Electrical Machines · Chapter 32

Parallel Operation of DC Generators

Part 2 · DC Machines — put two generators on the same bus and they must agree on one voltage. Which of them supplies the load, and in what proportion, follows entirely from the characteristics of Chapter 29.

Prof. Mithun Mondal Engineering Devotion Digital Textbook
i Learning Objectives

By the end of this chapter you should be able to:

  • Give the reasons for operating generators in parallel.

  • State the conditions that must be met and the procedure for paralleling.

  • Calculate how a load divides between two shunt generators.

  • Explain why a drooping characteristic is required for stable sharing.

  • Shift load between machines by field adjustment and calculate the required EMF.

  • Compute the circulating current on no load and recognise when a machine is motoring.

  • Explain the instability of paralleled compound generators.

  • Explain the purpose and connection of the equaliser bar.

Section 32-1

Why Operate in Parallel

A power station rarely runs one large machine. It runs several smaller ones on a common pair of bus bars, and switches them in and out as the load demands.

Continuity of supply

If one machine fails or is taken out for maintenance, the others carry on. A single machine means a single point of failure.

Efficiency at part load

Chapter 33 will show that a machine is most efficient near full load. Running two machines at 90 % beats running four at 45 %, so units are shut down as the load falls.

Maintenance without shutdown

Any one unit can be isolated, overhauled and returned to service while the station continues to supply.

Growth

Demand can be met as it grows by adding units, rather than by installing from the start a machine large enough for a load that does not yet exist.

Handling capacity

Several moderate machines are easier to transport, install and lift than one very large one.

Reserve

A spare unit on standby costs a fraction of duplicating one large machine.

Section 32-2

Conditions for Paralleling

The Three Conditions
Far simpler than for AC machines
  1. The terminal voltages must be equal — or the incoming machine's very slightly higher, so that it takes up load rather than drawing it.

  2. The polarities must agree: positive to positive and negative to negative.

  3. The characteristics should be drooping, so that the sharing is stable (Section 32-5).

Note what is not required. There is no frequency to match, no phase sequence, and no phase angle to align — the three conditions that dominate the synchronising of alternators in Part 4. A DC bus has only a magnitude and a sign, so paralleling a DC generator is a matter of matching two numbers, one of which has only two possible values.
! Reversed Polarity Is a Short Circuit

If a machine is connected with its polarity reversed, the two EMFs act in series around the loop rather than opposing each other. The driving voltage is then \(E_A + E_B\) — nearly 500 V in a 250 V system — across only the two armature resistances.

\[I = \frac{E_A + E_B}{R_A + R_B}\]

With \(R_A + R_B = 0.09~\Omega\) that is over 5000 A. Checking polarity with a voltmeter across the open switch is not a formality: a correct connection reads nearly zero, a reversed one reads about twice the bus voltage.

Section 32-3

Putting a Machine on the Bus

  1. Run the incoming machine up to speed with its main switch open.
  2. Excite it and let it build up, following Chapter 28 — field rheostat at minimum first, then adjusted.
  3. Check the polarity across the open switch with a voltmeter. A near-zero reading confirms correct connection; a reading of about twice the bus voltage means the machine is reversed.
  4. Adjust the field until the machine's voltage is equal to, or a fraction of a volt above, the bus voltage.
  5. Close the switch. The machine is now on the bus but carrying almost no load.
  6. Raise its excitation to make it take up load, lowering the excitation of the machine being relieved to keep the bus voltage constant.

Step 6 is the one students find counter-intuitive. A generator takes up load when its own EMF is raised, not when the load is somehow directed to it — and since the bus voltage would rise too, the other machine's field must be weakened by a corresponding amount.

Section 32-4

Load Sharing Between Shunt Generators

Once paralleled, both machines are connected to the same bus, so they must have the same terminal voltage. That single constraint determines everything.

The Two Equations
Common voltage, and currents that sum to the load
\[V = E_A - I_AR_A = E_B - I_BR_B\]
\[I_A + I_B = I_L\]

Two equations, two unknowns. Solving,

\[I_A = \frac{E_A - E_B + I_LR_B}{R_A + R_B}\]
0100200300 235240245250 current (A) volts A: 250 V, 0.05 Ω B: 245 V, 0.04 Ω bus 240.6 V I_A = 189 A I_B = 111 A One bus voltage, read off both characteristics — the currents sum to the load.
Load sharing is read directly from the two external characteristics at the common bus voltage.
1 Worked Example 32.1 — How the Load Divides

Problem. Two shunt generators run in parallel. Generator A has a no-load EMF of 250 V and an armature resistance of 0.05 \(\Omega\); generator B has 245 V and 0.04 \(\Omega\). They supply a total load of 300 A. Find the bus voltage, each machine's current, and each machine's output.

