By the end of this chapter you should be able to:
Name the four parameters that describe a transformer and say which test yields each.
Perform the open-circuit test and compute \(R_0\) and \(X_0\).
Explain which winding each test is performed on, and why.
Perform the short-circuit test and compute \(R_{01}\) and \(X_{01}\).
Explain why each test isolates one kind of loss.
Predetermine the efficiency at any load from the two readings.
Predetermine the regulation at any power factor.
Explain why the rating is given in kVA and not kW.
Why Test Rather Than Load

The performance of a transformer can be calculated from its equivalent circuit, and these tests are very economical and convenient, because they furnish the required information without actually loading the transformer.
The Four Parameters
The equivalent circuit of Chapter 44 contains four parameters, here referred to the primary:
the equivalent resistance \(R_{01}\);
the equivalent leakage reactance \(X_{01}\);
the core-loss conductance \(G_0\), or equivalently the resistance \(R_0\);
the magnetising susceptance \(B_0\), or equivalently the reactance \(X_0\).
| Test | Applies | Wattmeter reads | Yields |
|---|---|---|---|
| Open circuit | Rated voltage, no load | Iron loss | \(R_0\), \(X_0\) |
| Short circuit | Rated current, low voltage | Copper loss | \(R_{01}\), \(X_{01}\) |
Rated flux without rated current in one test; rated current without rated flux in the other. That is the whole idea.
The Open-Circuit Test

The shunt branch parameters are determined by this test.
The core loss and the magnetising current depend on the applied voltage only and are practically unaltered by the load current — the point established in Chapter 41 and used ever since.
Hence rated voltage is supplied, generally to the LV winding, keeping the HV winding open.
Since \(I_0\) is very small compared with the full-load current, the loss in \(R_1\) is neglected.
Thus the whole of \(W_0\) drawn from the source is dissipated as heat in the core.
The no-load power factor is very low — around 0.2 — so an ordinary wattmeter reads badly. A low-power-factor wattmeter must be used, or the reading will be dominated by its own error.
The test must also be conducted at rated voltage and rated frequency. Chapter 42 showed that \(X_0\) depends on the permeability and so on the operating flux density; values measured at half voltage would be wrong.
Problem. An open-circuit test on the LV side of the 2200/220 V, 50 kVA transformer used throughout Part 3 gives 220 V, 12 A, 500 W. Find the shunt-branch parameters referred to the LV side and to the HV side.
Power factor and components.
Parameters on the LV side.
Referred to the HV side. Dividing by \(K^{2} = 0.01\):
Comment. These are exactly the values assumed in Chapter 42, and the LV current of 12 A corresponds to \((0.1)(12) = 1.2\) A on the HV side — again the figure used there. Chapters 42 to 45 took these parameters on trust; this test is where they actually come from.
Note that \(I_0\) is 12 A against a rated LV current of \(50\,000/220 = 227.3\) A, so the test draws about 5 % of rated current and dissipates 500 W in a 50 kVA machine — one percent of rating.
Which Winding, and Why
Either test can in principle be done from either side, but there is a strongly preferred choice in each case, and it is a practical matter of instruments and safety.
Rated voltage must be applied, and it is far easier and safer to raise 220 V than 2200 V.
The current is small either way, so ammeter range is not a problem.
The HV winding, left open, has full rated voltage across it — but no current, so it is safe if not touched.
Rated current must be circulated, and the HV current is the smaller of the two — 22.7 A rather than 227 A.
Only a few percent of rated voltage is needed, so the supply is easy to obtain and control.
Shorting the LV winding needs only a thick link, not a switch rated for the full current.
Whichever side is used, the parameters obtained refer to that side, and must be transferred by \(K^{2}\) before being combined with quantities on the other. Failing to do so is the commonest error in these calculations.
The Short-Circuit Test

The input voltage is reduced to a small fraction of rated value and the secondary terminals are short-circuited.
A current then circulates in the secondary winding.
Since only a small fraction of rated voltage is applied, the flux in the core — and hence the core loss — is very small.
Hence the power input on short circuit is dissipated as heat in the windings.
Since the applied voltage is very small, of the order of 5 to 8 %, the magnetising branch can be eliminated from the equivalent circuit altogether.
