Set 17 — Equivalent Circuit Parameters
The transformer becomes an ordinary circuit the moment every quantity is moved onto one side. This set builds that circuit: impedances referred through the square of the turns ratio, winding resistances and leakage reactances gathered into \(R_{01}\), \(X_{01}\) and their secondary counterparts, and the exciting current represented by a parallel \(R_0\) and \(X_0\).
Two versions of the circuit are drilled side by side. The exact one keeps the shunt branch where it belongs and is solved by series-parallel reduction and current division; the approximate one moves it to the terminals and reduces the machine to a single series impedance. Problem 3 measures the gap between them, and it is under a tenth of a percent.
Referring across the windings uses \(a^2\) for impedance. With \(a = N_1/N_2\), a quantity moved from secondary to primary is scaled so that the volts, amperes and watts it accounts for are all preserved:
\[ V' = aV, \qquad I' = I/a, \qquad Z' = a^2Z \]The equivalent series parameters are the sum of the two windings once both are on the same side:
\[ R_{01} = R_1 + a^2R_2, \quad X_{01} = X_1 + a^2X_2, \quad Z_{01} = \sqrt{R_{01}^2 + X_{01}^2} \]\[ R_{02} = \frac{R_{01}}{a^2}, \qquad X_{02} = \frac{X_{01}}{a^2}, \qquad Z_{02} = \frac{Z_{01}}{a^2} \]The shunt branch carries the exciting current. Both elements sit across the same voltage, so they are naturally admittances in parallel:
\[ R_0 = \frac{V_1}{I_w}, \qquad X_0 = \frac{V_1}{I_\mu}, \qquad Y_0 = \frac{1}{R_0} - j\frac{1}{X_0} \]Exact circuit: \(Z_1\) in series with the parallel combination of \(Z_m = 1/Y_0\) and \((Z_2' + Z_L')\). Solve it as an ordinary series-parallel network and use current division for the two branch currents.
Approximate circuit: the shunt branch is moved to the input terminals, leaving \(R_{01}\) and \(X_{01}\) as a single series impedance. The error is of order \(I_0/I_1\) squared and is well under 0.1% at full load.
Terminal voltage from the equivalent circuit. With \(E_2\) the no-load secondary voltage and \(\phi\) the load angle (\(+\) for lagging):
\[ V_2 \simeq E_2 - I_2\left(R_{02}\cos\phi + X_{02}\sin\phi\right) \]Percentage regulation is that drop expressed as a fraction of the no-load secondary voltage:
\[ \%\,\text{reg} = \frac{E_2 - V_2}{E_2}\times100 = \%R\cos\phi + \%X\sin\phi \]
A 2000/200 V single-phase transformer, treated as ideal for this question, supplies a load impedance of \(8 + j6\ \Omega\) connected across its secondary, with 2000 V applied to the primary. Determine
- the load impedance referred to the primary
- the primary and secondary currents
- the real and reactive power, computed on each side, to confirm they agree
- the value, seen from the secondary, of a 400 Ω resistor connected in the primary circuit
Establish the turns ratio and the scaling rule. Voltages on the secondary side are multiplied by \(a\) and currents divided by \(a\), so any ratio of the two — an impedance — is multiplied by \(a^2\):
The angle is untouched: \(36.87^\circ\) on both sides. Referring rescales an impedance but never rotates it, so the load power factor is the same whichever side you stand on.
Currents, worked from the primary side. With the ideal transformer replaced by the referred load, the primary sees a single 1000 Ω impedance:
The same currents from the secondary side, as a check on the referral:
Power is invariant, which is the whole point of the \(a^2\). Compute it on each side:
| Computed on | Real power | Reactive power |
|---|---|---|
| Secondary (actual) | \(20^2 \times 8 = 3200\ \text{W}\) | \(20^2 \times 6 = 2400\ \text{var}\) |
| Primary (referred) | \(2^2 \times 800 = 3200\ \text{W}\) | \(2^2 \times 600 = 2400\ \text{var}\) |
Identical, and necessarily so: \(I'^2R' = (I/a)^2(a^2R) = I^2R\). The referred network is not an approximation — it is an exact replacement that no external measurement can distinguish from the original.
Referring the other way divides by \(a^2\). A 400 Ω resistor sitting in the primary circuit, viewed from the secondary, becomes
The direction of the scaling is fixed by one question: which side has more turns? Impedances always look larger when viewed from the high-voltage side.
