Solved Problems · Set 22

Sequence Impedances and Networks

Part 5 · Faults — three networks for one system, of which two are nearly the same and the third is a different system altogether. Chapter 23 of the textbook.

Prof. Mithun Mondal 20 solved · 12 practice · 3 challenge GATE · ESE · University

Set 22 — Sequence Impedances and Networks

Twenty worked problems on building the circuits that Set 21's transformation calls for. Because a balanced network is diagonalised by \(\mathbf{A}\), each sequence sees a network of its own, and the three can be constructed independently. The positive-sequence network is the one Part 4 already built. The negative-sequence network differs from it only in the machines. The zero-sequence network is a different object entirely: its connectivity is set by transformer windings rather than by lines, its impedances are roughly three times larger, and it exists only where an earth path does. The five-bus system of Part 4 acquires all three here.

Textbook Chapter 23 · 20 solved · 12 practice · 3 challenge · 12 MCQs

i Method Recap
  • Static elements are sequence-blind. A line, cable or reactor has \(Z_1 = Z_2\) exactly, because reversing the phase sequence of a passive symmetric element changes nothing it can detect.

  • Machines are not. A synchronous machine has \(Z_1 = jx'' _d\), \(Z_2 \approx jx''_d\) and \(Z_0 \approx j(0.15\text{–}0.6)x''_d\) — three different values, because the rotor sees the three fields differently.

  • Zero sequence returns through earth. All three phase currents flow the same way, so the return is in the earth, the earth wire or the sheath — a much larger loop, giving \(Z_0 \approx 3Z_1\) for an overhead line and 1–5 times for a cable.

  • Transformer connections govern the zero-sequence network. A delta blocks it from the lines and provides a circulating path; an earthed star passes it; an isolated star blocks it entirely. Six standard diagrams cover every case.

  • Neutral earthing enters as \(3Z_n\) in the zero-sequence network only, because that per-phase network carries \(I_0\) while the physical neutral carries \(3I_0\).

  • Each network is built and inverted separately. Three \(\mathbf{Y}_{\text{bus}}\) matrices, three \(\mathbf{Z}_{\text{bus}}\) matrices, and at a faulted bus \(k\) only \(Z_{0,kk}\), \(Z_{1,kk}\), \(Z_{2,kk}\) are needed.

  • Sources appear only in the positive-sequence network. Generators produce balanced \(abc\) voltages, which are pure positive sequence — so the negative and zero networks are passive and driven only by the fault.

VideoWalkthrough
Problem 1FoundationWhat It Is

Define the sequence impedances of a three-phase element, state how each would be measured, and explain why three separate networks result.

Solution

The definition. Set 21 showed that a balanced element's impedance matrix is diagonalised by \(\mathbf{A}\):

\[ V_0 = Z_0I_0 \qquad V_1 = Z_1I_1 \qquad V_2 = Z_2I_2 \]

The sequence impedance is simply the ratio of the voltage to the current of that sequence, with the other two absent. No cross terms exist, so each is a well-defined single number.

How each is measured, and the tests are genuinely performed:

\[ \begin{array}{lll} Z_1 & \text{apply a balanced } abc \text{ set} & \text{the ordinary impedance test} \\ Z_2 & \text{apply a balanced } acb \text{ set} & \text{swap two supply leads} \\ Z_0 & \text{apply the } \textit{same }\text{voltage to all three} & \text{three phases in parallel, return by earth} \end{array} \]

The zero-sequence test is the distinctive one: the three phases are joined together and energised against earth, so the measured impedance is \(V/I\) with \(I\) a third of the total current.

The zero-sequence test in detail, because the factor of three appears here too:

\[ Z_0 = \frac{V_{\text{applied}}}{I_{\text{total}}/3} = \frac{3V}{I_{\text{total}}} \]

Three phases in parallel carry \(3I_0\) for an applied \(V_0\), so the impedance per phase is three times the ratio a single ammeter and voltmeter would suggest.

Why three networks. Each sequence sees the whole system through its own impedances, and the topologies need not match:

\[ \begin{array}{lll} \text{Positive} & \text{the familiar network} & \text{sources present} \\ \text{Negative} & \text{same topology, machine values differ} & \text{no sources} \\ \text{Zero} & \text{different topology entirely} & \text{no sources} \end{array} \]

The third is the important one. A transformer that connects two buses in the positive-sequence network may not connect them at all in the zero-sequence network, and that is a difference of topology, not of value.

The sources appear once only. A generator produces a balanced \(abc\) set of internal voltages, which is pure positive sequence:

\[ E_{a0} = E_{a2} = 0 \qquad E_{a1} = E \]

So the negative- and zero-sequence networks contain impedances only. They are passive, and the fault at one bus is the sole excitation they receive — which is exactly why an unsymmetrical fault is analysed by connecting the three networks at that one bus.

And the structure of the whole of Part 5 follows. Build three networks; reduce each to a Thévenin impedance at the faulted bus; connect the three according to the fault's boundary conditions; solve one small circuit. The network analysis is done three times and the fault analysis once.

A sequence impedance is a property of the element, and a sequence network is a property of the system — and the two behave quite differently. The element values are catalogue data, measured once and tabulated. The networks are constructed afresh for every switching state, and the zero-sequence one changes shape when a transformer is switched or a neutral disconnected. Most errors in Part 5 are errors in the third network's topology, not in anybody's impedance.
Answer\(Z_k = V_k/I_k\) with the other sequences absent; three networks result because the topologies differ, and sources appear only in the positive-sequence one
Problem 2FoundationStatic Elements

Show that \(Z_1 = Z_2\) exactly for any static element, and state which elements this covers.

Solution

The argument from the matrix. Set 21 obtained, for a balanced element,

\[ Z_1 = Z_2 = Z_s - Z_m \]

The same expression for both — so the equality is exact and not an approximation. It follows purely from the circulant structure of \(\mathbf{Z}_{abc}\).

The argument from physics, which is more memorable. Negative sequence differs from positive only in the order in which the three phases peak. A static element has no moving part and no preferred direction of rotation:

\[ \text{No rotor} \quad\Rightarrow\quad \text{no way to distinguish } abc \text{ from } acb \]

Interchanging two phases relabels the element's terminals and nothing more. Its impedance cannot change.

Which elements this covers:

\[ \begin{array}{lll} \text{Transmission lines and cables} & Z_1 = Z_2 & \text{exactly} \\ \text{Transformers} & Z_1 = Z_2 = Z_0 & \text{all three equal in magnitude} \\ \text{Series reactors, capacitors} & Z_1 = Z_2 & \\ \text{Static loads} & Z_1 = Z_2 & \\ \text{Rotating machines} & Z_1 \ne Z_2 & \text{the exception} \end{array} \]

The transformer case deserves care. Its zero-sequence impedance equals its positive-sequence impedance — the leakage reactance is the same whatever the sequence, because the flux path is the same. What differs is whether a zero-sequence path exists at all:

\[ \begin{array}{ll} Z_0 = Z_1\ \text{in magnitude} & \text{when a path exists} \\ Z_0 = \infty & \text{when the connection blocks it} \end{array} \]

A three-limb core transformer is the exception to the first line: its zero-sequence flux has no iron return path and must go through the tank and air, giving \(Z_0 \approx 0.85Z_1\). A five-limb or shell-type core, or a bank of three single-phase units, gives \(Z_0 = Z_1\).

The practical consequence. Because \(Z_1 = Z_2\) for every line and transformer, the negative-sequence network of a real system differs from the positive-sequence one only in the machines:

\[ \text{Negative-sequence network} = \text{positive-sequence network, sources removed, machine } x''_d \to x_2 \]

And since \(x_2 \approx x''_d\) for a turbogenerator, the two networks are often taken as numerically identical — which is what this book's five-bus system will do.

The one further exception is a static var compensator or any element containing thyristors, which are switched in synchronism with the positive-sequence voltage and therefore do distinguish the two sequences. They are modelled specially, and they are the only non-rotating element that does.

That \(Z_1 = Z_2\) for everything except machines is the single most labour-saving fact in Part 5. It means the negative-sequence network never has to be built from scratch — it is the positive-sequence network with the sources shorted and a few machine reactances adjusted. Two of the three networks are one network, and the whole of the extra work is in the third.
AnswerExactly equal, because a static element cannot distinguish \(abc\) from \(acb\); only rotating machines and thyristor-controlled elements differ
Problem 3Exam levelRotating Machines

Give the three sequence impedances of a synchronous machine, explain the physical origin of each, and account for the large difference between them.

Solution

Positive sequence produces a field rotating with the rotor, so the machine's response depends on how long the disturbance has lasted:

\[ \begin{array}{lll} x''_d = 0.10\text{--}0.25 & \text{first 2--3 cycles} & \text{damper windings screen the flux} \\ x'_d = 0.15\text{--}0.40 & 0.1\text{--}2\ \text{s} & \text{field winding screens it} \\ x_d = 1.0\text{--}2.0 & \text{steady state} & \text{flux fully penetrates} \end{array} \]

A fault study uses \(x''_d\), so \(Z_1 = jx''_d\) in every network of Part 5.

Negative sequence produces a field rotating against the rotor at \(2\omega_s\) relative to it. The damper windings and rotor body are always screening it, so there is no time dependence at all:

\[ x_2 \approx x''_d \qquad \text{typically } 0.10\text{--}0.25 \]

More precisely \(x_2 = (x''_d + x''_q)/2\), the mean of the two axes — because the backward-rotating field sweeps past both the direct and quadrature axes twice per cycle. For a round-rotor machine the two are nearly equal and \(x_2 = x''_d\).

Zero sequence is different in kind. All three phase currents are in phase, so their magnetomotive forces are displaced by 120° in space and cancel:

\[ \text{MMF} \propto I_0\left(1 + a + a^{2}\right)\ \text{in space} = 0 \]

There is no rotating field, no fundamental air-gap flux, and therefore no reaction from the rotor. The only impedance is the leakage of the stator winding.

Hence \(x_0\) is small:

\[ x_0 = 0.02\text{--}0.10 \qquad \text{typically } 0.15\text{--}0.6\ \text{times } x''_d \]

Its exact value depends on the winding pitch: a two-thirds-pitch winding produces almost no zero-sequence flux and gives the lowest \(x_0\). Machine designers choose the pitch partly for this reason.

The three together, for a typical 200 MVA turbogenerator:

\[ \begin{array}{lccc} \text{Sequence} & \text{pu} & \text{Field seen by the rotor} & \text{Screened by} \\ \hline \text{Positive} & j0.20 & \text{stationary (synchronous)} & \text{dampers, transiently} \\ \text{Negative} & j0.20 & \text{rotating at } 2\omega_s & \text{dampers, always} \\ \text{Zero} & j0.06 & \text{none} & - \end{array} \]

Induction machines follow the same pattern with different numbers. A running induction motor has

\[ \begin{array}{ll} Z_1 & \text{the running impedance, at slip } s \approx 0.02 \\ Z_2 & \text{the impedance at slip } 2-s \approx 2,\ \text{i.e. the locked-rotor value} \\ Z_0 & \text{leakage only; usually no path, the neutral being isolated} \end{array} \]

The ratio \(Z_1/Z_2\) is about 6, which is the factor behind the motor derating figures of Set 21.

