Corona in Transmission Lines
Revision of Important Formulas
Problem-1
A 3 -phase line has conductors \(2 \mathrm{cm}\) in diameter spaced equilaterally \(1 \mathrm{m}\) apart. If the dielectric strength of air is \(30 \mathrm{kV/cm}\) (max), find the disruptive critical voltage for the line. Take air density factor \(\delta=0.952\) and irregularity factor \(m_{o}=0.9 .\)
Solution-1
Conductor radius, \(r=2 / 2=1 \mathrm{cm}\)
Conductor spacing \(d=1 \mathrm{m}=100 \mathrm{cm}\)
Dielectric strength of air, \(g_{o}=30~ \mathrm{kV} / \mathrm{cm}(\max .)=21 \cdot 2 ~\mathrm{kV}(\mathrm{rm.s.})\) per \(\mathrm{cm}\)
Disruptive critical voltage,
\[\begin{aligned} V_{c} &=m_{o} g_{o} \delta r \log _{e}(d / r)~ \mathrm{kV}^{*} / \mathrm{phase}(r . m . s . \text { value }) \\ &=0.9 \times 21 \cdot 2 \times 0.952 \times 1 \times \log _{e} 100 / 1=83 \cdot 64 \mathrm{kV} / \mathrm{phase} \end{aligned}\]Line voltage (r.m.s) =\(\sqrt{3} \times 83 \cdot 64=144 \cdot 8 \mathrm{kV}\)
Problem-2
A \(132 \mathrm{kV}\) line with \(1.956 \mathrm{cm}\) dia. conductors is built so that corona takes place if the line voltage exceeds \(210 \mathrm{kV}\) (r.m.s). If the value of potential gradient at which ionisation occurs can be taken as \(30 \mathrm{kV/cm}\), find the spacing between the conductors.
Solution-2
Assume the line is 3 -phase.
Conductor radius, \(r=1 \cdot 956 / 2=0 \cdot 978~ \mathrm{cm}\)
Dielectric strength of air, \(g_{o}=30 / \sqrt{2}=21 \cdot 2 \mathrm{kV}(\mathrm{r}\).m.s.\()\) per \(\mathrm{cm}\)
Disruptive voltage/phase, \(V_{c}=210 / \sqrt{3}=121 \cdot 25 \mathrm{kV}\)
Assume smooth conductors (i.e., irregularity factor \(m_{o}=1\) ) and standard pressure and temperature for which air density factor \(\delta=1\)
Let \(d ~\mathrm{cm}\) be the spacing between the conductors.
- Disruptive voltage (r.m.s) per phase is\[\begin{aligned} V_{c} &=m_{0} g_{o} \delta r \log _{e}(d / r) \mathrm{kV} \\ &=1 \times 21 \cdot 2 \times 1 \times 0.978 \times \log _{e}(d / r) \\ 121 \cdot 25 &=20 \cdot 733 \log _{e}(d / r) \\ \log _{e} \frac{d}{r} &=\frac{121 \cdot 25}{20 \cdot 733}=5.848 \\ 2 \cdot 3 \log _{10} d / r &=5 \cdot 848 \\ \log _{10} d / r &=5 \cdot 848 / 2 \cdot 3=2 \cdot 5426 \\ d / r &=\text { Antilog } 2 \cdot 5426 \\ d / r &=348 \cdot 8 \end{aligned}\]
Conductor spacing, \(d=348 \cdot 8 \times r=348 \cdot 8 \times 0.978=341 \mathrm{cm}\)
Problem-3
A 3-phase, \(220 \mathrm{kV}, 50 \mathrm{Hz}\) transmission line consists of \(1.5 \mathrm{cm}\) radius conductor spaced 2 metres apart in equilateral triangular formation. If the temperature is \(40^{\circ} \mathrm{C}\) and atmospheric pressure is \(76 \mathrm{cm},\) calculate the corona loss per km of the line. Take \(\mathrm{m}_{0}=0.85 .\)
Solution-3
- corona loss is given by:\[\begin{aligned} P &=\frac{242 \cdot 2}{\delta}(f+25) \sqrt{\frac{r}{d}}\left(V-V_{c}\right)^{2} \times 10^{-5} ~\mathrm{kW} / \mathrm{km} / \mathrm{phase} \\ \delta &=\frac{3 \cdot 92 b}{273+t}=\frac{3 \cdot 92 \times 76}{273+40}=0 \cdot 952\\ g_{o}&=21 \cdot 2~ \mathrm{kV} / \mathrm{cm}(\mathrm{rm.s.}) \end{aligned}\]
- Critical disruptive voltage per phase is\[\begin{aligned} V_{c} &=m_{0} g_{0} \delta r \log _{e} d / r \mathrm{kV} \\ &=0.85 \times 21 \cdot 2 \times 0.952 \times 1 \cdot 5 \times \log _{e} 200 / 1 \cdot 5=125 \cdot 9 \mathrm{kV} \end{aligned}\]
Supply voltage per phase, \(\quad V=220 / \sqrt{3}=127 \mathrm{kV}\)
Problem-4
A certain 3 -phase equilateral transmission line has a total corona loss of \(53~ \mathrm{kW}\) at \(106 ~\mathrm{kV}\) and a loss of \(98~ \mathrm{kW}\) at \(110.9~ \mathrm{kV}\).
What is the disruptive critical voltage?
What is the corona loss at \(113~ \mathrm{kV}\) ?
Solution-4
For first case, \(P=53~ \mathrm{kW}\) and \(V=106 / \sqrt{3}=61 \cdot 2 ~\mathrm{kV}\)
For second case, \(P=98~ \mathrm{kW}\) and \(V=110 \cdot 9 / \sqrt{3}=64~\mathrm{kV}\)
\(\therefore\)
Problem-5
Find the disruptive critical and visual corona voltage of a grid-line operating at \(132~ \mathrm{kV}\)
conductor surface factor: