Solved Problems · Set 11

Three-Phase Diode Rectifiers

Part 2 · AC–DC Converters — three phases hand the conduction round six times a cycle, so the output never falls far from the peak. Six problems on the pulse number that does most of the filtering for free.

Prof. Mithun Mondal 6 solved problems GATE · ESE · University

Set 11 — Three-Phase Diode Rectifiers

A single-phase bridge produces an output that falls to zero twice per cycle, which is why Set 10 needed 4000 µF to make it usable. Three phases remove most of that problem before any filter is fitted. At every instant one phase is nearer its peak than the others, and the rectifier simply connects the load to whichever that is — so the output is the envelope of three staggered sinusoids and never falls far below the peak.

The organising idea is the pulse number \(p\) — how many times per cycle the conduction hands over. Everything follows from it: the average output, the RMS, the ripple factor, the ripple frequency and the harmonic orders. One formula covers the three-pulse circuit, the six-pulse bridge and the twelve-pulse connection, and Problem 5 shows why the industry keeps going to higher \(p\).

Part 2 · Chapter 7 · 6 solved problems

i Method Recap
  • One formula covers every pulse number. For a \(p\)-pulse rectifier whose conducting waveform has peak \(V_m\):

    \[ V_{dc} = \frac{p}{\pi}V_m\sin\frac{\pi}{p}, \qquad V_{rms} = V_m\sqrt{\frac12+\frac{p}{4\pi}\sin\frac{2\pi}{p}} \]

    Use the phase peak for the three-pulse circuit and the line peak for the bridge — that is the only difference between them.

  • Ripple and ripple frequency both improve with \(p\):

    \[ RF = \sqrt{\left(\frac{V_{rms}}{V_{dc}}\right)^2-1}, \qquad f_{ripple} = p\,f \]
  • With an inductive load each diode conducts 120°, so the device currents follow immediately:

    \[ I_{D,avg} = \frac{I_{dc}}{3}, \qquad I_{D,rms} = \frac{I_{dc}}{\sqrt3} \]
  • The line current is a 120° quasi-square wave:

    \[ I_s = I_{dc}\sqrt{\frac23}, \qquad I_{s1} = \frac{\sqrt6}{\pi}I_{dc}, \qquad \frac{I_{s1}}{I_s} = \frac{3}{\pi} = 0.955 \]
  • Harmonics obey the pulse-number rule. A \(p\)-pulse converter draws only:

    \[ n = pk\pm1, \qquad I_n = \frac{I_{s1}}{n} \]

    So a six-pulse bridge has 5th, 7th, 11th, 13th — and no triplens at all — Problem 4.

  • The exact six-pulse distortion is a closed form worth remembering:

    \[ THD = \sqrt{\frac{\pi^2}{9}-1} = 31.08\% \]
Problem 1CoreThree Pulses

A three-phase half-wave (three-pulse) rectifier is supplied from a 415 V, 50 Hz three-phase system. Find the phase and peak voltages, the average and RMS output, the form and ripple factors, the ripple frequency, and the peak inverse voltage.

Vdc 280 339 V each phase conducts 120°
The rectifier follows whichever phase is highest — so the output never reaches zero
Solution

Establish the voltages. A three-pulse rectifier connects each phase to the load in turn, so the relevant peak is the phase peak:

\[ V_{ph} = \frac{415}{\sqrt3} = 239.6\ \text{V}, \qquad V_{m(ph)} = \sqrt2\,(239.6) = 338.8\ \text{V} \]

Each phase conducts for 120° — from 30° before its peak to 30° after — because that is the interval during which it is the highest of the three. Averaging over that window:

\[ V_{dc} = \frac{3}{2\pi}\int_{\pi/6}^{5\pi/6}V_{m}\sin\theta\,d\theta = \frac{3\sqrt3}{2\pi}V_{m(ph)} \]
\[ = (0.827)(338.8) = 280.2\ \text{V} \]

Which is the general \(p\)-pulse formula with \(p = 3\): \(\left(3/\pi\right)\sin60^\circ = 0.827\). The output is 83% of the phase peak, against the single-phase half-wave's 32%.