Setting up. Writing the common terminal voltage two ways, with \(I_B = 300 - I_A\):

\[250 - 0.05I_A = 245 - 0.04\left(300 - I_A\right)\]
\[250 - 0.05I_A = 245 - 12 + 0.04I_A = 233 + 0.04I_A\]

Solving.

\[250 - 233 = 0.09I_A \quad\Longrightarrow\quad I_A = \frac{17}{0.09} = 188.9~\mathrm{A}\]
\[I_B = 300 - 188.9 = 111.1~\mathrm{A}\]

Bus voltage.

\[V = 250 - (0.05)(188.9) = 250 - 9.44 = 240.6~\mathrm{V}\]

Check on B: \(245 - (0.04)(111.1) = 245 - 4.44 = 240.6\) V \(\checkmark\)

Outputs.

\[P_A = (240.6)(188.9) = 45.4~\mathrm{kW}, \qquad P_B = (240.6)(111.1) = 26.7~\mathrm{kW}\]

Comment. Machine A takes 63 % of the load although it is the one with the higher armature resistance. Load sharing is governed chiefly by the no-load EMFs, not by the resistances — a 5 V difference in EMF outweighs the 25 % difference in slope. The resistances decide only how the remaining margin is apportioned.

This is the practical basis of Section 32-6: to change the sharing, change an EMF, which means changing a field rheostat.

Section 32-5

Why a Drooping Characteristic Is Essential

Suppose machine A momentarily takes a little more than its share — because of a speed fluctuation, say.

With a drooping characteristic — stable

Taking more current makes A's terminal voltage fall. Since the bus voltage is common, A can no longer sustain the extra current, and it falls back.

The disturbance is self-correcting. The machines settle at a definite division of load and stay there.

With a rising characteristic — unstable

Taking more current makes A's voltage rise. It therefore forces the bus voltage up, which reduces B's current, which lowers B's voltage further, which lets A take yet more.

The disturbance grows. A ends up carrying the whole load and B is driven into motoring.

📉
The Stability Condition
Negative slope means negative feedback
\[\frac{\mathrm{d}V}{\mathrm{d}I} \lt 0 \quad\text{for each machine}\]

A drooping characteristic provides negative feedback on the current division, exactly as the saturating magnetisation curve of Chapter 28 provided negative feedback on the voltage build-up. In both cases the stabilising mechanism is a falling return for an increasing input.

This is why shunt generators parallel readily: their characteristics droop naturally. Series generators and over-compounded machines do not, and need the special measures of Sections 32-8 and 32-9.

Section 32-6

Shifting Load Between Machines

Since sharing depends on the EMFs, and each EMF depends on its field current, the operator controls the division with the field rheostats.

Table 32.1 — What each adjustment does.
ActionEffect on that machineEffect on the bus
Strengthen A's fieldA takes more loadBus voltage rises
Weaken A's fieldA takes less loadBus voltage falls
Strengthen A and weaken B togetherLoad shifts from B to ABus voltage unchanged
Strengthen bothBoth take moreBus voltage rises

The third row is the operator's working method. Load transfer and voltage control are separate objectives, and adjusting one field alone changes both at once.

2 Worked Example 32.2 — Adjusting for Equal Sharing

Problem. For the machines of Example 32.1, what EMF must generator B be adjusted to so that the two share the 300 A load equally? What is the bus voltage then?

With each machine at 150 A. Machine A is unchanged, so

\[V = 250 - (0.05)(150) = 250 - 7.5 = 242.5~\mathrm{V}\]

Required EMF of B.

\[E_B = V + I_BR_B = 242.5 + (0.04)(150) = 242.5 + 6 = 248.5~\mathrm{V}\]

So B's field rheostat must be adjusted to raise its no-load EMF from 245 V to 248.5 V.

