Part 7 · Chapter 25

Insulation Coordination

This chapter is where the whole part comes together. We now know the overvoltages a system faces and the arresters that limit them; insulation coordination is the discipline of fitting the two together — choosing how strong to make every insulation in the system, and how to protect it, so that the apparatus survives the stresses it will meet at an acceptable risk and an acceptable cost. Its guiding idea is quietly brilliant: arrange matters so that if anything must give way, it is always the cheap, self-healing insulation that fails first, never the costly transformer buried at the heart of the station.

High-Voltage Engineering Prof. Mithun Mondal Reading time ≈ 50 min
i What you'll learn
  • The coordination idea: arrange withstand and protective levels so that failure falls on cheap, self-restoring insulation.
  • The voltage stresses (continuous, temporary, switching, lightning) versus the standard withstand levels BIL and SIL.
  • The difference between self-restoring and non-self-restoring insulation, and why it changes the method.
  • The conventional (deterministic) method with its protective ratio, and the statistical method with its risk of failure.
  • The IEC 60071 framework — \(U_m\), Range I and Range II — and the procedure from representative overvoltage to standard withstand.
  • The altitude correction factor \(K_a\) and how a whole substation is coordinated beneath the arrester's protective level.
Section 25-1

The Coordination Idea

Insulation coordination is the selection of the insulation strength of equipment, and of the protective devices that guard it, in relation to the voltages that can appear on the system and the environment in which it operates. The aim is a design that is strong enough to keep failures acceptably rare, yet economical enough to build — for insulation is expensive, and over-insulating every component "to be safe" would make a power system unaffordable. Coordination is the art of buying just enough strength, in just the right places.

The organising principle is a ladder of levels. At the bottom sits the continuous operating voltage; above it the temporary and switching overvoltages; and capping them, the arrester's protective level — the ceiling of Chapter 24. Every insulation in the station is then given a withstand strength that lies above that ceiling by a margin. Crucially, the levels are also ordered among themselves so that the weakest planned path is always an external, self-restoring one — an air gap or a line insulator that simply flashes over and recovers — rather than the internal, non-self-restoring insulation of a transformer, which would be destroyed. Coordination thus channels the rare failure to where it does least harm.

V external (air) withstand transformer BIL / SIL arrester protective level switching / temporary OV continuous operating margin
The coordination ladder — the arrester protective level caps the overvoltages, the transformer withstand sits above it by a margin, and the external air insulation is set highest so that, if anything flashes, it is the self-restoring air gap and not the transformer
Section 25-2

Stresses and Withstand Levels

Coordination balances two columns: the stresses that appear and the strengths that resist them. The stresses are the overvoltage classes already met — continuous power-frequency, temporary, slow-front switching, and fast-front lightning (plus very-fast fronts in gas-insulated switchgear). The strengths are expressed as standardised rated withstand voltages, the voltages an insulation is guaranteed to survive in a defined test:

StressTest waveformWithstand level
Lightning (fast-front)\(1.2/50~\mu\mathrm{s}\) impulseBIL — lightning impulse withstand (LIWV)
Switching (slow-front)\(250/2500~\mu\mathrm{s}\) impulseSIL — switching impulse withstand (SIWV)
Temporary / continuous1-minute power frequencyshort-duration power-frequency withstand

The BIL (basic lightning impulse insulation level) is the headline number that appears on nearly every nameplate; the SIL (switching impulse level) joins it at the highest voltages, where, as Chapter 23 showed, slow-front stress governs. Coordination is fundamentally the act of choosing these withstand numbers so that each comfortably exceeds the corresponding stress, with the arrester holding that stress down to a known protective level in the first place.

Section 25-3

Self-Restoring or Not

A distinction runs through the whole subject and decides which method applies. Self-restoring insulation — air gaps, the air around line insulators, external clearances — fully recovers its strength after a flashover; the arc clears, the air de-ionises, and the insulation is as good as before. Non-self-restoring insulation — the oil-paper inside a transformer, the solid dielectric of a cable, the gas-barrier of a bushing — is permanently damaged by a single breakdown; one puncture and the component is ruined.

self-restoring (air) flashes → recovers non-self-restoring transformer punctures → ruined
Two kinds of insulation — self-restoring air recovers fully after a flashover, so a small statistical risk is acceptable; non-self-restoring internal insulation is destroyed by one breakdown, so it must be protected almost absolutely

The consequence is profound. For self-restoring insulation an occasional flashover is a nuisance, not a disaster, so we can accept a small, calculated probability of failure and design statistically. For non-self-restoring insulation no failure can be tolerated, so it is protected almost absolutely, by a firm deterministic margin above the arrester level. The two methods that follow are simply these two attitudes made quantitative.

Section 25-4

The Conventional (Deterministic) Method

The older, simpler approach treats both stress and strength as single fixed numbers. The highest overvoltage that can reach the equipment is held to the arrester's protective level, and the insulation's withstand is set above it by a fixed factor. The quality of the coordination is the protective ratio (or coordination factor):

Protective ratio
\[ K = \frac{\text{withstand voltage (BIL or SIL)}}{\text{protective level } U_{res}} \]

A ratio of around \(1.2\) or more — equivalently a protective margin of \(20\%\) or more — is the usual target, with the surplus covering the separation effect, ageing and uncertainty. This deterministic method is exactly right for non-self-restoring insulation, where the idea of an "acceptable failure rate" is meaningless and a clear, assured margin above the worst credible stress is what is wanted. Its weakness is that, by always assuming the worst case, it tends to over-insulate — which is acceptable for the transformer but wasteful if applied to the vast air clearances of an EHV station.

Section 25-5

The Statistical Method

For self-restoring insulation the deterministic worst case is needlessly expensive, because both the overvoltage and the withstand are really distributions, not single values. Switching overvoltages, being statistical (Chapter 23), are described by a probability distribution of crest values; and the flashover of an air gap is itself probabilistic, described by a \(50\%\) flashover voltage \(U_{50}\) with a spread, the conventional deviation \(\sigma\). The statistical method works with both distributions at once.

V → overvoltage (stress) withstand (strength) risk = overlap U₂ U₁₀
The risk of failure — the overvoltage distribution and the withstand distribution overlap; the shaded area where a high stress meets a weak gap is the probability of flashover. Coordination chooses the separation so that this risk is small but non-zero

The risk of failure is the overlap: the probability that, on a given event, the overvoltage happens to be high and the gap happens to be weak at the same moment. Formally it is the integral of the overvoltage probability density times the gap's flashover probability across all voltages. Rather than demand zero overlap (infinite insulation), the designer accepts a small risk — perhaps one failure in a thousand events — and sizes the gap accordingly. Two statistical quantities anchor the calculation: the statistical overvoltage \(U_2\) (the value exceeded by only \(2\%\) of overvoltages) and the statistical withstand \(U_{10}\) (the value the gap withstands \(90\%\) of the time, i.e. \(U_{10}=U_{50}-1.28\sigma\)). Their ratio is the statistical safety factor:

Statistical safety factor
\[ \gamma = \frac{U_{10}}{U_2}, \qquad U_{10} = U_{50}\,(1 - 1.28\,\sigma_{\!/U_{50}}) \]
Section 25-6

The IEC 60071 Framework

To make coordination uniform worldwide, the standard IEC 60071 lays down a common vocabulary and a fixed menu of withstand levels. Equipment is identified by its highest voltage for equipment \(U_m\) — the maximum sustained rms line-to-line voltage it is built for — and the standard splits the voltage world into two ranges, because different stresses dominate in each:

RangeHighest voltage \(U_m\)Governing stresses & standard withstands
Range I\(1~\mathrm{kV} < U_m \le 245~\mathrm{kV}\)lightning & power-frequency: BIL + short-duration power-frequency withstand
Range II\(U_m > 245~\mathrm{kV}\)switching & lightning: SIL + BIL

In Range I (distribution and sub-transmission up to \(245~\mathrm{kV}\)) the insulation is verified by a lightning-impulse withstand and a one-minute power-frequency test; switching surges are mild enough to be covered implicitly. In Range II (EHV and UHV above \(245~\mathrm{kV}\)) the switching-impulse withstand becomes a separate, governing requirement alongside the lightning one. For each \(U_m\) the standard offers a short list of permissible withstand values — so the engineer does not invent a BIL, but selects the lowest standard value that satisfies the coordination calculation.

Section 25-7

The Coordination Procedure

IEC 60071 turns all of this into a clear chain that carries the design from the overvoltages a point will see to the standard withstand voltage stamped on the equipment. Each step multiplies by a factor that accounts for one source of uncertainty:

repr. OV U_rp coord. U_cw required U_rw standard U_w ×K_c ×K_a·K_s select ≥
The IEC 60071 coordination chain — the representative overvoltage \(U_{rp}\) becomes the coordination withstand \(U_{cw}\) (via the coordination factor \(K_c\) for risk), then the required withstand \(U_{rw}\) (via atmospheric \(K_a\) and safety \(K_s\) factors), and finally a standard \(U_w\) at or above it is selected

Reading the chain: the representative overvoltage \(U_{rp}\) is what the location actually sees (set by the arrester for the protected equipment). Multiplying by the coordination factor \(K_c\) — which embeds the chosen risk — gives the coordination withstand voltage \(U_{cw}\), the strength needed in service. Multiplying again by the atmospheric correction \(K_a\) (for altitude) and the safety factor \(K_s\) (for ageing and manufacturing scatter) gives the required withstand voltage \(U_{rw}\). Finally the engineer selects the nearest standard withstand voltage \(U_w \ge U_{rw}\) from the IEC list — and that BIL or SIL is what the equipment is built and tested to.

Section 25-8

Altitude and a Coordinated Station

One correction deserves singling out because it bites hardest in practice: altitude. The strength of external (air) insulation falls as the air thins, so a clearance that is ample at sea level may flash over in a mountain substation. IEC accounts for this with the atmospheric correction factor

Altitude correction
\[ K_a = e^{\,m\,(H/8150)} \]
K_a altitude H (m) → 1.0 1.2 1.4 1000 2000 3000 ≈1.28
The altitude correction factor — \(K_a=e^{mH/8150}\) climbs steadily with altitude (about \(1.28\) at \(2000~\mathrm{m}\) for \(m=1\)), so external air insulation in a high-altitude station must be rated for a substantially higher withstand than at sea level

where \(H\) is the altitude in metres and the exponent \(m\) depends on the voltage type (near \(1\) for lightning-impulse and power-frequency withstand of air gaps). At \(2000~\mathrm{m}\) this already demands roughly a quarter more withstand than at sea level — a real cost for high-altitude grids. Humidity and temperature carry their own smaller test corrections, but altitude is the dominant environmental term.

Pull the threads together and a coordinated substation emerges as a tidy hierarchy. The metal-oxide arrester, mounted hard against the transformer, sets the lowest ceiling — the protective level. The transformer, the precious non-self-restoring heart, is given a BIL above that ceiling by a firm deterministic margin. The bus, disconnectors and bushings are coordinated next, and the external air clearances are set highest and designed statistically, so that any overvoltage that somehow defeats the arrester flashes harmlessly across an air gap rather than puncturing the transformer. Every nameplate BIL and every metre of clearance in that station is the output of the chain in Section 25-7 — the quiet, unseen calculation that lets a power system ride out the sky's worst and its own switching, year after year, at a price the world can afford.

Section 25-9

Worked Examples

1 Protective ratio (deterministic)

Problem. A transformer has a BIL of \(1050~\mathrm{kV}\); its arrester's protective (residual) level is \(850~\mathrm{kV}\). Find the protective ratio and judge the coordination.

Solution. Take \(K = \mathrm{BIL}/U_{res}\):

Working
\[ K = \frac{1050}{850} \approx 1.24 \]

A ratio of about 1.24 (a \(24\%\) margin) clears the customary \(\sim1.2\) target, so the non-self-restoring transformer insulation is well coordinated with its arrester.

2 Statistical withstand from \(U_{50}\)

Problem. An air gap has \(U_{50} = 1300~\mathrm{kV}\) with a conventional deviation \(\sigma = 3\%\) of \(U_{50}\). Find the statistical withstand voltage \(U_{10}\).

Solution. Use \(U_{10} = U_{50} - 1.28\sigma\), with \(\sigma = 0.03\times1300 = 39~\mathrm{kV}\):

Working
\[ U_{10} = 1300 - 1.28(39) \approx 1300 - 50 = 1250~\mathrm{kV} \]

The gap withstands about 1250 kV with \(90\%\) probability — the figure used as its statistical strength in the coordination.

3 Statistical safety factor

Problem. For that gap (\(U_{10} = 1250~\mathrm{kV}\)) the statistical overvoltage is \(U_2 = 1050~\mathrm{kV}\). Find the statistical safety factor.

Solution. Take \(\gamma = U_{10}/U_2\):

Working
\[ \gamma = \frac{1250}{1050} \approx 1.19 \]

A safety factor of about 1.19 — the gap's \(90\%\) withstand comfortably exceeds the \(2\%\) overvoltage, so the residual risk of flashover is small, as intended for self-restoring insulation.

4 Altitude correction

Problem. A substation sits at \(H = 2000~\mathrm{m}\). Find the atmospheric correction factor (\(m=1\)) and the required withstand if the sea-level coordination withstand is \(950~\mathrm{kV}\).

