Solved Problems · Set 24

Per-Unit System and Instrument Transformers

Part 3 · Transformers — choose a base and every winding, every connection and every voltage level collapses into one set of numbers; then two transformers built for measurement rather than power.

Prof. Mithun Mondal 6 solved problems GATE · ESE · University

Set 24 — Per-Unit System and Instrument Transformers

Set 23 ended with the same conversion done over and over: line to phase, phase to line, primary to secondary, ohms to percentages. The per-unit system removes all of it at once. Express every voltage, current, impedance and power as a fraction of a chosen base and the transformer disappears from the diagram: the two sides of a machine have the same per-unit impedance, a delta winding and a star winding read alike, and the percentage impedance of Sets 19 to 21 becomes simply the impedance.

The second half of the set turns to transformers whose output is a measurement rather than power. A current transformer and a potential transformer obey the same equations as any other, but the quantity of interest is no longer efficiency or regulation — it is the small error between the ratio marked on the case and the ratio actually obtained, and the small angle by which the secondary phasor fails to reproduce the primary. Both errors come from the exciting current and the winding impedance, so both are calculated with the machinery already built.

Part 3 · Three-Phase and Special Transformers · 6 solved problems

i Method Recap
  • Two bases are chosen; the rest follow. Pick a base volt-ampere for the whole system and a base voltage for one zone, then

    \[ I_{\text{base}} = \frac{S_{\text{base}}}{V_{\text{base}}}, \qquad Z_{\text{base}} = \frac{V_{\text{base}}^2}{S_{\text{base}}} \]

    Three-phase: \(I_{\text{base}} = S_{\text{base}}/(\sqrt3\,V_{L,\text{base}})\) and \(Z_{\text{base}} = V_{L,\text{base}}^2/S_{\text{base}}\), with \(S\) the three-phase total and \(V_L\) the line voltage. Both forms give the same per-unit numbers.

  • The base voltage changes at a transformer, in the ratio of its turns, and \(S_{\text{base}}\) never changes. That single rule is what makes a transformer vanish from a per-unit diagram.

  • To move an impedance from one base to another:

    \[ Z_{\text{pu,new}} = Z_{\text{pu,old}}\times\frac{S_{\text{base,new}}}{S_{\text{base,old}}}\times\left(\frac{V_{\text{base,old}}}{V_{\text{base,new}}}\right)^{\!2} \]
  • A transformer's per-unit impedance is the same from either side, because referring the ohms across the machine divides by \(a^2\) and referring the base does the same. Percentage impedance is a per-unit impedance multiplied by 100.

  • Test results read straight off as per-unit values when the test is run at rated current or rated voltage:

    \[ Z_{\text{pu}} = \frac{V_{sc}}{V_{\text{rated}}}, \qquad R_{\text{pu}} = \frac{P_{sc}}{S_{\text{rated}}}, \qquad P_{i,\text{pu}} = \frac{P_i}{S_{\text{rated}}}, \qquad I_{0,\text{pu}} = \frac{I_0}{I_{\text{rated}}} \]
  • A current transformer's error comes from the exciting current, which is the part of the primary ampere-turns that never reaches the secondary. With \(n\) secondary turns per primary turn, \(\delta\) the phase angle of the secondary burden, and \(I_\mu, I_w\) the magnetising and loss components referred to the primary:

    \[ R = n + \frac{I_\mu\sin\delta + I_w\cos\delta}{I_s}, \qquad \theta \approx \frac{I_\mu\cos\delta - I_w\sin\delta}{n\,I_s}\ \text{rad} \]

    Ratio error \(= (K_n - R)/R \times 100\%\), where \(K_n\) is the nominal ratio on the nameplate. A CT secondary must never be opened while primary current flows.

  • A potential transformer's error comes from the impedance drop taken by the burden current and the exciting current, exactly as in a voltage-regulation calculation. Referred to the secondary,

    \[ \Delta V = I_s\left(R_{02}\cos\delta + X_{02}\sin\delta\right), \qquad \theta \approx \frac{I_s\left(X_{02}\cos\delta - R_{02}\sin\delta\right)}{V_s} \]

    A PT is a small transformer worked at almost no load; its burden is quoted in VA and must be kept low. A PT secondary must never be short-circuited.

