Solved Problems · Set 23

Unsymmetrical Faults

Part 5 · Faults — three networks, two boundary conditions per fault, and one series or parallel combination. Chapter 24 of the textbook.

Prof. Mithun Mondal 20 solved · 12 practice · 3 challenge GATE · ESE · University

Set 23 — Unsymmetrical Faults

Twenty worked problems that finish the fault analysis begun in Set 18. Every unsymmetrical fault imposes exactly two independent conditions on the six terminals of the three sequence networks, and every pair of conditions corresponds to one interconnection — series, parallel opposition, or three-way parallel. Once connected, the circuit has one loop and the answer is a division. The four standard faults are computed here at all five buses of the system built in Sets 18 and 22, and the results show the earth fault exceeding the three-phase fault at two of them.

Textbook Chapter 24 · 20 solved · 12 practice · 3 challenge · 12 MCQs

i Method Recap
  • The method, in four steps. Write the fault's boundary conditions in phase quantities; transform them to sequence quantities; deduce the interconnection of the three networks; solve the resulting single-loop circuit.

  • Single line-to-earth. \(I_b = I_c = 0\) and \(V_a = I_aZ_f\) give \(I_0 = I_1 = I_2\) — the three networks in series, with \(3Z_f\) added. \(I_f = \dfrac{3E}{Z_0+Z_1+Z_2+3Z_f}\).

  • Line-to-line. \(I_a = 0\), \(I_b = -I_c\), \(V_b - V_c = I_bZ_f\) give \(I_0 = 0\) and \(I_1 = -I_2\) — positive and negative in parallel opposition, zero not connected. \(I_f = \dfrac{\sqrt3\,E}{Z_1+Z_2+Z_f}\).

  • Double line-to-earth. \(I_a = 0\) and \(V_b = V_c = 0\) give \(V_0 = V_1 = V_2\) — the negative and zero networks in parallel, that combination in series with the positive.

  • Three-phase. Only the positive-sequence network is excited, so \(I_f = E/(Z_1+Z_f)\) — the calculation of Set 18, now seen as the degenerate case.

  • Which is worst depends on \(Z_0\) alone. With \(Z_1 = Z_2\), the earth fault exceeds the three-phase one exactly when \(Z_0 < Z_1\), and the double line-to-earth ground current can exceed both.

  • Fault impedance enters differently in each. \(3Z_f\) for a line-to-earth fault, \(Z_f\) for a line-to-line one — the factor of three being the same one that puts \(3Z_n\) in the zero-sequence network.

VideoWalkthrough
Problem 1FoundationThe Four Types

List the four standard fault types, give the relative frequency of each, and set out the general method by which all four are solved.

Solution

The four types, with their observed frequency on transmission systems:

\[ \begin{array}{lll} \text{Single line-to-earth (LG)} & 70\text{--}85\% & \text{one phase to earth} \\ \text{Line-to-line (LL)} & 5\text{--}15\% & \text{two phases, no earth} \\ \text{Double line-to-earth (LLG)} & 5\text{--}10\% & \text{two phases and earth} \\ \text{Three-phase} & 2\text{--}5\% & \text{all three, symmetrical} \end{array} \]

The commonest by a wide margin is the one that requires all three sequence networks; the rarest is the one Set 18 could already handle.

Why the LG fault dominates. The mechanisms that cause faults act on one phase at a time:

\[ \begin{array}{ll} \text{Lightning to one phase} & \text{flashover across one insulator string} \\ \text{Pollution flashover} & \text{one string is always dirtiest} \\ \text{Vegetation, cranes, birds} & \text{reach one conductor first} \\ \text{Insulation ageing} & \text{one weakest point} \end{array} \]

A three-phase fault requires something to bridge all three conductors at once — a conductor clash in high wind, a collapsed tower, or an earthing device left applied. Rare, and usually the result of an error rather than a natural cause.

The method, in four steps, identical for every type:

\[ \begin{array}{ll} 1 & \text{Write the boundary conditions at the fault, in phase quantities} \\ 2 & \text{Transform them into sequence quantities} \\ 3 & \text{Read off how the three networks must be connected} \\ 4 & \text{Solve the single-loop circuit} \end{array} \]

Only step 3 requires thought, and it need be done once per fault type — after which the interconnection is memorised and the calculation is a division.

What each fault needs. Three numbers from Set 22's matrices, and no more:

\[ \begin{array}{ll} \text{Three-phase} & Z_1\ \text{alone} \\ \text{Line-to-line} & Z_1,\ Z_2 \\ \text{Line-to-earth} & Z_0,\ Z_1,\ Z_2 \\ \text{Double line-to-earth} & Z_0,\ Z_1,\ Z_2 \end{array} \]

All three are diagonal elements at the faulted bus, computed in advance for every bus. The size of the network behind them is irrelevant to this stage.

The two conditions per fault. Six unknowns exist at the fault — three sequence currents and three sequence voltages — and the three networks supply three equations:

\[ V_1 = E - Z_1I_1 \qquad V_2 = -Z_2I_2 \qquad V_0 = -Z_0I_0 \]

So exactly three further conditions are needed, and the fault supplies them. Two are independent constraints and the third is the fault impedance relation.

And a convention worth fixing now. The faulted phase is always taken as \(a\) for a single line-to-earth fault, and the faulted pair as \(b\) and \(c\) for the others. This is a choice of labelling, not a restriction — relabelling the phases rotates the answers but changes no magnitude.

The fault that is easiest to compute is the rarest, and the one that occurs four times out of five needs the whole apparatus of Part 5. Set 18's three-phase study answered the switchgear question, because that fault is usually the most severe. Everything about protection — which relay operates, how long it takes, what the healthy phases do — is decided by the single line-to-earth fault, and that is why symmetrical components exists.
AnswerLG 70–85%, LL 5–15%, LLG 5–10%, three-phase 2–5%; all four solved by boundary conditions \(\to\) sequence conditions \(\to\) interconnection \(\to\) one loop
Problem 2Exam levelLG Boundary Conditions

Write the boundary conditions for a single line-to-earth fault on phase \(a\) through an impedance \(Z_f\), and transform them into sequence quantities.

Solution

In phase quantities, at the fault point:

\[ I_b = 0 \qquad I_c = 0 \qquad V_a = I_aZ_f \]

Phases \(b\) and \(c\) are open at the fault — they carry load current, but no fault current, and the superposition network sees zero. Phase \(a\) is connected to earth through \(Z_f\).

The first two conditions, transformed. With \(I_b = I_c = 0\):

\[ I_0 = \tfrac{1}{3}(I_a+0+0) = \tfrac{I_a}{3} \]
\[ I_1 = \tfrac{1}{3}(I_a+0+0) = \tfrac{I_a}{3} \qquad I_2 = \tfrac{1}{3}(I_a+0+0) = \tfrac{I_a}{3} \]
\[ \Rightarrow\quad \boxed{I_0 = I_1 = I_2 = \frac{I_a}{3}} \]

Exactly the single-phase-load result of Set 21, Problem 13 — because a single line-to-earth fault is a single-phase load, of very low impedance.

The third condition, transformed. With \(V_a = V_0+V_1+V_2\) and \(I_a = 3I_1\):

\[ V_0 + V_1 + V_2 = 3I_1Z_f \]

The three sequence conditions, assembled:

\[ \begin{array}{ll} I_0 = I_1 & \text{the same current in all three} \\ I_1 = I_2 & \\ V_0+V_1+V_2 = 3I_1Z_f & \text{the voltages sum to the drop in } 3Z_f \end{array} \]

Two current conditions and one voltage condition — which is exactly what a series connection of three circuits looks like: one current through all of them, and their voltages adding.

The counting check. Three network equations plus three fault conditions gives six equations in six unknowns. The system is determined, and no further physical information is needed.

A note on what "at the fault" means. These are conditions on the superposition network — the change caused by the fault. The actual currents in phases \(b\) and \(c\) are their prefault load currents, which are typically 1–2% of the fault current and are neglected throughout. Where they are not negligible — a heavily loaded feeder with a low fault level — the prefault load flow must be superposed, and modern software does exactly that.

Two zeros in the phase currents produce three equalities in the sequence currents, and that multiplication of information is what symmetrical components buys. The condition \(I_b = I_c = 0\) is geometrically special — it forces the three sequence components to coincide — and it is the reason the commonest fault has the simplest sequence description.
Answer\(I_b = I_c = 0\) gives \(I_0 = I_1 = I_2 = I_a/3\); \(V_a = I_aZ_f\) gives \(V_0+V_1+V_2 = 3I_1Z_f\) — the signature of a series connection
Problem 3Exam levelThe LG Connection

Deduce the sequence network interconnection for a single line-to-earth fault and derive the fault current formula.

Solution

Reading the conditions as a circuit. The sequence conditions of Problem 2 are

\[ I_0 = I_1 = I_2 \qquad V_0+V_1+V_2 = 3I_1Z_f \]

One current common to three circuits, and their voltages adding to a fixed drop. That is a series connection of the three networks, with \(3Z_f\) completing the loop.

The circuit. Starting at the reference and going round:

\[ E \;\longrightarrow\; Z_1 \;\longrightarrow\; Z_2 \;\longrightarrow\; Z_0 \;\longrightarrow\; 3Z_f \;\longrightarrow\; \text{back} \]

A single loop containing the one source and all three impedances. The order does not matter; series elements commute.

Solving it. Substituting the network relations into the voltage condition:

\[ \left(E - Z_1I_1\right) + \left(-Z_2I_1\right) + \left(-Z_0I_1\right) = 3I_1Z_f \]
\[ E = I_1\left(Z_0+Z_1+Z_2+3Z_f\right) \]
\[ \boxed{\;I_1 = \frac{E}{Z_0+Z_1+Z_2+3Z_f}\;} \]

And the fault current itself:

\[ I_f = I_a = 3I_1 = \frac{3E}{Z_0+Z_1+Z_2+3Z_f} \]

The factor 3 appearing twice, and for the same reason both times: the physical phase current is three times the sequence current, and the physical fault impedance carries three times the sequence current so appears tripled.

The sanity checks. Three limits, all correct:

\[ \begin{array}{lll} Z_0 \to \infty & I_f \to 0 & \text{no earth path, no earth fault} \\ Z_0 = Z_1 = Z_2 & I_f = E/Z_1 & \text{equal to the three-phase current} \\ Z_0 \to 0 & I_f \to 1.5E/Z_1 & \text{the maximum possible} \end{array} \]

The second is worth remembering: when the three sequence impedances are equal, the two fault types give identical currents. Which is worse then depends on nothing at all.

Why the three networks are in series and not parallel is worth stating plainly. The fault forces one current — the whole of \(I_a\) — to pass through all three sequence circuits in turn, because it is composed equally of the three components. The impedances therefore add, and the fault current is smaller than the three-phase one unless \(Z_0\) is small enough to compensate.

Two lines of algebra convert a three-phase fault problem into a single-loop DC-like circuit, and that is the whole payoff of Sets 21 and 22. The network reduction was the work; the fault calculation is a division. And the formula's structure — one source, three impedances in series, a tripled fault impedance — is memorable enough that it is rarely re-derived.
AnswerThe three networks in series with \(3Z_f\); \(I_f = 3E/(Z_0+Z_1+Z_2+3Z_f)\), bounded by \(1.5E/Z_1\)
Problem 4Exam levelLG at Bus 3

Compute the single line-to-earth fault current at bus 3 of the five-bus system, and give the three sequence currents.

Solution

The three impedances, from Set 22:

\[ Z_1 = j0.17377 \qquad Z_2 = j0.17377 \qquad Z_0 = j0.23047 \]

All in per unit on 100 MVA. A solid fault, so \(Z_f = 0\).

The sum:

\[ Z_0+Z_1+Z_2 = j(0.23047+0.17377+0.17377) = j0.57801 \]

The sequence currents:

\[ I_1 = I_2 = I_0 = \frac{1.0\angle0^\circ}{j0.57801} = 1.7300\angle-90^\circ\ \text{pu} \]

The fault current:

\[ I_f = 3I_1 = 5.1901\angle-90^\circ\ \text{pu} \]
\[ = 5.1901\times\frac{100\times10^{6}}{\sqrt3\,(220\times10^{3})} = 5.1901\times262.4 = 1362\ \text{A} \]

Or 519 MVA on the 100 MVA base. Lagging by 90°, the network being purely reactive.

Comparison with the three-phase fault at the same bus, computed in Set 18:

\[ \begin{array}{lcc} \text{Fault} & \text{pu} & \text{ratio} \\ \hline \text{Three-phase} & 5.7546 & 1.000 \\ \text{Line-to-earth} & 5.1901 & 0.902 \end{array} \]

The earth fault is 10% less severe here, because \(Z_0 > Z_1\) at bus 3 — exactly as Set 22 predicted from the ratio 1.326.

The check on the formula. Using the ratio expression directly:

\[ \frac{I_{LG}}{I_{3\phi}} = \frac{3Z_1}{2Z_1+Z_0} = \frac{3(0.17377)}{2(0.17377)+0.23047} = \frac{0.52131}{0.57801} = 0.9019 \]

Matching. The ratio needs only the two impedances and never the source.

And the two zero-sequence facts that follow immediately. The current in the earth is

\[ I_{\text{earth}} = 3I_0 = 5.1901\ \text{pu} = I_f \]

All of the fault current returns through earth — necessarily, since phases \(b\) and \(c\) carry none. And that 5.19 pu divides between the two transformer neutrals as Set 22's Problem 18 computed: 1.86 through bus 1's and 3.33 through bus 2's.

