Electrical Machines · Chapter 52

Three-Phase Transformer Connections

Part 3 · Transformers — one core or three, and four ways to connect the windings, each with a different line ratio and a different character.

Prof. Mithun Mondal Engineering Devotion Digital Textbook
i Learning Objectives

By the end of this chapter you should be able to:

  • Describe the two ways of obtaining three-phase transformation.

  • Prove that the central limb of a three-phase core carries no flux.

  • Explain why the middle winding of a shell type is reversed.

  • Give the merits and limitations of a single three-phase unit against a bank.

  • Compute the line voltages, line currents and kVA for each of the four connections.

  • State the line-voltage ratio of each connection in terms of \(K\).

  • Explain the 30° phase shift and its consequence for paralleling.

  • Explain the third-harmonic problem of the star-star connection and its remedies.

Section 52-1

Bank or Single Unit

A three-phase transformer can be constructed in two different ways:

  • Using one pre-assembled and balanced three-phase transformer, consisting of three pairs of single-phase windings mounted onto one single laminated core.

  • Connecting together three single-phase transformers, known as a transformer bank.

Electrically the two are equivalent — the same connections, the same ratios, the same phasor relations. They differ in cost, size and, decisively, in what happens when one phase fails. Sections 52-2 to 52-4 deal with the physical difference; the rest of the chapter applies equally to both.
Video · Three-Phase Transformers
Section 52-2

Core-Type Construction

Evolution of the three-limb core-type three-phase transformer
Core-type construction.

The construction is best understood as an evolution in three steps.

  1. Three single-phase cores are positioned at \(120^{\circ}\) to one another, sharing a common central return limb.
  2. For balanced three-phase sinusoidal voltages applied, the fluxes \(\Phi_a\), \(\Phi_b\) and \(\Phi_c\) are also sinusoidal and balanced, so the total combined flux in the merged limb becomes zero. The central limb can therefore be removed, since it carries no flux.
  3. That structure is still not convenient to build. The practical form is a core of three limbs in the same plane, built from stacked laminations, each limb carrying the low-voltage and high-voltage windings of one phase.
! The Price of the Flat Core

The three-limb core is not magnetically symmetrical. The magnetising paths of limbs a and c are longer than that of the central limb b, because the outer fluxes must travel further through the yokes to return.

The result is an imbalance in the magnetising currents — the outer phases draw more than the centre. Since the exciting current is only a few percent of full load, the effect on the load currents is negligible, but it is measurable at no load and it makes the no-load currents of the three phases unequal.

1 Worked Example 52.1 — Proving the Central Limb Carries No Flux

Problem. Show that for balanced three-phase excitation the flux in the merged central limb is zero.

The three fluxes, each of peak value \(\Phi_m\) and displaced by \(120^{\circ}\):

\[\Phi_a = \Phi_m\angle0^{\circ}, \qquad \Phi_b = \Phi_m\angle-120^{\circ}, \qquad \Phi_c = \Phi_m\angle+120^{\circ}\]

In rectangular form, taking \(\Phi_m = 1\):

\[\begin{aligned} \Phi_a &= +1.00000 + j0.00000\\ \Phi_b &= -0.50000 - j0.86603\\ \Phi_c &= -0.50000 + j0.86603 \end{aligned}\]

Adding.

\[\text{real: } 1.00000 - 0.50000 - 0.50000 = 0\]
\[\text{imaginary: } 0.00000 - 0.86603 + 0.86603 = 0\]
\[\boxed{\Phi_a + \Phi_b + \Phi_c = 0}\]

Comment. The sum vanishes identically, not approximately. A limb carrying zero flux serves no purpose, so it is removed — saving its iron, its weight and its cost.

This is the same statement as the closure of the flux phasor triangle: three equal phasors at \(120^{\circ}\), laid tip to tail, return to their starting point. It is also the exact magnetic counterpart of the electrical result that balanced three-phase currents need no neutral conductor.

The condition is balance. If the three voltages are unbalanced the sum is no longer zero, and the residual flux must find a path — through the tank and structural steel of a three-limb core, causing stray loss and heating. Section 52-6 returns to this.

Three balanced fluxes sum to zero drawn from a common point placed tip to tail — the triangle closes Φa Φb Φc 120° apart, equal magnitude Φa Φb Φc start = finish Φa + Φb + Φc = 0 so the central limb carries no flux and can be removed entirely
Why a three-phase core needs no return limb.
Section 52-3

Shell-Type Construction

Shell-type three-phase transformer formed by stacking three single-phase shell units
Shell-type construction.
  • The shell type is constructed by stacking three single-phase shell transformers one above another.

  • The winding direction of the central unit b is made opposite to that of units a and c.

