A 3-phase, 500 kVA, 6000V/400V, 50Hz, delta-star connected
transformer is delivering 300 kW, at 0.8 pf lagging to a balanced
3-phase load connected to the LV side with HV side supplied from 6000 V,
3- phase supply. Calculate the line and winding currents in both the
sides. Assume the transformer to be ideal.
Solution-1
Note: it is not a bank of single phase transformers.
It is a single unit of \(3-\phi\) transformer with 500 kVA, 6000
V/400 V, 50Hz, \(\Delta/Y\)
connection
500 kVA represents total kVA & voltages specified are always
line to line.
Similarly unless otherwise specified, kW rating of a \(3-\phi\) load is the total kW absorbed by
the load.
\[\begin{aligned}
\text{Load KVA,}S &
=\dfrac{P}{\cos\theta}=\dfrac{300}{0.8}=375\mathrm{kVA}=\text{input
kVA}\\
\text{Line current drawn by load,}I_{2L} &
=\dfrac{S}{\sqrt{3}V_{LL}}=\dfrac{375\times1000}{\sqrt{3}\times400}=541.3\mathrm{A}\\
\text{HV side line current,}I_{1L} &
=\dfrac{375\times1000}{\sqrt{3}\times6000}=36.1\mathrm{A}\\
\text{LV Star-connection}I_{2P} & =I_{2L}=541.3\mathrm{A}\\
\text{HV delta-connected,}I_{1P} &
=\dfrac{I_{1L}}{\sqrt{3}}=\dfrac{36.1}{\sqrt{3}}=20.84\mathrm{A}
\end{aligned}\]
Problem-2
A 3-phase, 50Hz transformer has a delta-connected primary and star
connected secondary, the line voltage being 22,000 V and 400 V
respectively. The secondary has a star connected balanced load at 0.8
power factor lagging. The line current on the primary side is 5 A.
Determine the current in each coil of the primary and in each secondary
line. What is the output of the transformer in kW?
Solution-2
Note: In 3-phase T/F, the phase transformation ratio is equal to
the turn ratio but the terminal or line voltages depends upon the
connection employed
A 500-KVA, 3-phase, 50-Hz transformer has a voltage ratio (line
voltages) of 33/11-KV and is delta/star connected. The resistance per
phase are: high voltage 35 \(\Omega\),
low voltage 0.876 \(\Omega\) and the
iron loss is 3050 W. calculate the value of efficiency at full-load and
one-half of full-load respectively
A 3-phase transformer 33/6.6-KV, delta-star, 2 MVA has a primary
resistance of 8 \(\Omega\) per phase
and a secondary resistance of 0.08 ohm per phase. The percentage
impedance is 7%. Calculate the secondary voltage with rated primary
voltage and hence the regulation for full-load 0.75 p.f. lagging
conditions.
A 5000 KVA, 3-phase transformer, 6.6/33-KV, delta-star has a no-load
loss of 15 KW and a full-load loss of 50 KW. The impedance drop at
full-load is 7%. Calculate the primary voltage when a load of 3200 KW at
0.8 pf is delivered at 33 KV.