The applied voltage, expressed as a percentage of rated, is the percentage impedance — and by Chapter 45 it is also the maximum possible regulation.
At 5 % of rated voltage the flux density is 5 % of normal. Since \(P_h \propto B_m^{1.6}\) and \(P_e \propto B_m^{2}\), the iron loss falls to somewhere between \((0.05)^{1.6} = 0.0083\) and \((0.05)^{2} = 0.0025\) of its rated value.
For the transformer of this chapter that is 1.3 to 4.1 W out of a 702 W reading — well under the accuracy of the wattmeter. The test isolates the copper loss almost perfectly.
Problem. A short-circuit test on the HV side of the same transformer, with the LV winding shorted, gives 109 V, 22.73 A, 702 W. Find \(Z_{01}\), \(R_{01}\), \(X_{01}\) and the percentage impedance.
Check the current is the rated value.
Impedance.
Resistance.
Reactance.
Percentage impedance.
Comment. These recover the values used in Chapters 43 to 45 — \(R_{01} = 1.36~\Omega\), \(X_{01} = 4.60~\Omega\), \(Z_{01} = 4.797~\Omega\). The equivalent circuit is now fully determined by measurement rather than assumption.
Note how little the test costs. It runs at rated current, so the windings reach their normal working temperature — but the supply provides only \((109)(22.73) = 2.48\) kVA, 5 % of the machine's rating. The 702 W dissipated is precisely the full-load copper loss, which is the point.
Separating Hysteresis and Eddy Loss
The open-circuit wattmeter reads the total iron loss. If the two components are wanted separately, the test is repeated.
Carry out two open-circuit experiments using two different frequencies, but with the same maximum flux density in each. Since \(B_m \propto V/f\) from Chapter 41, that means holding the volts per hertz constant: halve the frequency and halve the voltage.
Plotting \(W_0/f\) against \(f\) gives a straight line whose intercept is \(A\) and slope is \(B\), and hence \(P_h = Af\) and \(P_e = Bf^{2}\) at any frequency.
The requirement of equal flux density is essential and easily overlooked. If the voltage were held constant while the frequency changed, \(B_m\) would change too, and the two unknowns could not be separated — the measurement would confound a change of frequency with a change of flux. Chapter 42 worked a numerical example of this separation.
Predetermining Efficiency and Regulation
The two wattmeter readings are the two losses of Chapter 44, and the impedance from the short-circuit test gives the percentage drops of Chapter 45. Everything follows.
\(W_0\) is the constant iron loss; \(W_{sc}\) the full-load copper loss.
with + for lagging, − for leading.
Problem. From the test results of Examples 46.1 and 46.2 — \(W_0 = 500\) W, \(W_{sc} = 702\) W — find the efficiency at quarter, half, three-quarter and full load at 0.8 power factor, and the load for maximum efficiency.
| Load \(x\) | Output (W) | Iron (W) | Copper (W) | Efficiency |
|---|---|---|---|---|
| 0.25 | 10 000 | 500 | 43.9 | 94.84 % |
| 0.50 | 20 000 | 500 | 175.5 | 96.73 % |
| 0.75 | 30 000 | 500 | 394.9 | 97.10 % |
| 0.844 | 33 756 | 500 | 500.0 | 97.12 % |
| 1.00 | 40 000 | 500 | 702.0 | 97.08 % |
Maximum-efficiency load.
Comment. These figures reproduce Chapter 44's Table 44.2, which used the same losses. The difference is that here they were measured, and by two tests that between them handled 2.5 kVA of a 50 kVA machine.
Problem. From the short-circuit data — \(V_{sc} = 109\) V, \(I_{sc} = 22.73\) A, \(R_{01} = 1.359~\Omega\), \(X_{01} = 4.599~\Omega\) — find the percentage drops and the full-load regulation at 0.8 lagging, unity and 0.8 leading.
Percentage drops.
Regulation.
| Power factor | Working | Regulation |
|---|---|---|
| 0.8 lagging | \((1.404)(0.8) + (4.752)(0.6)\) | +3.974 % |
| Unity | \((1.404)(1) + 0\) | +1.404 % |
| 0.8 leading | \((1.404)(0.8) - (4.752)(0.6)\) | −1.728 % |
Cross-check.
Comment. These match Chapter 45's 3.975 %, 1.405 % and −1.727 % to three decimal places, the small differences being rounding in the test readings.
The cross-check is worth making a habit. The percentage impedance computed from \(v_r\) and \(v_x\) must equal \(V_{sc}/V_1\) read straight off the voltmeter — if it does not, the arithmetic has gone astray somewhere between the two.
Why the Rating Is in kVA
The tests just described explain the convention directly, because each measures a loss governed by a different quantity.
Copper losses \(\left(I^{2}R\right)\) depend on the current passing through the transformer winding — which the short-circuit test measures at rated current.
Iron losses — core and insulation losses — depend on the voltage — which the open-circuit test measures at rated voltage.
Total losses therefore depend on voltage and current, expressed together in volt-amperes, and not on the load power factor.
Hence the transformer rating is expressed in VA or kVA, not in W or kW.
Manufacturers design a transformer with no idea which kind of load will be connected to it. The load may be resistive, inductive, capacitive, or a mixture of all three.
There would therefore be a different power factor at the secondary for every kind of load. A rating in kW would be meaningless without also stating the power factor — whereas the limits the machine actually has, its winding current and its core flux, are properties of the machine alone.
Problem. A 5 kVA, 500/250 V, 50 Hz transformer gives the following results. OC test on the LV side: 250 V, 1.0 A, 60 W. SC test on the HV side: 25 V, 10 A, 100 W. Find the complete equivalent circuit, the efficiency at full load and 0.8 power factor, the maximum efficiency, and the full-load regulation at 0.8 lagging.
Rated currents.
The SC test was indeed run at rated HV current \(\checkmark\)
Shunt branch, from the OC test (LV side).
Series branch, from the SC test (HV side).
Efficiency at full load, 0.8 power factor.
Maximum efficiency.
Regulation at full load, 0.8 lagging.
Comment. Note the cross-check: \(\sqrt{v_r^{2} + v_x^{2}} = \sqrt{4.000 + 21.00} = 5.000\,\%\), exactly the percentage impedance read from the voltmeter \(\checkmark\)
Two tests, drawing 250 VA and 250 VA respectively, have determined a 5 kVA machine completely. Each test handled 5 % of the rating, and between them they yield the efficiency at every load, the regulation at every power factor, and all four circuit parameters.
Note also that the maximum efficiency lies at 77 % of full load. Since \(x = \sqrt{W_0/W_{sc}}\), a transformer with iron loss below full-load copper loss always peaks below full load — which is the normal design for distribution service, as Chapter 44 explained.
Summary and Key Formulas
Four parameters describe the transformer: \(R_{01}\), \(X_{01}\), and the shunt branch \(R_0\) (or \(G_0\)) and \(X_0\) (or \(B_0\)).
The open-circuit test applies rated voltage with the far winding open. Iron loss and magnetising current depend on voltage alone, so \(W_0\) is the iron loss and \(R_0 = V_1^{2}/W_0\), \(X_0 = V_1/I_\mu\).
The short-circuit test applies 5 to 8 % of rated voltage with the far winding shorted. Flux and hence iron loss are negligible, so \(W_{sc}\) is the full-load copper loss and \(Z_{01} = V_{sc}/I_{sc}\), \(R_{01} = W_{sc}/I_{sc}^{2}\), \(X_{01} = \sqrt{Z_{01}^{2} - R_{01}^{2}}\).
Supply the LV side for the OC test (rated voltage is easier) and the HV side for the SC test (rated current is smaller).
Use a low-power-factor wattmeter for the OC test, and hold rated voltage and frequency.
Two OC tests at different frequencies but the same flux density separate hysteresis from eddy loss, since \(W_0/f = A + Bf\).
Efficiency at any load follows from \(W_0\) and \(W_{sc}\); regulation at any power factor from \(v_r\) and \(v_x\).
