonance. The loop sees the total \(X_C\) wherever the capacitors sit; \(f_{er}\) does not move — Challenge C2 and MCQ 10.

  10. Sizing compensation before checking the machines. The degree that the transfer requirement demands is frequently the degree that a shaft mode forbids. Do the subsynchronous study first and the capability arithmetic second — Problem 20.

  11. Assuming an infinite source busbar when energising. A finite short-circuit level subtracts from \(A\) and raises the open-circuit voltage: 5.5% becomes 12.2% behind a 3 GVA source — Challenge C1.

  12. Quoting a cable's SIL as a design figure. With \(Z_s = 40\ \Omega\) a 132 kV cable's nominal SIL implies 1906 A, far beyond any thermal rating. For a cable the meaningful number is the length at which charging current alone consumes the rating — Problem 10.

Looking Ahead

Part 3 closes here. A line began, in Set 9, as a series impedance; it acquired a lumped shunt admittance in Set 11, a distributed one in Set 12, and a set of performance figures in Sets 13 and 14. This set read the same two-port at its two extremes — nothing on the end, and the one load that makes the line invisible — and found the Ferranti effect waiting at the first and the surge impedance loading at the second. Everything between them turned out to be one accounting question: which of \(V^{2}\omega C\) and \(I^{2}\omega L\) is larger.

The two numbers that answered every problem here, \(\beta l\) and \(Z_s\), do not appear again in Part 5 — a fault lasts a few cycles and the line is a lumped reactance for its duration. But \(Z_s\) returns in the travelling-wave and insulation-coordination chapters, where it is the impedance a lightning stroke sees, and the reactive balance of Problem 14 returns in the voltage-stability work of Part 7, where a line loaded far above SIL is the thing that collapses. For the immediate sequel, Set 14 takes the same hardware and asks what it does to regulation and efficiency, and Set 32 begins fault analysis by short-circuiting the line this set spent twenty problems keeping healthy.