Solved Problems · Set 29

No-Load and Blocked-Rotor Testing

Part 4 · Induction Machines — three measurements, each designed so that one part of the circuit dominates, turn a machine on the bench into a set of numbers that predict its full-load behaviour.

Prof. Mithun Mondal 6 solved problems GATE · ESE · University

Set 29 — No-Load and Blocked-Rotor Testing

The six parameters of the equivalent circuit are not on the nameplate and cannot be computed reliably from the winding drawing. They are measured, by three tests chosen so that in each one a different part of the circuit dominates and the rest can be ignored: a DC measurement for the stator resistance, a run at rated voltage with the shaft free for the shunt branch, and a run at reduced voltage with the rotor clamped for the series branch.

This set works those tests both ways. Three problems extract parameters from readings — including the frequency correction that a reduced-frequency blocked-rotor test demands, and the design-class convention that divides a leakage reactance the tests cannot separate. Two more use a voltage sweep to split the no-load loss into core loss and windage, and then feed the whole parameter set back into the circuit to predict full-load current, torque and efficiency for a machine that was never loaded.

Part 4 · Testing and Control · 6 solved problems

i Method Recap
  • Three tests, three parts of the circuit. The DC test isolates \(R_1\), the no-load test isolates the shunt branch, and the blocked-rotor test isolates the series branch — because in each the other parts are either absent or negligible.

  • DC test. Apply direct current between two line terminals and read the voltage. No rotation, no reactance, no rotor current:

    \[ R_1 = \frac{V_{DC}}{2I_{DC}}\ \text{(star)}, \qquad R_1 = \frac{3V_{DC}}{2I_{DC}}\ \text{(delta)} \]

    Two windings in series are being measured in star, so the per-phase value is half the reading.

  • No-load test at rated voltage. The slip is nearly zero, so \(R_2'/s\) is enormous and the rotor branch carries almost nothing; what remains is the exciting branch:

    \[ \cos\phi_0 = \frac{P_0}{\sqrt3V_LI_0},\quad I_w = I_0\cos\phi_0,\quad I_\mu = I_0\sin\phi_0,\quad R_0 = \frac{V_{ph}}{I_w},\quad X_0 = \frac{V_{ph}}{I_\mu} \]

    Also \(|Z_{nl}| = V_{ph}/I_0 \approx X_1+X_m\), which is how \(X_m\) is separated once \(X_1\) is known.

  • Blocked-rotor test at reduced voltage, rotor held still. Now \(s = 1\), the rotor branch is a low impedance and the exciting branch may be ignored:

    \[ |Z_{01}| = \frac{V_{ph}}{I},\quad R_{01} = \frac{P_{BR}}{3I^2} = R_1+R_2',\quad X_{01} = \sqrt{|Z_{01}|^2-R_{01}^2} \]
  • Correct the reactance for test frequency, never the resistance. If the blocked-rotor test is run at \(f_{test}\) to keep the rotor resistance free of deep-bar effects:

    \[ X_{01}\big|_{f_{rated}} = \frac{f_{rated}}{f_{test}}\,X_{01}\big|_{f_{test}} \]
  • Divide the leakage reactance by design class. The tests give only the sum \(X_1+X_2'\); the split is a convention:

    \[ \text{Class A, D and wound rotor: } X_1 = X_2' = 0.5X_{01}; \qquad \text{Class B: } X_1 = 0.4X_{01},\ X_2' = 0.6X_{01} \]
  • The no-load input is not all core loss. It is stator copper loss plus core loss plus friction and windage. Running the no-load test at several voltages and extrapolating to zero voltage separates the last of these, since core loss vanishes with \(V^2\) while friction and windage does not.

VideoWalkthrough
Problem 1CoreThe Two Standard Tests

The following tests were made on a 400 V, 50 Hz, 4-pole, 3-phase star-connected induction motor of rated current 20 A. All readings are of line quantities and total three-phase power.

TestVoltageCurrentPower
No load400 V5.0 A520 W
Blocked rotor83 V20.0 A1140 W

A DC measurement gives a stator resistance of 0.55 Ω per phase. Determine

  1. the parameters of the exciting branch, \(R_0\) and \(X_0\)
  2. the total equivalent resistance and leakage reactance, and hence \(R_2'\), \(X_1\) and \(X_2'\)
  3. the current the machine would draw if switched directly on to 400 V at standstill.
Solution

The no-load test first. Take the phase voltage and find the no-load power factor from the three-phase power:

\[ V_{ph} = \frac{400}{\sqrt3} = 230.9\ \text{V}, \qquad \cos\phi_0 = \frac{P_0}{\sqrt3V_LI_0} = \frac{520}{\sqrt3\times400\times5.0} = 0.150 \]

A power factor of 0.15 means \(\phi_0 = 81.4^\circ\) — the current is almost entirely magnetising, exactly as it must be when the shaft is doing no work.

