Solved Problems · Set 10

Short Transmission Lines — Regulation

Part 3 · Line Performance — what to do when the voltage at the far end is wrong, and why the answer is almost never more copper. Chapter 13 of the textbook.

Prof. Mithun Mondal 20 solved · 12 practice · 3 challenge GATE · ESE · University

Set 10 — Short Transmission Lines — Regulation

Twenty worked problems on the quantity that most often decides whether a line is acceptable. Set 9 computed regulation; this set attacks it. The three available remedies — series capacitance, shunt capacitance and tap changing — act on entirely different terms of the same expression, and choosing between them requires knowing which term dominates. The set closes with the maximum power a short line can transfer, which turns out to be governed by the same impedance from the other direction.

Textbook Chapter 13 · 20 solved · 12 practice · 3 challenge · 12 MCQs

i Method Recap
  • Regulation in compact form. \(\%\text{reg} \approx \%R\cos\phi \pm \%X\sin\phi\). Two numbers describe the line and the load supplies the angle. Every remedy in this set attacks one of the three factors.

  • Series compensation attacks \(\%X\). A capacitor in series subtracts from the line reactance, so \(X_{\text{net}} = X_L - X_C\). It cannot reduce the regulation below the \(\%R\cos\phi\) floor, and it raises the fault current through the compensated section.

  • Shunt compensation attacks \(\sin\phi\). A capacitor across the load supplies its reactive demand locally, so the line carries less current at a better power factor. It reduces the losses as well, which series compensation does not.

  • Tap changing attacks neither — it raises \(V_S\). It corrects the receiving voltage without improving the line at all, so the losses and the reactive absorption are unchanged. It is a remedy for the symptom, and often the right one.

  • Capacitor sizing. To move a load of \(P\) from \(\cos\phi_1\) to \(\cos\phi_2\) requires \(Q_C = P(\tan\phi_1 - \tan\phi_2)\). This one line answers most compensation questions.

  • Power transfer. \(P_R = \dfrac{V_SV_R}{Z}\cos(\theta - \delta) - \dfrac{V_R^2}{Z}\cos\theta\), maximum at \(\delta = \theta\). For a line with \(R \to 0\) this collapses to the familiar \(V_SV_R\sin\delta/X\).

  • Know which term dominates before choosing a remedy. On a transmission line \(\%X \gg \%R\) and the reactive term rules; on a distribution feeder they are comparable and the resistive term can dominate at good power factors. The same remedy can be decisive on one and useless on the other.

VideoWalkthrough
Problem 1Warm-upRegulation

A 66 kV, 60 km three-phase line has \(R = 9.6\ \Omega\) and \(X_L = 24.0\ \Omega\) per phase and delivers 20 MW at 0.9 power factor lagging. Find its percentage resistance and reactance, and hence its voltage regulation. This line recurs throughout the set.

Solution

Per-phase voltage and line current:

\[ V_R = \frac{66\,000}{\sqrt3} = 38\,105\ \text{V}, \qquad I = \frac{20\times10^{6}}{\sqrt3(66\,000)(0.9)} = 194.4\ \text{A} \]

Percentage resistance and reactance at this current:

\[ \%R = \frac{IR}{V_R}\times100 = \frac{194.4(9.6)}{38\,105}\times100 = 4.90\% \]
\[ \%X = \frac{IX_L}{V_R}\times100 = \frac{194.4(24.0)}{38\,105}\times100 = 12.25\% \]

With \(\cos\phi = 0.9\) and \(\sin\phi = 0.4359\) lagging:

\[ \%\text{reg} \approx \%R\cos\phi + \%X\sin\phi = 4.90(0.9) + 12.25(0.4359) \]
\[ = 4.41 + 5.34 = 9.75\% \]

Reading the two contributions separately is the whole point of this decomposition: the reactance supplies 5.34 of the 9.75 points, and the resistance 4.41.

Neither term dominates here, and that is unusual — it is what makes this line a useful test case. On a 400 kV line with \(X/R = 20\) the reactive term would supply almost all of the regulation and series compensation would be the obvious remedy. On an 11 kV feeder with \(X/R = 0.5\) the resistive term would dominate and no amount of capacitance would help. At \(X/R = 2.5\) both remedies bite, which is why Problems 5 to 10 can compare them meaningfully on this one line.
Answer\(\%R = 4.90\), \(\%X = 12.25\), regulation \(= 9.75\%\)
Problem 2Exam levelBoth Voltages Given

A short three-phase line of impedance \((6 + j8)\ \Omega\) per phase has sending- and receiving-end voltages of 120 kV and 110 kV for a load at 0.9 power factor lagging. Determine the power output and the sending-end power factor.

Solution

Both voltages are given and the current is unknown — the reverse of Problem 1. Convert to per-phase:

\[ V_R = \frac{110\times10^{3}}{\sqrt3} = 63\,509\ \text{V}, \qquad V_S = \frac{120\times10^{3}}{\sqrt3} = 69\,282\ \text{V} \]

Using the approximate formula with \(I\) as the unknown:

\[ V_S = V_R + IR\cos\phi_R + IX_L\sin\phi_R \]
\[ 69\,282 = 63\,509 + I(6)(0.9) + I(8)(0.4359) \]

Collecting the current:

\[ 5773 = I(5.40 + 3.487) = 8.887I \quad\Rightarrow\quad I = 649.6\ \text{A} \]

Power output:

\[ P_R = \sqrt3\,V_LI\cos\phi_R = \sqrt3(110\times10^{3})(649.6)(0.9) = 111.4\ \text{MW} \]

Sending-end power factor:

\[ \cos\phi_S = \frac{V_R\cos\phi_R + IR}{V_S} = \frac{63\,509(0.9) + 649.6(6)}{69\,282} = \frac{57\,158 + 3898}{69\,282} = 0.881 \]

The regulation implied is \((120-110)/110 = 9.1\%\), which is what fixed the current in the first place.

Fixing both terminal voltages fixes the load, and that is a real constraint on system operation. A line between two buses whose voltages are each held by tap changers cannot carry an arbitrary load — the difference between the voltages determines the current, and hence the power. This is why parallel lines of unequal impedance share load in inverse proportion to their impedances whether or not that is desirable, and why phase-shifting transformers exist to override the natural division.
Answer\(I = 649.6\) A, \(P_R = 111.4\) MW, \(\cos\phi_S = 0.881\) lagging
Problem 3Warm-upPower Factor Shift

For the line of Problem 1, find the sending-end power factor and the reactive power absorbed by the line.

Solution

Sending-end voltage per phase, from the percentages of Problem 1:

\[ V_S = 38\,105(1 + 0.0975) = 41\,820\ \text{V} \]

Sending-end power factor:

\[ \cos\phi_S = \frac{V_R\cos\phi_R + IR}{V_S} = \frac{38\,105(0.9) + 194.4(9.6)}{41\,820} = \frac{34\,295 + 1866}{41\,820} = 0.865 \]

Reactive power absorbed by the line:

\[ Q_{\text{line}} = 3I^{2}X_L = 3(194.4)^{2}(24.0) = 2.72\ \text{MVAr} \]

Against the load's own reactive demand:

\[ Q_R = P_R\tan\phi_R = 20\tan(25.84^\circ) = 20(0.4843) = 9.69\ \text{MVAr} \]
\[ Q_S = 9.69 + 2.72 = 12.41\ \text{MVAr} \]

The line adds 28% to the reactive burden the sending end must supply — which is the direct cause of the power factor falling from 0.900 to 0.865.

