Solved Problems · Set 22

Isolated Converters: Flyback, Forward and Bridge

Part 3 · DC–DC Converters — add a transformer and three limitations disappear at once. Six problems on the topologies that connect to the mains.

Prof. Mithun Mondal 6 solved problems GATE · ESE · University

Set 22 — Isolated Converters: Flyback, Forward and Bridge

Every converter so far has shared a common node between input and output. That is fatal for anything connected to the mains: a fault in a 375 V converter would put 375 V on a 12 V output, and no safety standard permits it. It also caps the achievable gain, since Set 19 showed a single stage cannot sensibly exceed about five.

A transformer answers both at once, and a third question besides. It provides a turns ratio that costs nothing in efficiency, a galvanic barrier, and as many secondaries as wanted — and it introduces two new problems of its own. The core must be reset every cycle or it saturates, and the leakage inductance that no winding avoids stores energy that has nowhere to go.

Part 3 · Chapter 14 · 6 solved problems

i Method Recap
  • The flyback is a buck–boost with a tapped inductor. Energy is stored, then released:

    \[ V_o = V_{in}\frac{N_2}{N_1}\cdot\frac{D}{1-D}, \qquad V_R = V_o\frac{N_1}{N_2}, \qquad V_S = V_{in}+V_R+\text{spike} \]
  • The forward is a buck with an isolation transformer. Energy passes straight through:

    \[ V_o = V_{in}\frac{N_2}{N_1}D, \qquad V_S = V_{in}\left(1+\frac{N_p}{N_r}\right) \]
  • The core must be reset, and the reset scheme sets the duty limit:

    \[ D_{max} = \frac{1}{1+N_r/N_p} \quad\text{— higher }D\text{ costs switch voltage} \]
  • Bridge topologies apply bipolar excitation, so no reset winding is needed and the switch sees only the input:

    \[ V_o = V_{in}\frac{N_2}{N_1}D_{eff}, \qquad V_S = V_{in}, \qquad f_{ripple} = 2f_s \]
  • Compare topologies by switch VA stress, not by component count:

    \[ \text{VA} = V_{S,max}\times I_{S,pk} \quad\text{per switch, per watt delivered} \]
  • Leakage energy must be absorbed every cycle:

    \[ P_{leak} = \tfrac12L_{lk}I_{pk}^2f_s, \qquad P_{snub} = P_{leak}\frac{V_{clamp}}{V_{clamp}-V_R} \]
Problem 1CoreA 60 W Flyback

A flyback supplies 12 V at 5 A from a universal input of 85 to 265 V AC — rectified to 120 to 375 V DC — at \(f_s = 65\) kHz with an assumed efficiency of 85%. Choose the turns ratio for a maximum duty ratio near 0.45, then find the duty range, device stresses, magnetising inductance for 40% ripple, and the output capacitor current.

ipri 1.59 A isec 10.8 A store, D release, 1−D
Never simultaneous — the transformer is an inductor with two windings, not a transformer
Solution

Choose the turns ratio. The flyback's ratio is the buck–boost's, scaled by the turns:

\[ V_o = V_{in}\frac{N_2}{N_1}\cdot\frac{D}{1-D} \;\Longrightarrow\; \frac{N_1}{N_2} = \frac{V_{in,min}}{V_o}\cdot\frac{D_{max}}{1-D_{max}} \]
\[ = \frac{120}{12}\cdot\frac{0.45}{0.55} = (10)(0.818) = 8.18 \quad\to\quad \text{use }8{:}1 \]

Why cap \(D\) near 0.45? Because the reflected voltage adds to the input at the switch, and a larger duty ratio means a larger reflection. Problem 3 shows the same trade in a forward converter, where it is a hard limit rather than a choice.

The actual duty range with 8:1:

\[ \frac{D}{1-D} = \frac{V_o}{V_{in}/8}: \qquad V_{in} = 120 \Rightarrow \frac{12}{15} = 0.8 \Rightarrow D = 0.444 \]
\[ V_{in} = 375 \Rightarrow \frac{12}{46.9} = 0.256 \Rightarrow D = 0.204 \]

Device stresses. The switch must block the input plus the reflected output:

\[ V_R = V_o\frac{N_1}{N_2} = (12)(8) = 96\ \text{V} \]
\[ V_S = V_{in,max}+V_R = 375+96 = 471\ \text{V},\ \text{plus a leakage spike} \]

The spike of Problem 6 typically adds 50 to 100 V, so a 650 V MOSFET is the usual choice — 600 V is uncomfortably tight. Note that \(V_R\) is fixed by the turns ratio alone, independent of the operating point.