Comment. Note that the bus voltage has risen from 240.6 V to 242.5 V, because strengthening B's field without weakening A's adds excitation overall. To shift the load without moving the bus voltage, A's field must be weakened at the same time — the third row of Table 32.1.

Note also how small the adjustment is: 3.5 V out of 250, or 1.4 %, moves 39 A of load. Paralleled machines are very sensitive to field settings, which is why load sharing needs careful attention and, in modern installations, automatic control.

Section 32-7

Circulating Current and Motoring

What happens when the external load is removed but both machines remain connected? Their EMFs are unequal, so current still flows — around the loop formed by the two armatures.

🔄
Circulating Current
The stronger machine drives the weaker one as a motor
\[I_c = \frac{E_A - E_B}{R_A + R_B}\]

Machine A delivers this current and machine B absorbs it. B is no longer a generator — it is running as a motor, driven electrically by A and driving its own prime mover.

This is not merely inefficient. If B's prime mover is a diesel engine, it is now being motored; if a steam turbine, it may be damaged by windage heating with no steam flow. Every paralleled machine is therefore protected by a reverse-current relay, which trips its breaker if the current reverses.

3 Worked Example 32.3 — The Machine That Starts Motoring

Problem. For the machines of Example 32.1, find (a) the total load current at which machine B ceases to deliver any current, and (b) the circulating current if the external load is removed entirely.

(a) When B carries nothing. With \(I_B = 0\), machine B has no internal drop, so the bus voltage equals its EMF:

\[V = E_B = 245~\mathrm{V}\]
\[I_A = \frac{E_A - V}{R_A} = \frac{250 - 245}{0.05} = 100~\mathrm{A}\]

So at a total load of 100 A, machine A supplies everything and B floats. Below 100 A, machine B motors.

(b) With no external load. The whole of A's output circulates through B:

\[I_c = \frac{E_A - E_B}{R_A + R_B} = \frac{250 - 245}{0.09} = 55.6~\mathrm{A}\]
\[V = 250 - (0.05)(55.6) = 247.2~\mathrm{V}\]

Check from B's side: \(245 + (0.04)(55.6) = 247.2\) V \(\checkmark\) — note the plus sign, because B is absorbing current.

Comment. Machine B absorbs \((247.2)(55.6) = 13.7\) kW from machine A and delivers it as mechanical power to its own prime mover. A 5 V mismatch in a 250 V system — just 2 % — produces a 55.6 A circulating current, because the only thing limiting it is 0.09 \(\Omega\) of armature resistance.

The lesson generalises: in any parallel connection of low-impedance sources, small voltage differences produce large currents. It is the same arithmetic that gave Chapter 25 its circulating current between unequal armature paths.

Section 32-8

Compound Generators in Parallel

Compound generators are widely used because of the flat or rising characteristic of Chapter 29. That same characteristic makes them unstable in parallel.

! The Runaway

Suppose machine A momentarily takes a little more current. Because it is compound, that extra current flows through its own series field, strengthening it.

  1. A's series field strengthens, so A's EMF rises.
  2. A therefore takes more current still.
  3. Its series field strengthens further, and the process repeats.
  4. Meanwhile B's current falls, so its series field weakens and its EMF falls — accelerating the transfer.

The feedback is positive on both machines at once. A ends up carrying the entire load and driving B as a motor — and since B is now taking reverse current through its series field, B's series field reverses and its EMF collapses completely.

The instability is a direct consequence of Section 32-5. A cumulative compound machine's characteristic is flat or rising, so \(\mathrm{d}V/\mathrm{d}I \ge 0\) and the stabilising negative feedback is absent.

4 Worked Example 32.4 — When Is a Compound Machine Stable?

Problem. A compound generator has an armature-plus-series resistance of 0.03 \(\Omega\). Its series field contributes an EMF rise of \(k_{se}\) volts per ampere of load current. Find the condition on \(k_{se}\) for stable parallel operation, and evaluate for \(k_{se} = 0.02\) and 0.04 V/A.

