By the end of this chapter you should be able to:
Give the reasons that necessitate parallel operation.
State the four conditions and say which are absolute.
Write and solve the circuit equations for two paralleled transformers.
Identify the two components of each transformer's current.
Compute the circulating current from unequal ratios and its effects.
Show that with equal ratios the currents divide inversely as the impedances.
Compute the kVA carried by each machine.
State the condition for correct sharing and compute the capacity lost when it fails.
Why Transformers Are Paralleled
Parallel operation means two or more transformers are connected to the same supply bus bars on the primary side and to a common bus bar or load on the secondary side.
Non-availability of a single large transformer to meet the total load requirement.
Increase in power demand, leading to augmentation of the installed capacity.
Improved reliability. Even if there is a fault in one transformer, or it is taken out for maintenance, the load can continue to be serviced.
Transportation problems limit the installation of large transformers at site; it is easier to transport smaller ones and work them in parallel.
The reliability argument is usually decisive. A substation with two half-size units can be maintained without interrupting supply, whereas one full-size unit cannot — and the capital cost penalty is modest.
The Arrangement and Notation

| Symbol | Meaning |
|---|---|
| \(a_1, a_2\) | Turns ratios of the two transformers |
| \(Z_A, Z_B\) | Equivalent impedances referred to the secondary |
| \(Z_L, V_L, I_L\) | Secondary load impedance, voltage and current |
| \(I_A, I_B\) | Currents supplied to the load by each secondary |
Everything is referred to the secondary side, since that is where the two machines meet. The no-load secondary EMFs are then \(E_A = V_1/a_1\) and \(E_B = V_1/a_2\), both driven by the same primary voltage.
Conditions for Parallel Operation
For transformers sharing a common load:
- The voltage ratio must be the same.
- The per-unit impedance of each machine on its own base must be the same.
- The polarity must be the same, so that there is no circulating current between the transformers.
- The phase sequence must be the same, and no phase difference must exist between the voltages of the two transformers.
| Condition | If violated | Severity |
|---|---|---|
| Polarity | The two EMFs add round the secondary loop — a dead short circuit through both machines | Absolute |
| Phase sequence | Same, for three-phase banks | Absolute |
| Voltage ratio | A circulating current flows even at no load | Serious |
| Per-unit impedance | Load divides unequally; the bank loses capacity | Desirable |
The first two must be exactly right or the transformers must not be connected at all. The last two admit small departures — a fraction of a percent in ratio, or a few percent in impedance, is normal practice.
Condition 3 is the same check as Chapter 47's polarity test, and for the same reason. Condition 4 concerns three-phase transformers and their vector groups, which Part 3 takes up later; for single-phase units it reduces to getting the polarity right.
The Circuit Equations
Three equations describe the arrangement completely: one node equation and two loop equations.
Solving (2) and (3) for \(I_A\): equating the two expressions for \(V_L\) gives
There are two components in the current. The first represents the transformer's share of the load current; the second is the circulating current in the secondary winding.
Note the signs: the circulating component adds to the machine with the higher EMF and subtracts from the other, so it cancels in the sum and \(I_A + I_B = I_L\) as it must.
Unequal Ratios and Circulating Current
Setting the load to zero leaves only the second component, which therefore exists whether or not any load is connected.
Increase in copper loss. The current flows continuously, wasting \(I_c^{2}\left(R_A + R_B\right)\) day and night.
It overloads one transformer and reduces the permissible load kVA of the bank, because the machine with the higher EMF reaches its rated current sooner.
To eliminate the circulating current, the voltage ratio must be identical, that is \(a_1 = a_2\).
Note how small a difference suffices. The impedances are only a few percent, so their sum is small, and a ratio mismatch of even 1 % can drive a circulating current of several percent of rated. This is why the taps of paralleled transformers must be matched, not merely their nameplate ratios.