The rating is in kVA because copper loss follows current and iron loss follows voltage, neither depending on power factor — and the manufacturer cannot know the load.
| Quantity | Formula | From |
|---|---|---|
| No-load power factor | \(\cos\phi_0 = \dfrac{W_0}{V_1I_0}\) | OC test |
| Core-loss component | \(I_w = I_0\cos\phi_0\) | OC test |
| Magnetising component | \(I_\mu = I_0\sin\phi_0\) | OC test |
| Core-loss resistance | \(R_0 = \dfrac{V_1}{I_w} = \dfrac{V_1^{2}}{W_0}\) | OC test |
| Magnetising reactance | \(X_0 = \dfrac{V_1}{I_\mu}\) | OC test |
| Equivalent impedance | \(Z_{01} = \dfrac{V_{sc}}{I_{sc}}\) | SC test |
| Equivalent resistance | \(R_{01} = \dfrac{W_{sc}}{I_{sc}^{2}}\) | SC test |
| Equivalent reactance | \(X_{01} = \sqrt{Z_{01}^{2} - R_{01}^{2}}\) | SC test |
| Percentage impedance | \(\dfrac{V_{sc}}{V_1}\times100 = \sqrt{v_r^{2}+v_x^{2}}\) | SC test |
| Efficiency | \(\eta = \dfrac{xS\cos\phi}{xS\cos\phi + W_0 + x^{2}W_{sc}}\) | both |
| Maximum-efficiency load | \(x = \sqrt{W_0/W_{sc}}\) | both |
| Regulation | \(v_r\cos\phi \pm v_x\sin\phi\) | SC test |
| Loss separation | \(W_0/f = A + Bf\) | two OC tests |
Common Mistakes
Forgetting which side the parameters refer to. OC on LV gives LV-side values; transfer by \(K^{2}\) before combining with SC values from the HV side.
Computing \(R_0\) as \(V_1/I_0\). It is \(V_1/I_w\), equivalently \(V_1^{2}/W_0\).
Treating \(W_0\) as copper loss or \(W_{sc}\) as iron loss. Each test isolates the other one.
Running the SC test at rated voltage. That is a short circuit in earnest — 20 times rated current.
Running the OC test below rated voltage. \(X_0\) depends on the flux density, so the value would be wrong.
Using an ordinary wattmeter for the OC test. At a power factor near 0.2, a low-power-factor instrument is required.
Doing the two-frequency test at constant voltage. The volts per hertz must be held constant so that \(B_m\) does not change.
Forgetting that \(W_{sc}\) is the full-load copper loss. Only if the test ran at rated current; otherwise scale by the square of the current ratio.
Omitting the cross-check. \(\sqrt{v_r^{2}+v_x^{2}}\) must equal \(V_{sc}/V_1\).
Quoting a transformer rating in kW. Its limits are current and voltage, neither of which involves power factor.
Chapter Review
Always note which winding each test was performed on, and check that the SC current is the rated value for that side.
P46.1 An OC test on the 200 V LV side gives 200 V, 0.8 A, 70 W. Find \(\cos\phi_0\), \(I_w\), \(I_\mu\), \(R_0\) and \(X_0\).
Show answer
\[\cos\phi_0 = \frac{70}{160} = 0.4375, \qquad \sin\phi_0 = 0.8992\]\[I_w = 0.350~\mathrm{A}, \qquad I_\mu = 0.7194~\mathrm{A}\]\[R_0 = \frac{(200)^{2}}{70} = 571.4~\Omega, \qquad X_0 = \frac{200}{0.7194} = 278.0~\Omega\]P46.2 An SC test gives 30 V, 15 A, 250 W on a 600 V winding. Find \(Z_{01}\), \(R_{01}\), \(X_{01}\) and the percentage impedance.
Show answer
\[Z_{01} = \frac{30}{15} = 2.000~\Omega, \qquad R_{01} = \frac{250}{225} = 1.111~\Omega\]\[X_{01} = \sqrt{4.000 - 1.235} = \sqrt{2.765} = 1.663~\Omega\]\[\%Z = \frac{30}{600}\times100 = 5.00\,\%\]P46.3 A 10 kVA transformer has \(W_0 = 120\) W and \(W_{sc} = 200\) W. Find the efficiency at full load, 0.9 pf.