The three sequence impedances of a machine are three different physical situations, not three values of one quantity. Positive sequence asks how the rotor responds to a field it is synchronised with; negative sequence asks how it responds to one sweeping past at twice speed; zero sequence asks what happens when there is no air-gap field at all. That they differ by a factor of ten from largest to smallest is unsurprising once the question is put that way.
Answer\(Z_1 = jx''_d\), \(Z_2 = j(x''_d+x''_q)/2 \approx jx''_d\), \(Z_0 = jx_0 \approx 0.15\text{--}0.6\,x''_d\) — the last being pure leakage, since the zero-sequence MMF cancels in space
Problem 4Exam levelLine Zero Sequence

Derive the zero-sequence impedance of a transmission line from its self and mutual impedances, and justify the rule \(Z_0 \approx 3Z_1\).

Solution

From Set 21's diagonalisation:

\[ Z_0 = Z_s + 2Z_m \qquad Z_1 = Z_2 = Z_s - Z_m \]
\[ \Rightarrow\quad \frac{Z_0}{Z_1} = \frac{Z_s+2Z_m}{Z_s-Z_m} \]

A single ratio, determined entirely by how large the mutual is relative to the self.

The values for an overhead line with earth return. Working in inductance per kilometre, the self and mutual terms both refer to the earth-return conductor at Carson's equivalent depth \(D_e\):

\[ L_s = 0.2\ln\frac{D_e}{\text{GMR}} \qquad L_m = 0.2\ln\frac{D_e}{\text{GMD}} \qquad \text{mH/km} \]

With \(D_e = 931\) m for average soil at 50 Hz, from Problem 5.

A numerical case. GMR \(= 0.0114\) m and GMD \(= 7.56\) m, the line of Set 15:

\[ L_s = 0.2\ln\frac{931}{0.0114} = 2.2621 \qquad L_m = 0.2\ln\frac{931}{7.56} = 0.9627\ \text{mH/km} \]

The sequence inductances and reactances:

\[ L_1 = L_s - L_m = 0.2\ln\frac{\text{GMD}}{\text{GMR}} = 1.2994\ \text{mH/km} \Rightarrow x_1 = 0.4082\ \Omega/\text{km} \]

The \(D_e\) cancels — which is why the positive-sequence reactance of Set 15 could be computed without any reference to the earth at all.

\[ L_0 = L_s + 2L_m = 4.1874\ \text{mH/km} \Rightarrow x_0 = 1.3155\ \Omega/\text{km} \]
\[ \frac{x_0}{x_1} = \frac{1.3155}{0.4082} = 3.22 \]

The rule of thumb, derived. Here \(D_e\) does not cancel, which is the whole difference between the two sequences.

And the resistances. The earth-return resistance \(r_e = 0.0493\ \Omega\)/km appears once in each self term and once in each mutual, so:

\[ r_1 = r_c = 0.160 \qquad r_0 = r_c + 3r_e = 0.160 + 0.148 = 0.308\ \Omega/\text{km} \]
\[ \frac{r_0}{r_1} = 1.92 \]

So the zero-sequence resistance is nearly doubled as well — which matters for the damping of earth-fault transients and for the arc-resistance component of an earth-fault loop.

The physical reason, stated without algebra. Positive-sequence current returns through the other two phases, a few metres away; zero-sequence current returns through the earth, hundreds of metres below:

\[ \begin{array}{ll} \text{Positive sequence} & \text{loop area} \sim \text{phase spacing} \\ \text{Zero sequence} & \text{loop area} \sim \text{height above the return depth} \end{array} \]

A much larger loop, hence a much larger inductance. The earth's resistivity sets the return depth, so \(x_0\) depends on the soil — which is why it is quoted as a range rather than a number.

The observed range:

\[ \begin{array}{ll} \text{Single circuit, no earth wire} & x_0/x_1 = 3.0\text{--}3.5 \\ \text{Single circuit with earth wire} & 2.0\text{--}3.0 \\ \text{Double circuit} & 4.0\text{--}6.0\ \text{per circuit, from mutual coupling} \end{array} \]

An earth wire lowers \(x_0\) by providing a nearer return path in parallel with the earth. A double circuit raises it, for the reason of Problem 7.

The factor of three between \(x_0\) and \(x_1\) is geometric, and the geometry is the size of the current loop. Every phase-to-phase quantity in a power system is set by metres of conductor spacing; every phase-to-earth quantity by hundreds of metres of earth-return depth. The logarithm compresses that thousandfold difference in distance into a threefold difference in inductance, which is why \(x_0/x_1\) is so consistently near 3 across every line ever built.
Answer\(Z_0 = Z_s+2Z_m\) against \(Z_1 = Z_s-Z_m\); for a typical line \(x_0/x_1 = 3.22\) and \(r_0/r_1 = 1.92\), because the earth-return loop is far larger
Problem 5AnalysisThe Earth Return

Explain Carson's equivalent-depth model of the earth return, evaluate the depth for three soil resistivities, and state its effect on the zero-sequence impedance.

Solution

The problem Carson solved. Earth-return current does not flow in a wire; it spreads through a semi-infinite conducting half-space, with a distribution that depends on frequency and resistivity. Carson's 1926 solution replaces it by a fictitious conductor at an equivalent depth:

\[ D_e = 658.4\sqrt{\frac{\rho}{f}}\ \text{metres} \]

With \(\rho\) in Ω·m and \(f\) in hertz. That single substitution turns an electromagnetic field problem into a circuit one.

The values at 50 Hz:

\[ \begin{array}{lcc} \text{Soil} & \rho\ (\Omega\text{m}) & D_e\ (\text{m}) \\ \hline \text{Wet, marshy} & 10 & 294 \\ \text{Average} & 100 & 931 \\ \text{Dry, rocky} & 1000 & 2944 \end{array} \]

The 931 m used in Problem 4 corresponds to average soil. Note the range: a hundredfold change in resistivity gives a tenfold change in depth, because of the square root.

The effect on \(x_0\), which is much smaller than that range suggests:

\[ x_0 \propto \ln\frac{D_e}{\text{GMR}} \quad\Rightarrow\quad \frac{x_0(\rho=1000)}{x_0(\rho=10)} = \frac{\ln(2944/0.0114)}{\ln(294/0.0114)} = \frac{12.46}{10.16} = 1.23 \]

A hundredfold change in soil resistivity changes \(x_0\) by 23%. The logarithm again — and it is why a single value of \(x_0\) can be used for a line crossing varied terrain.

The earth resistance term is the surprise, and it does not depend on the soil at all:

\[ r_e = \frac{\pi^{2}f}{2}\times10^{-4} = 9.869\times10^{-4}f\ \Omega/\text{km} = 0.0493\ \Omega/\text{km at } 50\ \text{Hz} \]

Depending only on frequency. As the resistivity rises the current spreads deeper and wider, and the two effects cancel exactly in Carson's approximation. A remarkable result, and it means the resistive part of \(z_0\) is known even when the soil is not.

Where the approximation fails. Carson's series is truncated after the first terms, which requires

\[ \frac{D}{D_e} \ll 1 \]

— satisfied comfortably at power frequency, where \(D \sim 10\) m and \(D_e \sim 900\) m. At the frequencies of a lightning surge, \(D_e\) falls to metres and the approximation collapses, which is why travelling-wave studies use a full frequency-dependent earth model.

And the practical consequence for protection. The earth-fault loop impedance depends on soil, so a distance relay's earth-fault reach is less certain than its phase-fault reach:

\[ \begin{array}{ll} \text{Phase faults} & Z_1\ \text{known to} \sim2\% \\ \text{Earth faults} & Z_0\ \text{known to} \sim10\text{--}20\% \end{array} \]

Which is why earth-fault zones are set with a larger margin, and why \(Z_0\) is measured on commissioning rather than calculated where the setting is critical.

Carson's equivalent depth is one of the great simplifications in power engineering: an electromagnetic field problem in a conducting half-space, reduced to a single fictitious conductor at a calculable depth. It is accurate to a few per cent at power frequency, it is why zero-sequence impedance can be computed at all, and — because the resistance term turns out independent of soil — it makes the awkward half of the answer certain even when the soil data is not.
Answer\(D_e = 658.4\sqrt{\rho/f}\) — 294 to 2944 m over a hundredfold resistivity range, changing \(x_0\) by only 23%; and \(r_e = 0.049\ \Omega\)/km depends on frequency alone
Problem 6AnalysisCables

Explain why a cable's zero-sequence impedance behaves differently from an overhead line's, and give the range of \(Z_0/Z_1\) for the common constructions.

Solution

The difference is the metallic sheath. A cable's conductors are surrounded by an earthed screen only millimetres away, which offers a return path far closer than the earth:

\[ \begin{array}{ll} \text{Overhead line} & \text{return at } D_e \approx 900\ \text{m} \\ \text{Cable with bonded sheath} & \text{return at the sheath radius,} \sim0.05\ \text{m} \end{array} \]

A factor of about twenty thousand in the return distance — which the logarithm compresses, but not to nothing.

The zero-sequence current divides between the sheath and the earth in inverse proportion to the two paths' impedances:

\[ I_0 = I_{\text{sheath}} + I_{\text{earth}} \]

And the sheath, being close, takes most of it — typically 70–95%. That is why sheath bonding arrangements matter so much for zero-sequence behaviour.

The bonding arrangements, and each gives a different \(Z_0\):

\[ \begin{array}{lll} \text{Both ends bonded and earthed} & \text{sheath carries most of } I_0 & \text{lowest } Z_0 \\ \text{Single-point bonded} & \text{no sheath circulation} & \text{highest } Z_0 \\ \text{Cross-bonded} & \text{sheath current cancels in sections} & \text{intermediate} \end{array} \]

Cross-bonding is standard for long high-voltage circuits because it eliminates sheath circulating current under normal balanced load — which is a positive-sequence consideration — while still providing an earth-fault return.

The ratios in practice:

\[ \begin{array}{lc} \text{Construction} & Z_0/Z_1 \\ \hline \text{Overhead line, no earth wire} & 3.0\text{--}3.5 \\ \text{Overhead line with earth wire} & 2.0\text{--}3.0 \\ \text{Cable, both ends bonded} & 1.0\text{--}2.0 \\ \text{Cable, single-point bonded} & 3.0\text{--}5.0 \end{array} \]

A bonded cable's \(Z_0\) can be lower than three times \(Z_1\) and occasionally close to it — the opposite of the overhead-line rule, and a trap for anyone applying the factor of three by habit.

The resistive part is the striking one. The sheath is aluminium or lead of substantial cross-section but much higher resistivity than the conductor, so

\[ \frac{r_0}{r_1} = 3\text{--}10 \]

Far higher than an overhead line's 1.9. An earth fault on a cable is therefore a much more resistive fault than one on a line, which changes both the fault current's angle and the arc energy.

The consequence for a mixed circuit. A line that is partly overhead and partly cable has a zero-sequence impedance that is not a simple weighted average, because the earth-return mechanisms differ:

\[ \begin{array}{ll} \text{Positive sequence} & \text{add the two sections; well behaved} \\ \text{Zero sequence} & \text{add them, but the values differ by a factor of 2--3} \end{array} \]

And the distance-relay earth-fault reach, which depends on \(Z_0/Z_1\) through the residual compensation factor, must be set for a composite that is different in each section. This is one of the harder settings problems in practice.

