Electrical Machines · Chapter 48

Transformer Efficiency and Autotransformers

Part 3 · Transformers — where the efficiency peaks and why; and what happens when the two windings are merged into one.

Prof. Mithun Mondal Engineering Devotion Digital Textbook
i Learning Objectives

By the end of this chapter you should be able to:

  • Write the efficiency at any fraction of full load.

  • Derive the condition for maximum efficiency.

  • Compute the kVA at which the efficiency is greatest.

  • Compute the all-day efficiency for a stated duty cycle.

  • Describe the autotransformer and how it differs from a two-winding transformer.

  • Derive the saving of copper and show that it equals \(KW_0\).

  • Divide the throughput into conductively and inductively transferred power.

  • State the advantages, disadvantages and applications.

Section 48-1

Efficiency of a Transformer

\[\begin{aligned} \eta &= \frac{\text{output power}}{\text{input power}} = \frac{\text{output power}}{\text{output power} + \text{losses}}\\[4pt] &= \frac{\text{output power}}{\text{output power} + \text{iron losses} + \text{copper losses}}\\[4pt] &= \frac{V_2I_2\cos\phi_2}{V_2I_2\cos\phi_2 + P_i + P_c} \end{aligned}\]
Table 48.1 — Symbols used throughout this chapter.
SymbolMeaning
\(V_2\)Secondary terminal voltage
\(I_2\)Full-load secondary current
\(\cos\phi_2\)Power factor of the load
\(P_i\)Iron losses = hysteresis + eddy-current losses
\(P_c\)Full-load copper losses \(= I_2^{2}R_{02}\)

Both losses are known from the tests of Chapter 46 — \(P_i\) from the open-circuit wattmeter and \(P_c\) from the short-circuit wattmeter — or from Chapter 47's Sumpner test, halved.

Video · Efficiency and Autotransformers
Section 48-2

Efficiency at Any Load

If \(x\) is the fraction of full load, the output scales with \(x\) and the copper loss with \(x^{2}\), while the iron loss does not change at all.

\[\eta_x = \frac{x\times\text{Output}}{x\times\text{Output} + P_i + x^{2}P_c} = \frac{xV_2I_2\cos\phi_2}{xV_2I_2\cos\phi_2 + P_i + x^{2}I_2^{2}R_{02}}\]
The whole behaviour of the curve is contained in those two exponents. The output rises as \(x\) and the copper loss as \(x^{2}\), so at light load the fixed iron loss dominates and the efficiency is poor; at heavy load the copper loss overtakes it. Somewhere between, the two are equal and the efficiency is greatest — which is what the next section proves.
Section 48-3

Condition for Maximum Efficiency

Take the full-load expression and divide numerator and denominator by \(I_2\):

\[\eta = \frac{V_2I_2\cos\phi_2}{V_2I_2\cos\phi_2 + P_i + I_2^{2}R_{02}} = \frac{V_2\cos\phi_2}{V_2\cos\phi_2 + \dfrac{P_i}{I_2} + I_2R_{02}}\]
📐
The Derivation
Minimise the denominator

For a given load power factor, \(V_2\cos\phi_2\) is constant. So \(\eta\) is greatest when the denominator is least, that is when

\[\frac{\mathrm{d}}{\mathrm{d}I_2}\left(\frac{P_i}{I_2} + I_2R_{02}\right) = 0\]
\[-\frac{P_i}{I_2^{2}} + R_{02} = 0 \quad\Longrightarrow\quad \boxed{P_i = I_2^{2}R_{02} = P_c}\]

Efficiency is maximum when the iron loss equals the copper loss — that is, when the constant loss equals the variable loss.

This is Chapter 33's condition for the DC machine, unchanged. It carries over because it depends only on the shape of the loss expression — one term fixed and one proportional to the square of the current — and not on whether the machine rotates.

! Note What the Condition Does Not Involve

The power factor cancelled out of the derivation. The load fraction at which the efficiency peaks is the same at every power factor — only the value of that peak changes.

