By the end of this chapter you should be able to:
Define armature reaction and state its two effects.
Define the magnetic neutral axis and explain why it is the axis of commutation.
Explain the distortion of flux and why it crowds at the trailing pole tip.
Construct the mmf vector diagram and locate the new MNA.
Resolve the armature mmf into demagnetising and cross-magnetising components.
Derive and apply \(AT_d = ZI\theta_m/360\) and \(AT_c = ZI\left(1/2P - \theta_m/360\right)\).
Convert a brush lead from electrical to mechanical degrees.
Size the extra field turns and the compensating winding.
What Armature Reaction Is
Armature reaction is the effect of the magnetic field set up by armature current on the distribution of flux under the main poles.
The effect of the armature magnetic field is twofold:
It demagnetises or weakens the main flux, which leads to a reduced generated voltage.
It cross-magnetises or distorts it, which leads to sparking at the brushes.
Chapter 29 used both consequences repeatedly — the drooping internal characteristic came from the first, and Chapter 23's assumption that the commutating coil sits at zero EMF is invalidated by the second. This chapter supplies the mechanism and the arithmetic.
Main Field Alone

The flux is distributed symmetrically with respect to the polar axis.
The Magnetic Neutral Axis (MNA) is the axis along which no EMF is produced in the armature conductors, because they move parallel to the lines of flux.
The MNA is \(\perp\) to the flux passing through the armature.
The MNA is also called the axis of commutation, because the reversal of current in armature conductors takes place across this axis.
Armature Field Alone

This is the flux set up by \(I_a\) alone, the field coils being unexcited.
The mmfs of the armature conductors combine to send flux downwards through the armature, shown by the vector \(OF_A\).
The direction is worth noting: with the brushes on the geometrical neutral axis, \(OF_A\) lies along the brush axis, which is perpendicular to the main polar axis. The armature mmf therefore acts on the quadrature axis — the q-axis of Chapter 22 — while the field mmf acts on the direct axis.
Both Fields Together
Under actual conditions both mmfs — main and armature — exist simultaneously.

The flux through the armature is no longer uniform and symmetrical but distorted.
The flux is crowded at the trailing pole tips but weakened or thinned out at the leading pole tips.
The pole tip which is first met during rotation by armature conductors is known as the leading pole tip and the other as the trailing pole tip.
At first sight a redistribution should cost nothing: one tip gains what the other loses. It does not work out that way, because the machine is worked past the knee of its magnetisation curve.
The weakened tip is on the straight part of the B-H curve, so it loses flux in full proportion to the mmf removed. The crowded tip is driven further into saturation, so it gains much less than the mmf added would suggest. The net effect is a loss of total flux per pole — which is the demagnetising action of Section 30-1, and it exists even before any brush shift.
Brush Shift and the New MNA
The new position of the MNA is always \(\perp\) to the resultant mmf \(OF\).
With the shift of the MNA by \(\theta\), the brush also shifts, to lie in the new position of the MNA.
Due to the brush shift — the forward lead — a redistribution of \(I_a\) occurs: conductors which were earlier under the influence of an \(N\)-pole come under the influence of an \(S\)-pole, and vice versa.

The armature mmf \(OF_A\) lies in the direction of the new position of the MNA — that is, along the brush axis.
\(OF_A\) is therefore not vertical but inclined by an angle \(\theta\).
\(OF_A\) is resolved into \(OF_d\), parallel to the polar axis, and \(OF_c\), perpendicular to it.
Demagnetising and Cross-Magnetising

The component at right angles to \(OF_M\), which represents the main mmf. It produces distortion in the main field, and is therefore called the cross-magnetising or distorting component of armature reaction.
The component in direct opposition to \(OF_M\). It exerts a demagnetising influence on the main pole flux, and is therefore called the demagnetising or weakening component of armature reaction.
Demagnetising Ampere-Turns per Pole
Let
The conductors lying within the two sectors swept out by the brush shift are the demagnetising ones. Counting them and converting to turns, since two conductors constitute one turn:
If the lead angle is given in electrical degrees, it must be converted into mechanical degrees using
This conversion is the commonest source of error in armature-reaction problems, and the factor can be large: in an eight-pole machine, \(\theta_m = \theta_e/4\).