The line is itself a reactive load of 2.72 MVAr, and nobody ordered it. It scales as \(I^2\), so it grows fastest exactly when the system can least afford it — at peak load. This self-reinforcing behaviour is the mechanism behind voltage collapse: heavier loading demands more reactive power, which depresses the voltage, which raises the current for the same power, which demands more reactive power still. Set 34 follows that spiral to its conclusion; here it is visible as a single number.
Answer\(\cos\phi_S = 0.865\); the line absorbs 2.72 MVAr, raising \(Q_S\) to 12.41 MVAr
Problem 4Exam levelRegulation vs Power Factor

For the line of Problem 1 at fixed current, tabulate the regulation at power factors from 0.6 lagging to 0.6 leading, and identify the zero-regulation point.

Solution

With \(\%R = 4.90\) and \(\%X = 12.25\) from Problem 1:

\[ \begin{array}{lccc} \text{p.f.} & \%R\cos\phi & \pm\%X\sin\phi & \%\text{reg} \\ \hline 0.60\ \text{lag} & 2.94 & +9.80 & +12.74 \\ 0.80\ \text{lag} & 3.92 & +7.35 & +11.27 \\ 0.90\ \text{lag} & 4.41 & +5.34 & +9.75 \\ 1.00 & 4.90 & 0 & +4.90 \\ 0.90\ \text{lead} & 4.41 & -5.34 & -0.93 \\ 0.80\ \text{lead} & 3.92 & -7.35 & -3.43 \\ 0.60\ \text{lead} & 2.94 & -9.80 & -6.86 \end{array} \]

The zero-regulation power factor, from Set 9 Problem 13:

\[ \tan\phi = \frac{R}{X_L} = \frac{9.6}{24.0} = 0.4 \quad\Rightarrow\quad \phi = 21.8^\circ,\ \cos\phi = 0.928\ \text{leading} \]

Checking it against the table, which brackets it between unity (+4.90) and 0.90 leading (−0.93):

\[ 4.90(0.928) - 12.25(0.371) = 4.548 - 4.545 \approx 0\ \checkmark \]
Note that even at unity power factor the regulation is 4.90%, and no shunt capacitor can improve on that. Shunt compensation works by reducing \(\sin\phi\), and once \(\sin\phi = 0\) the mechanism is exhausted; going further into leading territory means overcompensating, which is possible but risks a dangerous voltage rise at light load. The \(\%R\cos\phi\) floor is what Problem 6 examines, and it is the reason a line with poor regulation and good power factor needs a different remedy entirely.
AnswerRegulation ranges \(+12.74\%\) to \(-6.86\%\); zero at \(\cos\phi = 0.928\) leading
Problem 5Exam levelSeries Compensation

A series capacitor providing 50% compensation is installed in the line of Problem 1. Find the new reactance, the new regulation, and the capacitor's reactive rating.

Solution

Fifty per cent compensation means the capacitor cancels half the line reactance:

\[ X_C = 0.50(24.0) = 12.0\ \Omega, \qquad X_{\text{net}} = 24.0 - 12.0 = 12.0\ \Omega \]

The current is unchanged at 194.4 A — the load still demands 20 MW at 0.9 power factor — so the new percentage reactance is simply halved:

\[ \%X = \frac{194.4(12.0)}{38\,105}\times100 = 6.12\% \]

New regulation:

\[ \%\text{reg} = 4.90(0.9) + 6.12(0.4359) = 4.41 + 2.67 = 7.08\% \]

Capacitor rating — three phases, each carrying the full line current:

\[ Q_C = 3I^{2}X_C = 3(194.4)^{2}(12.0) = 1.36\ \text{MVAr} \]

The improvement is from 9.75% to 7.08% — a reduction of 2.67 points, exactly the reactive contribution that was cancelled.

A series capacitor is in the current path, and everything about it follows from that. Its rating depends on \(I^2\), so it must be sized for the maximum line current, not the load; it must survive the full fault current, which requires spark gaps or metal-oxide varistors to bypass it; and it reduces the impedance seen by a fault, raising the fault level downstream. None of these complications afflicts a shunt capacitor, which is one reason series compensation is confined to long transmission lines where nothing else will do.
Answer\(X_{\text{net}} = 12.0\ \Omega\), regulation falls to \(7.08\%\), capacitor rated 1.36 MVAr
Problem 6Challenge-liteThe Resistive Floor

Find the regulation of the line of Problem 1 with 100% series compensation, and hence the lowest regulation series compensation alone can achieve. Comment on what limits it.

Solution

With \(X_C = X_L = 24.0\ \Omega\) the net reactance vanishes:

\[ X_{\text{net}} = 0 \quad\Rightarrow\quad \%X = 0 \]

The regulation reduces to the resistive term alone:

\[ \%\text{reg} = \%R\cos\phi = 4.90(0.9) = 4.41\% \]

Tabulating the degrees of compensation:

\[ \begin{array}{cccc} \text{Compensation} & X_{\text{net}}\ (\Omega) & \%X & \%\text{reg} \\ \hline 0\% & 24.0 & 12.25 & 9.75 \\ 50\% & 12.0 & 6.12 & 7.08 \\ 70\% & 7.2 & 3.67 & 6.01 \\ 100\% & 0 & 0 & 4.41 \end{array} \]

The floor is 4.41%, set entirely by \(\%R\cos\phi\), and no series capacitance whatever can go below it.

What limits compensation in practice. Full compensation is never used. Beyond about 70% the line becomes a net capacitance, and three problems appear: subsynchronous resonance, in which the compensated line's electrical resonance couples to a turbine-generator's torsional modes; ferroresonance with transformer magnetising inductance; and the loss of a well-defined fault-current direction, which confuses distance protection.

Series compensation removes the reactive term and leaves the resistive one untouched, which is exactly the wrong division of labour on a distribution feeder and exactly the right one on a transmission line. On the 400 kV line of Set 7, where \(\%X\) is twenty times \(\%R\), cancelling the reactance removes 95% of the regulation. Here, at \(X/R = 2.5\), it removes only 55%. Knowing the \(X/R\) ratio before choosing a remedy is not a refinement — it decides whether the remedy works at all.
AnswerFloor \(= \%R\cos\phi = 4.41\%\); practical compensation is limited to about 70% by subsynchronous resonance
Problem 7Exam levelShunt Capacitor Sizing

A shunt capacitor bank is to raise the power factor of the 20 MW load of Problem 1 from 0.9 to 0.95 lagging. Find its rating, and the new line current.

Solution

The load's reactive demand at each power factor:

\[ \phi_1 = \cos^{-1}(0.9) = 25.84^\circ, \qquad Q_1 = 20\tan(25.84^\circ) = 9.686\ \text{MVAr} \]
\[ \phi_2 = \cos^{-1}(0.95) = 18.19^\circ, \qquad Q_2 = 20\tan(18.19^\circ) = 6.574\ \text{MVAr} \]

The capacitor supplies the difference:

\[ Q_C = P(\tan\phi_1 - \tan\phi_2) = 20(0.4843 - 0.3287) = 3.11\ \text{MVAr} \]

The real power is unchanged, so the new line current follows from the improved power factor:

\[ I = \frac{20\times10^{6}}{\sqrt3(66\,000)(0.95)} = 184.2\ \text{A} \]

Down from 194.4 A, a reduction of 5.2%.

