Three-Phase Power and the Single-Line Diagram
Three windings spaced a third of a cycle apart deliver energy at a perfectly steady rate instead of in pulses, and because the three phases of a balanced system carry the same information three times over, the entire network collapses onto a single wire on paper — the diagram every later chapter is drawn on.
- Why a balanced three-phase load absorbs constant instantaneous power while a single-phase load pulsates at twice supply frequency, and what that buys mechanically.
- The operator \(a = 1\angle 120^\circ\), the identity \(1 + a + a^2 = 0\), and why it makes every three-phase relation a one-line calculation.
- Where the \(\sqrt3\) and the \(30^\circ\) come from in \(V_L = \sqrt3\,V_{ph}\) (star) and \(I_L = \sqrt3\,I_{ph}\) (delta) — derived, not memorised.
- Why \(S = \sqrt3\,V_L I_L\angle\phi\) holds for both connections, and why \(\phi\) is the load impedance angle and never the angle between \(V_L\) and \(I_L\).
- How a balanced three-phase network reduces to a per-phase equivalent circuit through \(Z_\Delta = 3Z_Y\) and a zero-current neutral.
- The two-wattmeter method from Blondel's theorem, including \(\tan\phi = \sqrt3\,(W_2-W_1)/(W_2+W_1)\) and the negative reading beyond \(\phi = 60^\circ\).
- How the per-phase circuit becomes the single-line diagram, what is written on it, and why Chapter 4 must normalise those numbers before anything can be added.
Why Three Phases and Not One
Chapter 1 followed a single-phase load and found something uncomfortable. With \(v = \sqrt2\,V\cos\omega t\) across an impedance carrying \(i = \sqrt2\,I\cos(\omega t - \phi)\), the instantaneous power was
The first term is the useful average; the second is an oscillation at twice supply frequency whose amplitude \(VI\) is larger than the average \(VI\cos\phi\) whenever the power factor is less than unity. A single-phase machine therefore receives its energy in a series of 100 pushes per second on a 50 Hz system, with a backward pull in between whenever \(\phi \ne 0\). The shaft must carry that torque ripple, the foundations must absorb it, and the machine cannot start without some auxiliary trick to produce a rotating field, because one alternating winding produces only a pulsating one.
Now suppose that instead of one winding we place three identical windings on the stator, spaced \(120^\circ\) apart in space, and drive them with three voltages of equal magnitude spaced \(120^\circ\) apart in time. Two things happen at once. The three currents produce a magnetic field of constant magnitude that rotates at synchronous speed — the induction motor and the synchronous machine both exist because of this. And the three pulsating powers, each peaking at a different instant, add to a total that does not pulsate at all. That second claim is proved in Section 3-5; it is the reason the whole industry is three-phase.
There is a third reason, and it is about money. Chapter 2 compared systems by the volume of conductor metal they need, holding the delivered power, the transmission loss and the length fixed. Apply that same accounting to the number of phases, comparing on the basis of the same voltage between conductors — the quantity the insulation must withstand.
Three conductors carrying \(1/\sqrt3\) of the single-phase current need only three-quarters of the metal, because loss scales with the square of the current while the number of conductors grows only from two to three. A fourth wire is often run as a neutral, but Section 3-2 shows it carries no current in a balanced system, so it is made of half the cross-section of a phase conductor and adds little.
No further increase in the number of phases pays for itself: six phases would save a little more copper but would double the number of terminals, breakers and insulators. Three is the smallest number of phases for which the instantaneous power is constant, which is why the count settled there in the 1890s and has never moved.
The Balanced Set and the Operator \(a\)
A three-phase source is balanced when its three phase voltages have equal magnitude and are displaced by exactly \(120^\circ\). Naming the phases \(a\), \(b\), \(c\) (equivalently R, Y, B) and taking \(V_{an}\) as the reference,
The order in which the three reach their positive maxima is the phase sequence. The set above is \(a\)–\(b\)–\(c\): \(a\) leads \(b\) by \(120^\circ\), \(b\) leads \(c\) by \(120^\circ\). Reversing any two of the three connections gives the \(a\)–\(c\)–\(b\) sequence, which reverses the direction of the rotating field and therefore the direction in which every motor on the system turns. Sequence is a physical property of the supply, not a labelling convention, and it survives into Chapter 22 as the positive and negative sequence components.
Repeated \(120^\circ\) rotations occur so often that they deserve a symbol. Define the operator \(a\) as the unit phasor that advances an angle by \(120^\circ\):
With it the balanced set is written \(\mathbf{V}_{an} = V\), \(\mathbf{V}_{bn} = a^2 V\), \(\mathbf{V}_{cn} = aV\). Adding the three complex numbers, the real parts give \(1 - \tfrac12 - \tfrac12 = 0\) and the imaginary parts give \(0 + \tfrac{\sqrt3}{2} - \tfrac{\sqrt3}{2} = 0\):
Three equal phasors \(120^\circ\) apart sum to zero. Applied to currents in a four-wire system the same identity gives \(\mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c = \mathbf{I}_n = 0\): the neutral of a balanced system carries no current, and can be removed, or made of reduced section, or earthed, without altering a single voltage or current elsewhere.
Balance is an assumption, and like every assumption in this book it has to be paid for eventually. It holds well on transmission, where lines are transposed and loads are large and aggregated; it holds poorly on a distribution feeder with unequal single-phase connections, and it fails completely during an unsymmetrical fault. Chapters 22 to 24 build the machinery that handles the failure. Until then, balance is what makes everything in this chapter simple.
The Star Connection: Line and Phase Quantities
Four quantities have to be kept apart, and most three-phase errors come from confusing two of them.
- Phase voltage \(V_{ph}\) — measured across one winding of the source or one branch of the load.
- Line voltage \(V_L\) — measured between any two line conductors.
- Phase current \(I_{ph}\) — flowing through one winding or one load branch.
- Line current \(I_L\) — flowing in a line conductor between source and load.
In the star (\(Y\)) connection the three windings are joined at a common point \(n\), the star point, and the free ends become the three lines. Each winding sits between a line and the star point, so the line current is the phase current. The line voltage, on the other hand, is a difference of two phase voltages, and that difference is where the \(\sqrt3\) comes from:
The same result follows from the triangle of the two phasors without any complex algebra. \(\mathbf{V}_{an}\) and \(-\mathbf{V}_{bn}\) have equal length \(V\) and include an angle of \(60^\circ\), so by the cosine rule
Repeating for the other two pairs gives \(\mathbf{V}_{bc} = \sqrt3\,V\angle{-90^\circ}\) and \(\mathbf{V}_{ca} = \sqrt3\,V\angle 150^\circ\): the three line voltages form a balanced set of their own, \(\sqrt3\) times as large as the phase voltages and leading them by \(30^\circ\). That \(30^\circ\) is not decoration. It reappears in the star–delta transformer, which shifts the phase of every voltage passing through it by \(30^\circ\), and in the two-wattmeter method of Section 3-7 where it is the entire origin of the \(\cos(30^\circ \pm \phi)\) readings.
The Delta Connection
In the delta (\(\Delta\), or mesh) connection the three windings are joined end to end in a closed loop and the lines are taken from the three junctions. Now each winding is connected directly between two lines, so the phase voltage is the line voltage. It is the current that must be resolved: the current leaving junction \(a\) is the difference of the two branch currents meeting there.
Before going further, one point about the closed loop. Three windings in series around a mesh look like an invitation to a large circulating current, and would be one if the three generated voltages did not sum to zero. They do, by the identity of Section 3-2, so the net driving voltage around the loop is zero and no circulating current flows — provided the set is balanced and free of triplen harmonics. Third-harmonic voltages are all in phase with one another and do not cancel around the mesh, which is exactly why a delta winding is deliberately provided on many transformers to give those harmonics a path and keep them out of the lines.