The rule \(Z_0 \approx 3Z_1\) is an overhead-line rule, and applying it to a cable can be wrong by a factor of three in either direction. The number depends on the sheath, its bonding and its resistivity — all construction details invisible in a single-line diagram. Cable zero-sequence impedance is measured on commissioning far more often than it is calculated, and for good reason.
AnswerThe sheath is a much closer return than the earth, so \(Z_0/Z_1\) is 1–2 for a bonded cable and 3–5 for a single-point-bonded one, with \(r_0/r_1\) of 3–10
Problem 7Challenge-liteParallel Circuits

Two circuits share a tower. Show that they are mutually coupled in the zero-sequence network only, quantify the coupling, and state what it does to earth-fault calculations.

Solution

Why the coupling is zero-sequence only. Consider the flux linking circuit B from a balanced current in circuit A:

\[ \begin{array}{ll} \text{Positive or negative sequence} & \text{the three currents sum to zero} \\ \text{Zero sequence} & \text{the three currents add} \end{array} \]

A balanced set of currents produces a field that falls off rapidly with distance — the three contributions largely cancel a few metres away. A zero-sequence set produces a field equivalent to \(3I_0\) in a single conductor with an earth return, which falls off only logarithmically.

The magnitudes:

\[ \begin{array}{lc} \text{Positive-sequence mutual } Z_{1M} & 1\text{--}5\%\ \text{of } Z_1 \\ \text{Zero-sequence mutual } Z_{0M} & 50\text{--}70\%\ \text{of } Z_0 \end{array} \]

Two orders of magnitude apart. The first is universally neglected; the second cannot be.

The zero-sequence mutual, computed. For two circuits whose conductors have a geometric mean separation \(D_{AB}\):

\[ L_{0M} = 0.6\ln\frac{D_e}{D_{AB}}\ \text{mH/km} \]

The factor 0.6 rather than 0.2 because all three phases of each circuit participate. With \(D_e = 931\) m and \(D_{AB} = 10\) m:

\[ L_{0M} = 0.6\ln(93.1) = 2.72\ \text{mH/km} \Rightarrow x_{0M} = 0.855\ \Omega/\text{km} \]

Against a self \(x_0\) of 1.32 Ω/km — a coupling of 65%.

The circuit consequence. The zero-sequence voltage drop along circuit A depends on circuit B's current:

\[ V_{0A} = Z_{0A}I_{0A} + Z_{0M}I_{0B} \]

So the two circuits' zero-sequence networks are not independent, and the singular transformation of Set 16 — with off-diagonal terms in \([\mathbf{y}]\) — is the only formation method that handles it.

What it does to an earth-fault calculation. Three effects, all of them significant:

\[ \begin{array}{ll} \text{Both circuits in service} & \text{the healthy circuit carries induced } I_0 \\ \text{One circuit out and earthed} & \text{a large circulating current in it} \\ \text{Distance relay reach} & \text{over- or under-reaches by up to 30\%} \end{array} \]

The middle case is the dangerous one for personnel: a circuit taken out of service and earthed at both ends carries substantial induced current from a fault on its neighbour, and the earthing arrangements must be rated for it.

The relay-reach problem is the commonest practical consequence. A distance relay computes the earth-fault loop impedance using a residual compensation factor:

\[ k_0 = \frac{Z_0 - Z_1}{3Z_1} \qquad Z_{\text{measured}} = \frac{V_a}{I_a + k_0(3I_0)} \]

Which assumes the only zero-sequence current is the circuit's own. With mutual coupling, part of \(3I_0\) belongs to the parallel circuit, the compensation is wrong, and the relay sees the fault at the wrong distance. The direction of the error depends on whether the parallel circuit is in service, out of service, or out and earthed — so a single setting cannot be right for all three.

Zero-sequence mutual coupling is the one place where symmetrical components' promise of three independent networks breaks down, and it breaks down badly. The coupling is 60% rather than a few per cent, it links circuits that share no bus, and its effect on protection reach is measured in tens of per cent. Every double-circuit line in the world has this problem, and it is managed by adaptive relay settings rather than solved.
Answer\(Z_{0M} \approx 0.855\ \Omega\)/km against a self of 1.32 — a 65% coupling, against 1–5% in the positive sequence; it moves distance-relay earth-fault reach by up to 30%
Problem 8Exam levelTransformer Connections

Set out the zero-sequence equivalent circuit for each of the six standard transformer connections, and state the rule that generates them.

Solution

The two rules, applied to each winding independently:

\[ \begin{array}{ll} \text{Earthed star} & \text{connects the line to the transformer's } Z_0 \\ \text{Isolated star} & \text{open circuit — no zero-sequence path} \\ \text{Delta} & \text{connects to the reference bus, not to the line} \end{array} \]

And a zero-sequence current can flow through the transformer only if both windings offer a path. Everything else follows.

The six connections:

\[ \begin{array}{lll} Y_g\text{--}Y_g & \text{through path, } Z_0\ \text{in series} & \text{both sides pass } I_0 \\ Y_g\text{--}Y & \text{open} & \text{no return on the isolated side} \\ Y_g\text{--}\Delta & Z_0\ \text{from the line to the reference} & \text{a shunt path; no through current} \\ Y\text{--}\Delta & \text{open} & \\ \Delta\text{--}\Delta & \text{open both sides} & \text{isolated from zero sequence} \\ Y\text{--}Y & \text{open both sides} & \end{array} \]

Only the first passes zero-sequence current through; only the third provides a source of it at a bus. The other four are open circuits.

The \(Y_g\)–\(\Delta\) case is the important one, and it deserves the physical explanation. Zero-sequence current flowing in the earthed star winding must be balanced by ampere-turns in the delta:

\[ \text{Star: } I_0\ \text{in each phase} \quad\Rightarrow\quad \text{Delta: } I_0\ \text{circulating} \]

The delta provides that path, so current can flow in the star winding — but it never leaves the delta side. In the sequence diagram this appears as an impedance from the star-side bus to the reference: a shunt, not a series element.

Which makes an earthed-star/delta transformer a zero-sequence source. It supplies earth-fault current to the star-side network without any connection to what lies beyond the delta. That is why a delta-star unit transformer at a generating station provides the earth-fault infeed even though the generator itself is delta-connected and cannot.

The three-winding case adds one further element. A \(Y_g\)–\(Y_g\)–\(\Delta\) autotransformer has all three:

\[ \begin{array}{ll} \text{Two earthed stars} & \text{a through path between them} \\ \text{The delta tertiary} & \text{a shunt path to the reference} \end{array} \]

Modelled as a star equivalent of three impedances \(Z_H\), \(Z_M\), \(Z_L\) with the tertiary's branch going to the reference. The delta tertiary of a large autotransformer exists partly for this purpose — without it the zero-sequence path would be poor and the earth-fault current low.

The commonest error is to draw the zero-sequence network with the same topology as the positive-sequence one. In a network of the sort in Problem 12, most transformers are open circuits to zero sequence, and the zero-sequence network is a set of disconnected islands where the positive-sequence network is fully meshed.

The zero-sequence network's topology is drawn from the winding connections, not from the single-line diagram. Two systems with identical line data, identical transformer ratings and identical impedances can have completely different earth-fault levels — because one has delta-star transformers and the other star-star. That is the one fact in Part 5 that has no analogue anywhere in Parts 1 to 4.
AnswerEarthed star connects the line; delta connects to the reference; isolated star is open. Only \(Y_g\)–\(Y_g\) passes zero sequence through, and only \(Y_g\)–\(\Delta\) is a source of it
Problem 9DesignNeutral Earthing

Compare the four neutral earthing arrangements, give the zero-sequence impedance each produces, and state the trade being made.

Solution

The four arrangements, with the impedance each contributes to the zero-sequence network:

\[ \begin{array}{lll} \text{Solid} & Z_n = 0 & \text{nothing added} \\ \text{Resistance} & Z_n = R & 3R\ \text{added} \\ \text{Reactance} & Z_n = jX & j3X\ \text{added} \\ \text{Isolated} & Z_n = \infty & \text{no path at all} \end{array} \]

And a fifth, resonant (Petersen coil) earthing, in which \(3X_n\) is tuned to resonate with the system's total capacitance to earth — which cancels the fault current rather than limiting it.

The earth-fault current each gives, for a system with \(Z_1 = Z_2 = j0.15\) and \(Z_0 = j0.05\) pu at the machine:

\[ I_f = \frac{3E}{Z_1+Z_2+Z_0+3Z_n} \]
\[ \begin{array}{lcc} \text{Earthing} & 3Z_n & I_f\ (\text{pu}) \\ \hline \text{Solid} & 0 & 8.57 \\ \text{Reactance } X_n = 0.10 & j0.30 & 4.62 \\ \text{Resistance } R_n = 0.30 & 0.90 & 3.11 \\ \text{Isolated} & \infty & \text{capacitive only, } \sim0.01 \end{array} \]

Three orders of magnitude between the extremes.

The trade being made is between fault damage and overvoltage:

\[ \begin{array}{lll} & \text{Fault current} & \text{Healthy-phase voltage rise} \\ \hline \text{Solid} & \text{high; damage, but easy to detect} & \times1.0\text{--}1.4 \\ \text{Impedance} & \text{limited} & \times1.4\text{--}1.7 \\ \text{Isolated} & \text{negligible} & \times\sqrt3 = 1.73,\ \text{sustained} \end{array} \]

An isolated system continues to run with one phase earthed — an advantage in a continuous process — but the other two phases sit at full line voltage to earth indefinitely, so the insulation must be rated for it, and a second earth fault on another phase becomes a phase-to-phase fault through two lengths of cable.

The effectively-earthed criterion formalises the boundary:

\[ \frac{X_0}{X_1} \le 3 \quad\text{and}\quad \frac{R_0}{X_1} \le 1 \quad\Rightarrow\quad \text{healthy-phase rise} \le 1.4 \]

A system meeting this is called effectively earthed and may use surge arresters rated at 80% of line-to-line voltage rather than 100% — a real saving on insulation and arrester cost at transmission voltages, and the reason transmission systems are solidly earthed.

The practice by voltage level:

\[ \begin{array}{ll} \text{Transmission, } \ge 132\ \text{kV} & \text{solidly earthed — insulation dominates the cost} \\ \text{Distribution, } 11\text{--}33\ \text{kV} & \text{resistance earthed — limit damage} \\ \text{Generator neutral} & \text{high-resistance or distribution transformer} \\ \text{Industrial process, } 3.3\text{--}11\ \text{kV} & \text{resistance or resonant — continuity of supply} \\ \text{Ship, mine, some rail} & \text{isolated — one fault must not trip} \end{array} \]

The generator case is distinctive. A generator's stator earth fault burns iron, which is expensive to repair, so the earth-fault current is limited to a few amperes — typically by a distribution transformer with a resistor on its secondary, giving an effective \(R_n\) of hundreds of ohms. The fault is then detected by voltage rather than current.

