Electric Power Systems · System Analysis

Unsymmetrical Faults

Solved Problems — Electric Power Systems

Dr. Mithun Mondal engineeringdevotion.com
Demonstrative Video

Unsymmetrical Faults Solved Problems

SECTION 01

Revision of important Concepts

image
SECTION 02

Problem-1

A 25 MVA, 13.2 kV alternator with solidly grounded neutral has a sub-transient reactance of 0.25 pu. The negative and zero sequence reactance are 0.35 and 0.1 pu, respectively. A single line to ground fault occurs at the terminals of an unloaded alternator. Neglecting resistance, determine

SECTION 03

Solution-1

\[\begin{aligned} I_{a1}& = \dfrac{E_a}{Z_1+Z_2+Z_0}\\ &= \dfrac{1}{j0.7} = -j1.428 \end{aligned}\]
  • \[I_{a1} = I_{a2} = I_{a0} = -j1.428\]
    For a L-G fault:
  • \[\begin{aligned} I_a & = I_{a1} + I_{a2} + I_{a0} \\ & = 3I_{a1} = -j4.285 \end{aligned}\]
    The p.u. fault current
  • Let base be 25 MVA and 13.2 kV

  • \(I_b=\dfrac{25 \times 1000}{\sqrt{3} \times 13.2} = 1093~A\)

  • The actual fault current = \(1093 \times 4.285=4685~A\)

  • \[\begin{aligned} V_{a1} & = E_a - I_{a1}\cdot Z_1\\ & = 1-(-j1.428)(j0.25)\\ & = 0.643\\ V_{a2} & = -I_{a2}Z_2 = -(-j1.128)(j0.35)\\ & = -0.4998\\ V_{a0} & = -I_{a0}Z_0\\ &= - (-j1.428)(j0.1)=0.1428 \end{aligned}\]
    To find out the voltages, first compute sequence components of voltages
  • As a numeric check \(V_a = V_{a1}+V_{a2} + V_{a0} =0\)

  • \(V_{b}=V_{b1}+V_{b2}+V_{b0}\) and \(V_{c}=V_{c1}+V_{c2}+V_{c0}\)

\[\begin{aligned} V_{b1}=& \lambda^{2} V_{a_{1}}\\ &=(-0.5-j 0.866)(0.643) \\ &=-0.3215-j 0.5568 \\ V_{b2}=& \lambda V_{a_{2}}\\ &=(-0.5+j 0.866)(-0.50) \\ &=(0.25-j 0.433) \\ V_{b0} &=V_{a_{0}}=V_{c_{0}}=-0.1428 \end{aligned}\]
\[\begin{aligned} V_{b} &=-0.3215-j 0.5568+0.25-j 0.433-0.1428 \\ &=-0.2143-j 0.9898 \\ V_{c} &=-0.3215+j 0.5568+0.25+j 0.433-0.1428 \\ &=-0.2143+j 0.9898 \end{aligned}\]
  • \[\begin{aligned} V_{a b} &=V_{a}-V_{b} . \text { since } V_{a}=0 \\ V_{a b} &=-V_{b}=0.2143+j 0.9898 \\ V_{a c} &=-V_{c}=0.2143-j 0.9898 \\ V_{b c} &=V_{b}-V_{c}=-j 2 \times 0.9898 \\ &=-j 1.9796 \end{aligned}\]
    Now, Line-to-Line voltage are:
  • \[\begin{aligned} V_{a b} &=0.2143+j 0.9898 \\ |V_{a b}|&=1.0127 \mathrm{p} \cdot \mathrm{u} \end{aligned}\]
    Now
  • \[\begin{array}{l} V_{a b}=1.0127 \times \frac{13.2}{\sqrt{3}}=7.717 \mathrm{kV} \\ V_{a c}=7.717 \mathrm{kV} \\ V_{b c}=1.9796 \times \frac{13.2}{\sqrt{3}}=15.08 \mathrm{kV} \end{array}\]
    The Line-to-Line voltage will be
SECTION 04

Problem-2

Determine the fault current and the line-to-line voltage at the fault when a line-to-line fault occurs at the terminals of the alternator described in the Previous question.

SECTION 05

Solution-2

\[\begin{aligned} I_{a_{1}} &=\frac{E_{a}}{Z_{1}+Z_{2}}=\frac{1+j 0.0}{j 0.25+j 0.35} \\ &=\frac{1+j 0.0}{j 0.6}=-j 1.667 \end{aligned}\]
  • we know \(I_b=1093~A\)

  • Fault current \(=1093 \times 2.8872=3155.71\) amperes

  • \[\begin{aligned} V_{a_{1}} &=E_{a}-I_{a_{1}} Z_{1}=1+j 0.0-(-j 1.667)(j 0.25) \\ &=1-0.4167=0.5833 \\ V_{a_{2}} &=-I_{a_{2}} Z_{2}=(-j 1.667)(j 0.35)=0.5834 \\ V_{a_{1}} &=V_{a_{2}}=0.5833 \mathrm{p} \cdot \mathrm{u} \\ V_{a} &=V_{a_{1}}+V_{a_{2}}+V_{a_{0}}=V_{a_{1}}+V_{a_{2}}=2 \times 0.5833=1.1666 \mathrm{p} . \mathrm{u} . \\ V_{b} &=\lambda^{2} V_{a_{1}}+\lambda V_{a_{2}} \\ &=(-0.5-j 0.866)(0.5833)+(-0.5+j 0.866)(0.5833) \\ &=-0.5833 \\ V_{b} &=V_{c}=-0.5833 \end{aligned}\]
    To find out L-L voltage, find sequence voltages:
SECTION 06

SECTION 07

Problem-3

Determine the fault current and the line-to-line voltages at the fault when a double line-to-ground fault occurs at the terminals of the alternator described in the previous question

SECTION 08

Solution-3

\[\begin{aligned} V_{a_{1}} &=1+j 0.0-(-j 3.0506)(j 0.25) \\ &=1-0.7626=0.2374 \\ V_{a_{2}} &=V_{a_{0}}=0.2374 \\ I_{a_{2}} &=-\frac{V_{a_{2}}}{Z_{2}}=-\frac{0.2374}{j 0.35}=j \frac{0.2374}{0.35}=j 0.678 \\ I_{a_{0}} &=-\frac{V_{a_{0}}}{Z_{0}}=-\frac{0.2374}{j 0.1}=j 2.374\\ I_{a_{2}}+I_{a_{0}}&=j 0.678+j 2.374=j 3.05=-I_{a_{1}} \end{aligned}\]
  • Fault current \(=I_{b}+I_{c}=3 I_{a_{0}}=3 \times j 2.374=j 7.122 \mathrm{p} . \mathrm{u} .\)

  • \[1093 \times 7.122=7784.3 \text { amperes }\]
    Since base current is 1093 amperes, the fault current will be
  • \[\begin{array}{l} V_{a}=V_{a_{1}}+V_{a_{2}}+V_{a_{0}}=3 V_{a_{1}}=3 \times 0.2374=0.7122 \\ V_{b}=V_{c}=0 \end{array}\]
    Now,
\[\begin{aligned} V_{a b} &=V_{a}=0.7122 \times \frac{13.2}{\sqrt{3}}=5.42 \mathrm{kV} \\ V_{a c} &=V_{a}=0.7122 \times \frac{13.2}{\sqrt{3}}=5.42 \mathrm{kV} \\ V_{b c} &=0.0 \mathrm{kV} \end{aligned}\]
The line-to-line fault voltage,