Applying KCL at junction \(a\), with branch currents \(\mathbf{I}_{ab} = I\angle 0^\circ\), \(\mathbf{I}_{bc} = a^2 I\) and \(\mathbf{I}_{ca} = aI\):
The structure of the two derivations is identical — a difference of two phasors \(120^\circ\) apart — which is why the same \(\sqrt3\) and the same \(30^\circ\) appear, with the sign of the shift reversed. In star the voltages combine and lead; in delta the currents combine and lag.
| Quantity | Star (Y) | Delta (Δ) |
|---|---|---|
| Line voltage | \(V_L = \sqrt3\,V_{ph}\), leading by \(30^\circ\) | \(V_L = V_{ph}\) |
| Line current | \(I_L = I_{ph}\) | \(I_L = \sqrt3\,I_{ph}\), lagging by \(30^\circ\) |
| Impedance per phase | \(Z_Y\) | \(Z_\Delta = 3Z_Y\) for the same load |
| Total power | \(P = 3V_{ph}I_{ph}\cos\phi = \sqrt3\,V_L I_L\cos\phi\) — the same expression for both | |
| Neutral available | Yes; carries \(0\) when balanced | No neutral point exists |
| Typical use | Generators, HV transformer windings, four-wire distribution | Motor windings, LV transformer windings, capacitor banks |
Power in a Balanced Three-Phase Circuit
Start with the promise made in Section 3-1. Let each phase carry \(v_k\) and \(i_k\) as in Chapter 1, with the phases displaced by \(120^\circ\) and the same impedance angle \(\phi\) in every phase. Each phase delivers the single-phase result, shifted:
The \(120^\circ\) displacement of the phase quantities becomes a \(240^\circ\) displacement of the double-frequency terms, because the argument contains \(2\omega t\). But three cosines whose arguments differ by \(240^\circ\) are still three unit phasors spaced \(120^\circ\) apart on the double-frequency plane, and by the identity \(1 + a + a^2 = 0\) they sum to zero at every instant. The oscillating parts cancel and only the constant parts survive:
A balanced three-phase load draws energy at a perfectly steady rate. The shaft of a three-phase motor sees no torque ripple of supply origin, and the prime mover driving a three-phase alternator sees a steady counter-torque. Neither statement is true of a single-phase machine, and both fail the moment the load becomes unbalanced.
For steady-state work the phasor form is what gets used. Chapter 1 defined complex power per phase as \(\mathbf{S} = \mathbf{V}\mathbf{I}^{*}\). Adding three identical contributions,
Identical for star and delta, because the \(\sqrt3\) that enters through the voltage in one connection enters through the current in the other. \(\phi\) is the angle of the load impedance — the angle between phase voltage and phase current — and never the angle between \(V_L\) and \(I_L\), which differs from it by \(30^\circ\).
Two habits follow from this. First, every three-phase rating quoted in this book — a 30 MVA generator, a 400 kV line, a 2 MVA transformer — is the three-phase total, and every voltage is the line-to-line value, unless it is explicitly labelled otherwise. Second, when a load is described as "50 kW at 0.8 power factor lagging" the reactive demand follows immediately as \(Q = P\tan\phi = 50 \times 0.75 = 37.5\) kvar, exactly as in Chapter 1; three phases changes the arithmetic of the currents, not the shape of the power triangle.
Per-Phase Analysis: Three Circuits Become One
Everything so far points to one conclusion: in a balanced system the three phases are copies of one another, differing only by a known \(120^\circ\) rotation. Solving all three is therefore three times as much work as it needs to be. Per-phase analysis makes the reduction formal, and it rests on two steps.
Step one: connect the neutrals. Take a star-connected source feeding a star-connected balanced load through three identical line impedances. The star point of the source and the star point of the load are both at the potential of the average of the three phase voltages, which by \(1+a+a^2=0\) is the same at both ends. Two points at identical potential may be joined by a wire of zero impedance without changing anything in the circuit, and the wire will carry \(\mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c = 0\). With that wire in place, phase \(a\) forms a complete loop on its own: source, line impedance, load impedance, return through the neutral. The three phases are decoupled.
Step two: convert every delta to its star equivalent. A delta load has no star point to connect, so it must first be replaced by the star that draws exactly the same line currents from the same line voltages. The general transformation, applied to the three branches of a mesh, is
The factor of three can also be read off the power. A delta branch sees the full line voltage \(V_L\) while a star branch sees \(V_L/\sqrt3\), so for the same impedance the delta branch dissipates three times as much; to draw the same power the delta impedance must be three times as large. This is the reason a star–delta starter reduces motor starting current to a third of its direct-on-line value: reconnecting the same windings in star triples their effective per-phase impedance as seen from the line.
Phases \(b\) and \(c\) are recovered at the end by multiplying the phase-\(a\) answer by \(a^2\) and \(a\) — that is, by subtracting \(120^\circ\) and adding \(120^\circ\). They are almost never written down, because they contain no new information.
This is the single most important simplification in power system analysis, and it is worth being explicit about what it costs. Per-phase analysis is exact for a balanced system and meaningless for an unbalanced one. Every load-flow calculation in Part 4, every symmetrical fault calculation in Chapter 21 and every stability study in Part 6 is a per-phase calculation. When the assumption breaks — a line-to-ground fault, one open conductor — Chapter 22 restores it by a change of variables that turns one unbalanced three-phase problem into three balanced ones.
Measuring Power: The Two-Wattmeter Method
A wattmeter reads the average of the product of the voltage across its pressure coil and the current through its current coil. To measure three-phase power the obvious approach is one meter per phase, but that requires access to the star point, which a delta load does not have and a sealed motor terminal box rarely offers. Blondel's theorem says fewer meters are needed anyway.
The total instantaneous power in a three-wire system is \(p = v_a i_a + v_b i_b + v_c i_c\), with all voltages referred to an arbitrary common point. With no neutral connection, \(i_a + i_b + i_c = 0\), so \(i_b = -(i_a + i_c)\). Substituting:
The total power is the sum of just two products. One wattmeter with its current coil in line \(a\) and its pressure coil across \(a\)–\(b\), a second with its current coil in line \(c\) and its pressure coil across \(c\)–\(b\), together measure the whole thing — for any load, balanced or not, star or delta. In general a system of \(n\) wires needs \(n-1\) wattmeters, which is Blondel's theorem.
Now specialise to a balanced load with lagging angle \(\phi\), abc sequence, \(V_{an}=V\angle0^\circ\). Then \(\mathbf{I}_a = I\angle{-\phi}\), \(\mathbf{I}_c = I\angle(120^\circ-\phi)\), \(\mathbf{V}_{ab} = \sqrt3 V\angle 30^\circ\) and \(\mathbf{V}_{cb} = -\mathbf{V}_{bc} = \sqrt3 V\angle 90^\circ\). Each meter reads the product of magnitudes times the cosine of the angle between its own voltage and its own current:
Adding and subtracting, with \(\cos X + \cos Y = 2\cos\frac{X+Y}{2}\cos\frac{X-Y}{2}\):
For a lagging load \(W_2 \ge W_1\); most textbooks simply label the higher-reading meter \(W_1\) and write \(\tan\phi = \sqrt3(W_1-W_2)/(W_1+W_2)\). The magnitude of the difference is what matters — the sign only tells you whether the load is lagging or leading.
The readings themselves are diagnostic. At unity power factor \(W_1 = W_2 = V_LI_L\cos30^\circ\): the meters agree. At \(\phi = 60^\circ\) (power factor 0.5), \(\cos(30^\circ+60^\circ) = 0\) and one meter reads exactly zero while the other carries all the power. Beyond \(\phi = 60^\circ\) the cosine goes negative, the pointer tries to go backwards, and the meter must be reversed and its reading subtracted. A student who forgets that subtraction on a low-power-factor load will report roughly twice the true power.
From Three Wires to One Line: The Single-Line Diagram
Section 3-6 established that a balanced network is solved one phase at a time. Draw that per-phase circuit for a real system — a generator, its step-up transformer, a transmission line, a step-down transformer, a load — and it is a chain of impedances between a source and a return. Two observations then finish the job of simplification.
The first is that the neutral return carries no current and drops no voltage, so drawing it adds nothing; it is understood to exist and is left out. The second is that the remaining single conductor stands for all three phases at once, since the other two differ only by \(\pm120^\circ\). What is left is one line per circuit, with a standard symbol wherever a piece of plant sits. That is the single-line diagram, or one-line diagram: the working drawing of power engineering.
It is not a wiring diagram and it is not to scale. Its purpose is to present, as compactly as possible, exactly the information needed to analyse the system: what is connected to what, at what voltage, with what rating, and through what impedance.
The three-line diagram — every conductor drawn — still has its uses in protection and metering work, where the phases genuinely differ: current transformer connections, relay wiring, the two-wattmeter arrangement of Section 3-7. For system studies it would be three times the ink for no extra information.
A single-line diagram is drawn at whatever level of detail the study demands. A planning diagram may show a whole regional grid with each substation as one bus. An operational diagram of a single substation shows every breaker, isolator, current transformer and earth switch. The same conventions apply at both extremes.
Symbols, Ratings and Reading an SLD
The symbols are largely standardised (IEC 60617 and IEEE 315 agree on the important ones). The table lists those used throughout this book, together with what has to be written beside each.
| Component | Symbol | Data marked alongside |
|---|---|---|
| Generator / alternator | Circle enclosing a sine or the letter G, with the winding connection (Y or Δ) and the earthing shown at its neutral | MVA rating, rated kV, \(X_d''\), \(X_d'\), \(X_d\) in % or per unit |
| Two-winding transformer | Two interlinked circles, or two coupled coils | MVA rating, voltage ratio kV/kV, \(X\) in % or per unit, vector group |
| Three-winding transformer | Three interlinked circles | Three MVA ratings, three voltages, \(X_{HM}, X_{ML}, X_{HL}\) |
| Transmission line | A plain straight line between two buses | Length, conductor type, \(R\), \(X\), \(B/2\) in ohms or per unit |
| Bus / busbar | A short thick line perpendicular to the connections | Bus number and nominal kV |
| Circuit breaker | A small square on the line (filled for air-blast, hollow for oil in older drawings) | Rated breaking capacity in MVA or kA |
| Isolator / disconnector | An open blade drawn at an angle to the line | Rated current; interrupts no load current |
| Static load | An arrow leaving the bus | MW and Mvar, or MVA and power factor |
| Synchronous / induction motor | Circle with M, connection shown | MVA or hp, kV, \(X''\) |
| Shunt capacitor / reactor | Two parallel bars / a coil, connected bus to earth | Mvar at rated voltage |
| Neutral earthing impedance | Resistor or reactor between the star point and the earth symbol | Ohms, or the earth-fault current it limits |
Three conventions matter more than the shapes. Every voltage written on a single-line diagram is a line-to-line value, and every MVA is a three-phase total, following Section 3-5. Every impedance is given as a percentage or a per-unit value on the plant's own rating — a transformer marked "20 MVA, 33/11 kV, 8%" has a reactance of 8% on a 20 MVA, 33 kV base, and Chapter 4 exists to convert that onto a common base before it can be added to anything else. The transformer connection and earthing are shown even though the neutral wire is not drawn, because they decide what happens in an unsymmetrical fault.
Read the diagram above from left to right and notice what it does not tell you. The generator reactance is 0.20 per unit on 30 MVA; the transformer reactance is 0.10 per unit on 35 MVA; the line reactance is 100 ohms at 132 kV. Three numbers on three different bases, one of them not even normalised. They cannot be added, cannot be put in series, cannot be used until they are expressed against a single common reference. Producing that common reference is what Chapter 4 does, and it is the last piece of preparation before the network itself can be analysed.
Worked Examples
Problem. A balanced star-connected load of \(Z = 8 + j6\;\Omega\) per phase is supplied at 400 V, 50 Hz (line value). Find the phase voltage, the line current, and \(P\), \(Q\) and \(S\).