The output diode sees the reverse of the same picture:

\[ V_D = V_o+\frac{V_{in,max}}{8} = 12+46.9 = 58.9\ \text{V} \quad\to\quad \text{100 V Schottky} \]

The magnetising inductance, sized at low line where the currents are worst:

\[ P_{in} = \frac{60}{0.85} = 70.6\ \text{W} \;\Longrightarrow\; I_{pri,avg} = \frac{70.6}{120} = 0.588\ \text{A} \]

That average is over the whole period; during the on-time the current is higher by \(1/D\):

\[ I_{pri,on} = \frac{0.588}{0.444} = 1.32\ \text{A}, \qquad \Delta I = 0.40(1.32) = 0.53\ \text{A} \]
\[ L_m = \frac{V_{in}D}{\Delta I\,f_s} = \frac{(120)(0.444)}{(0.53)\left(65\times10^{3}\right)} = 1.55\ \text{mH} \]
\[ I_{pk} = 1.32+0.265 = 1.59\ \text{A} \]

Now the flyback's weak point — the output capacitor. The secondary delivers current only during the off-time, so the capacitor supplies the entire load for \(DT_s\):

\[ I_{sec,avg} = \frac{I_o}{1-D} = \frac{5}{0.556} = 9.0\ \text{A} \]
\[ I_{C,rms} \approx I_o\sqrt{\frac{D}{1-D}} = 5\sqrt{0.8} = 4.47\ \text{A} \]

Four and a half amps of RMS ripple for a 5 A output — nearly one-for-one. This is the flyback's structural cost: no output inductor means the capacitor does all the filtering, and it must be several low-ESR parts in parallel. Problem 2 shows what an output inductor buys.

A flyback transformer is not a transformer. Primary and secondary never conduct together, so it stores energy rather than passing it — which is why it needs a gap, why its inductance is specified rather than its turns ratio alone, and why the whole output ripple lands on the capacitor. It is a buck–boost inductor that happens to have two windings.
Answera 8:1, \(D = 0.204\text{–}0.444\)   b\(V_S = 471\ \text{V},\ V_D = 58.9\ \text{V}\)   c\(L_m = 1.55\ \text{mH},\ I_{pk} = 1.59\ \text{A}\)   d\(I_{C,rms} = 4.47\ \text{A}\)
Problem 2CoreThe Forward Converter

The same 60 W output is produced by a forward converter with a 1:1 reset winding, limiting \(D\) to 0.45. Find the turns ratio, the duty range, the switch stress, the output inductor for 30% current ripple, and the output capacitor current. Compare with the flyback.

Solution

The forward is a buck behind a transformer, so its ratio is linear in \(D\):

\[ V_o = V_{in}\frac{N_2}{N_1}D \;\Longrightarrow\; \frac{N_2}{N_1} = \frac{12}{(120)(0.45)} = 0.222 \quad\to\quad \frac{N_1}{N_2} = 4.5 \]
\[ V_{in} = 375 \Rightarrow D = \frac{12}{(375)(0.222)} = 0.144 \]

A duty range of 0.144 to 0.45, similar to the flyback's. But note the ratio is 4.5:1 rather than 8:1 — the forward needs fewer primary turns for the same output, because it transfers during the on-time rather than storing.

The switch stress is the forward's penalty. During reset, the reset winding returns the magnetising energy to the input, and with \(N_r = N_p\) that puts the full input voltage back across the switch:

\[ V_S = V_{in}\left(1+\frac{N_p}{N_r}\right) = 2V_{in,max} = 750\ \text{V} \]

Against 471 V for the flyback. A 750 V requirement means a 900 V or 1000 V device, whose \(R_{DS(on)}\) is far worse — and that is why the single-switch forward is uncommon at universal input, and why the two-switch variant of Problem 5 exists.