Problem 1CoreChanging the Base

A three-phase alternator is rated 25 MVA, 11 kV and has a synchronous reactance of 0.20 per unit on its own rating. A transformer at the same station is rated 50 MVA, 11/132 kV with a leakage reactance of 12%. Express, on a system base of 100 MVA:

  1. the alternator reactance with a base voltage of 11 kV, and again with a base voltage of 10.5 kV
  2. the alternator reactance in ohms, checked from both bases
  3. the transformer reactance in per unit, referred to the 11 kV side and to the 132 kV side.
Solution

Write down what a per-unit reactance actually says. "0.20 pu on 25 MVA, 11 kV" means the reactance is 0.20 of the impedance that would draw rated current at rated voltage:

\[ Z_{\text{base}} = \frac{V_{\text{base}}^2}{S_{\text{base}}} = \frac{(11\times10^3)^2}{25\times10^6} = 4.84\ \Omega \]
\[ X_s = 0.20\times4.84 = 0.968\ \Omega \]

The line-voltage form \(V_L^2/S_{3\phi}\) is used throughout; it already contains the \(\sqrt3\) factors and gives the per-phase star-equivalent ohms directly.

Change the MVA base only. Base impedance falls as \(S_{\text{base}}\) rises, so the same ohms become a larger per-unit number:

\[ X_{\text{pu}} = 0.20\times\frac{100}{25}\times\left(\frac{11}{11}\right)^{\!2} = 0.80\ \text{pu} \]

Nothing physical has changed. The machine is 20% impedant against its own rating and 80% impedant against a rating four times larger.

Change the voltage base as well. A system whose nominal voltage is taken as 10.5 kV gives

\[ X_{\text{pu}} = 0.20\times\frac{100}{25}\times\left(\frac{11}{10.5}\right)^{\!2} = 0.80\times1.0975 = 0.878\ \text{pu} \]

Check the ohms from the new base, which is the only reliable way to be sure a base change has been done correctly:

\[ Z_{\text{base}} = \frac{(10.5\times10^3)^2}{100\times10^6} = 1.1025\ \Omega, \qquad X_s = 0.878\times1.1025 = 0.968\ \Omega\;\checkmark \]

The same 0.968 Ω as before. Per-unit values move with the base; ohms do not.

The transformer, whose 12% is on 50 MVA:

\[ X_{\text{pu}} = 0.12\times\frac{100}{50} = 0.24\ \text{pu} \]

No voltage correction is needed provided the base voltages on the two sides are in the transformer's own ratio, 11 : 132. If the 11 kV zone is on an 11 kV base, the 132 kV zone must be on a 132 kV base — and then 0.24 pu is the answer looking in from either side.

Confirm that claim in ohms, since it is the whole point of the method:

Referred to\(Z_{\text{base}}\)\(X\) in ohms\(X\) in per unit
11 kV side\(11^2/100 = 1.21\ \Omega\)0.29040.24
132 kV side\(132^2/100 = 174.24\ \Omega\)41.820.24

The ohms differ by \((132/11)^2 = 144\), and so do the base impedances, so the ratio survives. This is why a per-unit single-line diagram carries no transformers at all — only impedances in series.

Two per-unit numbers can only be added if they are on the same base, and a nameplate value is always on the machine's own base. Reading 0.20 pu and 12% off two nameplates and adding them gives 0.32, which is meaningless. Converting both to 100 MVA first gives 0.80 and 0.24, which may be added — and the difference between the two answers is a factor of three.
Answer(a) 0.80 pu and 0.878 pu   (b) \(X_s = 0.968\ \Omega\) from either base   (c) 0.24 pu on both sides
Problem 2Exam levelTest Data in Per Unit

A 100 kVA, 2200/220 V, 50 Hz single-phase transformer gave the following test results:

TestExcited fromVoltageCurrentPower
Open circuitLV, HV open220 V5.0 A800 W
Short circuitHV, LV shorted92 V45.45 A1200 W

Determine

  1. the base current and base impedance on each side
  2. the equivalent resistance, reactance and impedance in per unit, and show that the same values are obtained referred to either winding
  3. the no-load current and the iron loss in per unit
  4. the regulation at full load, 0.8 power factor lagging and leading, and the full-load efficiency at 0.8 power factor — all worked in per unit.
Solution

The bases come straight from the nameplate, with \(S_{\text{base}} = 100\) kVA common to both sides:

\[ I_1 = \frac{100\times10^3}{2200} = 45.45\ \text{A}, \qquad I_2 = \frac{100\times10^3}{220} = 454.5\ \text{A} \]
\[ Z_{\text{base,HV}} = \frac{2200^2}{100\times10^3} = 48.4\ \Omega, \qquad Z_{\text{base,LV}} = \frac{220^2}{100\times10^3} = 0.484\ \Omega \]

Note that the short-circuit test was run at 45.45 A — exactly rated HV current. That is what makes the shortcuts in the next step legitimate.