This is why a transformer's maximum-efficiency point can be quoted as a single kVA figure on the nameplate without reference to the load's character.

Section 48-4

The kVA at Maximum Efficiency

Writing the condition in terms of the load fraction, with \(P_c\) the full-load copper loss:

\[x^{2}P_c = P_i \quad\Longrightarrow\quad \boxed{x = \sqrt{\frac{P_i}{P_c}}}\]
🎯
In Practical Form
The output at which the efficiency is greatest
\[\text{kVA at }\eta_{\max} = \left(\text{full-load kVA}\right)\sqrt{\frac{P_i}{P_c}}\]

and at that point the total loss is \(2P_i\), so

\[\eta_{\max} = \frac{xS\cos\phi}{xS\cos\phi + 2P_i}\]

Since \(P_i\) is usually less than \(P_c\), the ratio is below one and the peak falls below full load — typically between 70 % and 90 %.

1 Worked Example 48.1 — Locating the Maximum

Problem. A 25 kVA transformer has an iron loss of 300 W and a full-load copper loss of 400 W. Find the load for maximum efficiency, the maximum efficiency at 0.8 power factor, and the full-load efficiency at the same power factor.

Load fraction.

\[x = \sqrt{\frac{300}{400}} = \sqrt{0.75} = 0.8660\]
\[\text{kVA} = (25)(0.8660) = 21.65~\mathrm{kVA}\]

Maximum efficiency. The total loss there is \(2P_i = 600\) W:

\[\eta_{\max} = \frac{(21\,651)(0.8)}{(21\,651)(0.8) + 600} = \frac{17\,321}{17\,921} = 96.65\,\%\]

Full-load efficiency.

\[\eta = \frac{20\,000}{20\,000 + 300 + 400} = \frac{20\,000}{20\,700} = 96.62\,\%\]

Comment. The maximum exceeds the full-load value by only 0.03 percentage points, though it occurs at 87 % of full load. The efficiency curve is extremely flat near its top, which is why the exact location of the peak matters far less than the total loss.

Notice also that the peak lies below full load precisely because \(P_i \lt P_c\). If the design were altered to make \(P_i = P_c\) at full load, the peak would sit exactly at full load — which is how a power transformer running continuously near rating is designed.

Section 48-5

All-Day Efficiency

  • Power transformers, at a generating station, are switched in or out of the circuit depending on the load to be handled.

  • A distribution transformer at a substation is never switched off, and remains energised irrespective of the load.

  • In that case the constant loss continues to be dissipated throughout the day, whether or not any output is being delivered.

The ordinary power efficiency is then a misleading figure of merit, and a concept of energy-based efficiency arises — the all-day efficiency.

🕐
All-Day Efficiency
A ratio of energies, not powers
\[\begin{aligned} \%\,\eta_{\text{all-day}} &= \frac{\text{Output energy in kWh during a day}}{\text{Input energy in kWh during a day}}\times100\\[4pt] &= \frac{\text{Output energy in kWh}}{\text{Output energy} + \text{Energy spent on total losses}}\times100 \end{aligned}\]

The iron-loss energy is always \(24P_i\), whatever the duty; the copper-loss energy is summed hour by hour with \(x^{2}P_c\).

The design consequence, already met in Chapter 44, is that a distribution transformer is built with a deliberately low iron loss, even at the cost of higher copper loss — which moves its maximum-efficiency point down to perhaps half load.

2 Worked Example 48.2 — A Realistic Duty Cycle

Problem. The 25 kVA transformer of Example 48.1 supplies: 20 kVA at 0.9 power factor for 2 hours, 15 kVA at 0.8 for 6 hours, 8 kVA at unity for 8 hours, and nothing for the remaining 8 hours. Find the all-day efficiency.