Resolve the no-load current into its two components:

\[ I_w = I_0\cos\phi_0 = 5.0\times0.150 = 0.751\ \text{A}, \qquad I_\mu = I_0\sin\phi_0 = 5.0\times0.9887 = 4.943\ \text{A} \]
\[ R_0 = \frac{V_{ph}}{I_w} = \frac{230.9}{0.751} = 307.7\ \Omega, \qquad X_0 = \frac{V_{ph}}{I_\mu} = \frac{230.9}{4.943} = 46.72\ \Omega \]

Note what \(R_0\) actually represents here: the whole 520 W of no-load input, which is core loss plus friction and windage plus the 41 W of no-load stator copper loss. Problem 5 separates those three; for the exciting branch alone the lumped value is the conventional answer.

Now the blocked-rotor test. With the rotor held, \(s=1\) and the rotor branch is a low impedance, so the exciting branch may be dropped:

\[ V_{ph} = \frac{83}{\sqrt3} = 47.92\ \text{V}, \qquad |Z_{01}| = \frac{47.92}{20.0} = 2.396\ \Omega \]
\[ R_{01} = \frac{P_{BR}}{3I^2} = \frac{1140}{3\times20^2} = 0.950\ \Omega \]

The blocked-rotor power factor is \(1140/(\sqrt3\times83\times20) = 0.396\) — poor, because at standstill the leakage reactance dominates.

Separate resistance from reactance by the impedance triangle:

\[ X_{01} = \sqrt{|Z_{01}|^2-R_{01}^2} = \sqrt{2.396^2-0.950^2} = \sqrt{4.838} = 2.200\ \Omega \]
\[ R_2' = R_{01}-R_1 = 0.950-0.55 = 0.400\ \Omega, \qquad X_1 = X_2' = \frac{X_{01}}{2} = 1.100\ \Omega \]

The equal split is the convention for a wound-rotor or Class A machine; Problem 4 examines what happens when it is not appropriate.

The magnetising reactance follows once \(X_1\) is known, because the no-load impedance is very nearly the series sum \(X_1+X_m\):

\[ |Z_{nl}| = \frac{V_{ph}}{I_0} = \frac{230.9}{5.0} = 46.19\ \Omega, \qquad X_m \approx |Z_{nl}|-X_1 = 46.19-1.10 = 45.09\ \Omega \]

The shunt-model value \(X_0 = 46.72\ \Omega\) and the series-model value \(|Z_{nl}| = 46.19\ \Omega\) differ by 1%, which is the price of the very low no-load power factor; the series value is the one to pair with \(X_1\).

The direct-on-line starting current. The blocked-rotor impedance is the standstill impedance, so it need only be scaled to full voltage:

\[ I_{st} = \frac{V_{ph}}{|Z_{01}|} = \frac{230.9}{2.396} = 96.4\ \text{A} \]
\[ \frac{I_{st}}{I_{rated}} = \frac{96.4}{20} = 4.8 \]

Equivalently, scale the test current in the ratio of the voltages: \(20\times400/83 = 96.4\ \text{A}\) — the same number, and the quicker route in an examination.

The completed parameter set:

ParameterValueTest that fixed it
\(R_1\)0.550 ΩDC
\(R_2'\)0.400 ΩBlocked rotor, minus DC
\(X_1 = X_2'\)1.100 ΩBlocked rotor, split by convention
\(R_0\)307.7 ΩNo load
\(X_0\)46.72 ΩNo load
\(X_m\)45.09 ΩNo load, minus \(X_1\)
Each test works by making one part of the circuit dominant and the rest invisible. At no load \(R_2'/s\) is thousands of ohms, so only the shunt branch conducts; with the rotor blocked the shunt branch is hundreds of ohms against a series branch of two, so only the series branch conducts. Both are the induction motor's version of the transformer's open-circuit and short-circuit tests, and the arithmetic is identical.
Answera\(R_0 = 307.7\ \Omega,\ X_0 = 46.72\ \Omega\) b\(R_{01} = 0.95\ \Omega,\ X_{01} = 2.20\ \Omega,\ R_2' = 0.40\ \Omega,\ X_1 = X_2' = 1.10\ \Omega\) c\(I_{st} = 96.4\ \text{A} = 4.8\times\) rated
Problem 2Exam levelReduced-Frequency Correction

A 415 V, 50 Hz, 6-pole, 3-phase star-connected induction motor of rated current 30 A is tested with the rotor locked. To keep the rotor current distribution the same as it would be at the small slip frequency of normal running, the test is performed at 12.5 Hz. The readings are 44 V between lines, 30 A and 2020 W. A DC test gives a stator resistance of 0.4 Ω per phase. Determine

  1. the equivalent resistance and the referred rotor resistance
  2. the total leakage reactance at 50 Hz, and \(X_1\) and \(X_2'\)
  3. the direct-on-line starting current and starting torque at 415 V
  4. what would have been predicted had the test reactance been used uncorrected.
Solution

Why the test is run at reduced frequency at all. At standstill the rotor frequency equals the supply frequency, and in a deep-bar or double-cage rotor the current then crowds into the top of the bar, raising the apparent resistance well above its running value. Testing at a quarter of rated frequency puts the rotor current where it sits in normal service, at a slip frequency of a few hertz.

