A three-phase generator with rating 1000 kVA, 33 kV has its armature resistance and synchronous reactance as 20 \(\Omega\)/phase and 70 \(\Omega\)/phase. Calculate p.u. impedance of the generator.
The generator ratings are chosen as base \(\mathrm{kV}\) and base \(\mathrm{kVA}\).
Base kilovolt, \(\mathrm{kV}_{\mathrm{b}}=33 \mathrm{kV}\)
Base kilovoltampere, \(\mathrm{kVA}_{\mathrm{b}}=1000 \mathrm{kVA}\)
A three phase, \(\Delta\) -Y transformer with rating \(100 \mathrm{kVA}, 11 \mathrm{kV} / 400 \mathrm{~V}\) has its primary and secondary leakage reactance as \(12 \Omega /\) phase and \(0.05 \Omega /\) phase respectively. Calculate the p.u. reactance of transformer.
Case-1: HV winding (primary) rating chosen as base value
Base kilovolt, \(\mathrm{kV}_{\mathrm{b}}=11 \mathrm{kV}\)
Base kilo volt-ampere, \(\mathrm{kVA}_{\mathrm{b}}=100 \mathrm{kVA}\)
Transformer line voltage ratio, \(\mathrm{K}=\dfrac{400}{11,000}=0.0364\)
Case-2: LV winding (secondary) rating chosen as base value
Base kilovolt, \(\mathrm{kV}_{\mathrm{b}}=400 / 1000=0.4 \mathrm{kV}\)
Base kilovoltampere, \(\mathrm{kVA}_{\mathrm{b}}=100 \mathrm{kVA}\)
Transformer line voltage ratio, \(\mathrm{K}=\dfrac{400}{11,000}=0.0364\)
p.u. reactance per phase, \(\mathrm{X}_{\mathrm{pu}}=\dfrac{\text { Total leakage reactance }}{\text { Base impedance }}=\dfrac{\mathrm{X}_{02}}{\mathrm{Z}_{\mathrm{b}}}=\dfrac{0.0659}{1.6}=0.0411 \mathrm{p}\).u.
Note:
It is observed that the p.u. reactance of a transformer referred to primary and secondary are same.
In \(3\phi\) transformer of the voltage ratio K is obtained using line values then using this value of K the phase impedance per phase of star-side can be directly transferred to delta side or vice versa
Step-1: Separate by Voltage zones
Step-2: Assign base values
Step-3: Calculate \(Z_B\) for each zones
Step-4: Calculate \(Z_{p.u.}\) for each zone
Step-5: Calculate \(Z_{p.u}\) for Tran-1
Step-6: Calculate \(Z_{p.u}\) for Tran-2
Step-7: Calculate p.u. current and voltages
Step-8: Use Ohm’s Law to calculate p.u. current
Step-9: Calculate \(I_B\) in each zone
Step-10: Calculate actual current in each zone
Step-11: Check using T/F ratios