A 25 kVA, 2000/200 V, 50 Hz single-phase transformer has the following measured winding data:
| Winding | Resistance | Leakage reactance |
|---|---|---|
| Primary (2000 V) | \(R_1 = 1.5\ \Omega\) | \(X_1 = 2.0\ \Omega\) |
| Secondary (200 V) | \(R_2 = 0.015\ \Omega\) | \(X_2 = 0.020\ \Omega\) |
Calculate
- \(R_{01}\), \(X_{01}\) and \(Z_{01}\) referred to the primary
- \(R_{02}\), \(X_{02}\) and \(Z_{02}\) referred to the secondary
- the full-load copper loss, obtained from each side independently
- the percentage resistance, reactance and impedance
Refer the secondary winding to the primary and add, element by element:
The two windings contribute almost equally, which is not a coincidence — a well-designed transformer splits the copper and the leakage flux roughly evenly between them, and the referral makes that symmetry visible.
Now refer the primary winding to the secondary instead, dividing by the same \(a^2\):
There is no need to repeat the work in practice: once \(Z_{01}\) is known, dividing by \(a^2\) gives \(Z_{02}\) directly. The long route is done here only to show that the two agree.
Full-load currents, from the rating and the two rated voltages:
The copper loss must come out the same from either side, and this is the standard check on a referral:
468.75 W on a 25 kVA rating is 1.9% — a normal figure for a distribution transformer of this size.
Express the parameters per unit of rated voltage, which makes them independent of the side chosen:
Computing \(\%R\) from the secondary side gives \((125 \times 0.030)/200 = 1.875\%\) as well — the percentage values are the one description of the transformer that does not need the phrase "referred to".
A 24 kVA, 2400/240 V, 50 Hz single-phase transformer has \(R_{01} = 3.0\ \Omega\) and \(X_{01} = 8.0\ \Omega\), shared equally between the two windings. A no-load test at rated primary voltage gives an exciting current of 0.5 A at a power factor of 0.2 lagging. The secondary delivers rated current at 0.8 power factor lagging with 240 V at its terminals. Determine
- \(R_0\) and \(X_0\) referred to the primary
- the primary current and the applied primary voltage from the exact equivalent circuit
- the same two quantities from the approximate equivalent circuit
- the error committed by the approximation
Split the exciting current and form the shunt branch. Both elements sit across the rated primary voltage during the no-load test:
The core loss follows immediately: \(P_i = V_1I_w = 2400 \times 0.1 = 240\ \text{W}\), or 1.0% of the rating.
Set up the loading condition with the secondary terminal voltage as the phasor reference, referred to the primary:
Exact circuit — work outwards from the load. With the split \(R_2' = 1.5\ \Omega\), \(X_2' = 4.0\ \Omega\), the voltage across the shunt branch is
The exciting current is driven by \(\bar{E}_1\), not by \(\bar{V}_1\) — this is the only structural difference between the two circuits:
Add the primary winding drop to reach the applied voltage:
Approximate circuit — the shunt branch is moved to the terminals. The two series impedances then merge into \(R_{01} + jX_{01}\), and the exciting current keeps its no-load value:
Compare, and notice how small the difference is:
| Quantity | Exact | Approximate | Error |
|---|---|---|---|
| \(I_1\) | 10.388 A | 10.379 A | 0.085% |
| \(V_1\) | 2474.6 V | 2472.4 V | 0.086% |
| \(\cos\phi_1\) | 0.7803 | 0.7804 | 0.01% |
Even the further simplification \(V_1 \simeq V_2' + I_2'(R_{01}\cos\phi + X_{01}\sin\phi) = 2400 + 10(2.4+4.8) = 2472\ \text{V}\), which drops the quadrature term entirely, is within 0.1%.
Alternative reading of why the error is so small. Moving the shunt branch changes only the current that flows through \(Z_1\) — by \(\bar{I}_0\), which is 0.5 A against 10.4 A — and the extra drop it causes is \(I_0Z_1 \approx 0.5 \times 4.27 = 2.1\ \text{V}\) out of 2475 V. The exact circuit is worth the trouble only when the exciting current is a large fraction of the load current, which means light load or a very small machine.