  • If the system is balanced with phase sequence a-b-c, the flux will also be balanced.

  • The magnitude of the combined flux in the sections joining adjacent units is then equal to the magnitude of each of its components.

🔁
Why the Middle Winding Is Reversed
It turns a difference into a sum

The flux in the section between units a and b is the combination of their two fluxes. Which combination depends on the winding sense:

\[\text{same sense: } \left|\Phi_a - \Phi_b\right| = \sqrt3\,\Phi_m\]
\[\text{middle reversed: } \left|\Phi_a + \Phi_b\right| = \left|-\Phi_c\right| = \Phi_m\]

Reversing the middle winding replaces a phasor difference by a phasor sum, and the sum of two of three balanced phasors is simply the negative of the third. The flux there falls from 1.732 to 1.000 times the phase flux — so the iron in those sections can be 42.3 % smaller.

2 Worked Example 52.2 — The Effect of the Reversal

Problem. Compute the flux in the joining section with and without the reversal, and find the saving in iron there.

Without reversal — the fluxes oppose in the joining section:

\[\Phi_a - \Phi_b = (1 + j0) - (-0.5 - j0.86603) = 1.5 + j0.86603\]
\[\left|\Phi_a - \Phi_b\right| = \sqrt{(1.5)^{2} + (0.86603)^{2}} = \sqrt{3} = 1.73205\,\Phi_m\]

With the middle winding reversed — they now add:

\[\Phi_a + \Phi_b = (1 + j0) + (-0.5 - j0.86603) = 0.5 - j0.86603\]
\[\left|\Phi_a + \Phi_b\right| = \sqrt{(0.5)^{2} + (0.86603)^{2}} = 1.00000\,\Phi_m\]

Saving.

\[1 - \frac{1.00000}{1.73205} = 1 - \frac{1}{\sqrt3} = 0.4226 = 42.26\,\%\]

Comment. The check that makes it memorable: since \(\Phi_a + \Phi_b + \Phi_c = 0\) from Example 52.1, it follows that \(\Phi_a + \Phi_b = -\Phi_c\), whose magnitude is \(\Phi_m\) by definition. The result is forced by the same identity that removed the central limb.

The saving is real iron. The joining sections need only 57.7 % of the cross-section they would otherwise require, and since they run the width of the stack, the reversal is worth roughly a sixth of the core's total weight — for the price of connecting one winding the other way round.

Flux in the joining section of a shell-type core 1.732 Φm 1.000 Φm all windings the same way combined flux = |Φa − Φb| middle winding reversed combined flux = |Φa + Φb| = |−Φc| 42.3 % less so the iron there can be 42.3 % smaller
Reversing the middle winding cuts the flux in the joining section from 1.732 to 1.000 times the phase flux.
Section 52-4

Merits and Limitations

Merits of a single three-phase unit
  • For the same kVA rating it is smaller, cheaper and lighter than three single-phase transformers connected together, because the copper and the iron core are used more effectively.

  • It requires a smaller quantity of iron and copper; for an equal rating its cost is nearly 15 % less.

  • Its smaller size allows a smaller tank and hence a smaller quantity of oil for cooling.

  • It occupies less space and has less weight.

  • It needs a smaller number of bushings, and the bus-bar structure and switchgear installation are simpler.

  • It operates at slightly better efficiency and regulation.

Limitations
  • It is difficult and costly to repair.

  • A single large unit is harder to transport than three smaller ones carried individually.

  • A fault or loss of one phase results in complete shutdown, because a common core is shared by all three.

  • The core of the defective phase saturates immediately, in the absence of an opposing magnetic field. Flux then escapes from the core to the metal enclosure, heating the metallic parts — and in some cases causing fire.

  • To restore service, the spare unit costs far more than one single-phase transformer.

  • Under self-cooling the capacity is reduced.

The trade is therefore between first cost, which favours the single unit, and continuity of supply, which favours the bank. Example 52.5 puts numbers on both sides.

Section 52-5

The Four Connections

The four three-phase transformer winding connections
The winding connections.

Each side of a three-phase transformer may be connected in star or in delta, giving four combinations. Everything follows from two elementary relations.

Star
\[V_L = \sqrt3\,V_{ph}, \qquad I_L = I_{ph}\]

Higher voltage per line, same current — so fewer turns and less insulation per phase.

Delta
\[V_L = V_{ph}, \qquad I_L = \sqrt3\,I_{ph}\]

Higher current per line, same voltage — so a thinner conductor per phase.

