Electrical Machines · Chapter 27

EMF Equation of a DC Generator

Part 2 · DC Machines — five quantities decide the voltage of every DC machine ever built. Three are fixed when the armature is wound; only two can be changed while it runs.

Prof. Mithun Mondal Engineering Devotion Digital Textbook
i Learning Objectives

By the end of this chapter you should be able to:

  • Derive the EMF equation \(E_g = \Phi PNZ/60A\) from Faraday's law.

  • Write it in its compact forms \(E_g = k\Phi N = k_a\Phi\omega\) and convert between them.

  • Explain why the same constant \(k_a\) relates torque to armature current.

  • Apply the equation to lap and wave windings and predict the voltage ratio.

  • Compute the frequency of the armature EMF and its consequence for iron loss.

  • Carry out a design calculation: find \(Z\), choose slots, conductors per slot and turns per coil.

  • Check a design against the volts-per-segment limit.

  • Step from generated EMF to terminal voltage for any machine type.

Section 27-1

The Equation Derived

Chapter 21 obtained this result while establishing the working principle. It is restated here because Chapters 28 to 39 use it constantly, and because the derivation repays a second reading now that the winding is understood.

Let

\[\begin{aligned} \Phi &= \text{flux per pole, in weber} \\ Z &= \text{total number of armature conductors} \\ P &= \text{number of poles} \\ A &= \text{number of parallel paths} \\ N &= \text{speed in rev/min} \\ E_g &= \text{generated emf, equal to that in any one parallel path} \end{aligned}\]
The Four Steps
  1. Flux cut per revolution. Each conductor passes every pole once per revolution, so it cuts \(\mathrm{d}\Phi = \Phi P\) weber.
  2. Time per revolution. At \(N\) rev/min the armature makes \(N/60\) revolutions per second, so \(\mathrm{d}t = 60/N\) seconds.
  3. EMF per conductor. By Faraday's law with one turn, \(e = \mathrm{d}\Phi/\mathrm{d}t = \Phi PN/60\) volts.
  4. Conductors in series per path. The \(Z\) conductors divide equally among \(A\) paths, giving \(Z/A\) in series. Series EMFs add.
🎯
The EMF Equation
The central equation of Part 2
\[E_g = \frac{\Phi PN}{60}\times\frac{Z}{A} = \frac{\Phi PNZ}{60A} \qquad\text{volts}\]
\[A = P \ \text{(lap)}, \qquad A = 2 \ \text{(wave)}\]
Note what the parallel paths do. They appear in the denominator, so more paths mean less voltage. This is not a defect: the paths are in parallel, so they share the current instead of adding their voltages. The armature has a fixed amount of copper cutting a fixed flux at a fixed speed, and \(A\) decides only whether that capability is delivered as volts or as amperes — exactly the point Chapter 25's Example 25.5 made numerically.
Section 27-2

Alternative Forms

For a given machine \(Z\), \(P\) and \(A\) are fixed once the armature is wound. Only \(\Phi\) and \(N\) can change while it runs, so the equation collapses to

\[E_g = k\,\Phi N \qquad\text{where}\qquad k = \frac{ZP}{60A}\]

and in terms of angular velocity, substituting \(N = 60\omega/2\pi\):

\[E_g = k_a\,\Phi\omega \qquad\text{where}\qquad k_a = \frac{ZP}{2\pi A}\]
Table 27.1 — The forms of the EMF equation and when to use each.
FormConstantSpeed unitUse it when
\(E_g = \dfrac{\Phi PNZ}{60A}\)rev/minDesigning: every quantity explicit
\(E_g = k\Phi N\)\(k = \dfrac{ZP}{60A}\)rev/minRatio problems on one machine
\(E_g = k_a\Phi\omega\)\(k_a = \dfrac{ZP}{2\pi A}\)rad/sPower and torque work
\(E_g \propto \Phi N\)eitherQuickest of all
050010001500 0100200300400 speed N (rev/min) E_g (V) 30 mWb 25 mWb 20 mWb 250 V at 1000 rev/min E_g = k Φ N — a straight line through the origin for each flux.
Generated EMF against speed for a 6-pole lap machine with \(Z = 500\), so \(k = 8.33\).

Every line passes through the origin, because a stationary armature generates nothing whatever the flux. The lines are straight only while the flux is held constant; if the flux itself is produced by a field current, saturation bends the relationship between \(E_g\) and \(I_f\) — which is the magnetisation curve of Chapter 28.