Table 48.2 — Energy accounting over 24 hours. \(P_c = 400\) W at full load.
HourskVApf\(x\)Output (kWh)Copper (kWh)
2200.90.8036.00.5120
6150.80.6072.00.8640
881.00.3264.00.3277
80000
Totals172.01.7037

Sample working, the second row.

\[x = \frac{15}{25} = 0.60, \qquad \text{output} = (15)(0.8)(6) = 72.0~\mathrm{kWh}\]
\[\text{copper} = \frac{(400)(0.60)^{2}(6)}{1000} = \frac{864}{1000} = 0.8640~\mathrm{kWh}\]

Iron-loss energy — the whole 24 hours.

\[\frac{(300)(24)}{1000} = 7.20~\mathrm{kWh}\]

All-day efficiency.

\[\eta_{\text{all-day}} = \frac{172.0}{172.0 + 1.7037 + 7.20} = \frac{172.0}{180.90} = 95.08\,\%\]

Comment. Against a commercial efficiency of 96.62 %, the all-day figure is 1.54 percentage points lower. The iron loss contributes 7.20 kWh against the copper loss's 1.70 kWh — more than four times as much, because it runs for 24 hours while the machine delivers useful output for 16, and at reduced load for most of those.

The remedy follows directly. Halving the iron loss to 150 W would save 3.6 kWh a day and raise the all-day efficiency to 96.99 %, a gain of nearly two points. Halving the copper loss would gain barely half a point. For this duty, iron loss deserves roughly four times the design attention.

Section 48-6

The Autotransformer

An autotransformer with a single tapped winding
The autotransformer.
  • A transformer with one winding only.

  • Part of the winding is common to both primary and secondary.

  • There is no electrical isolation, as there is in a two-winding transformer.

  • The theory and operation remain similar — the EMF equation, the turns ratio and the ampere-turn balance all apply unchanged.

  • Because there is only one winding, it uses less copper and is therefore cheaper.

  • It is used where the transformation ratio varies little from unity.

Step-up and step-down autotransformer connections
Step-up and step-down connections.
The last point is the whole story of the autotransformer. Its advantage grows as \(K\) approaches unity, and vanishes as \(K\) approaches zero. At \(K = 0.9\) it saves 90 % of the copper; at \(K = 0.1\) it saves 10 % and is not worth the loss of isolation. Section 48-7 derives exactly why.
Section 48-7

Saving of Copper

Autotransformer showing the series section AC and the common section BC with their currents
The two sections of the winding.
What Determines the Weight of Copper
Turns times current
  • Volume, and hence weight, is proportional to length × area of cross-section.

  • Length of conductor is proportional to the number of turns.

  • Cross-section is determined by the current it must carry.

  • Therefore weight \(\propto\) product of current and number of turns.

Applying this to the two sections of the autotransformer winding:

\[\begin{aligned} \text{Weight of Cu in section AC} &\propto \left(N_1 - N_2\right)I_1\\[4pt] \text{Weight of Cu in section BC} &\propto N_2\left(I_2 - I_1\right)\\[4pt] \therefore\quad \text{Total weight of Cu} &\propto \left(N_1 - N_2\right)I_1 + N_2\left(I_2 - I_1\right) \end{aligned}\]

If an ordinary two-winding transformer were to perform the same task, its primary would need \(N_1I_1\) and its secondary \(N_2I_2\), so its total weight would be proportional to \(N_1I_1 + N_2I_2\). Taking the ratio:

\[\therefore\ \frac{\text{Wt. of Cu in auto-transformer}}{\text{Wt. of Cu in ordinary transformer}} = \frac{\left(N_1 - N_2\right)I_1 + N_2\left(I_2 - I_1\right)}{N_1I_1 + N_2I_2} = \left(1 - K\right)\]
💰
The Saving
A fraction K of the two-winding weight
\[W_a = \left(1 - K\right)W_0\]
\[\boxed{\text{Saving} = W_0 - W_a = W_0 - \left(1 - K\right)W_0 = KW_0}\]

Hence the saving increases as \(K\) approaches unity.

00.250.500.751.0 transformation ratio K 05101520 rating multiplier 1/(1−K) copper saving = K K = 0.90 → 10× The saving is linear in K; the rating multiplier is not.
Copper saving and rating multiplier against the transformation ratio.
3 Worked Example 48.3 — How the Saving Varies

Problem. Compare the copper saving of autotransformers with ratios 250/200 V, 400/200 V and 2200/200 V, each replacing a two-winding transformer of the same duty.