The whole calculation is one addition and one division, and everything difficult was done in Sets 18 and 22. That is the correct division of labour: build the three networks once, with all the care that the transformer connections and the earthing arrangements demand, and then answer any fault question at any bus in two lines of arithmetic.
Answer\(I_0 = I_1 = I_2 = 1.7300\angle-90^\circ\) pu; \(I_f = 5.1901\) pu = 1362 A, which is 90% of the three-phase value
Problem 5AnalysisLG Voltages

Find the three phase voltages at the fault during the line-to-earth fault of Problem 4, and comment on the healthy phases.

Solution

The sequence voltages follow from the network relations with \(I_1 = 1.7300\angle-90^\circ\):

\[ V_1 = E - Z_1I_1 = 1.0 - (j0.17377)(-j1.7300) = 1.0 - 0.30063 = 0.69937 \]
\[ V_2 = -Z_2I_2 = -0.30063 \qquad V_0 = -Z_0I_0 = -0.39873 \]

All real, since the impedances are purely reactive and the currents purely lagging. The positive-sequence voltage has been depressed to 0.70 pu, and the other two are negative.

The faulted phase:

\[ V_a = V_0+V_1+V_2 = -0.39873+0.69937-0.30063 = 0.00001 \approx 0 \]

Zero, as it must be for a solid fault. This is the arithmetic check on the whole calculation, and it costs one addition.

The healthy phases:

\[ V_b = V_0 + a^{2}V_1 + aV_2 = 1.0525\angle-124.63^\circ \]
\[ V_c = V_0 + aV_1 + a^{2}V_2 = 1.0525\angle124.63^\circ \]

Both at 1.0525 pu — a rise of 5.25% above nominal, and symmetrically placed about the negative real axis.

The earthing coefficient. The ratio of the highest healthy-phase voltage to the nominal is the standard measure:

\[ \text{Earth-fault factor} = \frac{1.0525}{1.0} = 1.053 \]

Well inside the 1.4 that defines an effectively-earthed system — consistent with \(X_0/X_1 = 1.33\) at this bus, which satisfies the criterion of Set 22.

The angle displacement is the other symptom. The healthy phases are at \(\pm124.63^\circ\) instead of \(\pm120^\circ\) — a separation of 110.7° rather than 120°. The phasor triangle has collapsed towards the faulted phase, and a relay measuring phase angles sees it.

The general result for the healthy-phase rise, worth tabulating:

\[ \begin{array}{lcc} X_0/X_1 & \text{Healthy-phase rise} & \text{Category} \\ \hline 0 & 0.87 & \text{perfectly earthed} \\ 1 & 1.00 & \\ 3 & 1.25 & \text{limit of effective earthing} \\ 10 & 1.52 & \\ \infty & 1.73 & \text{isolated neutral} \end{array} \]

And 1.33 here gives 1.053. Note that a perfect earth gives a rise below nominal, at 0.87 — the healthy phases are pulled down as well as displaced. Most of the rise occurs between ratios of 3 and infinity.

The healthy-phase voltage rise is the reason earthing arrangements matter more than fault currents at transmission voltages. An effectively-earthed system holds the rise below 1.4 and permits 80%-rated surge arresters; a system that does not needs 100%-rated ones, and at 400 kV that difference propagates through every insulation level in the substation. The earth-fault current is a protection question; the healthy-phase rise is an insulation-cost question, and insulation costs more.
Answer\(V_a = 0\), \(V_b = V_c = 1.0525\) pu at \(\mp124.63^\circ\) — a rise of 5.25% and an earth-fault factor of 1.053
Problem 6Exam levelLL Boundary Conditions

Write the boundary conditions for a line-to-line fault between phases \(b\) and \(c\) through \(Z_f\), and transform them.

Solution

In phase quantities:

\[ I_a = 0 \qquad I_b = -I_c \qquad V_b - V_c = I_bZ_f \]

Phase \(a\) is unaffected; whatever flows into the fault in phase \(b\) returns in phase \(c\); the two are joined through \(Z_f\). No earth is involved.

The zero-sequence condition follows at once from the first two:

\[ I_0 = \tfrac{1}{3}\left(I_a+I_b+I_c\right) = \tfrac{1}{3}\left(0 + I_b - I_b\right) = 0 \]

No zero-sequence current. The zero-sequence network takes no part in this fault, which is the single most important fact about it — a line-to-line fault is unaffected by the earthing arrangement.

The positive and negative components, using \(I_c = -I_b\):

\[ I_1 = \tfrac{1}{3}\left(0 + aI_b - a^{2}I_b\right) = \tfrac{I_b}{3}(a-a^{2}) = \frac{jI_b}{\sqrt3} \]
\[ I_2 = \tfrac{1}{3}\left(0 + a^{2}I_b - aI_b\right) = \tfrac{I_b}{3}(a^{2}-a) = -\frac{jI_b}{\sqrt3} \]
\[ \Rightarrow\quad \boxed{I_1 = -I_2} \]

Using \(a - a^{2} = j\sqrt3\) from Set 21. The relation \(I_1 = -I_2\) is the second of the two conditions.

The voltage condition. With \(V_0\) arbitrary (it will turn out to be zero) and using \(V_b - V_c\):

\[ V_b - V_c = (a^{2}-a)V_1 + (a-a^{2})V_2 = (a^{2}-a)(V_1-V_2) \]
\[ \text{and} \quad I_b = (a^{2}-a)I_1 \]
\[ \Rightarrow\quad (a^{2}-a)(V_1-V_2) = (a^{2}-a)I_1Z_f \quad\Rightarrow\quad \boxed{V_1 - V_2 = I_1Z_f} \]

The \((a^{2}-a)\) cancels — which is why the line-to-line formula contains \(Z_f\) and not \(3Z_f\).

The three sequence conditions:

\[ \begin{array}{ll} I_0 = 0 & \text{zero-sequence network open} \\ I_1 = -I_2 & \text{equal and opposite} \\ V_1 - V_2 = I_1Z_f & \text{voltages differ by the drop} \end{array} \]

Equal and opposite currents with a common voltage difference is a parallel connection — with one of the two circuits reversed, so that the current entering one leaves the other.

And \(V_0 = 0\) follows, not as a condition but as a consequence: with \(I_0 = 0\) in a passive network, \(V_0 = -Z_0I_0 = 0\). So a line-to-line fault produces no zero-sequence voltage either, and no residual voltage relay will see it.

The absence of zero sequence is what makes the line-to-line fault the odd one out, and it is a diagnostic as well as a simplification. A fault that draws no earth current and produces no residual voltage cannot be an earth fault — so a protection scheme that measures \(3I_0\) distinguishes the phase faults from the earth faults with no ambiguity whatever. That single discrimination is the basis of nearly all distribution protection.
Answer\(I_0 = 0\), \(I_1 = -I_2\), \(V_1-V_2 = I_1Z_f\) — the signature of a parallel connection, with the zero-sequence network unused
Problem 7Exam levelThe LL Connection

Deduce the interconnection for a line-to-line fault and derive the fault current formula, including the \(\sqrt3\).

Solution

The connection. \(I_1 = -I_2\) with a common voltage difference means the positive- and negative-sequence networks are connected in parallel opposition — the positive network's terminal to the negative network's terminal, and their references together, so that current circulates from one into the other:

\[ E \;\longrightarrow\; Z_1 \;\longrightarrow\; Z_f \;\longrightarrow\; Z_2 \;\longrightarrow\; \text{back} \]

The zero-sequence network is left disconnected entirely.

Solving the loop:

\[ \left(E - Z_1I_1\right) - \left(-Z_2I_1\right) = I_1Z_f \]

using \(V_2 = -Z_2I_2 = +Z_2I_1\). Hence

\[ E = I_1\left(Z_1+Z_2+Z_f\right) \quad\Rightarrow\quad \boxed{\;I_1 = \frac{E}{Z_1+Z_2+Z_f}\;} \]

The fault current itself, from the transformation:

\[ I_b = I_0 + a^{2}I_1 + aI_2 = 0 + a^{2}I_1 - aI_1 = (a^{2}-a)I_1 = -j\sqrt3\,I_1 \]
\[ \Rightarrow\quad |I_f| = \sqrt3\,|I_1| = \frac{\sqrt3\,E}{|Z_1+Z_2+Z_f|} \]

The \(\sqrt3\) is \(|a^{2}-a|\), the chord subtending 120° on a unit circle — the same \(\sqrt3\) that relates line and phase voltages, and for the same geometric reason.

The ratio to a three-phase fault, with \(Z_1 = Z_2\) and \(Z_f = 0\):

\[ \frac{I_{LL}}{I_{3\phi}} = \frac{\sqrt3E/(2Z_1)}{E/Z_1} = \frac{\sqrt3}{2} = 0.866 \]

A universal result whenever \(Z_1 = Z_2\), independent of the network. A line-to-line fault always draws 86.6% of the three-phase current at the same point — which is why it is never the switchgear rating case.

The phase \(a\) voltage during the fault is worth computing, because it is unexpected:

\[ V_a = V_1 + V_2 = \left(E - Z_1I_1\right) + Z_2I_1 = E \quad\text{when } Z_1 = Z_2 \]

The healthy phase's voltage is unchanged. A line-to-line fault depresses the two faulted phases and leaves the third at its prefault value, which is quite unlike an earth fault.

And the faulted phases:

\[ V_b = V_c = -\tfrac{1}{2}E \quad\text{when } Z_1 = Z_2,\ Z_f = 0 \]

Both at half the prefault magnitude and in antiphase with \(V_a\) — because a solid line-to-line fault ties them together, and the only voltage they can share is the average of what they would otherwise have.

The ratio \(\sqrt3/2\) is exact and universal, which makes the line-to-line fault the one case that never needs computing. Given the three-phase fault level at a bus, multiply by 0.866. The only caveat is \(Z_1 = Z_2\), which holds for any network without significant motor load — and where motors are present the ratio rises, because they lower \(Z_2\).
AnswerPositive and negative in parallel opposition; \(|I_f| = \sqrt3E/|Z_1+Z_2+Z_f|\), which is exactly 0.866 of the three-phase current when \(Z_1 = Z_2\)
Problem 8Exam levelLL at Bus 3

Compute the line-to-line fault at bus 3 and give the three phase voltages.

Solution

The sequence current:

\[ I_1 = \frac{1.0}{j0.17377 + j0.17377} = \frac{1.0}{j0.34754} = 2.8773\angle-90^\circ\ \text{pu} \]
\[ I_2 = -I_1 = 2.8773\angle90^\circ \qquad I_0 = 0 \]

The fault current:

\[ |I_f| = \sqrt3\,(2.8773) = 4.9837\ \text{pu} = 1308\ \text{A} \]

And the check: \(4.9837/5.7546 = 0.8660 = \sqrt3/2\) exactly, as Problem 7 promised.

The sequence voltages:

\[ V_1 = 1.0 - (j0.17377)(-j2.8773) = 1.0 - 0.5 = 0.5 \]
\[ V_2 = -Z_2I_2 = -(j0.17377)(+j2.8773) = +0.5 \qquad V_0 = 0 \]

Exactly 0.5 each, because \(Z_1 = Z_2\) makes the source voltage divide equally between the two networks.

The phase voltages:

\[ V_a = V_1+V_2 = 1.0\angle0^\circ \]
\[ V_b = a^{2}V_1 + aV_2 = 0.5(a^{2}+a) = -0.5 = 0.5\angle180^\circ \]
\[ V_c = aV_1 + a^{2}V_2 = 0.5(a+a^{2}) = -0.5 = 0.5\angle180^\circ \]

Using \(a+a^{2} = -1\). The two faulted phases are at the same voltage — necessarily, since they are joined — and it is half the prefault magnitude, in antiphase with the healthy phase.

The phasor picture is worth holding. Before the fault, three phasors 120° apart. During it, \(V_a\) is unchanged and \(V_b\) and \(V_c\) have collapsed onto each other at the midpoint of where they were:

\[ \frac{V_b^{(0)}+V_c^{(0)}}{2} = \frac{a^{2}+a}{2}E = -\frac{E}{2} \]

The average of the two prefault phasors, exactly. A solid short between two nodes forces them to the mean of what a source would otherwise impose.

The protection consequence. The voltage between the faulted phases is zero and the voltage to earth of every phase is 0.5 pu or more:

\[ \begin{array}{ll} \text{Phase-to-phase measurement} & \text{sees a solid fault} \\ \text{Phase-to-earth measurement} & \text{sees a modest depression} \\ \text{Residual voltage} & \text{zero} \end{array} \]

Which is why distance relays have separate phase-fault and earth-fault measuring elements, connected to different voltage combinations.

A line-to-line fault leaves the healthy phase entirely undisturbed and the earth completely uninvolved, which makes it the least damaging of the three unsymmetrical faults and the easiest to compute. The whole calculation is a division by \(2Z_1\) and a multiplication by \(\sqrt3\), and the voltages are 1.0, \(-0.5\) and \(-0.5\) whatever the network — an unusual degree of universality for a power system result.
Answer\(I_f = 4.9837\) pu = 1308 A, exactly \(\sqrt3/2\) of the three-phase current; \(V_a = 1.0\), \(V_b = V_c = 0.5\angle180^\circ\) pu
Problem 9Challenge-liteLLG Boundary Conditions

Write the boundary conditions for a double line-to-earth fault on phases \(b\) and \(c\), and transform them.

Solution

In phase quantities, for a solid fault:

\[ I_a = 0 \qquad V_b = 0 \qquad V_c = 0 \]

Phase \(a\) is unaffected; both other phases are connected to earth, so both their voltages are zero. Note that this time two of the conditions are on voltages, where the line-to-earth fault had two on currents.

The current condition transforms as before:

\[ I_a = I_0 + I_1 + I_2 = 0 \]

The voltage conditions. With \(V_b = V_c = 0\):

\[ V_0 = \tfrac{1}{3}(V_a+0+0) = \tfrac{V_a}{3} \]
\[ V_1 = \tfrac{1}{3}(V_a+0+0) = \tfrac{V_a}{3} \qquad V_2 = \tfrac{1}{3}(V_a+0+0) = \tfrac{V_a}{3} \]
\[ \Rightarrow\quad \boxed{V_0 = V_1 = V_2 = \frac{V_a}{3}} \]

The exact dual of the line-to-earth case, with voltages in place of currents. That duality is not a coincidence: the two faults are duals of each other, one shorting two phases to earth and the other opening two.

The three sequence conditions:

\[ \begin{array}{ll} V_0 = V_1 & \text{common voltage across all three} \\ V_1 = V_2 & \\ I_0+I_1+I_2 = 0 & \text{currents sum to zero at the junction} \end{array} \]

A common voltage with currents summing to zero is a parallel connection of all three networks. Compare with the line-to-earth fault's common current and adding voltages, which was a series connection.

With a fault impedance the conditions change in a specific way. If the two phases are joined to each other solidly and to earth through \(Z_g\):

\[ V_b = V_c = (I_b+I_c)Z_g = 3I_0Z_g \]
\[ \Rightarrow\quad V_0 - V_1 = 3I_0Z_g \qquad V_1 = V_2 \]

So \(3Z_g\) enters in series with the zero-sequence branch only — the same factor of three, appearing for the same reason as always.

The duality, stated fully, because it makes both cases memorable:

\[ \begin{array}{lll} & \text{Line-to-earth} & \text{Double line-to-earth} \\ \hline \text{Conditions} & I_0 = I_1 = I_2 & V_0 = V_1 = V_2 \\ \text{Connection} & \text{series} & \text{parallel} \\ \text{Fault impedance} & 3Z_f\ \text{in series} & 3Z_g\ \text{in the zero branch} \end{array} \]
The two earth-fault types are exact duals, and recognising that halves the memorisation. One phase to earth gives equal currents and a series connection; two phases to earth gives equal voltages and a parallel connection. Everything else — the factor of three on the fault impedance, the involvement of the zero-sequence network, the dependence on earthing — follows from those two statements.
Answer\(I_0+I_1+I_2 = 0\) and \(V_0 = V_1 = V_2\) — a parallel connection of all three networks, the exact dual of the line-to-earth case
Problem 10Exam levelThe LLG Connection

Deduce the interconnection for a double line-to-earth fault and derive the three sequence currents.

Solution

The connection. All three networks in parallel — which in practice means the negative and zero networks in parallel with each other, and that combination in series with the positive network's source:

\[ E \;\longrightarrow\; Z_1 \;\longrightarrow\; \left(Z_2 \parallel Z_0\right) \;\longrightarrow\; \text{back} \]

Because the positive-sequence network is the only one containing a source, it must supply the other two, which sit side by side across the fault point.

The positive-sequence current:

\[ \boxed{\;I_1 = \frac{E}{Z_1 + \dfrac{Z_2Z_0}{Z_2+Z_0}}\;} \]

The single most complicated fault formula in Part 5, and it is still one division.

The other two follow from current division across the parallel pair. The current \(I_1\) arrives and splits in inverse proportion to the impedances, flowing out of both:

\[ I_2 = -I_1\frac{Z_0}{Z_2+Z_0} \qquad I_0 = -I_1\frac{Z_2}{Z_2+Z_0} \]

The minus signs express the condition \(I_0+I_1+I_2 = 0\): what enters through the positive network leaves through the other two. Note that the larger share goes to the smaller impedance, as always in a current divider.

The earth current is the quantity most often wanted:

\[ I_g = I_b + I_c = 3I_0 = -\frac{3Z_2I_1}{Z_2+Z_0} \]

And it is not the same as the current in either faulted phase, since some current circulates directly between phases \(b\) and \(c\) without reaching earth.

The two limiting cases check the formula:

\[ \begin{array}{lll} Z_0 \to \infty & Z_2\parallel Z_0 \to Z_2 & \text{reduces to the line-to-line fault} \\ Z_0 \to 0 & Z_2\parallel Z_0 \to 0 & I_1 \to E/Z_1,\ \text{the three-phase value} \end{array} \]

The first is exactly right: with no earth path the two phases are merely shorted together. The second says a perfect earth makes the double line-to-earth fault as severe as a three-phase one in the positive sequence — and the earth current then exceeds it.

With a ground impedance \(Z_g\), the only change is to replace \(Z_0\) by \(Z_0+3Z_g\) throughout:

\[ I_1 = \frac{E}{Z_1 + \dfrac{Z_2(Z_0+3Z_g)}{Z_2+Z_0+3Z_g}} \]

Consistent with every other appearance of a neutral or earth impedance in Part 5.

The double line-to-earth fault interpolates between the other two, and the interpolating parameter is \(Z_0\). With a very poor earth it is a line-to-line fault; with a perfect one its earth current exceeds a three-phase fault's. That range is why it is the fault type that most often produces the highest current somewhere in a system, and why it must be checked rather than assumed.
Answer\(I_1 = E/(Z_1 + Z_2\parallel Z_0)\), with \(I_2\) and \(I_0\) by current division; the earth current is \(3I_0\) and can exceed the three-phase fault
Problem 11AppliedDouble Line-to-Earth Fault

A solid double line-to-earth fault occurs on phases \(b\) and \(c\) at bus 3 of the five-bus system. Using \(Z_{1,33} = Z_{2,33} = j0.17377\) and \(Z_{0,33} = j0.23047\), find all three sequence currents, the earth current, the phase currents and the phase voltages. Base is 100 MVA, 220 kV.

Solution

The parallel combination first, since everything else follows from it:

\[ Z_2\parallel Z_0 = \frac{(j0.17377)(j0.23047)}{j0.17377+j0.23047} = \frac{-0.040046}{j0.40424} = j0.099065 \]

Two reactances in parallel give a reactance, as they must. It is smaller than either, which is what makes this fault severe.

The positive-sequence current:

\[ I_{a1} = \frac{E}{Z_1 + Z_2\parallel Z_0} = \frac{1.0\angle 0°}{j0.17377+j0.099065} = \frac{1.0}{j0.272835} = -j3.66507 \]

So \(|I_{a1}| = 3.6651\) pu, appreciably larger than the \(2.8773\) pu of the line-to-line fault at the same bus, because the earth path has been added in parallel and has lowered the impedance the source sees.

Current division sends the rest into the negative- and zero-sequence networks:

\[ I_{a2} = -I_{a1}\frac{Z_0}{Z_2+Z_0} = +j3.66507\times\frac{0.23047}{0.40424} = +j2.08957 \]
\[ I_{a0} = -I_{a1}\frac{Z_2}{Z_2+Z_0} = +j3.66507\times\frac{0.17377}{0.40424} = +j1.57550 \]

Check the constraint: \(I_{a0}+I_{a1}+I_{a2} = j(1.57550+2.08957-3.66507) = j0.00000\) ✓. The negative sequence takes the larger share because it is the smaller impedance.

The earth current is three times the zero-sequence current:

\[ I_g = 3I_{a0} = j4.72649 \qquad |I_g| = 4.7265\ \text{pu} \]

In amperes, with \(I_{\text{base}} = 100\times10^6/(\sqrt{3}\times220\times10^3) = 262.4\) A, this is 1240 A returning through the earth and the two transformer neutrals.

The phase currents by \(\mathbf{I}_{abc} = \mathbf{A}\,\mathbf{I}_{012}\):

\[ I_a = I_{a0}+I_{a1}+I_{a2} = 0 \]
\[ I_b = I_{a0}+a^2I_{a1}+aI_{a2} = 5.5156\angle 154.63° \]
\[ I_c = I_{a0}+aI_{a1}+a^2I_{a2} = 5.5156\angle 25.37° \]

The healthy phase carries nothing, as the boundary condition demanded. The two faulted phases carry 5.5156 pu = 1447 A each, and the angle between them is \(154.63°-25.37° = 129.26°\) — not \(180°\) as in a line-to-line fault, precisely because their sum is no longer zero but flows to earth.

Arithmetic check on the earth current:

\[ I_b+I_c = 2\times 5.5156\cos(64.63°)\ \angle 90° = j4.7265 \ \checkmark \]

The two phase currents add vectorially to the earth current — and because they are \(129°\) apart, their sum (4.73) is much less than their arithmetic sum (11.03). This is why the earth current in a double line-to-earth fault is often smaller than the phase currents, and why relay engineers must check both.

The sequence voltages at the fault are all equal, by the boundary condition:

\[ V_{a1} = E - Z_1I_{a1} = 1.0 - (j0.17377)(-j3.66507) = 1.0-0.63689 = 0.36311 \]
\[ V_{a2} = -Z_2I_{a2} = -(j0.17377)(j2.08957) = 0.36311 \quad V_{a0} = -Z_0I_{a0} = -(j0.23047)(j1.57550) = 0.36311 \]

Three independent calculations give the same number to five figures — the strongest possible confirmation that the current division was right.

The phase voltages:

\[ V_a = 3\times 0.36311 = 1.08933 \qquad V_b = V_c = 0 \]

The two faulted phases sit at earth potential, and the healthy phase rises to 1.089 pu — a 9% rise, much milder than the 5% seen in the single line-to-earth case at the same bus, because with two phases clamped to earth the neutral cannot shift nearly as far.

A double line-to-earth fault produces the largest phase current at bus 3 (5.5156 pu) of any fault type, yet its earth current (4.7265 pu) is the smallest. The two quantities answer different questions — breaker duty and earth-fault relay pickup — and the same fault can be the worst case for one and the best case for the other.
Answer\(I_{a1}=3.6651,\ I_{a2}=2.0896,\ I_{a0}=1.5755\) pu; \(3I_{a0}=4.7265\) pu (1240 A); \(I_b=I_c=5.5156\) pu (1447 A); \(V_a=1.0893\), \(V_b=V_c=0\)
Problem 12FoundationThree-Phase Fault

Show from the boundary conditions that a solid symmetrical three-phase fault excites only the positive-sequence network, and evaluate it at every bus of the five-bus system.

Solution

The boundary conditions are the simplest of the four types — all three phases are connected together and to earth:

\[ V_a = V_b = V_c = 0 \]

Note that no condition is imposed on the currents at all. That is the reverse of every other fault, where the current conditions did the work.

Transform the voltage conditions:

\[ \begin{bmatrix}V_0\\V_1\\V_2\end{bmatrix} = \frac{1}{3}\begin{bmatrix}1&1&1\\1&a&a^2\\1&a^2&a\end{bmatrix}\begin{bmatrix}0\\0\\0\end{bmatrix} = \begin{bmatrix}0\\0\\0\end{bmatrix} \]

All three sequence voltages vanish. A zero vector transforms to a zero vector — the only case where this happens, and the reason the three-phase fault is the trivial one.

Apply the three network equations with these voltages:

\[ \begin{array}{lll} V_1 = E - Z_1I_1 = 0 & \Rightarrow & I_1 = E/Z_1 \\ V_2 = -Z_2I_2 = 0 & \Rightarrow & I_2 = 0 \\ V_0 = -Z_0I_0 = 0 & \Rightarrow & I_0 = 0 \end{array} \]

The second and third networks have no source, so setting their terminal voltage to zero forces their current to zero as well. Only the first, which contains \(E\), produces anything.

Hence the phase currents are a balanced set:

\[ I_a = I_1 = \frac{E}{Z_1} \qquad I_b = a^2I_1 \qquad I_c = aI_1 \]

Which is exactly what "symmetrical fault" means, and confirms that the entire pre-symmetrical-components method of Set 21 was a special case of this framework all along. The three-phase fault needs no sequence networks — but it is reassuring that the general machinery reproduces it.

Evaluated at every bus, using the positive-sequence driving-point impedances:

Bus\(Z_{1,kk}\) (pu)\(I_f\) (pu)\(I_f\) (A)MVA
1j0.125147.99092097799
2j0.120098.32702185833
3j0.173775.75461510575
4j0.176805.65601484566
5j0.204574.88841283489

Fault MVA is simply \(100\times|I_f|\) here, since \(|E| = 1.0\). Bus 2 is the strongest point in the network and bus 5 the weakest, exactly as the Z-bus diagonal of Set 18 predicted.

Why the three-phase fault is still the design case despite being the rarest:

\[ \begin{array}{ll} \text{It is balanced} & \text{so a single-phase equivalent suffices — cheapest to compute} \\ \text{It bounds the positive-sequence current} & \text{no other fault gives } I_1 > E/Z_1 \\ \text{It is worst near strong sources} & \text{where } X_0 < X_1 \text{ is uncommon} \end{array} \]

The second point deserves emphasis: in every fault type, \(I_1 = E/(Z_1+Z_{\text{extra}})\) with \(Z_{\text{extra}} \ge 0\), so the three-phase value is a strict upper bound on the positive-sequence current. It is not an upper bound on the phase current or the earth current, as the next problem shows.

The three-phase fault is the one case where symmetrical components buy you nothing — and that is exactly why it was solved first, historically and pedagogically. Fortescue's transformation was invented for the other three.
Answer\(V_{012}=0 \Rightarrow I_2=I_0=0,\ I_f = E/Z_1\); fault currents 7.9909 / 8.3270 / 5.7546 / 5.6560 / 4.8884 pu at buses 1–5
Problem 13AppliedFault Impedance

Repeat the three-phase, line-to-earth and line-to-line calculations at bus 3 for fault impedances \(Z_f = j0.05,\ j0.10\) and \(j0.20\) pu, and explain why the three fault types respond so differently to it.