Neutral earthing is the one design decision that determines a system's entire earth-fault behaviour, and it is made once, at the planning stage, for reasons that have little to do with fault levels. Insulation cost decides it at transmission voltages; continuity of supply decides it in industry; personnel safety decides it in mines. The earth-fault current that results is a consequence rather than an objective, and every protection setting downstream follows from it.
Answer\(3Z_n\) in the zero-sequence network; 8.57 pu solidly earthed down to negligible when isolated, traded against a healthy-phase rise of \(\times1.0\) to \(\times1.73\)
Problem 10Exam levelPositive-Sequence Network

State the positive-sequence network of the five-bus system, and say what has and has not changed from Set 18.

Solution

It is the network of Set 18, unchanged. The fault network built there — generators behind their subtransient reactances, lines as pure reactances — is the positive-sequence network:

\[ \begin{array}{lll} \text{Generator 1} & x''_d = j0.25 & \text{bus 1 to reference} \\ \text{Generator 2} & x''_d = j0.20 & \text{bus 2 to reference} \\ \text{Lines} & j0.06,\ j0.24,\ j0.18,\ j0.18,\ j0.12,\ j0.03,\ j0.24 & \text{as in Part 4} \end{array} \]

Its impedance matrix is the one built in nine steps in Set 18:

\[ \mathbf{Z}_1 = j\begin{bmatrix} 0.12514 & 0.09989 & 0.10631 & 0.10502 & 0.10160 \\ 0.09989 & 0.12009 & 0.11495 & 0.11598 & 0.11872 \\ 0.10631 & 0.11495 & 0.17377 & 0.16201 & 0.13064 \\ 0.10502 & 0.11598 & 0.16201 & 0.17680 & 0.13626 \\ 0.10160 & 0.11872 & 0.13064 & 0.13626 & 0.20457 \end{bmatrix} \]

What has changed is only the label. Set 18 called it "the fault network" and computed three-phase fault currents from its diagonal. It is now called the positive-sequence network, and its diagonal is \(Z_{1,kk}\) — one of the three quantities every unsymmetrical fault formula needs.

What has not changed is the modelling. The same four assumptions of Set 18 apply, and their direction of error is unchanged:

\[ \begin{array}{ll} \text{Resistance neglected} & \text{overstates } I_f\ \text{by} <1\% \\ \text{Loads neglected} & \text{understates by 5--10\%} \\ \text{Motors neglected} & \text{understates by 10--30\%} \\ \text{Prefault } 1.0\ \text{pu} & \pm5\% \end{array} \]

And one further point specific to sequence work. The generators' internal voltages are pure positive sequence, so this is the only network with a source in it. Reducing it for a fault at bus \(k\) gives a Thévenin source \(E = 1.0\) pu behind \(Z_{1,kk}\); the other two networks reduce to a bare impedance.

The Thévenin impedances at the five buses, which are all that Set 23 will use:

\[ Z_{1,11} = j0.12514 \quad Z_{1,22} = j0.12009 \quad Z_{1,33} = j0.17377 \quad Z_{1,44} = j0.17680 \quad Z_{1,55} = j0.20457 \]
That the positive-sequence network needed no new work is the strongest argument for having built Part 4 the way it was built. A fault study, a load flow and an unsymmetrical fault study all read the same positive-sequence network — with different modelling of the machines and the loads, but the same topology and the same line data. The three studies differ in what they ask of it, not in what it is.
AnswerIdentical to Set 18's fault network; diagonal \(j0.12514\), \(j0.12009\), \(j0.17377\), \(j0.17680\), \(j0.20457\) — and the only network containing sources
Problem 11FoundationNegative-Sequence Network

Construct the negative-sequence network of the five-bus system and state precisely how it differs from the positive-sequence one.

Solution

Two changes only, and one of them is often nil:

\[ \begin{array}{ll} 1 & \text{Remove the sources — short the internal EMFs} \\ 2 & \text{Replace each machine's } x''_d \text{ by its } x_2 \end{array} \]

The lines are unchanged, because \(Z_1 = Z_2\) exactly for a static element (Problem 2). The topology is identical.

The machine values. For the turbogenerators of this system, taking \(x_2 = x''_d\) as is usual for a round-rotor machine:

\[ x_{2,\text{gen 1}} = 0.25 \qquad x_{2,\text{gen 2}} = 0.20 \]

Identical to the positive-sequence values. So for this system the two networks are numerically the same network.

Hence:

\[ \mathbf{Z}_2 = \mathbf{Z}_1 \]
\[ Z_{2,11} = j0.12514 \quad Z_{2,22} = j0.12009 \quad Z_{2,33} = j0.17377 \quad Z_{2,44} = j0.17680 \quad Z_{2,55} = j0.20457 \]

Which spares a whole matrix inversion, and is the usual situation in practice.

When the two do differ. Three cases, in increasing order of importance:

\[ \begin{array}{lll} \text{Salient-pole machines} & x_2 = (x''_d+x''_q)/2 & \text{differs from } x''_d \text{ by 10--20\%} \\ \text{Induction motor load included} & Z_2 \ll Z_1 & \text{motors are near locked rotor} \\ \text{Static var compensators} & \text{sequence-dependent control} & \text{modelled separately} \end{array} \]

The second is the one that bites: a system with substantial motor load has a negative-sequence network appreciably stiffer than its positive-sequence one, because every motor is a low-impedance shunt to negative sequence.

The critical structural point. The negative-sequence network is passive. No source appears anywhere in it:

\[ E_{a2} = 0\ \text{for every machine} \]

Because a generator's internal EMFs are a balanced \(abc\) set and therefore pure positive sequence. Any negative-sequence current that flows is driven entirely by the fault, entering the network at the faulted bus.

Which means the reduction is simpler. Reducing the negative-sequence network to the faulted bus gives a single impedance \(Z_{2,kk}\) to the reference, with no source in series. The same is true of the zero-sequence network. Only the positive-sequence network reduces to a source behind an impedance, and that source drives the whole fault.

The negative-sequence network is the positive-sequence network with the batteries taken out, and on a transmission system with no motor load it is numerically identical. That the two are so nearly the same is what makes the phase-fault formulas of Set 23 come out with such simple ratios — \(\sqrt3/2\) for a line-to-line fault against a three-phase one, and the rest. Those ratios are exact only when \(Z_1 = Z_2\).
AnswerSame topology, sources removed, \(x''_d \to x_2\); here \(x_2 = x''_d\) so \(\mathbf{Z}_2 = \mathbf{Z}_1\) exactly — and the network is passive
Problem 12Exam levelZero-Sequence Network

Construct the zero-sequence network of the five-bus system. Each generator connects through its own unit transformer, delta on the machine side and earthed star on the network side, with zero-sequence reactances of \(j0.10\) at bus 1 and \(j0.08\) at bus 2. Line zero-sequence reactances are three times their positive-sequence values.

Solution

The generators disappear. Their unit transformers are delta on the machine side, and a delta blocks zero sequence:

\[ \text{Machine } x_0 \quad\text{is not connected to anything} \]

However low the machine's own zero-sequence reactance, no zero-sequence current can reach it. The machine is simply absent from this network.

The transformers become shunts. Each is a \(Y_g\)–\(\Delta\), which by Problem 8 gives an impedance from the star-side bus to the reference:

\[ \begin{array}{ll} \text{Bus 1} & j0.10\ \text{to the reference} \\ \text{Bus 2} & j0.08\ \text{to the reference} \end{array} \]

These are the network's only earth connections, and therefore the only sources of earth-fault current in the whole system.

The lines are tripled:

\[ \begin{array}{lcc} \text{Line} & x_1 & x_0 = 3x_1 \\ \hline 1\text{--}2 & 0.06 & 0.18 \\ 1\text{--}3 & 0.24 & 0.72 \\ 2\text{--}3 & 0.18 & 0.54 \\ 2\text{--}4 & 0.18 & 0.54 \\ 2\text{--}5 & 0.12 & 0.36 \\ 3\text{--}4 & 0.03 & 0.09 \\ 4\text{--}5 & 0.24 & 0.72 \end{array} \]

The network, described: the same seven lines with three times the reactance, two shunt paths to the reference at buses 1 and 2, and nothing at all at buses 3, 4 and 5. Compare with the positive-sequence network, which has shunt sources at buses 1 and 2 of \(j0.25\) and \(j0.20\):

\[ \begin{array}{lcc} & \text{Positive} & \text{Zero} \\ \hline \text{Shunt at bus 1} & j0.25 & j0.10 \\ \text{Shunt at bus 2} & j0.20 & j0.08 \\ \text{Line } 1\text{--}2 & j0.06 & j0.18 \\ \text{Line } 3\text{--}4 & j0.03 & j0.09 \end{array} \]

The shunts are stiffer and the lines are weaker — the reverse of the positive-sequence situation, and it changes the character of the network completely.

The consequence, before any arithmetic. Buses 1 and 2 have a very stiff local earth connection and will have a low \(Z_0\); buses 3, 4 and 5 have none and must reach the earth through tripled line reactances, so their \(Z_0\) will be high. Expect

\[ Z_{0,11},\ Z_{0,22} < Z_{1,11},\ Z_{1,22} \qquad Z_{0,33},\ Z_{0,44},\ Z_{0,55} > Z_{1,kk} \]

Which is exactly what Problem 13 finds, and it means earth faults will be more severe than three-phase faults at the generator buses and less severe elsewhere.

If the unit transformers had been star–star with both neutrals earthed, the machines' own \(x_0\) would appear in series with the transformer's, giving shunts of perhaps \(j0.16\) and \(j0.14\) instead. If they had been star–star with the machine neutrals isolated — the usual arrangement — the network would have no earth connection at all and earth-fault current would be zero everywhere.

This network has five buses, seven lines and exactly two connections to earth, and every earth-fault current in the system flows through one of those two. Nothing in the single-line diagram says so; it is entirely a consequence of two winding connections. The zero-sequence network is where power system analysis stops being about impedances and starts being about how the equipment was ordered.
AnswerSeven lines at three times their reactance; shunts of \(j0.10\) and \(j0.08\) at buses 1 and 2 only; the generators absent entirely, blocked by their delta windings
Problem 13Exam levelBuilding Z₀-bus

Build the zero-sequence impedance matrix of the five-bus system and present it.

Solution

The method is that of Set 18, applied to a different network. Nine elements again: two shunts and seven lines, so one Type 1, one Type 3, and the rest as before.

The matrix:

\[ \mathbf{Z}_0 = j\begin{bmatrix} 0.06985 & 0.02412 & 0.03575 & 0.03342 & 0.02722 \\ 0.02412 & 0.06071 & 0.05140 & 0.05326 & 0.05823 \\ 0.03575 & 0.05140 & 0.23047 & 0.19466 & 0.09916 \\ 0.03342 & 0.05326 & 0.19466 & 0.23838 & 0.11497 \\ 0.02722 & 0.05823 & 0.09916 & 0.11497 & 0.31714 \end{bmatrix} \]

A check on bus 1's diagonal. The transformer's \(j0.10\) is in parallel with the path through the network to bus 2's \(j0.08\). The dominant alternative path is line 1–2 at \(j0.18\) in series with \(j0.08\):

\[ \frac{(0.10)(0.26)}{0.10+0.26} = 0.0722 \]

Against the computed 0.06985. The small difference is the further parallel paths through buses 3, 4 and 5 — which contribute little, since they lead nowhere except back to the same two earths.

