Solved Problems · Set 21

Symmetrical Components

Part 5 · Faults — the change of coordinates that turns one unbalanced three-phase problem into three balanced single-phase ones. Chapter 22 of the textbook.

Prof. Mithun Mondal 20 solved · 12 practice · 3 challenge GATE · ESE · University

Set 21 — Symmetrical Components

Twenty worked problems on the transformation that makes unsymmetrical fault analysis possible. Everything in Parts 3 and 4 assumed balance, which let one per-phase circuit stand for three. A single line-to-earth fault destroys that assumption, and a direct three-phase solution of a large network is intractable. Fortescue's theorem resolves any set of three phasors into three balanced sets, each of which can be analysed by the per-phase methods already built — and the three results superposed. The whole of Part 5 rests on this one change of basis.

Textbook Chapter 22 · 20 solved · 12 practice · 3 challenge · 12 MCQs

i Method Recap
  • The operator. \(a = 1\angle120^\circ = -0.5+j0.866\), so \(a^{2} = 1\angle240^\circ\), \(a^{3} = 1\), and — the identity used constantly — \(1 + a + a^{2} = 0\).

  • The transformation. \(\mathbf{V}_{abc} = \mathbf{A}\mathbf{V}_{012}\) with \(\mathbf{A} = \begin{bmatrix}1&1&1\\1&a^{2}&a\\1&a&a^{2}\end{bmatrix}\), and the inverse is \(\mathbf{A}^{-1} = \tfrac{1}{3}\mathbf{A}^{*}\) — no matrix inversion is ever needed.

  • The three sequences. Positive: three equal phasors 120° apart in \(abc\) order. Negative: three equal phasors in \(acb\) order. Zero: three identical phasors, in phase.

  • Zero sequence and the neutral. \(V_0 = \tfrac{1}{3}(V_a+V_b+V_c)\), so zero sequence exists only when the three do not sum to zero — which requires a fourth conductor or an earth return.

  • A balanced set is pure positive sequence. Its \(V_0\) and \(V_2\) are identically zero, which is why every balanced study in Parts 3 and 4 was a positive-sequence study without saying so.

  • Power is invariant in the form \(S = 3\left(V_0I_0^{*} + V_1I_1^{*} + V_2I_2^{*}\right)\). The cross terms vanish, so the three sequences do not exchange power.

  • The sequences decouple in any balanced network — a symmetric impedance matrix is diagonalised by \(\mathbf{A}\) — which is the property that makes the whole method work, and the subject of Set 22.

VideoWalkthrough
Problem 1FoundationThe Operator a

Define the operator \(a\), establish the identities that will be used throughout Part 5, and evaluate \(1-a\), \(a-a^{2}\) and \(a^{2}-a\).

Solution

The definition. \(a\) is the unit phasor that rotates by 120°:

\[ a = 1\angle120^\circ = e^{j2\pi/3} = -\frac{1}{2} + j\frac{\sqrt3}{2} = -0.5 + j0.866 \]

It is to a three-phase system what \(j\) is to a two-phase one: multiplication by \(a\) advances a phasor by a third of a cycle without changing its magnitude.

The powers:

\[ a^{2} = 1\angle240^\circ = 1\angle-120^\circ = -0.5 - j0.866 \qquad a^{3} = 1\angle360^\circ = 1 \]

So \(a^{4} = a\), and every power reduces to one of \(1\), \(a\), \(a^{2}\). Note also \(a^{*} = a^{2}\) and \(1/a = a^{2}\).

The central identity. The three cube roots of unity sum to zero:

\[ 1 + a + a^{2} = 1 + (-0.5+j0.866) + (-0.5-j0.866) = 0 \]

Geometrically, three unit vectors 120° apart. This identity is what makes a balanced set have no zero-sequence component, and it appears in almost every derivation in Part 5.

The three differences, which recur in the fault formulas of Set 23:

\[ 1 - a = 1.5 - j0.866 = \sqrt3\angle-30^\circ \]
\[ a - a^{2} = j1.732 = \sqrt3\angle90^\circ = j\sqrt3 \]
\[ a^{2} - a = -j1.732 = \sqrt3\angle-90^\circ \]

Each has magnitude \(\sqrt3\) — the chord subtending 120° on a unit circle. The \(\sqrt3\) in every line-to-line fault current comes from here.

The complete table, worth memorising:

\[ \begin{array}{lll} a = 1\angle120^\circ & a^{2} = 1\angle240^\circ & a^{3} = 1 \\ 1+a+a^{2} = 0 & a^{*} = a^{2} & 1/a = a^{2} \\ 1-a = \sqrt3\angle-30^\circ & 1-a^{2} = \sqrt3\angle30^\circ & a-a^{2} = j\sqrt3 \\ 1+a = -a^{2} = 1\angle60^\circ & 1+a^{2} = -a = 1\angle-60^\circ & a+a^{2} = -1 \end{array} \]

The last row follows from the central identity by moving one term across. \(1+a = -a^{2}\) is used often enough to be worth recognising directly rather than deriving each time.

\(a\) is a rotation, and every identity above is a statement about equilateral triangles. The three cube roots of unity are the triangle's vertices; their sum is zero because the centroid is the origin; the differences have magnitude \(\sqrt3\) because that is the side of a triangle inscribed in a unit circle. Working with \(a\) algebraically is fast, but the geometry is what makes the results memorable.
Answer\(a = -0.5+j0.866\), \(1+a+a^{2} = 0\); \(1-a = \sqrt3\angle-30^\circ\), \(a-a^{2} = j\sqrt3\), \(a^{2}-a = -j\sqrt3\)
Problem 2Exam levelThe Transformation

State Fortescue's theorem, write the transformation and its inverse, and show that the inverse requires no matrix inversion.

Solution

The theorem. Any set of three phasors can be written as the sum of three balanced sets:

\[ \begin{array}{lll} \text{Positive sequence} & V_{a1},\ a^{2}V_{a1},\ aV_{a1} & abc\ \text{order} \\ \text{Negative sequence} & V_{a2},\ aV_{a2},\ a^{2}V_{a2} & acb\ \text{order} \\ \text{Zero sequence} & V_{a0},\ V_{a0},\ V_{a0} & \text{all in phase} \end{array} \]

Three sets of three phasors, described by three complex numbers — the same information as the original three, re-expressed.

Adding them phase by phase:

\[ V_a = V_{a0} + V_{a1} + V_{a2} \]
\[ V_b = V_{a0} + a^{2}V_{a1} + aV_{a2} \]
\[ V_c = V_{a0} + aV_{a1} + a^{2}V_{a2} \]
\[ \Rightarrow\quad \begin{bmatrix}V_a\\V_b\\V_c\end{bmatrix} = \underbrace{\begin{bmatrix}1&1&1\\1&a^{2}&a\\1&a&a^{2}\end{bmatrix}}_{\mathbf{A}}\begin{bmatrix}V_{a0}\\V_{a1}\\V_{a2}\end{bmatrix} \]

Note the subscript convention: \(V_{a1}\) is phase \(a\)'s positive-sequence component, and the other two phases' components are obtained from it. Only phase \(a\)'s three components are ever tabulated.

The inverse. Because \(\mathbf{A}\) is a Vandermonde matrix of the cube roots of unity, its inverse is its own conjugate over three:

\[ \mathbf{A}^{-1} = \frac{1}{3}\mathbf{A}^{*} = \frac{1}{3}\begin{bmatrix}1&1&1\\1&a&a^{2}\\1&a^{2}&a\end{bmatrix} \]

Verified numerically to \(10^{-16}\). Since \(a^{*} = a^{2}\), conjugating \(\mathbf{A}\) simply swaps its last two columns — so the inverse is written down, never computed.

The resolution formulas, which is how the inverse is actually used:

\[ V_{a0} = \tfrac{1}{3}\left(V_a + V_b + V_c\right) \]
\[ V_{a1} = \tfrac{1}{3}\left(V_a + aV_b + a^{2}V_c\right) \]
\[ V_{a2} = \tfrac{1}{3}\left(V_a + a^{2}V_b + aV_c\right) \]

Why \(\mathbf{A}^{-1} = \mathbf{A}^{*}/3\). The columns of \(\mathbf{A}\) are orthogonal in the Hermitian sense:

\[ \mathbf{c}_1^{*T}\mathbf{c}_2 = 1 + a\cdot a^{2*} + a^{2}\cdot a^{*}\ \text{terms} \ \Rightarrow\ 1+a+a^{2} = 0 \]

And each column has squared norm 3. So \(\mathbf{A}/\sqrt3\) is unitary — which is the deeper reason the transformation preserves power, as Problem 10 shows.

An alternative normalisation uses \(\mathbf{A}/\sqrt3\) throughout, making the transformation exactly unitary and the power expression free of the factor 3. It is mathematically tidier and almost never used, because engineers want \(V_{a1}\) to be a voltage of the same size as \(V_a\).

Symmetrical components is a change of basis, and the basis was chosen so that the network's impedance matrix becomes diagonal. That is the whole trick: a balanced three-phase network has a circulant impedance matrix, every circulant matrix is diagonalised by the discrete Fourier matrix, and \(\mathbf{A}\) is the \(3\times3\) discrete Fourier matrix. Fortescue found it in 1918 without the modern language, and it is exactly a three-point DFT.
Answer\(\mathbf{V}_{abc} = \mathbf{A}\mathbf{V}_{012}\) with \(\mathbf{A}^{-1} = \tfrac{1}{3}\mathbf{A}^{*}\) — the inverse is the conjugate, so no inversion is needed
Problem 3Exam levelResolving a Set

A three-phase system has \(V_a = 200\angle0^\circ\), \(V_b = 200\angle245^\circ\) and \(V_c = 100\angle105^\circ\) V. Find its symmetrical components.

Solution

In rectangular form, noting \(245^\circ = -115^\circ\):

\[ V_a = 200 + j0 \qquad V_b = -84.52 - j181.26 \qquad V_c = -25.88 + j96.59 \]

Zero sequence — simply the average:

\[ V_{a0} = \tfrac{1}{3}(200 - 84.52 - 25.88) + \tfrac{j}{3}(0 - 181.26 + 96.59) \]
\[ = 29.86 - j28.22 = 41.09\angle-43.38^\circ\ \text{V} \]

Non-zero, so this set does not sum to zero and requires a neutral or earth path to exist physically.

Positive sequence. Rotate \(V_b\) forward by 120° and \(V_c\) back by 120°, then average:

\[ aV_b = 200\angle(245+120)^\circ = 200\angle5^\circ \qquad a^{2}V_c = 100\angle(105+240)^\circ = 100\angle345^\circ \]
\[ V_{a1} = \tfrac{1}{3}\left(200\angle0^\circ + 200\angle5^\circ + 100\angle-15^\circ\right) = 165.30\angle-0.98^\circ\ \text{V} \]

The three rotated phasors are nearly aligned — within 20° — which is why the positive-sequence component is large. That near-alignment is the definition of a nearly balanced set.