🔢
The Line-Voltage Ratio
Only the mixed connections change it

With \(K = N_1/N_2\) the ratio of each individual transformer, the ratio of line voltages is:

\[\text{Y-Y and }\Delta\text{-}\Delta:\ K \qquad \text{Y-}\Delta:\ \sqrt3\,K \qquad \Delta\text{-Y}:\ \frac{K}{\sqrt3}\]

Like connections preserve the turns ratio; mixed connections multiply or divide it by \(\sqrt3\) — and introduce a 30° phase shift as well.

Note that the kVA is the same in every case. Three transformers of 10 kVA form a 30 kVA bank however they are connected; the connection redistributes voltage and current but cannot create capacity.

3 Worked Example 52.3 — All Four Connections Compared

Problem. Three identical single-phase transformers, each rated 10 kVA, 200/100 V, 50 Hz, are connected in each of the four ways. Tabulate the line voltages, line currents and total kVA.

Winding currents, the same in every connection since each transformer is unchanged:

\[I_{HV} = \frac{10\,000}{200} = 50~\mathrm{A}, \qquad I_{LV} = \frac{10\,000}{100} = 100~\mathrm{A}\]
Table 52.1 — Three 10 kVA, 200/100 V transformers in each connection. \(K = 2\).
ConnectionHV \(V_L\)HV \(I_L\)LV \(V_L\)LV \(I_L\)Line ratioTotal kVA
Y-Y346.41 V50.00 A173.21 V100.00 A2.0000 = \(K\)30.00
Y-Δ346.41 V50.00 A100.00 V173.21 A3.4641 = \(\sqrt3K\)30.00
Δ-Y200.00 V86.60 A173.21 V100.00 A1.1547 = \(K/\sqrt3\)30.00
Δ-Δ200.00 V86.60 A100.00 V173.21 A2.0000 = \(K\)30.00

Sample working, the Y-Y connection. Both sides in star, so line voltage is \(\sqrt3\) times phase voltage and line current equals winding current:

\[V_{L,HV} = \sqrt3\,(200) = 346.41~\mathrm{V}, \qquad V_{L,LV} = \sqrt3\,(100) = 173.21~\mathrm{V}\]
\[\text{Total kVA} = \frac{\sqrt3\,V_LI_L}{1000} = \frac{\sqrt3\,(173.21)(100)}{1000} = 30.00~\mathrm{kVA}\]

And the Y-Δ connection, where the LV side is delta so the line current is \(\sqrt3\) times the winding current:

\[V_{L,LV} = 100~\mathrm{V}, \qquad I_{L,LV} = \sqrt3\,(100) = 173.21~\mathrm{A}\]
\[\text{Total kVA} = \frac{\sqrt3\,(100)(173.21)}{1000} = 30.00~\mathrm{kVA}\]

Comment. Every connection delivers 30.00 kVA — three times 10 kVA, as it must. The connection cannot alter the capacity, only the voltage and current at which it is delivered.

The line ratios span a factor of three, from 1.1547 for Δ-Y to 3.4641 for Y-Δ, though every transformer in the bank has the same 2 : 1 ratio. This is the practical value of the mixed connections: they provide a \(\sqrt3\) adjustment of the overall ratio without altering a single turn.

Section 52-6

Star-Star

Star-star connection of a three-phase transformer
The star-star connection.
  • Generally used for small, high-voltage transformers. Because of the star connection the number of turns per phase is reduced, since \(V_{ph} = V_L/\sqrt3\), and the amount of insulation required is reduced with it.

  • This connection can be used only if the connected load is balanced.

Two Serious Problems
  • Unbalanced loading. The connection is not satisfactory for unbalanced load in the absence of a neutral connection. If the neutral is not provided, the phase voltages become severely unbalanced when the load is unbalanced.

  • Third harmonics. The magnetising current contains a third harmonic which, under balanced conditions, is equal in magnitude and in phase in all three phases. Their sum at the star point is therefore not zero. With no path for that current, the flux wave is distorted, producing a voltage with harmonics in each of the transformers.

Both problems are solved by solidly grounding the neutral, or by providing a tertiary delta winding.

The third-harmonic point is the one to understand properly. Fundamental components in the three phases are 120° apart and sum to zero. But third harmonics are three times that, 360° apart — which means they are all in phase with one another. They cannot cancel at the star point, so without a neutral or a delta they simply cannot flow, and the magnetising current is forced to be sinusoidal — which, through the non-linear B-H curve of Chapter 42, forces the flux to be non-sinusoidal instead. Chapter 54 develops this fully.
Section 52-7

Star-Delta and Delta-Star

Star-delta connection of a three-phase transformer
The star-delta connection.
Star-Delta (Y-Δ) — stepping down
  • Mainly used as a step-down transformer at the substation end of a transmission line, where the voltage is to be stepped down.