The RMS, from the same window:

\[ V_{rms} = V_m\sqrt{\frac12+\frac{3}{4\pi}\sin\frac{2\pi}{3}} = (338.8)(0.8407) = 284.9\ \text{V} \]

Form and ripple factor:

\[ FF = \frac{284.9}{280.2} = 1.0166, \qquad RF = \sqrt{1.0335-1} = 0.183 = 18.3\% \]

Against 121% for single-phase half-wave and 48.3% for the single-phase bridge. Three phases alone, with no filter and no extra devices beyond two more diodes, have cut the ripple by a factor of 2.6 relative to a full bridge.

Ripple frequency and blocking voltage:

\[ f_{ripple} = 3f = 150\ \text{Hz} \]
\[ \text{PIV} = \sqrt3\,V_{m(ph)} = V_{m(line)} = 586.9\ \text{V} \]

The PIV is the line peak, not the phase peak, because a blocked diode has its own phase on the anode and the conducting phase on the cathode — and the difference between two phases is a line voltage. This catches people out reliably.

One defect remains. Each phase carries current in one direction only, so the supply sees a DC component in every phase:

\[ I_{ph,dc} = \frac{I_{dc}}{3} \ne 0 \]

That DC magnetises the supply transformer's core and drives it toward saturation, exactly as in the single-phase half-wave circuit of Set 9. It is the reason the three-pulse connection is rarely used on its own, and why the bridge of Problem 2 — which draws no DC at all — is the standard.

Pulse number does the filtering that capacitors would otherwise buy. Going from one pulse to three took the ripple factor from 121% to 18.3% by rearranging the supply rather than adding energy storage. That is the whole argument of this set, and Problem 2 pushes it one step further.
Answera\(V_{ph} = 239.6\ \text{V},\ V_m = 338.8\ \text{V}\)   b\(V_{dc} = 280.2\ \text{V},\ V_{rms} = 284.9\ \text{V}\)   c\(RF = 18.3\%\)   d\(150\ \text{Hz},\ \text{PIV} = 587\ \text{V}\)
Problem 2CoreSix Pulses

The same 415 V supply now feeds a three-phase bridge. Find the average and RMS output, the ripple factor and frequency, the PIV, and tabulate the comparison across all the rectifiers met so far.

Solution

The bridge works on line voltages. At any instant one diode of the upper group and one of the lower group conduct, connecting the load between the most positive and the most negative phase — which is a line-to-line voltage:

\[ V_{m(line)} = \sqrt2\,(415) = 586.9\ \text{V} \]

Apply the \(p\)-pulse formula with \(p = 6\):

\[ V_{dc} = \frac{6}{\pi}V_{m(line)}\sin\frac{\pi}{6} = \frac{3}{\pi}V_{m(line)} = (0.955)(586.9) = 560.4\ \text{V} \]

Equivalently, in terms of the phase peak:

\[ V_{dc} = \frac{3\sqrt3}{\pi}V_{m(ph)} = (1.654)(338.8) = 560.4\ \text{V}\ \checkmark \]

Exactly twice the three-pulse figure, and 95.5% of the line peak — the output is almost the peak of the supply, before any filtering at all.

The RMS and ripple:

\[ V_{rms} = V_{m(line)}\sqrt{\frac12+\frac{6}{4\pi}\sin\frac{\pi}{3}} = (586.9)(0.9558) = 560.9\ \text{V} \]
\[ FF = \frac{560.9}{560.4} = 1.00088, \qquad RF = \sqrt{1.00176-1} = 0.042 = 4.2\% \]

Note how close \(V_{rms}\) and \(V_{dc}\) have become — half a volt apart in 560. That closeness is why the ripple factor must be computed carefully: rounding either figure to four significant digits destroys the answer.