Negative sequence:

\[ a^{2}V_b = 200\angle(245+240)^\circ = 200\angle125^\circ \qquad aV_c = 100\angle-135^\circ \]
\[ V_{a2} = \tfrac{1}{3}\left(200\angle0^\circ + 200\angle125^\circ + 100\angle-135^\circ\right) = 31.42\angle81.10^\circ\ \text{V} \]

Here the three are spread over 225° and largely cancel, leaving a small residue.

The three components:

\[ \begin{array}{lcc} \text{Sequence} & \text{Magnitude (V)} & \text{Angle} \\ \hline \text{Zero} & 41.09 & -43.38^\circ \\ \text{Positive} & 165.30 & -0.98^\circ \\ \text{Negative} & 31.42 & +81.10^\circ \end{array} \]

The immediate reading. Positive sequence dominates at 165 V, so the system is recognisably three-phase; but 41 V of zero sequence and 31 V of negative sequence are 25% and 19% of it, which is a severe unbalance. Problem 15 quantifies that judgement.

The arithmetic is three weighted averages, and the weights are rotations. Each sequence component asks the same question — "how much of this pattern is present?" — by rotating the three phasors into alignment for that pattern and averaging. A phasor set that is already aligned under one rotation gives a large answer for that sequence and near-zero for the others, which is exactly what a filter does.
Answer\(V_{a0} = 41.09\angle-43.38^\circ\), \(V_{a1} = 165.30\angle-0.98^\circ\), \(V_{a2} = 31.42\angle81.10^\circ\) V
Problem 4FoundationReconstruction

Reconstruct the three phase voltages from the components found in Problem 3, and write out all nine phasors of the three balanced sets.

Solution

The nine phasors, three from each sequence:

\[ \begin{array}{lccc} & \text{Phase } a & \text{Phase } b & \text{Phase } c \\ \hline \text{Zero} & 41.09\angle-43.4^\circ & 41.09\angle-43.4^\circ & 41.09\angle-43.4^\circ \\ \text{Positive} & 165.30\angle-1.0^\circ & 165.30\angle-121.0^\circ & 165.30\angle119.0^\circ \\ \text{Negative} & 31.42\angle81.1^\circ & 31.42\angle-158.9^\circ & 31.42\angle-38.9^\circ \end{array} \]

The zero-sequence row is three identical phasors; the positive row is \(abc\); the negative row is \(acb\) — read the angles: \(81.1 \to -158.9 \to -38.9\) is clockwise.

Adding down the columns. Phase \(a\):

\[ V_a = 41.09\angle-43.4^\circ + 165.30\angle-1.0^\circ + 31.42\angle81.1^\circ \]
\[ = (29.86 - j28.22) + (165.28 - j2.82) + (4.86 + j31.04) = 200.00 + j0.00 \]

Exactly the original \(200\angle0^\circ\). The imaginary parts cancel to four decimals.

Phases \(b\) and \(c\), by the same addition:

\[ V_b = 200.00\angle-115.00^\circ \qquad V_c = 100.00\angle105.00^\circ \]

Both recovered exactly. The transformation is exact and reversible — nothing was approximated.

The nine phasors carry no more information than the three. Nine complex numbers appear, but they are generated by three: each row is determined by its phase-\(a\) entry. That is why only \(V_{a0}\), \(V_{a1}\) and \(V_{a2}\) are ever tabulated, and why the subscript \(a\) is usually dropped once the convention is established.

A useful check. Sum the three phase voltages:

\[ V_a + V_b + V_c = 3V_{a0} = 89.59 - j84.67 \]

Because the positive and negative rows each sum to zero across the phases (\(1+a+a^{2} = 0\) again), and the zero row sums to \(3V_{a0}\). This is the fastest check on any resolution.

And the geometric picture. Three phasor diagrams — one balanced \(abc\) star, one balanced \(acb\) star, one set of three parallel arrows — superposed vertex to vertex give the original unbalanced star. Drawing it once is worth more than the algebra for understanding what the method claims.

The reconstruction is where the method's honesty shows: nothing is lost and nothing is approximated. Three complex numbers in, three out, and the round trip is exact. Symmetrical components is not a simplification of the problem but a re-description of it — and the simplification comes later, when the network turns out to treat each of the three descriptions independently.
AnswerAll three phase voltages recovered exactly; \(V_a+V_b+V_c = 3V_{a0} = 89.59-j84.67\), the fastest check available
Problem 5AnalysisZero Sequence

Explain the physical meaning of the zero-sequence component, state the conditions under which it can exist, and relate it to the neutral current.

Solution

What it is. Three identical phasors — same magnitude, same angle, in all three phases:

\[ I_{a0} = I_{b0} = I_{c0} \]

Not a rotating set at all. The three currents flow in the same direction at the same instant, which is a fundamentally different thing from a three-phase quantity.

The consequence for the neutral. The neutral carries the sum:

\[ I_n = I_a + I_b + I_c = 3I_{a0} \]

The positive and negative sequences contribute nothing to it, by \(1+a+a^{2}=0\). The neutral current is exactly three times the zero-sequence current, which is both the physical meaning of zero sequence and the way it is measured.

When it can exist. Zero-sequence current needs a return path, so:

\[ \begin{array}{lll} \text{Star, earthed neutral} & \text{zero sequence flows} & \text{through the earth or neutral} \\ \text{Star, isolated neutral} & I_0 = 0 & \text{no return path} \\ \text{Delta} & I_0 \text{ circulates inside} & \text{never appears in the lines} \\ \text{Three-wire system} & I_0 = 0 & \text{by Kirchhoff at the source} \end{array} \]

A three-wire three-phase circuit cannot carry zero-sequence current, however unbalanced it is. That is a topological fact and not an approximation.

Zero-sequence voltage is different. It can exist wherever the three phase-to-earth voltages do not sum to zero — which happens during any earth fault, whether or not any zero-sequence current flows. An unearthed system develops large zero-sequence voltage on an earth fault and no zero-sequence current at all.

Why the impedance is different. Zero-sequence current returns through the earth or the neutral, so it sees a completely different circuit:

\[ \begin{array}{ll} \text{Positive/negative} & \text{return through the other two phases} \\ \text{Zero} & \text{return through earth, sheath, earth wire} \end{array} \]

Hence \(x_0 \approx 3x_1\) for an overhead line — a larger loop area and a resistive earth path. Set 22 develops this.

And the practical importance. Zero-sequence current is the signature of an earth fault, so measuring \(3I_0\) — by summing the three phase currents in a core-balance transformer, or by residually connecting three CTs — gives earth-fault protection that is inherently blind to load, to phase faults, and to balanced conditions. It is the most selective protection principle available.

The zero sequence is where the earth enters the analysis, and it is the only sequence that knows the earth exists. Positive and negative sequence describe currents that circulate among the three phases; zero sequence describes current that leaves the three-phase system altogether. That is why its impedance is unrelated to the others, why transformer connections govern it, and why every earth-fault question in Part 5 turns on the zero-sequence network alone.
AnswerThree identical in-phase quantities; \(I_n = 3I_{a0}\), so zero-sequence current requires an earth or neutral return and is zero in any three-wire system
Problem 6FoundationA Balanced Set

Resolve the balanced set \(100\angle0^\circ\), \(100\angle-120^\circ\), \(100\angle120^\circ\) and state what the result implies for every study in Parts 3 and 4.

Solution

Zero sequence is the average, and the three phasors are 120° apart:

\[ V_{a0} = \tfrac{1}{3}\left(100\angle0^\circ + 100\angle-120^\circ + 100\angle120^\circ\right) = \tfrac{100}{3}(1 + a^{2} + a) = 0 \]

Positive sequence — the rotations align all three:

\[ V_{a1} = \tfrac{1}{3}\left(100\angle0^\circ + 100\angle0^\circ + 100\angle0^\circ\right) = 100\angle0^\circ \]

Because \(aV_b = a\cdot a^{2}V_a = V_a\) and \(a^{2}V_c = a^{2}\cdot aV_a = V_a\). The whole set is positive sequence.

Negative sequence:

\[ V_{a2} = \tfrac{1}{3}\left(100\angle0^\circ + 100\angle120^\circ + 100\angle-120^\circ\right) = 0 \]

The result:

\[ V_{a0} = 0 \qquad V_{a1} = 100\angle0^\circ \qquad V_{a2} = 0 \]

A balanced \(abc\) set is pure positive sequence, with the positive-sequence component equal to the phase-\(a\) phasor itself.

The implication for everything before this set. Every calculation in Parts 3 and 4 assumed balance, so every one of them was a positive-sequence calculation:

\[ \begin{array}{ll} \text{The per-phase equivalent circuits} & \text{positive-sequence circuits} \\ \text{The line impedances } z = r+jx & \text{positive-sequence impedances} \\ \mathbf{Y}_{\text{bus}},\ \mathbf{Z}_{\text{bus}} & \text{positive-sequence networks} \\ \text{The load flow} & \text{a positive-sequence solution} \\ \text{The three-phase fault of Set 18} & \text{positive sequence only} \end{array} \]

The subscript 1 was omitted throughout because there was nothing to distinguish it from.

And that is why a three-phase fault is easy. A symmetrical fault applied to a balanced system leaves it balanced, so only the positive sequence is excited and the whole analysis of Set 18 needs one network. Every unsymmetrical fault excites all three, which is the subject of Set 23.

The converse check. If a resolution gives non-zero \(V_0\) or \(V_2\) for a set believed balanced, either the set is not balanced or the arithmetic is wrong. On measured data it is usually the former — real systems carry 0.5–2% negative sequence at all times.

The name "positive sequence" is a historical accident that has become a definition: it means "the balanced part", and every classical power-system quantity is a positive-sequence quantity. Synchronous reactance, surge impedance, the load flow, the stability limit — all are defined for balanced operation and all carry an implicit subscript 1. Making that subscript explicit is the first thing Part 5 does, and the last thing most of the subject needs.
Answer\(V_{a0} = V_{a2} = 0\) and \(V_{a1} = 100\angle0^\circ\) — so every balanced study in Parts 3 and 4 was a positive-sequence study
Problem 7FoundationReversed Sequence

Resolve the balanced set with reversed phase sequence — \(100\angle0^\circ\), \(100\angle120^\circ\), \(100\angle-120^\circ\) — and explain what a negative-sequence voltage does to a machine.

Solution

By the same three averages:

\[ V_{a0} = 0 \qquad V_{a1} = 0 \qquad V_{a2} = 100\angle0^\circ \]

Pure negative sequence — the exact mirror of Problem 6.

The physical distinction. Both sets are balanced; they differ only in the order in which the phases reach their maxima:

\[ \begin{array}{ll} abc\ \text{order} & \text{positive sequence} \\ acb\ \text{order} & \text{negative sequence} \end{array} \]

Interchanging any two phases converts one into the other, which is why swapping two leads reverses a motor.

What it does in a machine. A balanced three-phase set produces a rotating magnetic field, and the direction of rotation follows the sequence:

\[ \begin{array}{ll} \text{Positive sequence} & \text{field rotates at } +\omega_s \\ \text{Negative sequence} & \text{field rotates at } -\omega_s \end{array} \]

So a negative-sequence voltage applied to a machine running forward produces a field rotating backwards at synchronous speed — a relative speed of \(2\omega_s\) with respect to the rotor.

The consequences, and they are severe:

\[ \begin{array}{ll} \text{Rotor currents at } 2f & 100\ \text{Hz in a 50 Hz machine} \\ \text{Double-frequency heating} & \text{in the rotor surface, damper bars, wedges} \\ \text{Skin effect} & \text{concentrates the current, worsening the heating} \\ \text{Pulsating torque at } 2f & \text{vibration and shaft fatigue} \\ \text{Braking torque} & \text{a small net retarding effect} \end{array} \]

The standard limits reflect how little is tolerable:

\[ \begin{array}{ll} \text{Continuous } I_2 & 5\text{--}10\%\ \text{of rating for a turbogenerator} \\ \text{Short-time} & I_2^{2}t \le 6\text{--}30\ \text{(per unit, seconds)} \\ \text{Induction motors} & \text{derate sharply above 2\% voltage unbalance} \end{array} \]

The \(I_2^{2}t\) criterion is a thermal one, exactly like a fuse's \(I^{2}t\), and negative-sequence protection is set from it.

Why the machine's negative-sequence impedance is low. Because the field rotates against the rotor at \(2\omega_s\), the flux cannot penetrate — the damper windings and rotor body screen it, exactly as they do during the subtransient period. Hence

\[ x_2 \approx x''_d \approx 0.15\text{--}0.25\ \text{pu} \]

against a synchronous reactance of 1.0 to 2.0. A small negative-sequence voltage therefore drives a large negative-sequence current, which is why the limits are expressed in current.

Negative sequence is the component that machines cannot tolerate, and its effects are thermal rather than electrical. A 5% negative-sequence voltage causes no visible problem in the network and can destroy a turbogenerator's rotor in minutes. That asymmetry — harmless to the network, dangerous to the plant — is why negative-sequence protection exists as a separate relay function and why the sequence is worth isolating at all.
AnswerPure negative sequence, \(V_{a2} = 100\angle0^\circ\); it produces a backward-rotating field, double-frequency rotor heating, and \(x_2 \approx x''_d\)
Problem 8AnalysisZero Sequence in a Delta

Show that zero-sequence current cannot appear in the lines of a delta-connected element, and explain what happens to it inside.

Solution

The line currents of a delta are differences of phase currents:

\[ I_A = I_{ab} - I_{ca} \qquad I_B = I_{bc} - I_{ab} \qquad I_C = I_{ca} - I_{bc} \]

Their sum telescopes to zero:

\[ I_A + I_B + I_C = (I_{ab}-I_{ca}) + (I_{bc}-I_{ab}) + (I_{ca}-I_{bc}) = 0 \]
\[ \Rightarrow\quad I_{A0} = \tfrac{1}{3}(I_A+I_B+I_C) = 0 \]

Identically, whatever the phase currents are. There is no assumption of balance anywhere in this derivation.

But the phase currents may have a zero-sequence component. Resolving them:

\[ I_{ab0} = \tfrac{1}{3}\left(I_{ab}+I_{bc}+I_{ca}\right) \]

This need not be zero. A zero-sequence current can circulate around the closed delta — it simply cannot get out.

The delta is a zero-sequence trap. It presents two faces:

\[ \begin{array}{ll} \text{Seen from the lines} & \text{an open circuit to zero sequence} \\ \text{Seen from inside} & \text{a closed path in which } I_0 \text{ circulates} \end{array} \]

Both statements are needed. The first governs the zero-sequence network's connectivity; the second explains why a delta winding carries current during an earth fault elsewhere.

The consequences in transformers, which Set 22 develops:

\[ \begin{array}{lll} \Delta\text{--}\Delta & \text{no zero-sequence path either side} \\ \Delta\text{--}Y_{\text{earthed}} & \text{path on the } Y \text{ side; the } \Delta \text{ provides the return} \\ Y\text{--}Y\ \text{both earthed} & \text{zero sequence passes through} \\ Y_{\text{isolated}}\text{--}\Delta & \text{no path on either side} \end{array} \]

The delta winding of a \(\Delta\)\(Y\) transformer is what allows earth-fault current to flow on the star side, by providing somewhere for the zero-sequence ampere-turns to balance.

The same argument applies to triple harmonics. Third harmonics in a three-phase system are in phase in all three phases — they are a zero-sequence set — so a delta winding traps them exactly as it traps fundamental zero sequence. That is why transformer designers include a delta tertiary even where the main windings are both star.

The delta connection is the single most consequential element in zero-sequence analysis, and its effect is entirely topological. It blocks zero sequence from the lines and provides a circulating path within — so a transformer's winding connection, not its impedance, determines whether earth-fault current can flow. Two transformers with identical ratings and reactances give completely different earth-fault levels if their connections differ.
Answer\(I_A+I_B+I_C = 0\) identically, so \(I_{A0} = 0\) in the lines; zero sequence circulates inside the closed delta instead
Problem 9AnalysisStar with Earthed Neutral

A star-connected load has its neutral earthed through an impedance \(Z_n\). Show how \(Z_n\) enters the zero-sequence circuit and explain the factor of three.

Solution

The neutral current is the sum of the three phase currents:

\[ I_n = I_a + I_b + I_c = 3I_{a0} \]

The neutral-point voltage rise:

\[ V_n = I_nZ_n = 3I_{a0}Z_n \]

The neutral is displaced from earth potential by this amount whenever zero-sequence current flows.

Writing phase \(a\)'s loop from the phase terminal through the load to the neutral and thence to earth:

\[ V_a = I_aZ_{\text{load}} + V_n = I_aZ_{\text{load}} + 3I_{a0}Z_n \]

And resolving, the zero-sequence part of this equation is

\[ V_{a0} = I_{a0}Z_{\text{load},0} + 3I_{a0}Z_n = I_{a0}\left(Z_{\text{load},0} + 3Z_n\right) \]

The neutral impedance appears as \(3Z_n\) in the zero-sequence circuit, and only there — the positive- and negative-sequence equations contain no \(V_n\) term, because those currents sum to zero at the neutral and produce no displacement.

Where the three comes from. Two separate factors of the same origin:

\[ \begin{array}{ll} I_n = 3I_{a0} & \text{three phases' worth of current in one conductor} \\ \text{Per-phase circuit carries } I_{a0} & \text{so the impedance must be tripled} \end{array} \]

The zero-sequence network is a per-phase circuit carrying \(I_{a0}\), but the physical neutral carries \(3I_{a0}\). To produce the correct voltage drop with a third of the current, the impedance must be three times as large.

The three cases:

\[ \begin{array}{lll} Z_n = 0 & \text{solidly earthed} & \text{no addition; largest earth-fault current} \\ Z_n\ \text{finite} & \text{impedance earthed} & 3Z_n\ \text{in the zero-sequence path} \\ Z_n = \infty & \text{isolated neutral} & \text{no zero-sequence path at all} \end{array} \]

The middle case is a design choice: a neutral earthing resistor sized to limit earth-fault current to, say, 400 A is standard in industrial and generator-connection practice.

A worked instance. A generator with \(x_0 = 0.06\) pu earthed through a reactor of \(0.05\) pu appears in the zero-sequence network as

\[ x_0 + 3x_n = 0.06 + 3(0.05) = 0.21\ \text{pu} \]

More than tripling the machine's own zero-sequence reactance — which is exactly the intended effect.

The factor of three is the commonest single error in unsymmetrical fault analysis, and it has a physical rather than an algebraic explanation. The sequence networks are per-phase circuits; the neutral is not a per-phase conductor. Anywhere a physical element carries the sum of the three phase currents rather than one of them, its impedance is tripled on entering the zero-sequence network — and nowhere else.
Answer\(Z_n\) appears as \(3Z_n\) in the zero-sequence network only, because that network carries \(I_{a0}\) while the neutral carries \(3I_{a0}\)
Problem 10Challenge-litePower

Show that the complex power in a three-phase system is \(S = 3\left(V_0I_0^{*}+V_1I_1^{*}+V_2I_2^{*}\right)\), and verify it on a numerical example.

Solution

The starting point is the definition in phase quantities:

\[ S = V_aI_a^{*} + V_bI_b^{*} + V_cI_c^{*} = \mathbf{V}_{abc}^{T}\mathbf{I}_{abc}^{*} \]

Substituting the transformation:

\[ S = \left(\mathbf{A}\mathbf{V}_{012}\right)^{T}\left(\mathbf{A}\mathbf{I}_{012}\right)^{*} = \mathbf{V}_{012}^{T}\,\mathbf{A}^{T}\mathbf{A}^{*}\,\mathbf{I}_{012}^{*} \]

The middle product is the key. \(\mathbf{A}\) is symmetric, so \(\mathbf{A}^{T} = \mathbf{A}\), and:

\[ \mathbf{A}\mathbf{A}^{*} = \begin{bmatrix}1&1&1\\1&a^{2}&a\\1&a&a^{2}\end{bmatrix}\begin{bmatrix}1&1&1\\1&a&a^{2}\\1&a^{2}&a\end{bmatrix} = 3\mathbf{I} \]

Every diagonal entry is \(1+1+1 = 3\); every off-diagonal is a sum of the form \(1+a+a^{2} = 0\). That single identity does all the work.

Hence:

\[ S = 3\,\mathbf{V}_{012}^{T}\mathbf{I}_{012}^{*} = 3\left(V_{a0}I_{a0}^{*} + V_{a1}I_{a1}^{*} + V_{a2}I_{a2}^{*}\right) \]

No cross terms. Positive-sequence voltage and negative-sequence current produce no power between them, and the three sequences are energetically independent.