  • The ratio of secondary to primary line voltage is \(1/\sqrt3\) times the transformation ratio of each transformer.

  • Third-harmonic currents flow in the delta, providing a sinusoidal flux.

Delta-Star (Δ-Y) — stepping up
  • Used to step up the voltage, for example at the beginning of a high-tension transmission system.

  • Provides a three-phase four-wire service with the star neutral grounded.

  • Popular because it can serve both three-phase power equipment and single-phase lighting circuits.

  • The secondary line voltage is \(\sqrt3\) times the transformation ratio of each transformer.

The 30° Phase Shift
Why mixed banks cannot be paralleled with like ones

In both mixed connections there is a \(30^{\circ}\) shift between the primary and secondary line voltages and line currents.

A Y-Δ or Δ-Y bank therefore cannot be paralleled with either a Y-Y or a Δ-Δ bank, however well the ratios and impedances match — the fourth condition of Chapter 49.

A 30° difference between two sources of equal magnitude leaves a difference voltage of \(2\sin15^{\circ} = 0.518\) per unit across a total impedance of perhaps 0.10 pu, driving a circulating current of about five times rated.

This is what vector groups exist to record. The notation Dyn11, Yd1 and so on states the connection of each winding and the phase displacement in units of 30°, so that compatibility can be checked at a glance. Chapter 53 takes up the notation in full.

4 Worked Example 52.4 — Why Star on HV and Delta on LV

Problem. A 500 kVA, 33 kV / 415 V transformer is to be connected Δ-Y or Y-Δ. Compare the HV phase voltage, turns per phase at 10 V per turn, and phase current for the two possible HV connections.

HV in star.

\[V_{ph} = \frac{33\,000}{\sqrt3} = 19\,052.6~\mathrm{V}, \qquad N = \frac{19\,052.6}{10} = 1905~\text{turns}\]
\[I_{ph} = I_L = \frac{500\,000}{\sqrt3\,(33\,000)} = 8.748~\mathrm{A}\]

HV in delta.

\[V_{ph} = 33\,000~\mathrm{V}, \qquad N = \frac{33\,000}{10} = 3300~\text{turns}\]
\[I_{ph} = \frac{8.748}{\sqrt3} = 5.051~\mathrm{A}\]

The comparison.

\[\frac{N_{star}}{N_{delta}} = \frac{1905}{3300} = \frac{1}{\sqrt3} = 0.5774 \quad\Longrightarrow\quad 42.26\,\%\ \text{fewer turns}\]
\[\frac{I_{delta}}{I_{star}} = \frac{5.051}{8.748} = \frac{1}{\sqrt3} = 0.5774 \quad\Longrightarrow\quad 42.26\,\%\ \text{thinner conductor}\]

Comment. Star on the HV side needs 42.3 % fewer turns and 42.3 % less insulation per phase, since the winding stands at 19.05 kV rather than 33 kV. At high voltage, insulation dominates cost, so star wins.

Delta on the LV side needs a conductor of only 57.7 % the cross-section, and at low voltage copper dominates cost — so delta wins there. The delta also supplies the path the third harmonic needs, and tolerates unbalanced loading.

Hence the standard practice: star on the high-voltage side, delta on the low-voltage side, giving Y-Δ for a step-down substation and Δ-Y for a step-up at a generating station. The LV star of a Δ-Y unit is retained where a four-wire distribution neutral is needed, and its 415 V phase voltage of 239.6 V is exactly the domestic single-phase supply.

Section 52-8

Delta-Delta

  • Generally used for large, low-voltage transformers. The number of turns per phase is relatively greater than for the Y-Y connection, but the conductor is correspondingly thinner.

  • This connection can be used even for unbalanced loading.

  • Even if one transformer is disabled, the system can continue to operate in open-delta connection, though with reduced available capacity.

  • The closed delta gives the third-harmonic magnetising current a path to circulate, so the flux stays sinusoidal and no harmonic voltages are induced.

The delta's tolerance of unbalance and harmonics comes from the same property: it is a closed loop. Any current that must circulate — third-harmonic magnetising current, or the zero-sequence current an unbalanced load demands — has somewhere to go. The star point of a Y-Y connection offers no such path, which is the root of both of that connection's problems.
5 Worked Example 52.5 — What a Failed Phase Costs

Problem. A 1500 kVA three-phase supply is provided either by a bank of three 500 kVA single-phase units in Δ-Δ, or by one 1500 kVA three-phase unit costing 15 % less. Compare the cost of holding a spare, and the capacity available after one phase fails.