Reduce the readings to per-phase quantities:

\[ V_{ph} = \frac{44}{\sqrt3} = 25.40\ \text{V}, \qquad |Z| = \frac{25.40}{30} = 0.8468\ \Omega\ \text{(at 12.5 Hz)} \]
\[ R_{01} = \frac{P}{3I^2} = \frac{2020}{3\times30^2} = 0.7481\ \Omega \]

The rotor resistance, which needs no frequency correction because resistance is not a function of frequency:

\[ R_2' = R_{01}-R_1 = 0.7481-0.4 = 0.348\ \Omega \]

The reactance at test frequency, from the impedance triangle:

\[ X\big|_{12.5} = \sqrt{0.8468^2-0.7481^2} = \sqrt{0.7170-0.5597} = 0.3966\ \Omega \]

Scale it to rated frequency. Reactance is proportional to frequency, so the correction is a simple ratio:

\[ X_{01}\big|_{50} = \frac{50}{12.5}\times0.3966 = 4\times0.3966 = 1.586\ \Omega \]
\[ X_1 = X_2' = \frac{1.586}{2} = 0.793\ \Omega \]

This is the only quantity in the test that changes with frequency. The measured power, and therefore \(R_{01}\), is used exactly as read.

Direct-on-line starting current, using the corrected impedance at rated voltage:

\[ V_{ph} = \frac{415}{\sqrt3} = 239.6\ \text{V}, \qquad |Z_{01}| = \sqrt{0.7481^2+1.586^2} = 1.754\ \Omega \]
\[ I_{st} = \frac{239.6}{1.754} = 136.6\ \text{A} = 4.55\times\text{rated} \]

The starting torque is the air-gap power at \(s=1\) divided by synchronous speed:

\[ N_s = \frac{120\times50}{6} = 1000\ \text{rpm}, \qquad \omega_s = 104.72\ \text{rad/s} \]
\[ T_{st} = \frac{3I_{st}^2R_2'}{\omega_s} = \frac{3\times136.6^2\times0.348}{104.72} = 186\ \text{N·m} \]

What the uncorrected figure would have given. Using \(X = 0.397\ \Omega\) instead of 1.586 Ω:

QuantityCorrected (50 Hz)Uncorrected (12.5 Hz value)Error
\(X_{01}\)1.586 Ω0.397 Ω−75%
\(|Z_{01}|\)1.754 Ω0.847 Ω−52%
\(I_{st}\)136.6 A283 A+107%

A predicted starting current more than twice the true value — enough to specify a starter, a cable and a protective device that are all wrong. The frequency correction is not a refinement.

Resistance is measured; reactance is measured and then scaled. That single asymmetry is the whole content of the reduced-frequency test: the wattmeter reading gives \(R_{01}\) directly at any frequency, while the reactance found from the same readings belongs to the test frequency alone and must be multiplied by \(f_{rated}/f_{test}\) before it means anything.
Answera\(R_{01} = 0.748\ \Omega,\ R_2' = 0.348\ \Omega\) b\(X_{01} = 1.586\ \Omega,\ X_1 = X_2' = 0.793\ \Omega\) c\(I_{st} = 136.6\ \text{A},\ T_{st} = 186\ \text{N·m}\) duncorrected: 283 A, 107% too high
Problem 3Exam levelFull Parameter Extraction

The following test data were taken on a 7.5 hp, 4-pole, 208 V, 60 Hz, Y-connected induction motor having a rated current of 28 A.

DC test: \(V_{DC} = 13.6\ \text{V}\), \(I_{DC} = 28.0\ \text{A}\).

ReadingNo-load testLocked-rotor test
\(V_T\)208 V25 V
\(I_A\)8.12 A28.1 A
\(I_B\)8.20 A28.0 A
\(I_C\)8.18 A27.6 A
\(f\)60 Hz15 Hz
\(P_{in}\)420 W920 W
  1. Sketch the per-phase equivalent circuit and give every parameter.
  2. Find the slip at the pull-out torque.
  3. Find the value of the pull-out torque.
Solution

Start with the DC test, because every later step needs \(R_1\). Direct current between two terminals of a star winding passes through two phases in series:

DC test connection: a direct-current supply applied between two line terminals of the star-connected stator, with a voltmeter across the terminals and an ammeter in the supply lead, so that the measured resistance is that of two phase windings in series
DC test — the meter sees two phases in series, so the per-phase resistance is half the reading
\[ R_1 = \frac{V_{DC}}{2I_{DC}} = \frac{13.6}{2\times28} = 0.243\ \Omega \]

No reactance, no rotor e.m.f. and no core loss can appear in a DC measurement, which is exactly why it is done first.