The diagonal, in order:

\[ \begin{array}{lccc} \text{Bus} & Z_{0,kk} & Z_{1,kk} & Z_0/Z_1 \\ \hline 1 & j0.06985 & j0.12514 & 0.558 \\ 2 & j0.06071 & j0.12009 & 0.506 \\ 3 & j0.23047 & j0.17377 & 1.326 \\ 4 & j0.23838 & j0.17680 & 1.348 \\ 5 & j0.31714 & j0.20457 & 1.550 \end{array} \]

The prediction of Problem 12 confirmed: the ratio is about 0.5 at the transformer buses and rises to 1.55 at bus 5, the furthest from any earth.

The off-diagonals are revealing too. \(Z_{0,34} = j0.19466\) is 84% of \(Z_{0,33}\) — buses 3 and 4 are strongly coupled in the zero-sequence network as well, by the \(j0.09\) tie. But \(Z_{0,12} = j0.02412\) is only 35% of \(Z_{0,11}\), against 80% in the positive-sequence matrix:

\[ \frac{Z_{0,12}}{Z_{0,11}} = 0.35 \qquad\text{against}\qquad \frac{Z_{1,12}}{Z_{1,11}} = 0.80 \]

Buses 1 and 2 are much less coupled in zero sequence, because each has its own strong local earth and does not need the other.

The three matrices are now complete. \(\mathbf{Z}_1\) from Set 18, \(\mathbf{Z}_2 = \mathbf{Z}_1\) from Problem 11, and \(\mathbf{Z}_0\) here. Every unsymmetrical fault calculation of Set 23 needs three numbers from them — one diagonal element from each — and nothing more.

The zero-sequence matrix bears no resemblance to the positive-sequence one, and the ratio of their diagonals varies by a factor of three across five buses. Anyone who assumes \(Z_0 = 3Z_1\) at every bus — a natural extrapolation from the line rule — would get bus 1's earth fault wrong by a factor of five. The rule applies to lines, and a network is not a line.
AnswerDiagonal \(j0.06985\), \(j0.06071\), \(j0.23047\), \(j0.23838\), \(j0.31714\); the ratio \(Z_0/Z_1\) runs from 0.51 to 1.55
Problem 14AnalysisComparing the Three

Compare the three networks bus by bus and predict, without computing any fault current, at which buses an earth fault will exceed a three-phase fault.

Solution

The criterion. The two fault currents are

\[ I_{3\phi} = \frac{E}{Z_1} \qquad I_{LG} = \frac{3E}{Z_1+Z_2+Z_0} \]
\[ \frac{I_{LG}}{I_{3\phi}} = \frac{3Z_1}{Z_1+Z_2+Z_0} \]

With \(Z_1 = Z_2\), which holds here:

\[ \frac{I_{LG}}{I_{3\phi}} = \frac{3Z_1}{2Z_1+Z_0} \quad\Rightarrow\quad I_{LG} > I_{3\phi} \iff Z_0 < Z_1 \]

A single comparison. The earth fault is more severe wherever the zero-sequence impedance is lower than the positive-sequence one.

Applying it:

\[ \begin{array}{lccl} \text{Bus} & Z_0/Z_1 & I_{LG}/I_{3\phi} & \text{Prediction} \\ \hline 1 & 0.558 & 1.17 & \text{LG worse} \\ 2 & 0.506 & 1.20 & \text{LG worse} \\ 3 & 1.326 & 0.90 & \text{3-phase worse} \\ 4 & 1.348 & 0.90 & \text{3-phase worse} \\ 5 & 1.550 & 0.85 & \text{3-phase worse} \end{array} \]

At the two transformer buses the earth fault is 17–20% more severe; elsewhere the three-phase fault is worse by 10–15%.

The physical reason. At buses 1 and 2 the earth connection is the transformer — \(j0.10\) and \(j0.08\) — which is stiffer than the machine's \(j0.25\) and \(j0.20\) in the positive-sequence network. The zero-sequence network is locally the stronger of the two.

The bounds of the ratio are worth stating, because they set the range of what is possible:

\[ \begin{array}{ll} Z_0 \to 0 & I_{LG}/I_{3\phi} \to 1.5 \\ Z_0 = Z_1 & \text{ratio} = 1 \\ Z_0 \to \infty & \text{ratio} \to 0 \end{array} \]

The upper bound of 1.5 is reached only with a perfect earth at the fault point — never in practice, but a solidly-earthed transformer terminal approaches it. Values of 1.2 to 1.4 at generator and transformer buses are common.

The practical consequence, and it is a real one. Switchgear is normally rated on the three-phase fault level, which is the standard assumption:

\[ \text{At buses 1 and 2, the earth fault exceeds it by 17--20\%} \]

So a breaker selected on the three-phase level alone would be under-rated at those two buses. IEC and IEEE standards require the earth-fault level to be checked separately at solidly-earthed transformer terminals for exactly this reason, and it is the commonest place where the two differ enough to matter.

That an earth fault can exceed a three-phase fault surprises most people, and it happens at precisely the buses where switchgear is most heavily loaded. The mechanism is simple: a solidly-earthed transformer is a much lower zero-sequence impedance than a generator is a positive-sequence one. Anywhere the earth connection is stiffer than the source, the single-phase fault wins — and that is the transformer terminal, which is where the busbar is.
AnswerEarth faults exceed three-phase faults wherever \(Z_0 < Z_1\) — here at buses 1 and 2, by 17% and 20%; the theoretical maximum ratio is 1.5
Problem 15AnalysisThévenin at a Bus

Reduce all three networks to their Thévenin equivalents at bus 3, and set out what the resulting three-terminal picture represents.

Solution

The three reductions, each a single diagonal element:

\[ \begin{array}{lll} \text{Positive} & E = 1.0\angle0^\circ\ \text{behind } Z_1 = j0.17377 & \text{active} \\ \text{Negative} & Z_2 = j0.17377 & \text{passive} \\ \text{Zero} & Z_0 = j0.23047 & \text{passive} \end{array} \]

Three two-terminal circuits, each with one terminal at bus 3 and one at the reference.

What each represents. The whole five-bus system, seen from one bus, in one sequence:

\[ \begin{array}{ll} Z_1 & \text{everything that supplies positive-sequence current to bus 3} \\ Z_2 & \text{everything that will absorb negative-sequence current there} \\ Z_0 & \text{every earth path available to bus 3} \end{array} \]

Two generators, seven lines and two transformers, reduced to three numbers — and no information relevant to a fault at bus 3 has been lost.

Why only the positive network has a source. Thévenin's theorem gives the open-circuit voltage at the terminal:

\[ \begin{array}{ll} \text{Positive} & V_{1,\text{prefault}} = 1.0\ \text{pu} \\ \text{Negative} & V_{2,\text{prefault}} = 0 \\ \text{Zero} & V_{0,\text{prefault}} = 0 \end{array} \]

A healthy balanced system has no negative- or zero-sequence voltage anywhere, by definition. So those two Thévenin sources are zero and only their impedances remain.

The three-terminal picture. Draw three boxes, each with a terminal pair — one marked \(F_1\)–\(N_1\), one \(F_2\)–\(N_2\), one \(F_0\)–\(N_0\):

\[ \begin{array}{ll} F_k & \text{the faulted bus, in sequence } k \\ N_k & \text{the reference, in sequence } k \end{array} \]

The fault is a connection between these six terminals, and which connection depends entirely on the fault type. That is the whole content of Set 23.

The three sequence voltages and currents at the fault satisfy the network relations:

\[ V_1 = E - Z_1I_1 \qquad V_2 = -Z_2I_2 \qquad V_0 = -Z_0I_0 \]

Three equations, six unknowns. The fault type supplies the other three — for example \(I_1 = I_2 = I_0\) and \(V_1+V_2+V_0 = 0\) for a solid single line-to-earth fault, which is two independent conditions plus the definition.

And the reduction must be redone for each faulted bus. The three numbers above apply to bus 3 alone; a fault at bus 5 needs \(Z_{1,55}\), \(Z_{2,55}\) and \(Z_{0,55}\). That is why the three matrices are built rather than three single equivalents — each diagonal element is one bus's Thévenin impedance, computed in advance.

Six terminals and three numbers describe every possible fault at a bus, however large the system behind them. That reduction is the reason unsymmetrical fault analysis is tractable at all: a ten-thousand-bus network and a five-bus one both present the same three-box picture, and the fault calculation that follows is identical. All the difficulty is in obtaining the three numbers, and Part 4 built the machinery for that.
Answer\(E = 1.0\) behind \(j0.17377\); passive \(j0.17377\) and \(j0.23047\). Six terminals, and the fault type decides how they are joined
Problem 16DesignChanging a Connection

The unit transformer at bus 2 is replaced by a star–star unit with both neutrals isolated. Rebuild the zero-sequence matrix and assess the consequences.

Solution

The change. An isolated-star winding offers no zero-sequence path, so bus 2 loses its earth connection entirely:

\[ \text{Shunt at bus 2: } j0.08 \quad\longrightarrow\quad \text{open circuit} \]

The network now has exactly one connection to earth, at bus 1.

The new diagonal:

\[ \begin{array}{lccc} \text{Bus} & Z_{0,kk}\ \text{before} & \text{after} & \text{increase} \\ \hline 1 & j0.06985 & j0.10000 & \times1.43 \\ 2 & j0.06071 & j0.25171 & \times4.15 \\ 3 & j0.23047 & j0.36743 & \times1.59 \\ 4 & j0.23838 & j0.38543 & \times1.62 \\ 5 & j0.31714 & j0.49286 & \times1.55 \end{array} \]

Bus 1's value becomes exactly \(j0.10\) — the transformer alone, since no other earth path exists and the lines lead nowhere. Bus 2 rises fourfold.

The earth-fault currents fall correspondingly. At bus 5:

\[ I_{LG} = \frac{3}{2(0.20457)+0.49286} = 3.326\ \text{pu} \quad\text{against}\quad 4.131\ \text{pu before} \]

A 19% reduction from changing one transformer's winding connection — with no change whatever to any line, any machine, or any impedance value.

The consequences, and they cut both ways:

\[ \begin{array}{ll} \text{Lower earth-fault current} & \text{less damage; smaller earth grid} \\ \text{Higher healthy-phase voltage} & Z_0/Z_1 \ \text{now } 2.4\ \text{at bus 5, over the effectiveness limit} \\ \text{Harder detection} & \text{earth-fault relays see less current} \\ \text{Single point of failure} & \text{bus 1's transformer earths the whole system} \end{array} \]

The second is decisive at transmission voltages: \(X_0/X_1 > 3\) puts the system outside the effectively-earthed definition and forces 100%-rated surge arresters instead of 80%.

The fourth is the operational objection. With one earth point, taking bus 1's transformer out of service leaves the network with no earth reference:

\[ \text{Transformer 1 out} \quad\Rightarrow\quad Z_0 = \infty\ \text{everywhere} \]

Earth-fault current becomes negligible, earth-fault protection stops working, and the healthy phases rise to full line voltage on any earth fault. Systems are therefore designed with at least two earth points and an operating rule that one must always remain.