The numerical check. Take the voltages of Problem 3 with currents \(I_a = 10\angle-30^\circ\), \(I_b = 12\angle-160^\circ\), \(I_c = 8\angle80^\circ\) A. Resolving the currents:

\[ I_{a0} = 0.578\angle-135.0^\circ \quad I_{a1} = 9.966\angle-36.7^\circ \quad I_{a2} = 1.734\angle51.7^\circ \]

Both routes give the same answer:

\[ \begin{array}{ll} \text{From } abc & S = 4154.15 + j3035.15\ \text{VA} \\ \text{From } 012 & S = 4154.15 + j3035.15\ \text{VA} \end{array} \]

Agreeing to twelve significant figures. The transformation is power-invariant in this form.

Two consequences worth stating. The decoupling of power is why a negative-sequence quantity is a pure loss to the system — it carries no useful power in combination with the positive-sequence voltage, only \(V_2I_2^{*}\) with itself. And in a balanced system \(V_0 = V_2 = 0\), so \(S = 3V_1I_1^{*}\) — the familiar per-phase formula, recovered.

The factor 3 is the price of choosing a non-unitary transformation, and the absence of cross terms is the reward for choosing an orthogonal one. Normalising \(\mathbf{A}\) by \(\sqrt3\) would remove the 3 and make the transformation exactly unitary — mathematically preferable and universally rejected, because engineers want the positive-sequence voltage of a balanced 400 kV system to read 400 kV and not 693.
Answer\(\mathbf{A}\mathbf{A}^{*} = 3\mathbf{I}\) gives \(S = 3\sum V_kI_k^{*}\) with no cross terms; verified as \(4154.15+j3035.15\) VA by both routes
Problem 11Exam levelOne Phase Open

Phase \(a\) of a balanced 100 A supply is open-circuited, leaving \(I_a = 0\) and the other two unchanged. Find the sequence currents and interpret them.

Solution

The currents are \(I_a = 0\), \(I_b = 100\angle-120^\circ\), \(I_c = 100\angle120^\circ\) A.

Zero sequence:

\[ I_{a0} = \tfrac{1}{3}\left(0 + 100\angle-120^\circ + 100\angle120^\circ\right) = \tfrac{1}{3}(-100) = 33.33\angle180^\circ\ \text{A} \]

Using \(a+a^{2} = -1\). Non-zero — which requires an earth or neutral return path to be physically possible.

Positive sequence:

\[ I_{a1} = \tfrac{1}{3}\left(0 + a(100\angle-120^\circ) + a^{2}(100\angle120^\circ)\right) = \tfrac{1}{3}(100+100) = 66.67\angle0^\circ\ \text{A} \]

Negative sequence:

\[ I_{a2} = \tfrac{1}{3}\left(0 + a^{2}(100\angle-120^\circ) + a(100\angle120^\circ)\right) = \tfrac{1}{3}(100\angle120^\circ + 100\angle-120^\circ) = 33.33\angle180^\circ \]

The result:

\[ I_{a0} = I_{a2} = 33.33\angle180^\circ\ \text{A} \qquad I_{a1} = 66.67\angle0^\circ\ \text{A} \]

And the check: \(I_{a0}+I_{a1}+I_{a2} = -33.33 + 66.67 - 33.33 = 0 = I_a\), as required.

The relation \(I_{a0} = I_{a2}\) is not a coincidence. The single condition \(I_a = 0\) forces

\[ I_{a0} + I_{a1} + I_{a2} = 0 \]

one equation among three unknowns. The further symmetry of this particular case — \(I_b\) and \(I_c\) equal and opposite about the \(a\) axis — makes \(I_0\) and \(I_2\) equal. A general open phase would not.

The engineering point. An open conductor produces 33 A of negative sequence out of an original 100 A balanced supply — a negative-sequence unbalance of 50% relative to the positive-sequence current. A single broken conductor is one of the most damaging faults for rotating plant, and it draws no fault current at all, so overcurrent protection does not see it. Negative-sequence relays do.

Open-conductor faults are the case that overcurrent protection is blind to and symmetrical components make visible. There is no short circuit, no elevated current, and no voltage collapse — just a large negative-sequence component that cooks every induction motor on the feeder. Detecting it requires a relay that measures a sequence quantity, which is why the transformation is embedded in protection hardware rather than only in analysis.
Answer\(I_{a1} = 66.67\angle0^\circ\) and \(I_{a0} = I_{a2} = 33.33\angle180^\circ\) A — 50% negative-sequence unbalance with no increase in current at all
Problem 12AnalysisOne Phase Reduced

Resolve \(100\angle0^\circ\), \(100\angle-120^\circ\), \(50\angle120^\circ\) and compare with the open-phase case.

Solution

The three components:

\[ I_{a0} = 16.67\angle-60^\circ \qquad I_{a1} = 83.33\angle0^\circ \qquad I_{a2} = 16.67\angle+60^\circ \]

All in amperes. The check: \(16.67\angle-60^\circ + 83.33 + 16.67\angle60^\circ = 8.33-j14.43+83.33+8.33+j14.43 = 100\) ✓.

Comparison with the open-phase case of Problem 11:

\[ \begin{array}{lccc} \text{Case} & |I_1| & |I_2| & |I_2|/|I_1| \\ \hline \text{Balanced} & 100.00 & 0 & 0 \\ \text{Phase } c \text{ halved} & 83.33 & 16.67 & 20\% \\ \text{Phase } a \text{ open} & 66.67 & 33.33 & 50\% \end{array} \]

The unbalance grows linearly with the deficiency: half a phase missing gives 20% negative sequence, a whole phase missing gives 50%.

The general result for one phase scaled. Let phase \(c\) be \(kI\angle120^\circ\) while the other two are full. Then

\[ I_{a1} = \frac{I(2+k)}{3} \qquad I_{a2} = I_{a0}^{*}\ \text{in magnitude} = \frac{I(1-k)}{3} \]
\[ \frac{|I_2|}{|I_1|} = \frac{1-k}{2+k} \]

At \(k = 0.5\) this gives \(0.5/2.5 = 20\%\); at \(k = 0\), \(1/2 = 50\%\). Both confirmed.

The magnitudes of \(I_0\) and \(I_2\) are equal in both cases, and their angles are \(\mp60^\circ\) here and \(180^\circ\) both in Problem 11. Equal magnitudes are a consequence of only one phase being disturbed:

\[ \text{One phase changed by } \Delta \quad\Rightarrow\quad I_{a0},\ I_{a2}\ \text{both change by } \Delta/3 \]

Because the change appears in one entry of the vector, and both the zero and negative rows of \(\mathbf{A}^{-1}\) weight that entry by \(1/3\) in magnitude.

The practical threshold. Standards set 2% negative-sequence voltage as the limit for continuous operation of induction motors, and by the formula above that corresponds to

\[ \frac{1-k}{2+k} = 0.02 \quad\Rightarrow\quad k = 0.941 \]

A 6% reduction in one phase exhausts the entire allowance. That is how tight the unbalance requirement is, and why single-phase loads on three-phase systems are distributed with care.

Unbalance is a much more sensitive quantity than intuition suggests, because the negative-sequence component is a difference of large numbers. A 6% change in one phase voltage — invisible on a meter, well within any voltage tolerance — produces the full 2% negative sequence that standards allow. That amplification is why unbalance limits look so strict and why they are so often exceeded without anyone noticing.
Answer\(I_{a1} = 83.33\), \(|I_{a0}| = |I_{a2}| = 16.67\) A — 20% unbalance from halving one phase, against 50% from losing it
Problem 13AnalysisA Single-Phase Load

A single-phase load draws 100 A from phase \(a\) with a return through earth. Find the sequence currents and state the consequence.

Solution

The currents are \(I_a = 100\angle0^\circ\), \(I_b = I_c = 0\).

All three components follow immediately, since only one term survives each sum:

\[ I_{a0} = I_{a1} = I_{a2} = \tfrac{1}{3}(100) = 33.33\angle0^\circ\ \text{A} \]

Equal in magnitude and in phase. This is the most unbalanced condition possible, and its sequence signature is the simplest.

The check:

\[ I_a = 33.33+33.33+33.33 = 100 \quad\checkmark \]
\[ I_b = 33.33(1 + a^{2} + a) = 0 \quad\checkmark \qquad I_c = 33.33(1+a+a^{2}) = 0 \quad\checkmark \]

The identity \(1+a+a^{2}=0\) does the work of cancelling phases \(b\) and \(c\) — which is exactly what "three balanced sets superpose to give a single-phase current" means.

The consequence for the network. The negative-sequence current equals the positive-sequence current — a 100% unbalance factor, the theoretical maximum. A single-phase load of any size therefore imposes negative-sequence current of a third of it on every machine in the vicinity.

Which is why single-phase traction is a problem. A 25 kV AC railway takes a single-phase load of tens of megawatts from a three-phase transmission system:

\[ \begin{array}{ll} \text{Naive connection} & 100\%\ \text{unbalance at the feeding point} \\ \text{Rotated connections} & \text{successive substations on different phase pairs} \\ \text{Scott or Le Blanc transformer} & \text{splits into two balanced-ish phases} \\ \text{Static balancer} & \text{Steinmetz circuit: } L \text{ and } C \text{ on the other two} \end{array} \]

All four are used. The Steinmetz balancer is the elegant one: a capacitor and an inductor of correctly chosen size across the other two phase pairs make a single-phase resistive load appear balanced to the supply.

The same result applies to a single line-to-earth fault, where \(I_b = I_c = 0\) at the fault point by definition. Set 23 will use exactly this: \(I_{a0} = I_{a1} = I_{a2}\) is the boundary condition that determines the connection of the three sequence networks.

The single-phase case gives the simplest possible sequence signature — all three components equal — and it is the boundary condition of the commonest fault there is. That an earth fault and a single-phase load are indistinguishable in sequence terms is not a defect of the method; it is a statement that the network cannot tell them apart either, which is why earth-fault protection on a system with single-phase loads is set above the load unbalance.
Answer\(I_{a0} = I_{a1} = I_{a2} = 33.33\angle0^\circ\) A — 100% unbalance, and the same boundary condition as a single line-to-earth fault
Problem 14Exam levelA Line-to-Line Fault

During a line-to-line fault between phases \(b\) and \(c\), the currents are \(I_a = 0\) and \(I_b = -I_c = 100\angle-90^\circ\) A. Find the sequence currents and identify the relation between them.

Solution

Zero sequence is the average, and \(I_b = -I_c\):

\[ I_{a0} = \tfrac{1}{3}\left(0 + I_b - I_b\right) = 0 \]

Exactly zero, which is the defining feature of a fault not involving earth. No earth path is required and none exists.

Positive sequence:

\[ I_{a1} = \tfrac{1}{3}\left(0 + aI_b + a^{2}(-I_b)\right) = \tfrac{I_b}{3}\left(a - a^{2}\right) = \frac{j\sqrt3}{3}I_b = \frac{I_b}{\sqrt3}\angle90^\circ \]
\[ = \frac{100\angle-90^\circ}{\sqrt3}\angle90^\circ = 57.74\angle0^\circ\ \text{A} \]

The \(a-a^{2} = j\sqrt3\) identity of Problem 1, doing the work it was tabulated for.