The no-load test. Average the three line currents and reduce the voltage to a phase value:

No-load test circuit: the three-phase supply at rated voltage feeding the stator through ammeters in each line and two wattmeters, with the motor running uncoupled at almost synchronous speed
No-load test — rated voltage, uncoupled shaft, and a slip so small that the rotor branch is effectively open
\[ I_{L,av} = \frac{8.12+8.20+8.18}{3} = 8.17\ \text{A}, \qquad V_{\phi,nl} = \frac{208}{\sqrt3} = 120\ \text{V} \]
\[ |Z_{nl}| = \frac{120}{8.17} = 14.7\ \Omega = X_1+X_m \]

Strip the stator copper loss out of the no-load input to leave the rotational and core losses:

\[ P_{SCL} = 3I_1^2R_1 = 3\times8.17^2\times0.243 = 48.7\ \text{W} \]
\[ P_{rot,nl} = P_{in,nl}-P_{SCL} = 420-48.7 = 371.3\ \text{W} \]

This 371 W is core loss plus friction and windage together; Problem 5 shows how a run at several voltages splits it.

The locked-rotor test, taken at 15 Hz so that the rotor resistance is measured at a realistic slip frequency:

Locked-rotor test circuit: a reduced-voltage variable-frequency supply feeding the stator through ammeters and wattmeters, with the rotor shaft mechanically clamped so that it cannot turn
Locked-rotor test — reduced voltage at 15 Hz, rotor clamped, rated current in the windings
\[ I_{L,av} = \frac{28.1+28.0+27.6}{3} = 27.9\ \text{A}, \qquad |Z_{LR}| = \frac{V_T}{\sqrt3\,I_L} = \frac{25}{\sqrt3\times27.9} = 0.517\ \Omega \]
\[ \theta = \cos^{-1}\frac{P_{in}}{\sqrt3V_TI_L} = \cos^{-1}\frac{920}{\sqrt3\times25\times27.9} = \cos^{-1}0.762 = 40.4^\circ \]

Resolve the locked-rotor impedance and correct the reactance to 60 Hz:

\[ R_{LR} = 0.517\cos40.4^\circ = 0.394\ \Omega = R_1+R_2' \;\Longrightarrow\; R_2' = 0.394-0.243 = 0.151\ \Omega \]
\[ X_{LR}'= 0.517\sin40.4^\circ = 0.335\ \Omega\ \text{(at 15 Hz)}, \qquad X_{LR} = \frac{60}{15}\times0.335 = 1.34\ \Omega \]
\[ X_1 = X_2' = \frac{1.34}{2} = 0.67\ \Omega, \qquad X_m = |Z_{nl}|-X_1 = 14.7-0.67 = 14.03\ \Omega \]

The completed per-phase circuit:

Completed per-phase equivalent circuit of the tested motor: stator resistance 0.243 ohm and leakage reactance 0.67 ohm in series from the 120 volt phase source, a magnetising reactance of 14.03 ohm in shunt, and a rotor branch of 0.67 ohm reactance in series with 0.151 ohm divided by slip
The per-phase circuit built from the three tests — every element traceable to one measurement
ParameterValueSource
\(R_1\)0.243 ΩDC test
\(R_2'\)0.151 ΩLocked rotor minus DC
\(X_1 = X_2'\)0.67 ΩLocked rotor, corrected to 60 Hz, halved
\(X_m\)14.03 ΩNo load minus \(X_1\)
Core loss + windage371.3 WNo load minus stator copper

Reduce the stator side to a Thevenin equivalent, as Set 28, Problem 6 requires before any pull-out calculation:

Thevenin equivalent of the stator side: a voltage source of 114.6 volts in series with a resistance of 0.221 ohm and a reactance of 0.67 ohm, feeding the rotor branch of 0.67 ohm reactance and 0.151 ohm divided by slip
Thevenin reduction — the machine left of the rotor branch replaced by one source and one impedance
\[ V_{Th} = 114.6\ \text{V}, \qquad R_{Th} = 0.221\ \Omega, \qquad X_{Th} \approx X_1 = 0.67\ \Omega \]

From \(V_{Th} = V_\phi X_m/\sqrt{R_1^2+(X_1+X_m)^2} = 120\times14.03/14.70\) and \(R_{Th} \approx R_1\left(X_m/(X_1+X_m)\right)^2 = 0.243\times(14.03/14.70)^2\).

The slip at pull-out torque:

\[ s_{maxT} = \frac{R_2'}{\sqrt{R_{Th}^2+(X_{Th}+X_2')^2}} = \frac{0.151}{\sqrt{(0.221)^2+(0.67+0.67)^2}} = \frac{0.151}{1.358} = 0.111 = 11.1\% \]

The pull-out torque. A 4-pole 60 Hz machine has \(N_s = 1800\) rpm, so \(\omega_s = 188.5\) rad/s:

\[ T_{max} = \frac{3V_{Th}^2}{2\omega_s\left[R_{Th}+\sqrt{R_{Th}^2+(X_{Th}+X_2')^2}\right]} = \frac{3(114.6)^2}{2(188.5)\left[0.221+1.358\right]} \]
\[ = \frac{39\,400}{595.3} = 66.2\ \text{N·m} \]

Against a rated torque of roughly \(7.5\ \text{hp} = 5.6\ \text{kW}\) at about 1750 rpm, or 30 N·m, this is a pull-out margin of about 2.2 — entirely normal for a general-purpose cage machine.

Three meters and a clamp produce a complete dynamic model of the machine. Nothing here required access to the rotor, knowledge of the winding, or the manufacturer's data — and from these five parameters the torque at every slip, the starting current, the pull-out point and the efficiency all follow. It is the same logic as the transformer's open- and short-circuit tests of Set 18, extended by one measurement to handle the rotating member.
Answera\(R_1 = 0.243\ \Omega,\ R_2' = 0.151\ \Omega,\ X_1 = X_2' = 0.67\ \Omega,\ X_m = 14.03\ \Omega\) b\(s_{maxT} = 11.1\%\) c\(T_{max} = 66.2\ \text{N·m}\)
Problem 4Exam levelSplitting the Leakage

Tests on a 460 V, 60 Hz, 4-pole, 3-phase star-connected, 25 hp induction motor give, per phase and at rated frequency, a blocked-rotor resistance \(R_{BL} = 0.50\ \Omega\), a blocked-rotor reactance \(X_{BL} = 1.90\ \Omega\), a no-load impedance \(|Z_{nl}| = 12.6\ \Omega\) and a DC stator resistance \(R_1 = 0.20\ \Omega\). The tests cannot separate \(X_1\) from \(X_2'\). Using the NEMA design-class rule,

  1. find \(X_1\), \(X_2'\) and \(X_m\) if the machine is Design B
  2. repeat for Design A and Design C
  3. compute the slip at maximum torque and the pull-out torque for each, and say how much the choice of split actually matters.
Solution

Understand what the tests can and cannot see. The blocked-rotor test measures the two leakage reactances in series, and no terminal measurement can distinguish them — there is no accessible node between them. What is measured is only

\[ X_{BL} = X_1+X_2' = 1.90\ \Omega \]

The rotor resistance is unambiguous, though: \(R_2' = R_{BL}-R_1 = 0.50-0.20 = 0.30\ \Omega\).

The NEMA convention assigns the split by design class, reflecting the rotor-slot geometry each class uses:

Design class\(X_1\)\(X_2'\)Rotor construction
A and wound rotor\(0.5X_{BL}\)\(0.5X_{BL}\)Normal slots, low resistance
B\(0.4X_{BL}\)\(0.6X_{BL}\)Deep, narrow bars — high rotor leakage
C\(0.3X_{BL}\)\(0.7X_{BL}\)Double cage
D\(0.5X_{BL}\)\(0.5X_{BL}\)High-resistance bars

Design B, the default for a general-purpose 25 hp machine:

\[ X_1 = 0.4\times1.90 = 0.76\ \Omega, \qquad X_2' = 0.6\times1.90 = 1.14\ \Omega \]
\[ X_m = |Z_{nl}|-X_1 = 12.6-0.76 = 11.84\ \Omega \]

Designs A and C by the same rule:

\[ \text{A:}\quad X_1 = X_2' = 0.95\ \Omega,\ X_m = 11.65\ \Omega; \qquad \text{C:}\quad X_1 = 0.57,\ X_2' = 1.33\ \Omega,\ X_m = 12.03\ \Omega \]

Note that \(X_m\) moves in the opposite direction to \(X_1\), because their sum is pinned by the no-load measurement.

Now the Thevenin quantities for each case, with \(V_\phi = 460/\sqrt3 = 265.6\ \text{V}\) and \(\omega_s = 188.5\ \text{rad/s}\):

Class\(X_1\)\(X_2'\)\(X_m\)\(V_{Th}\)\(R_{Th}\)\(X_{Th}\)
A / D0.950.9511.65245.5 V0.171 Ω0.881 Ω
B0.761.1411.84249.5 V0.177 Ω0.717 Ω
C0.571.3312.03253.5 V0.182 Ω0.547 Ω

The key observation. Add \(X_{Th}\) and \(X_2'\) in each row:

\[ \text{A: }0.881+0.95 = 1.831, \quad \text{B: }0.717+1.14 = 1.857, \quad \text{C: }0.547+1.33 = 1.877\ \Omega \]

All three are close to \(X_{BL} = 1.90\ \Omega\), and for the reason that \(X_{Th}\approx X_1\) while \(X_1+X_2' = X_{BL}\) is fixed. The quantity that governs both pull-out results is therefore almost independent of how the split is made.

Slip at maximum torque and pull-out torque, with \(R_2' = 0.30\ \Omega\) throughout:

Class\(\sqrt{R_{Th}^2+(X_{Th}+X_2')^2}\)\(s_{maxT}\)\(T_{max}\)
A / D1.839 Ω0.163238.7 N·m
B1.865 Ω0.161242.7 N·m
C1.886 Ω0.159247.3 N·m

The pull-out slip varies by 2.5% across the whole range of design classes and the pull-out torque by 3.6% — a spread far smaller than the uncertainty in the test readings themselves.

Where the split does matter. It is not the torque but the magnetising branch and the stator voltage drop:

\[ X_m: 11.65 \to 12.03\ \Omega\ (+3.3\%), \qquad V_{Th}: 245.5 \to 253.5\ \text{V}\ (+3.3\%) \]

These affect the no-load current, the power factor at light load and the core-loss estimate. For torque and slip predictions the convention can be applied with a clear conscience; for magnetising-current studies it should not be leaned on.