Solution. In star the phase voltage is the line value divided by \(\sqrt3\):
Now the powers, computed twice as a check — once from the per-phase resistance and reactance, once from the line quantities:
The check \(S^2 = P^2+Q^2\) gives \(\sqrt{12.80^2 + 9.60^2} = \sqrt{163.8+92.2} = 16.00\) kVA, and \(P/S = 12.80/16.00 = 0.8\), the power factor. Every three-phase problem should close this way.
Problem. The three impedances of Example 1 are reconnected in delta across the same 400 V supply. Find the phase and line currents and the power drawn, and explain the ratio to the star case.
Solution. In delta each branch now sees the full line voltage:
Every quantity is exactly three times its star value: \(38.40/12.80 = 3\), \(69.28/23.09 = 3\). The reason is Section 3-6 in reverse. The same physical impedance connected in delta presents \(Z_\Delta/3 = Z/3\) per phase to the line instead of \(Z\), so the line current and hence the power triple. This is the star–delta starter in one line of arithmetic: start the motor in star to hold the starting current to a third, then switch to delta for running.
Problem. A balanced 11 kV (line) source feeds a delta-connected load of \(90 + j120\;\Omega\) per phase through a three-phase feeder of impedance \(1.0 + j3.0\;\Omega\) per conductor. Find the line current, the voltage at the load, the power delivered and the feeder loss.
Solution. Convert the delta load to its star equivalent, then draw the single-phase equivalent circuit of Section 3-6:
The load voltage follows from the star-equivalent impedance, and the line value by multiplying by \(\sqrt3\):
The voltage has fallen from 11.00 kV to 10.38 kV, a drop of 5.7%, and 43 kW of the 1.335 MW sent has been lost as heat in the conductors — 3.2%. Both numbers are the subject of Chapter 13. As a check on the delta conversion, each delta branch carries \(119.8/\sqrt3 = 69.2\) A, and \(10\,375/150 = 69.2\) A directly from the branch impedance \(|90+j120| = 150\;\Omega\). \(\checkmark\)
Problem. Two wattmeters connected to measure the power taken by a balanced 400 V three-phase load read 8.2 kW and 2.6 kW. Find the total power, the power factor, the reactive power and the line current. What would the readings become if the power factor fell to 0.5?
Solution. The load is inductive, so the larger reading is the \(\cos(30^\circ-\phi)\) meter, \(W_2 = 8.2\) kW and \(W_1 = 2.6\) kW.
At \(\cos\phi = 0.5\) the angle is \(\phi = 60^\circ\), so \(W_1 = V_LI_L\cos(30^\circ+60^\circ) = V_LI_L\cos 90^\circ = 0\). One meter reads zero and the other reads the entire power, \(W_2 = V_LI_L\cos(-30^\circ) = 0.866\,V_LI_L = \sqrt3 V_LI_L\times 0.5 = P\). Any power factor below 0.5 pushes \(W_1\) negative, and the meter must be reversed and its reading subtracted.
Problem. A 415 V, 50 Hz three-phase bus supplies an induction motor taking 60 kW at 0.80 power factor lagging and a resistance heater taking 15 kW at unity power factor. Find the total kVA and power factor, and the capacitance per phase of a delta-connected bank that will raise the power factor to 0.95 lagging.
Solution. Powers add as complex numbers, exactly as in Chapter 1 — this is the whole reason for working in \(P\) and \(Q\) rather than kVA.
Capacitors supply reactive power without absorbing real power, so \(P\) is unchanged and only \(Q\) is reduced:
The line current falls from \(87\,460/(\sqrt3\times415) = 121.7\) A to \(78\,950/(\sqrt3\times415) = 109.8\) A, a 10% reduction in every conductor, breaker and transformer between here and the generator. Had the bank been star-connected each unit would see only \(V_L/\sqrt3\), so three times the capacitance would be needed: \(C_Y = 3C_\Delta = 376\ \mu\)F. Delta connection is preferred for exactly this reason — less capacitance for the same kvar, though each unit must be insulated for the full line voltage.
Problem. For the system drawn in Section 3-9, find the full-load current of the generator, the current in the 132 kV line when it carries the generator's full 30 MVA, and the current drawn by the 20 MVA load at 33 kV. Comment on what the three answers imply for the analysis.