The output inductor, sized at high line where the ripple is worst — the buck rule of Set 18:

\[ V_{in}\frac{N_2}{N_1} = (375)(0.222) = 83.3\ \text{V}, \qquad D = 0.144, \qquad \Delta I = 0.30(5) = 1.5\ \text{A} \]
\[ L = \frac{\left(83.3-12\right)(0.144)}{(1.5)\left(65\times10^{3}\right)} = 105\ \mu\text{H} \]

And the payoff. With an inductor feeding the output, the capacitor sees only a triangular ripple:

\[ I_{C,rms} = \frac{\Delta I}{\sqrt{12}} = \frac{1.5}{3.464} = 0.43\ \text{A} \]
\[ \frac{4.47}{0.43} = 10.3\times \text{ less than the flyback} \]

An order of magnitude. That single row is why forward converters dominate wherever output ripple or capacitor lifetime matters — and why the flyback survives only where its simplicity outweighs it.

The two compared:

PropertyFlybackForward
Turns ratio8:14.5:1
Switch voltage471 V750 V
Magneticsgapped, stores energyungapped, transfers
Output inductornone105 µH
Output cap RMS4.47 A0.43 A
Reset windingnot neededrequired
Duty limitpractical onlyhard, 0.5
Multiple outputsexcellenteach needs an inductor
Component countlowesthigher

Read the last two rows together. A flyback with three outputs needs three diodes and three capacitors; a forward needs three diodes, three inductors and three capacitors — and the flyback's cross-regulation is better, because all outputs are fed from the same collapsing flux.

Where each belongs:

\[ \text{flyback: } \lesssim 75\ \text{W, multiple outputs, cost-critical} \]
\[ \text{forward: } 50\text{–}500\ \text{W, single output, low ripple} \]

The crossover is around 75 W and it is set by the capacitor. Below that, 4.5 A of ripple current is manageable with two or three ceramics; above it, the capacitor bank costs more than the forward converter's extra inductor and reset winding.

The output inductor is what the forward converter is buying. It costs a reset winding, a duty limit and twice the switch voltage — and it reduces the output capacitor's ripple current tenfold. Whether that is a good trade depends almost entirely on the power level, because the capacitor requirement scales with output current and the reset penalty does not.
Answera 4.5:1, \(D = 0.144\text{–}0.45\)   b\(V_S = 750\ \text{V}\)   c\(L = 105\ \mu\text{H}\)   d\(I_{C,rms} = 0.43\ \text{A}\) — 10.3× better
Problem 3Exam levelResetting the Core

Derive the relationship between a forward converter's reset winding ratio, its maximum duty ratio and its switch voltage stress. Evaluate for \(N_r/N_p = 1\), 0.5 and 2, and compare with the RCD clamp and active clamp alternatives.

Solution

Why reset is mandatory. During the on-time the primary carries a magnetising current that builds flux in the core:

\[ \Delta B = \frac{V_{in}DT_s}{N_pA_e} \]

Unlike a flyback, that flux is not delivered to the secondary — the forward's secondary conducts only while the primary does, and the magnetising component is left behind. If it is not removed each cycle it accumulates, and after a few cycles the core saturates and the switch sees a short circuit.

The reset winding drives the flux back. Volt-second balance on the core requires:

\[ V_{in}DT_s = \left(V_{in}\frac{N_p}{N_r}\right)D_{reset}T_s \;\Longrightarrow\; D_{reset} = D\frac{N_r}{N_p} \]

Reset must finish before the next cycle begins:

\[ D+D_{reset} \le 1 \;\Longrightarrow\; D_{max} = \frac{1}{1+N_r/N_p} \]

And the switch pays for it. During reset the reflected reset voltage adds to the input:

\[ V_S = V_{in}\left(1+\frac{N_p}{N_r}\right) \]
\(N_r/N_p\)\(D_{max}\)\(V_S\)Verdict
20.3331.5\(V_{in}\)low stress, poor utilisation
10.5002\(V_{in}\)the standard compromise
0.50.6673\(V_{in}\)good duty, punishing stress

A clean inverse trade: whatever is gained in duty ratio is paid in switch voltage, and the product \(D_{max}\times V_S/V_{in}\) is exactly 1 in every row. There is no free choice here, only a preference.