Table 48.3 — Copper saving against transformation ratio.
Ratio\(K = V_2/V_1\)\(W_a/W_0 = 1-K\)Saving \(= K\)
250 / 200 V0.8000.20080.0 %
400 / 200 V0.5000.50050.0 %
2200 / 200 V0.09090.9099.1 %

Comment. At a ratio close to unity the autotransformer uses only a fifth of the copper; at a ratio of 11 : 1 it saves under a tenth. Since the loss of isolation is the same in both cases, only the first is a bargain.

This settles the design question directly. Autotransformers are used where the two voltages are close — interconnecting 220 kV and 132 kV transmission systems, boosting a distribution feeder, or starting an induction motor at 60 % of line voltage. Where the ratio is large, a two-winding transformer costs little more in copper and gives isolation free.

Section 48-8

Conductive and Inductive Transfer

In a two-winding transformer every watt reaching the load must first cross the air gap magnetically. In an autotransformer only part of it does; the rest flows straight through the metal.

Inductively transferred
\[\boxed{P_{ind} = \text{Input}\times\left(1 - K\right)}\]

This part passes through the magnetic circuit and requires core and winding to handle it.

Conductively transferred
\[\boxed{P_{cond} = \text{Input}\times K}\]

This part flows directly through the common winding, needing no magnetic transfer at all.

🔑
Why the Saving Is So Large
Only the inductive part needs a machine

The physical size of a transformer is set by the power it must transfer magnetically. In an autotransformer that is only \((1 - K)\) of the throughput.

So an autotransformer of a given kVA is really a two-winding transformer of \((1-K)\) times that kVA, with the rest of the power simply passing through — which is the same statement as the copper saving, seen from the other side.

4 Worked Example 48.4 — Reconnecting as an Autotransformer

Problem. A 20 kVA, 2000/200 V two-winding transformer is reconnected as an autotransformer to give 2200/2000 V. Find its new rating, and check that neither winding is overloaded.

The windings and their ratings.

\[\text{200 V winding: } I = \frac{20\,000}{200} = 100~\mathrm{A} \quad\text{(becomes the series winding)}\]
\[\text{2000 V winding: } I = \frac{20\,000}{2000} = 10~\mathrm{A} \quad\text{(becomes the common winding)}\]

As an autotransformer. The HV side is 2000 + 200 = 2200 V, and its line current is the series winding's current:

\[\text{Rating} = \frac{(2200)(100)}{1000} = 220~\mathrm{kVA}\]

Check the common winding.

\[I_{LV} = \frac{220\,000}{2000} = 110~\mathrm{A}\]
\[I_{\text{common}} = 110 - 100 = 10~\mathrm{A} \quad\text{= its rating} \quad\checkmark\]

The uprating factor.

\[K = \frac{2000}{2200} = 0.9091, \qquad \frac{1}{1 - K} = 11.00\]
\[\frac{220}{20} = 11 \quad\checkmark\]

Comment. The same iron and the same copper now handle eleven times the throughput. Nothing has been added — the windings still carry exactly their rated currents and the core its rated flux. The extra 200 kVA simply passes through conductively without being transformed.

This is the single most useful fact about autotransformers, and it is why they dominate wherever two transmission voltages must be interconnected. It also explains their weakness: a fault on the LV side is fed by 11 times the fault current a two-winding transformer of the same physical size would allow, because the percentage impedance falls by the same factor.

5 Worked Example 48.5 — Splitting the Power

Problem. For the 220 kVA autotransformer of Example 48.4, find the conductively and inductively transferred power, and comment.

Inductively.

\[P_{ind} = (220)\left(1 - 0.9091\right) = (220)(0.0909) = 20.0~\mathrm{kVA}\]

Conductively.

\[P_{cond} = (220)(0.9091) = 200.0~\mathrm{kVA}\]

Check.

\[20.0 + 200.0 = 220~\mathrm{kVA} \quad\checkmark\]

Comment. The inductively transferred 20.0 kVA is exactly the original two-winding rating. That is not a coincidence but the whole explanation: the magnetic circuit is doing precisely the work it was designed for, and the other 200 kVA is simply conducted through the common winding.