The loss reduction that comes free with it:

\[ \frac{P_{\text{loss,new}}}{P_{\text{loss,old}}} = \left(\frac{184.2}{194.4}\right)^{2} = 0.898 \quad\Rightarrow\quad 10.2\%\ \text{less loss} \]
The capacitor is rated 3.11 MVAr and carries no load current at all — it sits across the busbar, not in series with anything. That single structural difference from Problem 5 explains everything: it need not withstand fault current, it can be switched in blocks to follow the load, and it reduces the line current and therefore the losses, which a series capacitor does not. Its drawback is that its output falls as \(V^2\) just when the voltage sags and it is most needed — the opposite of a series capacitor, whose effect grows with current.
Answer\(Q_C = 3.11\) MVAr; current falls to 184.2 A and losses by 10.2%
Problem 8Warm-upRegulation After Correction

Find the voltage regulation of the line of Problem 1 after the shunt correction of Problem 7.

Solution

Both the current and the angle have changed, so the percentages must be recomputed at \(I = 184.2\) A:

\[ \%R = \frac{184.2(9.6)}{38\,105}\times100 = 4.64\%, \qquad \%X = \frac{184.2(24.0)}{38\,105}\times100 = 11.60\% \]

With \(\cos\phi = 0.95\) and \(\sin\phi = 0.3122\):

\[ \%\text{reg} = 4.64(0.95) + 11.60(0.3122) = 4.41 + 3.62 = 8.03\% \]

Against the original 9.75%, an improvement of 1.72 points.

Note that the resistive contribution is unchanged at 4.41%. The current fell by 5.2% but \(\cos\phi\) rose by the same 5.6%, and the product \(I\cos\phi\) — which is fixed by the real power — cannot change at all:

\[ \%R\cos\phi = \frac{IR\cos\phi}{V_R} = \frac{R}{V_R}\cdot\frac{P_R}{\sqrt3 V_L} = \text{constant} \]
The resistive term is untouchable by shunt compensation, and the algebra above shows why. \(I\cos\phi\) is the real-power current, fixed by the load and the voltage; only the reactive current can be removed. So shunt correction and series compensation both bottom out at the same 4.41% floor, from opposite directions — one by driving \(\sin\phi\) to zero, the other by driving \(\%X\) to zero. That coincidence is confirmed numerically in Problem 9.
AnswerRegulation falls from 9.75% to \(8.03\%\); the resistive contribution stays at 4.41%
Problem 9Exam levelCorrection to Unity

Find the capacitor rating needed to correct the load of Problem 1 to unity power factor, and the resulting regulation and losses.

Solution

To unity, the capacitor must supply the whole of the load's reactive demand:

\[ Q_C = P\tan\phi_1 = 20(0.4843) = 9.69\ \text{MVAr} \]

New current:

\[ I = \frac{20\times10^{6}}{\sqrt3(66\,000)(1.0)} = 175.0\ \text{A} \]

Regulation, with the reactive term now vanishing entirely:

\[ \%R = \frac{175.0(9.6)}{38\,105}\times100 = 4.41\%, \qquad \%\text{reg} = 4.41(1.0) + 0 = 4.41\% \]

Exactly the floor of Problem 6, reached by an entirely different route.

Losses:

\[ P_{\text{loss}} = 3(175.0)^{2}(9.6) = 882\ \text{kW} \]
\[ \text{against } 3(194.4)^{2}(9.6) = 1088\ \text{kW originally} \quad\Rightarrow\quad 19\%\ \text{less} \]
Two remedies, one floor, and a decisive difference in the losses. Full series compensation and full shunt correction both give 4.41% regulation, but shunt correction also removes 206 kW of loss while series compensation removes none — the current is unchanged in that case. Against this, the shunt bank is 9.69 MVAr where the series bank was 1.36, so it is far larger and more expensive per unit of regulation improvement. The choice is between paying once for regulation and paying repeatedly in losses.
Answer\(Q_C = 9.69\) MVAr; regulation \(4.41\%\), losses fall from 1088 to 882 kW
Problem 10Challenge-liteSeries vs Shunt

Compare series and shunt compensation for the line of Problem 1 on every relevant criterion, and state when each is preferred.

Solution

Collecting the results of Problems 5 to 9 for equal regulation of 4.41%:

\[ \begin{array}{lcc} & \text{Series (100\%)} & \text{Shunt (to unity)} \\ \hline \text{Rating} & 1.36\ \text{MVAr} & 9.69\ \text{MVAr} \\ \text{Regulation} & 4.41\% & 4.41\% \\ \text{Line current} & 194.4\ \text{A} & 175.0\ \text{A} \\ \text{Losses} & 1088\ \text{kW} & 882\ \text{kW} \\ \text{Carries load current?} & \text{Yes} & \text{No} \\ \text{Carries fault current?} & \text{Yes} & \text{No} \\ \text{Output falls as } V^2? & \text{No} & \text{Yes} \end{array} \]

The mechanisms differ fundamentally. A series capacitor changes the line; a shunt capacitor changes the load. The first reduces the impedance between two points, the second reduces the current flowing between them.

Series compensation is preferred when the line is long and highly inductive, when the objective is to raise the power transfer limit (Problem 18), and when the reactive rating must be small. It self-regulates: its effect grows as \(I^2\), so it acts hardest at heavy load.

Shunt compensation is preferred when losses matter, when the reactive demand is at an identifiable load centre, when switching in blocks to follow the load is wanted, and on distribution feeders where \(X/R\) is low. Its weakness is that its output falls as the square of the voltage, so it fails just as the voltage collapses.

The seven-to-one difference in reactive rating is the headline, and it is not the whole story. A series capacitor achieves the same regulation with a seventh of the MVAr because it works against \(I^2X\) rather than supplying \(Q\) outright — but it must be insulated to line potential, protected against fault current, and it brings resonance risks that a shunt bank does not. In practice transmission systems use both: series capacitors on long lines for stability and power transfer, shunt banks at load centres for voltage support and loss reduction.
AnswerSeries: 1.36 MVAr, no loss reduction, fault-current exposed. Shunt: 9.69 MVAr, 19% less loss, fails as \(V^2\)
Problem 11Warm-upTap Changing

Instead of compensating the line of Problem 1, the sending-end transformer is tapped to hold the receiving-end voltage at 66 kV. Find the required tap setting, and state what the tap changer does not improve.

Solution

From Problem 3, holding \(V_R\) at 66 kV requires a sending-end voltage of

\[ V_S = 38\,105(1.0975) = 41\,820\ \text{V per phase} = 72.43\ \text{kV line} \]

The tap ratio required, relative to nominal:

\[ t = \frac{72.43}{66} = 1.0975 \quad\Rightarrow\quad +9.75\% \]

Standard on-load tap changers offer \(\pm10\%\) in steps of 1.25%, so the nearest available tap is \(+10\%\):

\[ V_S = 66(1.10) = 72.6\ \text{kV} \quad\Rightarrow\quad V_R = \frac{72.6}{1.0975} = 66.15\ \text{kV} \]

A slight overshoot of 0.23%, which is the granularity of the tap and is entirely acceptable.

What the tap changer does not improve. The current is unchanged at 194.4 A, so:

\[ \begin{array}{ll} \text{Losses} & 1088\ \text{kW — unchanged} \\ \text{Reactive absorption} & 2.72\ \text{MVAr — unchanged} \\ \text{Sending-end power factor} & 0.865 — \text{unchanged} \\ \text{Receiving-end voltage} & \text{corrected} \end{array} \]

Moreover the tap changer must draw 72.6 kV from a system that may not have it to give — it moves the voltage problem upstream rather than solving it.