Why 1:1 is chosen. Two practical reasons beyond the compromise:

\[ \text{(i) } N_r = N_p \Rightarrow \text{bifilar winding} \Rightarrow \text{tight coupling} \]

The reset winding must be closely coupled to the primary or its own leakage produces a spike far worse than the reset voltage itself. Winding it bifilar with the primary is easy when the turns are equal and awkward when they are not. And (ii) a 1:1 ratio means the reset winding can use the same wire gauge and the same layer, costing almost nothing.

The alternatives:

Reset method\(D_{max}\)\(V_S\)Magnetising energy
Tertiary winding 1:10.502\(V_{in}\)returned to input
RCD clamp~0.5set by clampdissipated
Resonant (\(LC\)) reset~0.51.6\(V_{in}\)returned
Active clamp> 0.5\(V_{in}/(1-D)\)returned, enables ZVS
Two-switch forward0.50\(V_{in}\)returned via clamp diodes

The last two rows are what modern designs use. A two-switch forward clamps the primary between the rail and ground with two diodes, so neither switch ever exceeds \(V_{in}\) — halving the voltage requirement at the cost of a second switch and a high-side driver. An active clamp goes further, recycling the magnetising energy into a capacitor that then provides zero-voltage switching.

Applying it to the Problem 2 design:

\[ \text{single-switch: } V_S = 750\ \text{V} \to 900\ \text{V device} \]
\[ \text{two-switch: } V_S = 375\ \text{V} \to 500\ \text{V devices} \]

Two 500 V MOSFETs cost less than one 900 V part and conduct far better, since \(R_{DS(on)}\) scales roughly as \(V_{BR}^{2.5}\). That is why the two-switch forward, not the single-switch version, is the standard 100 to 500 W topology.

Reset is a volt-second problem with an exact price. Whatever duty ratio the reset scheme permits, the switch voltage is its reciprocal — \(D_{max}V_S/V_{in} = 1\) in every tertiary-winding case. The only way out is to clamp the primary to the rail instead of reflecting it, which is what the two-switch and active-clamp topologies do.
Answera\(D_{max} = 1/(1+N_r/N_p),\ V_S = V_{in}(1+N_p/N_r)\)   b 0.333/1.5\(V_{in}\), 0.5/2\(V_{in}\), 0.667/3\(V_{in}\)   c two-switch forward gives \(V_S = V_{in}\)
Problem 4Exam levelA Kilowatt Bridge

A full-bridge converter delivers 48 V at 20.8 A (1 kW) from a 350 to 400 V DC link at \(f_s = 100\) kHz. Choose the turns ratio for an effective duty ratio near 0.8 at minimum input, find the device stresses and the output inductor, and explain why bridges dominate above 500 W.

Solution

How a bridge differs. Four switches apply \(+V_{in}\), then zero, then \(-V_{in}\), then zero — so the transformer is excited symmetrically and resets itself. No reset winding, and the output sees two pulses per switching period:

\[ V_o = V_{in}\frac{N_2}{N_1}D_{eff}, \qquad D_{eff} = 2D_{switch} \in [0,1] \]

The turns ratio, set at minimum input:

\[ \frac{N_1}{N_2} = \frac{V_{in,min}D_{eff,max}}{V_o} = \frac{(350)(0.8)}{48} = 5.83 \quad\to\quad \text{use }6{:}1 \]
\[ V_{in} = 350 \Rightarrow D_{eff} = \frac{48}{350/6} = 0.823; \qquad V_{in} = 400 \Rightarrow D_{eff} = 0.720 \]

A narrow duty range, because the input comes from a regulated PFC bus rather than a raw rectified mains. That is typical — bridges usually sit behind the boost PFC stage of Set 19, Problem 4.

The switch stress is the headline result:

\[ V_S = V_{in,max} = 400\ \text{V} \quad\to\quad \text{600 V devices} \]

Not \(2V_{in}\), as in the single-switch forward. Each switch is clamped between the rail and ground by the bridge structure itself, so no reflected voltage is added. That halving is the whole reason bridges scale.

