Set 3 — Per-Unit Quantities
Twenty worked problems on the change of variable that makes power system analysis tractable. Express every quantity as a fraction of a base value chosen per voltage zone, and three things happen at once: transformer turns ratios disappear from the impedance diagram, the \(\sqrt{3}\) factors of Set 1 cancel identically, and every machine impedance falls into a narrow, memorable range regardless of its size. The price is one piece of discipline — the bases must be chosen consistently — and almost every error in this topic is a violation of it.
Two bases are chosen; the rest follow. Pick \(\text{MVA}_B\) — one value for the entire system — and \(\text{kV}_B\) for one zone. Everything else is derived, never chosen: \(Z_B = \text{kV}_B^2/\text{MVA}_B\) and \(I_B = \text{MVA}_B/(\sqrt{3}\,\text{kV}_B)\).
The base MVA is common to the whole network; the base kV changes at every transformer, in the ratio of its nameplate. A network with three voltage levels has three base voltages and one base MVA. Getting this backwards is the single most common structural error in the subject.
Base change: \(Z_{pu,\text{new}} = Z_{pu,\text{old}}\left(\dfrac{\text{MVA}_{B,\text{new}}}{\text{MVA}_{B,\text{old}}}\right)\left(\dfrac{\text{kV}_{B,\text{old}}}{\text{kV}_{B,\text{new}}}\right)^{2}\). Note the directions — MVA the right way up, kV inverted and squared. Manufacturers quote impedance on the equipment's own rating, so this conversion is needed for almost every component in a real study.
A transformer's per-unit impedance is the same referred to either winding, provided the base voltages on the two sides are in the transformer's own ratio. This is the whole point of the method: it is what removes the ideal transformer from the impedance diagram.
Percent impedance is per-unit \(\times\,100\). Nothing more. A "5% transformer" has \(Z_{pu} = 0.05\) on its own rating.
Short-circuit MVA \(= \text{MVA}_B/Z_{pu}\). The reciprocal relationship means a low per-unit impedance implies a high fault level — which is why transformer impedance is deliberately specified, not merely tolerated.
Three-phase quantities and per-phase quantities give the same base impedance. \(Z_B = \text{kV}_{LL}^2/\text{MVA}_{3\phi} = \text{kV}_{LN}^2/\text{MVA}_{1\phi}\) identically. This is why per-unit calculations never carry an explicit \(\sqrt{3}\) or a factor of 3 — they cancel by construction.
A three-phase system is to be analysed on a base of 100 MVA and 132 kV. Find the base impedance, the base current and the base phase voltage, and verify that they are mutually consistent.
Base impedance, from the two chosen bases:
Base current, from three-phase apparent power:
Base phase voltage:
The consistency check — Ohm's law must hold among the bases themselves:
This is not a coincidence but a design requirement of the per-unit system. If the bases did not satisfy Ohm's law among themselves, then \(V_{pu} = I_{pu}Z_{pu}\) would not hold and the whole scheme would collapse.
A three-phase generator rated 1000 kVA, 33 kV has an armature resistance of 20 \(\Omega\)/phase and a synchronous reactance of 70 \(\Omega\)/phase. Calculate the per-unit impedance of the generator.
With no other system specified, the machine's own ratings are the natural choice of base:
Base impedance:
Per-unit impedance is simply the ohmic value divided by the base:
In magnitude and angle:
A generator has a sub-transient reactance \(X'' = 0.25\) p.u. on its own rating of 25 MVA, 11 kV. Find \(X''\) on (a) a 100 MVA, 11 kV base and (b) a 100 MVA, 13.8 kV base.
The base-change formula follows directly from the fact that the ohmic impedance is a property of the machine and does not change:
aThe voltage base is unchanged, so only the MVA ratio acts:
bNow both ratios act, and the voltage ratio is inverted and squared:
Sanity check via ohms, which should be invariant. On the machine's own base, \(Z_B = 11^2/25 = 4.84\ \Omega\), so \(X'' = 0.25(4.84) = 1.21\ \Omega\). On the 100 MVA, 13.8 kV base, \(Z_B = 13.8^2/100 = 1.9044\ \Omega\):
A three-phase \(\Delta\)–Y transformer rated 100 kVA, 11 kV/400 V has primary and secondary leakage reactances of 12 \(\Omega\)/phase and 0.05 \(\Omega\)/phase respectively. Calculate the per-unit reactance referred to each side and comment on the result.