The parameters of a 2300/230 V, 50 Hz single-phase transformer are, with the secondary quantities already referred to the primary,
| Primary winding | Secondary winding (referred) | Shunt branch |
|---|---|---|
| \(R_1 = 0.286\ \Omega\) | \(R_2' = 0.319\ \Omega\) | \(R_0 = 250\ \Omega\) |
| \(X_1 = 0.73\ \Omega\) | \(X_2' = 0.73\ \Omega\) | \(X_0 = 1250\ \Omega\) |
A load impedance \(Z_L = 0.387 + j0.29\ \Omega\) is connected across the secondary and normal voltage, 2300 V, is applied to the primary. Using the exact equivalent circuit, determine
- the input power factor
- the power input
- the power output
- the primary and secondary copper losses
- the efficiency and the regulation
Refer the load impedance to the primary. Nothing can be combined until every element is on the same side:
Form the series branch carrying the load current — the referred secondary winding in series with the referred load:
Convert the shunt branch to an impedance. \(R_0\) and \(X_0\) are in parallel, so add them as admittances and invert once:
Reduce the network. \(Z_m\) is in parallel with the series branch, and \(Z_1\) is in series with that combination:
Primary current and input power factor follow at once:
Split \(\bar{I}_1\) between the two branches by current division:
Check: \(\bar{I}_0 + \bar{I}_2' = (9.04 - j1.91) + (36.42 - j28.38) = 45.46 - j30.29 = 54.63\angle-33.67^\circ\ \checkmark\)
Powers. Input from the terminal quantities, output from the resistive part of the referred load:
Losses, and the balance that confirms them:
The core loss can be checked independently: the shunt branch voltage is \(I_0|Z_m| = 9.24 \times 245.1 = 2265\ \text{V}\), and \(2265^2/250 = 20\,520\ \text{W}\).
Efficiency and regulation. The referred secondary terminal voltage is the drop across the load itself:
On the actual secondary this is \(2233/10 = 223.3\ \text{V}\) against a no-load 230 V. Quoting the regulation on the no-load base instead gives \(67/2300 = 2.9\%\); always state which base is used.
A 100 kVA, 2000/400 V, 50 Hz single-phase transformer has, referred to the secondary, \(R_{02} = 0.02\ \Omega\) and \(X_{02} = 0.048\ \Omega\). The primary is held at 2000 V. Find the secondary terminal voltage and the percentage regulation at full load for
- 0.8 power factor lagging
- unity power factor
- 0.8 power factor leading
and determine the load power factor at which the regulation is zero.
Fix the no-load secondary voltage and the full-load current. With the primary held at rated voltage, the no-load secondary voltage is the rated 400 V:
Convert to percentages, which makes all three parts one line each:
0.8 power factor lagging. Both terms add, because a lagging current makes the reactive drop subtract from the terminal voltage:
Unity power factor. The reactive term vanishes and only the resistive drop remains:
Note that \(X_{02}\) is more than twice \(R_{02}\) yet contributes nothing here — the reactance only matters when the current has a quadrature component.
0.8 power factor leading. The sine term changes sign, and here it more than cancels the resistive drop:
A negative regulation is a real effect, not an arithmetic slip: a leading load makes the secondary terminal voltage rise above its no-load value.
The power factor for zero regulation is where the two terms cancel exactly:
Confirm one case exactly, without the approximation, by requiring the phasor magnitude of \(\bar{E}_2\) to be 400 V. At 0.8 lagging, \(\bar{I}_2 = 200 - j150\):
The approximate formula gave 388.8 V and 2.80% — a discrepancy of 0.05 V. The quadrature term it neglects enters only through \(6.6^2/(2\times400)\), about eight hundredths of a volt.
