Part 1 · Chapter 3

Three-Phase Power and the Single-Line Diagram

Three windings spaced a third of a cycle apart deliver energy at a perfectly steady rate instead of in pulses, and because the three phases of a balanced system carry the same information three times over, the entire network collapses onto a single wire on paper — the diagram every later chapter is drawn on.

Electric Power Systems Prof. Mithun Mondal Reading time ≈ 46 min
i What you'll learn
  • Why a balanced three-phase load absorbs constant instantaneous power while a single-phase load pulsates at twice supply frequency, and what that buys mechanically.
  • The operator \(a = 1\angle 120^\circ\), the identity \(1 + a + a^2 = 0\), and why it makes every three-phase relation a one-line calculation.
  • Where the \(\sqrt3\) and the \(30^\circ\) come from in \(V_L = \sqrt3\,V_{ph}\) (star) and \(I_L = \sqrt3\,I_{ph}\) (delta) — derived, not memorised.
  • Why \(S = \sqrt3\,V_L I_L\angle\phi\) holds for both connections, and why \(\phi\) is the load impedance angle and never the angle between \(V_L\) and \(I_L\).
  • How a balanced three-phase network reduces to a per-phase equivalent circuit through \(Z_\Delta = 3Z_Y\) and a zero-current neutral.
  • The two-wattmeter method from Blondel's theorem, including \(\tan\phi = \sqrt3\,(W_2-W_1)/(W_2+W_1)\) and the negative reading beyond \(\phi = 60^\circ\).
  • How the per-phase circuit becomes the single-line diagram, what is written on it, and why Chapter 4 must normalise those numbers before anything can be added.
Section 3-1

Why Three Phases and Not One

Chapter 1 followed a single-phase load and found something uncomfortable. With \(v = \sqrt2\,V\cos\omega t\) across an impedance carrying \(i = \sqrt2\,I\cos(\omega t - \phi)\), the instantaneous power was

Single-phase instantaneous power (Chapter 1)
\[ p(t) = VI\cos\phi \;+\; VI\cos(2\omega t - \phi) \]

The first term is the useful average; the second is an oscillation at twice supply frequency whose amplitude \(VI\) is larger than the average \(VI\cos\phi\) whenever the power factor is less than unity. A single-phase machine therefore receives its energy in a series of 100 pushes per second on a 50 Hz system, with a backward pull in between whenever \(\phi \ne 0\). The shaft must carry that torque ripple, the foundations must absorb it, and the machine cannot start without some auxiliary trick to produce a rotating field, because one alternating winding produces only a pulsating one.

Now suppose that instead of one winding we place three identical windings on the stator, spaced \(120^\circ\) apart in space, and drive them with three voltages of equal magnitude spaced \(120^\circ\) apart in time. Two things happen at once. The three currents produce a magnetic field of constant magnitude that rotates at synchronous speed — the induction motor and the synchronous machine both exist because of this. And the three pulsating powers, each peaking at a different instant, add to a total that does not pulsate at all. That second claim is proved in Section 3-5; it is the reason the whole industry is three-phase.

There is a third reason, and it is about money. Chapter 2 compared systems by the volume of conductor metal they need, holding the delivered power, the transmission loss and the length fixed. Apply that same accounting to the number of phases, comparing on the basis of the same voltage between conductors — the quantity the insulation must withstand.

Conductor material: single-phase two-wire against three-phase three-wire
\[ \text{1-}\phi:\quad I_1 = \frac{P}{V\cos\phi},\qquad W = 2I_1^2\frac{\rho l}{a_1} \;\Rightarrow\; a_1 = \frac{2I_1^2\rho l}{W},\qquad \mathcal{V}_1 = 2a_1 l = \frac{4\rho l^2 P^2}{W V^2\cos^2\phi} \]
\[ \text{3-}\phi:\quad I_3 = \frac{P}{\sqrt3\,V\cos\phi},\qquad W = 3I_3^2\frac{\rho l}{a_3} \;\Rightarrow\; a_3 = \frac{3I_3^2\rho l}{W},\qquad \mathcal{V}_3 = 3a_3 l = \frac{9\rho l^2 P^2}{3\,W V^2\cos^2\phi} \]
\[ \frac{\mathcal{V}_3}{\mathcal{V}_1} = \frac{3}{4} = 0.75 \]

Three conductors carrying \(1/\sqrt3\) of the single-phase current need only three-quarters of the metal, because loss scales with the square of the current while the number of conductors grows only from two to three. A fourth wire is often run as a neutral, but Section 3-2 shows it carries no current in a balanced system, so it is made of half the cross-section of a phase conductor and adds little.

🔑
Three reasons, one decision
Three phases give constant instantaneous power, a naturally rotating magnetic field, and the same delivered power at the same loss and the same line voltage using 75% of the conductor metal.

No further increase in the number of phases pays for itself: six phases would save a little more copper but would double the number of terminals, breakers and insulators. Three is the smallest number of phases for which the instantaneous power is constant, which is why the count settled there in the 1890s and has never moved.