1 Worked Example 27.1 — Finding the Conductor Count

Problem. A 6-pole DC generator is to give 250 V at 1000 rev/min with a flux of 30 mWb per pole. How many armature conductors are needed if the winding is (a) lap and (b) wave?

Rearranging.

\[Z = \frac{60AE_g}{\Phi PN}\]

(a) Lap winding (\(A = P = 6\)):

\[Z = \frac{(60)(6)(250)}{(0.030)(6)(1000)} = \frac{90\,000}{180} = 500~\text{conductors}\]

(b) Wave winding (\(A = 2\)):

\[Z = \frac{(60)(2)(250)}{180} = \frac{30\,000}{180} = 166.7 \quad\Longrightarrow\quad 168~\text{conductors}\]

The wave figure must be rounded to a whole even number compatible with the slot count — and checked against the integer condition of Chapter 25. With \(Z = 168\) and \(P = 6\), \(Y_A = (168 - 2)/6 = 27.67\) and \((168 + 2)/6 = 28.33\), neither an integer — so \(Z\) must be adjusted further, to 166 (giving \(Y_A = 28\)) with a dummy coil if necessary.

Comment. The wave winding needs almost exactly one-third the conductors, the ratio being \(2/P = 2/6\). That is a large saving in copper, slot space and cost — and it is precisely why wave windings are preferred whenever the current is low enough to permit only two parallel paths.

Section 27-3

The Machine Constant

The constant \(k_a = ZP/2\pi A\) does more than shorten the EMF equation. It also relates torque to armature current, and the reason is simple energy conservation.

The power converted from mechanical to electrical form is \(E_gI_a\), and it equals the mechanical power \(T\omega\):

\[T\omega = E_gI_a = \left(k_a\Phi\omega\right)I_a\]
🔗
One Constant, Two Equations
The same \(k_a\) serves EMF and torque
\[E_g = k_a\Phi\omega \qquad\qquad T = k_a\Phi I_a\]

Cancelling \(\omega\) from both sides of the power balance leaves the torque equation immediately. No new physics is needed — the torque constant and the EMF constant are the same number, which is why a DC machine works equally well in both directions.

In SI units this is exact: a machine with \(k_a\Phi = 2.0\) generates 2.0 V per rad/s and produces 2.0 N·m per ampere. Chapter 34 derives the torque equation independently and arrives at the same place, but the argument above shows it could not have come out otherwise.

2 Worked Example 27.2 — EMF and Torque from One Constant

Problem. The 6-pole lap machine of Example 27.1 has \(Z = 500\), \(\Phi = 30\) mWb and runs at 1000 rev/min carrying an armature current of 80 A. Find \(k_a\), the generated EMF, the converted power and the torque.

Machine constant.

\[k_a = \frac{ZP}{2\pi A} = \frac{(500)(6)}{2\pi(6)} = \frac{500}{2\pi} = 79.58\]

Angular velocity.

\[\omega = \frac{2\pi N}{60} = \frac{2\pi(1000)}{60} = 104.72~\mathrm{rad/s}\]

Generated EMF.

\[E_g = k_a\Phi\omega = (79.58)(0.030)(104.72) = 250.0~\mathrm{V}\]

Agreeing with Example 27.1, as it must.

Converted power.

\[P = E_gI_a = (250.0)(80) = 20\,000~\mathrm{W}\]

Torque.

\[T = k_a\Phi I_a = (79.58)(0.030)(80) = 191.0~\mathrm{N\,m}\]

Check: \(T = P/\omega = 20\,000/104.72 = 191.0\) N·m \(\checkmark\)

Comment. Note that \(k_a\Phi = (79.58)(0.030) = 2.387\), so this machine generates 2.387 V per rad/s and delivers 2.387 N·m per ampere. Motor manufacturers quote exactly this number — as the "voltage constant" or the "torque constant" — and the two are always numerically equal in SI units, though catalogues often disguise the fact by quoting one in V/krpm and the other in N·m/A.

Section 27-4

Effect of the Winding Type

Since \(A\) is the only term the winding decides, its effect follows at once:

\[\frac{E_{\text{wave}}}{E_{\text{lap}}} = \frac{A_{\text{lap}}}{A_{\text{wave}}} = \frac{P}{2}\]
Table 27.2 — The winding factor on voltage and current, for the same armature.
Poles \(P\)\(A\) lap\(A\) waveVoltage ratioCurrent ratio
22211
44221/2
66231/3
88241/4

The product of the two ratios is always unity, so the power is identical — the result established in Chapter 25. Note the first row: in a two-pole machine lap and wave are the same winding, since \(A = 2\) either way.

Section 27-5

Frequency of the Armature EMF

Chapter 21 insisted that the EMF inside the armature is alternating. Its frequency follows from the same reasoning as the EMF itself: a conductor completes one full cycle each time it passes a pair of poles.

Armature Frequency
The frequency the iron actually sees
\[f = \frac{PN}{120} \qquad\mathrm{Hz}\]

With \(P/2\) cycles per revolution and \(N/60\) revolutions per second, \(f = (P/2)(N/60) = PN/120\).

This is not an academic quantity. The armature iron is magnetised alternately north and south at this frequency, so from Chapters 6 and 7:

\[P_h \propto f, \qquad P_e \propto f^{2}\]

and both rise as the machine is speeded up. This is why a DC machine's iron loss is speed-dependent while its copper loss is not — a distinction that becomes important in the efficiency testing of Chapter 33.

3 Worked Example 27.3 — Frequency and Iron Loss

Problem. Find the armature frequency of a 6-pole machine at 1000 rev/min. If its iron loss at that speed is 300 W of hysteresis and 200 W of eddy current, find the total iron loss at 1500 rev/min.

Frequency at 1000 rev/min.

\[f = \frac{PN}{120} = \frac{(6)(1000)}{120} = 50~\mathrm{Hz}\]

Frequency at 1500 rev/min.

\[f = \frac{(6)(1500)}{120} = 75~\mathrm{Hz}\]

a ratio of 1.5, as it must be since \(f \propto N\).

Losses at the higher speed. Assuming the flux is held constant,

\[P_h' = 300(1.5) = 450~\mathrm{W}, \qquad P_e' = 200(1.5)^{2} = 200(2.25) = 450~\mathrm{W}\]
\[P_{\text{iron}}' = 450 + 450 = 900~\mathrm{W}\]

Ratio.

\[\frac{900}{500} = 1.80\]

Comment. A 50 % increase in speed has produced an 80 % increase in iron loss, because the eddy-current component grows as the square. Notice that the two components, unequal at 50 Hz, are exactly equal at 75 Hz — a useful reminder that eddy loss overtakes hysteresis loss at high frequency, which is why lamination thickness matters more in fast machines.

The compensation is that the EMF has also risen by 50 %, so at the same current the output has risen by 50 % while the iron loss rose by 80 %. The efficiency therefore falls slightly — one more reason a DC machine cannot simply be speeded up for more power.

Section 27-6

Design Calculations

In practice the EMF equation is used backwards. The voltage, speed and flux are given by the specification; the designer must find a conductor count and then a physically buildable arrangement of slots and coils.

  1. Find \(Z\) from \(Z = 60AE_g/\Phi PN\).
  2. Choose the slot number \(S\) so that \(Z/S\) is an even integer — the conductors per slot must divide into two layers.
  3. Deduce the turns per coil, \(T = Z/2S\) for a double-layer winding with one coil per slot.
  4. Check the volts per segment, \(EP/C\) for lap with \(C = S\), against the 15 V limit of Chapter 22.
  5. Check the winding is possible — parity of \(Y_B\) and \(Y_F\) for lap, the integer condition for wave (Chapter 25).
Step 4 is the one that usually bites. The EMF equation is satisfied by any combination of slots and turns giving the right \(Z\), so a beginner picks the smallest slot count that works — and produces a machine that flashes over across its commutator. The volts-per-segment check is what forces the slot count up, often by a factor of two, as Example 27.4 shows.
4 Worked Example 27.4 — A Complete Armature Design

Problem. Design the armature of a 4-pole lap-wound generator to give 220 V at 1000 rev/min with a flux of 20 mWb per pole. Find the conductor count and choose a workable slot number, conductors per slot and turns per coil.