Net terminal characteristic. The series field raises the EMF while the resistance lowers the terminal voltage:

\[V = E_0 + k_{se}I - I\left(R_a + R_{se}\right) = E_0 + \left(k_{se} - 0.03\right)I\]

Stability condition. From Section 32-5 the slope must be negative:

\[k_{se} - 0.03 \lt 0 \quad\Longrightarrow\quad k_{se} \lt R_a + R_{se} = 0.03~\mathrm{V/A}\]

Case \(k_{se} = 0.02\).

\[\frac{\mathrm{d}V}{\mathrm{d}I} = 0.02 - 0.03 = -0.010~\Omega \qquad\text{drooping - stable}\]

Case \(k_{se} = 0.04\).

\[\frac{\mathrm{d}V}{\mathrm{d}I} = 0.04 - 0.03 = +0.010~\Omega \qquad\text{rising - unstable}\]

Comment. An under-compounded machine, whose characteristic still droops, will parallel without special measures. A flat- or over-compounded machine will not — and those are precisely the machines one wants to use, since they were compounded to hold the voltage up in the first place.

The designer is therefore caught between two requirements: good voltage regulation demands a flat characteristic, and stable paralleling demands a drooping one. The equaliser bar of Section 32-9 resolves the conflict.

Section 32-9

The Equaliser Bar

The whole difficulty lies in one fact: each series field carries its own machine's current, so any imbalance is amplified. The remedy removes exactly that.

🔗
The Equaliser Bar
Put the two series fields in parallel with each other

A heavy, low-resistance conductor — the equaliser bar — connects the armature-side terminals of the two series fields together.

The two series windings are then directly in parallel, so they divide the total current between them in inverse proportion to their resistances, regardless of how the armature currents happen to divide.

\[\frac{I_{se,A}}{I_{se,B}} = \frac{R_{se,B}}{R_{se,A}}\]

The runaway is broken because a machine that takes more armature current no longer gets more series excitation.

A B series field A series field B equaliser bar + bus − bus With the bar fitted: the two series fields are in parallel, so each sees a share of the total current. A machine taking more armature current gets no extra excitation for it.
The equaliser bar joins the two series fields in parallel, breaking the positive-feedback loop.
! The Bar Must Be Heavy

The equaliser carries the difference between the two series-field currents, which can be a substantial fraction of the load. It must be of very low resistance — otherwise the two series fields are not properly in parallel and the equalising action is incomplete.

For the same reason the connection is made as short as possible and the machines are placed close together. A long, thin equaliser is worse than useless: it gives the appearance of protection without the substance.

Series generators, whose characteristics rise steeply, are unstable in parallel for the same reason and to a far greater degree. They too require an equaliser bar, and in practice are seldom paralleled at all.

5 Worked Example 32.5 — Series Field Currents With and Without the Bar

Problem. Two compound generators share a 400 A load, machine A carrying 240 A and machine B 160 A. Their series field resistances are 0.010 \(\Omega\) and 0.012 \(\Omega\). Find the series-field currents (a) without and (b) with an equaliser bar of negligible resistance.

(a) Without the bar. Each series field carries its own machine's armature current:

\[I_{se,A} = 240~\mathrm{A}, \qquad I_{se,B} = 160~\mathrm{A}\]

A ratio of 1.50, so A is excited half again as strongly as B — which drives it to take even more of the load.

(b) With the bar. The two windings are in parallel across it, and divide the total 400 A in inverse proportion to their resistances:

\[\frac{I_{se,A}}{I_{se,B}} = \frac{R_{se,B}}{R_{se,A}} = \frac{0.012}{0.010} = 1.20\]
\[I_{se,A} = 400\left(\frac{1.20}{2.20}\right) = 218.2~\mathrm{A}, \qquad I_{se,B} = 400\left(\frac{1}{2.20}\right) = 181.8~\mathrm{A}\]

Comment. The excitation ratio has fallen from 1.50 to 1.20, and — the decisive point — it no longer depends on how the armature currents divide at all. It is fixed once and for all by the two field resistances.

If A now momentarily takes more armature current, its series excitation does not follow, so its EMF does not rise, so the disturbance does not grow. The positive-feedback loop of Section 32-8 has been cut.

Note that the equaliser itself carries \(240 - 218.2 = 21.8\) A in this condition — modest here, but it can reach a large fraction of the load when the sharing is badly out, which is why the bar must be substantial.

Section 32-10

Summary and Key Formulas

  • Generators are paralleled for continuity, part-load efficiency, maintenance, growth, handling and reserve.

  • The conditions are equal terminal voltage, correct polarity and drooping characteristics. There is no frequency or phase to match.