A single-phase supply is still available. Taking one phase conductor and the neutral out of a three-phase four-wire system gives an ordinary single-phase circuit at \(V_L/\sqrt3\) — 230 V from a 400 V system. Domestic connections are made this way, and the distribution engineer's task is to spread them across the three phases so that the feeder as a whole stays close to balanced.
Section 3-2

The Balanced Set and the Operator \(a\)

A three-phase source is balanced when its three phase voltages have equal magnitude and are displaced by exactly \(120^\circ\). Naming the phases \(a\), \(b\), \(c\) (equivalently R, Y, B) and taking \(V_{an}\) as the reference,

A balanced set, abc sequence
\[ \mathbf{V}_{an} = V\angle 0^\circ, \qquad \mathbf{V}_{bn} = V\angle{-120^\circ}, \qquad \mathbf{V}_{cn} = V\angle{+120^\circ} \]

The order in which the three reach their positive maxima is the phase sequence. The set above is \(a\)–\(b\)–\(c\): \(a\) leads \(b\) by \(120^\circ\), \(b\) leads \(c\) by \(120^\circ\). Reversing any two of the three connections gives the \(a\)–\(c\)–\(b\) sequence, which reverses the direction of the rotating field and therefore the direction in which every motor on the system turns. Sequence is a physical property of the supply, not a labelling convention, and it survives into Chapter 22 as the positive and negative sequence components.

Repeated \(120^\circ\) rotations occur so often that they deserve a symbol. Define the operator \(a\) as the unit phasor that advances an angle by \(120^\circ\):

The 120° rotation operator
\[ a = 1\angle 120^\circ = -\tfrac12 + j\tfrac{\sqrt3}{2}, \qquad a^2 = 1\angle 240^\circ = -\tfrac12 - j\tfrac{\sqrt3}{2}, \qquad a^3 = 1\angle 360^\circ = 1 \]

With it the balanced set is written \(\mathbf{V}_{an} = V\), \(\mathbf{V}_{bn} = a^2 V\), \(\mathbf{V}_{cn} = aV\). Adding the three complex numbers, the real parts give \(1 - \tfrac12 - \tfrac12 = 0\) and the imaginary parts give \(0 + \tfrac{\sqrt3}{2} - \tfrac{\sqrt3}{2} = 0\):

🔑
The identity everything else rests on
\[ 1 + a + a^2 = 0 \qquad\Longrightarrow\qquad \mathbf{V}_{an} + \mathbf{V}_{bn} + \mathbf{V}_{cn} = 0 \]

Three equal phasors \(120^\circ\) apart sum to zero. Applied to currents in a four-wire system the same identity gives \(\mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c = \mathbf{I}_n = 0\): the neutral of a balanced system carries no current, and can be removed, or made of reduced section, or earthed, without altering a single voltage or current elsewhere.

Balance is an assumption, and like every assumption in this book it has to be paid for eventually. It holds well on transmission, where lines are transposed and loads are large and aggregated; it holds poorly on a distribution feeder with unequal single-phase connections, and it fails completely during an unsymmetrical fault. Chapters 22 to 24 build the machinery that handles the failure. Until then, balance is what makes everything in this chapter simple.

Section 3-3

The Star Connection: Line and Phase Quantities

Four quantities have to be kept apart, and most three-phase errors come from confusing two of them.

  • Phase voltage \(V_{ph}\) — measured across one winding of the source or one branch of the load.
  • Line voltage \(V_L\) — measured between any two line conductors.
  • Phase current \(I_{ph}\) — flowing through one winding or one load branch.
  • Line current \(I_L\) — flowing in a line conductor between source and load.

In the star (\(Y\)) connection the three windings are joined at a common point \(n\), the star point, and the free ends become the three lines. Each winding sits between a line and the star point, so the line current is the phase current. The line voltage, on the other hand, is a difference of two phase voltages, and that difference is where the \(\sqrt3\) comes from:

Line voltage of a star-connected source
\[ \mathbf{V}_{ab} = \mathbf{V}_{an} - \mathbf{V}_{bn} = V - a^2 V = V\!\left[1 - \left(-\tfrac12 - j\tfrac{\sqrt3}{2}\right)\right] = V\!\left(\tfrac32 + j\tfrac{\sqrt3}{2}\right) \]
\[ \left|\mathbf{V}_{ab}\right| = V\sqrt{\tfrac94 + \tfrac34} = V\sqrt3, \qquad \angle \mathbf{V}_{ab} = \arctan\frac{\sqrt3/2}{3/2} = 30^\circ \]
\[ \boxed{\;\mathbf{V}_{ab} = \sqrt3\,V\angle 30^\circ\;} \]

The same result follows from the triangle of the two phasors without any complex algebra. \(\mathbf{V}_{an}\) and \(-\mathbf{V}_{bn}\) have equal length \(V\) and include an angle of \(60^\circ\), so by the cosine rule

Geometric confirmation
\[ V_{ab} = \sqrt{V^2 + V^2 + 2V\!\cdot\!V\cos 60^\circ} = \sqrt{2V^2 + V^2} = \sqrt{3}\,V \]

Repeating for the other two pairs gives \(\mathbf{V}_{bc} = \sqrt3\,V\angle{-90^\circ}\) and \(\mathbf{V}_{ca} = \sqrt3\,V\angle 150^\circ\): the three line voltages form a balanced set of their own, \(\sqrt3\) times as large as the phase voltages and leading them by \(30^\circ\). That \(30^\circ\) is not decoration. It reappears in the star–delta transformer, which shifts the phase of every voltage passing through it by \(30^\circ\), and in the two-wattmeter method of Section 3-7 where it is the entire origin of the \(\cos(30^\circ \pm \phi)\) readings.

STAR (Y) n Iₙ = 0 a b c Z I_L = I_ph V_L = √3 V_ph ∠+30° DELTA (Δ) a b c I_ab V_L = V_ph I_L = √3 I_ph ∠−30°
The two connections: in star the voltages combine, in delta the currents do
Section 3-4

The Delta Connection

In the delta (\(\Delta\), or mesh) connection the three windings are joined end to end in a closed loop and the lines are taken from the three junctions. Now each winding is connected directly between two lines, so the phase voltage is the line voltage. It is the current that must be resolved: the current leaving junction \(a\) is the difference of the two branch currents meeting there.