A useful way to state it: an autotransformer of rating \(S\) is a two-winding transformer of rating \(S(1-K)\) with a conducting path added. Every property follows — the copper saving, the reduced impedance, the reduced losses, and the reduced size.

Section 48-9

Advantages, Disadvantages, Applications

Advantages
  • Less costly, because less copper and less iron are needed.

  • Better regulation, since the impedance is lower.

  • Lower losses compared with a two-winding transformer of the same rating, so higher efficiency.

  • Smaller and lighter for a given throughput.

Disadvantages
  • The secondary winding is not insulated from the primary. If a low supply voltage is taken from a high voltage and a break occurs in the secondary winding, the full primary voltage appears across the secondary terminals — dangerous to the operator and to the equipment.

  • Used only in limited places, where a slight variation of the output voltage from the input voltage is required.

  • The low impedance that improves regulation also gives a high short-circuit current.

The Broken-Winding Hazard, Quantified

Consider a 2200/220 V autotransformer supplying a 220 V load. The common winding is the 220 V section. If it breaks, the load is left connected across the series section — and the full 2200 V appears at its terminals.

A ten-fold overvoltage on equipment rated for 220 V, with no fuse necessarily operating, because the current may not rise until the equipment fails. In a two-winding transformer the same break simply disconnects the load.

This is why autotransformers are not used to supply low-voltage consumer circuits from high-voltage systems, however attractive the copper saving might look.

Applications
  • As a starter, to give 50 to 60 % of full voltage to the stator of a squirrel-cage induction motor during starting.

  • To give a small boost to a distribution cable, correcting the voltage drop.

  • As a voltage regulator.

  • In power transmission and distribution systems, and also in audio systems and railways.

  • As a continuously variable laboratory supply — the familiar rotating-brush variac.

Section 48-10

Summary and Key Formulas

  • Efficiency at a load fraction \(x\) is \(xS\cos\phi/(xS\cos\phi + P_i + x^{2}P_c)\): output rises as \(x\), copper loss as \(x^{2}\), iron loss not at all.

  • Dividing through by \(I_2\) and minimising the denominator gives the condition \(P_i = P_c\)constant loss equals variable loss.

  • The load fraction is \(x = \sqrt{P_i/P_c}\) and the kVA is \(S\sqrt{P_i/P_c}\). The power factor does not affect where the peak lies, only its value.

  • All-day efficiency is a ratio of energies over 24 hours. The iron-loss energy is \(24P_i\) regardless of duty, so the figure is always lower than the commercial efficiency.

  • An autotransformer has one winding, part common to both sides, and gives no isolation.

  • Copper weight \(\propto\) turns × current, giving \(W_a = (1-K)W_0\) and a saving of \(KW_0\), greatest as \(K \to 1\).

  • Power divides into \(P_{ind} = \text{Input}(1-K)\) and \(P_{cond} = \text{Input}\,K\).

  • A two-winding transformer reconnected as an autotransformer is uprated by \(1/(1-K)\).

  • Advantages: cheaper, better regulation, lower losses. Disadvantages: no isolation, the broken-winding hazard, and a high short-circuit current.

Table 48.4 — Formulas of this chapter.
QuantityFormulaNotes
Efficiency\(\eta = \dfrac{V_2I_2\cos\phi_2}{V_2I_2\cos\phi_2 + P_i + P_c}\)at full load
At load fraction \(x\)\(\eta_x = \dfrac{xS\cos\phi}{xS\cos\phi + P_i + x^{2}P_c}\)
Maximum-efficiency condition\(P_i = P_c\)constant = variable
Load fraction\(x = \sqrt{P_i/P_c}\)independent of pf
kVA at maximum\(S\sqrt{P_i/P_c}\)total loss \(= 2P_i\)
All-day efficiency\(\dfrac{\text{kWh out}}{\text{kWh out} + \text{kWh loss}}\)iron energy \(= 24P_i\)
Auto copper weight\(W_a = (1-K)W_0\)weight \(\propto NI\)
Saving\(KW_0\)grows as \(K \to 1\)
Inductive transfer\(P_{ind} = \text{Input}(1-K)\)through the core
Conductive transfer\(P_{cond} = \text{Input}\,K\)through the metal
Uprating on reconnection\(\dfrac{1}{1-K}\)11× at \(K = 0.909\)
Section 48-11