The line-voltage ratio, which is what must be used for a three-phase bank irrespective of the winding connections:
Case 1 — HV side as base. \(\text{kV}_B = 11\), \(\text{MVA}_B = 0.1\):
Case 2 — LV side as base. \(\text{kV}_B = 0.4\), \(\text{MVA}_B = 0.1\):
The two are identical. In ohms the reactance differs by a factor of 756; in per-unit it does not differ at all.
A 500 kVA, 11 kV/415 V distribution transformer is marked "impedance 5%". Find its impedance in ohms referred to the HV side and to the LV side, and verify the relation between them.
Percent impedance is nothing more than per-unit impedance multiplied by 100, always on the equipment's own rating:
HV side:
LV side:
The two ohmic values must be related by the square of the turns ratio:
The 500 kVA, 11 kV/415 V, 5% transformer of Problem 5 is supplied from a source of effectively infinite fault level. Find the short-circuit MVA and the symmetrical fault current at its LV terminals.
With an infinite source the pre-fault voltage stays at 1.0 p.u. and the only impedance in the loop is the transformer's own:
Short-circuit MVA follows immediately:
Base current on the LV side:
Hence the fault current:
Two generators operate in parallel on the same 11 kV bus:
- \(G_1\): 50 MVA, 11 kV, \(X'' = 0.20\) p.u.
- \(G_2\): 75 MVA, 11 kV, \(X'' = 0.15\) p.u.
Using a common base of 100 MVA, 11 kV, find each reactance on the common base, the equivalent reactance of the pair, and the fault MVA at the bus.
The two reactances are quoted on different bases and cannot be combined until they are on the same one. This is the step most often skipped, and skipping it is not a small error — here it would misstate the fault level by more than 30%.
The voltage bases are already equal at 11 kV, so only the MVA ratio acts.
The two machines are in parallel as seen from the bus:
Fault MVA at the bus:
Check by adding the individual contributions, each computed on its own rating:
For the single-line diagram shown, take a base of 50 MVA and 11 kV in the generator zone. Express every series reactance in per-unit on that base.
- \(G\): 25 MVA, 11 kV, \(X = 0.20\) p.u.
- \(T_1\): 30 MVA, 11/132 kV, \(X = 0.10\) p.u.
- Line: \(100\ \Omega\) reactance at 132 kV
- \(T_2\): 25 MVA, 132/33 kV, \(X = 0.08\) p.u.
Step 1 — mark the zones. Transformers divide the system into three zones. The base MVA of 50 applies to all of them; the base voltage changes at each transformer in that transformer's nameplate ratio:
The base voltages happen to coincide with the nameplate voltages here because the transformer ratios are consistent. When they are not — a 11/130 kV transformer feeding a 132 kV line, say — the base follows the transformer ratio, not the line's nominal voltage.
Step 2 — generator. Same voltage base, different MVA base:
Step 3 — transformer \(T_1\). Its rated voltages match the zone bases on both sides, so only the MVA ratio acts:
Step 4 — the line. Its ohms must be divided by the base impedance of zone 2:
Step 5 — transformer \(T_2\):
Step 6 — the series total. Because every ideal transformer has vanished, these four reactances are simply in series:
For the system of Problem 8, find the base current in each of the three zones and verify that the ratios match the transformer ratios.
Base current uses the same base MVA everywhere and the zone's own base voltage:
Checking the ratios against the transformers:
The consequence is worth stating explicitly: a current of, say, 0.9 p.u. flowing through the whole radial system is 2362 A at 11 kV, 196.8 A at 132 kV and 787.3 A at 33 kV — one per-unit number, three ammeter readings.
A load of 40 MW at 0.8 power factor lagging is supplied at 33 kV. Using a base of 50 MVA, 33 kV, express the load as a per-unit complex power, a per-unit current and a per-unit impedance, assuming the bus voltage is at 1.0 p.u. Convert the impedance back to ohms.
Apparent power of the load:
In per-unit on a 50 MVA base:
Note that the real part is numerically the power factor and the imaginary part is \(\sin\phi\) — a pleasant consequence of the base having been chosen equal to the load's own apparent power.
Per-unit current, from \(S = VI^{*}\) with \(V = 1.0\angle0^\circ\):
Per-unit impedance:
Back to ohms:
A 33 kV feeder of impedance \((5 + j12)\,\Omega\) supplies a load of 8 MVA at 0.85 power factor lagging. Using a base of 10 MVA, 33 kV and taking the receiving-end voltage as 1.0 p.u., find the sending-end voltage in per-unit and in kV, and the voltage regulation.