The switch currents:

\[ I_{pri} = \frac{I_o}{N_1/N_2} = \frac{20.8}{6} = 3.47\ \text{A during conduction} \]
\[ I_{S,rms} = I_{pri}\sqrt{\frac{D_{eff}}{2}} = (3.47)\sqrt{0.36} = 2.08\ \text{A per switch} \]

Each switch conducts for only half the effective duty, since the two diagonal pairs alternate. So four devices each carry 2.08 A rather than one carrying 3.47 — and the \(I^2R\) loss splits accordingly, the same arithmetic as the interleaving of Set 18.

The output filter benefits from the doubled ripple frequency:

\[ V_{sec} = \frac{400}{6} = 66.7\ \text{V}, \qquad \Delta I = 0.20(20.8) = 4.16\ \text{A} \]
\[ L = \frac{\left(66.7-48\right)(0.720)}{(4.16)\left(2\times100\times10^{3}\right)} = 16.2\ \mu\text{H} \]

Only 16 µH for a 20 A output, because the filter sees 200 kHz rather than 100. A forward converter at the same frequency would need twice the inductance for the same ripple.

Why bridges dominate above 500 W:

AdvantageMechanism
Half the switch voltageclamped to the rail, no reflection
Half the corebipolar flux swing — full \(B\)\(H\) loop used
Current split four waysconduction loss divided
Ripple at \(2f_s\)output filter halved
No reset circuitsymmetric excitation resets itself
Phase-shift controlenables zero-voltage switching

The second row is easy to miss and is worth as much as the first. A forward converter's core operates from zero to \(B_{max}\) and back; a bridge swings from \(-B_{max}\) to \(+B_{max}\), so the same core handles twice the volt-seconds. Set 24 works that through.

What bridges cost. Four switches means four gate drives, two of them high-side:

\[ \text{4 drivers}+\text{2 bootstrap or isolated supplies}+\text{dead time on 2 legs} \]

Set 7's dead-time and bootstrap analysis applies to each leg. And the shoot-through risk is doubled — two legs, each of which can destroy the converter if both devices conduct together. At 60 W that complexity is absurd; at 1 kW it is unavoidable.

The bridge halves the switch voltage and halves the core, and both come from the same cause. Symmetric bipolar excitation clamps the primary to the rail instead of reflecting a reset voltage, and it uses the full \(B\)\(H\) loop instead of half. Four switches is the price, and above about 500 W there is nothing to discuss.
Answera 6:1, \(D_{eff} = 0.720\text{–}0.823\)   b\(V_S = 400\ \text{V},\ I_{S,rms} = 2.08\ \text{A}\)   c\(L = 16.2\ \mu\text{H}\) at \(2f_s\)
Problem 5ChallengeWhich Topology, and Why

Compare the switch VA stress of the flyback, single-switch forward and two-switch forward at 60 W from a 375 V maximum input, then build a selection guide by power level for every isolated topology met so far.

Solution

Define the figure of merit. Component count is a poor guide; what determines cost and loss is how much voltage and current each switch must handle:

\[ \text{VA} = V_{S,max}\times I_{S,pk} \]

A switch rated for high voltage and high current is expensive and lossy in both dimensions, so their product is a reasonable proxy for silicon cost — and it exposes differences that counting transistors hides.

Flyback, from Problem 1:

\[ \text{VA} = (471)(1.59) = 748 \]

Single-switch forward, from Problem 2. The primary current is the reflected output current plus a small magnetising term:

\[ I_{S} \approx I_o\frac{N_2}{N_1} = (5)(0.222) = 1.11\ \text{A} \]
\[ \text{VA} = (750)(1.11) = 833 \]

Two-switch forward, where the clamp diodes hold each switch to the rail:

\[ \text{VA} = (375)(1.11) = 417\ \text{per switch} \]
Topology\(V_S\)\(I_{S,pk}\)VA per switchSwitches
Flyback471 V1.59 A7481
Forward, 1 switch750 V1.11 A833 — worst1
Forward, 2 switch375 V1.11 A417 — best2

The single-switch forward is worse than the flyback on this measure despite being the more sophisticated topology, entirely because of the \(2V_{in}\) reset stress. Add a second switch and it becomes the best of the three by a factor of two.