Negative sequence:

\[ I_{a2} = \tfrac{1}{3}\left(0 + a^{2}I_b + a(-I_b)\right) = \frac{I_b}{3}\left(a^{2}-a\right) = -I_{a1} = 57.74\angle180^\circ\ \text{A} \]

The result, and the relation:

\[ I_{a0} = 0 \qquad I_{a1} = -I_{a2} = 57.74\angle0^\circ\ \text{A} \]

Two conditions — \(I_0 = 0\) and \(I_1 = -I_2\) — which is exactly what determines how the sequence networks connect for this fault type in Set 23: positive and negative in parallel opposition, zero not connected.

The \(\sqrt3\) and its inverse. Note that \(|I_b| = \sqrt3|I_{a1}|\). The fault current in the faulted phases is \(\sqrt3\) times the positive-sequence component, which is why the standard line-to-line fault formula reads

\[ I_f = \frac{\sqrt3\,E}{Z_1+Z_2} \]

rather than \(E/(Z_1+Z_2)\). The \(\sqrt3\) is geometric, from the chord subtending 120°.

And the comparison with a three-phase fault. With \(Z_1 = Z_2\), as is nearly true for a network of lines:

\[ \frac{I_{LL}}{I_{3\phi}} = \frac{\sqrt3E/(2Z_1)}{E/Z_1} = \frac{\sqrt3}{2} = 0.866 \]

A line-to-line fault draws 87% of the three-phase current — which is why the three-phase case is the switchgear rating case, and why the line-to-line case is rarely the binding one.

Every unsymmetrical fault reduces to two statements in sequence quantities, and those two statements dictate how three separate networks are wired together. Here they are \(I_0 = 0\) and \(I_1 = -I_2\); for an earth fault they are \(I_0 = I_1 = I_2\). The whole of Set 23 is the systematic derivation of those pairs and the interconnections they imply — and the arithmetic afterwards is a single series or parallel combination.
Answer\(I_{a0} = 0\) and \(I_{a1} = -I_{a2} = 57.74\angle0^\circ\) A; the faulted-phase current is \(\sqrt3\) times the positive-sequence component
Problem 15DesignUnbalance Factors

Define the voltage unbalance factors, evaluate them for the set of Problem 3, and compare with the simpler NEMA definition.

Solution

The true definitions, as used in IEC standards:

\[ \text{VUF}_2 = \frac{|V_2|}{|V_1|}\times100\% \qquad \text{VUF}_0 = \frac{|V_0|}{|V_1|}\times100\% \]

Two separate factors, because the two sequences do different damage: negative sequence heats rotors, zero sequence flows in neutrals and earths.

For the set of Problem 3\(V_0 = 41.09\), \(V_1 = 165.30\), \(V_2 = 31.42\) V:

\[ \text{VUF}_2 = \frac{31.42}{165.30} = 19.01\% \qquad \text{VUF}_0 = \frac{41.09}{165.30} = 24.86\% \]

Both enormous. A 2% negative-sequence factor is the normal continuous limit, so this system is nearly ten times over.

The NEMA definition avoids the transformation entirely, using only the three line-voltage magnitudes:

\[ \text{NEMA} = \frac{\text{maximum deviation from the average}}{\text{average}}\times100\% \]
\[ |V_{ab}| = 337.36,\ |V_{bc}| = 283.97,\ |V_{ca}| = 245.67 \quad\Rightarrow\quad \text{avg} = 289.00 \]
\[ \text{NEMA} = \frac{337.36-289.00}{289.00} = 16.73\% \]

The two disagree, and systematically:

\[ \begin{array}{lc} \text{VUF}_2\ \text{(true)} & 19.01\% \\ \text{NEMA (magnitudes only)} & 16.73\% \end{array} \]

NEMA uses magnitudes and ignores the angles, so it cannot detect an unbalance in which the three magnitudes are equal but the angles are not 120° apart. Such a set has zero NEMA unbalance and a substantial \(V_2\).

Which to use. NEMA is a field measurement requiring three voltmeters and no phase information; the VUF requires a phase-coherent measurement and gives the physically meaningful quantity:

\[ \begin{array}{ll} \text{NEMA} & \text{quick, conservative, magnitude-only} \\ \text{VUF} & \text{correct, requires phase measurement} \end{array} \]

Modern instruments compute the VUF directly, and standards have moved to it. NEMA persists because a great deal of field practice and equipment derating data is expressed in it.

The derating consequence. An induction motor's derating factor against negative sequence is steep:

\[ \begin{array}{lc} \text{VUF}_2 & \text{Derating} \\ \hline 1\% & 0.99 \\ 2\% & 0.96 \\ 3\% & 0.90 \\ 5\% & 0.75 \end{array} \]

Because the negative-sequence impedance of a motor is its locked-rotor impedance — a sixth of its running impedance — so 2% of voltage unbalance gives 12% of negative-sequence current.

The factor of six between negative-sequence voltage and negative-sequence current in an induction motor is the reason unbalance limits are so tight. A motor sees a 2% unbalance in voltage as a 12% unbalance in current, and the heating goes as the square — so 2% of voltage unbalance produces 1.4% extra loss and a disproportionate temperature rise concentrated in the rotor. Motors fail from unbalance far more often than from anything the voltage magnitude does.
Answer\(\text{VUF}_2 = 19.01\%\) and \(\text{VUF}_0 = 24.86\%\); NEMA gives 16.73%, lower because it ignores the phase angles
Problem 16DesignMeasuring the Components

Describe how each sequence component is measured in practice, and design a filter that extracts the negative-sequence current from three CT secondaries.

Solution

Zero sequence is trivial to measure, because the summation is physical rather than computational:

\[ 3I_0 = I_a + I_b + I_c \]
\[ \begin{array}{ll} \text{Residual connection} & \text{three CT secondaries paralleled; the sum flows in the relay} \\ \text{Core-balance CT} & \text{all three primary conductors through one core} \end{array} \]

The second is the better one: it measures the true residual with no CT-mismatch error, and its sensitivity can be a few amperes primary. It cannot be used where the conductors are too large to pass through a common core, which is why the residual connection persists at transmission voltages.

Positive and negative sequence need the rotation, which historically meant a phase-shifting network:

\[ I_2 = \tfrac{1}{3}\left(I_a + a^{2}I_b + aI_c\right) \]

Two 120° shifts and a summation. A 120° lag at one frequency is produced by an \(R\)\(C\) or \(R\)\(L\) network, so the classical filter is three impedances and a summing junction.

The classical design, using the identity \(1+a+a^{2}=0\) to eliminate one term. Since \(I_a+I_b+I_c = 3I_0\), and for a three-wire system \(I_0 = 0\):

\[ 3I_2 = I_a + a^{2}I_b + aI_c = (a^{2}-1)I_b + (a-1)I_c \]

Substituting \(I_a = -I_b-I_c\). Only two inputs are needed, and each is multiplied by a constant of magnitude \(\sqrt3\) at \(\mp150^\circ\) and \(\pm150^\circ\).

Realising the shifts. An impedance of \(Z = |Z|\angle\phi\) in the current path converts the current into a voltage rotated by \(\phi\), so two impedances with a 60° angle difference and a summing resistor give the network:

\[ \begin{array}{ll} Z_b = R + j\omega L & \text{leading branch} \\ Z_c = R - j/\omega C & \text{lagging branch} \\ \text{Summing} & V_{\text{out}} \propto I_2\ \text{alone} \end{array} \]

Choosing the element values so that the positive-sequence contribution cancels exactly. Such filters were built with iron-cored reactors and oil-filled capacitors, and were tuned on site.

The frequency problem. A passive filter cancels the positive sequence only at the frequency it was tuned for:

\[ \begin{array}{ll} \text{At } 50\ \text{Hz} & \text{rejection} > 40\ \text{dB} \\ \text{At } 47\ \text{or } 53\ \text{Hz} & \text{rejection falls to } \sim20\ \text{dB} \\ \text{During a disturbance} & \text{frequency excursions produce false output} \end{array} \]

Which mattered: a negative-sequence relay that operated on a frequency excursion was a real nuisance in mid-century practice.

The modern answer is arithmetic. A numerical relay samples the three currents, computes the phasors by a Fourier algorithm over one cycle, and applies \(\mathbf{A}^{-1}\) directly:

\[ \begin{array}{ll} \text{Exact at any frequency} & \text{the algorithm tracks the measured frequency} \\ \text{All three sequences at once} & \text{one matrix multiply} \\ \text{No tuning, no drift} & - \end{array} \]

The transformation that took a cabinet of passive components in 1950 is nine complex multiplications today, and every numerical relay computes all three sequences continuously whether or not it uses them.

Symmetrical components moved from an analytical technique to a measurement, and that transition is why protection is where the theory is most used. A relay that measures \(I_2\) distinguishes an open conductor from a load change; one that measures \(3I_0\) distinguishes an earth fault from a phase fault; one that measures the angle between \(V_2\) and \(I_2\) determines the fault's direction. None of these is available from phase quantities alone.
Answer\(3I_0\) by residual connection or a core-balance CT; \(I_2\) classically by a tuned phase-shifting filter and now by direct computation in a numerical relay
Problem 17DesignNegative-Sequence Heating

A 200 MVA turbogenerator has a continuous negative-sequence capability of 8% and a short-time capability of \(I_2^{2}t = 10\). Find the time it can withstand the unbalance of Problem 11, and set a protection characteristic.

Solution

The unbalance of Problem 11 — one phase open — gave \(I_2 = 33.33\) A against a positive-sequence 66.67 A. In per unit of the machine rating, if the machine was carrying rated current before the break:

\[ I_2 = \frac{33.33}{100} = 0.333\ \text{pu} \]

Taking the original 100 A as rated. That is four times the continuous capability.

The withstand time:

\[ I_2^{2}t = 10 \quad\Rightarrow\quad t = \frac{10}{(0.333)^{2}} = \frac{10}{0.111} = 90\ \text{s} \]

Ninety seconds before rotor damage. Long enough for a relay to act with margin, and far too short for an operator to diagnose the problem.

The withstand characteristic across the range:

\[ \begin{array}{lcc} I_2\ (\text{pu}) & t\ (\text{s}) & \text{Comment} \\ \hline 0.08 & \infty & \text{continuous capability} \\ 0.10 & 1000 & \\ 0.20 & 250 & \\ 0.333 & 90 & \text{one phase open} \\ 0.50 & 40 & \\ 1.00 & 10 & \text{a sustained line-to-line fault} \end{array} \]

A hyperbolic curve in \(I_2^{2}\), exactly like a fuse's characteristic — because it is the same physics, a fixed amount of energy to reach a limiting temperature.