A tap changer treats the symptom and nothing else, which is sometimes exactly right and sometimes a trap. If the only requirement is a correct customer voltage, it is the cheapest remedy by a wide margin and needs no reactive plant at all. But it consumes reactive power from the upstream system to do so, and in a system already short of vars a tap changer raising its secondary voltage can deepen the shortage upstream — the mechanism by which tap changers are known to accelerate voltage collapse rather than arrest it. Set 34 returns to this; the warning is worth carrying from here.
AnswerTap \(= +9.75\%\), nearest standard \(+10\%\); losses, reactive absorption and power factor are all unchanged
Problem 12Exam levelDistribution Feeder

An 11 kV distribution feeder 5 km long has \(R = 0.54\ \Omega\)/km and \(X_L = 0.35\ \Omega\)/km and supplies 2 MW at 0.85 power factor lagging. Find its regulation, and the regulation achievable by full shunt correction and by full series compensation.

Solution

Feeder impedance — note that here \(R > X_L\):

\[ R = 2.70\ \Omega, \qquad X_L = 1.75\ \Omega, \qquad \frac{X}{R} = 0.65 \]

Per-phase voltage and current:

\[ V_R = \frac{11\,000}{\sqrt3} = 6351\ \text{V}, \qquad I = \frac{2\times10^{6}}{\sqrt3(11\,000)(0.85)} = 123.5\ \text{A} \]

Percentages and regulation, with \(\sin\phi = 0.5268\):

\[ \%R = \frac{123.5(2.70)}{6351}\times100 = 5.25\%, \qquad \%X = \frac{123.5(1.75)}{6351}\times100 = 3.40\% \]
\[ \%\text{reg} = 5.25(0.85) + 3.40(0.5268) = 4.46 + 1.79 = 6.25\% \]

Full shunt correction to unity. The current falls to \(I = 2\times10^6/(\sqrt3 \cdot 11\,000) = 105.0\) A:

\[ \%\text{reg} = \frac{105.0(2.70)}{6351}\times100 = 4.46\% \]

Full series compensation. The reactive term vanishes at the original current:

\[ \%\text{reg} = 5.25(0.85) = 4.46\% \]

Both remedies reach the same 4.46%, an improvement of only 1.79 points from 6.25%.

On a distribution feeder both compensation methods are nearly useless, and the arithmetic says exactly why. The resistive term supplies 4.46 of the 6.25 points — 71% of the regulation — and neither remedy touches it. The only effective measures here are a larger conductor, a higher distribution voltage, or moving the transformer closer to the load. This is the reverse of the transmission case of Problem 13, and it is why capacitor banks on low-voltage feeders are installed for loss reduction and power-factor penalties rather than for voltage support.
AnswerRegulation 6.25%; both full shunt and full series compensation reach only 4.46%
Problem 13Challenge-liteTransmission vs Distribution

A 400 kV transmission line has \(\%R = 0.5\) and \(\%X = 10\) at its rated load. Compare the effectiveness of series compensation on it with the distribution feeder of Problem 12, at 0.9 power factor lagging.

Solution

Transmission line, uncompensated, at \(\cos\phi = 0.9\):

\[ \%\text{reg} = 0.5(0.9) + 10(0.4359) = 0.45 + 4.36 = 4.81\% \]

Fully series compensated:

\[ \%\text{reg} = 0.45\% \quad\Rightarrow\quad \text{a reduction of } \frac{4.81 - 0.45}{4.81} = 91\% \]

Distribution feeder, from Problem 12:

\[ 6.25\% \to 4.46\% \quad\Rightarrow\quad \text{a reduction of } \frac{6.25 - 4.46}{6.25} = 29\% \]

The general result. The fraction of the regulation that compensation can remove is

\[ \frac{\%X\sin\phi}{\%R\cos\phi + \%X\sin\phi} = \frac{1}{1 + \dfrac{\%R}{\%X}\cot\phi} = \frac{1}{1 + \dfrac{R}{X}\cot\phi} \]

— a function of the line's \(X/R\) and the load angle only, independent of the loading.

Evaluating at \(\cos\phi = 0.9\), so \(\cot\phi = 2.065\):

\[ \begin{array}{ccc} X/R & \text{Removable fraction} & \text{Verdict} \\ \hline 0.65 & 1/(1 + 3.18) = 24\% & \text{Barely worth it} \\ 2.5 & 1/(1 + 0.83) = 55\% & \text{Worth considering} \\ 20 & 1/(1 + 0.10) = 91\% & \text{Highly effective} \end{array} \]
One formula decides whether to compensate at all, and it needs only the \(X/R\) ratio and the power factor. Below \(X/R \approx 2\) reactive compensation is a poor investment for voltage support, whatever its other merits; above \(X/R \approx 10\) it is decisive. Since \(X/R\) rises steadily with voltage class — from below 1 at 11 kV to 20 or more at 400 kV — this single ratio explains why compensation is a transmission technology and conductor sizing is a distribution one.
Answer91% removable at \(X/R = 20\) against 24% at \(X/R = 0.65\); removable fraction \(= 1/(1 + (R/X)\cot\phi)\)
Problem 14Exam levelEconomics

The shunt capacitor of Problem 9 costs \(\text{₹}500\) per kVAr installed. If energy costs \(\text{₹}5\) per kWh and the loss load factor is 0.4, find the annual saving in losses and the simple payback period.

Solution

From Problem 9, the loss reduction at full load:

\[ \Delta P = 1088 - 882 = 206\ \text{kW} \]

Annual energy saved, using the loss load factor to convert peak loss to average:

\[ \Delta E = 206 \times 8760 \times 0.4 = 721\,800\ \text{kWh} \]

Annual saving:

\[ \text{Saving} = 5 \times 721\,800 = \text{₹}3.61\ \text{million per year} \]

Capital cost of the bank:

\[ \text{Cost} = 9690 \times 500 = \text{₹}4.85\ \text{million} \]

Simple payback:

\[ \frac{4.85}{3.61} = 1.34\ \text{years} \]

And this counts only the loss saving. The released capacity — the line now carries 175 A instead of 194 A for the same power, freeing 10% of its thermal headroom — and the improved regulation are both obtained at no additional cost.

A payback under eighteen months is why power-factor correction is the most widely installed measure in power systems. Nothing else in this book returns capital that fast: a larger conductor pays back over decades, a higher voltage requires rebuilding the line. The loss load factor matters here more than it looks — at 0.4 the payback is 1.3 years, but a feeder with a flat load profile and LLF near 0.8 would pay back in eight months, while a lightly used one at LLF 0.15 would take three and a half years and might not justify the bank at all.
AnswerSaving \(\text{₹}3.61\) million a year against a cost of \(\text{₹}4.85\) million — a payback of 1.34 years
Problem 15Challenge-litePower Transfer Equation

Derive the receiving-end power of a short line in terms of the terminal voltages, the impedance \(Z\angle\theta\) and the load angle \(\delta\), and evaluate its parameters for the line of Problem 1.

Solution

Take \(\mathbf{V}_R = V_R\angle0\) and \(\mathbf{V}_S = V_S\angle\delta\). The current from the line equation:

\[ \mathbf{I} = \frac{\mathbf{V}_S - \mathbf{V}_R}{\mathbf{Z}} = \frac{V_S\angle\delta - V_R\angle0}{Z\angle\theta} \]

The complex power delivered to the load:

\[ \mathbf{S}_R = \mathbf{V}_R\mathbf{I}^{*} = V_R\angle0 \cdot \frac{V_S\angle-\delta - V_R\angle0}{Z\angle-\theta} \]
\[ = \frac{V_SV_R}{Z}\angle(\theta - \delta) - \frac{V_R^{2}}{Z}\angle\theta \]

Taking the real part:

\[ \boxed{P_R = \frac{V_SV_R}{Z}\cos(\theta - \delta) - \frac{V_R^{2}}{Z}\cos\theta} \]

For the line of Problem 1:

\[ Z = |9.6 + j24.0| = \sqrt{92.16 + 576} = 25.85\ \Omega \]
\[ \theta = \tan^{-1}\frac{24.0}{9.6} = \tan^{-1}(2.5) = 68.20^\circ, \qquad \cos\theta = \frac{R}{Z} = 0.3714 \]

Checking the lossless limit: with \(R \to 0\) we get \(Z \to X\), \(\theta \to 90^\circ\), \(\cos\theta \to 0\), and

\[ P_R \to \frac{V_SV_R}{X}\cos(90^\circ - \delta) = \frac{V_SV_R\sin\delta}{X}\ \checkmark \]

the familiar form used throughout the stability analysis of Set 24.