Step 1 — conductor count.

\[Z = \frac{60AE_g}{\Phi PN} = \frac{(60)(4)(220)}{(0.020)(4)(1000)} = \frac{52\,800}{80} = 660~\text{conductors}\]

Steps 2 to 4 — trying slot numbers. Each must divide 660 into an even number of conductors per slot, and the volts per segment must satisfy \(EP/C \le 15\) V with \(C = S\):

Table 27.3 — Candidate designs for \(Z = 660\), 4-pole lap, 220 V.
Slots \(S\)Conductors/slotTurns/coil \(T\)Segments \(C\)\(V_{\text{seg}} = EP/C\)Verdict
3320103326.67 VRejected — flashover risk
551265516.00 VRejected — still above 15 V
661056613.33 VAccepted

Verifying the accepted design.

\[Z = 2CT = (2)(66)(5) = 660 \ \checkmark\]
\[V_{\text{seg}} = \frac{EP}{C} = \frac{(220)(4)}{66} = 13.33~\mathrm{V} \ \checkmark\]

Step 5 — winding check. With \(Z = 660\) and \(P = 4\), the average pitch is \(Z/P = 165\) conductors, so for a simplex lap winding \(Y_B = 166\) and \(Y_F = 164\) — both even, which is inadmissible. Taking \(Y_A = 164\) instead gives \(Y_B = 165\) and \(Y_F = 163\), both odd \(\checkmark\)

Comment. The EMF equation alone was satisfied by all three candidates — every one of them produces exactly 220 V. What separates them is the commutator, not the magnetics, and the 33-slot design would have been a perfectly good generator on paper and a fire on the test bed.

Note also that the accepted design has twice the slots and half the turns per coil of the rejected one. That has a further benefit Chapter 24 noted: with \(L \propto T^{2}\), halving the turns per coil quarters the coil inductance and so quarters the reactance voltage of Chapter 23.

Section 27-7

From EMF to Terminal Voltage

The EMF equation gives what the armature generates. What appears at the terminals is less, by the drops of Chapter 26.

Table 27.4 — Getting from \(E_g\) to \(V\).
MachineTerminal voltage
Separately excited or shunt generator\(V = E_g - I_aR_a - 2v_b\)
Series or long-shunt generator\(V = E_g - I_a(R_a + R_{se}) - 2v_b\)
Short-shunt generator\(V = E_g - I_aR_a - I_LR_{se} - 2v_b\)
Any motor\(E_b = V - I_aR_a - 2v_b\) (add \(R_{se}\) if present)

The chain of reasoning for a complete problem therefore runs: flux and speed give \(E_g\); \(E_g\) and the drops give \(V\); \(V\) and the load give the currents — and in a shunt machine that last step feeds back into the second, which is why Chapter 26's Example 26.2 needed a simultaneous solution.

5 Worked Example 27.5 — From Flux to Terminals

Problem. A 4-pole wave-wound shunt generator has 500 conductors and runs at 1200 rev/min with a flux of 25 mWb per pole. The armature resistance is 0.10 \(\Omega\), the shunt field 200 \(\Omega\), brush drop 1 V per brush. It delivers 90 A. Find the generated EMF and the terminal voltage.

Generated EMF. Wave-wound, so \(A = 2\):

\[E_g = \frac{\Phi PNZ}{60A} = \frac{(0.025)(4)(1200)(500)}{(60)(2)} = \frac{60\,000}{120} = 500~\mathrm{V}\]

Terminal voltage. The shunt field current depends on \(V\), so solve as in Chapter 26:

\[V\left(1 + \frac{R_a}{R_{sh}}\right) = E_g - I_LR_a - 2v_b\]
\[V\left(1 + \frac{0.10}{200}\right) = 500 - (90)(0.10) - 2 = 489\]
\[V = \frac{489}{1.0005} = 488.76~\mathrm{V}\]

Currents.

\[I_{sh} = \frac{488.76}{200} = 2.444~\mathrm{A}, \qquad I_a = 90 + 2.444 = 92.44~\mathrm{A}\]

Check: \(500 - (92.44)(0.10) - 2 = 500 - 9.244 - 2 = 488.76\) V \(\checkmark\)

Powers.

\[P_{\text{dev}} = E_gI_a = (500)(92.44) = 46\,220~\mathrm{W}\]
\[P_{\text{out}} = VI_L = (488.76)(90) = 43\,988~\mathrm{W}\]

Comment. The whole chapter in one calculation: the winding data and the flux give the EMF, the circuit gives the terminal voltage, and the difference — 2.2 kW, or 4.8 % of the developed power — is what the armature resistance, the brushes and the field consume between them.

Had this machine been lap-wound, its EMF would have been only 250 V and it would have needed twice the conductors for the same voltage. At 90 A the wave winding's two paths carry 46 A each, which is entirely reasonable — so wave is the right choice here.