The general lesson about switching. The zero-sequence network's topology changes when plant is switched, in a way the positive-sequence network's does not:

\[ \begin{array}{ll} \text{Positive sequence} & \text{lose a circuit, lose a path — gradual} \\ \text{Zero sequence} & \text{lose an earth, lose the network — abrupt} \end{array} \]

Which is why earth-fault studies are repeated for every credible switching arrangement, and why the "minimum earthing" case is a standard study alongside the maximum-plant one.

One winding connection changed earth-fault currents across the whole system by 20 to 80% and moved it out of the effectively-earthed category. No impedance was altered and no line was touched. That the zero-sequence network is so sensitive to a choice made in a transformer specification is the strongest argument for treating it as a design decision rather than a modelling detail.
AnswerOne earth point remains; \(Z_{0}\) rises by 1.4 to 4.2 times, earth-fault current at bus 5 falls 19%, and the system ceases to be effectively earthed
Problem 17DesignAdding an Earth

An earthing transformer of zero-sequence reactance \(j0.12\) pu is installed at bus 5. Recompute the zero-sequence matrix and assess whether it is worth installing.

Solution

The modification is a Type 3 addition to \(\mathbf{Z}_0\) — a branch from bus 5 to the reference:

\[ Z_{0,ij}^{\text{new}} = Z_{0,ij} - \frac{Z_{0,i5}Z_{0,5j}}{Z_{0,55}+j0.12} \]

The result:

\[ \begin{array}{lccc} \text{Bus} & \text{before} & \text{after} & \text{reduction} \\ \hline 1 & j0.06985 & j0.06816 & 2\% \\ 2 & j0.06071 & j0.05295 & 13\% \\ 3 & j0.23047 & j0.20798 & 10\% \\ 4 & j0.23838 & j0.20814 & 13\% \\ 5 & j0.31714 & j0.08706 & 73\% \end{array} \]

A dramatic local effect and a modest remote one — which is the signature of a shunt element in any network.

The earth-fault current at bus 5:

\[ I_{LG} = \frac{3}{2(0.20457)+0.08706} = 6.046\ \text{pu} \quad\text{against}\quad 4.131\ \text{before} \]

A 46% increase — and it now exceeds the three-phase fault current at bus 5, which is 4.888 pu.

Is it worth installing? The arguments for:

\[ \begin{array}{ll} \text{Earth-fault detection} & \text{a stronger signal for the relays} \\ \text{Voltage control on earth faults} & Z_0/Z_1 \ \text{falls from } 1.55 \text{ to } 0.43 \\ \text{Effectively earthed} & \text{comfortably within the criterion} \\ \text{Redundancy} & \text{a third earth point, so one can be lost} \end{array} \]

And against:

\[ \begin{array}{ll} \text{Switchgear duty} & \text{the earth-fault level at bus 5 now exceeds the three-phase} \\ \text{Cost} & \text{a transformer that carries no load and earns nothing} \\ \text{Earth grid} & \text{must be rated for the higher fault current} \\ \text{Damage} & 46\%\ \text{more energy into every earth fault at bus 5} \end{array} \]

The first is the binding one. If bus 5's switchgear was rated on the 4.888 pu three-phase level, the new 6.046 pu earth-fault level exceeds it and the plant must be replaced.

The verdict depends on why it was proposed. If earth-fault detection at bus 5 is inadequate — and at \(Z_0/Z_1 = 1.55\) it may well be — the earthing transformer solves that. But a smaller one would too:

\[ \begin{array}{lcc} \text{Earthing transformer } x_0 & Z_{0,55} & I_{LG}\ \text{at bus 5} \\ \hline \text{none} & j0.317 & 4.13 \\ j0.30 & j0.155 & 5.35 \\ j0.12 & j0.087 & 6.05 \end{array} \]

A \(j0.30\) unit gives most of the detection benefit and keeps the earth-fault level below the three-phase one. Sizing an earthing transformer is a matter of choosing where on this curve to sit, not of making the earth as strong as possible.

Adding an earth point is one of the few network changes whose effect is overwhelmingly local, and that locality is what makes it a usable design lever. Bus 5's zero-sequence impedance fell by 73% while bus 1's moved 2%. A planner can fix an earth-fault detection problem at one substation without disturbing the fault levels anywhere else — which is not true of any change to the positive-sequence network.
Answer\(Z_{0,55}\) falls 73% to \(j0.08706\) and the earth fault rises 46% to 6.05 pu — above the three-phase level, so a larger reactance would be the better choice
Problem 18Challenge-liteZero-Sequence Distribution

For an earth fault at bus 3 drawing \(3I_0 = 5.190\) pu, find the zero-sequence voltage at every bus and the zero-sequence current in every line, and verify the balance.

Solution

The zero-sequence current per phase at the fault is

\[ I_0 = \frac{5.190}{3} = 1.7300\ \text{pu} \]

Drawn out of bus 3 in the zero-sequence network. Everything else follows by superposition, exactly as the positive-sequence fault profile did in Set 18.

The zero-sequence bus voltages, from column 3 of \(\mathbf{Z}_0\):

\[ V_{0,i} = -Z_{0,i3}\,I_0 \]
\[ \begin{array}{lcc} \text{Bus} & Z_{0,i3} & |V_{0,i}|\ (\text{pu}) \\ \hline 1 & j0.03575 & 0.0618 \\ 2 & j0.05140 & 0.0889 \\ 3 & j0.23047 & 0.3987 \\ 4 & j0.19466 & 0.3368 \\ 5 & j0.09916 & 0.1715 \end{array} \]

Largest at the fault and falling with electrical distance from it. Note that a zero-sequence voltage of 0.40 pu exists at bus 3 — this is the neutral displacement, and it is what a residual voltage relay measures.

The line currents, each \((V_{0,a}-V_{0,b})/z_{0,ab}\):

\[ \begin{array}{lccl} \text{Line} & z_0 & |I_0|\ (\text{pu}) & \text{direction} \\ \hline 1\text{--}2 & j0.18 & 0.1505 & 2 \to 1 \\ 1\text{--}3 & j0.72 & 0.4679 & 3 \to 1 \\ 2\text{--}3 & j0.54 & 0.5737 & 3 \to 2 \\ 2\text{--}4 & j0.54 & 0.4590 & 4 \to 2 \\ 2\text{--}5 & j0.36 & 0.2295 & 5 \to 2 \\ 3\text{--}4 & j0.09 & 0.6884 & 3 \to 4 \\ 4\text{--}5 & j0.72 & 0.2295 & 4 \to 5 \end{array} \]

All three of bus 3's branches carry current away from it — the fault is the source in this network and the two transformer neutrals are the sinks. Bus 5, with no earth of its own, is a pure through-route: it receives 0.2295 from bus 4 and passes the same on to bus 2.

The earth-path currents, through the two transformers:

\[ I_{0,\text{tr}1} = \frac{0.0618}{0.10} = 0.6184 \qquad I_{0,\text{tr}2} = \frac{0.0889}{0.08} = 1.1116 \]
\[ 0.6184 + 1.1116 = 1.7300 = I_0 \quad\checkmark \]

Every ampere of zero-sequence current entering the network at the fault leaves through one of the two transformer neutrals. The balance closes exactly.

Kirchhoff at bus 3. All three branches carry current away from the fault:

\[ 0.4679\ (\to 1) + 0.5737\ (\to 2) + 0.6884\ (\to 4) = 1.7300 = I_0 \quad\checkmark \]

Exactly the injected zero-sequence current. The 0.6884 on the stiff 3–4 tie is the largest single flow in the network, and it goes the long way round to bus 2's transformer via buses 4 and 5.

The physical picture, stated plainly. An earth fault at bus 3 injects zero-sequence current into the zero-sequence network at that bus. It spreads through the tripled line reactances towards buses 1 and 2, and leaves the network through the two transformer neutrals in the ratio 36:64 — bus 2's transformer taking the larger share, being both stiffer and better connected.

The zero-sequence current distribution is what earth-fault protection actually measures, and it bears no resemblance to the power flow. Line 3–4 carries the largest zero-sequence current in the system — 0.69 pu — although it connects two buses with no earth connection at all. Directional earth-fault relays are graded on these numbers, and computing them is the reason the zero-sequence network is built.
Answer\(V_0\) from 0.40 pu at the fault to 0.06 at bus 1; the two transformer neutrals carry 0.618 and 1.112, summing exactly to \(I_0 = 1.730\) pu
Problem 19AnalysisSources and Passivity

Explain why only the positive-sequence network contains sources, and examine what would follow if a generator produced an unbalanced internal EMF.

Solution

The argument. A synchronous machine's internal EMFs are generated by a rotating field cutting three identical windings displaced by 120°:

\[ E_a = E\angle0^\circ \qquad E_b = E\angle-120^\circ \qquad E_c = E\angle120^\circ \]
\[ \Rightarrow\quad E_0 = E_2 = 0,\qquad E_1 = E \]

A balanced \(abc\) set, so pure positive sequence — by Problem 6 of Set 21. The negative- and zero-sequence networks contain no source of any kind.

The structural consequence. The three networks reduce differently at a faulted bus:

\[ \begin{array}{ll} \text{Positive} & \text{a source } E\ \text{behind } Z_1 \\ \text{Negative} & \text{a bare } Z_2 \\ \text{Zero} & \text{a bare } Z_0 \end{array} \]

Which is why the fault current always has \(E\) in its numerator and a combination of all three impedances in its denominator. Every fault formula in Set 23 has that structure.

And the prefault condition. Before the fault the system is balanced, so

\[ V_{2}^{(0)} = V_{0}^{(0)} = 0\ \text{at every bus} \]

The negative- and zero-sequence networks are entirely dead until the fault occurs. That is what makes superposition so clean: the fault's contribution is the whole of the negative- and zero-sequence quantities.

If a machine's EMF were unbalanced, which happens in practice for a small residue:

\[ \begin{array}{ll} \text{Winding asymmetry} & E_2 \sim 0.1\text{--}0.5\%\ \text{of } E_1 \\ \text{Rotor eccentricity} & \text{similar} \\ \text{Inter-turn fault} & \text{much larger, and a fault condition in itself} \end{array} \]

A source in the negative-sequence network would drive negative-sequence current continuously, even with no fault — which is exactly what a machine with a winding fault does, and why negative-sequence current is used to detect one.

The magnitude of the effect. A \(0.3\%\) negative-sequence EMF driving the network's negative-sequence impedance of, say, \(j0.12\) pu:

\[ I_2 = \frac{0.003}{0.12} = 0.025\ \text{pu} = 2.5\% \]

Which is a third of a turbogenerator's continuous negative-sequence capability, produced by nothing but manufacturing tolerance. It is one reason machines are tested for negative-sequence emission before commissioning.

The same argument covers loads. A balanced load is a passive impedance and contributes to all three networks; an unbalanced load — a traction feeder, a large single-phase furnace — behaves as a negative-sequence source and injects \(I_2\) into the network continuously. Modelling it requires abandoning the assumption that only the positive-sequence network is driven, and it is done by injecting a specified \(I_2\) at the load's bus.