A convention that changes the answer by less than the measurement error is a good convention. The blocked-rotor test genuinely cannot separate \(X_1\) from \(X_2'\), and it does not need to: every torque quantity depends on \(X_{Th}+X_2' \approx X_1+X_2'\), which the test measures directly. The design-class rule exists so that the two reactances can be written down at all, not because the choice is critical.
AnsweraDesign B: \(X_1 = 0.76\ \Omega,\ X_2' = 1.14\ \Omega,\ X_m = 11.84\ \Omega\) bA: 0.95/0.95/11.65 Ω; C: 0.57/1.33/12.03 Ω c\(s_{maxT} = 0.159\)\(0.163\), \(T_{max} = 239\)\(247\ \text{N·m}\) — the split matters little
Problem 5CoreSeparating Windage From Core Loss

A 400 V, 50 Hz, 4-pole, 3-phase star-connected induction motor with a stator resistance of 0.35 Ω per phase is run uncoupled at rated frequency while the supply voltage is reduced in steps. The line readings are

Line voltage400 V350 V300 V250 V200 V
No-load current8.50 A7.35 A6.25 A5.20 A4.20 A
No-load input1256 W1054 W880 W733 W613 W

Separate the friction and windage loss from the core loss, and state the core loss at rated voltage.

Solution

Identify what the no-load input contains. With the shaft uncoupled the mechanical output is zero, so every watt drawn becomes a loss:

\[ P_0 = 3I_0^2R_1 + P_i + P_{fw} \]

The rotor copper loss is genuinely negligible here: the no-load slip is a few tenths of a per cent, so \(P_{cu2} = sP_g\) amounts to a watt or two.

Remove the stator copper loss from each reading, since it is the one term that depends on the current rather than on the voltage:

\[ P' = P_0-3I_0^2R_1 = P_i+P_{fw} \]
\(V_L\)\(I_0\)\(P_0\)\(3I_0^2R_1\)\(P' = P_i+P_{fw}\)\(V_L^2\)
400 V8.50 A1256 W75.9 W1180.1 W160 000
350 V7.35 A1054 W56.7 W997.3 W122 500
300 V6.25 A880 W41.0 W839.0 W90 000
250 V5.20 A733 W28.4 W704.6 W62 500
200 V4.20 A613 W18.5 W594.5 W40 000

Use the different voltage dependence of the two remaining losses. Core loss follows the flux, and hence the voltage, roughly as a square; friction and windage depends on speed, which barely changes:

\[ P' = P_{fw} + kV_L^2 \]

So plotting \(P'\) against \(V_L^2\) should give a straight line whose intercept is the friction and windage loss — the loss that survives when the flux is taken to zero.

Take the two extreme points to fix the line:

\[ k = \frac{1180.1-594.5}{160\,000-40\,000} = \frac{585.6}{120\,000} = 4.880\times10^{-3}\ \text{W/V}^2 \]
\[ P_{fw} = 594.5 - (4.880\times10^{-3})(40\,000) = 594.5-195.2 = 399\ \text{W} \approx 400\ \text{W} \]

Check the fit at the intermediate points — a curved plot would mean the square law has been broken by saturation:

\(V_L\)Measured \(P'\)Fitted \(399+kV_L^2\)Difference
350 V997.3 W996.8 W+0.5 W
300 V839.0 W838.2 W+0.8 W
250 V704.6 W704.0 W+0.6 W

Agreement to better than a watt, so the straight line is genuine and the extrapolation is trustworthy. A least-squares fit through all five points gives 399.5 W, confirming the two-point estimate.

The core loss at rated voltage is what is left after removing the intercept:

\[ P_i\big|_{400\ \text{V}} = 1180.1-400 = 780\ \text{W} \]
\[ \text{so at rated voltage:}\quad P_0 = \underbrace{76}_{\text{stator Cu}} + \underbrace{780}_{\text{core}} + \underbrace{400}_{\text{friction and windage}} = 1256\ \text{W}\;\checkmark \]

Why the separation is worth the extra readings. The two losses behave differently in every subsequent calculation:

LossValueWhere it leaves the power flowDepends on
Core loss780 WAt the stator, before the air gap\(V^2\) and frequency
Friction and windage400 WAt the shaft, after \(P_m\)Speed only

Lumping them together, as Problem 1 was content to do, puts 400 W in the wrong place in the ledger. It leaves the total loss right but the air-gap power — and therefore the torque — wrong.

