A 3-phase, 500 kVA, 6000V/400V, 50Hz, delta-star connected
transformer is delivering 300 kW, at 0.8 pf lagging to a balanced
3-phase load connected to the LV side with HV side supplied from 6000 V,
3- phase supply. Calculate the line and winding currents in both the
sides. Assume the transformer to be ideal.
Solution-1
Note: it is not a bank of single phase transformers.
It is a single unit of 3−ϕ3−ϕ transformer with 500 kVA, 6000
V/400 V, 50Hz, Δ/YΔ/Y
connection
500 kVA represents total kVA & voltages specified are always
line to line.
Similarly unless otherwise specified, kW rating of a 3−ϕ3−ϕ load is the total kW absorbed by
the load.
Load KVA,S=Pcosθ=3000.8=375kVA=input
kVALine current drawn by load,I2L=S√3VLL=375×1000√3×400=541.3AHV side line current,I1L=375×1000√3×6000=36.1ALV Star-connectionI2P=I2L=541.3AHV delta-connected,I1P=I1L√3=36.1√3=20.84ALoad KVA,S=Pcosθ=3000.8=375kVA=input kVALine current drawn by load,I2L=S√3VLL=375×1000√3×400=541.3AHV side line current,I1L=375×1000√3×6000=36.1ALV Star-connectionI2P=I2L=541.3AHV delta-connected,I1P=I1L√3=36.1√3=20.84A
Problem-2
A 3-phase, 50Hz transformer has a delta-connected primary and star
connected secondary, the line voltage being 22,000 V and 400 V
respectively. The secondary has a star connected balanced load at 0.8
power factor lagging. The line current on the primary side is 5 A.
Determine the current in each coil of the primary and in each secondary
line. What is the output of the transformer in kW?
Solution-2
Note: In 3-phase T/F, the phase transformation ratio is equal to
the turn ratio but the terminal or line voltages depends upon the
connection employed
Phase voltage on primary side=22,000V Phase voltage on secondary side=400/√3K=400/22,000×√3=1/55√3Primary phase current=5/√3ASecondary phase current=5√3÷155√3=275A Secondary line current =275A Output =√3VLILcosϕ=√3×400×275×0.8=15.24kWPhase voltage on primary side=22,000V Phase voltage on secondary side=400/√3K=400/22,000×√3=1/55√3Primary phase current=5/√3ASecondary phase current=5√3÷155√3=275A Secondary line current =275A Output =√3VLILcosϕ=√3×400×275×0.8=15.24kW
Problem-3
A 500-KVA, 3-phase, 50-Hz transformer has a voltage ratio (line
voltages) of 33/11-KV and is delta/star connected. The resistance per
phase are: high voltage 35 ΩΩ,
low voltage 0.876 ΩΩ and the
iron loss is 3050 W. calculate the value of efficiency at full-load and
one-half of full-load respectively
A 3-phase transformer 33/6.6-KV, delta-star, 2 MVA has a primary
resistance of 8 Ω per phase
and a secondary resistance of 0.08 ohm per phase. The percentage
impedance is 7%. Calculate the secondary voltage with rated primary
voltage and hence the regulation for full-load 0.75 p.f. lagging
conditions.
Solution-4
F.L.I2=2×106√3×6.6×103=175AK=6.6/√3×33=1/8.65R02=0.08+8/8.652=0.1867Ωper phaseZ02drop per phase=7100×6,600√3=266.7VZ02=266.7/175=1.523Ωper phaseX02=√Z202−R202=√1.5232−0.18672=1.51Ω/phase
Drop per phase=I2(R02cosϕ+X02sinϕ)=175(0.1867×0.75+1.51×0.66)=200VE2per-phase=6,600/√3=3,810VV2=3,810−200=3,610VV2L=3,610×√3=6,250V%regn.=200×100/3,810=5.23%
Problem-5
A 5000 KVA, 3-phase transformer, 6.6/33-KV, delta-star has a no-load
loss of 15 KW and a full-load loss of 50 KW. The impedance drop at
full-load is 7%. Calculate the primary voltage when a load of 3200 KW at
0.8 pf is delivered at 33 KV.
Solution-5
Full-loadI2=5×106/√3×33,000=87.5AImpedance drop/phase=7% of (33/√3)=7% of 19kV=1,330VZ02=1.330/87.5=15.3Ω /phaseF.L. Cu loss =50−15=35kW3I2R02=35,000R02=35,000/3×8.752=1.53Ω /phase X02=√15.32−1.532=15.23Ω
When load is3,200kWat 0.8
p.fI2=3,200/√3×33×0.8=70Adrop=70(1.53×0.8+15.23×0.6)=725V/ phase % regn. =725×10019,000=3.8%Primary voltage will have to be increased by3.8%Primary voltage=6.6+3.8% of 6.6=6.85kV=6.850V