The passivity of the negative- and zero-sequence networks is what makes fault analysis a superposition problem rather than a simultaneous one. Two of the three networks are dead before the fault and driven only by it, so their entire contents are the fault's own doing. Introduce a genuine negative-sequence source — an unbalanced load, a faulty machine — and that simplification is lost, which is why steady-state unbalance studies are a different and harder calculation than fault studies.
AnswerMachine EMFs are a balanced \(abc\) set, hence pure positive sequence; the other two networks are passive and dead until the fault, which is what makes superposition exact
Problem 20ChallengeA Complete Set

Present the three sequence networks of the five-bus system as a finished data set, state every assumption, and identify which of them most affects the answer.

Solution

Positive sequence. Generators \(j0.25\) at bus 1 and \(j0.20\) at bus 2 to the reference; seven lines at \(j0.06\), \(j0.24\), \(j0.18\), \(j0.18\), \(j0.12\), \(j0.03\), \(j0.24\); source \(E = 1.0\angle0^\circ\).

\[ \text{diag}\,\mathbf{Z}_1 = j\left[0.12514,\ 0.12009,\ 0.17377,\ 0.17680,\ 0.20457\right] \]

Negative sequence. Identical, sources removed.

\[ \text{diag}\,\mathbf{Z}_2 = \text{diag}\,\mathbf{Z}_1 \]

Zero sequence. Transformer earths \(j0.10\) at bus 1 and \(j0.08\) at bus 2; the same seven lines at three times their reactance; no generators.

\[ \text{diag}\,\mathbf{Z}_0 = j\left[0.06985,\ 0.06071,\ 0.23047,\ 0.23838,\ 0.31714\right] \]

The assumptions, in the order they were made:

\[ \begin{array}{lll} 1 & \text{Resistance neglected everywhere} & <1\%\ \text{on } |I_f| \\ 2 & \text{Line charging neglected} & \text{negligible for faults} \\ 3 & \text{Loads neglected} & \text{understates } I_f\ \text{by 5--10\%} \\ 4 & \text{Motor contribution neglected} & \text{understates by 10--30\%} \\ 5 & x_2 = x''_d\ \text{for the machines} & \text{a few \% on } Z_2 \\ 6 & x_0 = 3x_1\ \text{for the lines} & \text{2.0--3.5 in reality} \\ 7 & \text{Prefault } 1.0\ \text{pu everywhere} & \pm5\% \\ 8 & \text{Transformer connections as stated} & \textbf{decisive} \end{array} \]

Which matters most. Not the numerical ones. Assumptions 1 to 7 together move the answers by perhaps 30%, and each is defensible against a standard. Assumption 8 changes the answer by a factor of four (Problem 16) or removes it entirely:

\[ \begin{array}{ll} \text{Both unit transformers } Y_g\text{--}\Delta & Z_{0,55} = j0.317 \\ \text{One changed to } Y\text{--}Y\ \text{isolated} & Z_{0,55} = j0.493 \\ \text{Both changed} & Z_{0,55} = \infty \end{array} \]

A modelling decision with a hundredfold range of consequence, made by reading a nameplate rather than by calculation.

Assumption 6 is the second most important, and the least often examined. Taking \(x_0 = 3x_1\) when the true value is 2.0 or 3.5:

\[ \begin{array}{lcc} x_0/x_1\ \text{of the lines} & Z_{0,55} & I_{LG}\ \text{at bus 5} \\ \hline 2.0 & j0.228 & 4.71 \\ 3.0 & j0.317 & 4.13 \\ 3.5 & j0.362 & 3.89 \end{array} \]

A 21% spread in earth-fault current from a ratio that is rarely measured and usually assumed. On a system where earth-fault relay grading is tight, that is enough to matter.

The data set is now complete. Set 23 needs three numbers per faulted bus and nothing else:

\[ \begin{array}{lccc} \text{Bus} & Z_1 & Z_2 & Z_0 \\ \hline 1 & j0.12514 & j0.12514 & j0.06985 \\ 2 & j0.12009 & j0.12009 & j0.06071 \\ 3 & j0.17377 & j0.17377 & j0.23047 \\ 4 & j0.17680 & j0.17680 & j0.23838 \\ 5 & j0.20457 & j0.20457 & j0.31714 \end{array} \]
Fifteen numbers describe every possible fault at every bus of this system, and the hardest of them to get right is not a number at all. The impedances came from data sheets and a matrix inversion; the zero-sequence network's topology came from reading two transformer nameplates, and getting that wrong invalidates everything else. Fault studies fail on connectivity far more often than on arithmetic.
AnswerFifteen impedances, three per bus. Of the eight assumptions, the transformer connections dominate — they change the answer by a factor of four or remove it entirely
Practice

Practice Problems

Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not.

  1. P1. Why is \(Z_1 = Z_2\) exactly for a transmission line?

    Show answer
    A static element has no way to distinguish \(abc\) from \(acb\) — reversing the sequence just relabels its terminals. Problem 2.
  2. P2. A machine has \(x''_d = 0.18\). Estimate \(x_2\) and \(x_0\).

    Show answer
    \(x_2 \approx \mathbf{0.18}\); \(x_0 \approx 0.15\text{--}0.6\) of that, so \(\mathbf{0.03\text{--}0.11}\) pu. Problem 3.
  3. P3. A line has \(Z_s = 0.30+j1.10\) and \(Z_m = 0.05+j0.40\) Ω/km. Find \(Z_0\) and \(Z_1\).

    Show answer
    \(Z_0 = Z_s+2Z_m = \mathbf{0.40+j1.90}\); \(Z_1 = Z_s-Z_m = \mathbf{0.25+j0.70}\). Ratio \(x_0/x_1 = 2.71\).
  4. P4. Find Carson's equivalent depth for \(\rho = 200\ \Omega\)m at 50 Hz.

    Show answer
    \(658.4\sqrt{200/50} = \mathbf{1317}\) m.
  5. P5. Which transformer connections pass zero-sequence current straight through?

    Show answer
    Only \(\mathbf{Y_g\text{--}Y_g}\). \(Y_g\)–\(\Delta\) gives a shunt path but no through current; the other four are open. Problem 8.
  6. P6. A generator's neutral is earthed through \(j0.05\) pu and its \(x_0 = 0.06\). What appears in the zero-sequence network?

    Show answer
    \(x_0 + 3x_n = 0.06+0.15 = \mathbf{j0.21}\) pu.
  7. P7. A bus has \(Z_1 = Z_2 = j0.15\) and \(Z_0 = j0.10\). Which is worse, an earth fault or a three-phase fault?

    Show answer
    \(Z_0 < Z_1\), so the earth fault: ratio \(3(0.15)/(0.30+0.10) = 1.125\). Problem 14.
  8. P8. What is the theoretical maximum of \(I_{LG}/I_{3\phi}\)?

    Show answer
    \(\mathbf{1.5}\), reached as \(Z_0 \to 0\) with \(Z_1 = Z_2\).
  9. P9. Why is zero-sequence mutual coupling between parallel circuits so much larger than positive-sequence coupling?

    Show answer
    A balanced set's field cancels within metres; a zero-sequence set behaves as \(3I_0\) in one conductor with an earth return, whose field falls off only logarithmically. 60% against 1–5%. Problem 7.
  10. P10. A cable's sheath is bonded at both ends. Is \(Z_0/Z_1\) larger or smaller than for an overhead line?

    Show answer
    Smaller — 1–2 rather than 3–3.5, because the sheath is a much closer return than the earth. Problem 6.
  11. P11. Which sequence networks contain sources, and why?

    Show answer
    Only the positive. A machine's EMFs are a balanced \(abc\) set, hence pure positive sequence. Problem 19.
  12. P12. A system's only earthed transformer is switched out. What happens to earth-fault current?

    Show answer
    \(Z_0 \to \infty\), so the current becomes negligible — and the healthy phases rise to full line voltage on any earth fault. Problem 16.
Challenge

Challenge Problems

Three problems on the zero-sequence network's awkward corners — the ones that produce wrong answers in real studies.

  1. C1 — The earth wire. An overhead line carries an earth wire bonded to every tower. Show how it enters the zero-sequence impedance, quantify the reduction, and explain why it does not affect the positive sequence.

    Show answer

    Why the positive sequence is unaffected. The three phase currents sum to zero, so their net field at the earth wire's position is small and the induced current is negligible. The earth wire is electrically invisible to positive- and negative-sequence current.

    The zero-sequence case. All three phases carry \(I_0\) in the same direction, inducing a substantial voltage along the earth wire. Being bonded at every tower, it carries a circulating current \(I_w\) that opposes the inducing flux — a shorted turn.

    The circuit. Writing the two loop equations for the phase group and the earth wire:

    \[ V_0 = Z_{0}'I_0 + Z_{0w}I_w \qquad 0 = Z_{0w}I_0 + Z_{ww}I_w \]

    Eliminating \(I_w\):

    \[ Z_0 = Z_0' - \frac{Z_{0w}^{2}}{Z_{ww}} \]

    A reduction, always — the subtracted term is positive, being a squared quantity over an impedance of similar angle.

    The magnitude. With a steel earth wire of \(Z_{ww} \approx 3+j2\) Ω/km, \(Z_{0w} \approx 0.05+j0.8\) and \(Z_0' = 0.31+j1.32\):

    \[ \frac{Z_{0w}^{2}}{Z_{ww}} = \frac{(0.80\angle86^\circ)^{2}}{3.61\angle34^\circ} = 0.177\angle138^\circ = -0.132+j0.118 \]
    \[ Z_0 = 0.31+j1.32 - (-0.132+j0.118) = 0.442 + j1.202 \]

    The reactance falls by 9% and the resistance rises by 43% — the second being the loss in the earth wire itself, which the phase conductors now see as added resistance. With an aluminium-clad or OPGW earth wire of much lower \(Z_{ww}\) the reactance reduction reaches 25–30%.

    The practical points. The earth wire's material matters as much as its presence: a steel wire gives a small reduction and a large resistance increase, an ACSR or OPGW wire a large reduction and a small increase. And an earth wire that is not bonded at every tower — or whose bonds have corroded — behaves quite differently, which is why \(Z_0\) is measured after major line refurbishments.

  2. C2 — The autotransformer. A 400/220 kV autotransformer with a delta tertiary connects two networks. Derive its zero-sequence equivalent, explain what the tertiary does, and show what happens if it is omitted.

    Show answer

    The three-winding star equivalent. Measured on three short-circuit tests, the impedances \(Z_{HM}\), \(Z_{HL}\), \(Z_{ML}\) give

    \[ Z_H = \tfrac{1}{2}(Z_{HM}+Z_{HL}-Z_{ML}) \quad Z_M = \tfrac{1}{2}(Z_{HM}+Z_{ML}-Z_{HL}) \quad Z_L = \tfrac{1}{2}(Z_{HL}+Z_{ML}-Z_{HM}) \]

    A star of three branches meeting at a fictitious point. In the zero-sequence network:

    \[ \begin{array}{ll} Z_H & \text{from the 400 kV bus to the star point} \\ Z_M & \text{from the 220 kV bus to the star point} \\ Z_L & \text{from the star point to the } \textbf{reference}\ \text{(the delta)} \end{array} \]

    What the tertiary does. Three things, and only the first is usually mentioned:

    \[ \begin{array}{ll} 1 & \text{Provides a zero-sequence path, so the autotransformer earths both systems} \\ 2 & \text{Traps triple harmonics, which are a zero-sequence set} \\ 3 & \text{Stabilises the neutral against unbalanced loading} \end{array} \]

    Without the tertiary, an autotransformer is a \(Y_g\)–\(Y_g\) device with the two windings physically joined, so:

    \[ \begin{array}{ll} \text{Zero sequence passes through} & \text{but with no path to the reference} \\ \text{The two systems' zero-sequence networks are joined} & \text{whether or not that is wanted} \end{array} \]

    That coupling is the real problem. An earth fault on the 220 kV system draws zero-sequence current from the 400 kV system through the autotransformer, and the earth-fault levels of the two systems become interdependent. Adding a delta tertiary provides a local return and largely decouples them.

