Equal Area Criterion for Power System Stability

Demonstrative Video


Equal Area Criterion

image
  • Consider the situation in which the synchronous machine is operating in steady state delivering a power \(P_e = P_m\) when there is a fault occurs in the system.

  • Opening up of the circuit breakers in the faulted section subsequently clears the fault.

  • The circuit breakers take about 5/6 cycles to open and the subsequent post-fault transient last for another few cycles.

  • The input power, on the other hand, is supplied by a prime mover that is usually driven by a steam turbine.

  • The time constant of the turbine mass system is of the order of few seconds, while the electrical system time constant is in milliseconds.

  • Therefore, for all practical purpose, \(P_m\) remains constant during this period when the electrical transients occur.

  • The transient stability study therefore concentrates on the ability of the power system to recover from the fault and deliver the constant power \(P_m\) with a possible new load angle \(\delta\).

  • Suppose the system is operating in the steady state delivering \(P_m\) at an angle of \(\delta_0\) when due to malfunction of the line, circuit breakers open reducing the real power transferred to zero.

  • Since \(P_m\) remains constant, \(P_a\) becomes equal to \(P_m\).

  • The difference in the power gives rise to the rate of change of stored kinetic energy in the rotor masses.

  • Thus the rotor will accelerate under the constant influence of non-zero accelerating power and hence \(\delta\) will increase.

  • Now suppose the circuit breaker re-closes at an angle \(\delta_c\).

  • The power will then revert back to the normal operating curve.

  • At that point, \(P_e > P_m \Rightarrow P_a = -ve\)

  • Machine will decelerate, and due to the inertia of the rotor masses, \(\delta\) will still keep on increasing.

  • The increase in this angle may eventually stop and the rotor may start decelerating, otherwise the system will lose synchronism.

  • \[\dfrac{d}{dt}\left(\dfrac{d\delta}{dt}\right)^{2}=2\left(\dfrac{d\delta}{dt}\right)\left(\dfrac{d^{2}\delta}{dt^{2}}\right)\]
    Since,
  • \[\dfrac{H}{\omega_{s}}\dfrac{d}{dt}\left(\dfrac{d\delta}{dt}\right)^{2}=\left(P_{m}-P_{e}\right)\dfrac{d\delta}{dt}\]
    , we get Therefore, from
  • \[\left.\dfrac{H}{\omega_{s}}\left(\dfrac{d\delta}{dt}\right)^{2}\right|_{\delta_{0}}^{\delta_{c}}=\intop_{\delta_{0}}^{\delta_{c}}\left(P_{m}-P_{e}\right)d\delta\]
    we get and Multiplying both sides of the above equation by dt and then integrating between two arbitrary angles
  • Now suppose the generator is at rest at \(\delta_0\). We then have \(d\delta/dt = 0\).

  • Once a fault occurs, the machine starts accelerating.

  • Once the fault is cleared, the machine keeps on accelerating before it reaches its peak at \(\delta_c\), at which point we again have \(d\delta/dt = 0\).

  • \[A_{1}=\intop_{\delta_{0}}^{\delta_{c}}\left(P_{m}-P_{e}\right)d\delta=0\]
    Thus the area of accelerating is given as
  • \[A_{2}=\intop_{\delta_{0}}^{\delta_{c}}\left(P_{e}-P_{m}\right)d\delta=0\]
    is given by Similarly, the area of deceleration,
  • Now consider the case when the line is re closed at \(\delta_c\) such that the area of \(A_{1} > A_2\) .

  • The generator load angle will then cross the point \(\delta_m\), beyond which the \(P_e < P_m \Rightarrow P_a = +ve\)

  • The generator will therefore start accelerating before is slows down completely and will eventually become unstable.

  • If \(A_{1} < A_2\), the machine will decelerate completely before accelerating again.

  • The rotor inertia will force the subsequent acceleration and deceleration areas to be smaller than the first ones and the machine will eventually attain the steady state.

  • If \(A_{1} = A_2\), defines the boundary of the

  • The clearing angle \(\delta_{c}\) for this mode is called the , \(\delta_{cr}\).

image
  • \[\intop_{\delta_{0}}^{\delta_{cr}}\left(P_{m}-P_{e}\right)d\delta=\intop_{\delta_{cr}}^{\delta_{m}}\left(P_{e}-P_{m}\right)d\delta\]
    We then get by substituting
  • We can calculate the critical clearing angle from the above equation.

  • Since the critical clearing angle depends on the equality of the areas, this is called the .

  • Since we are interested in finding out the maximum time that the circuit breakers may take for opening, we should be more concerned about the rather than clearing angle.

  • Furthermore, notice that the clearing angle is independent of the generalized inertia constant H.

  • The critical clearing time, however, is dependent on \(H\) and will vary as this parameter varies.

  • To obtain a description for the critical clearing time, let us consider the period during which the fault occurs.

  • We then have \(P_e = 0\).

  • \[\dfrac{d^{2}\delta}{dt^{2}}=\dfrac{\omega_{s}}{2H}P_{m}\]
    We can therefore write from
  • \[\dfrac{d\delta}{dt}=\intop_{0}^{t}\left(\dfrac{\omega_{s}}{2H}P_{m}\right)dt=\dfrac{\omega_{s}}{2H}P_{m}t\]
    Integrating with the initial acceleration being zero we get
  • \[\delta=\intop_{0}^{t}\left(\dfrac{\omega_{s}}{2H}P_{m}t\right)dt=\dfrac{\omega_{s}}{4H}P_{m}t^{2}+\delta_{0}\]
    Further integration will lead to
  • \[t_{cr}=\sqrt{\dfrac{4H}{\omega_{s}P_{m}}\left(\delta_{cr}-\delta_{0}\right)}\]
    , we get the critical clearing time as and Replacing