Set 24 — Three-Phase Power
Set 23 closed by showing that single-phase power pulsates between zero and twice its average even at unity power factor, and that three loads fed 120° apart cancel that pulsation exactly. This set builds the system that exploits it. Two connections are possible — star and delta — each with its own relationship between line and phase quantities, and the \(\sqrt3\) factors that follow are the source of most errors in the subject. The compensating simplicity is that a balanced three-phase problem reduces to a single-phase one, so nothing from Set 23 is wasted.
Star (Y) connection:
\[ V_L = \sqrt3\,V_{ph} \ \text{(leading by }30°\text{)}, \qquad I_L = I_{ph} \]Delta (Δ) connection:
\[ V_L = V_{ph}, \qquad I_L = \sqrt3\,I_{ph} \ \text{(lagging by }30°\text{)} \]Total power — the same formula for both:
\[ P = \sqrt3\,V_LI_L\cos\phi = 3V_{ph}I_{ph}\cos\phi = 3|\mathbf{I}_{ph}|^2R_{ph} \]with \(\phi\) the impedance angle, never the angle between \(V_L\) and \(I_L\).
Similarly \(Q = \sqrt3V_LI_L\sin\phi\) and \(S = \sqrt3V_LI_L\), with \(S^2 = P^2+Q^2\) as before.
Balanced problems reduce to one phase. Convert any delta to star by \(\mathbf{Z}_Y = \mathbf{Z}_\Delta/3\), analyse a single phase with the neutral as reference, and multiply the power by three — Problem 13.
Unbalanced problems do not. A four-wire system still separates into three independent single-phase circuits; a three-wire system does not, and the star point shifts — Problems 14 and 15.
Convention: RMS phasors throughout, as adopted in Set 23, and positive (abc) sequence unless stated.
Prove that a balanced three-phase load draws constant instantaneous power, and show that this fails for any number of phases other than three or more. Explain the engineering consequences.
The three phase powers. Each phase behaves as the single-phase load of Set 23, Problem 1, with its own voltage displaced by 120°:
Note the doubling: a 120° displacement in \(\omega t\) becomes 240° in \(2\omega t\). That is the crux.
Sum the oscillating terms. Reducing \(480°\) modulo 360° gives 120°, so the three arguments differ by 120° from each other:
Three unit phasors 120° apart sum to zero — the same identity that makes the three source voltages balance.
Hence the total:
The instantaneous power equals the average power at every instant. Each phase still pulsates violently; what one phase gives up, the others take on.
Why not two phases? Two sources 180° apart give \(2\times180° = 360° \equiv 0\) in the doubled angle — the two pulsations are in phase and add rather than cancel:
| Phases \(n\) | Displacement | In \(2\omega t\) | Sum |
|---|---|---|---|
| 1 | — | — | Full pulsation |
| 2 (split phase) | 180° | 360° ≡ 0° | Reinforces |
| 3 | 120° | 240° | Zero |
| 4 | 90° | 180° | Zero |
| \(n \ge 3\) | \(360°/n\) | \(720°/n\) | Zero |
Any \(n \ge 3\) works. Three is chosen as the smallest that does — more phases would need more conductors for no further benefit.
The engineering consequences:
| Consequence | Why |
|---|---|
| Constant shaft torque | Torque follows power; no \(2\omega\) vibration |
| Self-starting motors | Three windings produce a rotating field |
| Smaller conductors | 25% less copper — Problem 18 |
| Two voltages available | \(V_L\) and \(V_{ph}\) from one supply |
| No neutral current when balanced | The three currents also sum to zero |
Define phase sequence, write the two possible sets of balanced voltages, and explain why the sequence matters in practice.
Phase sequence is the order in which the three voltages reach their positive maxima. Two orders are possible:
| Sequence | Also called | Voltages |
|---|---|---|
| abc | Positive | \(V\angle0°\), \(V\angle{-120°}\), \(V\angle{+120°}\) |
| acb | Negative | \(V\angle0°\), \(V\angle{+120°}\), \(V\angle{-120°}\) |
Note \(V\angle{+120°} = V\angle{-240°}\) — the same phasor, and legacy notation often uses the latter. Both describe \(V_c\) in positive sequence.
The balance conditions. A balanced set satisfies both:
Verifying the second for positive sequence:
This is the identity that made Problem 1 work, and it is why a balanced four-wire system carries no neutral current.
Why it matters:
| Consequence | Detail |
|---|---|
| Motor direction | Reversing the sequence reverses the rotating field, and the motor runs backwards |
| Paralleling supplies | Two sources of opposite sequence cannot be connected — a short circuit results |
| Unbalanced analysis | Symmetrical components (beyond this book) separate positive, negative and zero sequences |
| Metering | Some instruments read incorrectly on reversed sequence |
Swapping any two of the three conductors reverses the sequence — which is how a motor's direction is changed, and why the connection must be checked after any rewiring.
The \(a\)-operator is a convenient shorthand:
Positive sequence is then \(\mathbf{V}_a,\ a^2\mathbf{V}_a,\ a\mathbf{V}_a\). Multiplying by \(a\) rotates a phasor 120° anticlockwise without changing its magnitude.
Determining sequence experimentally. A simple indicator uses two lamps and a capacitor in a star: the unbalanced star point shifts one way or the other depending on sequence, making one lamp brighter. Problem 15's neutral-displacement calculation is exactly the analysis of such a device.
Derive the line–phase relationships for a star connection, including the 30° phase shift, and state which quantity leads.
The definitions. In a star, phase voltages are measured from each line to the neutral point; line voltages are measured between two lines:
Line voltage by KVL:
Convert to polar:
So the line voltage leads its phase voltage by 30° and is \(\sqrt3\) times larger.
The other two follow by symmetry:
| Line voltage | Value |
|---|---|
| \(\mathbf{V}_{ab}\) | \(\sqrt3V_{ph}\angle30°\) |
| \(\mathbf{V}_{bc}\) | \(\sqrt3V_{ph}\angle{-90°}\) |
| \(\mathbf{V}_{ca}\) | \(\sqrt3V_{ph}\angle150°\) |
Themselves a balanced set, 120° apart and summing to zero — as KVL round the three lines requires.
Where the \(\sqrt3\) comes from geometrically. Two phasors of equal length \(V\) separated by 120° have a difference of
The chord of a 120° arc. It is not an approximation and has nothing to do with the number of phases beyond the 120° displacement.
Currents are trivial in star:
because each line conductor is the phase conductor — there is nowhere else for the current to go. Numerically, a 400 V star system has \(V_{ph} = 400/\sqrt3 = 231\ \text{V}\), which is why domestic single-phase outlets in such systems read 230 V.
Derive the line–phase relationships for a delta connection, and explain why the roles of voltage and current are exchanged relative to star.
Voltages are immediate. Each delta branch is connected directly between two lines, so
There is no neutral and no other voltage available. A 400 V delta load has 400 V across every phase.
Currents require KCL at each corner of the delta. With phase currents \(\mathbf{I}_{ab}\), \(\mathbf{I}_{bc}\), \(\mathbf{I}_{ca}\) circulating round the triangle, the line current at corner \(a\) is
Current arrives along the line and splits into two branches — one leaving through \(ab\), one arriving from \(ca\).
With a balanced set \(\mathbf{I}_{ab} = I_{ph}\angle0°\), \(\mathbf{I}_{bc} = I_{ph}\angle{-120°}\), \(\mathbf{I}_{ca} = I_{ph}\angle{+120°}\):
The line current lags its phase current by 30° and is \(\sqrt3\) times larger — the exact mirror of the star voltage result.
Why the roles exchange. The two connections are duals:
| Star | Delta | |
|---|---|---|
| Elements meet at | A common node (neutral) | Form a closed loop |
| Shared quantity | Current (\(I_L = I_{ph}\)) | Voltage (\(V_L = V_{ph}\)) |
| Requires | KVL for line voltages | KCL for line currents |
| \(\sqrt3\) appears in | Voltage, leading 30° | Current, lagging 30° |
Set 17's duality again: series and parallel, KVL and KCL, voltage and current. A star and a delta are the three-phase versions of the same pair.
The power formula is identical for both, which is worth checking. For delta:
and for star:
The \(\sqrt3\) lands on different quantities but the product is the same — which is why one power formula serves both connections.
A 400 V three-phase system supplies a delta-connected load of 1500 W at 0.8 power factor lagging. Find the phase and line currents and the phase impedance.
Per-phase power. A balanced load shares the total equally:
For delta, the phase voltage is the line voltage:
Solve for the phase current:
The line current is \(\sqrt3\) larger in delta:
The phase impedance, with the angle from the power factor:
Check against the total-power formula:
and independently from the resistance:
A note on the impedance angle. It equals the power-factor angle exactly — the current lags the phase voltage by 36.87°. It does not lag the line current by that amount, nor the line voltage: those differ by the 30° of Problem 4. Only the per-phase relationship carries the impedance angle.
A 400 V three-phase system supplies 1200 W to a star-connected load at 0.8 power factor lagging. Find the line and phase currents and the phase impedance.
Per-phase power:
For star, the phase voltage is reduced by \(\sqrt3\):
This is the single change from Problem 5, and it is the whole difference between the two connections at this stage.