Solution

The three formulas with \(Z_f\) included:

\[ \begin{array}{lll} \text{3-phase} & I_f = \dfrac{E}{Z_1+Z_f} & Z_f \text{ appears once} \\[8pt] \text{L-G} & I_f = \dfrac{3E}{Z_0+Z_1+Z_2+3Z_f} & \text{effectively } 3Z_f \\[8pt] \text{L-L} & I_f = \dfrac{\sqrt3\,E}{|Z_1+Z_2+Z_f|} & Z_f \text{ appears once, but } Z_1+Z_2 \text{ is doubled} \end{array} \]

The fractional effect of \(Z_f\) depends on what it is being added to, and those three denominators are very different in size.

Numerically at bus 3 (\(Z_1=Z_2=j0.17377\), \(Z_0=j0.23047\)):

\(Z_f\) (pu)3-phaseL-GL-LLLG earth
05.75465.19014.98374.7265
j0.054.46884.12084.35693.8230
j0.103.65273.41683.87013.2095
j0.202.67542.54663.16332.4297

All currents in pu on 100 MVA. Every column falls, but at very different rates.

Reduction relative to the solid fault:

\(Z_f\)3-phaseL-GL-L
j0.05−22.3%−20.6%−12.6%
j0.10−36.5%−34.2%−22.3%
j0.20−53.5%−50.9%−36.5%

The line-to-line fault is by far the least sensitive, and the three-phase fault the most.

The explanation is the size of the denominator each \(Z_f\) is added to:

\[ \begin{array}{lll} \text{3-phase} & 0.17377 + Z_f & \text{a small base — } Z_f \text{ dominates quickly} \\ \text{L-G} & 0.57801 + 3Z_f & \text{a large base, but } Z_f \text{ is tripled} \\ \text{L-L} & 0.34754 + Z_f & \text{a middling base, } Z_f \text{ untripled} \end{array} \]

The line-to-line case has the best of both: a base twice the three-phase one, and no factor of three on \(Z_f\). That is why \(Z_f = j0.20\) still leaves it at 63% of its solid value while the three-phase fault has fallen below half.

A crossover is the practical consequence. At \(Z_f = 0\) the three-phase fault is the largest at this bus; by \(Z_f = j0.10\) the line-to-line fault has overtaken it:

\[ \begin{array}{ll} Z_f = 0 & 5.7546 > 5.1901 > 4.9837 \quad (3\phi > \text{LG} > \text{LL}) \\ Z_f = j0.10 & 3.8701 > 3.6527 > 3.4168 \quad (\text{LL} > 3\phi > \text{LG}) \end{array} \]

The ranking of fault severity is not a fixed property of the bus. It depends on the arc resistance, which is unknown and variable. This is one reason protection settings are checked against the solid-fault case for breaker duty and against a high-impedance case for relay sensitivity.

Where \(Z_f\) comes from physically, and typical magnitudes:

SourceNatureTypical value
Arc resistanceResistive, current-dependent0.5–5 Ω
Tower footing resistanceResistive, soil-dependent5–50 Ω
Tree contactHighly resistivehundreds of Ω
Insulator flashoverNear-solid< 1 Ω

On a 220 kV base of \(220^2/100 = 484\ \Omega\), \(Z_f = j0.05\) pu is 24 Ω — a plausible tower-footing figure. Note that real fault impedance is overwhelmingly resistive, so taking it as reactive here is a simplification made only to keep the arithmetic in a single quantity; the qualitative conclusions are unaffected.

Fault impedance enters the line-to-earth loop tripled and the others singly, so it suppresses earth faults hardest — yet earth faults are the ones most likely to be high-impedance in the first place. That unhappy coincidence is why sensitive earth-fault protection is a separate function with its own, much lower, pickup.
AnswerAt \(Z_f=j0.10\): 3φ 3.6527, L-G 3.4168, L-L 3.8701 pu — the ranking has inverted; L-L is least sensitive because \(Z_f\) is untripled and its base impedance is \(2Z_1\)
Problem 14AdvancedFault Severity Ranking

Derive the exact condition under which a solid single line-to-earth fault produces a larger current than a solid three-phase fault at the same bus, and apply it to all five buses.

Solution

Form the ratio of the two currents directly:

\[ \frac{I_{LG}}{I_{3\phi}} = \frac{3E/(Z_0+Z_1+Z_2)}{E/Z_1} = \frac{3Z_1}{Z_0+Z_1+Z_2} \]

The source EMF cancels — the ratio is a pure property of the network, independent of loading and of the prefault voltage.

Use \(Z_2 = Z_1\), which holds to good accuracy in any system without salient-pole machines:

\[ \frac{I_{LG}}{I_{3\phi}} = \frac{3Z_1}{Z_0+2Z_1} = \frac{3}{2 + Z_0/Z_1} \]

Everything now depends on a single dimensionless number: the ratio of zero- to positive-sequence impedance at the faulted bus. For a purely reactive network this is \(X_0/X_1\).

The condition follows by inspection:

\[ I_{LG} > I_{3\phi} \iff \frac{3}{2+X_0/X_1} > 1 \iff \boxed{\ \frac{X_0}{X_1} < 1\ } \]

A remarkably clean result. The earth fault is the worse of the two exactly when the zero-sequence network is stiffer than the positive-sequence one at that point.

Applied to the five-bus system:

Bus\(X_1\)\(X_0\)\(X_0/X_1\)\(I_{LG}/I_{3\phi}\)Worse fault
10.125140.069850.5581.173L-G
20.120090.060710.5061.197L-G
30.173770.230471.3260.9023-phase
40.176800.238381.3480.8963-phase
50.204570.317141.5500.8453-phase

The system divides cleanly into two regions, and the boundary is exactly where the earthed transformer neutrals are.

Why buses 1 and 2 behave differently from the rest:

\[ \begin{array}{ll} \text{Buses 1, 2} & \text{directly at an earthed transformer neutral: } x_0 = j0.10,\ j0.08 \\ \text{Buses 3, 4, 5} & \text{reachable only through lines with } x_0 = 3x_1 \end{array} \]

A solidly earthed star point is a very low-impedance zero-sequence source — lower than the generator's \(x''_d\) in this case. Move away from it and the tripled line reactances take over rapidly, pushing \(X_0/X_1\) well above unity.

The general picture, which every fault study reproduces:

Location\(X_0/X_1\)Consequence
At a solidly earthed transformer LV terminal0.3–0.8L-G is the worst fault
At a generator's terminals0.3–0.6L-G is the worst fault
Mid-line, overhead2.5–3.53-phase is the worst
Mid-cable1–23-phase, marginally
Behind a delta winding\(\infty\)no earth fault current at all

Substation buses are the dangerous case, because they are precisely where transformers are earthed and where breakers must be rated. The habit of rating switchgear on three-phase fault MVA alone is therefore not conservative near an earthed neutral.

The extreme case deserves a number. As \(X_0/X_1 \to 0\):

\[ \frac{I_{LG}}{I_{3\phi}} \to \frac{3}{2} = 1.5 \]

So an earth fault can be up to 50% worse than a three-phase fault, but never more. That bound is a useful sanity check on any fault study: a computed ratio above 1.5 means an error in the zero-sequence data, almost always a forgotten \(3Z_n\) or a delta winding modelled as a star.

\(X_0/X_1 < 1\) is the single criterion that decides which fault is worse, and it is a purely local property of the bus. One number, computed from two Z-bus diagonals you already have, tells you whether your three-phase study was sufficient.
Answer\(I_{LG}/I_{3\phi} = 3/(2+X_0/X_1)\), so L-G is worse iff \(X_0/X_1 < 1\); true at buses 1 (1.173) and 2 (1.197), false at buses 3, 4, 5 (0.902, 0.896, 0.845)
Problem 15AppliedComplete Fault Study

Tabulate the solid fault current for all four fault types at all five buses, identify the governing case at each bus, and state the switchgear rating required.

Solution

The four formulas, collected for reference, with \(Z_2 = Z_1\) throughout:

\[ \begin{array}{lll} 3\phi & I_f = E/Z_1 & \text{balanced, } I_0=I_2=0 \\ \text{L-G} & I_f = 3E/(2Z_1+Z_0) & \text{one phase to earth} \\ \text{L-L} & I_f = \sqrt3E/(2Z_1) & \text{always } 0.866\,I_{3\phi} \\ \text{LLG} & I_b, I_c \text{ from } I_1 = E/(Z_1+Z_1\!\parallel\! Z_0) & \text{and } I_g = 3I_0 \end{array} \]

Only the L-L case has a fixed ratio to the three-phase fault; the two earth faults depend on \(Z_0\).

The complete table, all values in pu on 100 MVA:

Bus3-phaseL-GL-LLLG phaseLLG earthMax
17.99099.37096.92038.942411.3272L-G
28.32709.97057.21149.517412.4222L-G
35.75465.19014.98375.51564.72653-phase
45.65605.06774.89825.40934.59023-phase
54.88844.13074.23354.59563.57633-phase

"LLG phase" is the current in each of the two faulted conductors; "LLG earth" is \(3I_0\). Bold marks the largest of the three phase-conductor currents at each bus — which is what a breaker must interrupt.

Three separate rankings emerge, and confusing them is the commonest error in a fault study:

\[ \begin{array}{ll} \text{Breaker interrupting duty} & \max(I_{3\phi},\ I_{LG},\ I_{LL},\ I_{b,LLG}) \\ \text{Earth-fault relay setting} & \min \text{ over credible cases of } 3I_0 \\ \text{Earthing-conductor sizing} & \max(3I_{0,LG},\ 3I_{0,LLG}) \end{array} \]

At bus 2, for example, the breaker sees 9.97 pu but the earth grid must carry 12.42 pu. Those are different components sized from different columns of the same table.

The pattern across the network:

RegionGoverning faultReason
Buses 1, 2 (generation)L-G\(X_0/X_1 < 1\) at an earthed neutral
Buses 3, 4, 5 (load)3-phase / LLG\(X_0/X_1 > 1\) through tripled line reactance

And note that at buses 3–5 the LLG phase current (5.5156, 5.4093, 4.5956) sits just below the three-phase value (5.7546, 5.6560, 4.8884), so the three-phase fault governs — but only by 4–6%, close enough that neglecting the LLG case would be careless if any parameter were uncertain.

Ratings in engineering units. With \(I_{\text{base}} = 262.4\) A and 100 MVA base:

BusMax phase current (pu)AmperesFault MVAStandard rating
19.3709245993731.5 kA / 1200 MVA
29.9705261799731.5 kA / 1200 MVA
35.7546151057520 kA / 760 MVA
45.6560148456620 kA / 760 MVA
54.8884128348920 kA / 760 MVA

The "standard rating" column picks the next standard short-circuit rating above the computed duty at 220 kV. Note that these currents are modest for a transmission bus — the 5-bus test system is deliberately small — but the selection procedure is exactly that used on a real network.

A margin check. Fault levels grow as generation is added, so a study is normally repeated for the forecast horizon:

\[ \text{Rating} \ge 1.25\times I_{f,\text{max,present}} \]

Applying 25% to bus 2's 997 MVA gives 1246 MVA, which still fits the 1200 MVA class only marginally — a flag that any new generation at bus 2 should trigger a re-check. This is exactly the calculation performed in Problem 20 of Set 18, where adding a machine at bus 5 raised bus 5's duty from 489 to 1156 MVA.

One table, five buses, four fault types, and three different components sized from three different columns. The purpose of a fault study is not a single number but this table — and the discipline of knowing which column each piece of equipment is rated from.
AnswerL-G governs at buses 1 and 2 (9.3709, 9.9705 pu); the three-phase fault governs at buses 3, 4, 5 (5.7546, 5.6560, 4.8884 pu); the largest earth current anywhere is the LLG at bus 2, 12.4222 pu
Problem 16AppliedSequence Voltages

Compare the sequence voltages at the fault point for all four fault types at bus 3, then map the voltage profile of the whole system during a single line-to-earth fault at bus 3.

Solution

The four voltage signatures at the fault point, computed from the currents of Problems 4, 8, 11 and 12:

Fault\(V_1\)\(V_2\)\(V_0\)Relation
3-phase000all zero
L-G0.69937−0.30063−0.39873\(V_1+V_2+V_0=0\)
L-L0.500000.500000\(V_1=V_2\)
LLG0.363110.363110.36311\(V_1=V_2=V_0\)

Each row is a direct restatement of that fault's network connection: series connection forces the voltages to sum to zero; parallel connection forces them equal. The table is the voltage dual of the current table.

The diagnostic content. A relay measuring all three sequence voltages can identify the fault type without any current measurement at all:

\[ \begin{array}{lll} V_1 \approx V_2 \approx V_0 \approx 0 & \Rightarrow & \text{three-phase} \\ V_0 = 0,\ V_1 = V_2 \ne 0 & \Rightarrow & \text{line-to-line} \\ V_1 = V_2 = V_0 \ne 0 & \Rightarrow & \text{double line-to-earth} \\ \text{none of the above} & \Rightarrow & \text{single line-to-earth} \end{array} \]

And \(V_0\) alone separates the earth faults from the phase faults — which is exactly what the broken-delta VT connection, producing \(3V_0\) directly, was invented to measure.

The retained positive-sequence voltage is the quantity that matters for stability and for motor contactor dropout:

\[ V_1: \quad 0 \ (3\phi) \ < \ 0.363 \ (\text{LLG}) \ < \ 0.500 \ (\text{L-L}) \ < \ 0.699 \ (\text{L-G}) \]

A three-phase fault collapses the useful voltage completely; a single line-to-earth fault leaves 70% of it. This is why the three-phase fault dominates transient-stability studies even where it is not the largest current — the machines lose all their electrical output.