Base impedance and the feeder in per-unit:
Load current in per-unit, with \(\mathbf{V}_R = 1.0\angle0^\circ\) as reference:
Voltage drop along the feeder:
Sending-end voltage:
Voltage regulation:
A three-winding transformer has ratings: primary 66 kV, 15 MVA; secondary 13.2 kV, 10 MVA; tertiary 2.3 kV, 5 MVA. Short-circuit tests give
Find the star-equivalent impedances \(Z_p\), \(Z_s\), \(Z_t\) on a common base of 15 MVA, 66 kV.
The three measurements are on two different MVA bases. Bring \(Z_{st}\) onto the common 15 MVA base first — nothing can be combined until they agree:
Each measured impedance is the sum of two arms of the star equivalent, since a short-circuit test energises two windings and shorts one:
Three equations, three unknowns. Adding all three and halving gives \(Z_p + Z_s + Z_t\), and subtracting each measurement in turn isolates one arm:
Verifying against the measurements:
A 5000 hp, 6.6 kV synchronous motor operates at 0.85 power factor with an efficiency of 92% and has \(X'' = 0.20\) p.u. on its own rating. Find its rating in kVA and its sub-transient reactance on a 25 MVA, 6.6 kV system base.
The horsepower figure is mechanical output. Convert to kilowatts:
Electrical input, using the efficiency:
Apparent power — this is the machine's own MVA base, and it is what the manufacturer's 0.20 p.u. refers to:
Base change to the system base. The voltage bases agree at 6.6 kV, so only the MVA ratio acts:
Cross-check in ohms. On its own base, \(Z_B = 6.6^2/4.77 = 9.132\ \Omega\), so \(X'' = 1.826\ \Omega\). On the system base, \(Z_B = 6.6^2/25 = 1.742\ \Omega\):
A transmission line of 80 \(\Omega\) reactance operates at 132 kV. On a 100 MVA base, find its per-unit reactance. Then compute what would result if the base voltage of the 33 kV zone were mistakenly used, and quantify the consequence for a fault calculation.
The correct calculation, using the base voltage of the zone the line actually occupies:
The erroneous calculation, using 33 kV:
The error factor is the square of the voltage ratio:
The consequence for a fault study. If this line were the only impedance in the loop, the correct fault level is
A sixteen-fold understatement of the fault level. Switchgear selected on the wrong figure would be catastrophically under-rated, and the error would not reveal itself until the first fault.
In a 100 MVA, 11 kV zone a machine carries a current of \(0.85\angle -25^\circ\) p.u. at a terminal voltage of \(1.0\angle 0^\circ\) p.u. Find the actual current in amperes, the actual terminal voltage, and the real and reactive power in MW and Mvar.
Base current for the zone:
Actual current — magnitude scaled by the base, angle carried straight through:
Actual terminal voltage, a line value since the base is a line value:
Complex power in per-unit:
And in real units, scaling by the base MVA:
Show that the base impedance computed from three-phase quantities and from per-phase quantities is identical, and verify numerically for a 30 MVA, 33 kV system.
Start from the per-phase definition, which is the physically meaningful one — impedance is a per-phase quantity:
Substitute the line-to-neutral voltage and the base current in terms of three-phase quantities:
Dividing, the two \(\sqrt3\) factors cancel exactly:
Now the per-phase route. Here \(\text{MVA}_{1\phi} = \text{MVA}_{3\phi}/3\) and \(\text{kV}_{LN} = \text{kV}_{LL}/\sqrt3\):
The factor of 3 in the numerator and the factor of 3 in the denominator are the same factor of 3, and they cancel. The two definitions are one definition.
Numerically, for 30 MVA and 33 kV:
For the system of Problem 8, with a total series reactance of 1.014 p.u. on a 50 MVA base, find the per-unit fault current, the fault MVA and the actual fault current for a three-phase fault at the 33 kV bus. Assume 1.0 p.u. pre-fault voltage.
Per-unit fault current, from a single application of Ohm's law to the whole three-voltage-level system:
Fault MVA:
Actual fault current at the 33 kV bus, using the base current of zone 3 found in Problem 9:
The same fault expressed in the other zones — one per-unit current, three ammeter readings:
Note how modest this fault level is. At 49.3 MVA the 33 kV bus is weak, because the 0.287 p.u. line reactance and the 0.40 p.u. generator reactance dominate the loop.
