Set 39 — Synchronous Motor Performance and V-Curves
Drive a synchronous machine from the supply instead of into it and the phasor equation changes by one sign: the impedance drop is subtracted from the terminal voltage rather than added to it, and the excitation e.m.f. lags rather than leads. Everything else — the reactance, the load angle, the phasor construction — carries across unchanged from Set 36.
What is genuinely new is what happens when the field is swept at constant load. The speed cannot change, and the in-phase component of the armature current is pinned at \(P/3V\), so the only thing the excitation can move is the reactive current. The armature current therefore falls to a minimum and rises again, tracing the V-curve, and the power factor passes through unity at the bottom of it. This set computes that curve point by point, finds the excitation unity power factor demands at three different loads, and closes on the pull-out torque — the limit beyond which a machine that cannot slow down has nowhere left to go.
A synchronous motor is an alternator with the phasor equation rearranged. The machine now absorbs current from the supply, so the impedance drop is subtracted from the terminal voltage instead of added to it:
\[ \mathbf{E}_f = \mathbf{V} - \mathbf{I}_a\left(R_a + jX_s\right) \]Everything else is unchanged. \(\mathbf{E}_f\) now lags \(\mathbf{V}\) by the load angle \(\delta\), where in a generator it led.
Speed is not a variable. The rotor turns at \(N_s = 120f/P\) whatever the load, from no load to pull-out, and stops dead beyond it. Load changes \(\delta\), never the speed.
Power in terms of the load angle, with \(R_a\) neglected:
\[ P = \frac{3VE_f}{X_s}\sin\delta \;\Longrightarrow\; E_f\sin\delta = \frac{PX_s}{3V} = \text{constant at constant load} \]That constant is the key to every V-curve calculation: sweeping the excitation moves \(E_f\) and \(\delta\) together along a line of fixed \(E_f\sin\delta\).
Resolve the armature current about \(\mathbf{V}\), and its two components separate cleanly:
\[ I_a\cos\phi = \frac{E_f\sin\delta}{X_s} = \frac{P}{3V}, \qquad I_a\sin\phi = \frac{E_f\cos\delta - V}{X_s} \]The in-phase component is fixed by the load alone. Only the quadrature component responds to the field, and it is positive (leading) when \(E_f\cos\delta > V\).
The V-curve is the plot of \(I_a\) against excitation at constant load:
\[ I_a = \sqrt{\left(\frac{P}{3V}\right)^2 + \left(\frac{E_f\cos\delta - V}{X_s}\right)^2} \]Minimum where the second term vanishes, which is also where the power factor is unity. Under-excited to the left of the minimum the current lags; over-excited to the right it leads.
Unity power factor needs a definite excitation, obtained by setting \(E_f\cos\delta = V\):
\[ E_f = \sqrt{V^2 + \left(\frac{PX_s}{3V}\right)^2} \]It rises with load, so the V-curves form a family whose minima march to the right as the machine is loaded.
The inverted-V curve is the same sweep plotted as power factor instead of current: it peaks at unity where the V-curve dips, and falls away on both sides.
Maximum power and pull-out torque occur at \(\delta = 90^\circ\):
\[ P_{max} = \frac{3VE_f}{X_s}, \qquad T_{max} = \frac{P_{max}}{\omega_s} \]Both are proportional to \(E_f\), so an under-excited motor pulls out at a lower load. There is a minimum excitation below which a given load cannot be carried at all.
A 3-phase, star-connected, 3300 V, 50 Hz, 6-pole synchronous motor draws 160 A at 0.8 power factor leading. Its armature resistance is 0.5 Ω per phase and its synchronous reactance 8 Ω per phase. Determine
- the excitation e.m.f. per phase and its line value;
- the load angle;
- the input power and the mechanical power developed.
Take the terminal voltage as reference and write the current with its sign. A leading current has a positive angle:
The impedance drop:
The real part is negative because the leading current makes the reactive drop point backwards along \(\mathbf V\).
Subtract it — the motor sign convention:
The load angle is the argument of that phasor, and its negative imaginary part says \(\mathbf{E}_f\) lags \(\mathbf{V}\) — the signature of motoring:
Input power from the terminal quantities, and mechanical power by deducting the armature copper loss:
Sanity-check the excitation. The motor is running at 4886 V of internal e.m.f. against a 3300 V supply — 48 % over-excited. That is exactly what a leading power factor demands, and it is the whole basis of the machine's use as a power-factor corrector. A motor drawing lagging current would have shown \(E_f\) below 3300 V.