Ripple frequency and PIV:

\[ f_{ripple} = 6f = 300\ \text{Hz}, \qquad \text{PIV} = V_{m(line)} = 586.9\ \text{V} \]

Same PIV as the three-pulse circuit, but twice the output voltage from it — so the bridge uses its devices twice as effectively. And 300 Hz ripple needs a filter nine times smaller than the same attenuation at 100 Hz.

The full comparison:

Rectifier\(p\)\(V_{dc}/V_m\)RF\(f_{ripple}\)Diodes
1-φ half-wave10.318121%50 Hz1
1-φ bridge20.63748.3%100 Hz4
3-φ half-wave30.82718.3%150 Hz3
3-φ bridge60.9554.2%300 Hz6
12-pulse120.9891.03%600 Hz12

Ripple falls roughly as \(1/p^2\) and the output rises toward the peak. Doubling the pulse number is worth about a factor of four in ripple — which is why Problem 5 finds twelve-pulse worthwhile despite the transformer it requires.

A six-pulse bridge delivers 95.5% of the peak with 4.2% ripple and no energy storage whatsoever. Compare Set 10, where reaching a comparable output needed 4000 µF, a 72 A peak current and a power factor of 0.29. Where three phases are available, almost every problem of Set 10 simply does not arise.
Answera\(V_{dc} = 560.4\ \text{V},\ V_{rms} = 560.9\ \text{V}\)   b\(RF = 4.2\%\)   c\(300\ \text{Hz}\)   d\(\text{PIV} = 587\ \text{V}\)
Problem 3Exam levelDevices and Lines

The bridge of Problem 2 supplies a highly inductive load drawing a constant 100 A. Find the output power, the average and RMS current of each diode, the RMS and fundamental line currents, the THD, the distortion factor and the power factor.

Solution

Output power:

\[ P_{dc} = (560.4)(100) = 56.04\ \text{kW} \]

Each diode conducts for 120° of every cycle — one third — carrying the full DC current while it does:

\[ I_{D,avg} = \frac{I_{dc}}{3} = 33.3\ \text{A}, \qquad I_{D,rms} = \frac{I_{dc}}{\sqrt3} = 57.7\ \text{A} \]

The \(\sqrt3\) is the familiar \(1/\sqrt{D}\) with \(D = 1/3\). As always the RMS is what rates the device, and it is 1.73 times the average.

The line current is a quasi-square wave. Each phase carries \(+I_{dc}\) for 120°, then zero for 60°, then \(-I_{dc}\) for 120°, then zero for 60°:

\[ I_s = I_{dc}\sqrt{\frac{240^\circ}{360^\circ}} = I_{dc}\sqrt{\frac23} = (100)(0.8165) = 81.65\ \text{A} \]

Less than the DC current, because each phase rests for 120° of every cycle. Note that unlike the three-pulse circuit, the waveform is symmetric — equal positive and negative blocks — so there is no DC in the transformer.

The fundamental, from the Fourier series of a 120° block:

\[ I_{s1} = \frac{\sqrt6}{\pi}I_{dc} = (0.7797)(100) = 77.97\ \text{A} \]
\[ \text{distortion factor} = \frac{I_{s1}}{I_s} = \frac{77.97}{81.65} = 0.9549 = \frac{3}{\pi} \]

Distortion and power factor:

\[ THD = \sqrt{\left(\frac{81.65}{77.97}\right)^2-1} = \sqrt{0.0966} = 31.1\% \]
\[ PF = \frac{I_{s1}}{I_s}\cos\phi_1 = (0.9549)(1) = 0.955 \]

Against 0.900 for the single-phase bridge and 0.29 for the capacitor-input circuit of Set 10. The gap in the waveform — the 60° rest between blocks — makes the current shape closer to a sine than a full square wave is.

Check against the apparent power:

\[ S = \sqrt3\,V_LI_s = \sqrt3\,(415)(81.65) = 58.69\ \text{kVA} \]
\[ PF = \frac{P}{S} = \frac{56.04}{58.69} = 0.955\ \checkmark \]

The two routes agree, confirming both the line current and the fundamental. As with every diode rectifier, the displacement factor is unity and every bit of the shortfall is harmonic content — which Problem 4 identifies precisely.