Common Mistakes

  • Letting the iron loss vary with load. It is fixed by the supply voltage.

  • Scaling the copper loss linearly. It varies as \(x^{2}\).

  • Thinking the power factor moves the maximum-efficiency load. It cancels; only the peak value changes.

  • Using kVA in the all-day numerator. Energy is kWh, so the power factor must be applied.

  • Omitting the no-load hours from the iron-loss energy. It runs the full 24 hours.

  • Defining \(K\) upside down in the saving formula. Here \(K = V_2/V_1\) and the saving is \(KW_0\).

  • Expecting a large saving at a large ratio. The saving is greatest when \(K\) is near unity.

  • Forgetting that an autotransformer gives no isolation. This is its defining limitation.

  • Overloading the common winding. It carries \(I_2 - I_1\), not \(I_2\).

  • Assuming the uprating is free of consequence. The percentage impedance falls by the same factor, so the fault current rises.

Section 48-12

Chapter Review

Practice Problems

For efficiency questions find \(x = \sqrt{P_i/P_c}\) first. For autotransformer questions identify which physical winding becomes the series and which the common.

  1. P48.1 A 100 kVA transformer has \(P_i = 900\) W and \(P_c = 1600\) W. Find the kVA at maximum efficiency.

    Show answer
    \[x = \sqrt{\frac{900}{1600}} = 0.750 \quad\Longrightarrow\quad 75.0~\mathrm{kVA}\]
  2. P48.2 For P48.1, find the maximum efficiency at 0.9 power factor and the full-load efficiency.

    Show answer
    \[\eta_{\max} = \frac{(75\,000)(0.9)}{67\,500 + 1800} = \frac{67\,500}{69\,300} = 97.40\,\%\]
    \[\eta_{FL} = \frac{90\,000}{90\,000 + 900 + 1600} = \frac{90\,000}{92\,500} = 97.30\,\%\]
  3. P48.3 A 50 kVA transformer with \(P_i = 400\) W and \(P_c = 700\) W supplies full load at 0.8 pf for 8 h, half load at 0.8 pf for 8 h, and nothing for 8 h. Find the all-day efficiency.

    Show answer
    \[\text{output} = (50)(1.0)(0.8)(8) + (50)(0.5)(0.8)(8) = 320 + 160 = 480~\mathrm{kWh}\]
    \[\text{copper} = \frac{(700)(1)(8) + (700)(0.25)(8)}{1000} = 5.60 + 1.40 = 7.00~\mathrm{kWh}\]
    \[\text{iron} = \frac{(400)(24)}{1000} = 9.60~\mathrm{kWh}\]
    \[\eta_{\text{all-day}} = \frac{480}{480 + 7.00 + 9.60} = \frac{480}{496.6} = 96.66\,\%\]
  4. P48.4 An autotransformer has \(K = 0.8\). Find the copper saving and the ratio of its weight to that of an equivalent two-winding transformer.

    Show answer
    \[\frac{W_a}{W_0} = 1 - K = 0.200, \qquad \text{saving} = KW_0 = 80\,\%\]
    It uses one fifth of the copper.
  5. P48.5 A 10 kVA, 1000/100 V two-winding transformer is reconnected as a 1100/1000 V autotransformer. Find its new rating.

    Show answer
    \[\text{100 V winding: } \frac{10\,000}{100} = 100~\mathrm{A} \quad\text{(series)}\]
    \[\text{Rating} = \frac{(1100)(100)}{1000} = 110~\mathrm{kVA}\]
    \[K = \frac{1000}{1100} = 0.9091, \qquad \frac{1}{1-K} = 11 \quad\Longrightarrow\quad (10)(11) = 110 \quad\checkmark\]
  6. P48.6 For P48.5, find the conductively and inductively transferred power.