A 3-phase, star-connected, 3300 V, 50 Hz, 6-pole synchronous motor of synchronous reactance 8 Ω per phase drives a load that takes a constant 600 kW from the supply. Armature resistance may be neglected. Compute the armature current, load angle and power factor as the excitation is swept, taking excitation e.m.f.s of 1200, 1500, 1905, 2400 and 2800 V per phase, and locate the minimum of the curve exactly.
One quantity is fixed by the load and does not move. With \(R_a = 0\) the power-angle relation gives
Whatever the excitation, \(E_f\) and \(\sin\delta\) adjust so that their product stays at 839.8 V. Raise the field and the load angle falls; weaken it and the angle opens up.
So does the in-phase component of the current. Resolving \(\mathbf{I}_a = (\mathbf{V}-\mathbf{E}_f)/jX_s\) along \(\mathbf V\):
Only the quadrature component varies:
Working one point in full, at \(E_f = 1500\) V per phase:
Repeating for each excitation gives the V-curve:
| \(E_f\) (V/phase) | Line value (V) | \(\delta\) | \(E_f\cos\delta\) (V) | \(I_a\) (A) | Power factor |
|---|---|---|---|---|---|
| 1200 | 2079 | 44.41° | 857.2 | 167.9 | 0.625 lagging |
| 1500 | 2598 | 34.05° | 1242.9 | 133.7 | 0.785 lagging |
| 1905 | 3300 | 26.15° | 1710.2 | 107.8 | 0.974 lagging |
| 2082 | 3606 | 23.79° | 1905.3 | 105.0 | 1.000 |
| 2400 | 4157 | 20.48° | 2248.3 | 113.4 | 0.926 leading |
| 2800 | 4850 | 17.45° | 2671.1 | 142.1 | 0.739 leading |
The current falls, reaches a minimum and rises again — the V shape that names the curve. The load angle, by contrast, decreases monotonically throughout.
Locate the minimum exactly. The quadrature term vanishes when \(E_f\cos\delta = V\), and with \(E_f\sin\delta = 839.8\) already fixed,
Note the row that surprises people. At \(E_f = 1905\) V the excitation e.m.f. exactly equals the terminal voltage, and the power factor is still 0.974 lagging, not unity. Equality of magnitudes is not the unity-power-factor condition; equality of the projections, \(E_f\cos\delta = V\), is. On load the projection always falls short, so unity power factor demands over-excitation.
For the motor of Problem 2, plot the power factor against excitation as a table and identify the normal excitation. Then find how the unity-power-factor excitation and the minimum armature current change when the load is 300 kW and when it is 900 kW, and state what this does to the family of V-curves.
The power factor at each excitation comes straight from Problem 2, since \(\cos\phi = (P/3V)/I_a\) and the numerator is fixed:
| \(E_f\) (V/phase) | 1200 | 1500 | 1905 | 2082 | 2400 | 2800 |
|---|---|---|---|---|---|---|
| Power factor | 0.625 | 0.785 | 0.974 | 1.000 | 0.926 | 0.739 |
| Nature | lagging | lagging | lagging | — | leading | leading |
A single-peaked curve, maximum at the same excitation where the V-curve is minimum. Plotted downwards it is the mirror image of the V, which is why it is called the inverted-V or power-factor curve.
The peak is "normal excitation". Below it the machine is under-excited and behaves like an inductive load; above it it is over-excited and behaves like a capacitive one. The terms describe the machine's reactive behaviour and have nothing to do with any rated field current.
Now change the load. The unity-power-factor excitation is the same expression with a new \(P\):
| Load | \(E_f\sin\delta\) (V) | Unity-p.f. \(E_f\) (V/phase) | Line value (V) | \(\delta\) there | \(I_{a,\text{min}}\) (A) |
|---|---|---|---|---|---|
| 300 kW | 419.9 | 1951.0 | 3379 | 12.43° | 52.5 |
| 600 kW | 839.8 | 2082.1 | 3606 | 23.79° | 105.0 |
| 900 kW | 1259.7 | 2284.0 | 3956 | 33.47° | 157.5 |
Reading the family. Three things happen together as the load rises:
- the whole V-curve lifts, because its minimum \(P/3V\) is proportional to the load;
- the minimum moves to the right, because more excitation is needed to hold unity power factor;
- the curve becomes flatter near its minimum, so the power factor is less sensitive to small field changes.
The locus of the minima — the line joining the unity-power-factor points — slopes upward and to the right across the family, and it is drawn on every manufacturer's V-curve chart.
A practical consequence. A field setting chosen to give unity power factor at 600 kW leaves the motor over-excited and taking leading current at 300 kW, and under-excited and taking lagging current at 900 kW. A fixed field is a fixed field; if unity power factor is required over a load range, the excitation must be regulated, and that regulator is what an automatic power-factor controller drives.