Before going further, one point about the closed loop. Three windings in series around a mesh look like an invitation to a large circulating current, and would be one if the three generated voltages did not sum to zero. They do, by the identity of Section 3-2, so the net driving voltage around the loop is zero and no circulating current flows — provided the set is balanced and free of triplen harmonics. Third-harmonic voltages are all in phase with one another and do not cancel around the mesh, which is exactly why a delta winding is deliberately provided on many transformers to give those harmonics a path and keep them out of the lines.

Applying KCL at junction \(a\), with branch currents \(\mathbf{I}_{ab} = I\angle 0^\circ\), \(\mathbf{I}_{bc} = a^2 I\) and \(\mathbf{I}_{ca} = aI\):

Line current of a delta-connected load
\[ \mathbf{I}_a = \mathbf{I}_{ab} - \mathbf{I}_{ca} = I - aI = I\!\left[1 - \left(-\tfrac12 + j\tfrac{\sqrt3}{2}\right)\right] = I\!\left(\tfrac32 - j\tfrac{\sqrt3}{2}\right) \]
\[ \left|\mathbf{I}_a\right| = I\sqrt{\tfrac94+\tfrac34} = \sqrt3\,I, \qquad \angle\mathbf{I}_a = -30^\circ \qquad\Longrightarrow\qquad \boxed{\;\mathbf{I}_a = \sqrt3\,I\angle{-30^\circ}\;} \]

The structure of the two derivations is identical — a difference of two phasors \(120^\circ\) apart — which is why the same \(\sqrt3\) and the same \(30^\circ\) appear, with the sign of the shift reversed. In star the voltages combine and lead; in delta the currents combine and lag.

QuantityStar (Y)Delta (Δ)
Line voltage\(V_L = \sqrt3\,V_{ph}\), leading by \(30^\circ\)\(V_L = V_{ph}\)
Line current\(I_L = I_{ph}\)\(I_L = \sqrt3\,I_{ph}\), lagging by \(30^\circ\)
Impedance per phase\(Z_Y\)\(Z_\Delta = 3Z_Y\) for the same load
Total power\(P = 3V_{ph}I_{ph}\cos\phi = \sqrt3\,V_L I_L\cos\phi\) — the same expression for both
Neutral availableYes; carries \(0\) when balancedNo neutral point exists
Typical useGenerators, HV transformer windings, four-wire distributionMotor windings, LV transformer windings, capacitor banks
Why generators are star-connected and motors are often delta. A star winding produces the line voltage from windings insulated for only \(V_L/\sqrt3\), which saves insulation on a high-voltage machine, and it provides a neutral to earth through a resistor or reactor so that an earth fault can be detected and limited — the point Chapter 23 takes up. A delta winding has no neutral to earth, tolerates unbalanced loading better, and traps triplen harmonics inside the mesh.
Section 3-5

Power in a Balanced Three-Phase Circuit

Start with the promise made in Section 3-1. Let each phase carry \(v_k\) and \(i_k\) as in Chapter 1, with the phases displaced by \(120^\circ\) and the same impedance angle \(\phi\) in every phase. Each phase delivers the single-phase result, shifted:

The three instantaneous powers
\[ p_a = VI\big[\cos\phi + \cos(2\omega t - \phi)\big] \]
\[ p_b = VI\big[\cos\phi + \cos(2\omega t - \phi - 240^\circ)\big], \qquad p_c = VI\big[\cos\phi + \cos(2\omega t - \phi + 240^\circ)\big] \]

The \(120^\circ\) displacement of the phase quantities becomes a \(240^\circ\) displacement of the double-frequency terms, because the argument contains \(2\omega t\). But three cosines whose arguments differ by \(240^\circ\) are still three unit phasors spaced \(120^\circ\) apart on the double-frequency plane, and by the identity \(1 + a + a^2 = 0\) they sum to zero at every instant. The oscillating parts cancel and only the constant parts survive:

🔑
Constant instantaneous power
\[ p_{3\phi}(t) = p_a + p_b + p_c = 3VI\cos\phi = \text{constant, independent of } t \]

A balanced three-phase load draws energy at a perfectly steady rate. The shaft of a three-phase motor sees no torque ripple of supply origin, and the prime mover driving a three-phase alternator sees a steady counter-torque. Neither statement is true of a single-phase machine, and both fail the moment the load becomes unbalanced.

v vₐ v_b v_c ωt p (pf = 0.866 lagging) pₐ + p_b + p_c = 3VI cos φ 0 ωt
Each phase power pulsates and briefly reverses; the sum of the three is a straight line

For steady-state work the phasor form is what gets used. Chapter 1 defined complex power per phase as \(\mathbf{S} = \mathbf{V}\mathbf{I}^{*}\). Adding three identical contributions,

Three-phase complex power
\[ \mathbf{S}_{3\phi} = 3\,\mathbf{V}_{ph}\mathbf{I}_{ph}^{*} = 3V_{ph}I_{ph}\angle\phi = P + jQ \]
\[ \text{Star: } V_{ph} = \frac{V_L}{\sqrt3},\; I_{ph}=I_L \;\Rightarrow\; S = 3\frac{V_L}{\sqrt3}I_L = \sqrt3\,V_L I_L \]
\[ \text{Delta: } V_{ph} = V_L,\; I_{ph}=\frac{I_L}{\sqrt3} \;\Rightarrow\; S = 3V_L\frac{I_L}{\sqrt3} = \sqrt3\,V_L I_L \]
🔑
The three-phase power formulae
\[ P = \sqrt3\,V_L I_L\cos\phi, \qquad Q = \sqrt3\,V_L I_L\sin\phi, \qquad S = \sqrt3\,V_L I_L = \sqrt{P^2+Q^2} \]

Identical for star and delta, because the \(\sqrt3\) that enters through the voltage in one connection enters through the current in the other. \(\phi\) is the angle of the load impedance — the angle between phase voltage and phase current — and never the angle between \(V_L\) and \(I_L\), which differs from it by \(30^\circ\).