    Show answer
    \[P_{ind} = (110)(1 - 0.9091) = 10.0~\mathrm{kVA}, \qquad P_{cond} = (110)(0.9091) = 100.0~\mathrm{kVA}\]
    The inductive part equals the original two-winding rating, as it must.
  7. P48.7 Derive the condition for maximum efficiency, and explain why the power factor does not appear in it.

    Show answer
    Start from \(\eta = V_2I_2\cos\phi_2/(V_2I_2\cos\phi_2 + P_i + I_2^{2}R_{02})\) and divide numerator and denominator by \(I_2\):
    \[\eta = \frac{V_2\cos\phi_2}{V_2\cos\phi_2 + P_i/I_2 + I_2R_{02}}\]
    For a given power factor the numerator is constant, so \(\eta\) is greatest when the denominator is least. Differentiating with respect to \(I_2\):
    \[-\frac{P_i}{I_2^{2}} + R_{02} = 0 \quad\Longrightarrow\quad P_i = I_2^{2}R_{02} = P_c\]

    Why the power factor is absent: the term \(V_2\cos\phi_2\) appears in both numerator and denominator and does not depend on \(I_2\), so it plays no part in the differentiation. Changing the power factor scales the efficiency but does not move the current at which it peaks.

  8. P48.8 Derive the copper saving of an autotransformer.

    Show answer
    The weight of copper is proportional to length × cross-section. Length is proportional to the number of turns, and cross-section to the current the conductor carries, so weight \(\propto NI\).
    \[\text{section AC} \propto \left(N_1 - N_2\right)I_1, \qquad \text{section BC} \propto N_2\left(I_2 - I_1\right)\]
    An ordinary two-winding transformer doing the same duty needs \(N_1I_1 + N_2I_2\). Taking the ratio and using \(N_1I_1 = N_2I_2\):
    \[\frac{W_a}{W_0} = \frac{N_1I_1 - N_2I_1 + N_2I_2 - N_2I_1}{N_1I_1 + N_2I_2} = \frac{2N_1I_1 - 2N_2I_1}{2N_1I_1} = 1 - \frac{N_2}{N_1} = 1 - K\]
    \[\text{Saving} = W_0 - W_a = KW_0\]

    The saving grows as \(K\) approaches unity, which is why autotransformers suit ratios close to 1 : 1.

  9. P48.9 Explain the broken-winding hazard and why it rules out some applications.

    Show answer
    Because the two sides share a winding, there is no electrical isolation. Consider a 2200/220 V autotransformer supplying a 220 V load from the common section.

    If the common winding breaks, the load is left connected across the series section, and the full 2200 V appears at its terminals — a tenfold overvoltage on equipment insulated for 220 V.

    Worse, no protective device need operate: the current may not rise until the equipment itself fails. In a two-winding transformer the same break simply disconnects the load, harmlessly.

    Consequence: autotransformers are not used to supply low-voltage consumer circuits from high-voltage systems, however attractive the copper saving. They are confined to duties where the two voltages are close, so that the worst-case overvoltage is modest.

  10. P48.10 Why is a distribution transformer designed with lower iron loss than a power transformer of the same rating?

    Show answer
    Because of the duty cycle. A power transformer at a generating station is switched in and out with the load and runs near full rating whenever it is energised; a distribution transformer is never switched off and is lightly loaded for much of the day.

    The iron loss therefore runs for all 24 hours in a distribution transformer, while output accumulates only during the loaded hours. In Example 48.2 the iron loss contributed 7.20 kWh against the copper loss's 1.70 kWh — more than four times as much.

    The design response is better core steel, thinner laminations and a lower working flux density, accepting a larger core and higher copper loss in exchange.