Problem. Two transformers on the same bus have no-load secondary EMFs of 240 V and 236 V, and equivalent impedances referred to the secondary of \(Z_A = 0.10 + j0.30~\Omega\) and \(Z_B = 0.08 + j0.32~\Omega\). Find the circulating current at no load and the power it wastes. Rated secondary current is 200 A for each.
Sum of the impedances.
Circulating current.
As a fraction of rated.
Power wasted.
Comment. A ratio mismatch of only \(4/240 = 1.67\,\%\) produces a circulating current of 3.1 % of rated — nearly twice the mismatch, because the impedances that oppose it are themselves only a few percent.
The 6.91 W looks trivial, but it flows for all 8760 hours of the year, and it is present at no load when the transformer should be drawing almost nothing. More importantly, the same 6.2 A adds to whatever load current transformer A carries, so A reaches its rated 200 A while B is still short of it — which is the effect that actually costs capacity.
Note also the angle. \(I_c\) lags by 73.8°, the impedance angle, so it is almost purely reactive — it circulates volt-amperes between the machines while transferring almost no power.
Equal Ratios and Load Sharing
With \(a_1 = a_2\) the circulating term vanishes and only the sharing term remains:
Thus the transformer currents are inversely proportional to their impedances — the machine with the lower impedance takes the larger share.
This is simply the current-divider rule. Two impedances across the same pair of terminals, driven by the same EMF, must divide the current this way.
The condition \(a_1 = a_2\) is easier to state than to achieve, since the ratio depends on the tap position as well as the nameplate. In practice both machines are set to the same tap, and the residual mismatch is accepted.
Problem. The transformers of Example 49.1 now supply a common load drawing 200 A at 0.8 lagging. Find each transformer's current, and verify the sum.
Sharing components. With \(\mathbf{I}_L = 200\angle-36.87^{\circ}\) A:
Adding the circulating component \(\mathbf{I}_c = 6.196\angle-73.81^{\circ}\):
Check.
Comment. The circulating current has pushed A up to 107.1 A and pulled B down to 92.9 A — a spread of 14.1 A on a 200 A load, where the impedances alone would have given 102.2 and 98.0.
Note that the magnitudes here happen to sum to exactly 200 A, because all three currents lie at nearly the same angle. That is a coincidence of this data, not a general rule — currents must be added as phasors, and in general \(\left|I_A\right| + \left|I_B\right| \gt \left|I_L\right|\).
The Volt-Amperes Shared
Multiplying each current by the common load voltage converts the sharing rule into kVA.
Problem. Transformer A is 200 kVA with 4 % impedance; transformer B is 300 kVA with 5 %. They share a 400 kVA load. Find the kVA each carries, and the maximum load the bank can supply.
Refer both impedances to a common base of 100 kVA. Since percentage impedance scales directly with the base kVA:
These common-base values are proportional to the ohmic impedances, which is what the sharing formula needs.
Sharing.
Loading of each.
Maximum bank output. A reaches its 200 kVA rating when
Comment. The installed capacity is 500 kVA but the bank can deliver only 440 kVA — 60 kVA, or 12 %, is stranded because A overloads while B still has 60 kVA of headroom.
Note that the machine with the lower percentage impedance is the one that overloads. It presents the easier path, so it takes more than its share. The remedy is not to derate A but to match the impedances — which is why percentage impedance is specified when a transformer is bought for an existing bank.
The Condition for Correct Sharing
If per-unit equivalent impedances are not equal, transformers will not share the load in proportion to their kVA ratings, and the overall rating of the transformer bank will be reduced.
Thus for efficient paralleling, the potential differences at full load across the internal impedances should be equal. This condition ensures that the load sharing between the transformers is according to their ratings.
The condition is equal percentage impedance on each machine's own base — not equal impedance on a common base.
A 200 kVA machine at 4 % and a 300 kVA machine at 6 % have equal impedance on a 100 kVA base (2 % each), so they would divide the load equally, 200 kVA apiece. A would then be at 100 % of rating while B sat at 67 %, and the 500 kVA bank would be limited to 400 kVA.