The second term is a pure loss term and it is why \(P_R \ne P_S\). It depends on \(V_R^2\) and on \(\cos\theta = R/Z\), vanishing only for a lossless line — which is exactly why the lossless approximation is so convenient and why it is safe on a transmission line with \(\cos\theta \approx 0.05\) and unsafe on this one with \(\cos\theta = 0.37\). Note also that \(\theta\), the impedance angle, is the complement of what most textbooks call the line's power factor angle — a persistent source of sign confusion.
Answer\(P_R = \frac{V_SV_R}{Z}\cos(\theta-\delta) - \frac{V_R^2}{Z}\cos\theta\); here \(Z = 25.85\ \Omega\), \(\theta = 68.20^\circ\)
Problem 16Exam levelMaximum Power

Find the maximum power the line of Problem 1 can deliver with both terminal voltages held at 66 kV, and the load angle at which it occurs.

Solution

From Problem 15, \(P_R\) is maximised when \(\cos(\theta - \delta) = 1\), that is at

\[ \delta = \theta = 68.20^\circ \]

The maximum, per phase, with \(V_S = V_R = 38\,105\) V:

\[ P_{R,\max} = \frac{V_SV_R}{Z} - \frac{V_R^{2}}{Z}\cos\theta = \frac{V_R^{2}}{Z}(1 - \cos\theta) \]
\[ = \frac{(38\,105)^{2}}{25.85}(1 - 0.3714) = \frac{1.452\times10^{9}}{25.85}(0.6286) \]
\[ = 5.617\times10^{7}(0.6286) = 3.531\times10^{7}\ \text{W per phase} \]

For three phases:

\[ P_{R,\max} = 3(35.31) = 105.9\ \text{MW} \]

Against the actual 20 MW delivered, the line operates at

\[ \frac{20}{105.9} = 19\%\ \text{of its theoretical maximum} \]

Comparing with the lossless estimate, which is what is usually quoted:

\[ P_{\max,\text{lossless}} = \frac{3V_R^{2}}{X} = \frac{3(1.452\times10^{9})}{24.0} = 181.5\ \text{MW} \]

The resistance has cut the true maximum to 58% of the lossless figure — a very large correction, because \(X/R\) here is only 2.5.

A 42% overestimate from neglecting resistance, on a line where neglecting it seemed reasonable enough. The error scales with \(\cos\theta = R/Z\), so on a 400 kV line with \(X/R = 20\) the lossless formula is within 5% and is used without hesitation. At \(X/R = 2.5\) it is not usable. Since the stability analysis of Set 24 rests entirely on \(P = V_SV_R\sin\delta/X\), it is worth knowing that the formula is a transmission-line result and does not transfer to sub-transmission or distribution.
Answer\(P_{R,\max} = 105.9\) MW at \(\delta = 68.2^\circ\) — against 181.5 MW by the lossless formula
Problem 17Exam levelLoad Angle

Find the load angle at which the line of Problem 1 delivers its actual 20 MW with both terminal voltages at 66 kV.

Solution

Per phase, the delivered power is

\[ P_R = \frac{20\times10^{6}}{3} = 6.667\times10^{6}\ \text{W} \]

Substituting into the power transfer equation of Problem 15:

\[ 6.667\times10^{6} = 5.617\times10^{7}\cos(68.20^\circ - \delta) - 5.617\times10^{7}(0.3714) \]

Evaluating the constant term and rearranging:

\[ 5.617\times10^{7}(0.3714) = 2.086\times10^{7} \]
\[ \cos(68.20^\circ - \delta) = \frac{6.667\times10^{6} + 2.086\times10^{7}}{5.617\times10^{7}} = \frac{2.753\times10^{7}}{5.617\times10^{7}} = 0.4901 \]

Hence:

\[ 68.20^\circ - \delta = 60.65^\circ \quad\Rightarrow\quad \delta = 7.55^\circ \]

A useful cross-check against the phasor solution. From Set 9's method the sending-end voltage had a quadrature component; here the load angle of 7.55° is the angle between the two terminal voltages when both are held at 66 kV, which is a different and larger quantity than the 1.4° found when \(V_S\) was free to rise.

Seven and a half degrees to deliver 19% of the maximum, and 68 degrees to deliver all of it — the relationship is strongly nonlinear. Near the origin \(P\) rises almost linearly with \(\delta\), so small angles carry disproportionately little power; near the maximum the curve flattens, so large increases in angle buy almost nothing. Operating practice keeps \(\delta\) below about 30° across any single line, which on this one corresponds to roughly 60 MW — well below the 105.9 MW maximum, and the margin is what preserves transient stability when a disturbance suddenly advances the angle.
Answer\(\delta = 7.55^\circ\) to deliver 20 MW, against \(68.2^\circ\) at maximum power
Problem 18Challenge-liteCompensation and Power Limit

Find the effect of 50% series compensation on the maximum power of the line of Problem 1, and repeat for a line of the same reactance but \(R = 1.2\ \Omega\). Explain the difference.

Solution

The Problem 1 line, \(R = 9.6\ \Omega\). With \(X\) halved to 12 \(\Omega\):

\[ Z = \sqrt{92.16 + 144} = 15.37\ \Omega, \qquad \cos\theta = \frac{9.6}{15.37} = 0.6246 \]
\[ P_{\max} = \frac{3(1.452\times10^{9})}{15.37}(1 - 0.6246) = 2.834\times10^{8}(0.3754) = 106.4\ \text{MW} \]

Against 105.9 MW uncompensated — an improvement of just 0.5%.

The low-resistance line, \(R = 1.2\ \Omega\), \(X = 24\ \Omega\). Uncompensated:

\[ Z = 24.03\ \Omega, \qquad \cos\theta = 0.0499 \]
\[ P_{\max} = \frac{3(1.452\times10^{9})}{24.03}(1 - 0.0499) = 1.813\times10^{8}(0.9501) = 172.2\ \text{MW} \]

With 50% compensation, \(X = 12\ \Omega\):

\[ Z = 12.06\ \Omega, \qquad \cos\theta = 0.0995 \]
\[ P_{\max} = \frac{3(1.452\times10^{9})}{12.06}(1 - 0.0995) = 3.612\times10^{8}(0.9005) = 325.3\ \text{MW} \]
\[ \text{Improvement} = \frac{325.3 - 172.2}{172.2} = 89\% \]

The explanation. Halving \(X\) halves \(Z\) only when \(X \gg R\). On the high-resistance line, \(Z\) fell from 25.85 only to 15.37 — a factor of 1.68, not 2 — and \(\cos\theta\) rose from 0.37 to 0.62, cancelling most of the gain.

Series compensation raises the power limit only on lines that are already predominantly inductive, which is precisely where it is used. The 89% gain on the low-resistance line is why series capacitors are installed on long EHV interconnectors — they buy stability margin more cheaply than a parallel circuit. The 0.5% gain on the high-resistance line shows that the technique does not generalise downward: on sub-transmission and distribution, where \(R\) is comparable to \(X\), cancelling the reactance simply converts an inductive line into a resistive one and the power limit barely moves.
Answer\(+0.5\%\) at \(X/R = 2.5\) against \(+89\%\) at \(X/R = 20\)
Problem 19Warm-upDegree of Compensation

For the low-resistance line of Problem 18 (\(R = 1.2\ \Omega\), \(X_L = 24\ \Omega\)), tabulate the maximum power against the degree of series compensation \(k = X_C/X_L\), and state what limits \(k\).