Cross-Magnetising Ampere-Turns per Pole
The cross-magnetising conductors are all the rest — those lying between \(\angle AOD\) and \(BOC\), outside the demagnetising sectors.
Halving amp-conductors to get amp-turns must halve both terms. It is easy to halve only the first, giving the incorrect \(ZI\left(1/2P - 2\theta_m/360\right)\).
The check is immediate. The demagnetising and cross-magnetising components must together account for the whole armature mmf:
and \(ZI/2P\) is indeed the total armature ampere-turns per pole, since there are \(Z/2P\) turns per pole each carrying \(I\). Any error in either formula breaks this identity at once — with the incorrect form above, the sum falls short.
The total armature ampere-conductors per pole, accounting for both cross-magnetising and demagnetising effects, is therefore \(ZI/P\), or \(ZI/2P\) ampere-turns per pole.
Problem. A 4-pole wave-wound generator has 720 armature conductors and delivers an armature current of 100 A. The brushes are given a forward lead of 6 mechanical degrees. Find \(AT_d\) and \(AT_c\) per pole, and verify the total.
Current per conductor. Wave-wound, so \(A = 2\):
Demagnetising ampere-turns.
Cross-magnetising ampere-turns.
Verification.
Comment. The cross-magnetising component is six and a half times the demagnetising one. This is typical, and it explains the priorities of Chapter 31: distortion is by far the larger effect, so compensating windings — which cancel the cross-magnetising mmf — matter more in large machines than extra field turns.
Note also that a 6° lead is modest. Doubling it to 12° would raise \(AT_d\) to 1200 AT while reducing \(AT_c\) to 3300, the total staying at 4500 — the brush shift merely reapportions the same armature mmf between the two effects.
Neutralising the Demagnetising Effect
For neutralising the demagnetising effect, an extra number of turns may be put on each pole.
The two denominators differ because the extra turns are added to the winding that already exists. In a shunt machine that winding carries the small field current \(I_{sh}\), so many extra turns are needed; in a series machine it carries the full armature current, so very few are.
Problem. The machine of Example 30.1 is a shunt generator whose field current is 2.5 A. How many extra turns per pole are needed to neutralise the demagnetising effect? How many would be needed if it were a series generator?
Shunt generator.
Series generator. The series winding carries the full armature current:
Comment. Forty times as many turns for the shunt machine — and each carries only \(1/40\) of the current, so the copper cross-section is correspondingly smaller and the total copper volume comparable. The ratio is simply \(I_a/I_{sh}\), exactly the ratio that made Chapter 29's series winding 6 turns against a 1200-turn shunt winding.
Problem. A 6-pole lap-wound generator has 600 armature conductors and an armature current of 120 A. The brush lead is 12 electrical degrees. Find \(AT_d\) and \(AT_c\) per pole.
Convert the angle.
Current per conductor. Lap-wound, so \(A = P = 6\):
Ampere-turns.
Check.
Comment. Had the 12° been taken as mechanical, \(AT_d\) would have come out as 400 AT — three times too large. The error scales with the number of pole pairs, so it is worst in exactly the large multi-pole machines where armature reaction matters most. Always check which kind of degree the question means.
Compensating Windings

It is embedded in pole-shoe slots, connected in series with the armature, such that the current in it flows in the opposite direction to that flowing in the armature conductors directly below the pole shoes.
It is used for large DC machines subjected to large fluctuations in load — for example rolling-mill motors and turbo-generators.
Its purpose is to neutralise the cross-magnetising effect of armature reaction.
Absence of a compensating winding results in sudden shifting of flux forward and backward with every change in load.
This shifting of flux causes a statically induced EMF in the armature coils — the transformer EMF of Chapter 12, not a motional one — whose magnitude depends on the rapidity of the change in load and on the amount of the change.
A rolling mill motor may go from no load to several times full load in a fraction of a second, so \(\mathrm{d}\Phi/\mathrm{d}t\) is enormous. The induced voltage can flash over between commutator segments and destroy the machine. Compensating windings are not a refinement in such service; they are essential.