Equal on their own bases means unequal on a common base — in the ratio of their kVA. That is the whole point.
Problem. A 200 kVA and a 300 kVA transformer share a 400 kVA load. Compare three impedance pairings.
| Case | A (200 kVA) | B (300 kVA) | \(S_A\) | \(S_B\) | A load | B load | Bank limit |
|---|---|---|---|---|---|---|---|
| 1 correct | 4 % | 4 % | 160.0 | 240.0 | 80.0 % | 80.0 % | 500 kVA |
| 2 mismatched | 4 % | 5 % | 181.8 | 218.2 | 90.9 % | 72.7 % | 440 kVA |
| 3 the trap | 4 % | 6 % | 200.0 | 200.0 | 100.0 % | 66.7 % | 400 kVA |
Case 1 working. On a 100 kVA base, \(Z_A = 2.000\,\%\) and \(Z_B = (4)(100/300) = 1.333\,\%\):
Comment. Only Case 1 uses the full installed capacity, and it is the one where the percentage impedances on their own bases are equal. Both machines reach 100 % together, so nothing is stranded.
Case 3 is the instructive failure. The two machines have equal impedance on a common base and therefore split the load equally — which sounds fair but is exactly wrong, because their ratings are not equal. The bank loses a fifth of its capacity.
Problem. An existing 500 kVA transformer has 5.5 % impedance. A 750 kVA unit is to be added in parallel. What percentage impedance should be specified, and what happens if a 4.5 % unit is supplied instead?
Specification. For correct sharing the percentage impedances on their own bases must be equal:
The rating does not enter — that is the convenience of the percentage form.
If 4.5 % is supplied. On a 100 kVA base:
B, the larger and lower-impedance machine, reaches its 750 kVA rating first:
Comment. Installed capacity is 1250 kVA but the bank delivers 1159 kVA — 91 kVA, or 7.27 %, is lost, and the older machine never exceeds 82 % of its rating.
The loss is modest here because the mismatch is modest. But note the direction: the new machine, being cheaper to buy at a lower impedance, is the one that overloads. Specifying percentage impedance is therefore a normal part of transformer procurement, and a lower value is not automatically better — a point already met in Chapter 45, where low impedance improved regulation but raised the fault level.
Summary and Key Formulas
Transformers are paralleled because a single large unit may be unavailable, demand grows, reliability improves, and transport is easier.
Four conditions: same voltage ratio, same per-unit impedance on own base, same polarity, same phase sequence. Polarity and phase sequence are absolute.
Each current has two components: a share of the load, and a circulating current.
The circulating current \(I_c = (E_A - E_B)/(Z_A + Z_B)\) flows even at no load, is nearly purely reactive, wastes copper loss and reduces the permissible kVA.
With equal ratios, \(I_A/I_B = Z_B/Z_A\) — currents divide inversely as the impedances.
Likewise \(S_A/S_B = Z_B/Z_A\) — the kVA load is inversely proportional to impedance.
For sharing in proportion to rating, impedances must be inversely proportional to ratings, i.e. equal percentage impedance on each machine's own base, equivalently \(I_AZ_A = I_BZ_B\).
If not, the bank loses capacity: the lower-impedance machine overloads while the other still has headroom.