A 3-phase, star-connected, 400 V, 50 Hz synchronous motor takes 50 kW from the supply at unity power factor. Its armature resistance is 0.2 Ω per phase and its synchronous reactance 1.5 Ω per phase. Find the excitation e.m.f., the load angle and the mechanical power developed. Then state what happens to the power factor if the load is increased with the field left alone.
The armature current is in phase with the terminal voltage, which is what unity power factor means and what makes this the simplest case of all:
Subtract the impedance drop. With \(\mathbf{I}_a\) real, the resistive drop comes off the real part and the reactive drop appears entirely as an imaginary part:
Magnitude and angle:
The excitation e.m.f. is 4.8 % above the terminal voltage. Even at unity power factor the motor must be slightly over-excited, for the reason set out in Problem 2.
Mechanical power developed, after the armature copper loss:
Friction, windage and iron losses would come off this figure to give the shaft output; they are not given here.
What happens if the load rises with the field fixed. The excitation e.m.f. is set by the field current and stays at 242.06 V; the load angle must therefore open up to carry the extra power. As \(\delta\) grows, \(E_f\cos\delta\) falls below \(V\), and by the resolution of Problem 2 the quadrature current turns lagging. A motor set for unity power factor at one load will always be under-excited at any larger load, and its power factor will worsen in the lagging direction.
The 3300 V, 6-pole, \(X_s = 8\ \Omega\) motor of Problem 2 carries its 600 kW load with the excitation set for unity power factor, that is \(E_f = 2082\) V per phase. Neglecting armature resistance, determine
- the maximum power the machine can develop and the pull-out torque;
- the ratio of pull-out torque to full-load torque;
- the smallest excitation at which the 600 kW load could be carried at all.
The power-angle characteristic peaks at 90°, where \(\sin\delta = 1\):
Speed is fixed, so torque follows by division. A 6-pole 50 Hz machine runs at 1000 rev/min:
The pull-out ratio. At 600 kW the running torque is
Because the speed never changes, the torque ratio and the power ratio are the same number — a convenience unique to the synchronous machine.
What pulling out means here. Load the motor beyond 1487.6 kW and \(\delta\) is driven past 90°. Beyond that angle a further advance of the load angle reduces the developed power, so the rotor cannot recover: it falls out of step, the current becomes large and oscillatory, and the machine stalls. There is no slower stable speed to run down to, as there would be in an induction motor.
The minimum excitation. The 600 kW load can be carried only if \(P_{max} \ge 600\) kW, so
This is exactly the constant \(E_f\sin\delta\) found in Problem 2 — and it must be, because at the limit \(\sin\delta = 1\). Weaken the field below 44 % of the per-phase terminal voltage and the machine drops out no matter how carefully it is handled.
Comparing three excitations at the same load:
| \(E_f\) (V/phase) | \(P_{max}\) (kW) | \(\delta\) at 600 kW | Pull-out margin |
|---|---|---|---|
| 839.8 | 600.0 | 90.0° | 1.00 — on the point of stalling |
| 1200 | 857.4 | 44.41° | 1.43 |
| 2082 | 1487.6 | 23.79° | 2.48 |
Excitation buys stability margin as directly as it buys leading kVAR, and the same field rheostat delivers both.
The motor of Problem 5 is running at 600 kW with \(E_f = 2082\) V per phase, giving unity power factor. The mechanical load is now raised to 900 kW and the field rheostat is not touched. Find the new load angle, armature current and power factor, and the field change needed to restore unity power factor.
Only the load angle can respond. The speed is fixed by the supply frequency and \(E_f\) is fixed by the untouched field, so the extra power must come from a larger \(\delta\):
The angle has opened from 23.79° to 37.23°. Physically the rotor has slipped back by 13.4 electrical degrees — about 4.5 mechanical degrees on a 6-pole machine — and then re-locked at the new position.
The current components:
Hence the new operating point:
The quadrature term has gone negative: \(E_f\cos\delta\) is now below \(V\), so the machine that was at unity power factor has become under-excited without the field being altered at all.
Restoring unity power factor needs the excitation of Problem 3's table at 900 kW:
At that excitation \(\delta\) settles back to 33.47° and the current falls from 160.5 A to 157.5 A.
Summarising the three states:
| Condition | Load | \(E_f\) | \(\delta\) | \(I_a\) | Power factor |
|---|---|---|---|---|---|
| Original | 600 kW | 2082 V | 23.79° | 105.0 A | 1.000 |
| Load raised, field fixed | 900 kW | 2082 V | 37.23° | 160.5 A | 0.981 lagging |
| Field restored | 900 kW | 2284 V | 33.47° | 157.5 A | 1.000 |
The stability cost of leaving the field alone. At \(E_f = 2082\) V the pull-out power is 1487.6 kW, so the margin has fallen from 2.48 at 600 kW to 1487.6/900 = 1.65. Raising the field to 2284 V restores it to 1632/900 = 1.81. Excitation therefore buys margin as well as power factor, which is why a large synchronous motor is normally left over-excited rather than trimmed to unity.