Two habits follow from this. First, every three-phase rating quoted in this book — a 30 MVA generator, a 400 kV line, a 2 MVA transformer — is the three-phase total, and every voltage is the line-to-line value, unless it is explicitly labelled otherwise. Second, when a load is described as "50 kW at 0.8 power factor lagging" the reactive demand follows immediately as \(Q = P\tan\phi = 50 \times 0.75 = 37.5\) kvar, exactly as in Chapter 1; three phases changes the arithmetic of the currents, not the shape of the power triangle.

Where the \(\sqrt3\) really lives. \(P=\sqrt3\,V_LI_L\cos\phi\) is not a three-phase correction factor pasted onto a single-phase formula. It is \(3V_{ph}I_{ph}\cos\phi\) — three identical single-phase circuits — rewritten in terms of the quantities an engineer can actually measure at the terminals. Whenever a three-phase calculation goes wrong by a factor of \(\sqrt3\) or 3, the cause is almost always a phase quantity used where a line quantity belonged.
Section 3-6

Per-Phase Analysis: Three Circuits Become One

Everything so far points to one conclusion: in a balanced system the three phases are copies of one another, differing only by a known \(120^\circ\) rotation. Solving all three is therefore three times as much work as it needs to be. Per-phase analysis makes the reduction formal, and it rests on two steps.

Step one: connect the neutrals. Take a star-connected source feeding a star-connected balanced load through three identical line impedances. The star point of the source and the star point of the load are both at the potential of the average of the three phase voltages, which by \(1+a+a^2=0\) is the same at both ends. Two points at identical potential may be joined by a wire of zero impedance without changing anything in the circuit, and the wire will carry \(\mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c = 0\). With that wire in place, phase \(a\) forms a complete loop on its own: source, line impedance, load impedance, return through the neutral. The three phases are decoupled.

Step two: convert every delta to its star equivalent. A delta load has no star point to connect, so it must first be replaced by the star that draws exactly the same line currents from the same line voltages. The general transformation, applied to the three branches of a mesh, is

Star–delta transformation, general and balanced
\[ Z_{ab} = \frac{Z_aZ_b + Z_bZ_c + Z_cZ_a}{Z_c}, \qquad Z_{bc} = \frac{Z_aZ_b + Z_bZ_c + Z_cZ_a}{Z_a}, \qquad Z_{ca} = \frac{Z_aZ_b + Z_bZ_c + Z_cZ_a}{Z_b} \]
\[ \text{Balanced: } Z_a=Z_b=Z_c=Z_Y \;\Longrightarrow\; Z_\Delta = \frac{3Z_Y^2}{Z_Y} = 3Z_Y \qquad\Longrightarrow\qquad \boxed{\;Z_Y = \frac{Z_\Delta}{3}\;} \]

The factor of three can also be read off the power. A delta branch sees the full line voltage \(V_L\) while a star branch sees \(V_L/\sqrt3\), so for the same impedance the delta branch dissipates three times as much; to draw the same power the delta impedance must be three times as large. This is the reason a star–delta starter reduces motor starting current to a third of its direct-on-line value: reconnecting the same windings in star triples their effective per-phase impedance as seen from the line.

🔑
The per-phase equivalent circuit
A balanced three-phase network is solved as one single-phase circuit carrying the phase voltage \(V_L/\sqrt3\), the line current \(I_L\), and one-third of the three-phase power, with every delta replaced by \(Z_\Delta/3\) and every neutral tied to a common zero-potential reference.

Phases \(b\) and \(c\) are recovered at the end by multiplying the phase-\(a\) answer by \(a^2\) and \(a\) — that is, by subtracting \(120^\circ\) and adding \(120^\circ\). They are almost never written down, because they contain no new information.

This is the single most important simplification in power system analysis, and it is worth being explicit about what it costs. Per-phase analysis is exact for a balanced system and meaningless for an unbalanced one. Every load-flow calculation in Part 4, every symmetrical fault calculation in Chapter 21 and every stability study in Part 6 is a per-phase calculation. When the assumption breaks — a line-to-ground fault, one open conductor — Chapter 22 restores it by a change of variables that turns one unbalanced three-phase problem into three balanced ones.

Section 3-7

Measuring Power: The Two-Wattmeter Method

A wattmeter reads the average of the product of the voltage across its pressure coil and the current through its current coil. To measure three-phase power the obvious approach is one meter per phase, but that requires access to the star point, which a delta load does not have and a sealed motor terminal box rarely offers. Blondel's theorem says fewer meters are needed anyway.

The total instantaneous power in a three-wire system is \(p = v_a i_a + v_b i_b + v_c i_c\), with all voltages referred to an arbitrary common point. With no neutral connection, \(i_a + i_b + i_c = 0\), so \(i_b = -(i_a + i_c)\). Substituting:

Blondel's theorem for three wires
\[ p = v_a i_a + v_b\big[-(i_a+i_c)\big] + v_c i_c = (v_a - v_b)\,i_a + (v_c - v_b)\,i_c = v_{ab}\,i_a + v_{cb}\,i_c \]

The total power is the sum of just two products. One wattmeter with its current coil in line \(a\) and its pressure coil across \(a\)–\(b\), a second with its current coil in line \(c\) and its pressure coil across \(c\)–\(b\), together measure the whole thing — for any load, balanced or not, star or delta. In general a system of \(n\) wires needs \(n-1\) wattmeters, which is Blondel's theorem.