| Quantity | Formula | Notes |
|---|---|---|
| Node equation | \(I_A + I_B = I_L\) | phasor sum |
| Transformer current | \(I_A = \dfrac{I_LZ_B}{Z_A+Z_B} + \dfrac{E_A-E_B}{Z_A+Z_B}\) | two components |
| Circulating current | \(I_c = \dfrac{E_A-E_B}{Z_A+Z_B}\) | present at no load |
| In terms of ratios | \(I_c = \dfrac{V_1(a_2-a_1)}{a_1a_2(Z_A+Z_B)}\) | zero if \(a_1 = a_2\) |
| Current sharing | \(\dfrac{I_A}{I_B} = \dfrac{Z_B}{Z_A}\) | equal ratios |
| kVA sharing | \(\dfrac{S_A}{S_B} = \dfrac{Z_B}{Z_A}\) | inverse to impedance |
| kVA on A | \(S_A = \left(\dfrac{Z_B}{Z_A+Z_B}\right)S_L\) | — |
| Correct sharing | \(I_AZ_A = I_BZ_B\) | equal %Z on own base |
| Base conversion | \(\%Z_{\text{new}} = \%Z_{\text{own}}\dfrac{S_{\text{base}}}{S_{\text{rated}}}\) | at fixed voltage |
| Circulating loss | \(I_c^{2}(R_A + R_B)\) | continuous |
Common Mistakes
Equalising percentage impedance on a common base. The condition is equal on each machine's own base — which means unequal on a common one.
Expecting equal machines to share equally regardless of impedance. The impedance decides, not the rating.
Getting the sharing ratio upside down. \(S_A/S_B = Z_B/Z_A\) — the lower impedance takes more.
Thinking the circulating current appears only on load. It flows at no load too.
Adding \(\left|I_A\right|\) and \(\left|I_B\right|\) arithmetically. They must be added as phasors.
Using primary-referred impedances with secondary currents. Refer everything to one side first.
Ignoring tap position. Equal nameplate ratios on different taps are not equal ratios.
Paralleling without a polarity check. Reversed polarity is a dead short through both machines.
Assuming a lower percentage impedance is better. It overloads that machine and raises the fault level.
Forgetting phase sequence and vector group for three-phase banks.
Chapter Review
For sharing problems, convert both impedances to a common base first — that is what makes them proportional to the ohmic values the formula needs.
P49.1 Two transformers with equal ratios have \(Z_A = 0.15 + j0.45~\Omega\) and \(Z_B = 0.10 + j0.30~\Omega\) referred to the secondary. Find the ratio in which they share a load.
Show answer
\[Z_A = 0.4743~\Omega, \qquad Z_B = 0.3162~\Omega\]B takes 1.5 times as much as A. Note both impedances have the same angle, so the currents are in phase and the magnitudes add directly.\[\frac{I_A}{I_B} = \frac{Z_B}{Z_A} = \frac{0.3162}{0.4743} = 0.6667\]P49.2 A 100 kVA transformer at 3 % and a 200 kVA at 4 % share 250 kVA. Find each share.
Show answer
\[Z_A = (3)\frac{100}{100} = 3.000\,\%, \qquad Z_B = (4)\frac{100}{200} = 2.000\,\%\]A is at 100 % of rating, B at 75 % — the bank is already limited.\[S_A = (250)\frac{2}{5} = 100.0~\mathrm{kVA}, \qquad S_B = (250)\frac{3}{5} = 150.0~\mathrm{kVA}\]P49.3 For P49.2, find the maximum load the bank can supply and the capacity lost.
Show answer
A carries the fraction \(2/5 = 0.400\) of the load, so it reaches 100 kVA at\[S_L = \frac{100}{0.400} = 250~\mathrm{kVA}\]\[\text{lost} = 300 - 250 = 50~\mathrm{kVA} = 16.67\,\%\]P49.4 Two transformers have secondary EMFs of 420 V and 415 V, with \(Z_A + Z_B = 0.25 + j0.90~\Omega\). Find the circulating current at no load.
Show answer
\[\left|Z_A + Z_B\right| = \sqrt{0.0625 + 0.81} = 0.9341~\Omega\]at an angle of \(-74.48^{\circ}\) — nearly purely reactive.\[I_c = \frac{420 - 415}{0.9341} = \frac{5}{0.9341} = 5.353~\mathrm{A}\]P49.5 A 400 kVA transformer at 5 % is to be paralleled with a 600 kVA unit. What percentage impedance should the new unit have?