Key Formulas
| Quantity | Relation | Notes |
|---|---|---|
| Turns ratio | \(a = N_1/N_2 = V_1/V_2 = I_2/I_1\) | Fixes every referral |
| Referred impedance | \(Z' = a^2Z\) (secondary to primary) | Angle unchanged — Problem 1 |
| Equivalent resistance | \(R_{01} = R_1 + a^2R_2\) | \(R_{02} = R_{01}/a^2\) — Problem 2 |
| Equivalent reactance | \(X_{01} = X_1 + a^2X_2\) | \(X_{02} = X_{01}/a^2\) — Problem 2 |
| Equivalent impedance | \(Z_{01} = \sqrt{R_{01}^2+X_{01}^2}\) | Never add \(R\) and \(X\) directly |
| Shunt branch | \(R_0 = V_1/I_w\), \(X_0 = V_1/I_\mu\) | From no-load data — Problem 3 |
| Shunt admittance | \(\bar{Y}_0 = 1/R_0 - j/X_0\), \(Z_m = 1/\bar{Y}_0\) | Parallel elements — Problem 4 |
| Exact circuit | \(Z_{\text{in}} = Z_1 + Z_m\!\parallel\!(Z_2'+Z_L')\) | Series-parallel reduction — Problem 4 |
| Current division | \(\bar{I}_2' = \bar{I}_1 Z_m/[Z_m+(Z_2'+Z_L')]\) | Splits \(\bar{I}_1\) — Problem 4 |
| Approximate circuit | \(\bar{V}_1 = \bar{V}_2' + \bar{I}_2'(R_{01}+jX_{01})\) | Error \(<0.1\%\) at full load — Problem 3 |
| Copper loss | \(P_{cu} = I_1^2R_{01} = I_2^2R_{02}\) | Same from either side — Problem 2 |
| Percentage values | \(\%R = I_1R_{01}/V_1 \times 100\) | Side-independent — Problems 2, 5 |
| Terminal voltage | \(V_2 \simeq E_2 - I_2(R_{02}\cos\phi + X_{02}\sin\phi)\) | \(-\sin\phi\) for leading — Problem 5 |
| Regulation | \(\%\text{reg} = \%R\cos\phi \pm \%X\sin\phi\) | Negative on leading loads — Problem 5 |
| Zero-regulation pf | \(\tan\phi = R_{02}/X_{02}\), leading | The two drops cancel — Problem 5 |
| Efficiency | \(\eta = P_{\text{out}}/P_{\text{in}}\) | Confirm with a loss balance — Problem 4 |
Common Mistakes
Referring an impedance with \(a\) instead of \(a^2\). Voltage scales with \(a\) and current with \(1/a\), so their ratio scales with \(a^2\) — a factor of 10 wrong in Problem 1.
Referring in the wrong direction. Impedances look larger from the high-voltage side; a 10 Ω load becomes 1000 Ω, not 0.1 Ω — Problem 1.
Adding \(R_{01}\) and \(X_{01}\) arithmetically to get \(Z_{01}\). They are in quadrature: \(3 + 4\) gives 5, not 7 — Problem 2.
Mixing sides within one calculation. Using \(I_2\) with \(R_{01}\) gives a copper loss a hundred times too large; the current and the resistance must be referred to the same winding — Problem 2.
Adding \(R_0\) and \(X_0\) as a series impedance. They are in parallel, so they must be combined as admittances before inverting — Problem 4.
Driving the exciting current from \(V_1\) in the exact circuit. In the exact circuit the shunt branch sits after \(Z_1\) and sees \(E_1\); using \(V_1\) there is the approximate circuit in disguise — Problem 3.
Dismissing the approximate circuit as crude. At rated load it is within 0.1% of the exact result, which is finer than the test data warrant — Problem 3.
Using \(+\!\sin\phi\) for a leading load. The sign of the reactive term flips, and with it the sign of the regulation — Problem 5.
Quoting a regulation without its base. Dividing the drop by \(V_2\) and by \(E_2\) gave 3.0% and 2.9% in Problem 4; both are defensible, but only if stated.
Accepting an answer that describes an impossible machine. Problem 4's data give a 20.5 kW core loss on a 100 kW transformer; the arithmetic is right and the parameters are wrong.
Every problem in this set began with the parameters already known — winding resistances handed over as measured data, or a shunt branch handed over as \(R_0\) and \(X_0\). That is the position a designer is in, not the position an engineer with a transformer on the bench is in. The circuit is now fully assembled and fully solvable; what is missing is a way to obtain its six parameters from the machine itself.
Two measurements are enough, and they exploit the separation that Problem 3 justified. Excite one winding at rated voltage with the other open, and the current is almost purely exciting current, so the readings isolate \(R_0\) and \(X_0\). Short one winding and raise the voltage only until rated current flows, and the flux — and with it the core loss — collapses to nothing, so the readings isolate \(R_{01}\) and \(X_{01}\). Two tests, a few hundred watts of input, and the whole equivalent circuit falls out.
Next: Set 18 — Open-Circuit and Short-Circuit Tests, where those two measurements are turned into equivalent-circuit parameters, into predicted regulation and efficiency, and — by way of Sumpner's test — into a full-load heat run on two transformers at once.