A 30 MVA, 11 kV generator with \(X'' = 0.15\) p.u. supplies a 30 MVA, 11/132 kV transformer with \(X = 0.10\) p.u. Find the fault MVA and fault current for a three-phase fault (a) at the generator terminals and (b) on the 132 kV side of the transformer.
Both items are already on a 30 MVA base and their rated voltages match the zone bases, so no base change is needed. Take \(\text{MVA}_B = 30\).
aFault at the generator terminals. The transformer is on the far side of the fault and carries no fault current, so only the generator reactance is in the loop:
bFault on the 132 kV side. Now both reactances are in series:
Both results in one table:
Three identical single-phase transformers, each rated 20 MVA, 66 kV/11.55 kV with \(X = 0.08\) p.u. on its own rating, are connected as a bank with the HV windings in delta and the LV windings in star. Find the three-phase rating, the line-voltage ratio of the bank, and the per-unit reactance on the bank's own three-phase base.
Three-phase rating. Each unit contributes its full rating:
HV side, delta. Each winding stands across a line pair, so the line voltage equals the winding voltage:
LV side, star. Each winding stands between a line and the neutral, so the line voltage is \(\sqrt3\) times the winding voltage:
Per-unit reactance. Take the LV side. The winding reactance in ohms, on the unit's own single-phase base:
Now the bank's own three-phase base on the LV side:
Unchanged. The \(\sqrt3\) on the voltage was squared to 3 in the base impedance, and the factor of 3 on the MVA cancelled it exactly.
Draw the per-unit impedance diagram for the system below on a base of 10 MVA, 13.8 kV in the generator zone, and find the generator internal voltage required to hold 1.0 p.u. at the load.
- \(G\): 10 MVA, 13.8 kV, \(X = 0.15\) p.u.
- \(T_1\): 10 MVA, 13.8/138 kV, \(X = 0.10\) p.u.
- Line: 20 km at \(j0.5\ \Omega/\text{km}\)
- \(T_2\): 5 MVA, 138/13.8 kV, \(X = 0.08\) p.u.
- Load: 4 MW at 0.9 p.f. lagging, 13.8 kV
Zone bases. One base MVA of 10 throughout; base voltages follow the transformer ratios:
Generator and \(T_1\). Both are already on 10 MVA with matching voltage bases, so they transfer unchanged:
Line. Total reactance \(20 \times 0.5 = 10\ \Omega\), divided by the zone-2 base impedance:
Negligible against everything else — a short line at a high voltage is electrically almost nothing, which is precisely the argument for transmitting at 138 kV rather than 13.8 kV.
Transformer \(T_2\). Rated 5 MVA, so a base change is required:
Total series reactance:
Load current. With \(\mathbf{V}_{\text{load}} = 1.0\angle0^\circ\):
Generator internal voltage:
Actual currents, using the zone base currents \(I_{B1} = I_{B3} = 418.4\) A and \(I_{B2} = 41.84\) A:
Practice Problems
Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not.
P1. Find the base impedance and base current for a base of 200 MVA, 220 kV.
Show answer
\(Z_B = 220^2/200 = \mathbf{242}\ \Omega\); \(I_B = 200\times10^6/(\sqrt3\cdot220\,000) = \mathbf{524.9}\) A.P2. A transformer is 8% on 20 MVA. What is its per-unit impedance on a 100 MVA base?
Show answer
\(0.08(100/20) = \mathbf{0.40}\) p.u. A common slip is to divide instead of multiply — remember that a smaller machine looks more impedant on a larger base.P3. A generator is \(X'' = 0.12\) p.u. on 60 MVA, 13.8 kV. Find its reactance in ohms.
Show answer
\(Z_B = 13.8^2/60 = 3.174\ \Omega\), so \(X'' = 0.12(3.174) = \mathbf{0.381}\ \Omega\).P4. A 25 MVA transformer of 6% impedance feeds a bus from an infinite source. Find the fault MVA and comment on the switchgear rating needed at 11 kV.
Show answer
\(25/0.06 = \mathbf{417}\) MVA. At 11 kV that is \(417\times10^6/(\sqrt3\cdot11\,000) = \mathbf{21.9}\) kA, so 25 kA switchgear would be the next standard rating up.P5. A 132 kV line has 60 \(\Omega\) reactance. Find its per-unit value on 100 MVA, and check it lies in the usual band.