Solution

With \(X_{\text{net}} = (1 - k)X_L\), and using \(P_{\max} = 3V_R^2(1 - \cos\theta)/Z\) throughout:

\[ \begin{array}{ccccc} k & X_{\text{net}}\ (\Omega) & Z\ (\Omega) & \cos\theta & P_{\max}\ (\text{MW}) \\ \hline 0 & 24.0 & 24.03 & 0.050 & 172 \\ 0.30 & 16.8 & 16.84 & 0.071 & 240 \\ 0.50 & 12.0 & 12.06 & 0.100 & 325 \\ 0.70 & 7.2 & 7.30 & 0.164 & 499 \\ 0.90 & 2.4 & 2.68 & 0.448 & 897 \end{array} \]

The gain accelerates as \(k \to 1\) because \(P_{\max} \propto 1/Z\) and \(Z \to R\).

What limits \(k\). Practical compensation stops at 0.5 to 0.7, for reasons that are entirely non-electrical in origin:

\[ \begin{array}{ll} \text{Subsynchronous resonance} & \text{Series } LC \text{ resonates near turbine torsional modes} \\ \text{Ferroresonance} & \text{With transformer magnetising inductance} \\ \text{Protection} & \text{Distance relays mis-measure through a capacitor} \\ \text{Fault current} & \text{Lower impedance raises the fault level} \\ \text{Capacitor duty} & \text{Must survive or be bypassed during faults} \end{array} \]

Subsynchronous resonance is the binding constraint and the one that has caused real damage: the compensated line's electrical resonance at \(f\sqrt{k}\) can couple to a turbine-generator shaft's torsional natural frequency and destroy it, as happened at Mohave in 1970.

The electrical case says compensate as far as possible; the mechanical case says stop at 70%. That is an unusual and instructive constraint — a limit on an electrical design set by the torsional dynamics of a steam turbine hundreds of kilometres away. It is also why modern installations use thyristor-controlled series capacitors, which can be modulated to damp the very oscillation they would otherwise excite, rather than fixed banks.
Answer\(P_{\max}\) rises from 172 to 897 MW as \(k\) goes 0 to 0.9; practice stops at 0.5–0.7 for subsynchronous resonance
Problem 20Exam levelComplete Study

The line of Problem 1 must meet a 5% regulation limit while delivering 20 MW. Evaluate every remedy, recommend one, and justify the choice.

Solution

The starting point. Regulation 9.75%, of which 4.41 points are resistive and 5.34 reactive. The target is 5%.

Option 1 — series compensation. The reactive contribution must fall to \(5.00 - 4.41 = 0.59\) points:

\[ \%X\sin\phi = 0.59 \quad\Rightarrow\quad \%X = \frac{0.59}{0.4359} = 1.35 \]
\[ X_{\text{net}} = 24.0\left(\frac{1.35}{12.25}\right) = 2.65\ \Omega \quad\Rightarrow\quad k = 0.89 \]

Eighty-nine per cent compensation — beyond the practical limit of Problem 19, and inviting subsynchronous resonance. Rejected.

Option 2 — shunt correction. Even at unity power factor the regulation is 4.41%, which meets the target with a margin of 0.59 points. The required bank, from Problem 9:

\[ Q_C = 9.69\ \text{MVAr} \]

Correcting only to 0.98 lagging would give \(\%\text{reg} = 4.50(0.98) + 11.25(0.199) = 4.41 + 2.24 = 6.65\%\) — insufficient. Full correction is needed. Feasible.

Option 3 — tap changing. A \(+10\%\) tap holds \(V_R\) at 66 kV, meeting the customer's requirement but leaving the losses at 1088 kW and the reactive absorption at 2.72 MVAr. Feasible but treats only the symptom.

Option 4 — larger conductor. To halve \(\%R\) requires roughly twice the metal, and it would leave the reactive term almost untouched:

\[ \%\text{reg} = 2.45(0.9) + 12.0(0.4359) = 2.21 + 5.23 = 7.44\% \]

Still failing, at very large cost. Rejected.

Recommendation: shunt capacitors, 9.69 MVAr at the load. It achieves 4.41%, comfortably inside the limit; it reduces losses by 206 kW, paying back in 1.34 years (Problem 14); it releases 10% of the line's thermal capacity; and it introduces none of the resonance or protection complications of series compensation.

The one caution is light load: with the full bank connected and little load, the leading current would raise the receiving voltage. The bank should therefore be switched in blocks, following the load.

The winning remedy was not the one that attacked the larger term. The reactive contribution was 5.34 points against the resistive 4.41, which argues for series compensation — but the resistive floor made the reactive attack insufficient on its own, and 89% compensation is unacceptable for reasons that have nothing to do with regulation. Shunt correction wins by driving \(\sin\phi\) to zero, which removes the entire reactive term at once and reduces the losses as a by-product. The lesson is that a remedy must be evaluated against the target, not against the dominant term.
AnswerShunt correction to unity: 9.69 MVAr gives 4.41% regulation, 206 kW less loss and a 1.34-year payback
Practice

Practice Problems

Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not.

  1. P1. A line has \(\%R = 3\), \(\%X = 9\). Find its regulation at 0.8 p.f. lagging.

    Show answer
    \(3(0.8) + 9(0.6) = 2.4 + 5.4 = \mathbf{7.8\%}\).
  2. P2. What is the lowest regulation series compensation alone can give that line at 0.8 p.f. lagging?

    Show answer
    The resistive floor: \(\%R\cos\phi = 3(0.8) = \mathbf{2.4\%}\).
  3. P3. A 5 MW load at 0.8 p.f. lagging is to be corrected to 0.95. Find the capacitor rating.

    Show answer
    \(Q_C = 5(\tan36.87^\circ - \tan18.19^\circ) = 5(0.750 - 0.329) = \mathbf{2.11}\) MVAr.
  4. P4. By what factor do the losses fall when a load is corrected from 0.8 to 0.95 p.f. at constant power?

    Show answer
    \((0.8/0.95)^2 = 0.709\), so losses fall by \(\mathbf{29\%}\).
  5. P5. A line has \(X/R = 8\) and a load at 0.85 p.f. What fraction of its regulation can series compensation remove?

    Show answer
    \(1/(1 + (1/8)\cot\phi)\); \(\cot\phi = 1.614\), so \(1/(1+0.202) = \mathbf{83\%}\).
  6. P6. A series capacitor of 15 \(\Omega\) carries 300 A in a three-phase line. Find its reactive rating.

    Show answer
    \(3I^2X_C = 3(300)^2(15) = \mathbf{4.05}\) MVAr.
  7. P7. A line has \(Z = 10 + j30\ \Omega\). Find \(Z\), \(\theta\) and \(\cos\theta\) for the power transfer equation.

    Show answer
    \(Z = 31.6\ \Omega\), \(\theta = \tan^{-1}3 = 71.57^\circ\), \(\cos\theta = R/Z = \mathbf{0.316}\).
  8. P8. For that line with both terminals at 132 kV, find the maximum three-phase power.

    Show answer
    \(V_{ph} = 76\,210\) V; \(P = 3(76\,210)^2(1-0.316)/31.6 = \mathbf{377}\) MW.
  9. P9. Why does a tap changer not reduce line losses?