Work the short-circuit test in ohms first, referred to the HV side where it was made:

\[ Z_{01} = \frac{92}{45.45} = 2.024\ \Omega, \qquad R_{01} = \frac{1200}{45.45^2} = 0.5808\ \Omega \]
\[ X_{01} = \sqrt{2.024^2 - 0.5808^2} = \sqrt{3.759} = 1.939\ \Omega \]

Divide by the base impedance:

\[ Z_{\text{pu}} = \frac{2.024}{48.4} = 0.0418, \quad R_{\text{pu}} = \frac{0.5808}{48.4} = 0.0120, \quad X_{\text{pu}} = \frac{1.939}{48.4} = 0.0401 \]

The same three numbers without touching an ohm. Because the test was at rated current, the applied voltage is the impedance drop and the input power is the full-load copper loss:

\[ Z_{\text{pu}} = \frac{V_{sc}}{V_{\text{rated}}} = \frac{92}{2200} = 0.0418\;\checkmark \]
\[ R_{\text{pu}} = \frac{P_{sc}}{S_{\text{rated}}} = \frac{1200}{100\times10^3} = 0.0120\;\checkmark \]

The second is worth dwelling on: per-unit resistance and per-unit copper loss are the same number, because \(P_{cu}/S = I^2R/(VI) = R/(V/I) = R_{\text{pu}}\) at rated current. The percentage impedance of Sets 19 to 21 is \(100Z_{\text{pu}}\), here 4.18%.

Refer the impedance to the low-voltage side and repeat. With \(a = 2200/220 = 10\):

\[ Z_{02} = \frac{Z_{01}}{a^2} = \frac{2.024}{100} = 0.02024\ \Omega, \qquad \frac{0.02024}{0.484} = 0.0418\ \text{pu}\;\checkmark \]

Referring divided the ohms by 100 and the base impedance is also 100 times smaller, so the quotient is untouched. A per-unit impedance has no side.

The open-circuit test in per unit, using the LV bases:

\[ I_{0,\text{pu}} = \frac{5.0}{454.5} = 0.0110, \qquad P_{i,\text{pu}} = \frac{800}{100\times10^3} = 0.0080 \]

1.1% exciting current and 0.8% iron loss — both immediately comparable with any other transformer of any rating, which is exactly what per unit is for.

Regulation becomes a one-line calculation. At full load the per-unit current is 1.0, so the approximate drop is just \(R\cos\phi \pm X\sin\phi\):

\[ \text{regn}_{\text{lag}} = 0.0120(0.8) + 0.0401(0.6) = 0.00960+0.02404 = 0.0336 = 3.36\% \]
\[ \text{regn}_{\text{lead}} = 0.0120(0.8) - 0.0401(0.6) = -0.0144 = -1.44\% \]

No voltages, no currents, no choice of side — and the answer is a percentage on any base.

Efficiency, likewise. Output at full load and 0.8 power factor is 0.8 pu; the losses are the two per-unit numbers already found:

\[ \eta = \frac{0.8}{0.8+0.0080+0.0120} = \frac{0.8}{0.8200} = 0.9756 = 97.56\% \]
\[ x_{\text{opt}} = \sqrt{\frac{P_{i}}{P_{cu,\text{FL}}}} = \sqrt{\frac{0.0080}{0.0120}} = 0.816 \;\Longrightarrow\; \eta_{\max} = \frac{0.816(0.8)}{0.816(0.8)+2(0.0080)} = 97.61\% \]
Per unit turns a test sheet into a machine description. Four numbers — \(R = 0.012\), \(X = 0.040\), \(P_i = 0.008\), \(I_0 = 0.011\) — contain everything Sets 18 to 20 extracted from this transformer, are independent of which winding was tested, and would look almost identical for a 10 MVA machine of the same design. That is why manufacturers publish them and why protection engineers work in nothing else.
Answer\(R = 0.0120,\ X = 0.0401,\ Z = 0.0418\ \text{pu}\) (both sides); \(I_0 = 0.011,\ P_i = 0.008\ \text{pu}\); regn 3.36% lag, −1.44% lead; \(\eta = 97.56\%\)
Problem 3Exam levelA Two-Transformer System

A small transmission scheme consists of the following, all three-phase:

ElementRatingReactance
Generator G25 MVA, 11 kV0.15 pu
Transformer T125 MVA, 11/132 kV10%
Overhead line100 Ω per phase
Transformer T220 MVA, 132/33 kV8%

Taking a base of 25 MVA and 11 kV in the generator zone, and neglecting all resistance, find

  1. the base voltage and base impedance in each of the three zones
  2. the per-unit reactance of every element and the total
  3. the short-circuit MVA and the fault current for a three-phase fault on the 33 kV busbar, and the corresponding current in the line and in the generator.
Solution

Mark out the zones. A transformer separates two zones, and the base voltage changes across it in the ratio of its nameplate voltages while \(S_{\text{base}} = 25\) MVA holds everywhere:

ZoneContains\(V_{\text{base}}\)\(Z_{\text{base}} = V_{\text{base}}^2/S_{\text{base}}\)\(I_{\text{base}} = S_{\text{base}}/\sqrt3V_{\text{base}}\)
1Generator11 kV4.84 Ω1312.2 A
2Line132 kV696.96 Ω109.35 A
333 kV busbar33 kV43.56 Ω437.4 A

The base voltages 11, 132 and 33 kV are in exactly the transformers' own ratios, which is the condition for the transformers to disappear from the per-unit diagram.

Convert each reactance to the 25 MVA base. The generator is already there; T1 is already there; T2 and the line are not:

\[ X_{T2} = 0.08\times\frac{25}{20} = 0.100\ \text{pu} \]
\[ X_{\text{line}} = \frac{100}{696.96} = 0.1435\ \text{pu} \]

The line reactance is divided by the base impedance of its own zone — 696.96 Ω, not 4.84 Ω. Using the wrong zone's base is the single commonest error in this calculation.

The elements are now in series and simply add:

\[ X_{\text{total}} = 0.15+0.10+0.1435+0.10 = 0.4935\ \text{pu} \]
ElementAs givenOn 25 MVA base
Generator0.15 pu on 25 MVA0.1500
T110% on 25 MVA0.1000
Line100 Ω0.1435
T28% on 20 MVA0.1000
Total0.4935

The fault. With 1.0 pu voltage behind the reactance and the fault a dead short:

\[ I_f = \frac{1.0}{0.4935} = 2.026\ \text{pu} \qquad\Longrightarrow\qquad \text{SC MVA} = 2.026\times25 = 50.7\ \text{MVA} \]

The short-circuit level is the base MVA divided by the per-unit reactance — a number a switchgear engineer can use directly, with no reference to voltage level at all.

Convert to amperes in each zone, using that zone's base current:

\[ I_{f,33\,\text{kV}} = 2.026\times437.4 = 886\ \text{A} \]
\[ I_{f,\text{line}} = 2.026\times109.35 = 222\ \text{A}, \qquad I_{f,\text{gen}} = 2.026\times1312.2 = 2659\ \text{A} \]

One per-unit number, three currents. As a check, 886 A at 33 kV should appear as \(886\times33/132 = 222\) A on the 132 kV side, and it does.

What the calculation would have looked like in ohms. Every impedance would have to be referred to one voltage level: the generator's \(0.15\times4.84 = 0.726\ \Omega\) becomes \(0.726\times144 = 104.5\ \Omega\) at 132 kV, T1's \(0.10\times696.96 = 69.70\ \Omega\), the line's 100 Ω, and T2's \(0.10\times696.96 = 69.70\ \Omega\) — total 343.9 Ω, giving \(76210/343.9 = 222\) A at 132 kV. The same answer, after four referrals that per unit did for free.

The per-unit diagram is a series circuit, and that is the whole gain. Three voltage levels, two transformers and four elements reduce to one number, 0.4935, from which every current at every point follows by one multiplication. The method scales: a real network with fifty branches is handled the same way, which is why every power-system program in existence works internally in per unit.
Answer\(X_{\text{total}} = 0.4935\ \text{pu}\); SC level 50.7 MVA; \(I_f = 886\ \text{A}\) at 33 kV, 222 A in the line, 2659 A at the generator
Problem 4CoreCT Burden and the Leads

A 800/5 A current transformer of rated burden 15 VA supplies an ammeter of burden 1.2 VA and the current coil of a wattmeter of burden 2.5 VA, both at rated secondary current. The instruments are 40 m from the CT and are wired with 2.5 mm² copper, resistivity 1.72 × 10−8 Ω·m. All burdens may be taken as resistive.