Why \(I_2^{2}t\). The rotor surface loss is proportional to \(I_2^{2}\), and the heating is adiabatic on this timescale — the rotor body cannot conduct the heat away fast enough:

\[ \Delta T \propto \int I_2^{2}\,dt \]

So the limit is on the integral, and a varying \(I_2\) is accumulated rather than compared to a threshold. Numerical relays implement exactly this integral.

The protection setting, in two stages:

\[ \begin{array}{lll} \text{Alarm} & I_2 > 0.06\ \text{pu} & \text{below the continuous capability} \\ \text{Trip} & I_2^{2}t > 8 & 80\%\ \text{of the machine's capability} \\ \text{Definite-time backup} & I_2 > 0.5,\ t > 30\ \text{s} & \text{in case the integral fails} \end{array} \]

The alarm exists because most negative-sequence conditions are external and correctable — a broken conductor, an open pole on a breaker, a large single-phase load — and shutting the machine down is the last resort.

The reset problem. A machine that has absorbed 60% of its \(I_2^{2}t\) capability and then returns to balanced operation cools, but not instantly. A relay that resets its integrator immediately would permit repeated near-limit excursions:

\[ \text{Reset time constant} \approx 4\text{--}10\ \text{minutes} \]

Matching the rotor's thermal time constant. This is a genuine setting, not a detail, and getting it wrong is how machines are damaged by a sequence of individually survivable events.

Negative-sequence protection is a thermal replica of the rotor, and it exists because nothing else in the protection system can see the condition. An open conductor causes no overcurrent, no earth-fault current, no undervoltage and no distance-relay operation. The machine is being destroyed by a quantity that no phase measurement reveals, and only the transformation of Problem 2 makes it visible.
Answer90 seconds at \(I_2 = 0.333\) pu; a two-stage scheme alarming at 0.06 pu and tripping on \(I_2^{2}t > 8\), with a 4–10 minute reset
Problem 18Challenge-liteTransformer Phase Shift

A star–delta transformer shifts the positive-sequence voltage by \(+30^\circ\). Show what it does to the negative sequence, and explain why the two shifts are opposite.

Solution

The physical origin. In a \(Y\)\(\Delta\) transformer, a line-to-neutral voltage on the star side corresponds to a line-to-line voltage on the delta side, and line-to-line leads line-to-neutral by 30°.

For positive sequence. Take the star-side voltages balanced \(abc\) with \(V_a = V\angle0^\circ\). The delta-side line voltage corresponding to phase \(a\) is

\[ V_{ab} = V_a - V_b = V(1-a^{2}) = \sqrt3\,V\angle30^\circ \]

Using \(1-a^{2} = \sqrt3\angle30^\circ\) from Problem 1. The shift is \(+30^\circ\).

For negative sequence, the phase order is reversed, so \(V_b = aV_a\) rather than \(a^{2}V_a\):

\[ V_{ab} = V_a - V_b = V(1-a) = \sqrt3\,V\angle-30^\circ \]

The shift is \(-30^\circ\) — equal and opposite.

The general rule, which follows immediately:

\[ \begin{array}{ll} \text{Positive sequence} & \text{shifted by } +30^\circ\ \text{(or the group's angle)} \\ \text{Negative sequence} & \text{shifted by } -30^\circ\ \text{(the negative of it)} \\ \text{Zero sequence} & \text{no shift; and usually no path} \end{array} \]

And the direction depends on which side is taken as reference: crossing from delta to star reverses both signs. IEC vector groups — Yd1, Yd11 and the rest — encode the angle in units of 30°.

Why opposite. The shift arises from the difference of two phasors 120° apart, and reversing the sequence reverses which of the two leads. Geometrically, the isoceles triangle formed by \(V_a\), \(-V_b\) and their sum is reflected. Algebraically it is the difference between \(1-a^{2}\) and \(1-a\), which are conjugates.

The consequence for fault studies. Currents and voltages on the far side of a transformer must be shifted before they can be combined:

\[ \begin{array}{ll} \text{Fault currents} & \text{a } Y\text{--}\Delta \text{ transformer redistributes them between phases} \\ \text{Distance relays} & \text{must compensate for the group to reach correctly} \\ \text{Differential protection} & \text{the CT connections or the relay must correct the shift} \end{array} \]

A single line-to-earth fault on the delta side appears as a two-phase current pattern on the star side, in the ratio 2:1:1 — a result that comes directly from applying the two opposite shifts and recombining.

And a simplification often used. If the study needs only magnitudes — as most fault-level calculations do — the phase shifts can be ignored entirely, because they affect all quantities on one side of the transformer equally. They matter only when quantities from both sides are combined, which is exactly what protection does.

That the two sequences shift in opposite directions is the reason transformer vector groups matter, and it is invisible in a balanced study. A balanced system has only positive sequence, so a \(30^\circ\) shift is a change of reference and nothing more. Introduce a negative-sequence component and the two are displaced by 60° relative to each other — a real, physical redistribution that determines which phases carry fault current on the far side.
AnswerPositive sequence shifts \(+30^\circ\) and negative sequence \(-30^\circ\), because \(1-a^{2}\) and \(1-a\) are conjugates; zero sequence usually has no path at all
Problem 19Challenge-liteA Change of Basis

Show that \(\mathbf{A}\) diagonalises the impedance matrix of any balanced three-phase element, and identify the eigenvalues.

Solution

A balanced element's impedance matrix has equal self-impedances and equal mutual impedances:

\[ \mathbf{Z}_{abc} = \begin{bmatrix} Z_s & Z_m & Z_m \\ Z_m & Z_s & Z_m \\ Z_m & Z_m & Z_s \end{bmatrix} \]

This is a circulant matrix — each row is the previous one rotated. Transposed lines and symmetrically wound machines both produce it.

Transforming. With \(\mathbf{V}_{abc} = \mathbf{Z}_{abc}\mathbf{I}_{abc}\) and \(\mathbf{V}_{abc} = \mathbf{A}\mathbf{V}_{012}\):

\[ \mathbf{V}_{012} = \mathbf{A}^{-1}\mathbf{Z}_{abc}\mathbf{A}\,\mathbf{I}_{012} \quad\Rightarrow\quad \mathbf{Z}_{012} = \mathbf{A}^{-1}\mathbf{Z}_{abc}\mathbf{A} \]

A similarity transformation, so the result has the same eigenvalues as \(\mathbf{Z}_{abc}\).

Carrying it out. Apply \(\mathbf{Z}_{abc}\) to each column of \(\mathbf{A}\). The first column is \([1,1,1]^{T}\):

\[ \mathbf{Z}_{abc}\begin{bmatrix}1\\1\\1\end{bmatrix} = (Z_s+2Z_m)\begin{bmatrix}1\\1\\1\end{bmatrix} \]

An eigenvector, with eigenvalue \(Z_s+2Z_m\).

The second column is \([1, a^{2}, a]^{T}\):

\[ \text{row 1: } Z_s + Z_m(a^{2}+a) = Z_s - Z_m \]

using \(a+a^{2} = -1\); and the other rows give \(a^{2}(Z_s-Z_m)\) and \(a(Z_s-Z_m)\). So it too is an eigenvector, with eigenvalue \(Z_s-Z_m\). The third column gives the same eigenvalue.

The result:

\[ \mathbf{Z}_{012} = \begin{bmatrix} Z_s+2Z_m & 0 & 0 \\ 0 & Z_s-Z_m & 0 \\ 0 & 0 & Z_s-Z_m \end{bmatrix} = \begin{bmatrix} Z_0 & 0 & 0 \\ 0 & Z_1 & 0 \\ 0 & 0 & Z_2 \end{bmatrix} \]
\[ Z_0 = Z_s + 2Z_m \qquad Z_1 = Z_2 = Z_s - Z_m \]

This is the whole justification of the method. The matrix is diagonal, so the three sequences do not interact:

\[ V_0 = Z_0I_0 \qquad V_1 = Z_1I_1 \qquad V_2 = Z_2I_2 \]

Three independent single-phase problems. Everything Part 5 does rests on this diagonalisation, and it holds only because the network is balanced — a fact worth stating clearly, since the method is used to analyse unbalanced conditions.

The apparent paradox, resolved. Symmetrical components requires a balanced network but permits unbalanced conditions. A transposed line is balanced; a fault on it is not. The transformation diagonalises the line and the fault appears as a boundary condition coupling the three networks at one point only — which is precisely the structure Set 23 exploits.

And \(Z_0 \ne Z_1\) follows immediately. The difference is \(3Z_m\), and for an overhead line the mutual impedance between phases is a substantial fraction of the self-impedance because of the shared earth return. Hence \(Z_0 \approx 3Z_1\) — the rule of thumb of Set 22, derived rather than asserted.

Fortescue's transformation is the eigenvector matrix of a circulant, and every circulant of size \(n\) is diagonalised by the \(n\)-point discrete Fourier matrix. Three-phase symmetrical components is the case \(n = 3\). The same construction gives the modal transformations used for travelling-wave analysis on multi-conductor lines and the \(dq0\) transformation of machine theory — all of them changes of basis chosen to make a structured matrix diagonal.
Answer\(\mathbf{Z}_{012}\) is diagonal with \(Z_0 = Z_s+2Z_m\) and \(Z_1 = Z_2 = Z_s-Z_m\) — so the three sequences decouple, and \(Z_0 - Z_1 = 3Z_m\)
Problem 20ChallengeA Complete Resolution

A 400 kV busbar during an earth fault has \(V_a = 20\angle0^\circ\), \(V_b = 235\angle-105^\circ\), \(V_c = 240\angle115^\circ\) kV to earth. Resolve, interpret every component, and identify the fault type.

Solution

The nominal phase voltage for reference:

\[ \frac{400}{\sqrt3} = 230.9\ \text{kV} \]

So phases \(b\) and \(c\) are near normal and phase \(a\) has collapsed to 8.7% of nominal.

Zero sequence:

\[ V_{a0} = \tfrac{1}{3}\left(20\angle0^\circ + 235\angle-105^\circ + 240\angle115^\circ\right) \]
\[ = \tfrac{1}{3}\left[(20) + (-60.82 - j227.00) + (-101.42 + j217.51)\right] = -47.41 - j3.16 \]
\[ = 47.52\angle-176.2^\circ\ \text{kV} \]

Substantial, and roughly in antiphase with the healthy-phase voltages. Zero sequence is present, so the fault involves earth.

Positive sequence. Rotating \(V_b\) by \(+120^\circ\) and \(V_c\) by \(+240^\circ\):

\[ V_{a1} = \tfrac{1}{3}\left(20\angle0^\circ + 235\angle15^\circ + 240\angle-5^\circ\right) = 162.57\angle4.69^\circ\ \text{kV} \]

Depressed to 70% of nominal — the network's positive-sequence voltage pulled down by the fault current, exactly as the fault-study voltage profile of Set 18 described.

Negative sequence:

\[ V_{a2} = \tfrac{1}{3}\left(20\angle0^\circ + 235\angle135^\circ + 240\angle-125^\circ\right) = 95.15\angle-173.88^\circ\ \text{kV} \]

Large — 41% of nominal, and nearly in antiphase with the positive sequence, which is characteristic of a phase-\(a\) earth fault.

The three components:

\[ \begin{array}{lcc} \text{Sequence} & \text{kV} & \text{as \% of nominal} \\ \hline \text{Zero} & 47.52 & 20.6 \\ \text{Positive} & 162.57 & 70.4 \\ \text{Negative} & 95.15 & 41.2 \end{array} \]

The check, in rectangular form:

\[ (-47.42-j3.16) + (162.03+j13.30) + (-94.61-j10.14) = 20.00 + j0.00 \]

Exactly \(V_a\). Note how much cancellation is involved — three quantities of 47, 163 and 95 kV combining to 20 — which is why the resolution must be carried to full precision and why a graphical construction of a faulted phasor set is unreliable.

Identifying the fault. Three observations, in order:

\[ \begin{array}{lll} V_0 \ne 0 & \text{earth is involved} & \text{not a phase-to-phase fault} \\ \text{One phase collapsed} & \text{single line-to-earth} & \text{on phase } a \\ V_2\ \text{large, } \approx 0.6V_1 & \text{a severe fault} & \text{close to this busbar} \end{array} \]

And \(V_0\), \(V_2\) are both nearly in antiphase with \(V_1\) — the signature of an earth fault on phase \(a\), since the three must very nearly cancel there.

The magnitude of \(V_a\) at the fault is 20 kV rather than zero, so the fault is not solid:

\[ V_a = I_fZ_f \quad\Rightarrow\quad Z_f = \frac{20\ \text{kV}}{I_f} \]

With a typical fault current of 15 kA that gives \(Z_f = 1.3\ \Omega\) — consistent with an arc of a metre or two, which is what a 400 kV flashover produces.

The healthy-phase voltages are near normal, at 235 and 240 kV against 231 nominal — a rise of under 4%. That identifies the system as solidly earthed:

\[ \begin{array}{ll} \text{Solidly earthed} & \text{healthy phases rise by } 0\text{--}20\% \\ \text{Resistance earthed} & \text{rise up to } 50\% \\ \text{Isolated or resonant earthed} & \text{healthy phases rise to } \sqrt3 = 173\% \end{array} \]

The ratio of the healthy-phase rise to nominal is the classical earthing-coefficient measurement, and it is read directly from these numbers.

Three voltmeter readings and a phase reference identify the fault type, the faulted phase, the presence of fault impedance and the system's earthing arrangement. None of those four is apparent from the phase quantities alone; all four fall out of the resolution. That is why disturbance recorders store phase quantities and analysis software reports sequence quantities — the transformation is where the diagnosis lives.
Answer\(V_0 = 47.5\), \(V_1 = 162.6\), \(V_2 = 95.2\) kV: a single line-to-earth fault on phase \(a\) through a small impedance, on a solidly earthed system
Practice

Practice Problems

Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not.

  1. P1. Evaluate \(a^{4}\), \(a^{5}\) and \(a^{-1}\).

    Show answer
    \(a^{4} = \mathbf{a}\), \(a^{5} = \mathbf{a^{2}}\), \(a^{-1} = \mathbf{a^{2}}\) — every power reduces modulo 3.
  2. P2. Simplify \(1 + a\) and \(a + a^{2}\).

    Show answer
    \(1+a = \mathbf{-a^{2}} = 1\angle60^\circ\); \(a+a^{2} = \mathbf{-1}\). Both from \(1+a+a^{2}=0\).
  3. P3. A set has \(V_a+V_b+V_c = 60\angle30^\circ\). What is \(V_0\)?

    Show answer
    \(\mathbf{20\angle30^\circ}\) — one third of the sum, always.
  4. P4. A balanced \(acb\) set of 50 V. Give its three components.

    Show answer
    \(V_0 = 0\), \(V_1 = 0\), \(V_2 = \mathbf{50\angle0^\circ}\) — pure negative sequence.
  5. P5. Three CT secondaries are paralleled and 12 A flows in the connection. What is \(I_0\)?

    Show answer
    \(\mathbf{4}\) A. The residual connection measures \(3I_0\).
  6. P6. A generator's neutral is earthed through \(j0.04\) pu. What appears in its zero-sequence circuit?

    Show answer
    \(3Z_n = \mathbf{j0.12}\) pu, in series with the machine's own \(Z_0\) — and in the zero-sequence network only.
  7. P7. Why can zero-sequence current not flow in the lines of a delta?

    Show answer
    The three line currents are differences of phase currents and sum identically to zero. Zero sequence circulates inside the delta instead.
  8. P8. \(V_1 = 240\), \(V_2 = 12\) V. What is the negative-sequence unbalance factor?

    Show answer
    \(12/240 = \mathbf{5\%}\) — well beyond the 2% continuous limit for motors.
  9. P9. A single-phase current of 60 A flows in phase \(b\) only. Give the three components.

    Show answer
    \(I_0 = 20\angle\theta\), \(I_1 = 20\angle(\theta+120^\circ)\), \(I_2 = 20\angle(\theta-120^\circ)\)equal magnitudes, with the rotations that place the sum in phase \(b\).
  10. P10. A machine has \(I_2^{2}t = 12\) and carries \(I_2 = 0.4\) pu. How long can it survive?

    Show answer
    \(12/0.16 = \mathbf{75}\) s.
  11. P11. A \(Y\)\(\Delta\) transformer shifts positive sequence by \(+30^\circ\). What does it do to negative sequence and to zero?

    Show answer
    Negative sequence \(\mathbf{-30^\circ}\); zero sequence has no path through the delta at all.
  12. P12. A balanced line has \(Z_s = j0.5\) and \(Z_m = j0.15\) pu. Find its three sequence impedances.

    Show answer
    \(Z_0 = Z_s+2Z_m = \mathbf{j0.80}\); \(Z_1 = Z_2 = Z_s-Z_m = \mathbf{j0.35}\). Ratio \(Z_0/Z_1 = 2.3\).
Challenge

Challenge Problems

Three problems that push the transformation past the cases it is usually shown on.

  1. C1 — The Steinmetz balancer. A single-phase resistive load of \(P\) watts is connected between phases \(a\) and \(b\) of a balanced supply. Find the reactive elements that must be connected across the other two phase pairs to make the supply see a perfectly balanced three-phase load, and verify that the negative-sequence current vanishes.

    Show answer

    The claim. Connect a capacitor of susceptance \(B_C = G/\sqrt3\) across \(bc\) and an inductor of susceptance \(B_L = G/\sqrt3\) across \(ca\), where \(G\) is the load's conductance. The three delta branches are then

    \[ Y_{ab} = G \qquad Y_{bc} = +j\frac{G}{\sqrt3} \qquad Y_{ca} = -j\frac{G}{\sqrt3} \]

    The verification. With \(V_{ab} = V\angle30^\circ\), \(V_{bc} = V\angle-90^\circ\), \(V_{ca} = V\angle150^\circ\) (balanced line voltages), the branch currents are

    \[ I_{ab} = GV\angle30^\circ \qquad I_{bc} = \frac{GV}{\sqrt3}\angle0^\circ \qquad I_{ca} = \frac{GV}{\sqrt3}\angle60^\circ \]

    and the line currents \(I_A = I_{ab}-I_{ca}\), \(I_B = I_{bc}-I_{ab}\), \(I_C = I_{ca}-I_{bc}\) come out equal in magnitude at \(GV/\sqrt3\) and 120° apart — a balanced \(abc\) set. So \(I_2 = 0\) and \(I_0 = 0\) identically.

    What has happened. The reactive elements consume no average power, so the real power drawn is still \(P\). They circulate reactive power between the phases in exactly the pattern that cancels the negative-sequence component of the single-phase load. Two reactive elements convert a 100%-unbalanced load into a perfectly balanced one at no energy cost.

    The limitation, and it is severe. The balance is exact only at the design load and the design frequency. A load that varies needs a variable balancer — which is what a static var compensator with independent phase control is, and why railway feeder stations use them. A fixed Steinmetz circuit sized for full load makes the unbalance worse at light load.

  2. C2 — When the network is not balanced. An untransposed line has unequal mutual impedances between its three phase pairs. Show that the sequence impedance matrix is no longer diagonal, quantify the coupling for a typical horizontal line, and say what it means for fault analysis.

    Show answer

    The general transformation. With unequal mutuals \(Z_{ab}\), \(Z_{bc}\), \(Z_{ca}\), the matrix \(\mathbf{Z}_{abc}\) is symmetric but not circulant, so \(\mathbf{A}\) does not diagonalise it. Carrying out \(\mathbf{A}^{-1}\mathbf{Z}_{abc}\mathbf{A}\) gives off-diagonal terms of the form

    \[ Z_{01} = \tfrac{1}{3}\left(Z_{ca} + aZ_{ab} + a^{2}Z_{bc}\right)\ \text{-like combinations} \]

    Each is a weighted difference of the three mutuals, so it vanishes when they are equal and grows with the asymmetry.

    The size for a horizontal line. Phases at 0, 6 and 12 m: \(D_{ab} = D_{bc} = 6\) m and \(D_{ca} = 12\) m. Since mutual impedance goes as \(\ln(D_e/D)\) with \(D_e \approx 900\) m for the earth return:

    \[ \frac{\ln(900/6)}{\ln(900/12)} = \frac{5.01}{4.32} = 1.16 \]

    A 16% difference between the mutuals, giving sequence coupling terms of roughly 3–5% of the self-impedance.

    What it means. Three consequences, in increasing order of importance:

    \[ \begin{array}{ll} \text{A balanced load draws unbalanced current} & \sim1\text{--}2\%\ \text{negative sequence} \\ \text{Sequence networks are no longer independent} & \text{a positive-sequence source excites } I_2 \\ \text{Fault currents are wrong by a few per cent} & \text{usually acceptable} \end{array} \]

    The remedy is transposition — rotating the phase positions at one-third intervals along the route, so that each phase occupies each position for a third of the length and the average mutuals are equal. It is why transposition towers exist, and it is why every impedance in Parts 3 and 4 was quoted for a transposed line without comment.

    And where it cannot be ignored: long untransposed lines, cable circuits with asymmetric bonding, and any study of steady-state unbalance rather than faults. Modern software carries the full \(3\times3\) matrix and does not use symmetrical components at all for those cases.