Show answer
\(60/174.24 = \mathbf{0.344}\) p.u. — within the 0.05–0.5 band expected of a transmission line on a 100 MVA base, so no base error is indicated.P6. Two transformers, 10 MVA at 5% and 15 MVA at 6%, operate in parallel. Find the equivalent per-unit impedance on a 25 MVA base.
Show answer
On 25 MVA: \(0.125\) and \(0.10\). Parallel: \((0.125)(0.10)/0.225 = \mathbf{0.0556}\) p.u. Check by fault level: \(200 + 250 = 450\) MVA, and \(25/0.0556 = 450\) MVA ✓P7. A base of 50 MVA, 11 kV is chosen in the generator zone of a system whose step-up transformer is 11/220 kV. What are the base voltage and base current in the transmission zone?
Show answer
\(\mathbf{220}\) kV and \(50\times10^6/(\sqrt3\cdot220\,000) = \mathbf{131.2}\) A. The base MVA stays at 50 — it never changes across a transformer.P8. A 15 MVA, 11 kV machine has \(X'' = 0.18\) p.u. What is the symmetrical short-circuit current at its terminals?
Show answer
\(I_B = 787.3\) A, so \(I_f = 787.3/0.18 = \mathbf{4374}\) A. Equivalently \(15/0.18 = 83.3\) MVA.P9. A load draws 0.6 p.u. current at 0.9 p.u. voltage with a 0.8 lagging power factor. Find \(P\) and \(Q\) in per-unit.
Show answer
\(S = (0.9)(0.6) = 0.54\) p.u., so \(P = \mathbf{0.432}\) and \(Q = \mathbf{0.324}\) p.u.P10. Three single-phase units of 10 MVA, 33/6.35 kV, 7% are connected Y–Y. Find the bank's three-phase rating, line-voltage ratio and per-unit impedance.
Show answer
\(\mathbf{30}\) MVA; ratio \(\sqrt3(33)/\sqrt3(6.35) = \mathbf{57.2/11}\) kV; impedance \(\mathbf{7\%}\) — unchanged, as always.P11. On a 100 MVA base, a system has 0.05 p.u. source reactance and a 0.10 p.u. transformer. Find the fault MVA at the transformer's LV terminals.
Show answer
\(100/0.15 = \mathbf{667}\) MVA. Note the source is much the stronger of the two, so the transformer sets the fault level.P12. A 400 kV line of 90 \(\Omega\) is computed as 0.9 p.u. on a 100 MVA base. Is this plausible? If not, what base voltage was probably used?
Show answer
Not plausible — the correct value is \(90/(400^2/100) = 90/1600 = \mathbf{0.056}\) p.u. A result of 0.9 implies \(Z_B = 100\ \Omega\), i.e. a base of \(\mathbf{100}\) kV was used instead of 400 kV.
Challenge Problems
Each of these needs an idea rather than a formula. Decide what the governing principle is before opening the answer.
C1. Prove that a transformer's per-unit impedance is identical referred to either winding, and identify the precise condition on the base voltages under which the proof holds. What goes wrong in the impedance diagram if that condition is violated — for example, if a designer picks 11 kV and 132 kV as bases for a transformer actually wound 11/138 kV?
Show answer
Let the transformer have turns ratio \(a = V_1/V_2\) and impedance \(Z_2\) referred to side 2. Referred to side 1 it is \(Z_1 = a^2Z_2\). With base voltages \(V_{B1}, V_{B2}\) and common \(S_B\):These are equal if and only if \(a^2/V_{B1}^2 = 1/V_{B2}^2\), that is \(V_{B1}/V_{B2} = a\).\[ \frac{Z_1}{Z_{B1}} = \frac{a^2Z_2}{V_{B1}^2/S_B} = \frac{a^2 Z_2 S_B}{V_{B1}^2}, \qquad \frac{Z_2}{Z_{B2}} = \frac{Z_2S_B}{V_{B2}^2} \]
The condition: the base voltages must stand in exactly the transformer's own turns ratio. Nothing else is required — the absolute values are free.
If violated: with bases 11/132 on a 11/138 kV transformer, \(V_{B1}/V_{B2} = 12\) but \(a = 12.545\). The two per-unit impedances now differ by \((12.545/12)^2 = 1.093\), so the impedance is 9.3% larger seen from one side than the other. The ideal transformer can no longer be deleted: what remains is an off-nominal-ratio ideal transformer of ratio \(1{:}1.045\) that must be retained in the model.