  1. Find the total burden imposed on the CT and say whether it is acceptable.
  2. Find the smallest standard conductor size that brings the CT within its rating.
Solution

The leads are part of the burden, and the current travels out and back, so the length that counts is twice the run:

\[ \ell = 2\times40 = 80\ \text{m}, \qquad R_{\text{lead}} = \frac{\rho\ell}{A} = \frac{1.72\times10^{-8}\times80}{2.5\times10^{-6}} = 0.550\ \Omega \]

Convert that resistance into volt-amperes at rated secondary current, which is how CT burdens are always quoted:

\[ \text{VA}_{\text{lead}} = I_s^2R_{\text{lead}} = 5^2\times0.550 = 13.76\ \text{VA} \]

The 5 A squared is what makes CT leads so expensive. The same run on a 1 A CT would impose \(1^2\times0.550 = 0.55\) VA, twenty-five times less — which is the entire reason 1 A secondaries are used where cable runs are long.

Add the instruments:

\[ \text{VA}_{\text{total}} = 1.2 + 2.5 + 13.76 = 17.46\ \text{VA} \;>\; 15\ \text{VA} \]

The CT is over-burdened by 16%. Beyond its rated burden a CT's exciting current rises sharply, its ratio and phase errors leave the accuracy class, and under fault conditions the core saturates and the secondary current collapses just when the protection needs it.

Work backwards for the conductor. The instruments are fixed, so the leads may take only

\[ \text{VA}_{\text{lead,max}} = 15 - 3.7 = 11.3\ \text{VA} \qquad\Longrightarrow\qquad R_{\max} = \frac{11.3}{25} = 0.452\ \Omega \]
\[ A_{\min} = \frac{\rho\ell}{R_{\max}} = \frac{1.72\times10^{-8}\times80}{0.452} = 3.04\ \text{mm}^2 \]

Choose the next standard size, 4 mm², and confirm:

Conductor\(R_{\text{lead}}\)Lead VATotal VAVerdict
2.5 mm²0.550 Ω13.7617.46Over-burdened
4 mm²0.344 Ω8.6012.30Acceptable
6 mm²0.229 Ω5.739.43Comfortable

4 mm² leaves 18% margin, which is sensible practice because a wattmeter may later be replaced by a transducer of higher burden.

The same burden as an impedance, which is the form Problem 5 needs:

\[ Z_{\text{burden}} = \frac{\text{VA}}{I_s^2} = \frac{12.30}{25} = 0.492\ \Omega \qquad\text{against a rated }\frac{15}{25} = 0.60\ \Omega \]

Taking all three burdens as resistive lets them be added arithmetically. If the instruments were quoted at a power factor, the impedances would have to be added as phasors and the total would be a little smaller.

On a 5 A CT the cable usually is the burden. Here the two instruments together account for 3.7 VA and the wiring for 13.8 VA — four times as much. Any discussion of CT accuracy that starts with the instruments has started in the wrong place; the first question is always how far away they are and in what cross-section.
Answer(a) 17.46 VA, exceeding the 15 VA rating   (b) 4 mm² leads, giving 12.30 VA
Problem 5Exam levelCT Ratio and Phase-Angle Error

A 500/5 A current transformer has a single primary turn and 100 secondary turns, so its nominal ratio is 100. With rated primary current flowing, the exciting current referred to the primary has a magnetising component \(I_\mu = 3.0\) A and a loss component \(I_w = 1.2\) A. The total secondary burden has a phase angle of 30° lagging.

  1. Find the actual ratio, the ratio error and the secondary current when 500 A flows in the primary.
  2. Find the phase-angle error in minutes.
  3. Repeat the ratio error and phase angle for a purely resistive burden and comment.
  4. Find the number of secondary turns that would make the ratio error zero at this loading.
Solution

Where the error comes from. The primary ampere-turns are used for two things: driving the secondary current and magnetising the core. Only the first reaches the meter, so

\[ \mathbf{I}_p = n\mathbf{I}_s + \mathbf{I}_0 \]

Resolving \(\mathbf{I}_0\) along and across the reversed secondary current, and keeping only the component that lies along \(\mathbf{I}_p\), gives the actual ratio; the component across it gives the phase angle.

The actual ratio. With the burden at \(\delta = 30^\circ\) and the secondary current at its nominal 5 A:

\[ R = n + \frac{I_\mu\sin\delta + I_w\cos\delta}{I_s} = 100 + \frac{3.0(0.5)+1.2(0.8660)}{5} \]
\[ = 100 + \frac{1.500+1.039}{5} = 100 + 0.508 = 100.51 \]

The turns ratio is 100; the current ratio is 100.51. The extra half is the exciting current, which the primary must supply and the secondary never sees.

Ratio error and the actual secondary current:

\[ \varepsilon = \frac{K_n - R}{R}\times100 = \frac{100-100.51}{100.51}\times100 = -0.51\% \]
\[ I_s = \frac{I_p}{R} = \frac{500}{100.51} = 4.975\ \text{A} \]

An ammeter scaled 0–500 A would read \(100\times4.975 = 497.5\) A when 500 A is flowing. A CT always reads low, because the error term is always added to \(n\).