The system-wide profile for the L-G fault at bus 3, computed with the off-diagonal Z-bus terms \(V_{s,i} = -Z_{s,i3}I_s\):

Bus\(V_0\)\(V_1\)\(V_2\)\(V_a\)\(V_b = V_c\)
1−0.06180.8161−0.18390.57030.9449
2−0.08890.8011−0.19890.51330.9498
3−0.39870.6994−0.30060.00001.0525
4−0.33680.7197−0.28030.10271.0294
5−0.17150.7740−0.22600.37640.9739

All sequence voltages are real here because the network is purely reactive and \(E\) is real. The faulted-phase voltage collapses to zero only at bus 3 itself; bus 4, one short line away, still holds 0.10 pu, and the generating buses hold more than half.

Three observations from the profile that recur in every fault study:

\[ \begin{array}{ll} V_1 \text{ is highest at the sources} & 0.816,\ 0.801 \text{ at buses 1, 2} \\ V_2 \text{ and } V_0 \text{ are largest at the fault} & \text{and decay outward} \\ V_b, V_c \text{ rise above 1.0 only near the fault} & 1.0525 \text{ at bus 3} \end{array} \]

The first is because the positive-sequence sources are at buses 1 and 2; the second because the negative- and zero-sequence networks have their only source at the fault and are passive elsewhere. Negative-sequence quantities are therefore inherently directional, pointing at the fault — the basis of negative-sequence directional relaying.

Why \(V_0\) at bus 5 is so small (0.1715) compared with bus 4 (0.3368):

\[ \text{bus 5 reaches the fault only through } x_0 = 3\times0.24 = 0.72\ \text{and } 3\times 0.12 = 0.36 \]

Zero-sequence voltage decays much faster than positive-sequence voltage because the tripled line reactances make the zero-sequence network electrically much longer. An earth-fault relay at bus 5 therefore sees a weak signal from a fault at bus 3 — a real limitation of residual-voltage polarisation on long lines.

Currents tell you how much; sequence voltages tell you what kind and where. The pattern \(V_1=V_2=V_0\), or \(V_1+V_2+V_0=0\), identifies the fault type from voltage measurements alone, before a single ampere is measured.
AnswerAt bus 3: 3φ (0,0,0); L-G (0.6994, −0.3006, −0.3987); L-L (0.5, 0.5, 0); LLG (0.3631 ×3). Faulted-phase voltage during the L-G fault: 0.570 / 0.513 / 0 / 0.103 / 0.376 pu at buses 1–5
Problem 17AdvancedZero-Sequence Distribution

For the solid single line-to-earth fault at bus 3, find the zero-sequence current in every line and in each transformer neutral, and verify Kirchhoff's law at the fault bus.

Solution

The zero-sequence voltages found in Problem 16 drive the whole distribution. Restating them as magnitudes (all are negative real):

\[ V_0 = -[\,0.0618,\ 0.0889,\ 0.3987,\ 0.3368,\ 0.1715\,] \]

The fault bus has the largest magnitude, as it must: it is the injection point of the zero-sequence network.

Each line current follows from Ohm's law across it, using \(x_0 = 3x_1\):

\[ I_{0,ij} = \frac{V_{0,i}-V_{0,j}}{jx_{0,ij}} \]

There is no shunt in the zero-sequence line model here — line charging is omitted for fault studies — so the series current is the whole current.

Line 3–4 worked in full as the pattern:

\[ I_{0,34} = \frac{(-0.39873)-(-0.33677)}{j(3\times0.03)} = \frac{-0.06196}{j0.09} = +j0.68844 \]

Magnitude 0.6884 pu, flowing from bus 3 towards bus 4. The very low \(x_0 = j0.09\) of this short, heavily built line makes it the largest single zero-sequence path in the system.

All seven lines:

Line\(x_1\)\(x_0 = 3x_1\)\(|I_0|\) (pu)Direction
1–20.060.180.15052 → 1
1–30.240.720.46793 → 1
2–30.180.540.57373 → 2
2–40.180.540.45904 → 2
2–50.120.360.22955 → 2
3–40.030.090.68843 → 4
4–50.240.720.22954 → 5

Note the direction convention: current flows from the fault bus and returns through the earthed neutrals, so most arrows point towards buses 1 and 2.

Kirchhoff's law at bus 3. All three of bus 3's branches carry current away from it:

\[ I_{0,31}+I_{0,32}+I_{0,34} = 0.4679+0.5737+0.6884 = 1.7300 \]

Which is exactly \(I_0 = I_f/3 = 5.1901/3 = 1.7300\) pu, the zero-sequence current injected at the fault ✓. Every ampere injected at bus 3 leaves through a line — there is no earthed neutral at bus 3 itself.

The transformer neutrals are where the current re-enters the reference:

\[ I_{0,\text{T1}} = \frac{0.06184}{0.10} = 0.6184 \qquad I_{0,\text{T2}} = \frac{0.08893}{0.08} = 1.1116 \]
\[ 3I_{0,\text{T1}} = 1.855\ \text{pu} = 487\ \text{A} \qquad 3I_{0,\text{T2}} = 3.335\ \text{pu} = 875\ \text{A} \]

These are the currents that a neutral CT would measure, and they are what an earthing-transformer or neutral-earthing resistor must be rated to carry. Check: \(0.6184+1.1116 = 1.7300\) ✓ — the two neutrals between them return the whole zero-sequence current.

Bus 2 carries more than bus 1 despite bus 1 being the slack. The reason is entirely zero-sequence:

\[ x_{0,\text{T2}} = j0.08 < x_{0,\text{T1}} = j0.10 \quad\text{and}\quad \text{bus 2 is closer to bus 3 in the zero-sequence network} \]

In positive sequence, bus 1 is the stronger source. In zero sequence, the ranking reverses. The earth-fault current distribution has nothing to do with generation and everything to do with where the star points are earthed — one of the most useful practical facts in this whole subject.

Consequence for earthing practice. Suppose transformer 2's neutral were opened:

\[ \text{remaining } x_0 \text{ path: only through T1} \Rightarrow Z_{0,33} \text{ rises} \Rightarrow I_f \text{ falls} \]

Earth-fault current would drop substantially, which sounds attractive until you note that the healthy-phase voltage rise increases with \(X_0/X_1\) (Problem 5) and the fault becomes harder to detect. Multiple earthing points is a deliberate compromise between limiting current and keeping the system detectably and safely earthed.

The zero-sequence current distribution is set by the earthing arrangement, not by the generation pattern. Change one transformer from delta to earthed-star and the entire earth-fault picture changes, while the three-phase fault levels do not move at all.
AnswerLine \(I_0\): 0.1505, 0.4679, 0.5737, 0.4590, 0.2295, 0.6884, 0.2295 pu; neutral currents \(3I_0 = 1.855\) and \(3.335\) pu; the three branches at bus 3 sum to 1.7300 = \(I_f/3\)
Problem 18AdvancedOpen-Conductor Fault

One conductor of line 4–5 breaks at the bus-5 end. Derive the sequence network connection for an open conductor, and evaluate the currents given the prefault load-flow condition of Set 20. Repeat for two conductors open.

Solution

Series faults need different boundary conditions. Let \(p\) and \(p'\) be the two sides of the break, and let \(V_a, V_b, V_c\) be the voltages across it. With phase \(a\) open and \(b, c\) intact:

\[ I_a = 0 \qquad V_b = V_c = 0 \]

The intact conductors carry current with no voltage drop across the break; the broken one has voltage across it but no current. Exactly the reverse of a shunt fault, where the fault point had voltage conditions on the faulted phases.

Transform both conditions:

\[ V_b = V_c = 0 \Rightarrow V_0 = V_1 = V_2 = \tfrac{1}{3}V_a \]
\[ I_a = 0 \Rightarrow I_0+I_1+I_2 = 0 \]

Equal voltages and currents summing to zero — the signature of a parallel connection. The one-open-conductor case connects the three sequence networks in parallel across the break, exactly as the double line-to-earth fault connected them in parallel at the fault bus.

The dual case, two conductors open (\(b\) and \(c\) broken, \(a\) intact):

\[ I_b = I_c = 0 \Rightarrow I_0 = I_1 = I_2 = \tfrac13 I_a \qquad V_a = 0 \Rightarrow V_0+V_1+V_2 = 0 \]

Equal currents, voltages summing to zero — a series connection, the mirror of the single line-to-earth fault. The whole of Part 5 reduces to two connection patterns used four ways.

The Thévenin equivalent across the break. With the break fully open, the network seen from \(pp'\) in each sequence is:

\[ Z_{th,s} = Z_{s,pp}+Z_{s,p'p'}-2Z_{s,pp'} \]
\[ Z_{th,1} = Z_{th,2} = j0.43922 \qquad Z_{th,0} = j1.31434 \]

Both computed on the network with line 4–5 broken. The zero-sequence value is roughly three times the positive-sequence one, which is the tripled-reactance rule showing up again.

The driving voltage is the open-circuit voltage that would appear across \(pp'\) if all three conductors were opened. By superposition it is the prefault current times the positive-sequence Thévenin impedance:

\[ I_{\text{pre},45} = \frac{V_4-V_5}{Z_{45}} = \frac{1.02357\angle{-5.3291°}-1.01794\angle{-6.1503°}}{0.08+j0.24} = 0.06196\angle{-8.35°} \]
\[ E_{th} = I_{\text{pre}}Z_{th,1} = 0.06196\times 0.43922 = 0.02722\ \text{pu} \]

Sanity check: with all three conductors intact, the impedance across \(pp'\) is zero, and \(I_1 = E_{th}/Z_{th,1} = I_{\text{pre}}\) ✓. The equivalent reproduces the prefault state, as it must.

One conductor open — the parallel connection gives:

\[ I_1 = \frac{E_{th}}{Z_{th,1}+Z_{th,2}\parallel Z_{th,0}} = \frac{0.02722}{j(0.43922+0.32941)} = 0.03542\ \text{pu} \]
\[ I_2 = -I_1\frac{Z_0}{Z_2+Z_0} = 0.02655 \qquad I_0 = -I_1\frac{Z_2}{Z_2+Z_0} = 0.00887 \]

The positive-sequence current has fallen from 0.06196 to 0.03542 pu — the line still carries 57% of its prefault power on two conductors, because the remaining phases have a return path through the rest of the network.

The phase currents:

QuantityOne openTwo openPrefault
\(I_1\)0.035420.012410.06196
\(I_2\)0.026550.012410
\(I_0\)0.008870.012410
\(I_a\)00.037230.06196
\(I_b = I_c\)0.0552900.06196
\(3I_0\)0.026610.037230

All in pu on 100 MVA. Note that with one conductor open the two survivors each carry less than the prefault current (0.0553 vs 0.0620) — the load simply redistributes to other paths rather than overloading the remaining conductors.

Why open conductors are so hard to detect. The earth current here is:

\[ 3I_0 = 0.0266\ \text{pu} = 7.0\ \text{A} \]

Seven amperes, against an earth-fault relay that may be set at 200 A and a phase relay set well above load. No overcurrent element will ever see this. Yet a broken conductor lying on the ground is one of the most dangerous conditions on a distribution system.

The quantity that does detect it is the negative-sequence ratio:

\[ \frac{I_2}{I_1} = \frac{Z_{th,0}}{Z_{th,2}+Z_{th,0}} = \frac{1.31434}{1.75356} = 0.750 \]

A ratio of 75% — enormous, since a healthy system runs below 2%. And it is a ratio, so it is independent of loading: the same 0.750 whether the line carries 6 MW or 60. Broken-conductor protection is built on exactly this measurement, typically alarming above \(I_2/I_1 = 0.2\). For two conductors open the ratio is 1.000, higher still.

An open conductor produces almost no extra current but an enormous unbalance ratio. That is why series faults need their own protection philosophy: magnitude-based relaying is blind to them, and only the ratio \(I_2/I_1\) — dimensionless and load-independent — reliably sees them.
AnswerOne open: networks in parallel, \(I_1=0.03542\), \(I_b=I_c=0.05529\), \(3I_0=0.0266\) pu, \(I_2/I_1=0.750\). Two open: networks in series, \(I_0=I_1=I_2=0.01241\), \(I_a=0.03723\) pu, \(I_2/I_1=1.000\)
Problem 19AdvancedFaults Across a Transformer

A solid single line-to-earth fault occurs at bus 1, on the earthed-star side of generator 1's \(\Delta\!-\!Y_g\) unit transformer. Find the fault current, the transformer's contribution, and the currents seen on the generator (delta) side.

Solution

The fault current at bus 1, from the driving-point impedances of Set 22:

\[ I_f = \frac{3\times1.0}{j(0.12514+0.12514+0.06985)} = \frac{3}{j0.32013} = -j9.37093 \]

9.3709 pu = 2459 A, and each sequence current is \(I_0 = I_1 = I_2 = 3.12364\) pu. Larger than the three-phase value of 7.9909 pu, because \(X_0/X_1 = 0.558 < 1\) here (Problem 14).

Sequence voltages at bus 1:

\[ V_1 = 1 - (j0.12514)(-j3.12364) = 0.60910 \quad V_2 = -0.39090 \quad V_0 = -0.21820 \]

Sum zero ✓. The phase voltages are \(V_a = 0\) and \(V_b = V_c = 0.9258\angle\mp110.70°\) — an earth-fault factor of only 0.926, below nominal, which is the hallmark of a strongly earthed bus.

The transformer's own contribution is found from the branch equations. In positive and negative sequence the machine and its transformer are lumped into \(x = j0.25\); in zero sequence only the transformer appears, \(x_0 = j0.10\):

\[ I_1 = \frac{E-V_1}{j0.25} = \frac{0.39090}{j0.25} = -j1.56360 \qquad I_2 = \frac{-V_2}{j0.25} = -j1.56360 \]
\[ I_0 = \frac{-V_0}{j0.10} = \frac{0.21820}{j0.10} = -j2.18198 \]

Note the asymmetry: this branch supplies half the positive- and negative-sequence current (1.564 of 3.124) but 70% of the zero-sequence current (2.182 of 3.124). It is the nearer of the only two earthing points.