    The side effect is that the maximum-efficiency point moves down, since \(x = \sqrt{P_i/P_c}\) falls as \(P_i\) falls — typically to about half load, which is where a distribution transformer actually spends its time. The peak is placed where the machine lives, not where its nameplate says.

Multiple-Choice Questions
  1. MCQ 1. Efficiency is maximum when:
    (a) iron loss = copper loss   (b) iron loss = 2 × copper loss   (c) at full load always   (d) at no load

    Show answer
    (a) iron loss = copper loss — constant loss equals variable loss.
  2. MCQ 2. The load fraction at maximum efficiency is:
    (a) \(P_c/P_i\)   (b) \(\sqrt{P_i/P_c}\)   (c) \(\sqrt{P_c/P_i}\)   (d) \(P_i/P_c\)

    Show answer
    (b) \(\sqrt{P_i/P_c}\).
  3. MCQ 3. Changing the load power factor moves the maximum-efficiency load:
    (a) up   (b) down   (c) not at all   (d) to full load

    Show answer
    (c) not at all. The power factor cancels in the derivation; only the peak value changes.
  4. MCQ 4. All-day efficiency is based on:
    (a) power   (b) energy   (c) current   (d) voltage

    Show answer
    (b) energy, in kWh over 24 hours.
  5. MCQ 5. In an autotransformer, part of the winding is:
    (a) isolated   (b) common to both sides   (c) short-circuited   (d) unused

    Show answer
    (b) common to both sides, which is why there is no isolation.
  6. MCQ 6. The copper weight of an autotransformer relative to a two-winding one is:
    (a) \(K\)   (b) \(1-K\)   (c) \(K^{2}\)   (d) \(1/K\)

    Show answer
    (b) \(1-K\), so the saving is \(KW_0\).
  7. MCQ 7. The copper saving is greatest when \(K\) is:
    (a) near zero   (b) near unity   (c) exactly 0.5   (d) greater than 1

    Show answer
    (b) near unity, which is why autotransformers suit close ratios.
  8. MCQ 8. The inductively transferred power is:
    (a) Input × \(K\)   (b) Input × \((1-K)\)   (c) Input   (d) zero

    Show answer
    (b) Input × \((1-K)\). The rest is conducted through the common winding.
  9. MCQ 9. The chief disadvantage of an autotransformer is:
    (a) high cost   (b) poor regulation   (c) no electrical isolation   (d) high losses

    Show answer
    (c) no electrical isolation, with the broken-winding hazard that follows.
  10. MCQ 10. A 10 kVA two-winding transformer reconnected as an autotransformer with \(K = 0.9\) becomes:
    (a) 10 kVA   (b) 20 kVA   (c) 90 kVA   (d) 100 kVA

    Show answer
    (d) 100 kVA, since the uprating is \(1/(1-K) = 10\).
Conceptual Questions
  1. Write the efficiency at any load fraction and explain the exponents.

  2. Derive the condition for maximum efficiency and explain why the power factor does not appear.

  3. Derive the kVA at which the efficiency is greatest.

  4. Define all-day efficiency and explain why it differs from commercial efficiency.

  5. Describe the autotransformer and state how it differs from a two-winding transformer.

  6. Derive the saving of copper and comment on its dependence on \(K\).

  7. Explain the division into conductively and inductively transferred power.

  8. Give the advantages, disadvantages and applications of the autotransformer.

Looking Ahead

A single transformer has now been treated completely. Chapter 49 asks what happens when two or more are connected in parallel — the usual arrangement in any substation, since it permits maintenance without interruption and allows capacity to be added as demand grows.

Four conditions must be satisfied: the same voltage ratio, the same polarity, the same percentage impedance, and — for three-phase units — the same phase sequence and vector group. The first two are absolute; a mismatch produces a circulating current or a short circuit. The third governs how the load divides: transformers share load in inverse proportion to their percentage impedances, so unequal values leave one machine overloaded while the other is still idle.

Chapters 50 and 51 then cover the practical matters set aside so far — inrush current, tap changing and cooling — and the per-unit system, which makes the percentage impedance of this chapter into a general method of calculation. Part 3 closes with three-phase transformers and their connections.