Show answer
\[\eta = \frac{9000}{9000 + 120 + 200} = \frac{9000}{9320} = 96.57\,\%\]P46.4 For P46.3, find the load for maximum efficiency and that efficiency.
Show answer
\[x = \sqrt{\frac{120}{200}} = 0.7746 \quad\Longrightarrow\quad 7.746~\mathrm{kVA}\]\[\eta_{\max} = \frac{(7746)(0.9)}{6971 + 240} = \frac{6971}{7211} = 96.67\,\%\]P46.5 For the transformer of P46.2 on a 600 V winding rated 15 A, find \(v_r\), \(v_x\) and the regulation at 0.85 lagging.
Show answer
\[v_r = \frac{(15)(1.111)}{600}\times100 = 2.778\,\%, \qquad v_x = \frac{(15)(1.663)}{600}\times100 = 4.158\,\%\]\[\sin\phi = 0.5268\]Check: \(\sqrt{v_r^{2}+v_x^{2}} = 5.00\,\%\), equal to \(V_{sc}/V_1\) \(\checkmark\)\[\text{Regulation} = (2.778)(0.85) + (4.158)(0.5268) = 2.361 + 2.190 = 4.551\,\%\]P46.6 An SC test is run at 12 A instead of the rated 15 A, giving 160 W. Find the full-load copper loss.
Show answer
Copper loss varies as the square of the current, so the reading must be scaled up.\[W_{sc,FL} = (160)\left(\frac{15}{12}\right)^{2} = (160)(1.5625) = 250~\mathrm{W}\]P46.7 Why is the OC test performed on the LV side and the SC test on the HV side?
Show answer
Each test is placed on the side that makes the awkward quantity manageable.OC test needs rated voltage, and the LV winding has the lower voltage — far easier and safer to supply 220 V than 2200 V. The current is small either way, so nothing is lost.
SC test needs rated current, and the HV winding has the lower current — 22.7 A rather than 227 A. Only a few percent of rated voltage is needed, so the supply is easy to obtain, and shorting the LV winding requires only a thick link.
Since the two windings differ in voltage and current in opposite senses, the two tests naturally fall on opposite sides. Whichever side is used, the parameters obtained refer to that side and must be transferred by \(K^{2}\) before being combined.
P46.8 Explain quantitatively why the SC test measures copper loss almost free of iron loss.
Show answer
Because the applied voltage is only about 5 % of rated, and from Chapter 41 \(B_m \propto V\), so the flux density is 5 % of normal.Iron loss follows \(P_h \propto B_m^{1.6}\) and \(P_e \propto B_m^{2}\), so it falls to between \((0.05)^{1.6} = 0.0083\) and \((0.05)^{2} = 0.0025\) of its rated value.
For a machine with 500 W of iron loss that is 1.3 to 4.1 W — against a short-circuit wattmeter reading of some 700 W. The contamination is a fraction of a percent, well below the instrument's own accuracy.
The converse argument applies to the OC test: at 5 % of rated current the copper loss is \((0.05)^{2} = 0.25\,\%\) of its full-load value.
P46.9 Why must the two-frequency loss-separation test hold the flux density constant?
Show answer
Because the relation being fitted, \(W_0 = Af + Bf^{2}\), assumes \(A\) and \(B\) are constants — and they are constants only at a fixed \(B_m\). In full, \(P_h = k_hB_m^{1.6}f\) and \(P_e = k_eB_m^{2}f^{2}\).If the voltage were held fixed while the frequency changed, then \(B_m \propto V/f\) would change too, and both coefficients would vary from one reading to the next. The measurement would confound a change of frequency with a change of flux, and the two unknowns could not be separated.
The remedy is to hold the volts per hertz constant — halve the frequency and halve the voltage — so that \(B_m\) is identical in both experiments and only \(f\) varies.
P46.10 Explain fully why a transformer is rated in kVA rather than kW.
Show answer
Because its two limits are thermal, and neither involves power factor.The winding may not exceed its rated current, or the \(I^{2}R\) loss overheats it. The core may not exceed its rated voltage, or the flux density saturates it and the iron loss and magnetising current run away. The product of these two limits is a volt-ampere limit.
The losses correspond exactly: copper loss is fixed by current, iron loss by voltage. Neither depends on the load's power factor, so the machine is equally fully loaded regardless of what it is feeding.
