By the end of this chapter you should be able to:
Explain hunting as an oscillation of the load angle about its steady value.
Define the synchronising power coefficient and compute the natural frequency of oscillation.
Describe the construction and the two functions of damper windings.
Define the short-circuit ratio (SCR) and relate it to \(X_d\), stability and machine size.
What Is Hunting?
A synchronous machine carries its load at a definite load angle \(\delta\). When the load changes suddenly, the rotor must move to a new angle, but its inertia makes it overshoot. A restoring torque pulls it back, it overshoots the other way, and the rotor swings about the new equilibrium. This periodic swinging of \(\delta\) — and with it of speed, current and power — is called hunting.
Causes: sudden changes in load (motor) or in prime-mover torque (generator); pulsating loads such as reciprocating compressors; faults and switching on the network; periodic torque from diesel prime movers.
Effects: large current and power swings, mechanical stress, flicker, and — if the swing passes the stability limit — loss of synchronism (pole slipping).
If the forcing frequency is close to the machine's natural frequency, resonance magnifies the swing dramatically.
Synchronising Power and Natural Frequency
For a cylindrical-rotor machine \(P = (E_fV/X_s)\sin\delta\). A small displacement \(\Delta\delta\) produces a restoring power
\(P_s\) is the synchronising power coefficient. It is largest at no load (\(\delta = 0\)) and falls to zero at the stability limit \(\delta = 90^\circ\). Combining it with the swing equation \(\frac{2H}{\omega_s}\frac{d^2\Delta\delta}{dt^2} + P_s\Delta\delta = 0\) gives simple harmonic motion:
\(H\) is the inertia constant (stored kinetic energy at synchronous speed ÷ rated VA, in seconds), \(P_s\) in pu per electrical radian and \(\omega_s = 2\pi f\) electrical rad/s. Typical \(f_n\) is 0.5–2 Hz.
Problem. A 50 Hz generator with \(H = 4\) s operates at \(E_f = 1.5\) pu, \(V = 1.0\) pu, \(X_s = 1.0\) pu and \(\delta = 30^\circ\). Find the synchronising power coefficient and the natural frequency of oscillation.
At heavier load (larger \(\delta\)) \(P_s\) falls, so the oscillation becomes slower and the machine is closer to instability.
Damper Windings
A damper (amortisseur) winding consists of copper or brass bars embedded in slots in the pole faces, short-circuited at both ends by rings or segments — effectively a partial squirrel cage on the rotor.
At synchronous speed the bars carry no current. When the rotor swings, it moves relative to the stator field, EMFs are induced in the bars, and the resulting induction-motor torque opposes the relative motion, damping the oscillation.
A synchronous motor has no starting torque of its own. The damper winding lets it start as an induction motor and run up close to \(N_s\), after which the field is excited and the rotor pulls into step (Chapter 79).
Dampers also reduce the negative-sequence field under unbalanced load and help suppress oscillations caused by harmonic fields.
They lower the subtransient reactance \(X''_d\), which raises the initial short-circuit current — a trade-off for the protection engineer.
Short-Circuit Ratio
The short-circuit ratio is read from the open-circuit characteristic (OCC) and short-circuit characteristic (SCC) of Chapter 75:
| Property | High SCR (≈ 1.0–1.5) | Low SCR (≈ 0.5–0.7) |
|---|---|---|
| Synchronous reactance | Low | High |
| Voltage regulation | Better | Poorer |
| Steady-state stability limit | Higher | Lower |
| Air gap, size and cost | Larger, heavier, dearer | Smaller, cheaper |
| Short-circuit current | Higher | Lower |
| Typical machine | Hydro (salient-pole) | Turbo-alternator |
Problem. An alternator needs 20 A of field current for rated voltage on open circuit and 25 A for rated armature current on short circuit. Find the SCR and the approximate saturated synchronous reactance.
Summary and Common Mistakes
Hunting is oscillation of \(\delta\) after a disturbance; its natural frequency is \(\sqrt{\omega_sP_s/2H}\).
\(P_s = (E_fV/X_s)\cos\delta\) falls as load rises.
Damper windings damp hunting and allow induction starting.
\(\text{SCR} \approx 1/X_{d,\text{sat}}\); high SCR means a larger, stiffer, more stable machine.
Inverting the SCR ratio (short-circuit field current goes in the denominator).
Using mechanical rather than electrical radians in the natural-frequency formula.
Claiming damper bars carry current in steady synchronous operation.
Chapter Review
P81.1 Recompute \(f_n\) for Example 81.1 at no load (\(\delta = 0\)).
Show answer
\(P_s = 1.5\) pu/rad; \(\omega_n = \sqrt{314.16 \times 1.5/8} = 7.67\) rad/s; \(f_n = 1.22\) Hz.P81.2 A machine has \(X_{d,\text{sat}} = 0.8\) pu. Estimate its SCR and say whether it is more likely a hydro or a turbo machine.
Show answer
SCR ≈ 1/0.8 = 1.25 — typical of a salient-pole hydro generator.
MCQ 1. Damper windings are placed:
(a) on the stator yoke (b) in the pole faces (c) in the armature slots (d) on the shaftShow answer
(b)MCQ 2. A machine with a high SCR has:
(a) high \(X_d\) (b) poor regulation (c) high stability limit (d) small air gapShow answer
(c) — low reactance means a high maximum power \(E_fV/X_d\).
Why is hunting more dangerous when a pulsating load has a frequency near \(f_n\)?
Explain how a damper winding produces a damping torque.
Why do turbo-alternators have a lower SCR than hydro generators?
Part 6 begins with the motor found in almost every home: the single-phase induction motor. Chapter 82 describes its construction, and Chapters 83–84 explain why a pulsating field can produce torque at all.