Section 27-8

Applications

Armature Design

The equation is inverted to find \(Z\), then the slot and coil arrangement follows from the volts-per-segment and winding-parity checks.

Speed Control

Since \(E \propto \Phi N\), a motor's speed is set by the voltage it must balance and the flux available — the two methods of Chapter 37.

Tachogenerators

With the flux fixed by a permanent magnet, \(E \propto N\) exactly, giving a voltage that is a direct linear measure of speed.

Motor Constants

The \(k_a\Phi\) of Section 27-3 is what a catalogue calls the torque constant or back-EMF constant — the same number in SI units.

Loss Prediction

The armature frequency \(PN/120\) fixes the hysteresis and eddy-current losses, which is why iron loss varies with speed but copper loss does not.

Fault Diagnosis

A machine generating below specification has lost flux, speed or conductors. Since \(Z\) cannot change, a low output points to weak field or a slipping drive.

Section 27-9

Summary and Key Formulas

  • The EMF equation is \(E_g = \Phi PNZ/60A\), from flux cut per revolution \(\Phi P\), time per revolution \(60/N\), and \(Z/A\) conductors in series per path.

  • Compactly, \(E_g = k\Phi N\) with \(k = ZP/60A\), or \(E_g = k_a\Phi\omega\) with \(k_a = ZP/2\pi A\). Always, \(E_g \propto \Phi N\).

  • The same constant gives the torque: \(T = k_a\Phi I_a\), which follows from \(T\omega = E_gI_a\).

  • Because \(A\) is in the denominator, more paths mean less voltage, and \(E_{\text{wave}}/E_{\text{lap}} = P/2\).

  • The armature frequency is \(f = PN/120\). Hysteresis loss varies as \(f\) and eddy loss as \(f^{2}\), so iron loss is speed-dependent.

  • Design procedure: find \(Z\); choose \(S\) so \(Z/S\) is even; deduce \(T = Z/2S\); check \(EP/C \le 15\) V; check the winding parity or integer condition.

  • The volts-per-segment check usually forces a higher slot count than the EMF equation alone would suggest.

  • Terminal voltage follows by subtracting the armature, series-field and brush drops appropriate to the machine type.

Table 27.5 — Formulas of this chapter.
QuantityFormulaNotes
Generated EMF\(E_g = \dfrac{\Phi PNZ}{60A}\)the design form
Compact, rev/min\(E_g = k\Phi N\), \(k = \dfrac{ZP}{60A}\)ratio problems
Compact, rad/s\(E_g = k_a\Phi\omega\), \(k_a = \dfrac{ZP}{2\pi A}\)power and torque
Torque\(T = k_a\Phi I_a\)same \(k_a\)
Angular velocity\(\omega = 2\pi N/60\)
Conductor count\(Z = \dfrac{60AE_g}{\Phi PN}\)design step 1
Turns per coil\(T = Z/2S\)double layer, one coil/slot
Volts per segment\(EP/C\), \(C = S\)keep \(\le 15\) V
Armature frequency\(f = PN/120\)
Voltage ratio\(E_{\text{wave}}/E_{\text{lap}} = P/2\)same armature
Iron loss scaling\(P_h \propto N\), \(P_e \propto N^{2}\)at constant flux
Section 27-10

Common Mistakes

  • Putting \(A\) in the numerator. Parallel paths divide the conductors, so \(A\) belongs in the denominator.

  • Confusing \(P\) with \(A\). They cancel for a lap winding, giving \(E = \Phi NZ/60\), but not for wave.

  • Leaving the flux in milliweber. It must be in weber before substitution.

  • Using \(\omega\) in the \(60\) form or \(N\) in the \(2\pi\) form. The constants differ by \(2\pi/60\).

  • Treating the torque constant as a different number from the EMF constant. In SI units they are identical.

  • Using \(f = PN/60\). One cycle takes a pair of poles, so the divisor is 120.

  • Accepting the first slot count that gives the right \(Z\). The volts-per-segment limit must also be met.

  • Assuming iron loss is constant. It varies with speed through \(f\); only copper loss is speed-independent.

  • Forgetting the wave-winding integer condition after rounding \(Z\) up from a fractional design value.

  • Stopping at \(E_g\). The terminal voltage is lower by the armature, series-field and brush drops.

Section 27-11

Chapter Review

Practice Problems

List \(\Phi\) (in weber), \(P\), \(N\), \(Z\) and \(A\) before substituting — and state which winding type fixes \(A\).