The phase angle, in radians and then in the minutes that instrument specifications use:

\[ \theta = \frac{I_\mu\cos\delta - I_w\sin\delta}{n\,I_s} = \frac{3.0(0.8660)-1.2(0.5)}{100\times5} = \frac{1.998}{500} = 0.003996\ \text{rad} \]
\[ \theta = 0.229^\circ = 13.7\ \text{minutes} \]

Positive, meaning the reversed secondary current leads the primary current. For an ammeter this is irrelevant; for the current coil of a wattmeter or a directional relay it is the error that matters, since 13.7 minutes of angle at a power factor of 0.1 shifts the reading by about 4%.

Now a purely resistive burden, \(\delta = 0\):

\[ R = 100 + \frac{0 + 1.2}{5} = 100.24, \qquad \varepsilon = \frac{100-100.24}{100.24}\times100 = -0.24\% \]
\[ \theta = \frac{3.0 - 0}{500} = 0.00600\ \text{rad} = 20.6\ \text{minutes} \]
Burden angle \(\delta\)Actual ratioRatio errorPhase angle
0° (resistive)100.24−0.24%20.6 min
30° (inductive)100.51−0.51%13.7 min

The burden's power factor trades one error against the other: making the burden more inductive worsens the ratio and improves the angle. This is why a CT's accuracy class is always quoted with a stated burden and burden power factor.

Turns compensation. Since the exciting current adds 0.508 to the ratio, removing 0.508 from the turns cancels it:

\[ n = 100 - 0.508 = 99.5 \qquad\Longrightarrow\qquad R = 99.5+0.508 = 100.01 \]

This is genuine practice — CTs are routinely wound with fewer secondary turns than the nominal ratio suggests. On a 100-turn secondary a whole turn is 1% of the ratio, so the correction here is coarser than the error; on a 1000-turn winding it is precise. The compensation is also exact at only one burden and one current, which is why the class limits still apply everywhere else.

Both CT errors are the exciting current seen from two directions, and both are reduced the same way. Anything that lowers \(I_\mu\) and \(I_w\) — a better core material, a larger core area, a lower flux density, and above all a lower burden — improves the ratio error and the phase angle together. That is why Problem 4's cable question is not a separate matter from this one: halving the burden roughly halves both errors.
Answer(a) \(R = 100.51\), error −0.51%, \(I_s = 4.975\ \text{A}\)   (b) \(\theta = 13.7'\)   (c) −0.24% and 20.6′   (d) 99.5 turns
Problem 6Exam levelPT Burden and Ratio Error

A single-phase potential transformer is rated 11000/110 V and is wound with a turns ratio of exactly 100. Referred to the secondary, its total equivalent resistance and reactance are \(R_{02} = 0.6\) Ω and \(X_{02} = 1.2\) Ω, of which the primary winding contributes half of each. The exciting current referred to the secondary is 0.06 A at a power factor of 0.174 lagging. The secondary carries a burden of 50 VA at 0.8 power factor lagging.

  1. Find the ratio error and the phase-angle error at this burden.
  2. Find the secondary voltage when the primary is exactly 11000 V.
  3. Find the errors at zero burden, and state whether the transformer meets accuracy class 0.5 (±0.5% and ±20 minutes).
Solution

A PT is a transformer running at almost no load, so its error is nothing but its voltage regulation — the drop taken by the burden current in the winding impedance. Start with that current:

\[ I_s = \frac{50}{110} = 0.4545\ \text{A} \qquad\text{at}\qquad \delta = \cos^{-1}0.8 = 36.87^\circ\ \text{lagging} \]

The in-phase drop is what shifts the ratio, exactly as in a regulation calculation:

\[ \Delta V_b = I_s\left(R_{02}\cos\delta + X_{02}\sin\delta\right) = 0.4545\left(0.6(0.8)+1.2(0.6)\right) \]
\[ = 0.4545\times1.200 = 0.5455\ \text{V} \]

The quadrature drop is what turns the secondary phasor:

\[ \theta_b = \frac{I_s\left(X_{02}\cos\delta - R_{02}\sin\delta\right)}{V_s} = \frac{0.4545\left(1.2(0.8)-0.6(0.6)\right)}{110} \]
\[ = \frac{0.4545\times0.600}{110} = 0.002479\ \text{rad} = 8.52\ \text{minutes} \]