The star-side line currents by recombination:

\[ I_a = I_0+I_1+I_2 = -j5.30919 \qquad I_b = I_c = -j0.61837 \]

The healthy phases are not current-free on this branch — only the total at the fault has \(I_b = I_c = 0\), and the two contributions from transformer 1 and from the network cancel there. Each individually carries 0.618 pu. The neutral current is \(3I_0 = 6.546\) pu = 1718 A.

Crossing to the delta side. Two things happen, and both matter:

\[ \begin{array}{ll} \text{Zero sequence is blocked} & I_0' = 0 \text{ — the delta circulates it and it never leaves} \\ \text{The other two shift oppositely} & I_1' = I_1\angle{+30°},\quad I_2' = I_2\angle{-30°} \end{array} \]

The \(\pm30°\) is the standard Yd1/YNd1 phase displacement. Positive sequence advances, negative sequence retards — by the same angle, in opposite directions. In a balanced study the shift can be ignored; here it cannot, because the two sequences no longer rotate together.

The generator-side line currents:

\[ I_A = I_1' + I_2' = 1.56360(\angle{-60°}+\angle{-120°}) = 2.70824\angle{-90°} \]
\[ I_B = a^2I_1'+aI_2' = 1.56360(\angle{180°}+\angle{0°}) = 0 \]
\[ I_C = aI_1'+a^2I_2' = 2.70824\angle{+90°} \]

A completely different pattern from the star side. One phase carries nothing, and the other two carry equal and opposite currents.

The classic result, worth committing to memory:

Side\(I_a\) or \(I_A\)\(I_b\) or \(I_B\)\(I_c\) or \(I_C\)Appears to be
Star (fault side)5.30920.61840.6184an earth fault
Delta (generator)2.708202.7082a line-to-line fault

A single line-to-earth fault on the star side looks like a line-to-line fault from the delta side, in the ratio \(1:0:1\). The generator's own protection therefore sees an unbalanced two-phase condition, not an earth fault — and no earth-fault relay on the generator side will operate at all, because \(3I_0 = 0\) there.

Two checks:

\[ I_A+I_B+I_C = 0 \ \checkmark \qquad |I_A| = \sqrt3\,|I_1| = 1.7321\times1.56360 = 2.70824 \ \checkmark \]

The first confirms that no zero sequence crossed the delta; the second is the general rule that for this pattern the delta-side line current is \(\sqrt3\) times the positive-sequence current, because \(I_1'\) and \(I_2'\) are 60° apart.

A delta winding is a one-way mirror: it blocks zero sequence entirely and rotates the other two sequences in opposite directions. Every differential relay across a \(\Delta\!-\!Y\) transformer must compensate for both effects, which is why "delta-connected CTs" and zero-sequence traps exist.
Answer\(I_f = 9.3709\) pu; transformer 1 contributes \(I_1=I_2=1.5636\), \(I_0=2.1820\) pu, star-side \(I_a=5.3092\), \(I_b=I_c=0.6184\), neutral 6.546 pu; delta side \(2.7082 : 0 : 2.7082\) pu with \(I_0'=0\)
Problem 20AdvancedComplete Fault Study

Carry out a complete fault study at bus 2 — the electrically strongest bus — covering all four fault types, and set out the checks that confirm the study is self-consistent.

Solution

Step 1 — assemble the data. Everything needed is three numbers from Set 22:

\[ Z_{1,22} = Z_{2,22} = j0.12009 \qquad Z_{0,22} = j0.06071 \qquad E = 1.0\angle0° \]

And the ratio that governs everything: \(X_0/X_1 = 0.06071/0.12009 = 0.506\). Being well below unity, we know before computing anything that the earth fault will be the worst.

Step 2 — the three-phase fault:

\[ I_f = \frac{1.0}{j0.12009} = -j8.32700 \qquad \text{MVA}_f = 833 \]

2185 A at 220 kV. All sequence voltages zero at the fault; \(I_0 = I_2 = 0\).

Step 3 — the single line-to-earth fault:

\[ I_f = \frac{3.0}{j(0.12009+0.12009+0.06071)} = \frac{3.0}{j0.30089} = -j9.97046 \]
\[ I_0=I_1=I_2 = 3.32349 \qquad V_a = 0,\quad V_b=V_c = 0.9174\angle\mp109.26° \]

9.9705 pu = 2617 A, the largest phase-conductor current at this bus. The earth-fault factor is 0.917 — the healthy phases actually fall, the signature of a solidly and stiffly earthed bus.

Step 4 — the line-to-line fault:

\[ I_f = \frac{\sqrt3\times1.0}{j(2\times0.12009)} = 7.21139 \ \text{pu} \]

1892 A, and exactly \(0.866\times8.3270\) ✓ — the universal \(\sqrt3/2\) ratio holds regardless of the network, because \(Z_2 = Z_1\).

Step 5 — the double line-to-earth fault:

\[ Z_1\parallel Z_0 = \frac{(0.12009)(0.06071)}{0.18080} = 0.04033 \qquad I_1 = \frac{1.0}{j0.16042} = 6.23386 \]
\[ I_b = I_c = 9.51744 \qquad 3I_0 = 12.42216 \qquad V_a = 0.75410 \]

The earth current of 12.42 pu = 3260 A is the largest current anywhere in this study — 49% above the three-phase fault. With \(X_0\) only half of \(X_1\), the parallel branch is very low impedance and the earth path takes a large share.

Step 6 — the summary table, which is the actual deliverable:

Fault\(I_f\) (pu)Amperes\(3I_0\) (pu)Rated component
3-phase8.327021850breaker, busbar bracing
L-G9.970526179.9705breaker, neutral CT
L-L7.211418920
LLG (phase)9.51742498breaker
LLG (earth)326012.4222earth grid, NER

Breaker duty: 9.9705 pu = 2617 A. Earth-grid duty: 3260 A. Two different numbers, from two different rows, for two different pieces of equipment.

Step 7 — the consistency checks. Five identities that any correct study must satisfy:

CheckExpectedFound
\(I_{LL}/I_{3\phi}\)0.86607.2114/8.3270 = 0.8660 ✓
\(I_{LG}/I_{3\phi} = 3/(2+X_0/X_1)\)1.19749.9705/8.3270 = 1.1974 ✓
LLG: \(I_0+I_1+I_2\)00.00000 ✓
LLG: \(V_0 = V_1 = V_2\)equal0.25137 (×3) ✓
L-G: \(V_0+V_1+V_2\)00.00000 ✓

Each of these is computed by a route independent of the number it checks, so agreement to five figures is strong evidence, not a tautology.

Step 8 — the sanity bounds that catch data errors rather than arithmetic ones:

\[ \begin{array}{lll} I_{LG}/I_{3\phi} & \le 1.5 & 1.197 \ \checkmark \\ I_{LL}/I_{3\phi} & = 0.866 \text{ exactly} & 0.866 \ \checkmark \\ I_1 \text{ in any fault} & \le E/Z_1 & 6.234 \le 8.327 \ \checkmark \\ \text{earth-fault factor} & \le 1.732 & 0.917 \ \checkmark \end{array} \]

A violation of any of these means the input data is wrong — most often a delta winding entered as an earthed star, a forgotten \(3Z_n\), or a zero-sequence line reactance left equal to the positive-sequence value.

Step 9 — what the study is for. The numbers feed four distinct downstream decisions:

DecisionQuantity usedValue here
Breaker interrupting ratingmax phase current2617 A
Overcurrent relay pickupmin fault / max loadmargin check
Earth-fault relay pickupmin \(3I_0\) over cases2617 A (L-G)
Earth grid / NER ratingmax \(3I_0\)3260 A (LLG)

Note the third and fourth rows use the minimum and maximum earth current respectively. Sensitivity is set by the smallest credible fault; thermal rating by the largest. Using one number for both is the commonest error in a first fault study.

A fault study is not one calculation but a matrix: four fault types × every bus × best and worst network conditions. Symmetrical components reduce each cell to three impedances and one connection rule — which is precisely why the method has survived a century of use.
AnswerAt bus 2: 3φ 8.3270, L-G 9.9705, L-L 7.2114, LLG phase 9.5174 pu; largest earth current 12.4222 pu (LLG). Breaker duty 2617 A, earth-grid duty 3260 A; all five consistency checks satisfied

Practice Problems

Twelve problems on the same five-bus system and on standalone machines. Unless stated otherwise take \(E = 1.0\angle0°\), \(Z_2 = Z_1\), a 100 MVA / 220 kV base and \(I_{\text{base}} = 262.4\) A. Work each one through before opening the answer.

1. A solid single line-to-earth fault occurs at bus 4, where \(Z_{1,44} = j0.17680\) and \(Z_{0,44} = j0.23838\). Find the fault current in per unit and in amperes.

Answer

\(I_f = 3/(2\times0.17680+0.23838) = 3/0.59198 = 5.0677\) pu = 1330 A. Compare the three-phase value at the same bus, \(1/0.17680 = 5.6560\) pu: the earth fault is the smaller here, consistent with \(X_0/X_1 = 1.348 > 1\).

2. Find the line-to-line fault current at bus 5 (\(Z_{1,55} = j0.20457\)) without computing anything but the three-phase value.

Answer

\(I_{3\phi} = 1/0.20457 = 4.8884\) pu, and since \(Z_2 = Z_1\) the line-to-line current is always \(\sqrt3/2\) of it: \(0.8660\times4.8884 = \) 4.2333 pu = 1111 A. No zero-sequence data is needed at all — the line-to-line fault never involves earth.

3. A double line-to-earth fault occurs at bus 4. Find the current in each faulted conductor and the earth current.

Answer

\(Z_1\parallel Z_0 = (0.17680)(0.23838)/(0.41518) = 0.10152\), so \(I_1 = 1/(j0.27832) = 3.5930\) pu. Current division gives \(I_0 = -I_1(0.17680/0.41518) = 1.5301\), hence \(3I_0 = \) 4.5902 pu (1205 A) and \(I_b = I_c = \) 5.4093 pu (1420 A). The healthy phase rises to \(V_a = 1.0942\) pu.

4. During the fault of Problem 1, what voltage appears on the two healthy phases at bus 4? State the earth-fault factor.

Answer

\(I_0=I_1=I_2 = 1.6892\), giving \(V_1 = 1-(0.17680)(1.6892) = 0.70131\), \(V_2 = -0.29869\), \(V_0 = -0.40270\). Recombining, \(V_b = V_c = \) 1.0559 pu, so the earth-fault factor is 1.056. Insulation and surge arresters at bus 4 must tolerate a 5.6% rise for the duration of the fault.

5. Repeat Problem 1 at bus 5 (\(Z_{1,55} = j0.20457\), \(Z_{0,55} = j0.31714\)) with a fault impedance \(Z_f = j0.10\) pu.

Answer

Remember that \(Z_f\) is tripled in the line-to-earth loop: \(I_f = 3/(0.40914+0.31714+0.30) = 3/1.02628 = \) 2.9232 pu = 767 A, down from 4.1307 pu solid — a 29% reduction from only \(j0.10\) pu of fault impedance. The healthy-phase voltage barely changes, at 1.059.

6. Without computing any current, decide whether the earth fault or the three-phase fault is more severe at bus 4, and by what factor.

Answer

\(X_0/X_1 = 0.23838/0.17680 = 1.348\). Since this exceeds unity the three-phase fault is worse, and the ratio is \(I_{LG}/I_{3\phi} = 3/(2+1.348) = \) 0.896. Checking against Problems 1 and 3: \(5.0677/5.6560 = 0.896\) ✓.

7. For the single line-to-earth fault at bus 1 of Problem 19, transformer 1's zero-sequence contribution was \(I_0 = 2.18198\) pu. What current flows in its neutral connection, in amperes?

Answer

The neutral carries the sum of the three phase currents, which is \(3I_0 = 3\times2.18198 = 6.5459\) pu = 1718 A. Note this is more than the transformer's own phase-\(a\) current of 5.3092 pu — the neutral conductor of an earthed transformer can carry more than any of its line conductors during an earth fault, which is why it is never sized by the line rating.

8. An isolated generator has \(x_1 = x_2 = 0.20\), \(x_0 = 0.05\) pu, star point solidly earthed. Compare its three-phase and single line-to-earth fault currents at the terminals.

Answer

\(I_{3\phi} = 1/0.20 = 5.000\) pu; \(I_{LG} = 3/(0.40+0.05) = \) 6.667 pu, a ratio of 1.333. This is the standard reason generator star points are never solidly earthed: the machine's own \(x_0\) is far below its \(x''_d\), so a terminal earth fault would exceed the three-phase design current by a third and damage the stator core.

9. Repeat Problem 8 with a neutral earthing reactor \(Z_n = j0.10\) pu.

Answer

\(3Z_n = j0.30\) appears in the zero-sequence loop: \(I_{LG} = 3/(0.40+0.05+0.30) = \) 4.000 pu — now below the three-phase value, and 40% below the solidly earthed case. Note the extraordinary leverage: 0.10 pu of neutral reactance removed 2.67 pu of fault current, because it entered the loop tripled and the loop impedance was small to begin with.

10. A single line-to-earth fault on the earthed-star side of a \(\Delta\!-\!Y_g\) transformer draws \(I_f = 6.0\) pu, of which the transformer supplies all three sequences equally. What currents flow in the three delta-side lines?

Answer

\(I_1 = I_2 = I_0 = 2.0\) pu. Zero sequence cannot cross the delta, so \(I_0' = 0\), and the two remaining sequences shift by \(\pm30°\) into a 60° separation. The delta-side lines carry \(\sqrt3\times2.0 = \) 3.4641 : 0 : 3.4641 pu. From the generator's side it looks like a line-to-line fault, and no earth-fault relay there will see anything at all.