Two losses that cannot be measured separately can still be separated, provided they depend on different variables. Here one scales with \(V^2\) and the other does not, so a single sweep of the supply voltage splits them by extrapolation to a condition — zero flux at full speed — that can never actually be reached. The same trick separates hysteresis from eddy-current loss by sweeping frequency instead.
Answer\(P_{fw} = 400\ \text{W}\) (intercept), \(P_i = 780\ \text{W}\) at 400 V
Problem 6Exam levelPredicting Full Load

The machine of Problem 5 — 400 V, 50 Hz, 4-pole, star-connected, \(R_1 = 0.35\ \Omega\) per phase, no-load 400 V, 8.50 A, 1256 W, of which 400 W is friction and windage — also gave a blocked-rotor test at rated frequency of 99 V, 40 A, 2880 W. Using the approximate equivalent circuit, predict at a full-load slip of 4%

  1. the referred rotor current and the line current
  2. the power factor
  3. the shaft output power
  4. the shaft torque
  5. the efficiency.
Solution

Extract the series-branch parameters from the blocked-rotor test:

\[ |Z_{01}| = \frac{99/\sqrt3}{40} = \frac{57.16}{40} = 1.429\ \Omega, \qquad R_{01} = \frac{2880}{3\times40^2} = 0.600\ \Omega \]
\[ X_{01} = \sqrt{1.429^2-0.600^2} = 1.297\ \Omega, \qquad R_2' = 0.600-0.35 = 0.250\ \Omega \]

Build the exciting branch from the core loss alone, not from the whole no-load input. Problem 5 established the split:

\[ 3I_0^2R_1 = 3\times8.50^2\times0.35 = 75.9\ \text{W}, \qquad P_i = 1256-75.9-400 = 780\ \text{W} \]
\[ I_w = \frac{P_i}{3V_{ph}} = \frac{780}{3\times230.9} = 1.126\ \text{A}, \qquad I_\mu = \sqrt{I_0^2-I_w^2} = \sqrt{8.50^2-1.126^2} = 8.425\ \text{A} \]

If the whole 1256 W were put into \(R_0\), the friction and windage would be charged to the machine twice — once at the terminals and again when it is deducted from \(P_m\). Here the shunt branch carries the core loss only.

Solve the series branch at 4% slip:

\[ \frac{R_2'}{s} = \frac{0.250}{0.04} = 6.25\ \Omega, \qquad Z = (0.35+6.25)+j1.297 = 6.60+j1.297 = 6.726\angle11.12^\circ\ \Omega \]
\[ I_2' = \frac{230.9}{6.726} = 34.33\angle-11.12^\circ = 33.69-j6.62\ \text{A} \]

Add the exciting current to get the line current and the power factor:

\[ I_0 = 1.13-j8.43\ \text{A}, \qquad I_1 = 34.82-j15.05 = 37.9\angle-23.4^\circ\ \text{A} \]
\[ \cos\phi_1 = \cos23.4^\circ = 0.918\ \text{lagging} \]

Air-gap power, mechanical power and shaft output:

\[ P_g = 3I_2'^2\frac{R_2'}{s} = 3\times34.33^2\times6.25 = 22\,103\ \text{W} \]
\[ P_{cu2} = sP_g = 884\ \text{W}, \qquad P_m = 0.96\times22\,103 = 21\,219\ \text{W} \]
\[ P_{out} = P_m-P_{fw} = 21\,219-400 = 20\,819\ \text{W} = 20.8\ \text{kW} \]

Input power, shaft torque and efficiency:

\[ P_1 = \sqrt3\,V_LI_1\cos\phi_1 = \sqrt3\times400\times37.9\times0.918 = 24\,121\ \text{W} \]
\[ N = 1500(1-0.04) = 1440\ \text{rpm}, \qquad T_{sh} = \frac{20\,819}{2\pi\times1440/60} = 138.1\ \text{N·m} \]
\[ \eta = \frac{20\,819}{24\,121} = 0.863 = 86.3\% \]

Verify by the loss ledger, which must close exactly if the exciting branch was built correctly:

TermExpressionValue
Shaft output20 819 W
Stator copper loss\(3I_2'^2R_1\)1238 W
Core lossfrom Problem 5780 W
Rotor copper loss\(sP_g\)884 W
Friction and windagefrom Problem 5400 W
Total24 121 W ✓

The ledger closing to the watt is the strongest available check that the parameters, the slip and the loss split are all consistent.

A sanity check on the prediction itself. The predicted full-load current of 37.9 A is close to the 40 A used in the blocked-rotor test, which is how such a test should be set up; the starting current would be \(230.9/1.429 = 162\ \text{A}\), or 4.3 times full load, and the output of 20.8 kW at 400 V is consistent with a 28 hp frame. Nothing in the answer is physically out of range.

Two tests and a DC measurement have predicted the full-load current, power factor, torque and efficiency of a machine that was never loaded. That is the point of the whole exercise: a loaded test of a 20 kW motor needs a 20 kW brake and 20 kW of electricity, while these tests need a fraction of rated power and no dynamometer at all.
Answera\(I_2' = 34.3\ \text{A},\ I_1 = 37.9\ \text{A}\) b\(0.918\ \text{lag}\) c\(P_{out} = 20.8\ \text{kW}\) d\(T_{sh} = 138\ \text{N·m}\) e\(\eta = 86.3\%\)
Formulas

Key Formulas

QuantityRelationNotes
DC test, star\(R_1 = V_{DC}/2I_{DC}\)Two phases in series — Problem 3
No-load power factor\(\cos\phi_0 = P_0/\sqrt3V_LI_0\)Typically 0.1–0.2 — Problem 1
Exciting components\(I_w = I_0\cos\phi_0,\ I_\mu = I_0\sin\phi_0\)Problem 1
Shunt branch\(R_0 = V_{ph}/I_w,\quad X_0 = V_{ph}/I_\mu\)Per phase — Problem 1
No-load impedance\(|Z_{nl}| = V_{ph}/I_0 \approx X_1+X_m\)Gives \(X_m\) once \(X_1\) is known — Problems 3, 4
Blocked-rotor resistance\(R_{01} = P_{BR}/3I^2 = R_1+R_2'\)Independent of test frequency — Problem 2
Blocked-rotor reactance\(X_{01} = \sqrt{|Z_{01}|^2-R_{01}^2}\)At the test frequency — Problem 2
Frequency correction\(X_{01}\big|_{f_r} = (f_r/f_t)X_{01}\big|_{f_t}\)Reactance only — Problems 2, 3
Leakage split\(X_1 = X_2' = 0.5X_{01}\) (A, D); \(0.4/0.6\) (B); \(0.3/0.7\) (C)NEMA convention — Problem 4
No-load loss split\(P_0 = 3I_0^2R_1+P_i+P_{fw}\)Problems 3, 5
Windage by extrapolation\(P_i+P_{fw} = P_{fw}+kV_L^2\)Intercept at \(V=0\) is \(P_{fw}\) — Problem 5
Starting current\(I_{st} = V_{ph}/|Z_{01}| = I_{BR}\dfrac{V_{rated}}{V_{BR}}\)Problems 1, 2
Starting torque\(T_{st} = 3I_{st}^2R_2'/\omega_s\)Air-gap power at \(s=1\) — Problem 2
Thevenin values\(V_{Th} = V_{ph}\dfrac{X_m}{\sqrt{R_1^2+(X_1+X_m)^2}},\ R_{Th}\approx R_1\left(\dfrac{X_m}{X_1+X_m}\right)^2\)Problems 3, 4
Pull-out slip and torque\(s_{maxT} = \dfrac{R_2'}{\sqrt{R_{Th}^2+(X_{Th}+X_2')^2}},\ T_{max} = \dfrac{3V_{Th}^2}{2\omega_s[R_{Th}+\sqrt{\cdots}]}\)Problems 3, 4
Pitfalls

Common Mistakes

  1. Taking the DC reading as the per-phase resistance. A star winding presents two phases in series, so \(R_1 = V_{DC}/2I_{DC} = 0.243\ \Omega\) in Problem 3, not 0.486 Ω. Every later parameter inherits the error.

  2. Correcting the blocked-rotor resistance for frequency. Only the reactance scales. In Problem 2 the wattmeter gives \(R_{01} = 0.748\ \Omega\) at 12.5 Hz and that number is used unchanged at 50 Hz.

  3. Forgetting to correct the reactance at all. Problem 2's uncorrected value predicts 283 A of starting current instead of 137 A — an error of more than 100%.

  4. Treating the whole no-load input as core loss. It also contains the no-load stator copper loss and the friction and windage — 76 W and 400 W of the 1256 W in Problem 5, so the core loss is 780 W, not 1256 W.

  5. Charging the friction and windage twice. If \(R_0\) is built from the whole no-load input and \(P_{fw}\) is then also subtracted from \(P_m\), the same 400 W is counted at both ends — the trap Problem 6 avoids by putting only the core loss in the shunt branch.

  6. Assuming the blocked-rotor test can separate \(X_1\) and \(X_2'\). It measures their sum, and only their sum. The design-class rule of Problem 4 is a convention, not a measurement.

  7. Using \(|Z_{nl}|\) as \(X_m\) directly. It is \(X_1+X_m\). In Problem 3 that is a 4.8% error, small but easily avoided once \(X_1\) is known.

  8. Using line voltage where phase voltage belongs. Every impedance in these tests is per phase, so the 25 V of Problem 3 becomes 14.4 V before it is divided by the current.

  9. Using \(R_1\) in place of \(R_{Th}\) in the pull-out formulae. In Problem 3 they are 0.243 Ω and 0.221 Ω, which happens to leave \(s_{maxT}\) unchanged at 11.1%; on a machine with a smaller \(X_m\) the difference would show.

  10. Running the blocked-rotor test at rated voltage. The standstill impedance is a few ohms, so rated voltage would drive four to six times rated current through the windings. The test voltage is chosen to give rated current — 83 V in Problem 1, 99 V in Problem 6.

Looking Ahead

The circuit of Set 28 now has numbers in it, obtained without loading the machine, without opening it, and without any information the nameplate does not carry. Three measurements — a DC reading, a run at no load and a run with the rotor clamped — fix five parameters, and Problem 6 turned those five into a complete prediction of full-load current, torque and efficiency.

The same two test results support a second, older method that dispenses with the circuit algebra altogether. Plot the no-load current phasor and the blocked-rotor current phasor on the complex plane and the locus of the stator current at every slip between them turns out to be a circle. Once it is drawn, output, torque, slip, power factor and efficiency at any load are read off as lengths on the diagram.

Next: Set 30 — The Circle Diagram, where the no-load and blocked-rotor points construct the locus, the output and torque lines are located, and full-load performance is obtained by measurement rather than calculation.