  1. P27.1 A 4-pole lap generator has 720 conductors, 25 mWb per pole, at 900 rev/min. Find \(E_g\).

    Show answer
    \[E_g = \frac{(0.025)(4)(900)(720)}{(60)(4)} = \frac{64\,800}{240} = 270~\mathrm{V}\]
  2. P27.2 Repeat P27.1 for a wave winding, and state the current ratio.

    Show answer
    \[E_g = \frac{64\,800}{(60)(2)} = 540~\mathrm{V}\]
    Twice the lap value, since \(P/2 = 2\). The current capability is halved, so the power is unchanged.
  3. P27.3 A 6-pole wave generator must give 400 V at 800 rev/min with 30 mWb per pole. Find \(Z\).

    Show answer
    \[Z = \frac{60AE_g}{\Phi PN} = \frac{(60)(2)(400)}{(0.030)(6)(800)} = \frac{48\,000}{144} = 333.3\]
    So 334 conductors, rounded up — then checked against the wave integer condition: \((334 + 2)/6 = 56\), an integer \(\checkmark\)
  4. P27.4 A generator gives 200 V at 800 rev/min. Find the EMF at 1000 rev/min with the flux reduced by 15 %.

    Show answer
    Since \(E \propto \Phi N\):
    \[E = 200\left(\frac{1000}{800}\right)(0.85) = 200(1.25)(0.85) = 212.5~\mathrm{V}\]
  5. P27.5 An 8-pole lap machine has \(Z = 800\). Find \(k\) and \(k_a\), and the EMF at 20 mWb and 600 rev/min.

    Show answer
    \[k = \frac{ZP}{60A} = \frac{(800)(8)}{(60)(8)} = 13.33, \qquad k_a = \frac{ZP}{2\pi A} = \frac{800}{2\pi} = 127.3\]
    \[E_g = k\Phi N = (13.33)(0.020)(600) = 160~\mathrm{V}\]
    Check by the other form: \(\omega = 2\pi(600)/60 = 62.83\) rad/s, and \((127.3)(0.020)(62.83) = 160\) V \(\checkmark\)
  6. P27.6 For the machine of P27.5 carrying 50 A, find the torque and the converted power.

    Show answer
    \[T = k_a\Phi I_a = (127.3)(0.020)(50) = 127.3~\mathrm{N\,m}\]
    \[P = E_gI_a = (160)(50) = 8000~\mathrm{W}\]
    Check: \(T = P/\omega = 8000/62.83 = 127.3\) N·m \(\checkmark\)
  7. P27.7 Find the armature frequency of a 4-pole machine at 1500 rev/min, and of a 12-pole machine at 500 rev/min.

    Show answer
    \[f = \frac{(4)(1500)}{120} = 50~\mathrm{Hz}, \qquad f = \frac{(12)(500)}{120} = 50~\mathrm{Hz}\]
    Both 50 Hz — the pole count and speed trade off exactly, which is why slow machines need many poles.
  8. P27.8 A machine's iron loss is 800 W at 1000 rev/min, of which two-thirds is hysteresis. Find the loss at 1400 rev/min at constant flux.

    Show answer
    \[P_h = 533~\mathrm{W}, \qquad P_e = 267~\mathrm{W}, \qquad r = 1.4\]
    \[P_h' = (533)(1.4) = 747~\mathrm{W}, \qquad P_e' = (267)(1.96) = 523~\mathrm{W}\]
    \[P_{\text{iron}}' = 747 + 523 = 1270~\mathrm{W}\]
    A 40 % speed rise gives a 59 % loss increase.
  9. P27.9 A 4-pole lap machine needs \(Z = 480\) and generates 300 V. Find the minimum slot number satisfying the 15 V per segment limit.

    Show answer
    \[\frac{EP}{C} \le 15 \quad\Longrightarrow\quad C \ge \frac{(300)(4)}{15} = 80\]
    With \(C = S\), at least 80 slots. Then conductors per slot \(= 480/80 = 6\), giving 3-turn coils.

    A choice of, say, 60 slots would give 8 conductors per slot and 4-turn coils, but \(V_{\text{seg}} = 1200/60 = 20\) V — above the limit.