The compensating winding must provide sufficient mmf to counterbalance the armature mmf. Its conductors carry the full armature current \(I_a\), whereas each armature conductor carries only \(I_a/A\), so
where \(Z_a\) is the number of armature conductors to be compensated and \(Z_c\) the number of compensating conductors.
Only the conductors lying directly under the pole shoe can be compensated, since that is where the winding is:
taking a typical pole arc to pole pitch ratio of 0.7. Note that the current \(I\) must appear — a count of turns is not a count of ampere-turns.
Problem. A 6-pole lap-wound machine has 480 armature conductors and an armature current of 240 A. The pole arc to pole pitch ratio is 0.7. Find the compensating ampere-turns per pole and the number of compensating conductors per pole.
Current per armature conductor.
Armature ampere-turns per pole.
Compensating ampere-turns per pole.
Compensating conductors. Each carries the full \(I_a = 240\) A, so the turns needed are
so 10 conductors per pole would be provided.
Cross-check by \(Z_c = Z_a/A\). The armature conductors under one pole shoe number
Comment. The two routes agree exactly, as they must — one works through ampere-turns and the other through conductor counts, and they are the same statement. Ten heavy conductors in the pole face against 480 in the armature: the compensating winding is small in turns because each of its conductors carries six times the current of an armature conductor.
Note that only 70 % of the armature reaction is compensated, because only the conductors under the pole arc can be reached. The interpolar region is dealt with by the interpoles of Chapter 31.
Problem. A generator's field provides 6000 AT per pole, giving 250 V on open circuit. Near this point the magnetisation curve has a slope of 0.025 V per ampere-turn. If armature reaction contributes 600 demagnetising AT per pole, find the generated EMF on load and the percentage loss.
Effective excitation.
Voltage lost.
Generated EMF on load.
Percentage loss.
Comment. Six percent of the voltage, lost to a magnetic effect that no amount of good copper or good iron can prevent. This is the \(\Delta V_{AR}\) that separated the internal from the no-load characteristic in Chapter 29, and it is why that chapter's Example 29.1 gave a drooping internal characteristic even at constant field current and speed.
Note that the calculation uses the local slope of the magnetisation curve. Well into saturation the slope is small, so a given \(AT_d\) costs less voltage; on the straight part it costs more. A heavily saturated machine is less affected by armature reaction — one of the few advantages of working the iron hard.
Summary and Key Formulas
Armature reaction is the effect of the armature current's magnetic field on the distribution of flux under the main poles. It demagnetises — reducing the generated voltage — and cross-magnetises — distorting the field and causing sparking.
With the main field alone, flux is symmetrical about the polar axis and the MNA — the axis of commutation, where no EMF is induced — coincides with the GNA.
The armature mmf \(OF_A\) acts along the brush axis, on the quadrature axis.
With both fields, \(\overrightarrow{OF} = \overrightarrow{OF_M} + \overrightarrow{OF_A}\), the flux is crowded at the trailing pole tip and thinned at the leading tip, and the net flux falls because the crowded tip saturates.
The MNA shifts to lie \(\perp\) to \(OF\), and the brushes must follow it. This tilts \(OF_A\) by \(\theta\) and resolves it into \(OF_d\) and \(OF_c\).
\(AT_d = ZI\theta_m/360\) and \(AT_c = ZI\left(1/2P - \theta_m/360\right)\), with \(I = I_a/A\). Their sum is always \(ZI/2P\).
Electrical degrees must be converted: \(\theta_m = \theta_e/(P/2)\).
Extra field turns \(AT_d/I_{sh}\) (shunt) or \(AT_d/I_a\) (series) neutralise the demagnetising effect, but not the distortion.
