Introduction
Power System Protection
-
Essential for: Equipment safety, personnel safety, system reliability
-
Protection zones: Generators, transformers, buses, transmission lines
-
Basic requirements: Selectivity, speed, sensitivity, reliability
-
Protection system components: Relays, CTs, VTs, circuit breakers
-
Coordination: Primary and backup protection
-
Stability: Ability to remain inoperative during external faults
Over-current Protection
Over-current Protection - Principles
-
Operates when current exceeds preset value
-
Types:
-
Instantaneous (no intentional delay)
-
Time-delayed (IDMT characteristic)
-
-
Applications: Feeders, motors, transformers
-
Relay types: Electromechanical, digital, numerical
-
Pickup current: 1.25 to 1.5 times full load current
Over-current Protection - Characteristics
-
IDMT (Inverse Definite Minimum Time) curves:
-
Standard inverse (SI): \(t = \frac{0.14 \times TMS}{(I/I_s)^{0.02} - 1}\)
-
Very inverse (VI): \(t = \frac{13.5 \times TMS}{I/I_s - 1}\)
-
Extremely inverse (EI): \(t = \frac{80 \times TMS}{(I/I_s)^2 - 1}\)
-
Long time inverse
-
-
Settings: Pickup current, time multiplier setting (TMS)
-
Coordination: Grading margin (0.2-0.5 sec)
-
Plug setting multiplier (PSM) = Fault current / Pickup current
Differential Protection
Differential Protection - Principles
-
Principle: Compare current at both ends of protected zone
-
Operates when \(|I_1 - I_2| >\) threshold
-
Kirchhoff’s Current Law: \(\sum I_{in} = \sum I_{out}\)
-
Applications: Transformers, generators, busbars, transmission lines
-
Merits: High sensitivity, complete protection zone
-
Unit protection: Internal faults only
Differential Protection - Practical Issues
-
CT mismatches and saturation
-
Magnetizing inrush currents in transformers
-
Percentage differential relay: \(\frac{|I_1 - I_2|}{|I_1 + I_2|} \times 100\%\)
-
Biased differential protection
-
Restricted earth fault protection
-
Harmonic restraint for transformer protection (2nd harmonic)
-
Slope settings: Typically 10-40%
Directional Protection
Directional Protection - Principles
-
Responds to power/current flow direction
-
Requires reference quantity (voltage)
-
Power direction: \(P = VI\cos\phi\)
-
Torque equation: \(T = K_1 V I \cos(\theta - \phi)\)
-
Maximum torque angle (MTA): Usually 30°-45° lagging
-
Relay connection: 90° connection most common
Directional Protection - Applications
-
Applications: Parallel feeders, ring mains, interconnected systems
-
Directional over-current relay
-
Power directional relay
-
Reverse power protection for generators
-
Coordination with non-directional relays
-
Dead zone problem and solutions
-
Voltage polarization: Cross-polarization, self-polarization
Distance Protection
Distance Protection - Principles
-
Measures impedance (\(Z = V/I\))
-
Independent of current magnitude
-
Fault location estimation
-
Types: Impedance, reactance, mho relays
-
Reach setting: Based on line impedance
-
Suitable for long transmission lines
Distance Protection - Zones
-
Zone 1: 80-85% of line (instantaneous)
-
Zone 2: 120-150% of line (time delayed, 0.3-0.5 sec)
-
Zone 3: Backup for adjacent lines (1-3 sec)
-
Zone 4: Reverse direction (optional)
-
Coordination between zones
-
Load encroachment considerations
-
Under-reach and over-reach concepts
Distance Protection - Relay Characteristics
-
Impedance relay: Circle passing through origin
-
Reactance relay: Straight line parallel to R-axis
-
Mho relay: Circle passing through origin and relay point
-
Quadrilateral characteristic: Combination of multiple elements
-
Blinders: Prevent operation on load or out-of-zone faults
-
Offset mho: For ground fault protection
Circuit Breakers
Circuit Breakers - Principles
-
Functions: Interrupt fault current, isolate faulty section
-
Arc interruption: Key principle
-
Recovery voltage: RRRV (Rate of Rise of Recovery Voltage)
-
Breaking capacity: Maximum current it can interrupt
-
Making capacity: Peak current it can close onto
-
DC time constant: \(\tau = L/R\) (affects asymmetrical current)
Circuit Breakers - Types
-
Oil Circuit Breakers:
-
Bulk oil (BOB): Up to 132 kV
-
Minimum oil (MOCB): Up to 36 kV
-
-
Air blast circuit breakers: Up to 800 kV
-
Vacuum circuit breakers: Up to 38 kV
-
SF6 circuit breakers: Most common for high voltage (>145 kV)
-
Comparison: Speed, maintenance, environmental impact
Circuit Breakers - Ratings and Selection
-
Rated voltage and current
-
Breaking capacity (symmetrical and asymmetrical)
-
Making capacity = \(2.55 \times\) breaking capacity
-
Operating sequence: O-0.3s-CO-15s-CO
-
TRV (Transient Recovery Voltage) withstand
-
X/R ratio consideration: Higher X/R = more severe duty