  10. P27.10 Explain why a DC machine's iron loss depends on speed but its copper loss does not.

    Show answer
    Iron loss arises from the alternating magnetisation of the armature core at frequency \(f = PN/120\). Since \(P_h \propto f\) and \(P_e \propto f^{2}\), both rise directly with speed.

    Copper loss is \(I^{2}R\) and depends only on the current the load draws and the resistance of the winding — neither of which the speed affects.

    This is exactly why the Swinburne test of Chapter 33 can measure the two separately: run the machine on no load at rated speed and the iron loss is present while the copper loss is negligible.

Multiple-Choice Questions
  1. MCQ 1. In the EMF equation, the number of parallel paths appears:
    (a) in the numerator   (b) in the denominator   (c) squared   (d) not at all

    Show answer
    (b) in the denominator — more paths mean fewer conductors in series and so less EMF.
  2. MCQ 2. For a lap winding the EMF equation reduces to:
    (a) \(\Phi NZ/60\)   (b) \(\Phi NZ/120\)   (c) \(\Phi PNZ/60\)   (d) \(\Phi NZ/2\)

    Show answer
    (a) \(\Phi NZ/60\), since \(A = P\) and the two cancel.
  3. MCQ 3. The generated EMF is proportional to:
    (a) \(\Phi + N\)   (b) \(\Phi N\)   (c) \(\Phi/N\)   (d) \(\Phi N^{2}\)

    Show answer
    (b) \(\Phi N\).
  4. MCQ 4. The machine constant \(k_a\) equals:
    (a) \(ZP/60A\)   (b) \(ZP/2\pi A\)   (c) \(ZA/2\pi P\)   (d) \(60A/ZP\)

    Show answer
    (b) \(ZP/2\pi A\), for use with \(\omega\) in rad/s.
  5. MCQ 5. The torque of a DC machine is:
    (a) \(k_a\Phi\omega\)   (b) \(k_a\Phi I_a\)   (c) \(k_aI_a\omega\)   (d) \(k_a\Phi/I_a\)

    Show answer
    (b) \(k_a\Phi I_a\) — the same constant as the EMF equation.
  6. MCQ 6. The armature frequency of a DC machine is:
    (a) \(PN/60\)   (b) \(PN/120\)   (c) \(120P/N\)   (d) zero

    Show answer
    (b) \(PN/120\), since one cycle requires a pair of poles.
  7. MCQ 7. Doubling the speed at constant flux multiplies the eddy-current loss by:
    (a) 1   (b) 2   (c) 4   (d) 8

    Show answer
    (c) 4, since \(P_e \propto f^{2}\) and \(f \propto N\).
  8. MCQ 8. Rewinding a 6-pole armature from lap to wave multiplies the EMF by:
    (a) 2   (b) 3   (c) 6   (d) 1/3

    Show answer
    (b) 3, the ratio \(P/2\).
  9. MCQ 9. In an armature design, the volts-per-segment check usually:
    (a) reduces the slot count   (b) increases the slot count   (c) has no effect   (d) changes the flux

    Show answer
    (b) increases the slot count, because more coils are needed to divide the voltage more finely.
  10. MCQ 10. If flux is halved and speed doubled, the generated EMF is:
    (a) halved   (b) doubled   (c) unchanged   (d) quadrupled

    Show answer
    (c) unchanged, since \(E \propto \Phi N\) and the product is the same.
Conceptual Questions
  1. Derive the EMF equation from Faraday's law, justifying each of the four steps.

  2. Explain why the number of parallel paths appears in the denominator.

  3. Show that the EMF constant and the torque constant are the same number, and explain physically why they must be.

  4. Explain the effect of choosing lap or wave on voltage, current and power.

  5. Derive the armature frequency and explain its consequences for iron loss.

  6. Set out the steps of an armature design and explain which check usually dominates.

  7. Explain the chain of reasoning from flux and speed to terminal voltage in a shunt generator, and why it requires a simultaneous solution.

Looking Ahead

The EMF equation assumes the flux is known. In a self-excited machine it is not — the flux depends on the field current, which depends on the voltage, which depends on the flux. Chapter 28 resolves that circle with the magnetisation curve and the field-resistance line, and derives the critical field resistance above which a shunt generator will not build up at all, and the critical speed below which it likewise fails.

Chapter 29 then plots the characteristics of every generator type — open-circuit, internal and external — and shows why the shunt machine droops while the series machine rises. The \(I_aR_a\) drop of Section 27-7 is one reason for the droop; Chapter 30's armature reaction is the other, and the more interesting.