The same 100 A appears as three different numbers depending on where you stand. The load sees 100 A DC, each diode sees 33.3 A average and 57.7 A RMS, and each line sees 81.65 A RMS of which only 77.97 A does any work. Knowing which of those five figures a question is asking for is most of the skill.
Answera\(56.04\ \text{kW}\)   b\(33.3\ \text{A},\ 57.7\ \text{A}\)   c\(I_s = 81.65\ \text{A},\ I_{s1} = 77.97\ \text{A}\)   d\(THD = 31.1\%,\ PF = 0.955\)
Problem 4Exam levelThe 6k±1 Rule

For the same 100 A bridge, identify which harmonics appear in the line current, compute the amplitudes of the first four, verify the THD from the harmonic series, and explain why no triplen harmonics are present.

Solution

Which harmonics exist. A \(p\)-pulse converter draws line-current harmonics only of order:

\[ n = pk\pm1, \qquad k = 1,2,3,\dots \]
\[ p = 6:\qquad n = 5,\ 7,\ 11,\ 13,\ 17,\ 19,\ 23,\ 25,\ \dots \]

No even harmonics, because the waveform has half-wave symmetry; and no triplens, for a reason worth working out separately.

Amplitudes fall as \(1/n\):

\[ I_n = \frac{I_{s1}}{n} \]
OrderFrequencyAmplitude% of fundamental
150 Hz77.97 A100%
5250 Hz15.59 A20.0%
7350 Hz11.14 A14.3%
11550 Hz7.09 A9.1%
13650 Hz6.00 A7.7%

The 5th alone is 20% of the fundamental — and it is a negative-sequence component, so in a motor it produces a torque pulsation at six times line frequency and heats the rotor without doing useful work.

Verify the THD from the series. Summing all the \(6k\pm1\) terms:

\[ THD = \sqrt{\sum_{n=5,7,11,13,\dots}\left(\frac{1}{n}\right)^2} = \sqrt{\frac{1}{25}+\frac{1}{49}+\frac{1}{121}+\frac{1}{169}+\dots} \]
\[ = \sqrt{0.0966} = 31.08\% \]

Which agrees with the closed form obtained from the RMS values in Problem 3:

\[ THD = \sqrt{\frac{\pi^2}{9}-1} = 31.08\%\ \checkmark \]

Two completely independent routes — a harmonic sum and a ratio of RMS values — landing on the same figure. This is the standard check that a harmonic analysis is complete.

Why no triplens. Third-harmonic components in a three-phase system are in phase with each other — zero sequence — so they can only flow if there is a return path:

\[ 3\times120^\circ = 360^\circ \equiv 0^\circ \quad\text{in all three phases} \]

A three-wire supply has no neutral, so zero-sequence current has nowhere to go and the triplens are simply absent from the line current. This is the structural advantage over Set 10's single-phase circuit, whose third harmonic was its worst offender and whose triplens added in the neutral.

What this means for the installation:

ConsequenceCaused by
Transformer heating beyond its kVA ratingeddy losses rising as \(n^2\)
Voltage distortion at the common coupling pointharmonic currents in the source impedance
Resonance with power-factor capacitors5th or 7th near the plant resonance
Motor torque pulsation at \(6f\)5th (negative seq.) and 7th (positive seq.)

The third of these is the dangerous one. A capacitor bank installed to correct displacement power factor can resonate with the supply inductance near 250 or 350 Hz, amplifying the very harmonic the rectifier injects — a common cause of capacitor failures in plants that added correction without a harmonic study.