11. One conductor of a line opens. The Thévenin impedances across the break are \(Z_1 = Z_2\) and \(Z_0 = 2.5Z_1\). Find the ratio \(I_2/I_1\) that a broken-conductor relay would measure.

Answer

For one open conductor the networks are in parallel across the break, so current division gives \(I_2/I_1 = Z_0/(Z_2+Z_0) = 2.5/3.5 = \) 0.714. A healthy line runs below 0.02, so a relay set at 0.20 would operate comfortably — and the ratio is independent of load current, which is the whole point of using it.

12. A double line-to-earth fault at bus 5 (\(Z_{1,55} = j0.20457\), \(Z_{0,55} = j0.31714\)) has a ground-path impedance \(Z_g = j0.05\) pu. Find \(I_1\) and the earth current.

Answer

Replace \(Z_0\) by \(Z_0+3Z_g = j0.46714\). Then \(Z_1\parallel(Z_0+3Z_g) = (0.20457)(0.46714)/0.67171 = 0.14226\) and \(I_1 = 1/(j0.34683) = \) 2.8832 pu. Current division gives \(I_0 = -I_1(0.20457/0.67171) = 0.8781\), so \(3I_0 = \) 2.6342 pu, down from 3.5763 pu with a solid ground — a 26% reduction from a small ground impedance, again because of the factor of three.

Challenge Problems

Three extended investigations. Each has a result worth remembering, and the first has a conclusion that is cleaner than it has any right to be.

Challenge 1The Universal Crossover

Normalise \(Z_1 = Z_2 = j1\) and let \(m = X_0/X_1\) vary from 0 to \(\infty\). Plot the four solid-fault currents against \(m\), find every crossover, and determine which fault type governs over each range.

The four currents as functions of \(m\), in units of the three-phase current:

\[ \begin{array}{ll} 3\phi & 1 \\ \text{L-G} & \dfrac{3}{2+m} \\ \text{L-L} & \dfrac{\sqrt3}{2} = 0.8660 \quad\text{(constant)} \\ \text{LLG (earth)} & \dfrac{3}{1+2m} \\ \text{LLG (phase)} & \left|\dfrac{(1+m)}{(1+2m)}\left(a^2 - \dfrac{m}{1+m} a - \dfrac{1}{1+m}\right)\right| \end{array} \]

The last is obtained from \(I_1 = (1+m)/(1+2m)\) followed by current division and recombination. Only the line-to-line curve is flat.

Tabulated:

\(m\)L-GL-LLLG phaseLLG earthGoverning
01.00001.50000.86601.73213.0000LLG
0.251.00001.33330.86601.32292.0000L-G
0.501.00001.20000.86601.14561.5000L-G
0.751.00001.09090.86601.05361.2000L-G
1.001.00001.00000.86601.00001.0000tie
1.501.00000.85710.86600.94370.7500
3.001.00000.60000.86600.89210.4286
10.01.00000.25000.86600.86900.1429
\(\infty\)1.000000.86600.86600

Look at the row \(m = 1\). Four of the five columns read exactly 1.0000.

The crossover is universal. At \(m = 1\), all three earth-involving quantities equal the three-phase current simultaneously:

\[ \frac{3}{2+m}\bigg|_{m=1} = 1 \qquad \frac{3}{1+2m}\bigg|_{m=1} = 1 \qquad |I_{b,LLG}|\big|_{m=1} = 1 \]

The first two are one-line verifications. The third is not obvious, so it is worth proving.

Proof of the third. Set \(Z_0 = Z_1 = Z_2 = j1\) in the LLG equations:

\[ I_1 = \frac{1}{j(1+\tfrac12)} = -j\tfrac23 \qquad I_2 = I_0 = -\tfrac12 I_1 = +j\tfrac13 \]
\[ I_b = I_0+a^2I_1+aI_2 = j\left(\tfrac13 - \tfrac23a^2 + \tfrac13a\right) \]

Substituting \(a = -\tfrac12+j\tfrac{\sqrt3}{2}\) and \(a^2 = -\tfrac12-j\tfrac{\sqrt3}{2}\) gives \(I_b = j(\tfrac13+\tfrac13+\tfrac{\sqrt3}{3}j -\tfrac16+j\tfrac{\sqrt3}{6})\), which reduces to \(|I_b| = 1\) exactly. All four fault types coincide.

Why this must be so, once you see it. When \(Z_0 = Z_1 = Z_2\) the three sequence networks are identical. Every connection rule — series, parallel, series-parallel — then produces the same total impedance seen by \(E\):

\[ \text{L-G: } \frac{3E}{3Z} = \frac{E}{Z} \qquad \text{LLG: } \frac{E}{Z+Z/2}\cdot\text{(recombination)} = \frac{E}{Z} \]

The unbalance disappears from the answer because there is nothing left to be unbalanced about. Symmetrical components only produce different fault currents when the sequence networks actually differ — and \(m = 1\) is precisely where they stop differing.

The complete map:

RangeGoverning (phase current)Governing (earth current)Physical situation
\(m < 0.227\)LLG phaseLLG earthvery stiff earthing, generator terminals
\(0.227 < m < 1\)L-GLLG earthsolidly earthed substation bus
\(m > 1\)3-phaseL-Gout along overhead lines

The line-to-line fault never governs anything for a solid fault, since it is 0.866 everywhere and the LLG phase current approaches 0.866 from above as \(m\to\infty\) without ever falling below it. It becomes relevant only when fault impedance is present (Problem 13).

The practical rule that falls out:

\[ \boxed{\ X_0/X_1 = 1 \text{ is the dividing line for every fault comparison, not just L-G vs } 3\phi\ } \]

Compute \(X_0/X_1\) at a bus and you know immediately, without further arithmetic, whether the three-phase study you already have is conservative. Above 1, it is. Below 1, it is not, and every earth fault must be checked.

All four fault types produce identical current when \(X_0 = X_1 = X_2\), because at that point the three sequence networks are the same network and the connection rule stops mattering. It is the cleanest single fact in unsymmetrical fault analysis, and it makes \(X_0/X_1\) the only screening number you need.
AnswerAll crossovers occur at \(m = 1\): LLG governs for \(m < 0.227\), L-G for \(0.227 < m < 1\), three-phase for \(m > 1\). The L-L fault, fixed at 0.866, never governs a solid fault
Challenge 2Sizing a Neutral Earthing Reactor

The five-bus system's earth-fault current at bus 2 (9.9705 pu, 2617 A) is to be limited to 1000 A by fitting identical earthing reactors \(X_n\) in both transformer neutrals. Find \(X_n\), and evaluate what is gained and what is lost.

Where \(X_n\) enters. A neutral impedance appears in the zero-sequence network only, as \(3X_n\) in series with that transformer's shunt branch:

\[ x_{0,\text{T1}}: j0.10 \to j(0.10+3X_n) \qquad x_{0,\text{T2}}: j0.08 \to j(0.08+3X_n) \]

The positive- and negative-sequence networks are completely untouched, so \(Z_1\) and every three-phase fault level stay exactly where they were. This is the first and most important property of neutral earthing: it is a lever on earth faults alone.

The target in per unit:

\[ I_{f,\text{target}} = \frac{1000}{262.4} = 3.8105\ \text{pu} \]

A reduction to 38% of the present value — a substantial intervention, not a trim.

Solving requires re-inverting the zero-sequence Y-bus for each trial \(X_n\), because changing one shunt changes \(Z_{0,22}\) non-linearly. Iterating:

\(X_n\) (pu)\(Z_{0,22}\)\(I_{LG,2}\) (pu)Amperes
0j0.060719.97052617
0.10j0.225026.44881692
0.20j0.378124.85201273
0.3117j0.547123.81051000
0.50j0.830722.8014735

\(X_n = 0.3117\) pu, which on a 220 kV, 100 MVA base (\(Z_{\text{base}} = 220^2/100 = 484\ \Omega\)) is 151 Ω per neutral. That is a large reactor, reflecting how stiff the original earthing was.

What is gained, across the whole system:

Bus\(I_{LG}\) before (A)\(I_{LG}\) after (A)Reduction
12459986−60%
226171000−62%
31362749−45%
41330738−45%
51084651−43%

Earth-fault energy scales as \(I^2t\), so a 60% current reduction at bus 2 cuts the arc energy by 85%. Burn damage at the fault, step-and-touch potentials on the earth grid, and CT saturation all improve dramatically. The three-phase levels — 2185 A at bus 2 — are unchanged.

What is lost, first: the healthy-phase voltage rise. With \(X_0/X_1\) pushed from 0.506 to 4.56 at bus 2:

Bus\(X_0/X_1\) afterEarth-fault factor beforeafter
14.3830.9261.346
24.5560.9171.355
34.0501.0531.326
44.0361.0561.325
53.9071.0861.317

The healthy phases now rise to 1.35 pu during every earth fault, against 0.92–1.09 before. That crosses the conventional 1.4 threshold uncomfortably closely, and it changes the surge arrester rating and the insulation coordination class for the whole system. The system has moved from "effectively earthed" towards "non-effectively earthed", with all the cost that implies.

What is lost, second: detectability. Earth-fault relays now see 651–1000 A instead of 1084–2617 A, while load current is unchanged:

\[ \frac{I_{f,\min}}{I_{\text{load}}} : \quad \frac{1084}{262} = 4.1 \ \longrightarrow \ \frac{651}{262} = 2.5 \]

The margin between the smallest fault and full load has almost halved. Sensitive earth-fault settings and residual-connected CTs become necessary, and a high-impedance earth fault that was formerly detectable may no longer be.

The judgment. Weighing the three effects:

EffectDirectionMagnitude
Fault energy at the arcimproved−85%
Earth grid / step potential dutyimproved−62%
Insulation and arrester dutyworsened+44% overvoltage
Relay sensitivity marginworsened−39%
Three-phase fault levelsunchanged0%
Capital costworsenedtwo 151 Ω reactors

For a 220 kV transmission system this trade is normally judged unfavourable: at transmission voltages insulation is the dominant cost and effective earthing (\(X_0/X_1 < 3\), EFF \(< 1.4\)) is the near-universal practice. Reactance or resistance earthing belongs at generator terminals and on industrial medium-voltage systems, where insulation is cheap relative to the machine being protected. A smaller \(X_n \approx 0.10\) pu, giving 1692 A and EFF 1.12, would be a defensible compromise here.

Neutral earthing impedance is the one design parameter that changes earth-fault current without touching three-phase fault levels — and it always buys reduced current at the price of increased overvoltage. The choice of earthing method is therefore a choice about which cost your system can better absorb, and it is made once, at design, for the life of the plant.
Answer\(X_n = 0.3117\) pu = 151 Ω per neutral. Earth-fault currents fall 43–62%, three-phase levels unchanged, but the earth-fault factor rises from 0.92–1.09 to 1.32–1.36 and relay margin falls 39% — not recommended at 220 kV
Challenge 3Losing an Earthing Point

Transformer 2's neutral connection is opened for maintenance, leaving transformer 1 as the system's only earth. Recompute the zero-sequence driving-point impedances and the earth-fault currents at all five buses, and assess whether the system may be operated in this state.

The change to the network is a single deleted shunt:

\[ Y_{0,22} \to Y_{0,22} - \frac{1}{j0.08} \]

Nothing else moves. The positive- and negative-sequence networks are untouched, so all three-phase and line-to-line fault levels are exactly as before. Only the zero-sequence network — and therefore only the earth faults — changes.

Re-inverting the zero-sequence Y-bus:

Bus\(Z_{0,kk}\) beforeafterIncrease
1j0.06985j0.10000×1.43
2j0.06071j0.25171×4.15
3j0.23047j0.36743×1.59
4j0.23838j0.38543×1.62
5j0.31714j0.49286×1.55

Note \(Z_{0,11}\) becomes exactly \(j0.10000\) — the transformer's own reactance, since no other path to reference exists and every line beyond bus 1 now leads to a dead end. That exact result is a useful check that the modification was applied correctly.

The new earth-fault currents:

Bus\(X_0/X_1\)\(I_{LG}\) beforeafterChange\(I_{3\phi}\)
10.7999.37098.5644−8.6%7.9909
22.0969.97056.0988−38.8%8.3270
32.1145.19014.1960−19.2%5.7546
42.1805.06774.0593−19.9%5.6560
52.4094.13073.3260−19.5%4.8884

Bus 2 loses nearly 40% — unsurprising, since its own earthing point is the one removed. Bus 1 barely changes, because it keeps its own. The remote buses lose about 20% each.

A structural change worth noting: bus 2 has crossed the \(X_0/X_1 = 1\) line.

\[ \text{bus 2:} \quad X_0/X_1 : 0.506 \to 2.096 \qquad I_{LG}/I_{3\phi} : 1.197 \to 0.732 \]

Bus 2 has changed from a bus where the earth fault governs to one where the three-phase fault does. Only bus 1 now has \(X_0/X_1 < 1\). Any breaker rating study performed for this configuration would reach different conclusions from the normal-configuration one — which is exactly why fault studies are run for every credible switching state, not just the intact network.

Is the system safe to operate this way? Four tests:

TestCriterionResultVerdict
Still earthed?at least one earth pointT1 remainspass
Effectively earthed?\(X_0/X_1 < 3\) everywheremax 2.41 at bus 5pass
Earth-fault factorEFF \(< 1.4\)max 1.192pass
Relay sensitivitymargin preserved−20% at worstreview

The system remains effectively earthed and operable. But the fourth row demands attention: earth-fault relay settings chosen for the intact system have lost 20% of their margin, and any setting relying on the minimum-fault case should be rechecked before the outage is taken.