  • Reversed polarity puts the two EMFs in series around the loop, giving a fault current of \((E_A + E_B)/(R_A + R_B)\).

  • Once paralleled, \(V = E_A - I_AR_A = E_B - I_BR_B\) and \(I_A + I_B = I_L\) determine the sharing completely.

  • Sharing is governed chiefly by the no-load EMFs, and is adjusted by the field rheostats.

  • To shift load without changing the bus voltage, strengthen one field and weaken the other together.

  • A drooping characteristic gives negative feedback and stable sharing; a rising one gives a runaway.

  • On light load a machine with the lower EMF motors, absorbing a circulating current \((E_A - E_B)/(R_A + R_B)\). Reverse-current relays protect against this.

  • Compound generators are unstable in parallel, because extra current strengthens a machine's own series field. Stability requires \(k_{se} \lt R_a + R_{se}\).

  • The equaliser bar puts the series fields directly in parallel, so each sees a share of the total current and the feedback loop is broken. It must be short and of very low resistance.

Table 32.2 — Formulas of this chapter.
QuantityRelationNotes
Common bus voltage\(V = E_A - I_AR_A = E_B - I_BR_B\)the governing constraint
Load division\(I_A + I_B = I_L\)
Machine A's current\(I_A = \dfrac{E_A - E_B + I_LR_B}{R_A + R_B}\)general solution
Equal-EMF sharing\(\dfrac{I_A}{I_B} = \dfrac{R_B}{R_A}\)when \(E_A = E_B\)
Circulating current\(I_c = \dfrac{E_A - E_B}{R_A + R_B}\)no external load
Fault on reversed polarity\(\dfrac{E_A + E_B}{R_A + R_B}\)thousands of amperes
Load at which B floats\(I_L = \dfrac{E_A - E_B}{R_A}\)below this, B motors
Stability condition\(\mathrm{d}V/\mathrm{d}I \lt 0\)drooping characteristic
Compound stability\(k_{se} \lt R_a + R_{se}\)else an equaliser is needed
Series fields with equaliser\(\dfrac{I_{se,A}}{I_{se,B}} = \dfrac{R_{se,B}}{R_{se,A}}\)independent of armature currents
Section 32-11

Common Mistakes

  • Assuming the machines share equally because they are identical in rating. They share according to their EMFs and resistances, not their nameplates.

  • Thinking the machine with the lower resistance takes more load. The EMF difference usually dominates, as Example 32.1 shows.

  • Adjusting one field alone to shift load. That changes the bus voltage too; both rheostats must move together.

  • Forgetting the sign when a machine motors. For an absorbing machine \(V = E + IR\), not \(E - IR\).

  • Omitting the polarity check before closing the switch. A reversed connection is a dead short across both armatures.

  • Believing a rising characteristic merely shares badly. It does not share at all — one machine takes everything.

  • Connecting the equaliser bar to the wrong side of the series field. It must join the armature-side terminals, so the two windings end up in parallel.

  • Using a light conductor for the equaliser. Its resistance must be negligible compared with the series fields, or it does nothing useful.

  • Expecting an equaliser to fix unequal load sharing. It secures stability; the division is still set by the fields.

  • Paralleling a series generator without special measures. Its steeply rising characteristic makes it the least stable of all.

Section 32-12

Chapter Review

Practice Problems

Write the common bus voltage two ways, then use \(I_A + I_B = I_L\). Watch the sign for any machine that is absorbing.

  1. P32.1 Two shunt generators supply 250 A in parallel. A has \(E = 240\) V, \(R_a = 0.06~\Omega\); B has \(E = 235\) V, \(R_a = 0.05~\Omega\). Find the bus voltage and each current.

    Show answer
    \[I_A = \frac{E_A - E_B + I_LR_B}{R_A + R_B} = \frac{240 - 235 + (250)(0.05)}{0.11} = \frac{17.5}{0.11} = 159.1~\mathrm{A}\]
    \[I_B = 250 - 159.1 = 90.9~\mathrm{A}\]
    \[V = 240 - (0.06)(159.1) = 240 - 9.55 = 230.5~\mathrm{V}\]
    Check: \(235 - (0.05)(90.9) = 230.5\) V \(\checkmark\)
  2. P32.2 For P32.1, what must \(E_B\) become for equal sharing at 125 A each?