Pulse number sets the harmonic spectrum, and eliminating a harmonic is worth far more than attenuating it. The six-pulse bridge has no triplens at all — not small ones — because of a symmetry, not a filter. Problem 5 uses the same principle to remove the 5th and 7th.
Answera\(n = 6k\pm1\): 5, 7, 11, 13   b\(15.6,\ 11.1,\ 7.1,\ 6.0\ \text{A}\)   c\(THD = 31.08\%\) both ways   d triplens are zero-sequence, no return path
Problem 5ChallengeTwelve Pulses

Two six-pulse bridges are fed from a transformer with one star and one delta secondary, giving a 30° phase shift, and their outputs are connected in series. Each secondary provides the same 415 V. Find the output voltage, the ripple factor and frequency, which harmonics survive, and the resulting line-current THD.

Solution

Where the 30° comes from. A star secondary and a delta secondary on the same core produce line voltages 30° apart. Feeding two identical bridges from them gives two six-pulse outputs whose ripples are 30° out of step — half of the 60° ripple period.

So when one bridge's output is at a ripple peak, the other is at a trough, and the series sum has twelve smaller ripples per cycle instead of six large ones.

Output voltage, the two bridges in series:

\[ V_{dc} = 2\left(\frac{3}{\pi}V_{m(line)}\right) = 2(560.4) = 1120.9\ \text{V} \]
\[ f_{ripple} = 12f = 600\ \text{Hz} \]

The ripple factor, from the general formula with \(p = 12\):

\[ \frac{V_{dc}}{V_m} = \frac{12}{\pi}\sin15^\circ = 0.98862, \qquad \frac{V_{rms}}{V_m} = \sqrt{\frac12+\frac{12}{4\pi}\sin30^\circ} = 0.98867 \]
\[ RF = \sqrt{\left(\frac{0.98867}{0.98862}\right)^2-1} = 1.03\% \]

Four times better than six-pulse, consistent with the \(1/p^2\) scaling. At 1% ripple and 600 Hz, the output filter for most loads becomes trivial or unnecessary.

The harmonic cancellation is the real prize. Applying the pulse rule with \(p = 12\):

\[ n = 12k\pm1 = 11,\ 13,\ 23,\ 25,\ 35,\ 37,\dots \]

The 5th and 7th have vanished. They are still drawn by each bridge individually, but the 30° phase shift makes them 150° and 210° apart on the primary side — effectively in antiphase — so they cancel in the transformer rather than reaching the supply.

The resulting distortion:

\[ THD = \sqrt{\frac{1}{121}+\frac{1}{169}+\frac{1}{529}+\frac{1}{625}+\dots} = 15.2\% \]
Quantity6-pulse12-pulseImprovement
Output ripple4.2%1.03%4.1×
Ripple frequency300 Hz600 Hz
Lowest harmonic5th11th
Line THD31.1%15.2%2.0×
Devices612
Transformersimpletwo secondaries

Halving the THD and quartering the ripple, for twice the devices and a purpose-wound transformer. At the multi-megawatt scale where the harmonic limits are strict and the transformer exists anyway, that trade is decisive — which is why HVDC converters and large electrolysis rectifiers are twelve-pulse or higher.

Why not go further? The same trick extends to 18 and 24 pulses with additional phase-shifted windings:

\[ p = 24:\quad n = 23,\ 25,\dots \quad THD \approx 7.6\% \]

But the returns diminish and the transformer complexity does not. Beyond twelve pulses it is usually cheaper to fit a tuned filter or an active front end — and once an active front end is present it delivers under 5% THD and a controllable power factor, which no pulse number can.

Phase-shifting cancels harmonics rather than filtering them. No energy is stored and nothing is dissipated: two identical distorted currents are simply arranged so their 5th and 7th components oppose. That is a far better bargain than any passive filter, and it is available only because three-phase supplies come with phase shifts already built in.
Answera\(V_{dc} = 1120.9\ \text{V}\)   b\(RF = 1.03\%,\ 600\ \text{Hz}\)   c\(n = 12k\pm1\): 11, 13, 23, 25   d\(THD = 15.2\%\)
Problem 6ChallengeA 111 kW Rectifier

A three-phase bridge on the 415 V supply delivers 200 A to a highly inductive load. Each diode is modelled as \(v_F = 0.9+0.003\,i\). Find the actual output voltage and power, the loss per diode and in total, the rectifier efficiency, and the device ratings required.