The complete selection guide:

PowerTopologySwitch stressWhy
< 15 WFlyback, DCM\(V_{in}+V_R\)cheapest possible
15–75 WFlyback, CCM\(V_{in}+V_R\)multiple outputs, low count
75–200 WTwo-switch forward\(V_{in}\)output inductor, low ripple
200–500 WTwo-switch forward or half bridge\(V_{in}\)
500 W – 3 kWFull bridge\(V_{in}\)current split four ways
> 1 kW, efficiency-criticalPhase-shifted full bridge\(V_{in}\)zero-voltage switching
> 3 kWInterleaved or resonant bridge\(V_{in}\)thermal and EMI limits

Every entry above 75 W has a switch stress of exactly \(V_{in}\), and that is not a coincidence — any topology that reflects a voltage back onto its switch is uncompetitive above the point where device cost matters.

The half bridge, and why it sits where it does. Two switches apply \(\pm V_{in}/2\) to the transformer:

\[ V_S = V_{in}, \qquad I_{pri} = 2\times\text{(full bridge value for the same power)} \]

Same voltage stress as a full bridge but twice the current, because only half the input voltage reaches the transformer. So a half bridge suits mid power, where current is manageable, and a full bridge takes over when the current becomes the constraint — typically around 500 W.

Two considerations the VA figure misses:

FactorEffect
Output capacitor RMSflyback 4.47 A vs forward 0.43 A — often decisive
Gate-drive complexityhigh-side drives, isolated supplies, dead time
Multiple outputsflyback needs no extra inductors
Core utilisationbridges use the full \(B\)\(H\) loop
Control loopflyback has a right-half-plane zero; forward does not

The last row connects back to Set 19. A flyback is a buck–boost, so it inherits the right-half-plane zero and its bandwidth limit; a forward is a buck, and has neither. For a supply that must respond quickly to load steps, that alone can decide the choice.

Count VA, not transistors. The single-switch forward has the fewest switches of the two forward variants and the worst silicon requirement of all three topologies, because its reset scheme doubles the voltage. Adding a switch to clamp the primary halves the stress and halves the VA — a better converter with more parts, which is usually how power electronics works.
Answera flyback 748, 1-switch forward 833, 2-switch forward 417   b flyback < 75 W, two-switch forward to 500 W, full bridge above
Problem 6ChallengeThe Energy in the Leakage

The flyback of Problem 1 has 15 µH of primary leakage inductance. Find the leakage energy per cycle and the power it represents, design an RCD clamp for a 144 V clamp voltage, and compare the converter run in DCM instead of CCM.

Solution

Where the problem comes from. Not all the primary flux links the secondary. When the switch turns off, the magnetising current transfers to the secondary but the leakage current has nowhere to go:

\[ E_{leak} = \tfrac12L_{lk}I_{pk}^2 = \tfrac12\left(15\times10^{-6}\right)(1.59)^2 = 18.9\ \mu\text{J} \]
\[ P_{leak} = E_{leak}f_s = \left(18.9\times10^{-6}\right)\left(65\times10^{3}\right) = 1.23\ \text{W} \]

Two per cent of a 60 W output, dumped into the switch's drain node every cycle. With nowhere to go, it charges the drain capacitance to whatever voltage is needed — hundreds of volts above the 471 V of Problem 1, which is why the device would fail without a clamp.

The RCD clamp catches the drain at a chosen voltage and burns the energy in a resistor. Choose the clamp at 1.5 times the reflected voltage:

\[ V_{clamp} = 1.5V_R = 1.5(96) = 144\ \text{V} \]
\[ V_{S,total} = V_{in,max}+V_{clamp} = 375+144 = 519\ \text{V} \quad\to\quad \text{650 V device}\ \checkmark \]

The clamp dissipates more than the leakage energy alone, because while the drain is held above \(V_R\) the transformer keeps pushing current into the clamp:

\[ P_{snub} = P_{leak}\frac{V_{clamp}}{V_{clamp}-V_R} = (1.23)\frac{144}{144-96} = (1.23)(3) = 3.69\ \text{W} \]

Three times the leakage energy — 6% of the output power, wasted. And the multiplier is \(V_{clamp}/(V_{clamp}-V_R)\), which grows without bound as the clamp voltage approaches \(V_R\). Clamping tightly to protect the switch costs efficiency very rapidly.