-
Selection criteria based on system requirements
-
Capability curve: Current vs time characteristic
Protection Coordination
Protection Coordination
-
Primary and backup protection philosophy
-
Coordination between different protection schemes
-
Grading: Time grading, current grading, both
-
Discrimination: Achieved through proper coordination
-
Fault study requirements for protection design
-
Communication-based protection (pilot protection)
-
Selectivity index: Measure of coordination effectiveness
Earth Fault Protection
Earth Fault Protection
-
Sensitive earth fault (SEF): Uses residual current
-
Standby earth fault (SBEF): Backup protection
-
Residual current: \(I_R = I_A + I_B + I_C\)
-
Core balance CT: Encircles all three phases
-
Neutral displacement relay: Voltage-based
-
Earth fault factor: Voltage rise in healthy phases
-
Restricted earth fault: For transformer protection
Special Protection Schemes
Generator Protection
-
Stator protection: Differential, earth fault, inter-turn fault
-
Rotor protection: Earth fault, inter-turn fault
-
System-related protection: Reverse power, loss of excitation
-
Over/under frequency protection
-
Negative sequence protection: Unbalanced loading
-
Loss of synchronism protection
-
Capability curve: P-Q diagram limits
Transformer Protection
-
Gas actuated relay (Buchholz): Mechanical protection
-
Thermal protection: Winding temperature indicator
-
Electrical protection: Differential, overcurrent, earth fault
-
Magnetizing inrush current: 2nd harmonic content
-
Vector group compensation in differential protection
-
Tap changer protection
-
Through fault withstand capability
Motor Protection
-
Starting protection: Thermal overload, locked rotor
-
Running protection: Phase unbalance, earth fault
-
Stalling protection: Thermal and electrical
-
Bearing protection: RTD-based temperature monitoring
-
Surge protection: For variable frequency drives
-
Single phasing protection: Negative sequence relay
-
Starting time limitation: Thermal capacity curve
Busbar Protection
-
High impedance scheme: Simple, economical
-
Low impedance scheme: More sensitive, complex
-
Differential protection principle
-
Zone overlap: Avoiding blind spots
-
CT saturation effects
-
Check synchronism relay
-
Bus transfer schemes
Current and Voltage Transformers
Current Transformers (CTs)
-
Accuracy classes: 0.1, 0.2, 0.5, 1.0, 3.0, 5.0
-
Protection class: 5P, 10P (P = Protection)
-
Burden: Connected load in VA
-
Saturation: Knee point voltage
-
CT ratio: Primary/Secondary (e.g., 400/1A)
-
Polarity: Subtractive or additive
-
Core balance CT: Zero sequence current measurement
Voltage Transformers (VTs)
-
Accuracy classes: 0.1, 0.2, 0.5, 1.0, 3.0
-
Burden: Connected load in VA
-
Ferranti effect: Capacitive loading
-
Ratio: Primary/Secondary (e.g., 11000/110V)
-
Electromagnetic VT: Up to 35 kV
-
Capacitive VT: Above 35 kV
-
Neutral grounding: Broken delta connection
GATE Focus Areas
GATE Focus Areas
-
Numerical problems on relay settings and coordination
-
Zone of protection diagrams and overlap
-
CT ratios and burden calculations
-
Comparison of different protection schemes
-
Circuit breaker ratings and selection criteria
-
Time-current coordination curves
-
Fault calculation for protection applications
-
Distance relay characteristics and settings
-
IDMT relay calculations and TMS settings
Sample Questions
Sample GATE Questions - 1
Example
A 400 kV system has a fault level of 25 kA. The circuit breaker should have a breaking capacity of at least:
-
10 kA
-
25 kA
-
40 kA
-
63 kA
Answer: B) 25 kA
Sample GATE Questions - 2
Example
For a distance relay with Zone 1 set to 80% of line impedance, if the line impedance is 20 \(\Omega\), the relay reach is:
-
16 \(\Omega\)
-
20 \(\Omega\)
-
24 \(\Omega\)
-
25 \(\Omega\)
Answer: A) 16 \(\Omega\)
Sample GATE Questions - 3
Example
In differential protection, percentage bias is used to:
-
Increase sensitivity
-
Prevent maloperation due to CT errors
-
Reduce operating time
-
Increase fault current
Answer: B) Prevent maloperation due to CT errors
Sample GATE Questions - 4
Example
The 2nd harmonic component is used in transformer differential protection to:
-
Detect internal faults
-
Prevent operation during inrush current
-
Improve sensitivity
-
Reduce operating time
Answer: B) Prevent operation during inrush current
Sample GATE Questions - 5
Example
A standard inverse IDMT relay has TMS = 0.5 and PSM = 4. The operating time is approximately:
-
0.19 sec
-
0.38 sec
-
0.57 sec
-
0.76 sec
Answer: A) 0.19 sec (Using SI formula: \(t = \frac{0.14 \times 0.5}{4^{0.02} - 1} \approx 0.19\) sec)