Phase current, which equals the line current in star:
The phase impedance:
Compare with Problem 5's delta. The two problems have different total powers, so the comparison must be normalised. For the same load power on the same line voltage:
| Star | Delta | Ratio | |
|---|---|---|---|
| \(V_{ph}\) | \(V_L/\sqrt3\) | \(V_L\) | \(1/\sqrt3\) |
| \(I_{ph}\) at same \(P\) | \(\sqrt3 \times\) larger | smaller | \(\sqrt3\) |
| \(Z_{ph}\) at same \(P\) | \(Z_\Delta/3\) | \(3Z_Y\) | \(1/3\) |
| \(I_L\) | Identical | 1 | |
The last row is the important one: two loads drawing equal power from equal line voltage draw equal line current, whichever way they are connected. The supply cannot tell the difference.
Verify the \(Z_\Delta = 3Z_Y\) relation on these numbers, scaling Problem 5's load to 1200 W:
Impedance scales inversely with power at fixed voltage, so the scaling is legitimate. The factor of three is exact and is the basis of Problem 19.
A 400 V, 50 Hz three-phase supply feeds a delta-connected load of 6 Ω resistance and 8 Ω reactance per phase. Find the phase and line currents and the active, reactive and apparent powers.
Delta, so the phase voltage is the line voltage:
Per-phase impedance:
Reading the power factor straight off the impedance triangle avoids computing an angle at all.
aCurrents:
bThe three powers, from the line quantities:
Two independent checks. From the per-phase elements:
and from the power triangle:
The \(3I_{ph}^2R\) route is the most reliable — it needs no \(\sqrt3\), no power factor and no angle, only the phase current and the resistance.
Note the poor power factor. At 0.6 lagging the supply carries 48 kVA to deliver 28.8 kW — 67% more current than a unity-power-factor load of the same wattage would need. Problem 17 corrects it.
Each phase of a star-connected load has 6 Ω resistance and 6 Ω reactance, on a 400 V, 50 Hz supply. Find the phase voltage and current, the power factor, and the power per phase and in total.
Phase voltage:
Per-phase impedance, the special case \(R = X\):
Equal resistance and reactance always give exactly 45°, hence \(\text{pf} = \cos45° = 0.7071\) and \(P = Q\).
Phase current, equal to line current:
Power per phase — using \(I^2R\), which needs no power factor:
A closed form worth noting. Substituting \(V_{ph} = V_L/\sqrt3\) and \(I_{ph} = V_{ph}/|\mathbf{Z}|\):
The three and the \(\sqrt3^2\) cancel exactly, leaving a formula in line voltage alone — convenient, and free of any \(\sqrt3\) to misplace.
The reactive power equals the real power here, since \(R = X\):
So the supply must carry 41% more apparent power than the load consumes — a direct consequence of the 0.707 power factor.
A balanced star-connected load of \((8+j6)\ \Omega\) per phase is supplied at 400 V three-phase. Find the line current, power factor, total power and total volt-amperes.
Phase voltage and impedance:
A 3-4-5 triangle scaled by two — the arithmetic is exact throughout.
Line current, equal to phase current in star:
Power factor from the impedance triangle:
Total power and apparent power:
Confirm by the closed form of Problem 8:
Both agreeing, and neither requiring a power factor or a \(\sqrt3\).
What if the same impedance were connected in delta? By Problem 6's equivalence, a delta of \((8+j6)\) behaves as a star of \((8+j6)/3\), so every current and power triples:
Which is Problem 12's result, previewed. Note that this is the same load impedance reconnected, not a different load.
A star-connected load consumes 12 kW at 0.8 power factor lagging from a 400 V, 50 Hz supply. Find the resistance and inductance per phase.
Per-phase power and voltage:
Phase current:
Impedance magnitude:
Resolve into components using \(\cos\phi = 0.8\), \(\sin\phi = 0.6\):
Convert reactance to inductance at 50 Hz:
Check by an independent route. The resistance can be found directly from the power without ever computing the impedance:
and the reactive power gives the reactance:
A caution about the connection. The same 12 kW at 0.8 lagging in a delta would give \(R = 25.6\ \Omega\) and \(L = 61.1\ \text{mH}\) — exactly three times each, by the equivalence of Problem 6. The nameplate data alone cannot tell you which connection is inside the machine, so it must be stated.
A balanced delta load of \((12+j9)\ \Omega\) per phase is supplied from a 415 V, 50 Hz three-phase system. Find the phase and line currents, power factor, and total active and apparent power.
Delta, so the phase voltage is the line voltage:
Per-phase impedance:
Another 3-4-5 triangle, this time scaled by three.
Currents:
Powers:
Check with the delta closed form. Adapting Problem 8's result — for delta the phase voltage is \(V_L\) rather than \(V_L/\sqrt3\), so a factor of three appears:
Agreeing to four figures, and computed without a power factor, a \(\sqrt3\) or a current.