Compensating windings in the pole shoes, in series with the armature and carrying current the opposite way, neutralise the cross-magnetising effect. They need \(Z_c = Z_a/A\) conductors, or \(0.7\times ZI/2P\) ampere-turns per pole.
| Quantity | Formula | Notes |
|---|---|---|
| Current per conductor | \(I = I_a/A\) | \(I_a/2\) wave, \(I_a/P\) lap |
| Resultant mmf | \(\overrightarrow{OF} = \overrightarrow{OF_M} + \overrightarrow{OF_A}\) | new MNA \(\perp\) to \(OF\) |
| Demagnetising AT/pole | \(AT_d = ZI\dfrac{\theta_m}{360}\) | needs brush shift |
| Cross-magnetising AT/pole | \(AT_c = ZI\left(\dfrac{1}{2P} - \dfrac{\theta_m}{360}\right)\) | halve both terms |
| Total armature AT/pole | \(AT_d + AT_c = \dfrac{ZI}{2P}\) | the consistency check |
| Angle conversion | \(\theta_m = \dfrac{\theta_e}{P/2}\) | electrical to mechanical |
| Extra turns, shunt | \(AT_d/I_{sh}\) | many turns, small current |
| Extra turns, series | \(AT_d/I_a\) | few turns, large current |
| Compensating conductors | \(Z_c = Z_a/A\) | \(Z_a\) = conductors under the pole |
| Compensating AT/pole | \(0.7\times\dfrac{ZI}{2P}\) | for pole arc/pitch = 0.7 |
| Voltage lost | \(\Delta E = AT_d\times\dfrac{\mathrm{d}E}{\mathrm{d}(AT)}\) | use the local OCC slope |
Common Mistakes
Using \(I_a\) where \(I\) is meant. The formulas need the current in one conductor, which is \(I_a/A\).
Failing to convert electrical to mechanical degrees. The error is a factor of \(P/2\) — three times over in a six-pole machine.
Halving only the first term when converting cross-magnetising amp-conductors to amp-turns. Both terms must be halved.
Skipping the sum check. \(AT_d + AT_c\) must equal \(ZI/2P\); if it does not, one formula is wrong.
Omitting the current from the compensating ampere-turns. \(0.7\times Z/2P\) is a turn count; the ampere-turns need \(\times I\).
Confusing MNA with GNA. They coincide only on no load.
Thinking distortion alone costs no flux. It does, because the crowded tip saturates and cannot gain what the weakened tip loses.
Expecting extra field turns to stop sparking. They restore the flux but leave the cross-magnetising distortion untouched.
Expecting a compensating winding to cover the whole armature. Only the conductors under the pole arc — about 70 % — can be compensated.
Confusing leading and trailing pole tips. The leading tip is met first by the armature conductors, and it is the one that is weakened.
Chapter Review
Always compute \(I = I_a/A\) first, convert the angle if necessary, and finish by checking \(AT_d + AT_c = ZI/2P\) — which confirms the formulas, though not the angle.
P30.1 A 4-pole lap generator has 500 conductors and an armature current of 80 A, with a brush lead of 8 mechanical degrees. Find \(AT_d\) and \(AT_c\).
Show answer
\[I = \frac{80}{4} = 20~\mathrm{A}, \qquad ZI = (500)(20) = 10\,000\]\[AT_d = (10\,000)\frac{8}{360} = 222.2~\mathrm{AT/pole}\]Check: \(222.2 + 1027.8 = 1250 = 10\,000/8\) \(\checkmark\)\[AT_c = (10\,000)\left(\frac{1}{8} - \frac{8}{360}\right) = (10\,000)(0.125 - 0.02222) = 1027.8~\mathrm{AT/pole}\]P30.2 An 8-pole wave generator has 720 conductors and 200 A armature current, brush lead 5 mechanical degrees. Find both components.
Show answer
\[I = \frac{200}{2} = 100~\mathrm{A}, \qquad ZI = 72\,000\]\[AT_d = (72\,000)\frac{5}{360} = 1000~\mathrm{AT/pole}\]Check: \(1000 + 3500 = 4500 = 72\,000/16\) \(\checkmark\)\[AT_c = (72\,000)\left(\frac{1}{16} - \frac{5}{360}\right) = (72\,000)(0.0625 - 0.013889) = 3500~\mathrm{AT/pole}\]P30.3 Repeat P30.2 with the brush lead given as 20 electrical degrees.
Show answer
which is exactly the case of P30.2, so \(AT_d = 1000\) and \(AT_c = 3500\) AT/pole.\[\theta_m = \frac{20}{8/2} = \frac{20}{4} = 5^{\circ}\ \text{mechanical}\]Had the 20° been used directly, \(AT_d\) would have been 4000 AT — four times too large — and \(AT_c\) only 500 AT.