Size the components:

\[ R = \frac{V_{clamp}^2}{P_{snub}} = \frac{144^2}{3.69} = 5.6\ \text{k}\Omega \]
\[ C = \frac{V_{clamp}}{\Delta V\,Rf_s} = \frac{144}{(14.4)\left(5620\right)\left(65\times10^{3}\right)} = 27\ \text{nF} \]

For 10% ripple on the clamp capacitor. Note that \(R\) must be rated for nearly 4 W — it is a real power component, not a signal resistor, and it is often several resistors in series to share the voltage.

The trade in clamp voltage:

\(V_{clamp}\)Multiplier\(P_{snub}\)Total \(V_S\)
120 V (1.25\(V_R\))5.06.15 W495 V
144 V (1.5\(V_R\))3.03.69 W519 V
192 V (2.0\(V_R\))2.02.46 W567 V
288 V (3.0\(V_R\))1.51.85 W663 V — too high

Efficiency wants a high clamp; the device wants a low one. The 1.5× choice is the usual compromise, and reducing the leakage inductance is a far better answer than optimising the clamp — which is a magnetics problem, addressed in Set 24.

Now compare DCM. The boundary magnetising inductance at low line and full load:

\[ L_{m,crit} = \frac{V_{in}^2D^2}{2P_{in}f_s} = \frac{(120)^2(0.444)^2}{2(70.6)\left(65\times10^{3}\right)} = 310\ \mu\text{H} \]

Choosing \(L_m = 200\ \mu\text{H}\) puts the converter firmly in DCM, where it becomes the energy pump of Set 20:

\[ I_{pk} = \sqrt{\frac{2P_{in}}{L_mf_s}} = \sqrt{\frac{141.2}{13}} = 3.30\ \text{A}, \qquad D = \frac{L_mI_{pk}f_s}{V_{in}} = 0.357 \]

What DCM costs and buys:

\[ I_{rms,DCM} = I_{pk}\sqrt{\frac{D}{3}} = 1.14\ \text{A}; \qquad I_{rms,CCM} = 0.89\ \text{A} \]
\[ \frac{P_{cond,DCM}}{P_{cond,CCM}} = \left(\frac{1.14}{0.89}\right)^2 = 1.64 \]
CCMDCM
\(L_m\)1.55 mH200 µH
Peak current1.59 A3.30 A
Conduction loss1.64×
Leakage energy18.9 µJ82 µJ — 4.3×
Diode recoverypresentnone
RHP zeropresentnone
Transformer sizelargersmaller

The fourth row is the one that decides it at this power. Leakage energy goes as \(I_{pk}^2\), so doubling the peak current quadruples the snubber loss — which would take the clamp from 3.7 W to over 15 W. DCM is excellent below about 20 W where the absolute numbers are small, and unusable at 60.

Leakage inductance is the one thing a transformer cannot be designed away from, only reduced. Its energy must be absorbed every cycle, the absorbing costs three times the energy itself, and it scales as the square of the peak current. That last dependence is why the choice between CCM and DCM in a flyback is really a choice about the snubber.
Answera\(E = 18.9\ \mu\text{J},\ P_{leak} = 1.23\ \text{W}\)   b\(P_{snub} = 3.69\ \text{W},\ R = 5.6\ \text{k}\Omega,\ C = 27\ \text{nF}\)   c DCM: 64% more conduction loss, 4.3× the leakage energy
Formulas