Show answer
Equal percentage impedance on their own bases. The ohmic impedances are then in the ratio \(600 : 400\), i.e. inversely as the ratings.\[\%Z = 5\,\%\]P49.6 For P49.5, if the new unit arrives at 4 %, what fraction of a 1000 kVA load does each carry?
Show answer
\[Z_A = (5)\frac{100}{400} = 1.250\,\%, \qquad Z_B = (4)\frac{100}{600} = 0.6667\,\%\]A is at 87.0 % and B at 108.7 % — B is overloaded at a total load well within the installed 1000 kVA.\[S_A = (1000)\frac{0.6667}{1.9167} = 347.8~\mathrm{kVA}, \qquad S_B = 652.2~\mathrm{kVA}\]P49.7 Derive the two components of \(I_A\) from the circuit equations.
Show answer
From the two loop equations, both equal to \(V_L\):\[E_A - I_AZ_A = E_B - \left(I_L - I_A\right)Z_B\]\[E_A - E_B = I_AZ_A + I_AZ_B - I_LZ_B\]\[I_A\left(Z_A + Z_B\right) = \left(E_A - E_B\right) + I_LZ_B\]\[I_A = \frac{I_LZ_B}{Z_A + Z_B} + \frac{E_A - E_B}{Z_A + Z_B}\]The first term is A's share of the load current, set by the current-divider rule. The second is the circulating current, driven by the difference of the two EMFs round the secondary loop.
By symmetry \(I_B\) has the same sharing form with \(Z_A\) in the numerator, but the circulating term carries a minus sign. The circulating component therefore cancels in the sum, leaving \(I_A + I_B = I_L\) — it circulates between the machines and never reaches the load.
P49.8 Why is the circulating current almost purely reactive, and why does that matter?
Show answer
Because it is driven by \((E_A - E_B)\) through the impedance \((Z_A + Z_B)\), and a transformer's impedance is mostly reactance — typically \(X\) is three or four times \(R\). The current therefore lags the driving voltage by close to 90°, as Example 49.1's 73.8° shows.Why it matters, two ways. It transfers almost no real power between the machines, so it is not doing useful work — it merely occupies winding capacity. And because it is nearly in quadrature with the load current, it adds to the load current almost at right angles, so its effect on the total current magnitude is smaller than its own size would suggest.
What it does do is consume rated current in one machine, which is the real cost: the bank's capacity is reduced even though little energy is wasted.
P49.9 Explain why equal percentage impedance on a common base is the wrong condition.
Show answer
Because equal impedance on a common base means equal ohmic impedance, and the sharing rule \(S_A/S_B = Z_B/Z_A\) then gives an equal split of kVA — regardless of how the ratings differ.Example. A 200 kVA machine at 4 % and a 300 kVA machine at 6 % both come to 2 % on a 100 kVA base. They therefore divide a load equally: 200 kVA each. A is then at 100 % of its rating while B is at only 67 %, and the 500 kVA bank is limited to 400 kVA.
The correct condition is equal percentage impedance on each machine's own base, because \(\%Z_{\text{own}} = Z_{\Omega}S_{\text{rated}}/V^{2}\), so equal \(\%Z_{\text{own}}\) makes \(Z_{\Omega} \propto 1/S_{\text{rated}}\) — exactly what the sharing rule needs to divide load in proportion to rating.
Equal on their own bases means unequal on a common base, in the ratio of the ratings.
P49.10 Two identical transformers are paralleled, but one is on a tap 2.5 % higher. Discuss the consequences.
Show answer
The two secondary EMFs now differ by 2.5 %, so a circulating current flows even at no load, given by \(I_c = (E_A - E_B)/(Z_A + Z_B)\).Magnitude. With two identical machines of, say, 5 % impedance each, the sum is 10 % on the machine base, so \(I_c \approx (2.5/10) = 25\,\%\) of rated current — ten times the tap mismatch, because the opposing impedance is itself only a few percent.