This is not a pathology to be avoided — it is exactly how tap-changing transformers are represented in load flow, as a per-unit impedance plus a residual ideal transformer of ratio \(1{:}t\). What the per-unit system removes is the nominal ratio; the deviation from nominal is real, controllable, and is the whole mechanism of voltage control in Set 34.C2. Machine reactances cluster in narrow per-unit bands almost independently of rating — sub-transient reactance is near 0.15 p.u. for a 10 MVA machine and for a 1000 MVA machine alike. Explain physically why this should be so, and what it implies about the fault current a machine can deliver relative to its own rating.
Show answer
Per-unit reactance is \(X_{pu} = X\,S_{\text{rated}}/V_{\text{rated}}^2\). Now \(X\) itself scales with the machine's geometry: reactance \(\propto N^2\mu A/\ell\) and rated voltage \(\propto N\phi f\), while rated MVA \(\propto\) the machine's active volume. Working the scaling through, the geometric factors cancel to leading order and \(X_{pu}\) depends on proportions — airgap length relative to bore, winding depth relative to pole pitch — not on absolute size.
Those proportions are fixed by the same physics for every machine: the airgap must be small enough that the excitation is economical and large enough that mechanical clearance and armature reaction are tolerable. Designers of a 10 MVA and a 1000 MVA machine face the same optimum and arrive at the same ratios, so both land near \(X'' \approx 0.15\) p.u.
Implication: every synchronous machine delivers roughly \(1/0.15 \approx 6\text{--}7\) times its own rated current into a terminal fault, regardless of size. This is why fault levels track installed capacity so closely, why a network planner can estimate a fault level from a one-line diagram before any data arrives, and why a per-unit value far outside the band is a data error rather than an unusual machine — the argument of Problems 2 and 14.C3. The per-unit system is often described as "dimensionless". Examine that claim carefully. Is a per-unit voltage the same kind of object as a per-unit impedance? What breaks if one uses two different base MVAs in different parts of the same network, and why is this different from using different base kV?
Show answer
Dimensionless, but not interchangeable. Each per-unit quantity is a pure number, but it is a ratio to a different base, and those bases carry the dimensions. A per-unit voltage of 1.05 and a per-unit impedance of 1.05 are both dimensionless and mean entirely unrelated things. What the system guarantees is that the relations between them survive: \(V_{pu} = I_{pu}Z_{pu}\) and \(S_{pu} = V_{pu}I_{pu}^*\) hold only because the four bases were chosen to satisfy those same relations, as verified in Problem 1.
Two base MVAs: catastrophic. Suppose zone 1 uses 100 MVA and zone 2 uses 50. A current of 1.0 p.u. flowing from zone 1 into zone 2 becomes 2.0 p.u. on crossing the boundary — but no transformer is present to justify a change, and KCL is violated at the boundary node. The network is no longer a connected circuit; series impedances can no longer simply be added, and every fault and load-flow result is wrong.
Two base kVs: not merely allowed but required. The base voltage must change at every transformer, in the transformer's ratio — and it does so precisely because a real transformer is there to change the real voltage. The base change mirrors a physical change; that is why it is legitimate. There is no physical device that changes MVA, so there is no justification for a base MVA that changes.
The asymmetry, then, is not a convention: base voltage tracks a physical transformation that actually occurs, and base MVA tracks a conserved quantity that does not.