Now specialise to a balanced load with lagging angle \(\phi\), abc sequence, \(V_{an}=V\angle0^\circ\). Then \(\mathbf{I}_a = I\angle{-\phi}\), \(\mathbf{I}_c = I\angle(120^\circ-\phi)\), \(\mathbf{V}_{ab} = \sqrt3 V\angle 30^\circ\) and \(\mathbf{V}_{cb} = -\mathbf{V}_{bc} = \sqrt3 V\angle 90^\circ\). Each meter reads the product of magnitudes times the cosine of the angle between its own voltage and its own current:

The two readings
\[ W_1 = \left|\mathbf{V}_{ab}\right|\left|\mathbf{I}_a\right|\cos\big(30^\circ - (-\phi)\big) = V_L I_L\cos(30^\circ + \phi) \]
\[ W_2 = \left|\mathbf{V}_{cb}\right|\left|\mathbf{I}_c\right|\cos\big(90^\circ - (120^\circ-\phi)\big) = V_L I_L\cos(\phi - 30^\circ) = V_L I_L\cos(30^\circ - \phi) \]

Adding and subtracting, with \(\cos X + \cos Y = 2\cos\frac{X+Y}{2}\cos\frac{X-Y}{2}\):

Sum, difference and the power factor
\[ W_1 + W_2 = 2V_LI_L\cos 30^\circ\cos\phi = \sqrt3\,V_L I_L\cos\phi = P \]
\[ W_2 - W_1 = 2V_LI_L\sin 30^\circ\sin\phi = V_L I_L\sin\phi = \frac{Q}{\sqrt3} \]
\[ \Longrightarrow\quad Q = \sqrt3\,(W_2 - W_1), \qquad \tan\phi = \frac{\sqrt3\,(W_2-W_1)}{W_2+W_1} \]
🔑
Two meters, three answers
\[ P = W_1 + W_2, \qquad Q = \sqrt3\,(W_2-W_1), \qquad \tan\phi = \sqrt3\,\frac{W_2-W_1}{W_2+W_1} \]

For a lagging load \(W_2 \ge W_1\); most textbooks simply label the higher-reading meter \(W_1\) and write \(\tan\phi = \sqrt3(W_1-W_2)/(W_1+W_2)\). The magnitude of the difference is what matters — the sign only tells you whether the load is lagging or leading.

The readings themselves are diagnostic. At unity power factor \(W_1 = W_2 = V_LI_L\cos30^\circ\): the meters agree. At \(\phi = 60^\circ\) (power factor 0.5), \(\cos(30^\circ+60^\circ) = 0\) and one meter reads exactly zero while the other carries all the power. Beyond \(\phi = 60^\circ\) the cosine goes negative, the pointer tries to go backwards, and the meter must be reversed and its reading subtracted. A student who forgets that subtraction on a low-power-factor load will report roughly twice the true power.

a b c source W₁ W₂ v_ab v_cb balanced 3-φ load Y or Δ p = v_ab·i_a + v_cb·i_c ⇒ P = W₁ + W₂
Blondel's theorem: three wires need only two wattmeters, whatever the load
Section 3-8

From Three Wires to One Line: The Single-Line Diagram

Section 3-6 established that a balanced network is solved one phase at a time. Draw that per-phase circuit for a real system — a generator, its step-up transformer, a transmission line, a step-down transformer, a load — and it is a chain of impedances between a source and a return. Two observations then finish the job of simplification.

The first is that the neutral return carries no current and drops no voltage, so drawing it adds nothing; it is understood to exist and is left out. The second is that the remaining single conductor stands for all three phases at once, since the other two differ only by \(\pm120^\circ\). What is left is one line per circuit, with a standard symbol wherever a piece of plant sits. That is the single-line diagram, or one-line diagram: the working drawing of power engineering.

🔑
Definition
A single-line diagram represents a three-phase power system by standard symbols for its components joined by single lines, each line standing for all three phase conductors, with the neutral omitted and the ratings and impedances of the plant written alongside.

It is not a wiring diagram and it is not to scale. Its purpose is to present, as compactly as possible, exactly the information needed to analyse the system: what is connected to what, at what voltage, with what rating, and through what impedance.

The three-line diagram — every conductor drawn — still has its uses in protection and metering work, where the phases genuinely differ: current transformer connections, relay wiring, the two-wattmeter arrangement of Section 3-7. For system studies it would be three times the ink for no extra information.

A single-line diagram is drawn at whatever level of detail the study demands. A planning diagram may show a whole regional grid with each substation as one bus. An operational diagram of a single substation shows every breaker, isolator, current transformer and earth switch. The same conventions apply at both extremes.

The diagram is the input to every later chapter. The bus admittance matrix of Chapter 16 is read directly off a single-line diagram; the load-flow problem of Chapter 18 attaches four quantities to each of its buses; the fault studies of Part 5 replace each symbol on it by a sequence impedance. Learning to read one accurately is not preliminary work — it is the interface between the physical plant and every calculation in this book.
Section 3-9

Symbols, Ratings and Reading an SLD

The symbols are largely standardised (IEC 60617 and IEEE 315 agree on the important ones). The table lists those used throughout this book, together with what has to be written beside each.