The two closed forms side by side:
| Connection | \(P\) | \(Q\) |
|---|---|---|
| Star | \(V_L^2R/|\mathbf{Z}|^2\) | \(V_L^2X/|\mathbf{Z}|^2\) |
| Delta | \(3V_L^2R/|\mathbf{Z}|^2\) | \(3V_L^2X/|\mathbf{Z}|^2\) |
The factor of three between them is the whole content of Problem 12.
A load of \(20\angle30°\ \Omega\) per phase is supplied at 400 V. Compare the line current and total power when connected in star and in delta, and explain the ratio.
The power factor is the same in both cases, being a property of the impedance alone:
aStar connection:
bDelta connection:
The ratios:
Why exactly three, traced through the two \(\sqrt3\) factors:
| Step | Star | Delta | Factor |
|---|---|---|---|
| Phase voltage | \(V_L/\sqrt3\) | \(V_L\) | \(\sqrt3\) |
| Phase current | \(V_L/\sqrt3 Z\) | \(V_L/Z\) | \(\sqrt3\) |
| Power per phase | \(V_{ph}I_{ph}\cos\phi\) | \(\sqrt3 \times \sqrt3 = 3\) | |
Each phase sees \(\sqrt3\) times the voltage and therefore carries \(\sqrt3\) times the current, and power is their product.
The practical application — star–delta starting. An induction motor started in star draws only a third of the current it would draw in delta, and develops a third of the torque. Once running, it is switched to delta for full performance:
| Stage | Connection | Line current | Torque |
|---|---|---|---|
| Starting | Star | 33% | 33% |
| Running | Delta | 100% | 100% |
This limits the inrush that would otherwise dip the supply voltage for every other customer on the feeder — at the cost of reduced starting torque, so it suits only motors that start on light load.
A 400 V three-phase supply feeds a delta load of \((30+j40)\ \Omega\) per phase through a line of impedance \((0.5+j1)\ \Omega\) per conductor. Find the line current, the voltage at the load and the transmission efficiency, using a per-phase equivalent circuit.
The difficulty and its resolution. The line impedance is in the line conductors while the load is in delta — they cannot be added directly. Convert the delta to its star equivalent, and everything becomes a single series path per phase.
Build the per-phase circuit. Take one phase from the source neutral through the line to the load neutral:
This is legitimate because in a balanced system no current flows between the two neutrals, so they may be joined by an imaginary wire of zero impedance.
The line current:
The voltage at the load:
A drop from 400 V to 375 V — 6.2%, which would be unacceptable in practice and indicates an undersized cable.
Powers and efficiency, counting all three phases:
Note that the load's delta resistance is 30 Ω but the star-equivalent 10 Ω must be used with the line current — mixing the two is the standard error here.
Why the per-phase method works, stated carefully:
| Requirement | Reason |
|---|---|
| Balanced source | Otherwise the phases differ |
| Balanced load | Otherwise neutrals are not at equal potential |
| Any delta converted to star | To put everything in the line path |
| Multiply power by three at the end | One phase was analysed |
If either source or load is unbalanced the method fails, and Problems 14 to 16 must be used instead.
A three-phase four-wire supply at 400 V line feeds three non-inductive loads of 16 kW, 8 kW and 12 kW between the R, Y and B phases and neutral. Calculate the neutral current.
The four-wire system decouples. Because the neutral holds each load's return at the star point, every phase behaves as an independent single-phase circuit at \(V_{ph}\):
This is what makes the problem easy — and it is exactly what fails in Problem 15.
The three phase voltages:
Each load is resistive, so its current is in phase with its own phase voltage, with magnitude \(P/V_{ph}\):
The angle matches the voltage because the load is purely resistive. For a reactive load each current would be displaced by its own impedance angle, and the arithmetic below would be unchanged in form.
The neutral carries the phasor sum by KCL at the star point:
Resolving into rectangular components:
Exactly 30 A — the numbers were chosen to make it so.
A check worth doing. Had the three loads been equal, the currents would form a balanced set and
by the identity of Problem 2. The 30 A here measures the departure from balance, not the size of the load — note that it is smaller than any of the three phase currents.
The common error is to compute each current as \(P/\mathbf{V}\) with the voltage as a phasor in the denominator, which conjugates the angle and flips the sign of every imaginary part. Dividing a scalar power by a phasor is not a valid operation; the correct statement is \(\mathbf{I} = (S/\mathbf{V})^{*}\), and for a resistive load this reduces to a magnitude at the voltage's own angle.
An unbalanced star load of \(\mathbf{Z}_A = 10\ \Omega\), \(\mathbf{Z}_B = (10+j10)\ \Omega\), \(\mathbf{Z}_C = 20\ \Omega\) is supplied at 400 V three-phase with no neutral. