1-Mark Questions
QQuestion 1 1 Mark
In a 100 bus power system, there are 10 generators. In a particular iteration of Newton Raphson load flow technique (in polar coordinates), two of the PV buses are converted to PQ type. In this iteration,
AOptions
- the number of unknown voltage angles increases by two and the number of unknown voltage magnitudes increases by two.
- the number of unknown voltage angles remains unchanged and the number of unknown voltage magnitudes increases by two.
- the number of unknown voltage angles increases by two and the number of unknown voltage magnitudes decreases by two.
- the number of unknown voltage angles remains unchanged and the number of unknown voltage magnitudes decreases by two.
SSolution
In Newton-Raphson load flow:
Bus types:
- PV bus: Known \(P\), \(|V|\); Unknown \(\theta\)
- PQ bus: Known \(P\), \(Q\); Unknown \(\theta\), \(|V|\)
- Slack bus: Known \(|V|\), \(\theta\)
Initial state:
- Total buses: 100
- Slack: 1, PV: 9, PQ: 90
- Unknown \(\theta\): 99 (all except slack)
- Unknown \(|V|\): 90 (PQ buses only)
After converting 2 PV to PQ:
- Slack: 1, PV: 7, PQ: 92
- Unknown \(\theta\): 99 (unchanged - still all except slack)
- Unknown \(|V|\): 92 (increased by 2)
Correct answer: B
QQuestion 2 1 Mark
The magnitude of three-phase fault currents at buses A and B of a power system are 10 pu and 8 pu, respectively. Neglect all resistances in the system and consider the pre-fault system to be unloaded. The pre-fault voltage at all buses in the system is 1.0 pu. The voltage magnitude at bus B during a three-phase fault at bus A is 0.8 pu. The voltage magnitude at bus A during a three-phase fault at bus B, in pu, is \_\_\_\_\_\_\_\_.
SSolution
Fault at bus A:
Voltage at B during fault at A:
Fault at bus B:
By reciprocity: \(Z_{AB} = Z_{BA} = 0.02\) pu
Voltage at A during fault at B:
Answer: 0.84 pu (range: 0.83 to 0.85)
2-Mark Questions
QQuestion 3 2 Mark
At no load condition, a 3-phase, 50 Hz, lossless power transmission line has sending-end and receiving-end voltages of 400 kV and 420 kV respectively. Assuming the velocity of traveling wave to be the velocity of light, the length of the line, in km, is \_\_\_\_\_\_\_\_\_\_\_\_.
SSolution
For a lossless line at no-load, Ferranti effect causes \(V_R > V_S\).
Using the transmission line equation:
For lossless line: \(\beta = \frac{2\pi f}{v} = \frac{2\pi \times 50}{3 \times 10^8}\)
From voltage ratio:
Answer: 296 km (range: 294 to 298)
QQuestion 4 2 Mark
The power consumption of an industry is 500 kVA, at 0.8 p.f. lagging. A synchronous motor is added to raise the power factor of the industry to unity. If the power intake of the motor is 100 kW, the p.f. of the motor is \_\_\_\_\_\_\_\_\_\_\_\_\_
SSolution
Industry:
- \(S_1 = 500\) kVA, \(\cos\phi_1 = 0.8\) lagging
- \(P_1 = 400\) kW, \(Q_1 = 300\) kVAr (lagging)
Combined at unity pf:
- \(P_{total} = 400 + 100 = 500\) kW
- \(Q_{total} = 0\) (unity pf)
Synchronous motor:
Answer: 0.32 (range: 0.31 to 0.33)
QQuestion 5 2 Mark
Three single-phase transformers are connected to form a delta-star three-phase transformer of 110 kV/ 11 kV. The transformer supplies at 11 kV a load of 8 MW at 0.8 p.f. lagging to a nearby plant. Neglect the transformer losses. The ratio of phase currents in delta side to star side is
AOptions
- \(1 : 10\sqrt{3}\)
- \(10\sqrt{3} : 1\)
- \(1 : 10\)
- \(\sqrt{3} : 10\)
SSolution
Star side (secondary):
For star: \(I_{ph,Y} = I_{L,Y} = 524.86\) A
Transformation ratio:
Current ratio (from VA balance):
Correct answer: A