Key Formulas
| Quantity | Relation | Notes |
|---|---|---|
| Motor phasor equation | \(\mathbf{E}_f = \mathbf{V} - \mathbf{I}_a(R_a+jX_s)\) | Note the minus — Problems 1, 4 |
| Load angle | \(\delta = \arg(\mathbf{V}) - \arg(\mathbf{E}_f)\) | \(\mathbf{E}_f\) lags for a motor |
| Synchronous speed | \(N_s = 120f/P\) | Independent of load, always |
| Power-angle relation | \(P = (3VE_f/X_s)\sin\delta\) | \(R_a\) neglected — Problems 2, 5, 6 |
| Constant of the V-curve | \(E_f\sin\delta = PX_s/3V\) | Fixed while the load is fixed |
| In-phase current | \(I_a\cos\phi = P/3V\) | Set by the load, not the field |
| Quadrature current | \(I_a\sin\phi = (E_f\cos\delta - V)/X_s\) | Positive = leading — Problem 2 |
| V-curve | \(I_a = \sqrt{(P/3V)^2+\left((E_f\cos\delta-V)/X_s\right)^2}\) | Minimum at unity power factor |
| Unity-p.f. excitation | \(E_f = \sqrt{V^2+(PX_s/3V)^2}\) | Rises with load — Problems 3, 4, 6 |
| Minimum armature current | \(I_{a,\text{min}} = P/3V\) | The bottom of the V |
| Maximum power | \(P_{max} = 3VE_f/X_s\) at \(\delta = 90^\circ\) | Proportional to excitation — Problem 5 |
| Pull-out torque | \(T_{max} = P_{max}/\omega_s\), \(\omega_s = 2\pi N_s/60\) | Torque ratio equals power ratio |
| Minimum excitation for a load | \(E_f \ge PX_s/3V\) | Below it the machine cannot hold step |
| Mechanical power | \(P_{mech} = P_{in} - 3I_a^2R_a\) | Before friction, windage and iron loss |
Common Mistakes
Adding the impedance drop instead of subtracting it. A motor absorbs current, so \(\mathbf{E}_f = \mathbf{V} - \mathbf{I}_aZ_s\); using the generator sign gives an \(E_f\) that is wrong and a load angle of the wrong sign — Problem 1.
Taking \(E_f = V\) as the unity-power-factor condition. The condition is \(E_f\cos\delta = V\); at \(E_f = V\) the motor of Problem 2 is still at 0.974 lagging — Problems 2 and 4.
Expecting the load angle to be minimum where the current is. The load angle falls monotonically with excitation; only the current turns round — Problem 2.
Letting the in-phase current change with excitation. It is \(P/3V\) and cannot move while the load is constant; if a V-curve calculation shows it moving, the arithmetic is wrong — Problem 2.
Using a leading angle with a negative sign, or a lagging one with a positive sign. Fix the convention at the start — leading current positive — and keep it — Problem 1.
Believing a synchronous motor slows down under overload. It runs at \(N_s\) or it stops; there is no intermediate speed — Problem 5.
Forgetting that pull-out torque is proportional to excitation. Weakening the field to trim the power factor also erodes the stability margin — Problems 5 and 6.
Confusing the mechanical and electrical load angle. 37.2 electrical degrees is 12.4 mechanical degrees on a 6-pole machine — Problem 6.
Assuming a field setting stays correct as the load changes. Unity power factor at one load means lagging current at any larger one — Problems 3, 4 and 6.
Quoting the terminal power as the mechanical power. Subtract \(3I_a^2R_a\) first, and the rotational losses after that — Problems 1 and 4.
The V-curve is really one observation written six different ways: at constant load the in-phase current is pinned and only the quadrature current can move, so the field rheostat is a reactive-power control and nothing else. That is an odd thing for a motor to be, and it is the reason synchronous machines are still specified for large constant-speed drives long after induction motors took over everything else.
Two threads are left hanging. The power-angle relation has been used repeatedly but never made the subject of a problem in its own right, and the leading current the machine can be made to draw has been treated as a curiosity rather than as something to be sold. Both are worth money: one decides how close a machine runs to its stability limit, the other decides how large a capacitor bank a factory does not have to buy.
Next: Set 40 — Power Angle and Power-Factor Correction, where a synchronous condenser is sized for a plant, a motor is asked to drive a load and correct the power factor at the same time, and the two demands are shown to compete for the same field current.