Electrical Machines · Induction Motors

Motor Starts: Induction Motor Starting & Testing

Dr. Mithun Mondal BITS Pilani, Hyderabad Campus Electrical Machines

Demonstrative Video

SECTION 01

Methods of starting 3-\(\Phi\) IM

  • The purpose of starter:

    • To reduce the heavy starting current

    • To provide overload and under voltage protection.

  • The method employed in starting a IM depends upon the the size of the motor and the type of the motor.

  • The common methods used to start IMs are:

    1. Direct-on-line starting

    2. Stator resistance starting

    3. Autotransformer starting

    4. Star-delta starting

  • Methods (1) to (4) are applicable to all IMs

  • Method (4) is applicable only to slip ring (wound rotor)

Key Concepts
  • In practice, any one of the four methods is used for starting squirrel cage motors, depending upon the size of the motor

  • But slip ring motors are invariably started by rotor resistance starting

  • Except DOL other three methods of starting squirrel-cage motors employ reduced voltage across motor terminals at starting

  • All methods of starting squirrel-cage control depends on applied voltage across the stator

SECTION 02

Testing of Induction Motors

  • gives the information regarding no-load losses such as core loss, friction loss and windage loss

  • Rotor copper loss at no load is very less that its value is negligible

  • evaluate the resistance and impedance of the magnetizing path

No Load IM
no load IM
No Load Im
Key Concepts
\[P_{constant} = P_i = P_1+P_2\]
\[\begin{aligned} P_{in} & =\sqrt{3}V_{0}I_{0}\cos\phi_{0}\\ I_{\mu} & =I_{o}\sin\phi_{0}\\ I_{\omega} & =I_{0}\cos\phi_{0}\\ R_{c} & =\dfrac{V_{ip}}{I_{\omega}}\\ X_{m} & =\dfrac{V_{ip}}{I_{\mu}} \end{aligned}\]
As motor is running at no-load, the total input power is equal to the constant iron loss, friction and windage losses of the motor
Friction and windage loss can be separated from
  • Friction and windage loss can be separated from \(P_0\)

  • At no load various readings of the No load loss are taken at the different stator applied voltages.

  • The readings are taken from rated to the breakdown value at rated frequency.

The curve is almost parabolic at the normal voltage
  • The curve is almost parabolic at the normal voltage.

  • As the iron losses are almost proportional to the square of the flux density and therefore, the applied voltage.

  • The curve is extended to the left to cut the vertical axis at the point A.

curve P0
Curve P0
  • At the vertical axis \(V = 0\) and hence the intercept OA represents the independent voltage loss.

  • This means the friction and the windage losses are separated from the total no load loss.

Blocked Rotor
blocked rotor
Blocked Rotor
Key Concepts
\[\begin{aligned} P_{sc} & =\sqrt{3}V_{scl}I_{scl}\cos\phi_{sc}\\ R_{e1} & =\dfrac{P_{scp}}{I_{scp}^{2}}\\ Z_{e1} & =\dfrac{V_{scp}}{I_{scp}}\\ X_{e1} & =\sqrt{Z_{e1}^{2}-R_{e1}^{2}} \end{aligned}\]
This test should be performed at the reduced frequency
  • This test should be performed at the reduced frequency.

  • To obtain accurate results, Blocked Rotor Test is performed at a frequency 25 percent or less than the rated frequency.

  • The leakage reactances at the rated frequency are obtained by considering that the reactance is proportional to the frequency.

  • \[R_2 = R_{e1} - R_1\]
    and then some suitable test are done on stator windings to find the value of