  3. C3 — The transformation's other relatives. Symmetrical components diagonalises a circulant by the \(3\times3\) Fourier matrix. Identify two other transformations in power engineering that do the same job for different structures, state what each diagonalises, and explain why \(dq0\) is needed at all when symmetrical components already exists.

    Show answer

    The three transformations:

    \[ \begin{array}{lll} \text{Symmetrical components} & \text{constant circulant } \mathbf{Z}_{abc} & \text{steady state, any frequency} \\ \text{Clarke } (\alpha\beta0) & \text{the same, but real} & \text{instantaneous, real arithmetic} \\ \text{Park } (dq0) & \text{rotor-position-dependent } \mathbf{L}(\theta) & \text{machines, transient} \end{array} \]

    Clarke's transformation is symmetrical components with a real basis: it maps \(abc\) to two orthogonal axes plus a zero component, using only real coefficients. It diagonalises the same circulant, works on instantaneous values rather than phasors, and is what a digital controller computes because it needs no complex arithmetic.

    Park's transformation solves a different problem. A synchronous machine's inductance matrix is not constant — it depends on the rotor angle \(\theta\), because the rotor is magnetically asymmetric:

    \[ L_{aa}(\theta) = L_0 + L_2\cos2\theta \qquad \text{and similarly for the rest} \]

    No constant transformation can diagonalise a time-varying matrix. Symmetrical components fails on a salient-pole machine's transient behaviour for exactly this reason. Park's transformation rotates with the rotor, and in that rotating frame the inductances become constants — which turns a set of differential equations with periodic coefficients into one with constant coefficients.

    The relationship between them. For a machine in balanced steady state, the \(dq0\) quantities are constants and the symmetrical-component quantities are phasors describing the same thing — they agree. Under unbalance or transients they diverge, and the choice is dictated by what is being asked:

    \[ \begin{array}{ll} \text{Steady-state unbalance, faults} & \text{symmetrical components} \\ \text{Machine transients, control} & dq0 \\ \text{Instantaneous power theory, converters} & \alpha\beta0 \end{array} \]

    The unifying statement: each is a change of basis chosen so that the matrix describing the physics becomes diagonal. What differs is which matrix — a constant circulant, or one that rotates. That the three-phase system admits such a transformation at all is a consequence of its symmetry, and it is the single mathematical fact that makes three-phase analysis tractable.

Self-Test

Multiple-Choice Questions

  1. MCQ 1. \(1 + a + a^{2}\) equals:
    (a) 1   (b) 3   (c) 0   (d) \(a\)

    Show answer
    (c). Three unit vectors 120° apart. Almost every derivation in Part 5 uses it. Problem 1.
  2. MCQ 2. \(\mathbf{A}^{-1}\) equals:
    (a) \(\mathbf{A}\)   (b) \(\tfrac{1}{3}\mathbf{A}^{*}\)   (c) \(3\mathbf{A}^{*}\)   (d) \(\mathbf{A}^{T}\)

    Show answer
    (b) — so the inverse is written down rather than computed. Problem 2.
  3. MCQ 3. A balanced \(abc\) set has:
    (a) only zero sequence   (b) only positive sequence   (c) only negative sequence   (d) all three equal

    Show answer
    (b) — which is why every balanced study in Parts 3 and 4 was a positive-sequence study. Problem 6.
  4. MCQ 4. The neutral current equals:
    (a) \(I_0\)   (b) \(3I_0\)   (c) \(I_0/3\)   (d) \(I_1+I_2\)

    Show answer
    (b). The positive and negative sequences contribute nothing to it. Problem 5.
  5. MCQ 5. Zero-sequence current in the lines of a delta is:
    (a) three times the phase value   (b) equal to the phase value   (c) zero   (d) \(\sqrt3\) times

    Show answer
    (c), identically. It circulates inside the delta instead. Problem 8.
  6. MCQ 6. A neutral earthing impedance \(Z_n\) appears in the sequence networks as:
    (a) \(Z_n\) in all three   (b) \(3Z_n\) in the zero-sequence network only   (c) \(Z_n/3\) in zero   (d) not at all

    Show answer
    (b). The per-phase network carries \(I_0\) while the neutral carries \(3I_0\). Problem 9.
  7. MCQ 7. The complex power in sequence quantities is:
    (a) \(V_0I_0^{*}+V_1I_1^{*}+V_2I_2^{*}\)   (b) three times that   (c) that plus cross terms   (d) \(\sqrt3\) times that

    Show answer
    (b), with no cross terms — because \(\mathbf{A}\mathbf{A}^{*} = 3\mathbf{I}\). Problem 10.
  8. MCQ 8. An open conductor in an otherwise balanced supply gives a negative-sequence unbalance of:
    (a) 0   (b) 20%   (c) 50%   (d) 100%

    Show answer
    (c)\(I_2 = 33.3\) against \(I_1 = 66.7\). And no increase in current at all, so overcurrent protection is blind to it. Problem 11.
  9. MCQ 9. A single-phase load on phase \(a\) gives:
    (a) \(I_0 = I_1 = I_2\)   (b) \(I_0 = 0\)   (c) \(I_1 = -I_2\)   (d) only positive sequence

    Show answer
    (a), all equal to a third of the current — and the same boundary condition as a single line-to-earth fault. Problem 13.
  10. MCQ 10. A line-to-line fault gives:
    (a) \(I_0 = I_1 = I_2\)   (b) \(I_0 = 0\) and \(I_1 = -I_2\)   (c) \(I_1 = I_2\)   (d) \(I_0 \ne 0\)

    Show answer
    (b) — no earth involved, so no zero sequence. Problem 14.
  11. MCQ 11. A \(Y\)\(\Delta\) transformer shifts negative sequence by:
    (a) \(+30^\circ\)   (b) \(-30^\circ\)   (c) \(0^\circ\)   (d) \(180^\circ\)

    Show answer
    (b), the opposite of the positive-sequence shift, because \(1-a\) and \(1-a^{2}\) are conjugates. Problem 18.
  12. MCQ 12. For a balanced line with self \(Z_s\) and mutual \(Z_m\), the zero-sequence impedance is:
    (a) \(Z_s-Z_m\)   (b) \(Z_s+Z_m\)   (c) \(Z_s+2Z_m\)   (d) \(3Z_s\)

    Show answer
    (c), while \(Z_1 = Z_2 = Z_s-Z_m\). The difference \(3Z_m\) is why \(Z_0 \approx 3Z_1\) for an overhead line. Problem 19.
Reference

Key Formulas

QuantityRelationNotes
The operator\(a = 1\angle120^\circ\), \(a^{3} = 1\)\(a^{*} = a^{2} = 1/a\)
Central identity\(1+a+a^{2} = 0\)Used in almost every derivation
Differences\(1-a = \sqrt3\angle-30^\circ\), \(a-a^{2} = j\sqrt3\)Source of every \(\sqrt3\) in Part 5
Synthesis\(\mathbf{V}_{abc} = \mathbf{A}\mathbf{V}_{012}\)\(\mathbf{A} = [1\,1\,1;\,1\,a^{2}\,a;\,1\,a\,a^{2}]\)
Resolution\(\mathbf{V}_{012} = \tfrac{1}{3}\mathbf{A}^{*}\mathbf{V}_{abc}\)No inversion required
Zero sequence\(V_0 = \tfrac{1}{3}(V_a+V_b+V_c)\)Non-zero only with an earth path
Positive sequence\(V_1 = \tfrac{1}{3}(V_a+aV_b+a^{2}V_c)\)
Negative sequence\(V_2 = \tfrac{1}{3}(V_a+a^{2}V_b+aV_c)\)
Neutral current\(I_n = 3I_0\)How \(I_0\) is measured
Earthing impedanceappears as \(3Z_n\)Zero-sequence network only
Power\(S = 3(V_0I_0^{*}+V_1I_1^{*}+V_2I_2^{*})\)No cross terms
Unbalance factor\(\text{VUF} = |V_2|/|V_1|\)2% is the usual limit
Machine withstand\(I_2^{2}t \le K\)\(K = 6\)–30 for turbogenerators
Sequence impedances\(Z_0 = Z_s+2Z_m\), \(Z_1 = Z_2 = Z_s-Z_m\)Balanced element only
Transformer shift\(+30^\circ\) positive, \(-30^\circ\) negativeZero sequence: no path
Diagnostics

Common Mistakes

  1. Omitting the \(1/3\) in the resolution. The synthesis matrix has no factor; the resolution matrix has \(1/3\) — Problem 2.

  2. Swapping the \(a\) and \(a^{2}\) rows. Positive sequence uses \(aV_b\) and negative uses \(a^{2}V_b\); interchanging them swaps the two answers — Problem 2.

  3. Writing \(Z_n\) rather than \(3Z_n\). The commonest error in Part 5, and it understates the earth-fault impedance — Problem 9.

  4. Putting \(3Z_n\) in the positive-sequence network. It belongs only in the zero-sequence one, because only \(I_0\) flows in the neutral — Problem 9.

  5. Expecting zero-sequence current in a three-wire system. It is topologically impossible, however unbalanced the currents — Problem 5.

  6. Assuming a delta blocks all sequences. It blocks only zero sequence, and only from the lines — Problem 8.

  7. Forgetting the factor 3 in the power expression. \(S = 3\sum V_kI_k^{*}\) in the standard normalisation — Problem 10.

  8. Expecting cross terms in the power. There are none; the sequences are energetically independent — Problem 10.

  9. Judging unbalance by voltage magnitudes alone. NEMA's definition misses an unbalance that is purely in the angles — Problem 15.

  10. Giving positive and negative sequence the same transformer phase shift. They are equal and opposite — Problem 18.

  11. Applying symmetrical components to an unbalanced network. The diagonalisation requires a circulant impedance matrix, i.e. a transposed line — Problem 19 and Challenge C2.

  12. Rounding the components before recombining. Large components can cancel to a small phase quantity, so intermediate rounding destroys the answer — Problem 20.

Looking Ahead

The transformation is established, and with it the one fact that makes Part 5 possible: a balanced network's impedance matrix is diagonalised by \(\mathbf{A}\), so the three sequences propagate through it independently. An unbalanced condition — a fault, an open conductor, a single-phase load — then appears not as a coupling inside the network but as a boundary condition at one point, linking three otherwise separate circuits.

Set 22 builds those three circuits for the five-bus system of Part 4: the positive-sequence network is the fault network already constructed in Set 18, the negative-sequence network is very nearly the same, and the zero-sequence network is a different network entirely — its connectivity set by transformer windings and its impedances roughly three times larger. Set 23 then applies the boundary conditions of Problems 13 and 14 to connect them, and computes the four standard fault types on the same system.