The exciting current contributes as well, because it flows through the primary winding whether a burden is connected or not. Only the primary half of the impedance is involved, and the exciting current is nearly in quadrature with the voltage:

\[ \cos\phi_0 = 0.174 \;\Rightarrow\; \phi_0 = 80^\circ, \qquad R_{p} = 0.3\ \Omega, \quad X_{p} = 0.6\ \Omega \]
\[ \Delta V_0 = 0.06\left(0.3(0.174)+0.6(0.985)\right) = 0.06\times0.643 = 0.0386\ \text{V} \]
\[ \theta_0 = \frac{0.06\left(0.6(0.174)-0.3(0.985)\right)}{110} = \frac{-0.01147}{110} = -0.36\ \text{minutes} \]

Small, but not zero — and it is the reason a PT has an error even with nothing connected to it.

Combine and form the actual ratio. The primary must exceed \(n\) times the secondary by the total drop:

\[ \Delta V = 0.5455+0.0386 = 0.5841\ \text{V} \]
\[ R = n\,\frac{V_s+\Delta V}{V_s} = 100\times\frac{110.584}{110} = 100.53 \]
\[ \varepsilon = \frac{K_n-R}{R}\times100 = \frac{100-100.53}{100.53}\times100 = -0.53\% \]

Negative again, and for the same reason as the CT: the instrument reads low, because part of what the primary supplies is lost inside the transformer.

The secondary voltage at exactly 11000 V primary:

\[ V_s = \frac{11000}{100.53} = 109.42\ \text{V} \]

A voltmeter scaled \(\times100\) would read 10942 V — 58 V low on 11 kV.

Phase angle and the zero-burden case. Adding the two contributions:

\[ \theta = 8.52 - 0.36 = 8.16\ \text{minutes} \]
BurdenRatio errorPhase angleClass 0.5?
Zero−0.035%−0.36 minYes
50 VA at 0.8 lag−0.53%8.16 minNo — ratio just outside

The phase angle is comfortably inside the 20-minute limit, but the ratio error of −0.53% just breaks the ±0.5% limit. The transformer is a class 1.0 unit at this burden. Reducing the burden to about 45 VA, or improving its power factor, would bring it back into class 0.5 — which is why a PT's class is meaningless unless the burden is quoted with it.

The two instrument transformers fail in opposite ways, and for opposite reasons. A CT works into a near short circuit, so its error is set by the exciting current it must steal, and is worst when the burden is large. A PT works into a near open circuit, so its error is set by the drop the burden current causes, and is also worst when the burden is large — but it approaches perfection as the burden vanishes, which a CT never does. Hence the two rules that matter in a substation: never open a CT secondary, never short a PT secondary.
Answer(a) −0.53% and 8.16′   (b) \(V_s = 109.42\ \text{V}\)   (c) −0.035% and −0.36′ at zero burden; fails class 0.5 on ratio at 50 VA
Formulas

Key Formulas

QuantityRelationNotes
Base current\(I_{\text{base}} = \dfrac{S_{\text{base}}}{V_{\text{base}}}\), three-phase \(\dfrac{S_{\text{base}}}{\sqrt3V_{L,\text{base}}}\)Problems 2, 3
Base impedance\(Z_{\text{base}} = \dfrac{V_{\text{base}}^2}{S_{\text{base}}}\)Line voltage and three-phase MVA — Problems 1, 3
Base change\(Z_{\text{pu,new}} = Z_{\text{pu,old}}\dfrac{S_{\text{new}}}{S_{\text{old}}}\left(\dfrac{V_{\text{old}}}{V_{\text{new}}}\right)^{2}\)Problems 1, 3
Per-unit from SC test\(Z_{\text{pu}} = \dfrac{V_{sc}}{V_{\text{rated}}},\quad R_{\text{pu}} = \dfrac{P_{sc}}{S_{\text{rated}}}\)Test at rated current — Problem 2
Per-unit from OC test\(I_{0,\text{pu}} = \dfrac{I_0}{I_{\text{rated}}},\quad P_{i,\text{pu}} = \dfrac{P_i}{S_{\text{rated}}}\)Problem 2
Regulation in per unit\(\text{regn} = x\left(R_{\text{pu}}\cos\phi \pm X_{\text{pu}}\sin\phi\right)\)+ lag, − lead — Problem 2
Efficiency in per unit\(\eta = \dfrac{x\cos\phi}{x\cos\phi + P_{i,\text{pu}} + x^2R_{\text{pu}}}\)Problem 2
Short-circuit level\(\text{SC MVA} = \dfrac{S_{\text{base}}}{X_{\text{pu}}},\quad I_f = \dfrac{I_{\text{base}}}{X_{\text{pu}}}\)1.0 pu prefault voltage — Problem 3
CT burden\(\text{VA} = I_s^2Z_b\), leads \(R = \rho\ell/A\) with \(\ell = 2\times\)runProblem 4
CT actual ratio\(R = n + \dfrac{I_\mu\sin\delta + I_w\cos\delta}{I_s}\)Problem 5
CT phase angle\(\theta = \dfrac{I_\mu\cos\delta - I_w\sin\delta}{n I_s}\) rad1 rad = 3438 minutes — Problem 5
Ratio error\(\varepsilon = \dfrac{K_n - R}{R}\times100\%\)Negative means reading low — Problems 5, 6
PT ratio drop\(\Delta V = I_s(R_{02}\cos\delta + X_{02}\sin\delta)\)Plus the exciting-current term — Problem 6
PT phase angle\(\theta = \dfrac{I_s(X_{02}\cos\delta - R_{02}\sin\delta)}{V_s}\) radProblem 6
Pitfalls