Note that the sum check would not have caught this. The identity \(AT_d + AT_c = ZI/2P\) holds for any value of \(\theta_m\) whatever, so it validates the formulas but not the input angle. What should raise suspicion is the physics: the pole pitch of an 8-pole machine is \(360/8 = 45\) mechanical degrees, so a "lead" of 20° would be nearly half a pole pitch — absurd for a brush shift, which is normally a few degrees at most.
P30.4 For the machine of P30.1, find the extra shunt field turns per pole if \(I_{sh} = 1.8\) A.
Show answer
\[\text{extra turns/pole} = \frac{222.2}{1.8} = 123.5 \quad\Longrightarrow\quad 124~\text{turns}\]P30.5 A 4-pole lap machine has 400 conductors and 160 A armature current. Find the compensating ampere-turns and conductors per pole, taking pole arc/pole pitch = 0.7.
Show answer
\[I = \frac{160}{4} = 40~\mathrm{A}, \qquad \frac{ZI}{2P} = \frac{(400)(40)}{8} = 2000~\mathrm{AT/pole}\]\[AT_{\text{comp}} = (0.7)(2000) = 1400~\mathrm{AT/pole}\]Cross-check: \(Z_a = (400/4)(0.7) = 70\), so \(Z_c = 70/4 = 17.5\) \(\checkmark\)\[\text{turns} = \frac{1400}{160} = 8.75 \quad\Longrightarrow\quad 17.5~\text{conductors/pole}, \ \text{say 18}\]P30.6 A machine loses 20 V to armature reaction. The local OCC slope is 0.02 V/AT. Find \(AT_d\).
Show answer
\[AT_d = \frac{\Delta E}{\mathrm{d}E/\mathrm{d}(AT)} = \frac{20}{0.02} = 1000~\mathrm{AT/pole}\]P30.7 Explain why distorting the flux across a pole face reduces the total flux per pole.
Show answer
Because the machine is worked past the knee of its magnetisation curve. The leading tip loses mmf and, being on the relatively straight part of the curve, loses flux in full proportion. The trailing tip gains the same mmf but is pushed further into saturation, so it gains much less flux than the leading tip lost.The two do not cancel, and the net flux per pole falls. On a perfectly linear magnetic circuit there would be no such loss — distortion would be free, and armature reaction would produce sparking but no voltage droop.
P30.8 Why are compensating windings fitted to rolling-mill motors but not to small general-purpose machines?
Show answer
A rolling-mill motor is subject to large and very rapid load fluctuations — from no load to several times full load in a fraction of a second as the billet enters the rolls.Without compensation, the flux shifts forward and backward with each such change, and the resulting \(\mathrm{d}\Phi/\mathrm{d}t\) induces a statically induced EMF in the armature coils whose magnitude depends on the rapidity and the amount of the change. That voltage can flash over between commutator segments.
A small machine on a steady load has slow, modest flux shifts, so the induced voltage is negligible and the expense of pole-face slots and heavy compensating conductors is not justified.
P30.9 A designer proposes to cure sparking by adding extra field turns. Comment.
Show answer
It will not work. Extra field turns neutralise the demagnetising component, restoring the flux per pole and hence the generated voltage.Sparking is caused by the cross-magnetising component, which distorts the field and shifts the magnetic neutral axis away from the brushes. Extra field turns leave that entirely untouched — and by restoring the flux they may even make the distortion slightly worse.
The correct remedies are a compensating winding for the flux under the pole shoes, and interpoles for the interpolar region — the subject of Chapter 31.
P30.10 Two identical machines run at the same armature current, one with its iron heavily saturated and one only lightly. Which loses more voltage to armature reaction?
Show answer
The lightly saturated machine loses more voltage. The demagnetising ampere-turns are the same in both, since \(AT_d\) depends only on \(Z\), \(I\) and \(\theta_m\) — not on the iron.But the voltage lost is \(AT_d\) multiplied by the local slope of the magnetisation curve. Well into saturation that slope is small, so the same lost ampere-turns cost fewer volts.