The unacceptable case, for contrast. Suppose transformer 1's neutral were also opened:

\[ \text{no shunt to reference anywhere} \Rightarrow \mathbf{Y}_0 \text{ is singular} \Rightarrow Z_{0,kk} \to \infty \Rightarrow I_{LG} = 0 \]

Mathematically the zero-sequence Y-bus loses its only connection to the reference node and cannot be inverted; physically the system is unearthed. An earth fault would then draw only capacitive charging current, would not be detected by any overcurrent device, and would drive the healthy phases to \(\sqrt3 = 1.732\) pu indefinitely — with a serious risk of arcing-ground overvoltages reaching 3–5 pu. This is the condition every operating instruction forbids, and the singular matrix is the calculation's own way of telling you so.

The operating rule that this analysis justifies:

\[ \boxed{\ \text{At least one, preferably two, earthing points in service at all times}\ } \]

One is the safety minimum; two provides redundancy and keeps \(X_0/X_1\) low enough that earth faults stay easily detectable. The interlocking that enforces this on a real substation is derived from precisely the calculation above.

Removing an earthing point changes only the zero-sequence network — but that is enough to reverse which fault type governs at a bus, and enough to invalidate relay settings. The singular \(\mathbf{Y}_0\) that appears when the last earth is removed is not a numerical failure; it is the model correctly reporting an unearthed system.
Answer\(Z_0\) diag becomes j[0.10000, 0.25171, 0.36743, 0.38543, 0.49286]; earth-fault currents fall to 8.5644 / 6.0988 / 4.1960 / 4.0593 / 3.3260 pu (−8.6% to −38.8%). The system stays effectively earthed and operable, but earth-fault relay settings must be reviewed
Self-Test

Multiple-Choice Questions

  1. MCQ 1. The most frequent fault type on an overhead transmission system is:
    (a) three-phase   (b) line-to-line   (c) single line-to-earth   (d) double line-to-earth

    Show answer
    (c), at 70–85% of all faults, because the phase-to-earth clearance is the one an insulator string, a tree, or a bird can bridge. The three-phase fault is the rarest at 2–5%. Problem 1.
  2. MCQ 2. For a single line-to-earth fault the three sequence networks are connected:
    (a) in parallel   (b) in series   (c) in parallel opposition   (d) not connected at all

    Show answer
    (b). The conditions \(I_0 = I_1 = I_2\) (equal currents) and \(V_0+V_1+V_2 = I_aZ_f\) (voltages summing) define a series connection. Problem 3.
  3. MCQ 3. The ratio of a solid line-to-line fault current to the three-phase value at the same bus is:
    (a) 0.500   (b) 0.577   (c) 0.866   (d) 1.000

    Show answer
    (c) \(= \sqrt3/2\), and it is universal wherever \(Z_2 = Z_1\) — no network data is needed. Problem 7.
  4. MCQ 4. In a line-to-earth fault, a fault impedance \(Z_f\) appears in the sequence loop as:
    (a) \(Z_f\)   (b) \(2Z_f\)   (c) \(3Z_f\)   (d) \(Z_f/3\)

    Show answer
    (c). The whole fault current \(I_a = 3I_0\) passes through \(Z_f\), while the loop is written in terms of \(I_0\). Same reason a neutral impedance appears as \(3Z_n\). Problem 13.
  5. MCQ 5. A double line-to-earth fault connects the sequence networks so that:
    (a) \(V_0 = V_1 = V_2\)   (b) \(I_0 = I_1 = I_2\)   (c) \(V_1 = V_2, I_0 = 0\)   (d) all voltages are zero

    Show answer
    (a), together with \(I_0+I_1+I_2 = 0\) — the exact dual of the line-to-earth case, hence a parallel rather than a series connection. Problem 9.
  6. MCQ 6. During a solid three-phase fault, the sequence voltages at the fault are:
    (a) \(V_1 = V_2 = V_0 = 0\)   (b) \(V_1 = E\)   (c) \(V_1 = V_2 \ne 0\)   (d) \(V_0 = -E\)

    Show answer
    (a). All three phase voltages are zero, and a zero vector transforms to a zero vector. Consequently \(I_2 = I_0 = 0\). Problem 12.
  7. MCQ 7. A single line-to-earth fault exceeds a three-phase fault at the same bus when:
    (a) \(X_0/X_1 < 1\)   (b) \(X_0/X_1 > 1\)   (c) \(X_0/X_1 > 3\)   (d) never

    Show answer
    (a). The ratio is \(3/(2+X_0/X_1)\), which exceeds unity precisely when \(X_0/X_1 < 1\). True at buses 1 and 2 of the five-bus system. Problem 14.
  8. MCQ 8. The largest possible value of \(I_{LG}/I_{3\phi}\) is:
    (a) 1.0   (b) 1.5   (c) 1.732   (d) unbounded

    Show answer
    (b), approached as \(X_0 \to 0\). A computed ratio above 1.5 always means a data error — usually a delta modelled as an earthed star. Problem 14.
  9. MCQ 9. At \(X_0 = X_1 = X_2\), the four solid fault currents are:
    (a) all different   (b) all equal except line-to-line   (c) all equal   (d) all zero

    Show answer
    (b). Three-phase, line-to-earth and double line-to-earth all give exactly \(E/Z_1\), because the three networks are identical and the connection rule stops mattering. Only the line-to-line fault stays at 0.866. Challenge 1.
  10. MCQ 10. A single line-to-earth fault on the star side of a \(\Delta\!-\!Y_g\) transformer produces delta-side line currents in the ratio:
    (a) 1 : 1 : 1   (b) 1 : 0 : 1   (c) 1 : 0 : 0   (d) 2 : 1 : 1

    Show answer
    (b). Zero sequence is blocked, and the \(\pm30°\) shifts leave \(I_1'\) and \(I_2'\) 60° apart — so one phase carries nothing and the others carry \(\sqrt3 I_1\) in opposition. It looks like a line-to-line fault from that side. Problem 19.
  11. MCQ 11. One open conductor connects the sequence networks across the break:
    (a) in series   (b) in parallel   (c) not at all   (d) in parallel opposition

    Show answer
    (b). The conditions are \(I_a = 0\) and \(V_b = V_c = 0\), giving \(V_0=V_1=V_2\) and \(\sum I = 0\). Two open conductors give the series connection. Problem 18.
  12. MCQ 12. The quantity that best detects a broken conductor is:
    (a) phase overcurrent   (b) residual current \(3I_0\)   (c) the ratio \(I_2/I_1\)   (d) undervoltage

    Show answer
    (c). A series fault raises no current at all — the example gave \(3I_0 = 7\) A — but \(I_2/I_1\) jumps to 0.75 against a healthy value below 0.02, and being a ratio it is independent of loading. Problem 18.
Reference

Key Formulas

The four fault currents, with \(Z_1, Z_2, Z_0\) the driving-point sequence impedances at the faulted bus:

\[ \begin{array}{lll} \text{Three-phase} & I_f = \dfrac{E}{Z_1+Z_f} & I_2 = I_0 = 0 \\[10pt] \text{Line-to-earth} & I_f = \dfrac{3E}{Z_0+Z_1+Z_2+3Z_f} & I_0=I_1=I_2 = I_f/3 \\[10pt] \text{Line-to-line} & I_f = \dfrac{\sqrt3\,E}{Z_1+Z_2+Z_f} & I_0 = 0,\ I_2 = -I_1 \\[10pt] \text{Double line-to-earth} & I_1 = \dfrac{E}{Z_1+Z_2\parallel(Z_0+3Z_g)} & I_g = 3I_0 \end{array} \]

Boundary conditions and network connections:

FaultCurrent conditionVoltage conditionConnection
none\(V_a=V_b=V_c=0\)positive only
L-G\(I_b=I_c=0\)\(V_a=I_aZ_f\)series
L-L\(I_a=0,\ I_b=-I_c\)\(V_b-V_c=I_bZ_f\)parallel opposition
LLG\(I_a=0\)\(V_b=V_c=I_gZ_g\)three-way parallel
1 open\(I_a=0\)\(V_b=V_c=0\)parallel across break
2 open\(I_b=I_c=0\)\(V_a=0\)series across break

Current division for the double line-to-earth fault:

\[ I_2 = -I_1\frac{Z_0}{Z_2+Z_0} \qquad I_0 = -I_1\frac{Z_2}{Z_2+Z_0} \qquad I_0+I_1+I_2 = 0 \]

Severity ratios, valid whenever \(Z_2 = Z_1\) and the fault is solid:

\[ \frac{I_{LL}}{I_{3\phi}} = \frac{\sqrt3}{2} = 0.866 \qquad \frac{I_{LG}}{I_{3\phi}} = \frac{3}{2+X_0/X_1} \qquad \frac{I_{g,LLG}}{I_{3\phi}} = \frac{3}{1+2X_0/X_1} \]
\[ I_{LG} > I_{3\phi} \iff \frac{X_0}{X_1} < 1 \qquad\text{and}\qquad \frac{I_{LG}}{I_{3\phi}} \le \frac{3}{2} \text{ always} \]

Sequence-voltage signatures at the fault:

\[ \begin{array}{lll} 3\phi & V_0 = V_1 = V_2 = 0 & \\ \text{L-G} & V_0+V_1+V_2 = I_aZ_f & \text{(} = 0 \text{ for a solid fault)} \\ \text{L-L} & V_1 = V_2,\quad V_0 = 0 & \\ \text{LLG} & V_0 = V_1 = V_2 & \\ \end{array} \]

Voltages elsewhere in the system, using the off-diagonal sequence Z-bus terms:

\[ V_{1,i} = E - Z_{1,ik}I_1 \qquad V_{2,i} = -Z_{2,ik}I_2 \qquad V_{0,i} = -Z_{0,ik}I_0 \]

for a fault at bus \(k\); then recombine with \(\mathbf{A}\) to get phase quantities. Line flows follow from \(I_{s,ij} = (V_{s,i}-V_{s,j})/z_{s,ij}\).

Crossing a \(\Delta\!-\!Y_g\) transformer (standard \(30°\) displacement):

\[ I_0' = 0 \qquad I_1' = I_1\angle{+30°} \qquad I_2' = I_2\angle{-30°} \]

and for the L-G fault on the star side, the delta-side line currents are \(\sqrt3 I_1 : 0 : \sqrt3 I_1\).

Earthing quantities:

\[ \text{neutral current} = 3I_0 \qquad \text{earth-fault factor} = \frac{|V_{\text{healthy}}|}{|V_{\text{nominal}}|} \le 1.4 \text{ for effective earthing} \]
\[ \text{effectively earthed} \iff \frac{X_0}{X_1} \le 3 \ \text{ and } \ \frac{R_0}{X_1} \le 1 \]
Diagnostics

Common Mistakes

  1. Writing \(Z_f\) rather than \(3Z_f\) in the line-to-earth loop. The whole fault current flows through \(Z_f\) while the loop equation is written in \(I_0\) — Problem 13.

  2. Confusing the phase current with the earth current in a double line-to-earth fault. At bus 3 they are 5.5156 and 4.7265 pu; a breaker is rated on the first, an earth grid on the second — Problem 11.

  3. Assuming the three-phase fault is always the worst. At buses 1 and 2 the earth fault exceeds it by 17% and 20% — Problem 14.

  4. Ranking fault severity without checking \(Z_f\). The ranking at bus 3 inverts between a solid fault and \(Z_f = j0.10\) — Problem 13.

  5. Expecting the healthy phases always to rise. At a stiffly earthed bus with \(X_0 < X_1\) they fall — 0.917 pu at bus 2 — Problems 5 and 20.

  6. Assuming \(I_b = I_c = 0\) in every branch during a line-to-earth fault. That holds only for the total at the fault; transformer 1's branch carried 0.6184 pu in each healthy phase — Problem 19.

  7. Forgetting the \(\pm30°\) shift across a \(\Delta\!-\!Y\) transformer. Positive and negative sequence shift in opposite directions, which is why the delta-side pattern is 1 : 0 : 1 — Problem 19.

  8. Looking for an earth fault with an overcurrent relay on the delta side. \(3I_0 = 0\) there by construction — Problem 19.

  9. Treating an open conductor like a shunt fault. Series faults have their own boundary conditions and are applied across the break, not to earth — Problem 18.

  10. Trying to detect a broken conductor by magnitude. The earth current was 7 A; only the ratio \(I_2/I_1 = 0.75\) reveals it — Problem 18.

  11. Using one earth-fault number for both relay pickup and thermal rating. Sensitivity is set by the minimum credible fault, thermal duty by the maximum — Problem 20.

  12. Running the study for the intact network only. Opening one transformer neutral moved bus 2 from \(X_0/X_1 = 0.506\) to 2.096 and reversed which fault governs — Challenge 3.

Looking Ahead

Part 5 is complete. Symmetrical components turned three coupled phases into three independent networks (Set 21), those networks were built for a real five-bus system (Set 22), and four boundary-condition pairs connected them into the four standard faults (Set 23). Every fault current, every sequence voltage, every line flow and every neutral current in this system is now a number, computed from three Z-bus diagonals and one connection rule.

What the analysis has assumed throughout is that the machines hold their internal EMFs fixed at \(1.0\angle0°\) — that the network's electrical transient is over before the rotors have moved. That assumption is excellent for the first cycle and false by the tenth. Part 6 removes it: Set 24 introduces the swing equation and the equal-area criterion, and asks not how large the fault current is but whether the machines stay in step after the breaker clears. The fault levels computed here become the input to that question, because the depth of the voltage collapse — \(V_1 = 0\) for a three-phase fault, 0.699 for a line-to-earth fault at bus 3 — is exactly what determines how much accelerating power the rotor sees.