By the end of this chapter you should be able to:
Explain why the per-unit system is used, and calculate base values and per-unit quantities.
Convert per-unit impedances to a new base, and show that per-unit values do not depend on which side they are referred to.
State the conditions for parallel operation of transformers, and calculate circulating current and load sharing.
Demonstrative Video
Why Per-Unit?
A power system contains transformers and machines of very different sizes, ratings and voltage ratios, and their equivalent-circuit parameters in ohms vary over a huge range. Comparing them is much simpler if every parameter is normalised. Percentage values are one form of scaling, but they leave a factor of 100 to carry through the calculations. The per-unit system scales every quantity by a logically chosen base, giving dimensionless values with no extra factors and no dependence on the system of units.
Base Values
Two base quantities are chosen, normally the rated voltage and the rated VA from the nameplate. All the others are derived from them:
Independence of side. Referring an impedance to the other side divides it by \(a^2\), and the base impedance on that side is also smaller by \(a^2\):
When several machines are in one circuit, a common system base is chosen and all impedances are converted to it.
Problem. A 50 kVA, 2400/240 V transformer has \(Z_{eq} = 1.5 + j2.5\ \Omega\) referred to the HV side. Find the per-unit impedance, and check it from the LV side.
From the LV side, \(a = 10\). The impedance is \(0.015 + j0.025\ \Omega\) and \(Z_{base,LV} = 1.152\ \Omega\), which gives the same per-unit value.
Parallel Operation
Parallel operation means connecting two or more transformers to the same primary busbars and to a common secondary busbar and load.

A single large enough unit may not be available.
Demand grows, so capacity is added in steps.
Reliability: if one unit fails or is under maintenance, the load can still be supplied.
Smaller units are easier to transport to site.
The voltage ratios must be the same.
The per-unit impedances on their own ratings should be the same, preferably with the same X/R ratio.
The polarity must be the same.
For three-phase units, the phase sequence and phase displacement (vector group) must be the same.
With turns ratios \(a_1, a_2\) and impedances \(Z_A, Z_B\) referred to the secondary:
Unequal Ratios: Circulating Current
Solving the equations shows that each transformer current has two components: its share of the load, and a current circulating around the loop formed by the two secondaries. The circulating current flows even with no load connected:
It increases the copper loss and may overload one transformer, reducing the kVA the bank can deliver. Even a small difference in voltage ratio produces a large \(I_c\), because \(Z_A + Z_B\) is small.
Problem. Two transformers have open-circuit secondary voltages of 240 V and 245 V, and each has \(Z = 0.02 + j0.08\ \Omega\) referred to the secondary. Find the circulating current on no load.
Equal Ratios: Load Sharing
With \(a_1 = a_2\) there is no circulating current, and the load divides inversely as the impedances:
In terms of complex power, with \(S = VI^*\):
Problem. Transformer A (500 kVA, \(Z = 0.01 + j0.05\) pu) and transformer B (250 kVA, \(Z = 0.015 + j0.04\) pu) share a 750 kVA load at 0.8 p.f. lagging. Find the load on each.
On a 500 kVA base, \(Z_B = 2(0.015 + j0.04) = 0.03 + j0.08\) pu.
B is overloaded by about 12 % while A carries only 94 % of its rating, because B's per-unit impedance (0.043) is lower than A's (0.051).
Summary
Per-unit value = actual value ÷ base value. \(Z_{base} = V_{base}^2/S_{base}\).
Per-unit impedance is the same on both sides of a transformer.
Unequal voltage ratios cause circulating current. Unequal per-unit impedances cause unfair load sharing.
Chapter Review
MCQ 1. Transformers in parallel share load in proportion to their ratings if they have equal
(a) ohmic impedance (b) per-unit impedance on their own ratings (c) kVA (d) copper lossShow answer
(b).MCQ 2. Circulating current between parallel transformers is caused by unequal
(a) kVA ratings (b) voltage ratios (c) X/R ratios (d) loadsShow answer
(b) voltage ratios.MCQ 3. If the base kVA is doubled, a per-unit impedance
(a) halves (b) doubles (c) is unchanged (d) quadruplesShow answer
(b) doubles.
Why is a small difference in voltage ratio serious for parallel transformers?
Why must polarity be checked before paralleling?