Spare holding.

\[\text{Bank: spare} = 500~\mathrm{kVA} = 33.3\,\%\ \text{of the installation}\]
\[\text{Single unit: spare} = 1500~\mathrm{kVA} = 100\,\%\ \text{of the installation}\]

Cost with a spare held, taking the bank's cost as 1.00 and the single unit's as 0.85:

\[\text{Bank} = 1.00 + 0.333 = 1.333\]
\[\text{Single unit} = 0.85 + 0.85 = 1.700\]
\[\frac{1.700 - 1.333}{1.333} = 27.5\,\%\ \text{dearer}\]

Capacity after one phase fails. The bank runs on in open delta:

\[S_{open} = \sqrt3\,(500) = 866.03~\mathrm{kVA} = 57.74\,\%\ \text{of the original}\]
\[\text{each survivor loaded to } \frac{866.03}{2(500)} = 86.60\,\%\ \text{of its own rating}\]

The single three-phase unit gives 0 kVA — complete shutdown.

Comment. The single unit's 15 % cost advantage reverses to a 27.5 % penalty once a spare must be held, because the spare must be a whole three-phase machine rather than a third of one.

And the operational difference is starker still. The bank loses 42 % of its capacity and keeps running; the single unit loses all of it. Where continuity is worth more than first cost — a steel mill, a hospital, a remote substation with a long repair lead time — the bank is chosen despite being dearer.

Chapter 53 derives the 57.74 % figure and explains why the two survivors can only be loaded to 86.6 %, rather than the 100 % one might expect.

Section 52-9

Choosing a Connection

Table 52.2 — Comparison of the four connections.
Y-YY-ΔΔ-YΔ-Δ
Line ratio\(K\)\(\sqrt3K\)\(K/\sqrt3\)\(K\)
Phase shift30°30°
Neutral availableBoth sidesHV onlyLV onlyNeither
Unbalanced loadPoorGoodGoodGood
Third-harmonic pathNoneIn the deltaIn the deltaIn the delta
Continues on one phase lostNoNoNoYes, open delta
Typical useSmall HV units, with tertiaryStep-down at a substationStep-up at a generating stationLarge LV units
The Working Rules
Four questions decide it
  • Is a neutral needed? A four-wire distribution supply needs star on the LV side.

  • Which side is high voltage? Star there saves insulation.

  • Is there at least one delta? If not, a tertiary must be added or the neutral solidly earthed.

  • Must it parallel with existing plant? Then the vector group must match exactly.

Section 52-10

Summary and Key Formulas

  • Three-phase transformation is obtained either from one three-phase unit on a single core or from a bank of three single-phase transformers.

  • For balanced excitation \(\Phi_a + \Phi_b + \Phi_c = 0\), so the central limb carries no flux and is removed. The practical core has three limbs in one plane, which is magnetically asymmetrical — the outer phases draw more magnetising current.

  • In the shell type the middle winding is reversed, replacing \(\left|\Phi_a - \Phi_b\right| = \sqrt3\Phi_m\) by \(\left|\Phi_a + \Phi_b\right| = \Phi_m\) — 42.3 % less iron in the joining sections.

  • A single unit is about 15 % cheaper, smaller, lighter and simpler to connect; a bank is easier to transport and repair, and keeps running on two phases.

  • Star: \(V_L = \sqrt3V_{ph}\), \(I_L = I_{ph}\). Delta: \(V_L = V_{ph}\), \(I_L = \sqrt3I_{ph}\).

  • Line ratios: Y-Y and Δ-Δ give \(K\); Y-Δ gives \(\sqrt3K\); Δ-Y gives \(K/\sqrt3\). The kVA is \(3\times\) the unit rating in every case.

  • Mixed connections introduce a 30° phase shift, so they cannot be paralleled with Y-Y or Δ-Δ banks.

  • Y-Y is troubled by unbalanced loading and by third harmonics, which are in phase in all three phases and cannot sum to zero at the star point. Remedy: solid earthing of the neutral, or a tertiary delta.

  • Δ-Δ tolerates unbalance and harmonics because the closed loop gives circulating current a path, and survives the loss of one phase as an open delta.

  • Standard practice: star on the HV side to save insulation, delta on the LV side to save copper and to carry the harmonic.