Solution. Compute \(K_a = e^{H/8150}\), then \(U_{rw} = U_{cw}K_a\):

Working
\[ K_a = e^{2000/8150} = e^{0.245} \approx 1.28, \qquad U_{rw} \approx 950 \times 1.28 \approx 1214~\mathrm{kV} \]

At \(2000~\mathrm{m}\) the insulation must withstand about 1214 kV, so the next standard value above it (e.g. \(1300~\mathrm{kV}\)) would be selected — altitude alone pushing the design up a full step.

5 The coordination chain

Problem. A representative slow-front overvoltage is \(U_{rp} = 850~\mathrm{kV}\). With \(K_c = 1.05\), \(K_s = 1.05\) and \(K_a = 1.13\), find the required withstand and select a standard value (list: \(950, 1050, 1175~\mathrm{kV}\)).

Solution. Walk the chain \(U_{cw}=K_c U_{rp}\), then \(U_{rw}=K_a K_s U_{cw}\):

Working
\[ U_{cw} = 1.05(850) \approx 893, \quad U_{rw} = (1.13)(1.05)(893) \approx 1060~\mathrm{kV} \;\Rightarrow\; U_w = 1175~\mathrm{kV} \]

The chain gives a required withstand of about \(1060~\mathrm{kV}\), so the smallest standard value at or above it, 1175 kV, is chosen — the BIL/SIL that lands on the nameplate.

Review

Chapter Summary

The idea

Coordinate withstand and protective levels so failures fall on cheap, self-restoring insulation — strong enough yet economical.

Stress vs strength

Lightning, switching and power-frequency stresses meet standardised withstands — BIL, SIL and the power-frequency withstand.

Two attitudes

Non-self-restoring insulation gets a firm deterministic margin; self-restoring insulation is designed to an accepted statistical risk.

Risk of failure

The overlap of the overvoltage and withstand distributions; \(U_{10}=U_{50}-1.28\sigma\), and \(\gamma=U_{10}/U_2\).

IEC 60071

Equipment set by \(U_m\); Range I (≤245 kV) and Range II (>245 kV) fix which standard withstands govern.

The chain

\(U_{rp}\!\to\!U_{cw}\!\to\!U_{rw}\!\to\!U_w\) via \(K_c\), \(K_a\), \(K_s\); altitude correction \(K_a=e^{mH/8150}\).

Practice

Problems

For each item, first identify what it tests — the coordination idea, the stress/withstand pairing, the self-restoring distinction, the deterministic ratio, the statistical method, the IEC framework, or the procedure chain — then apply it. Difficulty rises down the list.

  1. State the aim of insulation coordination and explain the principle of letting self-restoring insulation fail first.
  2. Name the standard withstand level associated with lightning stress and with switching stress.
  3. Distinguish self-restoring from non-self-restoring insulation and say which design method suits each.
  4. A transformer BIL is \(750~\mathrm{kV}\) and its arrester protective level is \(610~\mathrm{kV}\). Find the protective ratio and judge it.
  5. An air gap has \(U_{50}=1100~\mathrm{kV}\) and \(\sigma=3.5\%\) of \(U_{50}\). Find \(U_{10}\).
  6. For that gap, with \(U_2 = 880~\mathrm{kV}\), find the statistical safety factor.
  7. State the \(U_m\) boundary between Range I and Range II and which withstands govern in each.
  8. A station is at \(1500~\mathrm{m}\). Find \(K_a\) (\(m=1\)) and the required withstand if the coordination withstand is \(870~\mathrm{kV}\).
  9. Walk the coordination chain for \(U_{rp}=1000~\mathrm{kV}\), \(K_c=1.05\), \(K_s=1.05\), \(K_a=1.10\); pick a standard value from \(1050, 1175, 1300~\mathrm{kV}\).
  10. Explain why the statistical method saves cost on EHV air insulation but the deterministic method is kept for the transformer.
Tip: this chapter is one principle and one chain. The principle: stack the levels so the arrester caps the overvoltage, the transformer's withstand sits above that cap by a firm margin, and the self-restoring air insulation is highest — if anything flashes, let it be the air. The chain turns that principle into numbers: \(U_{rp}\to U_{cw}\to U_{rw}\to U_w\), multiplying by a coordination factor for risk, an altitude factor \(K_a=e^{mH/8150}\) and a safety factor, then selecting the smallest standard BIL or SIL above the result. Master those, and you can read — or design — the insulation level on any equipment nameplate. With the system now protected and coordinated, Part 8 turns to the modern frontier: HVDC and the polymeric insulation of today's grid.