Solution

Two diodes are always in the path. Both carry the full 200 A while conducting, so the drop is:

\[ v_F = 0.9+(0.003)(200) = 1.5\ \text{V}, \qquad \Delta V = 2(1.5) = 3.0\ \text{V} \]
\[ V_{dc} = 560.4-3.0 = 557.4\ \text{V}, \qquad P_o = (557.4)(200) = 111.5\ \text{kW} \]

A 0.54% reduction — negligible here, unlike the motor drive of Set 9 where a back EMF amplified a similar drop into an 8.8% current error. With a constant-current load there is no amplification.

Device currents, from the 120° conduction of Problem 3:

\[ I_{D,avg} = \frac{200}{3} = 66.7\ \text{A}, \qquad I_{D,rms} = \frac{200}{\sqrt3} = 115.5\ \text{A} \]

Loss per diode, using the average for the offset and the RMS for the slope:

\[ P_D = V_0I_{avg}+r_dI_{rms}^2 = (0.9)(66.7)+(0.003)(13{,}333) = 60.0+40.0 = 100.0\ \text{W} \]
\[ P_{total} = 6(100.0) = 600\ \text{W} \]

Note the split: 60 W from the junction offset and 40 W from the bulk resistance. Using the average current for both terms would give 73 W and understate the loss by 27% — the Set 2 error, still costing marks.

Cross-check against the terminal drop, which must agree:

\[ P = \Delta V\,I_{dc} = (3.0)(200) = 600\ \text{W}\ \checkmark \]
\[ \eta = \frac{111{,}480}{111{,}480+600} = 99.46\% \]

Two independent routes agreeing exactly. A line-frequency rectifier is a very efficient machine, because there is no switching loss at all — the diodes commutate naturally at the crossings of the line voltages.

Device selection. Apply the constraints from Part 1 simultaneously:

ConstraintRequiredSpecify
Blocking voltage587 V peak1200 V class (2× margin)
Average current66.7 A\(\ge\) 100 A device
RMS current115.5 Athe binding current constraint
Dissipation100 W eachsee below

The RMS again exceeds the average by \(\sqrt3\), and it is the one that sets the die size.

Close the loop with Set 8. One hundred watts per diode is a real thermal problem:

\[ R_{th(j-a)} \le \frac{T_{j,max}-T_a}{P} = \frac{125-45}{100} = 0.80\ \text{K/W} \]

With a typical module \(R_{th(j-c)} = 0.35\) and interface 0.05, the heatsink must reach 0.40 K/W per device — or, for a six-pack module dissipating all 600 W through one baseplate, roughly 0.1 K/W overall. That is forced-air territory, exactly as Set 8's inverter turned out to be.

A 99.5% efficient converter still needs a fan. Six hundred watts is a rounding error against 111 kW and a serious cooling problem in a cabinet, and both statements are true at once. Part 1's thermal work is not a separate topic from Part 2's waveform work — the RMS current that fixes the ripple factor is the same one that sizes the heatsink.
Answera\(V_{dc} = 557.4\ \text{V},\ P_o = 111.5\ \text{kW}\)   b\(100\ \text{W}\) each, \(600\ \text{W}\) total   c\(\eta = 99.46\%\)   d 1200 V, 115.5 A RMS
Formulas