Working the iron hard therefore buys some immunity to armature reaction — though at the cost of higher excitation and a poorer response to field control.
MCQ 1. Armature reaction is the effect of:
(a) the field on the armature (b) the armature field on the main flux (c) the brushes on the commutator (d) saturation on the fieldShow answer
(b) the armature field on the main flux and its distribution under the poles.MCQ 2. The magnetic neutral axis is where:
(a) flux is maximum (b) no EMF is induced in the conductors (c) the poles are (d) current is maximumShow answer
(b) no EMF is induced, because the conductors move parallel to the flux lines. It is also the axis of commutation.MCQ 3. Under load, flux is crowded at the:
(a) leading pole tip (b) trailing pole tip (c) pole centre (d) interpolar gapShow answer
(b) trailing pole tip, and thinned at the leading tip.MCQ 4. The demagnetising component of armature reaction arises only when:
(a) the machine is loaded (b) the brushes are shifted (c) the field is weak (d) the speed is highShow answer
(b) the brushes are shifted. Without a lead, the armature mmf lies wholly on the quadrature axis.MCQ 5. The demagnetising ampere-turns per pole are:
(a) \(ZI\theta_m/180\) (b) \(ZI\theta_m/360\) (c) \(2ZI\theta_m/360\) (d) \(ZI/2P\)Show answer
(b) \(ZI\theta_m/360\).MCQ 6. The sum \(AT_d + AT_c\) equals:
(a) \(ZI/P\) (b) \(ZI/2P\) (c) \(ZI\) (d) \(ZI\theta_m/360\)Show answer
(b) \(ZI/2P\) — the total armature ampere-turns per pole. This is the check on both formulas.MCQ 7. A brush lead of 12 electrical degrees on a 6-pole machine is, in mechanical degrees:
(a) 36 (b) 12 (c) 4 (d) 2Show answer
(c) 4, from \(\theta_m = \theta_e/(P/2) = 12/3\).MCQ 8. A compensating winding is connected:
(a) in parallel with the field (b) in series with the armature (c) across the brushes (d) to a separate supplyShow answer
(b) in series with the armature, so its mmf tracks the armature current automatically.MCQ 9. The compensating winding neutralises the:
(a) demagnetising component (b) cross-magnetising component (c) residual flux (d) brush dropShow answer
(b) cross-magnetising component — the distorting effect under the pole shoes.MCQ 10. The number of compensating conductors is:
(a) \(Z_aA\) (b) \(Z_a/A\) (c) \(Z_a\) (d) \(Z_a/2\)Show answer
(b) \(Z_a/A\), because each carries \(A\) times the current of an armature conductor.
Define armature reaction and state its two effects with their consequences.
Define the magnetic neutral axis and explain why it is called the axis of commutation.
Explain, with a vector diagram, how the resultant mmf is formed and where the new MNA lies.
Explain why distortion of the flux also causes a loss of total flux per pole.
Derive the demagnetising ampere-turns per pole.
Derive the cross-magnetising ampere-turns per pole and state the check on the result.
Explain how the demagnetising effect may be neutralised, and why this does not cure sparking.
Describe a compensating winding, its purpose, its connection, and where it is needed.
Armature reaction shifts the magnetic neutral axis, which destroys the assumption of Chapter 23 that a commutating coil sits where its EMF is zero. Chapter 31 takes up the consequences under the heading of commutation: the reactance voltage revisited, the difference between resistance and EMF commutation, and the two remedies that make large DC machines possible.
Interpoles — narrow poles on the quadrature axis, wound in series with the armature — generate an EMF in the commutating coil that exactly cancels the reactance voltage of Chapter 23. Because they are series-connected, their strength tracks the load automatically, which is precisely what a shifting neutral axis demands. Compensating windings, introduced here, deal with the distortion under the pole faces; the two are complementary and large machines carry both.
Chapter 32 then takes up the parallel operation of DC generators, where the characteristics of Chapter 29 decide how two machines share a load, and Chapter 33 turns to losses and efficiency, bringing the iron loss of Chapter 27 together with the copper and brush losses of Chapter 26 into a complete power-flow diagram.