ComponentSymbolData marked alongside
Generator / alternatorCircle enclosing a sine or the letter G, with the winding connection (Y or Δ) and the earthing shown at its neutralMVA rating, rated kV, \(X_d''\), \(X_d'\), \(X_d\) in % or per unit
Two-winding transformerTwo interlinked circles, or two coupled coilsMVA rating, voltage ratio kV/kV, \(X\) in % or per unit, vector group
Three-winding transformerThree interlinked circlesThree MVA ratings, three voltages, \(X_{HM}, X_{ML}, X_{HL}\)
Transmission lineA plain straight line between two busesLength, conductor type, \(R\), \(X\), \(B/2\) in ohms or per unit
Bus / busbarA short thick line perpendicular to the connectionsBus number and nominal kV
Circuit breakerA small square on the line (filled for air-blast, hollow for oil in older drawings)Rated breaking capacity in MVA or kA
Isolator / disconnectorAn open blade drawn at an angle to the lineRated current; interrupts no load current
Static loadAn arrow leaving the busMW and Mvar, or MVA and power factor
Synchronous / induction motorCircle with M, connection shownMVA or hp, kV, \(X''\)
Shunt capacitor / reactorTwo parallel bars / a coil, connected bus to earthMvar at rated voltage
Neutral earthing impedanceResistor or reactor between the star point and the earth symbolOhms, or the earth-fault current it limits

Three conventions matter more than the shapes. Every voltage written on a single-line diagram is a line-to-line value, and every MVA is a three-phase total, following Section 3-5. Every impedance is given as a percentage or a per-unit value on the plant's own rating — a transformer marked "20 MVA, 33/11 kV, 8%" has a reactance of 8% on a 20 MVA, 33 kV base, and Chapter 4 exists to convert that onto a common base before it can be added to anything else. The transformer connection and earthing are shown even though the neutral wire is not drawn, because they decide what happens in an unsymmetrical fault.

G 30 MVA 11 kV, X″=0.20 Bus 1 11 kV CB T1 35 MVA 11/132 kV, X=0.10 Bus 2 132 kV line j100 Ω Bus 3 T2 25 MVA 132/33 kV, X=0.08 Bus 4 33 kV 20 MVA 0.85 pf lag 5 Mvar every line = three phase conductors · every kV = line-to-line · every MVA = three-phase
A typical single-line diagram: generator, breaker, transformers, line, load and capacitor bank

Read the diagram above from left to right and notice what it does not tell you. The generator reactance is 0.20 per unit on 30 MVA; the transformer reactance is 0.10 per unit on 35 MVA; the line reactance is 100 ohms at 132 kV. Three numbers on three different bases, one of them not even normalised. They cannot be added, cannot be put in series, cannot be used until they are expressed against a single common reference. Producing that common reference is what Chapter 4 does, and it is the last piece of preparation before the network itself can be analysed.

Section 3-10

Worked Examples

1 A balanced star-connected load

Problem. A balanced star-connected load of \(Z = 8 + j6\;\Omega\) per phase is supplied at 400 V, 50 Hz (line value). Find the phase voltage, the line current, and \(P\), \(Q\) and \(S\).

Solution. In star the phase voltage is the line value divided by \(\sqrt3\):

Phase quantities
\[ V_{ph} = \frac{400}{\sqrt3} = 230.9\ \text{V}, \qquad Z = 8+j6 = 10\angle 36.87^\circ\ \Omega \]
\[ I_{ph} = \frac{230.9}{10} = 23.09\ \text{A} = I_L \quad\text{(star)}, \qquad \phi = 36.87^\circ \text{ lagging},\;\; \cos\phi = 0.8 \]

Now the powers, computed twice as a check — once from the per-phase resistance and reactance, once from the line quantities:

Power, two ways
\[ P = 3I_{ph}^2R = 3(23.09)^2(8) = 12\,800\ \text{W} = 12.80\ \text{kW} \]
\[ P = \sqrt3\,V_LI_L\cos\phi = 1.732\times400\times23.09\times0.8 = 12.80\ \text{kW} \;\checkmark \]
\[ Q = 3I_{ph}^2X = 3(23.09)^2(6) = 9.60\ \text{kvar}, \qquad S = \sqrt3\,V_LI_L = 16.00\ \text{kVA} \]

The check \(S^2 = P^2+Q^2\) gives \(\sqrt{12.80^2 + 9.60^2} = \sqrt{163.8+92.2} = 16.00\) kVA, and \(P/S = 12.80/16.00 = 0.8\), the power factor. Every three-phase problem should close this way.

2 The same impedance reconnected in delta

Problem. The three impedances of Example 1 are reconnected in delta across the same 400 V supply. Find the phase and line currents and the power drawn, and explain the ratio to the star case.

Solution. In delta each branch now sees the full line voltage:

Delta quantities
\[ V_{ph} = V_L = 400\ \text{V}, \qquad I_{ph} = \frac{400}{10} = 40\ \text{A}, \qquad I_L = \sqrt3\times40 = 69.28\ \text{A} \]
\[ P = 3I_{ph}^2R = 3(40)^2(8) = 38\,400\ \text{W} = 38.40\ \text{kW} \]
\[ Q = 3(40)^2(6) = 28.80\ \text{kvar}, \qquad S = \sqrt3\times400\times69.28 = 48.00\ \text{kVA} \]

Every quantity is exactly three times its star value: \(38.40/12.80 = 3\), \(69.28/23.09 = 3\). The reason is Section 3-6 in reverse. The same physical impedance connected in delta presents \(Z_\Delta/3 = Z/3\) per phase to the line instead of \(Z\), so the line current and hence the power triple. This is the star–delta starter in one line of arithmetic: start the motor in star to hold the starting current to a third, then switch to delta for running.

3 A feeder with line impedance, solved per phase

Problem. A balanced 11 kV (line) source feeds a delta-connected load of \(90 + j120\;\Omega\) per phase through a three-phase feeder of impedance \(1.0 + j3.0\;\Omega\) per conductor. Find the line current, the voltage at the load, the power delivered and the feeder loss.