Key Formulas

QuantityRelationNotes
\(p\)-pulse average\(V_{dc} = \dfrac{p}{\pi}V_m\sin\dfrac{\pi}{p}\)Covers every circuit here
\(p\)-pulse RMS\(V_{rms} = V_m\sqrt{\dfrac12+\dfrac{p}{4\pi}\sin\dfrac{2\pi}{p}}\)Keep full precision
3-pulse output\(\dfrac{3\sqrt3}{2\pi}V_{m(ph)} = 0.827V_m\)RF = 18.3%
6-pulse output\(\dfrac{3}{\pi}V_{m(line)} = 0.955V_{m(line)}\)RF = 4.2%
Ripple frequency\(f_{ripple} = pf\)Filter scales as \(1/p^2\)
PIV\(\text{PIV} = V_{m(line)}\)Line, not phase — both circuits
Diode currents\(I_{avg} = I_{dc}/3,\ I_{rms} = I_{dc}/\sqrt3\)120° conduction
Line RMS current\(I_s = I_{dc}\sqrt{2/3} = 0.8165I_{dc}\)Problem 3
Line fundamental\(I_{s1} = \dfrac{\sqrt6}{\pi}I_{dc} = 0.7797I_{dc}\)120° block
Distortion factor\(I_{s1}/I_s = 3/\pi = 0.955\)= PF for a diode bridge
Harmonic orders\(n = pk\pm1\)No triplens in 3-wire
Harmonic amplitude\(I_n = I_{s1}/n\)Problem 4
6-pulse THD\(\sqrt{\pi^2/9-1} = 31.08\%\)Exact closed form
12-pulse THD15.2%5th and 7th cancel — Problem 5
Bridge conduction drop\(\Delta V = 2v_F\)Two diodes always in series
Pitfalls

Common Mistakes

  1. Using the phase peak in the bridge formula. A six-pulse bridge works on line voltages; \(V_{dc} = 3V_{m(line)}/\pi\) or equivalently \(3\sqrt3\,V_{m(ph)}/\pi\) — Problem 2.

  2. Quoting the PIV as the phase peak. A blocked diode sees the difference between two phases, i.e. a line voltage — Problems 1 and 2.

  3. Rounding \(V_{rms}\) and \(V_{dc}\) before taking the ripple factor. They differ by 0.5 V in 560; four significant figures destroys the answer — Problem 2.

  4. Taking the diode RMS as \(I_{dc}/3\). The average is \(I_{dc}/3\); the RMS is \(I_{dc}/\sqrt3\), larger by 1.73 — Problem 3.

  5. Using \(I_s = I_{dc}\) for the line current. Each phase rests for 120° per cycle, so \(I_s = 0.8165I_{dc}\) — Problem 3.

  6. Expecting a third harmonic. Triplens are zero-sequence and cannot flow in a three-wire supply — the lowest is the 5th — Problem 4.

  7. Assuming twelve-pulse halves every harmonic. It removes the 5th and 7th entirely and leaves the 11th and 13th untouched — Problem 5.

  8. Believing higher pulse number improves the power factor much. It goes from 0.955 to 0.988 — displacement was already unity, so there is little left to gain — Problem 5.

  9. Subtracting one diode drop from the bridge output. Two conduct at all times, so the loss is \(2v_F\) — Problem 6.

  10. Treating 99.5% efficiency as no thermal problem. Six hundred watts still needs forced cooling, whatever fraction of 111 kW it is — Problem 6.

Looking Ahead

Six problems, one parameter. The pulse number set the output ratio, the ripple factor, the ripple frequency and the harmonic spectrum, and going from \(p = 1\) to \(p = 12\) took the ripple from 121% to 1.03% without storing a single joule. Problem 5's harmonic cancellation was the most economical result in Part 2 so far: two distorted currents arranged to oppose, at no cost in loss.

But every rectifier in Sets 9 to 11 has produced exactly one output voltage, fixed by the supply. A diode conducts when the circuit says so and there is no control input anywhere. Replace the diodes with thyristors — whose ratings, triggering and protection Part 1 has already covered — and the conduction can be delayed by a firing angle, making the output continuously adjustable from full positive to full negative.

Next: Set 12 — Single-Phase Controlled Converters, where the firing angle scales the output as \(\cos\alpha\), the semiconverter is traded against the full converter, inversion returns power to the supply, and the displacement factor — unity for every circuit so far — becomes the dominant term in the power factor.