Per-Unit Quantities

Demonstrative Video


Revision of Important Formulas

\[\boxed{Z_B = \dfrac{KV_B^2}{MVA_B}}\]

\[\boxed{Z_{p u(n e w)}=Z_{p u(g i v e n)}\left[\frac{M V A_{B(n e w)}}{M V A_{B(g i v e n)}}\right]\left[\frac{k V_{B(g i v e n)}}{k V_{B(n e w)}}\right]^{2}}\]

Problem-1

A three-phase generator with rating 1000 kVA, 33 kV has its armature resistance and synchronous reactance as 20 \(\Omega\)/phase and 70 \(\Omega\)/phase. Calculate p.u. impedance of the generator.

Solution-1

Problem-2

A three phase, \(\Delta\) -Y transformer with rating \(100 \mathrm{kVA}, 11 \mathrm{kV} / 400 \mathrm{~V}\) has its primary and secondary leakage reactance as \(12 \Omega /\) phase and \(0.05 \Omega /\) phase respectively. Calculate the p.u. reactance of transformer.

Solution-2

Case-1: HV winding (primary) rating chosen as base value

Case-2: LV winding (secondary) rating chosen as base value

Note:

Problem-3

Using the P.U. system and taking into account the transformer percent impedances, solve for the current in each part of the three-phase system shown below. assume both transformers are either delta-delta or wye-wye connected and that there is no phase shift between primary and secondary current and voltage image

Solution-3

image

image

image

image

image

image

image

image

image

image

image

image