    Show answer
    \[V = 240 - (0.06)(125) = 232.5~\mathrm{V}\]
    \[E_B = 232.5 + (0.05)(125) = 232.5 + 6.25 = 238.75~\mathrm{V}\]
  3. P32.3 For P32.1, find the circulating current if the load is removed, and identify which machine motors.

    Show answer
    \[I_c = \frac{240 - 235}{0.11} = 45.5~\mathrm{A}\]
    \[V = 240 - (0.06)(45.5) = 237.3~\mathrm{V}\]
    Check: \(235 + (0.05)(45.5) = 237.3\) V \(\checkmark\)

    Machine B motors, since it has the lower EMF. It absorbs about \((237.3)(45.5) = 10.8\) kW.

  4. P32.4 Two generators have equal no-load EMFs of 220 V, with \(R_A = 0.04~\Omega\) and \(R_B = 0.06~\Omega\). They supply 400 A. Find each current.

    Show answer
    With equal EMFs the sharing is inversely proportional to the resistances:
    \[\frac{I_A}{I_B} = \frac{R_B}{R_A} = \frac{0.06}{0.04} = 1.5\]
    \[I_A = 400\left(\frac{1.5}{2.5}\right) = 240~\mathrm{A}, \qquad I_B = 160~\mathrm{A}\]
    \[V = 220 - (0.04)(240) = 210.4~\mathrm{V}\]
  5. P32.5 A generator is connected to a 250 V bus with reversed polarity. Both armature resistances are 0.05 \(\Omega\) and both EMFs 250 V. Find the fault current.

    Show answer
    \[I = \frac{E_A + E_B}{R_A + R_B} = \frac{500}{0.10} = 5000~\mathrm{A}\]
    Twenty times a typical rated current — hence the voltmeter check across the open switch, which would have read 500 V instead of zero.
  6. P32.6 A compound generator has \(R_a + R_{se} = 0.025~\Omega\) and a series field contributing 0.035 V per ampere. Is it stable in parallel? What would make it so?

    Show answer
    \[\frac{\mathrm{d}V}{\mathrm{d}I} = 0.035 - 0.025 = +0.010~\Omega\]
    The characteristic rises, so it is unstable in parallel.

    Remedies: fit an equaliser bar, or reduce the series excitation — by fitting a diverter resistor across the series field — until \(k_{se} \lt 0.025\). The first is preferred, because the second sacrifices the compounding the machine was built for.

  7. P32.7 Explain why a drooping characteristic gives stable load sharing.

    Show answer
    If a machine momentarily takes more than its share, a drooping characteristic makes its terminal voltage fall. Since all machines are tied to one bus voltage, it cannot sustain the excess and falls back.

    The response opposes the disturbance — negative feedback — so the division of load is a stable equilibrium.

    With a rising characteristic the response reinforces the disturbance: more current gives more voltage, which lets the machine take more still. The same distinction decided the stability of the operating point in Chapter 28, where saturation supplied the falling return.

  8. P32.8 Why must a paralleled machine have a reverse-current relay?

    Show answer
    If the machine's EMF falls below the bus voltage — through loss of excitation, loss of speed, or simply because the load has dropped — current flows into it and it runs as a motor.

    It then drives its own prime mover, which may be damaged: a diesel engine is motored against compression, and a steam turbine overheats from windage with no steam flow to cool it. The station also wastes the power absorbed.

    The relay detects the reversal of current direction and trips the machine's breaker, disconnecting it from the bus.

  9. P32.9 Where exactly is the equaliser bar connected, and why there?

    Show answer
    It joins the terminals on the armature side of each series field — the junction between each armature and its own series winding.

    Connected there, the two series windings have one end common (through the bar) and the other end common (through the positive bus), so they are directly in parallel. They then divide the total current in inverse proportion to their resistances.

    Neither machine's series excitation depends on its own armature current any more, which is precisely the feedback path that caused the runaway.

  10. P32.10 Two identical machines share a 500 A load unequally at 300 A and 200 A. Their series fields are each 0.008 \(\Omega\). Find the series-field currents with an equaliser fitted, and the current in the bar.

    Show answer
    Equal resistances, so with the bar the total divides equally:
    \[I_{se,A} = I_{se,B} = \frac{500}{2} = 250~\mathrm{A}\]
    \[I_{\text{bar}} = 300 - 250 = 50~\mathrm{A}\]
    flowing from machine A's junction to machine B's.