Table 52.3 — Formulas of this chapter.
QuantityFormulaNotes
Flux balance\(\Phi_a + \Phi_b + \Phi_c = 0\)removes the central limb
Shell joining flux, same sense\(\left|\Phi_a - \Phi_b\right| = \sqrt3\,\Phi_m\)1.732
Shell joining flux, reversed\(\left|\Phi_a + \Phi_b\right| = \Phi_m\)42.3 % less iron
Star relations\(V_L = \sqrt3V_{ph},\ I_L = I_{ph}\)
Delta relations\(V_L = V_{ph},\ I_L = \sqrt3I_{ph}\)
Line ratio, Y-Y and Δ-Δ\(K\)no phase shift
Line ratio, Y-Δ\(\sqrt3\,K\)30° shift
Line ratio, Δ-Y\(K/\sqrt3\)30° shift
Total capacity\(S = \sqrt3\,V_LI_L = 3S_{unit}\)same in all four
Open-delta capacity\(\sqrt3\,S_{unit} = 0.5774\,S_{\Delta\Delta}\)Chapter 53
Section 52-11

Common Mistakes

  • Thinking a connection changes the kVA. Three 10 kVA units give 30 kVA in every connection.

  • Applying \(\sqrt3\) to voltage and current on the same side. Star takes it on voltage, delta on current — never both.

  • Using \(K\) as the line ratio for mixed connections. Y-Δ gives \(\sqrt3K\) and Δ-Y gives \(K/\sqrt3\).

  • Getting Y-Δ and Δ-Y the wrong way round. The first letter is the HV winding.

  • Ignoring the 30° shift when paralleling. It makes a mixed bank incompatible with a like one whatever the ratios.

  • Saying third harmonics cancel at the star point. They are in phase, so they add rather than cancel.

  • Believing a three-limb core is magnetically symmetrical. The outer limbs have longer paths.

  • Forgetting the shell type's reversed middle winding. Without it the joining flux is \(\sqrt3\) times larger.

  • Assuming a single unit is always cheaper. Once a spare is held, the bank usually wins.

  • Expecting a Y-Y bank to run on unbalanced load without a neutral. The phase voltages shift badly.

Section 52-12

Chapter Review

Practice Problems

Work always from the winding voltage and current of one transformer, then apply the star or delta relation to each side separately.

  1. P52.1 Three 25 kVA, 1100/220 V transformers are connected Δ-Y. Find the line voltages, line currents and total kVA.

    Show answer
    \[I_{HV} = \frac{25\,000}{1100} = 22.727~\mathrm{A}, \qquad I_{LV} = \frac{25\,000}{220} = 113.64~\mathrm{A}\]
    HV in delta, LV in star:
    \[V_{L,HV} = 1100~\mathrm{V}, \qquad I_{L,HV} = \sqrt3\,(22.727) = 39.36~\mathrm{A}\]
    \[V_{L,LV} = \sqrt3\,(220) = 381.05~\mathrm{V}, \qquad I_{L,LV} = 113.64~\mathrm{A}\]
    \[S = \frac{\sqrt3\,(381.05)(113.64)}{1000} = 75.00~\mathrm{kVA}\]
  2. P52.2 For P52.1, find the line-voltage ratio and check it against \(K/\sqrt3\).

    Show answer
    \[\frac{1100}{381.05} = 2.8868, \qquad K = \frac{1100}{220} = 5, \qquad \frac{K}{\sqrt3} = \frac{5}{1.7321} = 2.8868 \quad\checkmark\]
  3. P52.3 The same three transformers are connected Y-Δ. Find the line voltages and the line ratio.

    Show answer
    \[V_{L,HV} = \sqrt3\,(1100) = 1905.3~\mathrm{V}, \qquad V_{L,LV} = 220~\mathrm{V}\]
    \[\text{ratio} = \frac{1905.3}{220} = 8.6603 = \sqrt3\,K = \sqrt3\,(5) \quad\checkmark\]
  4. P52.4 A three-limb core has a mean flux path of 1.10 m for the centre limb and 1.35 m for each outer limb, with \(\mu_r = 5000\) and a cross-section of 0.030 m². Find the two reluctances and their ratio.

    Show answer
    \[\mu = (5000)(4\pi\times10^{-7}) = 6.2832\times10^{-3}~\mathrm{H/m}\]
    \[S_{centre} = \frac{1.10}{(6.2832\times10^{-3})(0.030)} = 5835.7~\mathrm{A/Wb}\]
    \[S_{outer} = \frac{1.35}{(6.2832\times10^{-3})(0.030)} = 7162.0~\mathrm{A/Wb}\]
    \[\frac{S_{outer}}{S_{centre}} = 1.2273 = \frac{1.35}{1.10}\]
    Only the path length differs, so the reluctance ratio is simply the length ratio.
  5. P52.5 For P52.4, with 500 turns per phase and a peak flux of 0.020 Wb, find the RMS magnetising current in each limb and the percentage unbalance.

