Synchronizing an Alternator: A Hands-On Experiment

Demonstrative Video



SYNCHRONIZATION OF AN ALTERNATOR

OBJECTIVE:

NAME PLATE DETAILS:

NAME PLATE DETAILS OF DC SHUNT MOTOR & ALTERNATOR

 

DC Motor

3-Phase Alternator

 KW Rating

5.2 KW

6.5 KVA/5.2 KW

Voltage

220 V DC

415 V AC   50 Hz

Current

20 A

9 A

Speed

1500 RPM

1500 RPM

Excitation current

0.9 A

5.8 A

Winding type

Shunt

Salient pole

 

Ra : 2.7 ,       Rsh : 179

R - N = 2.6

 

APPARATUS REQUIRED:

S.No.

Name of the Equipment

Range

 Quantity

Type

1.

Voltmeter

300 VDC

1 No

Digital

2.

Voltmeter

500 VAC

1 No

Digital

3.

Ammeter

20 ADC

2 Nos

Digital

4.

Ammeter

20 AAC

1 No

Digital

5.

Rheostat

360Ω/1.6A

1 No

 Coil

6.

Tachometer

2000 Rpm

1 No

Digital

 

THEORY: SYNCHRONIZATION

Following conditions should be met:

  1. Generated voltage must be approximately equal to the grid voltage.
  2. Frequency of the generated voltage must be equal to that of the grid.
  3. Phase sequence of the generated voltage must be the same as that of the grid.
  4. Phase of the generated voltages relative to some reference must be very close to the phase of grid lines.

Fulfillment of these conditions is checked by the dark lamp method and via synchroscope.

SYNCHRONIZATION BY DARK LAMP METHOD:

V-curves and inverted V-curves of a synchronous motor:

Equipment and Components Required:

CIRCUIT DIAGRAM:

image

EM LAB SET-UP:

image

CONNECTION FOR SYNCHRONIZATION:

image

PROCEDURE FOR V CURVES:

  1. Connect the circuit.
  2. Motor field rheostat must be kept in minimum resistance position. Alternator field switch should be kept at off position; field regulator of alternator should be kept in minimum output position.
  3. Switch ON the MCB, start the Motor-Alternator set using the 3-point starter.
  4. Adjust the field rheostat of the motor in order to bring the Motor-Alternator set to rated speed i.e., 1500 rpm.
  5. Switch on the field supply to the alternator and vary the field regulator (This is a variac connected with a rectifier; so, VARIAC output voltage is to be varied) in steps; note the field current (If) and generated output voltage (VG) until the VG reaches rated value i.e., 415 V.
  6. Synchronize the alternator to the mains. For this purpose, make sure that the magnitudes, the phase, phase sequence, and frequency of the alternator terminal voltage and the infinite bus voltage are matched.
  7. Synchronize synchronous machine with the three-phase grid using the 3-lamp method.
  8. Connect lamps in between the 3-phase terminals of the alternator and the AC mains. If the lamps are glowing, this indicates that there is a voltage difference between the AC mains voltage and the alternator terminal voltage. By adjusting the excitation, the voltage magnitudes can be matched (let’s say it is (\(V/\sqrt{2}\)).
  9. If the speed of the DC motor is adjusted, then the frequency of the generated voltage of the alternator can be adjusted. If w1 is the frequency of the generated voltage and ws is the frequency of the AC mains voltage, as long as the difference between the two frequencies (ws and w1) is very low (which can be achieved by adjusting the speed of the DC motor), the lamps will have an oscillatory illumination; that is, they will go from a huge brightness to darkness and vice versa. Adjust the speed of the DC motor such that this oscillation in the illumination becomes very slow; this will be visible in the synchroscope in the form of a red colored LED light moving in the anticlockwise direction slowly. When both the voltages are matching exactly, then the lamps will be dark and the LED will be glowing green and will come to the 12 O’ clock position in the clock.
  10. Dark Lamp method: when all the lamps are completely dark, at which time all the voltages of the bus are exactly in phase with the corresponding voltages of the generator. At this moment the synchronizing switch is closed and the generator is synchronized with the mains.
  11. Disconnect the DC machine’s armature from the DC mains. Now the synchronous machine is working as a synchronous motor and the DC machine functions as a generator. At no-load (without taking any output from the coupled DC machine) vary the field current of the synchronous machine with the help of sliding rheostat and correspondingly record the armature current. If we adjust the field current of the alternator at this juncture, we would see that its armature current follows a ‘V’ shape. i.e, when \(I_f\) value is 0.8A, \(I_a\) may be 4 A; as we increase \(I_f\) from 0.8 towards 1.2 A, the \(I_a\) value may go down to 2.5 A or so and when \(I_f\) varies further to 1.5 A or 2 A, again \(I_a\) will go up and reach 3.5 or 4 A; thus \(I_a\) vs. \(I_f\) variation follows a ‘V’ shape.

PROCEDURE FOR INVERTED V CURVES:

  1. Measure the power factor using a power factor meter or estimate the power factor using the 2-wattmeter method.
  2. Vary the field excitation and measure its values.
  3. Draw the curve between \(I_f\) and \(\cos\phi\) to obtain the Inverted-V curve.

OBSERVATION TABLE:

Table: Reading with constant Power (Constant Power = 0 kW)

S. No.

If (A)

Ia (A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QUESTIONS:

  1. State the conditions for synchronization of two alternators.
  2. State the effect of wrong synchronization.
  3. State why a pair of lamps are required in the lamp method of synchronization?
  4. Explain the necessity of synchronization of alternators.
  5. State the advantages of using a number of small generating units instead of a single large unit for supplying power.
  6. Why is the frequency of the incoming alternator kept slightly higher than the bus-bar frequency?
  7. What is the difference between a synchronous motor and a synchronous condenser?
  8. For the given test setup, how can you make the synchronous machine become a generator feeding power to the bus?
  9. If the two 400V machines are to be synchronized by either the dark lamp or bright lamp method, what will be the voltage rating of the bulb?
  10. What is a synchroscope?
  11. Will the UPF always occur at a particular value of field current for a synchronous motor irrespective of the power it is delivering?
  12. Why is the armature current minimum at the UPF condition?