Solution. Convert the delta load to its star equivalent, then draw the single-phase equivalent circuit of Section 3-6:

Per-phase equivalent
\[ Z_Y = \frac{Z_\Delta}{3} = \frac{90+j120}{3} = 30 + j40 = 50\angle 53.13^\circ\ \Omega \]
\[ Z_{\text{total}} = (1.0+j3.0) + (30+j40) = 31 + j43 = 53.01\angle 54.21^\circ\ \Omega \]
\[ V_{ph} = \frac{11\,000}{\sqrt3} = 6350.9\ \text{V}, \qquad I_L = \frac{6350.9}{53.01} = 119.8\ \text{A at } -54.21^\circ \]

The load voltage follows from the star-equivalent impedance, and the line value by multiplying by \(\sqrt3\):

Load voltage and powers
\[ V_{ph,\text{load}} = 119.8\times50 = 5990\ \text{V} \;\Longrightarrow\; V_{L,\text{load}} = \sqrt3\times5990 = 10\,375\ \text{V} = 10.38\ \text{kV} \]
\[ P_{\text{load}} = 3I_L^2(30) = 3(119.8)^2(30) = 1.292\ \text{MW}, \qquad Q_{\text{load}} = 3(119.8)^2(40) = 1.722\ \text{Mvar} \]
\[ P_{\text{loss}} = 3I_L^2(1.0) = 3(119.8)^2 = 43.06\ \text{kW} \]

The voltage has fallen from 11.00 kV to 10.38 kV, a drop of 5.7%, and 43 kW of the 1.335 MW sent has been lost as heat in the conductors — 3.2%. Both numbers are the subject of Chapter 13. As a check on the delta conversion, each delta branch carries \(119.8/\sqrt3 = 69.2\) A, and \(10\,375/150 = 69.2\) A directly from the branch impedance \(|90+j120| = 150\;\Omega\). \(\checkmark\)

4 Reading a load from two wattmeters

Problem. Two wattmeters connected to measure the power taken by a balanced 400 V three-phase load read 8.2 kW and 2.6 kW. Find the total power, the power factor, the reactive power and the line current. What would the readings become if the power factor fell to 0.5?

Solution. The load is inductive, so the larger reading is the \(\cos(30^\circ-\phi)\) meter, \(W_2 = 8.2\) kW and \(W_1 = 2.6\) kW.

From the readings
\[ P = W_1 + W_2 = 10.8\ \text{kW} \]
\[ \tan\phi = \frac{\sqrt3\,(8.2-2.6)}{10.8} = \frac{1.732\times5.6}{10.8} = 0.8981 \;\Longrightarrow\; \phi = 41.92^\circ, \;\; \cos\phi = 0.744 \]
\[ Q = \sqrt3\,(W_2-W_1) = 1.732\times5.6 = 9.70\ \text{kvar}, \qquad S = \sqrt{10.8^2+9.70^2} = 14.52\ \text{kVA} \]
\[ I_L = \frac{S}{\sqrt3\,V_L} = \frac{14\,520}{1.732\times400} = 20.96\ \text{A} \]

At \(\cos\phi = 0.5\) the angle is \(\phi = 60^\circ\), so \(W_1 = V_LI_L\cos(30^\circ+60^\circ) = V_LI_L\cos 90^\circ = 0\). One meter reads zero and the other reads the entire power, \(W_2 = V_LI_L\cos(-30^\circ) = 0.866\,V_LI_L = \sqrt3 V_LI_L\times 0.5 = P\). Any power factor below 0.5 pushes \(W_1\) negative, and the meter must be reversed and its reading subtracted.

5 Combining loads and correcting the power factor

Problem. A 415 V, 50 Hz three-phase bus supplies an induction motor taking 60 kW at 0.80 power factor lagging and a resistance heater taking 15 kW at unity power factor. Find the total kVA and power factor, and the capacitance per phase of a delta-connected bank that will raise the power factor to 0.95 lagging.

Solution. Powers add as complex numbers, exactly as in Chapter 1 — this is the whole reason for working in \(P\) and \(Q\) rather than kVA.

Combining the two loads
\[ \text{Motor: } P_1 = 60\ \text{kW},\quad Q_1 = 60\tan(36.87^\circ) = 60\times0.75 = 45\ \text{kvar} \]
\[ \text{Heater: } P_2 = 15\ \text{kW},\quad Q_2 = 0 \]
\[ P = 75\ \text{kW},\quad Q = 45\ \text{kvar},\quad S = \sqrt{75^2+45^2} = 87.46\ \text{kVA},\quad \cos\phi = \frac{75}{87.46} = 0.858 \]

Capacitors supply reactive power without absorbing real power, so \(P\) is unchanged and only \(Q\) is reduced:

Sizing the bank
\[ \cos\phi' = 0.95 \;\Rightarrow\; \phi' = 18.19^\circ, \qquad Q' = 75\tan 18.19^\circ = 75\times0.3287 = 24.65\ \text{kvar} \]
\[ Q_C = Q - Q' = 45 - 24.65 = 20.35\ \text{kvar} \]
\[ \text{Delta bank: } Q_C = 3V_L^2\omega C_\Delta \;\Longrightarrow\; C_\Delta = \frac{20\,350}{3(314.16)(415)^2} = 125.4\ \mu\text{F per phase} \]

The line current falls from \(87\,460/(\sqrt3\times415) = 121.7\) A to \(78\,950/(\sqrt3\times415) = 109.8\) A, a 10% reduction in every conductor, breaker and transformer between here and the generator. Had the bank been star-connected each unit would see only \(V_L/\sqrt3\), so three times the capacitance would be needed: \(C_Y = 3C_\Delta = 376\ \mu\)F. Delta connection is preferred for exactly this reason — less capacitance for the same kvar, though each unit must be insulated for the full line voltage.