Common Mistakes

  1. Adding per-unit values taken from different nameplates. 0.15 pu on 25 MVA and 8% on 20 MVA are not comparable until both are on one base — the 8% becomes 0.10 pu — Problems 1 and 3.

  2. Inverting the voltage ratio in the base-change formula. The old base voltage goes on top: \((V_{\text{old}}/V_{\text{new}})^2\). Getting it upside down turns 0.878 pu into 0.729 pu — Problem 1.

  3. Dividing a line's ohms by the wrong zone's base impedance. The 100 Ω line in Problem 3 must be divided by 696.96 Ω, not by 4.84 Ω; the error is a factor of 144.

  4. Using \(V_{ph}^2/S_{1\phi}\) and \(V_L^2/S_{3\phi}\) in the same calculation. Either is correct on its own and both give the same per-unit numbers, but mixing them introduces a factor of three — Problem 3.

  5. Believing a per-unit impedance changes when it is referred across a transformer. The ohms change by \(a^2\) and the base changes by \(a^2\); 0.0418 pu is the answer on both sides — Problem 2.

  6. Taking \(R_{\text{pu}} = P_{sc}/S\) when the short-circuit test was not at rated current. The shortcut needs \(I = I_{\text{rated}}\); otherwise scale by \((I_{\text{rated}}/I_{sc})^2\) — Problem 2.

  7. Counting the one-way length of the CT leads. The current goes out and comes back, so 40 m of run is 80 m of conductor and 0.550 Ω, not 0.275 Ω — Problem 4.

  8. Adding CT burdens in ohms instead of volt-amperes, or the reverse, without squaring the current. A burden of 0.55 Ω is 13.76 VA on a 5 A CT and 0.55 VA on a 1 A CT — Problem 4.

  9. Swapping the sine and cosine in the CT error formulas. The ratio error takes \(I_\mu\sin\delta + I_w\cos\delta\) and the phase angle \(I_\mu\cos\delta - I_w\sin\delta\); interchanging them makes the resistive-burden case wrong by a factor of two and a half — Problem 5.

  10. Quoting a phase-angle error in degrees when the class limit is in minutes. 0.229° is 13.7 minutes, not 13.7 degrees, and the difference decides whether a CT passes — Problems 5 and 6.

  11. Quoting an accuracy class without a burden. The PT of Problem 6 is class 0.5 at zero burden and class 1.0 at 50 VA; the class alone says nothing.

  12. Assuming a PT's error vanishes because it draws almost no current. Even at zero burden the exciting current flows in the primary impedance, leaving −0.035% and −0.36 minutes — Problem 6.

Looking Ahead

Per unit has closed the transformer chapters by removing the thing that made them laborious. The \(\sqrt3\) factors of Set 23, the referrals of Set 17, the percentages of Sets 19 to 21 and the base changes of a fault study are all one operation, done once at the start; and the test results of Set 18, expressed in per unit, describe a machine rather than a specimen. The instrument transformers then showed the same equations doing a different job: a CT's ratio error is its exciting current, and a PT's ratio error is its regulation.

The transformer has been a machine with no moving parts, in which the primary and secondary frequencies are necessarily equal. Cut the magnetic circuit with an air gap, let the secondary rotate, and the secondary frequency becomes whatever the relative motion makes it. Everything built so far — referred impedances, equivalent circuits, no-load and short-circuit tests — carries straight across, with slip as the one new quantity.

Next: Set 25 — Induction Motor Fundamentals, where synchronous speed, slip, rotor frequency and rotor emf are established and the rotating transformer begins.