Solution. Every rating on the diagram is a three-phase MVA and every voltage is line-to-line, so \(I = S/(\sqrt3 V_L)\) throughout.
The same 30 MVA appears as 1575 A at the generator terminals and 131 A on the line — a ratio of exactly 12, the transformer ratio \(132/11\), as Chapter 2's voltage-ladder argument requires. Now try to combine the impedances. The generator offers 0.20 per unit on 30 MVA, the transformer 0.10 per unit on 35 MVA, the line 100 ohms at 132 kV, the second transformer 0.08 per unit on 25 MVA. These four numbers are measured against four different yardsticks and refer to three different voltage levels; adding them in series, which is what any fault or load-flow calculation must do, is meaningless as they stand. Referring impedances through transformer turns ratios by hand would work but is error-prone and has to be repeated for every base change. The per-unit system of Chapter 4 does it once and for all.
Chapter Summary
The three pulsating phase powers cancel: \(p_{3\phi} = 3VI\cos\phi\) at every instant.
\(a = 1\angle120^\circ\), \(1+a+a^2 = 0\), so a balanced neutral carries no current.
\(I_L = I_{ph}\) and \(V_L = \sqrt3 V_{ph}\) leading by \(30^\circ\).
\(V_L = V_{ph}\) and \(I_L = \sqrt3 I_{ph}\) lagging by \(30^\circ\); \(Z_\Delta = 3Z_Y\).
\(P = \sqrt3 V_LI_L\cos\phi\) for both connections; \(\phi\) is the impedance angle.
Balanced networks are solved as one single-phase circuit at \(V_L/\sqrt3\).
\(P = W_1+W_2\), \(\tan\phi = \sqrt3(W_2-W_1)/(W_2+W_1)\); one reads zero at pf 0.5.
One line for three conductors, symbols for plant, ratings and impedances marked.
Problems
Assume balanced conditions, abc phase sequence and 50 Hz throughout. Quote every voltage as a line value and every power as a three-phase total unless the question says otherwise.
- A balanced star-connected load of \(15 + j20\;\Omega\) per phase is supplied at 415 V. Find the line current, the power factor, and \(P\), \(Q\) and \(S\). Verify that \(S^2 = P^2+Q^2\).
- The same three impedances are reconnected in delta on the same supply. Without repeating the full calculation, state the new line current and power, and justify the factor you used.
- A 400 V three-phase supply feeds a delta-connected load of \(30\angle 40^\circ\;\Omega\) per phase through a feeder of \(0.4 + j0.6\;\Omega\) per conductor. Find the load terminal voltage, the line current and the percentage voltage drop.
- Two wattmeters measuring a balanced load read 12 kW and 4 kW. Find the total power, the power factor and the reactive power. Repeat for readings of 12 kW and \(-4\) kW, and state what the negative sign means physically.
- Show that for a balanced load the ratio \(W_1/W_2\) of the two wattmeter readings depends only on the power factor, and use this to find the power factor when one meter reads half the other.
- A 6.6 kV bus supplies a 400 kW motor at 0.75 power factor lagging and a 250 kW furnace at unity power factor. Find the total line current and the delta-connected capacitor bank in kvar and in microfarads per phase needed to bring the overall power factor to 0.92 lagging.
- Prove that three sinusoidal quantities of equal amplitude displaced by \(120^\circ\) sum to zero at every instant, and explain why the same proof applied to the double-frequency terms of the phase powers gives constant total power but does not apply to the third-harmonic components of the phase voltages.
- Draw the single-line diagram of a system consisting of a star-connected earthed generator (25 MVA, 13.8 kV, \(X'' = 0.18\)) feeding through a circuit breaker and a delta–star transformer (30 MVA, 13.8/110 kV, \(X = 0.09\)) a 110 kV line of \(j65\;\Omega\), which supplies a star–star transformer (20 MVA, 110/11 kV, \(X = 0.07\)) and a 15 MVA load at 0.9 power factor lagging. Mark all ratings, and state the full-load current at each of the three voltage levels.