The manufacturer also cannot know the load. It may be resistive, inductive, capacitive or mixed, giving a different power factor in every installation. A rating in kW would be meaningless without also stating that power factor.
The same 50 kVA transformer delivers 50 kW at unity power factor, 40 kW at 0.8, and no real power at all into a purely reactive load — while being fully loaded in every case.
MCQ 1. The open-circuit test determines:
(a) \(R_{01}\) and \(X_{01}\) (b) \(R_0\) and \(X_0\) (c) the turns ratio (d) the copper lossShow answer
(b) \(R_0\) and \(X_0\), the shunt branch.MCQ 2. In the OC test the wattmeter reads essentially:
(a) copper loss (b) iron loss (c) total loss (d) output powerShow answer
(b) iron loss, since the current is only a few percent of rated.MCQ 3. The OC test is normally performed on the:
(a) HV side (b) LV side (c) either, equally (d) both simultaneouslyShow answer
(b) LV side, because rated voltage must be applied and the LV value is lower.MCQ 4. The SC test applies about:
(a) rated voltage (b) 50 % of rated (c) 5–8 % of rated (d) zero voltageShow answer
(c) 5–8 % of rated, just enough to circulate rated current.MCQ 5. In the SC test the iron loss is negligible because:
(a) the core is removed (b) the flux is only a few percent of normal (c) the frequency is low (d) the current is smallShow answer
(b) the flux is only a few percent of normal, and iron loss follows \(B_m^{1.6}\) to \(B_m^{2}\).MCQ 6. \(R_{01}\) is obtained from the SC test as:
(a) \(V_{sc}/I_{sc}\) (b) \(W_{sc}/I_{sc}\) (c) \(W_{sc}/I_{sc}^{2}\) (d) \(W_{sc}/V_{sc}\)Show answer
(c) \(W_{sc}/I_{sc}^{2}\). The first option gives \(Z_{01}\).MCQ 7. The voltage applied in the SC test, as a percentage of rated, equals the:
(a) efficiency (b) percentage impedance (c) turns ratio (d) power factorShow answer
(b) percentage impedance — and hence the maximum possible regulation.MCQ 8. A low-power-factor wattmeter is needed for the:
(a) OC test (b) SC test (c) both (d) neitherShow answer
(a) OC test, where the power factor is around 0.2.MCQ 9. To separate hysteresis from eddy loss, the two tests must have the same:
(a) frequency (b) voltage (c) flux density (d) currentShow answer
(c) flux density, achieved by holding the volts per hertz constant.MCQ 10. A transformer is rated in kVA because its losses depend on:
(a) power factor (b) voltage and current, not power factor (c) load type (d) frequency onlyShow answer
(b) voltage and current, not power factor. Iron loss follows voltage, copper loss follows current.
Name the four equivalent-circuit parameters and say which test yields each.
Describe the open-circuit test and derive \(R_0\) and \(X_0\) from its readings.
Explain which winding is supplied for each test, and why.
Describe the short-circuit test and derive \(Z_{01}\), \(R_{01}\) and \(X_{01}\).
Show quantitatively why each test isolates one loss.
Explain how hysteresis and eddy loss are separated, and why the flux density must be held constant.
Show how efficiency and regulation are predetermined from the two sets of readings.
Explain fully why a transformer's rating is expressed in kVA.
The two tests give every parameter, but neither loads the transformer. Neither therefore reveals the temperature rise, which is what actually determines the rating — exactly the limitation Chapter 39 identified in Swinburne's test on a DC machine.
Chapter 47 supplies the remedy with Sumpner's test, also called the back-to-back test, which does for transformers what Hopkinson's test did for DC machines. Two identical transformers are connected so that their secondaries oppose; one supply circulates rated current through the windings while a second establishes rated flux in the cores. Both machines then run at full load simultaneously while the mains provides only the losses — so a proper heat run becomes affordable, and iron and copper losses are read on separate wattmeters at the same time.
Chapter 48 then takes up efficiency in more detail and introduces the autotransformer, in which a single winding serves as both primary and secondary — with a saving in copper that grows dramatically as the ratio approaches unity.