Multiple-Choice Questions
MCQ 1. The base impedance of a three-phase system is:
(a) \(\text{kV}_{LL}^2/\text{MVA}\) (b) \(\sqrt3\,\text{kV}_{LL}^2/\text{MVA}\) (c) \(\text{kV}_{LL}^2/(3\,\text{MVA})\) (d) \(\text{kV}_{LL}/\text{MVA}\)Show answer
(a). No \(\sqrt3\) or 3 appears — they cancel identically, as shown in Problem 16.MCQ 2. In a network with four voltage levels, the number of base MVA values is:
(a) 1 (b) 2 (c) 4 (d) depends on the transformersShow answer
(a) one. The base MVA is common to the entire network; only the base kV changes, once per transformer.MCQ 3. A transformer's per-unit impedance referred to the primary compared with that referred to the secondary is:
(a) larger by \(a^2\) (b) smaller by \(a^2\) (c) equal (d) larger by \(a\)Show answer
(c) equal — provided the base voltages stand in the transformer's ratio. This is the property that removes the ideal transformer from the diagram.MCQ 4. An impedance of \(Z_{pu}\) on \(\text{MVA}_1\) becomes, on \(\text{MVA}_2\) at the same voltage base:
(a) \(Z_{pu}\,\text{MVA}_1/\text{MVA}_2\) (b) \(Z_{pu}\,\text{MVA}_2/\text{MVA}_1\) (c) \(Z_{pu}(\text{MVA}_2/\text{MVA}_1)^2\) (d) unchangedShow answer
(b). MVA goes the right way up, unsquared; only the kV ratio is inverted and squared.MCQ 5. A transformer marked 6% has a per-unit impedance, on its own rating, of:
(a) 6 (b) 0.6 (c) 0.06 (d) 0.006Show answer
(c) 0.06. Percent impedance is per-unit \(\times\,100\), nothing more.MCQ 6. The short-circuit MVA of a system of per-unit impedance \(Z_{pu}\) on base \(\text{MVA}_B\) is:
(a) \(\text{MVA}_B\,Z_{pu}\) (b) \(\text{MVA}_B/Z_{pu}\) (c) \(Z_{pu}/\text{MVA}_B\) (d) \(\sqrt3\,\text{MVA}_B/Z_{pu}\)Show answer
(b). Low impedance means a high fault level — the two are reciprocal.MCQ 7. Three single-phase transformers of per-unit impedance \(z\) each are connected as a Δ–Y bank. The bank's per-unit impedance is:
(a) \(z/3\) (b) \(3z\) (c) \(\sqrt3 z\) (d) \(z\)Show answer
(d) \(z\). The voltage-base and MVA-base changes cancel exactly, whatever the connection — Problem 19.MCQ 8. Base current and base voltage across a transformer are related by:
(a) both scale with the turns ratio (b) base current scales inversely with base voltage (c) base current is unchanged (d) base voltage is unchangedShow answer
(b). Their product, the base MVA, is common to the whole network, so one must fall as the other rises.MCQ 9. A sub-transient reactance computed as 8 p.u. on a 100 MVA base most likely indicates:
(a) a very small machine (b) a base error (c) a saturated machine (d) a correct value for a small generatorShow answer
(b) a base error. Even a very small machine on a 100 MVA base rarely exceeds 2–3 p.u. A value an order of magnitude out is a wrong base until proved otherwise.MCQ 10. In per-unit, the power factor of a load is:
(a) divided by the base (b) multiplied by \(\sqrt3\) (c) unchanged (d) referred to the base MVAShow answer
(c) unchanged. The transformation scales magnitudes by positive reals and leaves every angle alone, so any cosine of an angle is invariant.MCQ 11. Two areas of one network are analysed with base MVAs of 100 and 50 respectively. The result is:
(a) valid, if the base kVs are right (b) valid, but currents must be scaled (c) invalid — KCL is violated at the boundary (d) valid only for balanced systemsShow answer
(c). A per-unit current would change value at a boundary where no transformer exists. See Challenge C3.MCQ 12. One arm of a three-winding transformer's star equivalent comes out negative. This means:
(a) a measurement error (b) an arithmetic error (c) nothing is wrong — only the pairwise sums are physical (d) the transformer is faultyShow answer
(c). The star arms are a computational device; only \(Z_{ps}\), \(Z_{pt}\) and \(Z_{st}\) are measurable, and a negative arm is common in real data.