    Without the bar the fields would carry 300 A and 200 A, a ratio of 1.5, and A's stronger excitation would drive the imbalance further. With the bar both fields see 250 A whatever the armatures do.

Multiple-Choice Questions
  1. MCQ 1. Generators are operated in parallel chiefly to:
    (a) raise the voltage   (b) improve continuity and part-load efficiency   (c) reduce the current   (d) simplify the switchgear

    Show answer
    (b) improve continuity and part-load efficiency, among the other reasons of Section 32-1.
  2. MCQ 2. Which is not a condition for paralleling DC generators?
    (a) equal terminal voltage   (b) correct polarity   (c) matching frequency   (d) drooping characteristics

    Show answer
    (c) matching frequency — a DC bus has no frequency. That condition belongs to alternators.
  3. MCQ 3. A voltmeter across the open paralleling switch should read:
    (a) twice bus voltage   (b) nearly zero   (c) bus voltage   (d) half bus voltage

    Show answer
    (b) nearly zero when polarity and voltage are correct. About twice bus voltage indicates reversed polarity.
  4. MCQ 4. Two paralleled generators must have the same:
    (a) armature current   (b) EMF   (c) terminal voltage   (d) speed

    Show answer
    (c) terminal voltage, since both are tied to the same bus. Their EMFs generally differ.
  5. MCQ 5. To make a machine take up more load, its field is:
    (a) weakened   (b) strengthened   (c) opened   (d) short-circuited

    Show answer
    (b) strengthened, raising its EMF. The other machine's field must be weakened to hold the bus voltage.
  6. MCQ 6. Stable load sharing requires a characteristic that is:
    (a) rising   (b) flat   (c) drooping   (d) vertical

    Show answer
    (c) drooping, giving negative feedback on the current division.
  7. MCQ 7. On no external load with unequal EMFs, the machine with the lower EMF:
    (a) shuts down   (b) runs as a motor   (c) overspeeds   (d) supplies more current

    Show answer
    (b) runs as a motor, absorbing the circulating current \((E_A - E_B)/(R_A + R_B)\).
  8. MCQ 8. Compound generators are unstable in parallel because:
    (a) their armature resistance is high   (b) extra current strengthens their own series field   (c) they have two windings   (d) their speed varies

    Show answer
    (b) extra current strengthens their own series field, raising the EMF and taking still more current — positive feedback.
  9. MCQ 9. The equaliser bar connects:
    (a) the two field rheostats   (b) the armature-side terminals of the series fields   (c) the negative bus to earth   (d) the two shunt fields

    Show answer
    (b) the armature-side terminals of the series fields, placing the two windings in parallel.
  10. MCQ 10. The equaliser bar must have:
    (a) high resistance   (b) very low resistance   (c) an inductance   (d) a fuse

    Show answer
    (b) very low resistance, or the two series fields are not effectively in parallel and the equalising action is incomplete.
Conceptual Questions
  1. Give the reasons for operating generators in parallel and compare with a single large machine.

  2. State the conditions for paralleling and explain why the list is shorter than for alternators.

  3. Describe the procedure for putting a generator on the bus, explaining the purpose of each step.

  4. Derive the expression for the current supplied by each of two paralleled shunt generators.

  5. Explain why a drooping characteristic is essential for stable sharing.

  6. Explain how load is transferred between machines without disturbing the bus voltage.

  7. Explain how a machine comes to motor on light load and how it is protected.

  8. Explain the instability of paralleled compound generators and how the equaliser bar cures it.

Looking Ahead

Section 32-1 justified paralleling partly on efficiency, asserting that a machine is most efficient near full load. Chapter 33 makes that precise: it gathers the iron loss of Chapter 27, the copper and brush losses of Chapter 26 and the mechanical losses into a complete power-flow diagram, and derives the condition for maximum efficiency — that the variable losses equal the constant ones.

From Chapter 34 the treatment turns to the DC motor. The machine does not change; only the direction of energy flow does. Back EMF, the torque constant \(k_a\Phi\), armature reaction and commutation all reappear, and Chapter 36 confronts the problem Chapter 21 raised and left open: a motor at rest has no back EMF, so its starting current would be twenty times rated unless something is done about it.