    And a subtlety in \(Z_L\). The star-equivalent impedances are not physical: \(Z_L\) is frequently negative for an autotransformer, because the three measured impedances do not satisfy the triangle relations a physical star would require. It is nonetheless the correct circuit model, and a negative branch impedance in a transformer equivalent is normal rather than an error.

  3. C3 — The study that gave the wrong answer. An earth-fault study of a 132 kV network predicts 8 kA at a substation; the measured value on a real fault is 5.2 kA. Identify the four most likely causes in order of probability, and state how each would be confirmed.

    Show answer

    Cause 1: a transformer connection wrong in the data. The commonest, and it produces errors of exactly this size. A \(Y_g\)–\(\Delta\) entered where the plant is \(Y_g\)–\(Y\), or an earthing switch modelled as closed when it is open, removes an earth path and raises \(Z_0\). Confirm by physically checking the nameplates and the neutral earthing arrangement of every transformer within two buses.

    Cause 2: \(x_0/x_1\) assumed as 3 when it is higher. A ratio of 3.5 rather than 3.0 raises \(Z_0\) by 15% and reduces the earth-fault current by around 8%. Not enough alone, but it compounds. Confirm by a zero-sequence impedance measurement on the line, or by the line's design data.

    Cause 3: mutual coupling with a parallel circuit neglected. If the faulted circuit shares a tower with another, and that other was out of service and earthed, the coupling changes the effective \(Z_0\) substantially. Confirm by checking the switching state at the time of the fault against the study's assumption.

    Cause 4: fault impedance. The measurement is of a real fault with an arc; the study assumes a solid fault. An arc of 1–2 Ω on a 132 kV system is 0.1–0.2 pu, which is comparable to the whole \(Z_0\). Confirm by the recorded voltage at the fault point — a solid fault gives zero, an arc gives a few kilovolts.

    The diagnosis strategy. Compute the \(Z_0\) the measurement implies:

    \[ \frac{8.0}{5.2} = 1.54 \quad\Rightarrow\quad 2Z_1 + Z_0^{\text{true}} = 1.54\left(2Z_1+Z_0^{\text{assumed}}\right) \]

    and see which of the four causes could account for that much. A 54% increase in the total sequence impedance is too large for causes 2 or 4 alone and is characteristic of a missing earth path — so cause 1 is the working hypothesis, and it is the one to check first because it costs nothing to check.

    The general lesson: when a fault study disagrees with a measurement, suspect the topology before the impedances. Impedance errors give tens of per cent; topology errors give factors.

Self-Test

Multiple-Choice Questions

  1. MCQ 1. For a transmission line:
    (a) \(Z_1 = Z_2 = Z_0\)   (b) \(Z_1 = Z_2 \ne Z_0\)   (c) \(Z_1 \ne Z_2 = Z_0\)   (d) all three differ

    Show answer
    (b). Static elements cannot distinguish the two rotating sequences, but zero sequence returns through earth. Problems 2 and 4.
  2. MCQ 2. A synchronous machine's zero-sequence reactance is small because:
    (a) the winding resistance is low   (b) the zero-sequence MMF cancels in space   (c) the rotor screens it   (d) of saturation

    Show answer
    (b) — no rotating field is produced, so only leakage remains. Problem 3.
  3. MCQ 3. For an overhead line, \(x_0/x_1\) is typically:
    (a) 1   (b) 2   (c) 3   (d) 10

    Show answer
    (c), because the earth-return loop is far larger than the phase-to-phase one. Problem 4.
  4. MCQ 4. Carson's equivalent depth \(D_e\) depends on:
    (a) conductor size   (b) soil resistivity and frequency   (c) phase spacing   (d) line length

    Show answer
    (b) — \(658.4\sqrt{\rho/f}\). But the earth resistance term depends on frequency alone. Problem 5.
  5. MCQ 5. A delta winding in the zero-sequence network is drawn as:
    (a) an open circuit to the line   (b) a short to the line   (c) a connection to the reference bus   (d) both (a) and (c)

    Show answer
    (d). It blocks the line and provides a circulating path — drawn as a connection from the transformer's internal node to the reference. Problem 8.
  6. MCQ 6. Which connection passes zero-sequence current from one side to the other?
    (a) \(Y_g\)–\(\Delta\)   (b) \(Y_g\)–\(Y_g\)   (c) \(\Delta\)–\(\Delta\)   (d) \(Y\)–\(Y\)

    Show answer
    (b), and only that one. Problem 8.
  7. MCQ 7. An earth fault exceeds a three-phase fault when:
    (a) \(Z_0 > Z_1\)   (b) \(Z_0 < Z_1\)   (c) \(Z_0 = Z_1\)   (d) never

    Show answer
    (b). The ratio is \(3Z_1/(2Z_1+Z_0)\), which exceeds 1 exactly when \(Z_0 < Z_1\). Problem 14.
  8. MCQ 8. Zero-sequence mutual coupling between two circuits on one tower is about:
    (a) 1% of the self   (b) 10%   (c) 60%   (d) 200%

    Show answer
    (c) — against 1–5% in the positive sequence. It moves distance-relay reach by up to 30%. Problem 7.
  9. MCQ 9. Which network contains sources?
    (a) all three   (b) positive only   (c) positive and negative   (d) zero only

    Show answer
    (b). Machine EMFs are a balanced \(abc\) set. Problem 19.
  10. MCQ 10. A system is "effectively earthed" if:
    (a) \(X_0/X_1 \le 3\) and \(R_0/X_1 \le 1\)   (b) \(Z_n = 0\)   (c) every neutral is earthed   (d) \(Z_0 = Z_1\)

    Show answer
    (a), which bounds the healthy-phase rise at 1.4 and permits 80%-rated arresters. Problem 9.
  11. MCQ 11. An isolated-neutral system on an earth fault has healthy phases at:
    (a) nominal   (b) \(1.4\times\) nominal   (c) \(\sqrt3\times\) nominal   (d) zero

    Show answer
    (c), sustained — which is why the insulation must be rated line-to-line. Problem 9.
  12. MCQ 12. Adding an earthing transformer at one bus:
    (a) affects that bus most and others little   (b) affects all buses equally   (c) affects only remote buses   (d) has no effect

    Show answer
    (a) — 73% at the bus itself, 2–13% elsewhere. That locality is what makes it a usable design lever. Problem 17.
Reference

Key Formulas

QuantityRelationNotes
Sequence impedances\(Z_0 = Z_s+2Z_m\), \(Z_1 = Z_2 = Z_s-Z_m\)Balanced element
Static element\(Z_1 = Z_2\) exactlyLines, cables, transformers
Machine\(Z_1 = jx''_d\), \(Z_2 = j(x''_d+x''_q)/2\)\(Z_0 \approx 0.15\)–0.6 of \(x''_d\)
Line inductances\(L_s = 0.2\ln(D_e/\text{GMR})\), \(L_m = 0.2\ln(D_e/\text{GMD})\)mH/km
Carson depth\(D_e = 658.4\sqrt{\rho/f}\) m294–2944 m over normal soils
Earth resistance\(r_e = 9.869\times10^{-4}f\) Ω/kmIndependent of soil
Zero-sequence resistance\(r_0 = r_c + 3r_e\)About twice \(r_1\)
Zero-sequence mutual\(L_{0M} = 0.6\ln(D_e/D_{AB})\)50–70% of the self
Neutral earthingappears as \(3Z_n\)Zero-sequence network only
Effectively earthed\(X_0/X_1 \le 3\), \(R_0/X_1 \le 1\)Healthy-phase rise \(\le 1.4\)
Fault ratio\(I_{LG}/I_{3\phi} = 3Z_1/(2Z_1+Z_0)\)Maximum 1.5
Earth wire effect\(Z_0 = Z_0' - Z_{0w}^{2}/Z_{ww}\)Lowers \(x_0\), raises \(r_0\)
Three-winding star\(Z_H = \tfrac{1}{2}(Z_{HM}+Z_{HL}-Z_{ML})\)\(Z_L\) is often negative
Residual compensation\(k_0 = (Z_0-Z_1)/3Z_1\)Distance relay setting
Diagnostics

Common Mistakes

  1. Drawing the zero-sequence network with the positive-sequence topology. The connectivity comes from winding connections, not from the single-line diagram — Problems 8 and 12.

  2. Including a machine in the zero-sequence network behind a delta. The delta blocks it entirely; the machine is absent — Problem 12.

  3. Writing \(Z_n\) rather than \(3Z_n\). Still the commonest error in Part 5 — Problem 9.

  4. Applying \(Z_0 = 3Z_1\) at a bus. The rule is for lines; at a network bus the ratio ranged from 0.51 to 1.55 — Problem 13.

  5. Applying the overhead-line rule to a cable. A bonded cable's ratio is 1–2, not 3 — Problem 6.

  6. Neglecting zero-sequence mutual coupling on a double-circuit line. It is 60%, not the 1–5% of the positive sequence — Problem 7.

  7. Assuming a three-phase fault is always the worst. At a solidly-earthed transformer terminal the earth fault can exceed it by 20% — Problem 14.

  8. Putting sources in the negative- or zero-sequence networks. Machine EMFs are pure positive sequence — Problem 19.

  9. Forgetting that a transformer's \(Z_0\) equals its \(Z_1\). The question is whether a path exists, not what the impedance is — Problem 2.

  10. Using the same zero-sequence network for every switching state. Losing one earthed transformer can make \(Z_0\) infinite — Problem 16.

  11. Sizing an earthing transformer as small as possible. A very low \(Z_0\) can push the earth-fault level above the switchgear rating — Problem 17.

  12. Suspecting the impedances when a study disagrees with a measurement. Topology errors give factors; impedance errors give tens of per cent — Challenge C3.

Looking Ahead

Three networks now exist for the five-bus system, and they are strikingly unalike. The positive-sequence one is Part 4's, unchanged. The negative-sequence one is the same network with the sources removed. The zero-sequence one has three times the line reactance, two earth connections where the positive-sequence network has two generators, and no machines at all — and its diagonal ranges from half the positive-sequence value at the transformer buses to one and a half times it at bus 5.

Set 23 connects them. Each fault type imposes two boundary conditions on the six terminals of Problem 15, and each pair of conditions corresponds to one interconnection: series for a line-to-earth fault, parallel opposition for a line-to-line fault, and a three-way parallel for a double line-to-earth fault. The arithmetic that follows is one series or parallel combination, and the four standard faults are then computed at every bus of the system.