Key Formulas
| Quantity | Relation | Notes |
|---|---|---|
| Per-unit definition | \(X_{pu} = X_{\text{actual}}/X_{\text{base}}\) | Applies to every quantity alike |
| Base impedance | \(Z_B = \text{kV}_B^2/\text{MVA}_B\) | Line kV and three-phase MVA |
| Base impedance (per phase) | \(Z_B = \text{kV}_{LN}^2/\text{MVA}_{1\phi}\) | Identical value — the 3s cancel |
| Base current | \(I_B = \dfrac{\text{MVA}_B\times10^6}{\sqrt3\,\text{kV}_B\times10^3}\) | Amperes |
| Base consistency | \(Z_B = V_{B,LN}/I_B\) | Choose two bases only; derive the rest |
| Base change | \(Z_{pu}^{\text{new}} = Z_{pu}^{\text{old}}\dfrac{\text{MVA}_{new}}{\text{MVA}_{old}}\left(\dfrac{\text{kV}_{old}}{\text{kV}_{new}}\right)^{2}\) | MVA upright, kV inverted and squared |
| Percent impedance | \(\%Z = 100\,Z_{pu}\) | Always on the equipment's own rating |
| Short-circuit MVA | \(\text{MVA}_{sc} = \text{MVA}_B/Z_{pu}\) | Fault levels of parallel sources add |
| Fault current | \(I_f = I_B/Z_{pu}\) | Use the base current of the faulted zone |
| Base kV across a transformer | \(\text{kV}_{B2} = \text{kV}_{B1}\times\) nameplate ratio | MVA base never changes |
| Transformer p.u. | same from either side | Only if base kVs are in the turns ratio |
| Off-nominal ratio | residual ideal transformer \(1{:}t\) | What remains when bases ≠ turns ratio |
| Single-phase bank | \(S_{3\phi} = 3S_{1\phi}\), \(Z_{pu}\) unchanged | Any connection: Y–Y, Δ–Y, Y–Δ, Δ–Δ |
| Three-winding star arms | \(Z_p = \tfrac12(Z_{ps}+Z_{pt}-Z_{st})\) | Cyclic for \(Z_s\) and \(Z_t\); may be negative |
| Complex power | \(S_{pu} = V_{pu}I_{pu}^{*}\) | Same form as in real units |
| Angles | unchanged by the transformation | Power factor is base-independent |
| Sanity band — lines | \(0.05\)–\(0.5\) p.u. | On a 100 MVA base |
| Sanity band — transformers | \(0.05\)–\(0.15\) p.u. | On the transformer's own rating |
| Sanity band — machines | \(X'' \approx 0.15\) p.u. | Nearly independent of rating |
Common Mistakes
Changing the base MVA somewhere in the network. It is one value for the whole system. Changing it breaks KCL at the boundary and invalidates everything downstream — Challenge C3.
Inverting the base-change formula. MVA the right way up, kV inverted and squared. Getting the MVA ratio backwards is the single most frequent slip in the whole topic.
Using a zone's nominal voltage instead of the base derived from the transformer ratio. They coincide only when the transformer ratios are consistent. When they are not, the base follows the transformer and an off-nominal ratio remains in the model.
Dividing a line's ohms by the wrong zone's base impedance. Problem 14 shows the error is a factor of 16 for a 132/33 kV mix-up, and it is completely silent.
Forgetting to convert a manufacturer's impedance to the study base. Nameplate values are on the equipment's own rating. Problem 7 misstates the fault level by a third if this is skipped.
Introducing a \(\sqrt3\) into a per-unit calculation. There is never one. Its appearance means line and phase quantities have been mixed — treat it as an error indicator.
Taking a motor's horsepower as its MVA base. Convert through 0.746, then through efficiency, then through power factor — Problem 13.
Converting to amperes mid-calculation. Stay in per-unit until the final step, then convert once per zone using that zone's base current.
Assuming a per-unit impedance is dimensionless in the sense of being interchangeable. A 1.05 p.u. voltage and a 1.05 p.u. impedance are ratios to different bases and have nothing to do with one another.
Choosing \(Z_B\) or \(I_B\) independently. Only two bases are free. Choosing a third breaks the Ohm's-law consistency demonstrated in Problem 1, and every later result inherits the inconsistency silently.
Rejecting a negative arm in a three-winding equivalent. It is normal. Only the pairwise sums are physical quantities — Problem 12.
Not checking results against the sanity bands. A one-minute check of every element against its expected band catches nearly every base error before it propagates into a fault study.
The impedance diagram assembled in Problem 20 is a small thing — four reactances in series — but it is the same object, built the same way, that every remaining set in this book operates on. Set 4 develops it into a full reactance diagram for a multi-machine system, and from Set 16 onwards it is no longer drawn at all but stored as a matrix.
What the per-unit system bought was the right to treat that diagram as a single connected circuit. Transformers are gone; \(\sqrt3\) factors are gone; a machine, a line and a transformer add like resistors. Everything that follows — the \(Y\)-bus of Set 16, the Gauss–Seidel and Newton–Raphson iterations of Sets 19 and 20, the sequence networks of Set 22, the swing equation of Set 24 — is written in per-unit and would be almost unmanageable without it. The discipline of base selection practised here is therefore not an exercise in bookkeeping; it is the price of admission to the rest of the subject.