    Show answer
    It raises \(V_S\) but leaves the current unchanged — the load still demands the same power at the same corrected voltage. Losses go as \(I^2R\) — Problem 11.
  10. P10. A shunt capacitor's output falls as \(V^2\). Why is this a serious drawback?

    Show answer
    Its support weakens exactly when the voltage sags and it is most needed — the opposite of a series capacitor, whose effect grows with current.
  11. P11. What limits series compensation to about 70%?

    Show answer
    Subsynchronous resonance chiefly — the series \(LC\) resonance can couple to turbine-generator torsional modes. Also ferroresonance, protection mis-measurement and raised fault levels — Problem 19.
  12. P12. A feeder has \(X/R = 0.5\) and poor regulation. What should be done?

    Show answer
    Not reactive compensation — the resistive term dominates. Use a larger conductor, a higher voltage, or move the transformer closer to the load — Problem 12.
Challenge

Challenge Problems

Each of these needs an idea rather than a formula. Decide what the governing principle is before opening the answer.

  1. C1. Series and shunt compensation both reduced the regulation of Problem 1 to the same 4.41% floor. Establish why that floor exists, prove it cannot be beaten by either method, and identify what can beat it.

    Show answer
    The floor. Regulation is \(\%R\cos\phi + \%X\sin\phi\). Expanding the resistive term:
    \[ \%R\cos\phi = \frac{IR\cos\phi}{V_R}\times100 = \frac{R}{V_R}\cdot\frac{P_R}{\sqrt3 V_L}\times100 \]
    Every quantity on the right is fixed by the line's resistance, the delivered power and the operating voltage. Neither compensation method can change any of them.

    Why series compensation cannot beat it. A series capacitor changes only \(X\). At \(X_{\text{net}} = 0\) the reactive term vanishes and the resistive term stands alone. Going further — overcompensating so \(X_{\text{net}} < 0\) — would make the reactive term negative and could indeed reduce the total, but the line then behaves as a net capacitance with all the resonance hazards of Problem 19, and the improvement is bought at severe risk.

    Why shunt compensation cannot beat it. A shunt capacitor changes only \(\phi\). At unity power factor \(\sin\phi = 0\) and again the resistive term stands alone. Overcorrecting into leading territory would make the reactive term negative, but the leading current then raises the receiving voltage at light load — a real operational hazard, and the reason capacitor banks are switched in blocks.

    What can beat it. Only measures that change \(R\), \(P_R\) or \(V_L\):
    A larger conductor, reducing \(R\) directly. Expensive: halving \(R\) needs twice the metal for 2.2 points here.
    A higher operating voltage, which reduces the term as \(1/V^2\) — the most effective measure by far, and the reason the problem barely exists at 400 kV.
    A shorter electrical distance, by moving the supply point closer to the load.
    Deliberate overcompensation, accepting the light-load risk and managing it by switching.

    The structural point: reactive compensation manipulates the reactive power flow, and the resistive voltage drop is caused by real power flow. They are orthogonal, and no amount of the first will address the second.
  2. C2. Series and shunt capacitors both inject reactive power, yet they behave oppositely under fault, under light load and as the voltage falls. Set out the differences and explain them from the circuit topology alone.

    Show answer
    The topological difference: a series capacitor carries the line current; a shunt capacitor sees the bus voltage. Every behavioural difference follows.

    Output. Series: \(Q = 3I^2X_C\), rising as the square of the current. Shunt: \(Q = V^2/X_C\), falling as the square of the voltage.

    Under heavy load. Series output rises — self-regulating, acting hardest when needed. Shunt output falls slightly as the bus voltage sags. Advantage: series.

    Under light load. Series output falls to near zero — harmlessly. Shunt output stays at full value and can drive the voltage dangerously high, requiring switching. Advantage: series.

    As the voltage collapses. Shunt output falls as \(V^2\), so at 0.8 p.u. voltage it delivers only 64% of its rating — it withdraws support precisely during a collapse. Series compensation is unaffected by voltage and its effect actually strengthens as the current rises. Decisive advantage: series, and the reason SVCs and STATCOMs were developed — a STATCOM's output falls only as \(V\), not \(V^2\).

    Under fault. Series must carry the full fault current, requiring MOV or spark-gap bypass, and it lowers the impedance so it raises the fault level. Shunt sees a collapsed voltage and delivers almost nothing — harmless. Advantage: shunt.

    On losses. Series leaves the current unchanged, so losses are unchanged. Shunt reduces the current and hence the losses — 19% in Problem 9. Advantage: shunt.

    Resonance. Series introduces an \(LC\) resonance in the current path — subsynchronous resonance, ferroresonance. Shunt introduces a parallel resonance with the source inductance, which matters for harmonics but is far less hazardous. Advantage: shunt.

    Insulation. Series sits at line potential and must be insulated to it, on a platform. Shunt sits at bus potential with one terminal earthed. Advantage: shunt.

    Conclusion: series for power transfer and stability on long inductive lines; shunt for voltage support and loss reduction at load centres. Real systems use both, and the choice is made by which of the above columns the particular problem falls in.
  3. C3. Problem 16 found the true maximum power to be 58% of the lossless estimate. Derive the general correction factor, and establish when the lossless formula of Set 24 may be trusted.

    Show answer
    The two expressions. With equal terminal voltages \(V\):
    \[ P_{\max} = \frac{3V^2}{Z}(1 - \cos\theta), \qquad P_{\max,\text{lossless}} = \frac{3V^2}{X} \]
    The ratio. Writing \(Z = X/\sin\theta\) and \(\cos\theta = R/Z\):
    \[ \frac{P_{\max}}{P_{\max,\text{lossless}}} = \frac{X}{Z}(1 - \cos\theta) = \sin\theta(1 - \cos\theta) \]
    Expressing in terms of \(n = X/R\), where \(\sin\theta = n/\sqrt{1+n^2}\) and \(\cos\theta = 1/\sqrt{1+n^2}\):
    \[ \frac{P_{\max}}{P_{\max,\text{lossless}}} = \frac{n}{\sqrt{1+n^2}}\left(1 - \frac{1}{\sqrt{1+n^2}}\right) \]
    Evaluating:
    \[ \begin{array}{cc} X/R & \text{Ratio} \\ \hline 1 & 0.207 \\ 2.5 & 0.583 \\ 5 & 0.784 \\ 10 & 0.891 \\ 20 & 0.947 \\ 50 & 0.980 \end{array} \]
    The 0.583 at \(X/R = 2.5\) confirms Problem 16's 58%.

    Asymptotics. For large \(n\), expanding gives ratio \(\approx 1 - 1/n - 1/2n^2\), so the error is approximately \(1/n = R/X\) — a memorable rule: the lossless formula overestimates the power limit by roughly the reciprocal of the X/R ratio.

    When it may be trusted:
    \(X/R > 20\) (EHV transmission): error under 5%. Use freely.
    \(X/R = 10\) to 20 (HV transmission): error 5–11%. Acceptable for screening, not for a stability margin.
    \(X/R = 3\) to 10 (sub-transmission): error 11–50%. Do not use.
    \(X/R < 3\) (distribution): error above 50%. Meaningless.