Consequences. The higher-tap machine carries 25 % of rated current circulating at no load, and on load that current adds to its share. It therefore reaches rated current when the bank is at roughly 75 % of installed capacity, while the other machine is well below rating.
There is also a continuous copper loss \(I_c^{2}(R_A + R_B)\) for no return, and the current is nearly reactive, so it does not even transfer useful power.
The remedy is trivial: put both machines on the same tap. This is why tap positions are checked as a matter of routine before paralleling.
MCQ 1. The most compelling reason for parallel operation is usually:
(a) lower cost (b) improved reliability (c) higher efficiency (d) better power factorShow answer
(b) improved reliability — one unit can be maintained without interrupting supply.MCQ 2. Reversed polarity between two paralleled transformers causes:
(a) reduced output (b) a dead short circuit (c) poor power factor (d) no effectShow answer
(b) a dead short circuit, as the two EMFs add round the secondary loop.MCQ 3. The circulating current flows:
(a) only at full load (b) only on overload (c) even at no load (d) neverShow answer
(c) even at no load, since it depends only on the EMF difference.MCQ 4. With equal ratios, the currents divide:
(a) equally (b) in proportion to impedance (c) inversely as impedance (d) by ratingShow answer
(c) inversely as impedance — \(I_A/I_B = Z_B/Z_A\).MCQ 5. The kVA carried by each transformer is:
(a) proportional to its impedance (b) inversely proportional to its impedance (c) equal (d) proportional to its rating alwaysShow answer
(b) inversely proportional to its impedance.MCQ 6. For sharing in proportion to rating, the impedances must be:
(a) equal (b) proportional to rating (c) inversely proportional to rating (d) zeroShow answer
(c) inversely proportional to rating, i.e. equal percentage impedance on their own bases.MCQ 7. If the percentage impedances differ, the machine that overloads first is the one with:
(a) the higher impedance (b) the lower impedance (c) the larger rating (d) the smaller ratingShow answer
(b) the lower impedance — it presents the easier path and takes more than its share.MCQ 8. The circulating current is nearly:
(a) in phase with the load (b) purely resistive (c) purely reactive (d) zero alwaysShow answer
(c) purely reactive, since transformer impedance is mostly reactance.MCQ 9. Unequal percentage impedances result in:
(a) a short circuit (b) reduced bank capacity (c) reversed power flow (d) no effectShow answer
(b) reduced bank capacity — one machine overloads while the other has headroom.MCQ 10. Two paralleled transformers should be set to:
(a) different taps (b) the same tap (c) any taps (d) no tapsShow answer
(b) the same tap, or the ratio mismatch drives a circulating current.
Give the reasons that necessitate parallel operation of transformers.
State the four conditions and rank them by the severity of violating each.
Write the circuit equations and derive the two components of \(I_A\).
Derive the circulating current in terms of the turns ratios and list its undesirable effects.
Show that with equal ratios the currents divide inversely as the impedances.
Derive the kVA carried by each transformer.
State and justify the condition for correct load sharing.
Explain why equal percentage impedance on a common base is the wrong condition.
Two practical matters remain before three-phase transformers. Chapter 50 covers inrush current, tap changing and cooling — the transient met in Chapter 42, where switching on at a voltage zero with residual flux demanded a flux density the core could not supply; the taps this chapter has just shown must be matched; and the cooling classes introduced in Chapter 40.
Chapter 51 then develops the per-unit system properly. This chapter used it informally, converting percentage impedances to a common base to compare them. The per-unit system makes that a general method: parameters are referred to chosen base values, so that the scaling factors vanish from the calculation and — remarkably — the per-unit impedance of a transformer is the same whichever side it is referred to, so the turns ratio disappears from the equivalent circuit altogether.
Part 3 then closes with three-phase transformers: their construction, their winding connections, the vector groups that Condition 4 of this chapter referred to, and the open-delta connection.