Key Formulas

QuantityRelationNotes
Flyback ratio\(V_o = V_{in}\dfrac{N_2}{N_1}\dfrac{D}{1-D}\)Buck–boost with turns
Reflected voltage\(V_R = V_o\dfrac{N_1}{N_2}\)Fixed by turns alone
Flyback switch\(V_S = V_{in,max}+V_R+\text{spike}\)
Flyback diode\(V_D = V_o+V_{in,max}\dfrac{N_2}{N_1}\)
Magnetising inductance\(L_m = \dfrac{V_{in}D}{\Delta I f_s}\)At low line
Flyback cap RMS\(I_o\sqrt{D/(1-D)}\)Large — the weak point
Forward ratio\(V_o = V_{in}\dfrac{N_2}{N_1}D\)Buck with turns
Forward inductor\(L = \dfrac{\left(V_{in}n-V_o\right)D}{\Delta I f_s}\)At high line
Forward cap RMS\(\Delta I/\sqrt{12}\)10× better
Reset duty limit\(D_{max} = \dfrac{1}{1+N_r/N_p}\)
Reset switch stress\(V_S = V_{in}\left(1+\dfrac{N_p}{N_r}\right)\)\(D_{max}V_S/V_{in} = 1\)
Bridge ratio\(V_o = V_{in}\dfrac{N_2}{N_1}D_{eff}\)\(V_S = V_{in}\)
Bridge switch RMS\(I_{pri}\sqrt{D_{eff}/2}\)Four-way split
Bridge filterdesigned at \(2f_s\)Halves \(L\)
Switch VA\(V_{S,max}\times I_{S,pk}\)The comparison to make
Leakage energy\(P_{leak} = \tfrac12L_{lk}I_{pk}^2f_s\)
Clamp dissipation\(P_{leak}\dfrac{V_{clamp}}{V_{clamp}-V_R}\)Diverges as clamp tightens
Clamp components\(R = V_{clamp}^2/P_{snub},\ C = \dfrac{V_{clamp}}{\Delta V Rf_s}\)Problem 6
Flyback DCM boundary\(L_{m,crit} = \dfrac{V_{in}^2D^2}{2P_{in}f_s}\)
Pitfalls

Common Mistakes

  1. Treating a flyback transformer as a transformer. The windings never conduct together; it is a gapped, two-winding inductor — Problem 1.

  2. Forgetting the reflected voltage at the switch. \(V_S = V_{in}+V_R\), plus a leakage spike — 471 V here from a 375 V input — Problem 1.

  3. Using the period-average primary current for the on-time value. Divide by \(D\) — 0.588 A becomes 1.32 — Problem 1.

  4. Underestimating a flyback's output capacitor current. 4.47 A RMS for a 5 A output — Problems 1 and 2.

  5. Sizing a forward converter's inductor at low line. Like any buck, the ripple is worst at high line — Problem 2.

  6. Forgetting that the reset winding doubles the switch voltage. 750 V from a 375 V input with a 1:1 reset — Problems 2 and 3.

  7. Choosing a reset ratio for duty ratio alone. \(D_{max}V_S/V_{in} = 1\) always — the trade is exact — Problem 3.

  8. Assuming a full bridge's switch sees \(2V_{in}\). It sees \(V_{in}\); the bridge clamps it — Problem 4.

  9. Comparing topologies by transistor count. The two-switch forward has twice the switches and half the VA stress of the single-switch version — Problem 5.

  10. Assuming the snubber only burns the leakage energy. It burns \(V_{clamp}/(V_{clamp}-V_R)\) times as much — three times here — Problem 6.

Looking Ahead

Six problems and the transformer has answered all three limitations at once. The turns ratio provided a gain of 8:1 with no efficiency ceiling, the barrier made a mains connection legal, and multiple secondaries became free. In exchange, the core needs resetting — a volt-second problem whose price is exactly \(D_{max}V_S/V_{in} = 1\) — and the leakage inductance needs a snubber that burns three times the energy it captures.

What every design in this set assumed is a controller that sets the duty ratio correctly at every input voltage and load. That controller is not a detail. The power stages of Sets 18 to 22 each have their own transfer function — a resonant double pole in a buck, a right-half-plane zero in a boost or flyback, a fourth-order pair in a Ćuk — and closing a loop around them without oscillating is a design problem of its own. Isolation makes it harder still, because the feedback must cross the same barrier the power does.

Next: Set 23 — SMPS Design and Closed-Loop Control, where the buck's small-signal model is built and compensated to a 20 kHz crossover with 59° of phase margin, current-mode control reduces the plant to first order at the cost of needing slope compensation, load-transient response is predicted two ways, and the optocoupler's gain tolerance is confronted.