    The wider point: the entire equal-area and swing-equation apparatus of Sets 24 to 29 rests on \(P = EV\sin\delta/X\). That is legitimate because transient stability is a transmission phenomenon, where \(X/R\) is large. Applying the same machinery to a distribution network — as is sometimes attempted for distributed generation studies — is not a small approximation but a category error.
Self-Test

Multiple-Choice Questions

  1. MCQ 1. A series capacitor improves regulation by reducing:
    (a) \(\%R\)   (b) \(\%X\)   (c) \(\sin\phi\)   (d) the load current

    Show answer
    (b). It subtracts from the line reactance and leaves the current unchanged — Problem 5.
  2. MCQ 2. A shunt capacitor improves regulation by reducing:
    (a) \(\%R\)   (b) \(\%X\)   (c) \(\sin\phi\) and the current   (d) the line length

    Show answer
    (c). Supplying the load's vars locally lowers both the angle and the current — Problem 7.
  3. MCQ 3. The lowest regulation obtainable by compensation alone is:
    (a) zero   (b) \(\%R\cos\phi\)   (c) \(\%X\sin\phi\)   (d) half the original

    Show answer
    (b). Neither method can change \(I\cos\phi\), which is fixed by the real power — Problems 6, 8 and Challenge C1.
  4. MCQ 4. To correct a load of \(P\) from \(\phi_1\) to \(\phi_2\) requires a capacitor of:
    (a) \(P(\cos\phi_1 - \cos\phi_2)\)   (b) \(P(\tan\phi_1 - \tan\phi_2)\)   (c) \(P(\sin\phi_1 - \sin\phi_2)\)   (d) \(P\tan\phi_2\)

    Show answer
    (b). The capacitor supplies the difference in reactive demand at constant real power.
  5. MCQ 5. A tap-changing transformer improves:
    (a) the receiving voltage only   (b) the losses   (c) the power factor   (d) all three

    Show answer
    (a). The current is unchanged, so losses, reactive absorption and power factor are all untouched — Problem 11.
  6. MCQ 6. On a distribution feeder with \(X/R < 1\), reactive compensation for voltage support is:
    (a) highly effective   (b) largely ineffective   (c) dangerous   (d) mandatory

    Show answer
    (b). The resistive term dominates and neither method touches it — Problems 12 and 13.
  7. MCQ 7. A series capacitor's reactive output varies as:
    (a) \(V^2\)   (b) \(I^2\)   (c) \(V\)   (d) it is constant

    Show answer
    (b) \(3I^2X_C\) — self-regulating, acting hardest at heavy load. A shunt capacitor varies as \(V^2\).
  8. MCQ 8. Series compensation is normally limited to about 70% because of:
    (a) cost   (b) subsynchronous resonance   (c) insulation   (d) losses

    Show answer
    (b). The series resonance can couple to turbine-generator torsional modes — Problem 19.
  9. MCQ 9. The maximum power of a short line occurs at a load angle:
    (a) \(\delta = 90^\circ\)   (b) \(\delta = \theta\), the impedance angle   (c) \(\delta = 0\)   (d) \(\delta = 45^\circ\)

    Show answer
    (b). Option (a) is the lossless special case, where \(\theta \to 90^\circ\) — Problem 16.
  10. MCQ 10. Neglecting resistance overestimates the maximum power by roughly:
    (a) \(R/X\)   (b) \(X/R\)   (c) \((R/X)^2\)   (d) it underestimates it

    Show answer
    (a). About 5% at \(X/R = 20\) and 42% at \(X/R = 2.5\) — Challenge C3.
  11. MCQ 11. Series compensation raises the power limit substantially only when:
    (a) the load is leading   (b) \(X \gg R\)   (c) the line is short   (d) always

    Show answer
    (b). Problem 18 found +89% at \(X/R = 20\) but only +0.5% at \(X/R = 2.5\).
  12. MCQ 12. The chief weakness of shunt capacitors during a voltage collapse is that their output:
    (a) rises uncontrollably   (b) falls as \(V^2\)   (c) becomes inductive   (d) is unaffected

    Show answer
    (b). They withdraw support exactly when it is most needed — the reason SVCs and STATCOMs exist.
Reference

Key Formulas

QuantityRelationNotes
Regulation, compact\(\%R\cos\phi \pm \%X\sin\phi\)\(+\) lagging, \(-\) leading
Percentage impedance\(\%R = IR/V_R\), \(\%X = IX/V_R\)Per-unit on the load's own base
Resistive floor\(\%R\cos\phi\)Unbeatable by any compensation
Series compensation\(X_{\text{net}} = X_L(1-k)\), \(k = X_C/X_L\)Practical \(k \le 0.7\)
Series capacitor rating\(Q_C = 3I^2X_C\)Carries load and fault current
Shunt capacitor sizing\(Q_C = P(\tan\phi_1 - \tan\phi_2)\)At constant real power
Shunt capacitor output\(Q_C = V^2/X_C\)Falls as \(V^2\) — its weakness
Loss ratio after correction\((\cos\phi_1/\cos\phi_2)^2\)Shunt only; series leaves \(I\) unchanged
Removable fraction\(1/[1 + (R/X)\cot\phi]\)Decides whether to compensate
Tap ratio\(t = V_{S,\text{required}}/V_{S,\text{nominal}}\)Corrects voltage only
Power transfer\(P_R = \frac{V_SV_R}{Z}\cos(\theta-\delta) - \frac{V_R^2}{Z}\cos\theta\)\(\cos\theta = R/Z\)
Maximum power\(P_{\max} = \frac{V_R^2}{Z}(1-\cos\theta)\) at \(\delta=\theta\)Per phase, equal terminal voltages
Lossless limit\(P_{\max} = V_SV_R/X\)Overestimates by about \(R/X\)
Correction factor\(\sin\theta(1-\cos\theta)\)0.58 at \(X/R = 2.5\); 0.95 at 20
Diagnostics

Common Mistakes

  1. Forgetting to recompute \(\%R\) and \(\%X\) after shunt correction. The current changes, so both percentages change — Problem 8.

  2. Expecting series compensation to reduce losses. The current is unchanged; only shunt correction reduces it — Problem 10.

  3. Expecting compensation to reach zero regulation. The \(\%R\cos\phi\) floor is untouchable — Challenge C1.

  4. Sizing a shunt capacitor from \(\cos\phi\) rather than \(\tan\phi\). The formula is \(P(\tan\phi_1 - \tan\phi_2)\).

  5. Rating a series capacitor on the load rather than the current. It is \(3I^2X_C\), and it must also survive the fault current.

  6. Applying reactive compensation to a low-\(X/R\) feeder. Problem 12 found it removing only 29% of the regulation.

  7. Assuming a tap changer solves the underlying problem. It corrects the voltage and nothing else, and can worsen the upstream var balance — Problem 11.

  8. Using \(P_{\max} = V_SV_R/X\) on a line with low \(X/R\). A 42% overestimate at \(X/R = 2.5\) — Problem 16.

  9. Taking \(\delta = 90^\circ\) at maximum power. It is \(\delta = \theta\); the 90° is the lossless special case.

  10. Confusing \(\theta\), the impedance angle, with \(\phi\), the load angle. \(\cos\theta = R/Z\) is a property of the line alone.

  11. Leaving a full capacitor bank connected at light load. The leading current raises the receiving voltage; banks must be switched in blocks — Problem 20.

  12. Compensating beyond 70% without considering resonance. Subsynchronous resonance has destroyed turbine shafts — Problem 19.

Looking Ahead

The short line has now been analysed and remedied. Its regulation is understood, its compensation options compared, and its power limit computed — all from a single series impedance and the assumption that the current is the same at both ends.

That assumption is what Set 11 abandons. Restoring the shunt admittance as a lumped element at the ends gives the nominal-\(\pi\) and nominal-T models, in which \(A \ne 1\) and the sending and receiving currents differ. The immediate consequence is that the no-load receiving voltage is no longer the sending voltage — the Ferranti effect appears, and with it the whole reactive behaviour of a long line that the short model could not represent. Set 12 then shows that even the nominal-\(\pi\) is an approximation, and derives the exact solution from the wave equation.