6 Reading the single-line diagram of Section 3-9

Problem. For the system drawn in Section 3-9, find the full-load current of the generator, the current in the 132 kV line when it carries the generator's full 30 MVA, and the current drawn by the 20 MVA load at 33 kV. Comment on what the three answers imply for the analysis.

Solution. Every rating on the diagram is a three-phase MVA and every voltage is line-to-line, so \(I = S/(\sqrt3 V_L)\) throughout.

Currents at three voltage levels
\[ I_{11\,\text{kV}} = \frac{30\times10^6}{\sqrt3\,(11\times10^3)} = \frac{30\times10^6}{19\,053} = 1574.6\ \text{A} \]
\[ I_{132\,\text{kV}} = \frac{30\times10^6}{\sqrt3\,(132\times10^3)} = 131.2\ \text{A} \]
\[ I_{33\,\text{kV}} = \frac{20\times10^6}{\sqrt3\,(33\times10^3)} = 349.9\ \text{A} \]

The same 30 MVA appears as 1575 A at the generator terminals and 131 A on the line — a ratio of exactly 12, the transformer ratio \(132/11\), as Chapter 2's voltage-ladder argument requires. Now try to combine the impedances. The generator offers 0.20 per unit on 30 MVA, the transformer 0.10 per unit on 35 MVA, the line 100 ohms at 132 kV, the second transformer 0.08 per unit on 25 MVA. These four numbers are measured against four different yardsticks and refer to three different voltage levels; adding them in series, which is what any fault or load-flow calculation must do, is meaningless as they stand. Referring impedances through transformer turns ratios by hand would work but is error-prone and has to be repeated for every base change. The per-unit system of Chapter 4 does it once and for all.

Review

Chapter Summary

Constant power

The three pulsating phase powers cancel: \(p_{3\phi} = 3VI\cos\phi\) at every instant.

The operator \(a\)

\(a = 1\angle120^\circ\), \(1+a+a^2 = 0\), so a balanced neutral carries no current.

Star

\(I_L = I_{ph}\) and \(V_L = \sqrt3 V_{ph}\) leading by \(30^\circ\).

Delta

\(V_L = V_{ph}\) and \(I_L = \sqrt3 I_{ph}\) lagging by \(30^\circ\); \(Z_\Delta = 3Z_Y\).

Power

\(P = \sqrt3 V_LI_L\cos\phi\) for both connections; \(\phi\) is the impedance angle.

Per phase

Balanced networks are solved as one single-phase circuit at \(V_L/\sqrt3\).

Two wattmeters

\(P = W_1+W_2\), \(\tan\phi = \sqrt3(W_2-W_1)/(W_2+W_1)\); one reads zero at pf 0.5.

Single-line diagram

One line for three conductors, symbols for plant, ratings and impedances marked.

Practice

Problems

Assume balanced conditions, abc phase sequence and 50 Hz throughout. Quote every voltage as a line value and every power as a three-phase total unless the question says otherwise.

  1. A balanced star-connected load of \(15 + j20\;\Omega\) per phase is supplied at 415 V. Find the line current, the power factor, and \(P\), \(Q\) and \(S\). Verify that \(S^2 = P^2+Q^2\).
  2. The same three impedances are reconnected in delta on the same supply. Without repeating the full calculation, state the new line current and power, and justify the factor you used.
  3. A 400 V three-phase supply feeds a delta-connected load of \(30\angle 40^\circ\;\Omega\) per phase through a feeder of \(0.4 + j0.6\;\Omega\) per conductor. Find the load terminal voltage, the line current and the percentage voltage drop.
  4. Two wattmeters measuring a balanced load read 12 kW and 4 kW. Find the total power, the power factor and the reactive power. Repeat for readings of 12 kW and \(-4\) kW, and state what the negative sign means physically.
  5. Show that for a balanced load the ratio \(W_1/W_2\) of the two wattmeter readings depends only on the power factor, and use this to find the power factor when one meter reads half the other.
  6. A 6.6 kV bus supplies a 400 kW motor at 0.75 power factor lagging and a 250 kW furnace at unity power factor. Find the total line current and the delta-connected capacitor bank in kvar and in microfarads per phase needed to bring the overall power factor to 0.92 lagging.
  7. Prove that three sinusoidal quantities of equal amplitude displaced by \(120^\circ\) sum to zero at every instant, and explain why the same proof applied to the double-frequency terms of the phase powers gives constant total power but does not apply to the third-harmonic components of the phase voltages.
  8. Draw the single-line diagram of a system consisting of a star-connected earthed generator (25 MVA, 13.8 kV, \(X'' = 0.18\)) feeding through a circuit breaker and a delta–star transformer (30 MVA, 13.8/110 kV, \(X = 0.09\)) a 110 kV line of \(j65\;\Omega\), which supplies a star–star transformer (20 MVA, 110/11 kV, \(X = 0.07\)) and a 15 MVA load at 0.9 power factor lagging. Mark all ratings, and state the full-load current at each of the three voltage levels.
Tip: before any three-phase calculation, write down which quantities are line values and which are phase values, and which connection each element uses. Almost every wrong answer in this subject is a correct answer to a slightly different question — the star current computed for a delta load, the phase voltage substituted into a line formula, the impedance angle confused with the angle between \(V_L\) and \(I_L\). The arithmetic is never the difficulty.