    Show answer
    \[\hat{F}_{centre} = (0.020)(5835.7) = 116.71~\mathrm{At} \quad\Longrightarrow\quad \hat{I} = \frac{116.71}{500} = 0.23343~\mathrm{A}\]
    \[I_{centre} = \frac{0.23343}{\sqrt2} = 0.16506~\mathrm{A}\]
    \[\hat{F}_{outer} = (0.020)(7162.0) = 143.24~\mathrm{At} \quad\Longrightarrow\quad I_{outer} = \frac{143.24/500}{\sqrt2} = 0.20257~\mathrm{A}\]
    \[\frac{0.20257}{0.16506} - 1 = 22.73\,\%\ \text{higher in the outer limbs}\]
  6. P52.6 A Δ-Δ bank of three 300 kVA units loses one transformer. Find the open-delta capacity and the loading of each survivor.

    Show answer
    \[S_{open} = \sqrt3\,(300) = 519.62~\mathrm{kVA}\]
    \[\frac{519.62}{900} = 57.74\,\%\ \text{of the original bank}\]
    \[\frac{519.62}{2(300)} = 86.60\,\%\ \text{of each survivor's rating}\]
  7. P52.7 Prove that the central limb of a three-phase core carries no flux, and state the condition required.

    Show answer
    With balanced excitation the three fluxes are equal in magnitude and 120° apart:
    \[\Phi_a = \Phi_m\angle0^{\circ}, \quad \Phi_b = \Phi_m\angle-120^{\circ}, \quad \Phi_c = \Phi_m\angle+120^{\circ}\]
    Resolving,
    \[\text{real}: \Phi_m\left(1 - 0.5 - 0.5\right) = 0, \qquad \text{imaginary}: \Phi_m\left(0 - 0.86603 + 0.86603\right) = 0\]
    so \(\Phi_a + \Phi_b + \Phi_c = 0\). Equivalently, three equal phasors at 120° laid tip to tail form a closed equilateral triangle.

    The merged limb carries the sum of the three fluxes, which is zero, so it can be removed — saving its iron, weight and cost. This is the magnetic counterpart of balanced three-phase currents needing no neutral conductor.

    The condition is balance. If the excitation is unbalanced the sum is no longer zero, and in a three-limb core the residual flux must return through the oil, the tank and the structural steel, causing stray loss and local heating.

  8. P52.8 Explain why the middle winding of a shell-type three-phase transformer is reversed.

    Show answer
    The flux in the core section joining two adjacent units is the combination of their fluxes, and the winding sense decides whether that combination is a difference or a sum.
    \[\text{same sense}: \left|\Phi_a - \Phi_b\right| = \sqrt3\,\Phi_m = 1.732\,\Phi_m\]
    \[\text{middle reversed}: \left|\Phi_a + \Phi_b\right| = \left|-\Phi_c\right| = \Phi_m\]

    The second line follows immediately from \(\Phi_a + \Phi_b + \Phi_c = 0\): the sum of two of the three balanced fluxes is the negative of the third, whose magnitude is \(\Phi_m\) by definition.

    The benefit is that the joining sections need only \(1/\sqrt3 = 57.7\,\%\) of the cross-section they would otherwise require — a saving of 42.3 % of the iron there, obtained simply by connecting one winding the other way round.

  9. P52.9 Explain the third-harmonic problem of the star-star connection and its remedies.

    Show answer
    The magnetising current of any iron-cored transformer is non-sinusoidal, with a strong third harmonic (Chapter 42).

    The difficulty. Fundamental components in the three phases are 120° apart and sum to zero at the star point. Third harmonics are at three times that displacement, 360° apart — so they are all in phase with one another and their sum at the star point is not zero.

    With no neutral and no delta, that current has nowhere to flow. It is therefore suppressed, forcing the magnetising current to be sinusoidal — which, through the non-linear B-H curve, forces the flux to be non-sinusoidal instead. The distorted flux induces harmonic voltages in every winding, and the phase voltages become distorted and unbalanced.

    Remedies: solidly ground the star neutral, giving the harmonic a path; or provide a tertiary delta winding, in which the harmonic can circulate without leaving the transformer. The tertiary is standard on large Y-Y units and often does useful work supplying station auxiliaries.

  10. P52.10 Why is star normally used on the HV side and delta on the LV side?

    Show answer
    Because the dominant cost is different at the two voltage levels.

    Star on HV. The phase voltage is \(V_L/\sqrt3\), so the winding stands at 57.7 % of the line voltage. That means 42.3 % fewer turns and 42.3 % less insulation. At high voltage, insulation dominates the cost of a winding, so star is the economical choice. A neutral is also available for earthing and for surge protection.

    Delta on LV. The phase current is \(I_L/\sqrt3\), so the conductor need only be 57.7 % of the cross-section — a 42.3 % saving in copper, and at low voltage copper dominates the cost.

    Two further reasons for the delta: it provides the closed path the third-harmonic magnetising current requires, keeping the flux sinusoidal; and it tolerates unbalanced loading, since zero-sequence current can circulate within it.

    Hence Y-Δ for step-down at a substation and Δ-Y for step-up at a generating station. Where a four-wire distribution neutral is needed the LV side must be star instead, and the delta moves to the HV side.

Multiple-Choice Questions
  1. MCQ 1. The central limb of a three-phase core can be removed because it carries:
    (a) twice the flux   (b) zero flux   (c) \(\sqrt3\) times the flux   (d) direct flux

    Show answer
    (b) zero flux, since \(\Phi_a + \Phi_b + \Phi_c = 0\) for balanced excitation.
  2. MCQ 2. In a three-limb core, the magnetising current of the outer phases compared with the centre is:
    (a) smaller   (b) equal   (c) larger   (d) zero

    Show answer
    (c) larger, because their flux paths are longer.
  3. MCQ 3. Reversing the middle winding of a shell type changes the joining flux from:
    (a) \(\Phi_m\) to \(\sqrt3\Phi_m\)   (b) \(\sqrt3\Phi_m\) to \(\Phi_m\)   (c) \(2\Phi_m\) to \(\Phi_m\)   (d) zero to \(\Phi_m\)

    Show answer
    (b) \(\sqrt3\Phi_m\) to \(\Phi_m\), a 42.3 % reduction.
  4. MCQ 4. Three 10 kVA transformers connected Y-Δ give a total capacity of:
    (a) 10 kVA   (b) 17.3 kVA   (c) 30 kVA   (d) 52 kVA

    Show answer
    (c) 30 kVA — the connection cannot change the capacity.
  5. MCQ 5. The line-voltage ratio of a Y-Δ bank is:
    (a) \(K\)   (b) \(\sqrt3K\)   (c) \(K/\sqrt3\)   (d) \(K^{2}\)

    Show answer
    (b) \(\sqrt3K\).
  6. MCQ 6. The phase shift introduced by a Δ-Y connection is:
    (a) 0°   (b) 30°   (c) 60°   (d) 90°

    Show answer
    (b) 30°, which prevents paralleling with Y-Y or Δ-Δ banks.
  7. MCQ 7. Third-harmonic magnetising currents in the three phases are:
    (a) 120° apart   (b) in phase with one another   (c) 60° apart   (d) absent

    Show answer
    (b) in phase with one another, so they cannot cancel at a star point.
  8. MCQ 8. The connection best able to handle unbalanced loading and harmonics is:
    (a) Y-Y without neutral   (b) Δ-Δ   (c) Y-Y with tertiary removed   (d) none

    Show answer
    (b) Δ-Δ — the closed loop gives circulating current a path.
  9. MCQ 9. Star is preferred on the HV side because it reduces:
    (a) current   (b) insulation and turns   (c) core loss   (d) frequency

    Show answer
    (b) insulation and turns, by 42.3 % since \(V_{ph} = V_L/\sqrt3\).
  10. MCQ 10. A single three-phase unit costs about how much less than an equivalent bank?
    (a) 5 %   (b) 15 %   (c) 40 %   (d) 60 %

    Show answer
    (b) 15 %, though the advantage reverses once a spare must be held.
Conceptual Questions
  1. Describe the two ways of obtaining three-phase transformation.

  2. Prove that the central limb of a three-phase core carries no flux, and state the condition.

  3. Explain why the middle winding of a shell-type transformer is reversed.

  4. Give the merits and limitations of a single three-phase unit against a bank.

  5. Derive the line-voltage ratio for each of the four connections.

  6. Explain the 30° phase shift and its consequence for parallel operation.

  7. Explain the two serious problems of the star-star connection and their remedies.

  8. Justify the usual practice of star on the HV side and delta on the LV side.

Looking Ahead

Two threads from this chapter are taken up next. Chapter 53 derives the open-delta or V-V connection properly — why two transformers can carry only \(\sqrt3\) times one unit's rating rather than twice it, why the survivors are limited to 86.6 % of their own rating, and why the connection is used deliberately for small loads as well as after a failure.

The same chapter formalises the vector groups that the 30° shift makes necessary — the Dyn11 and Yd1 notation, in which the letters give the connections and the clock number gives the phase displacement in units of 30°. Chapter 49's fourth paralleling condition then becomes a simple check that two labels match.

Chapter 54 develops the harmonic behaviour that Section 52-6 could only sketch — why the third harmonic is peculiar to three-phase working, what the tertiary winding really does, and how the choice of connection and of earthing determines whether the flux or the current bears the distortion. Chapter 55 then covers the Scott connection, which converts three phases to two, and Chapter 56 closes Part 3 with instrument transformers.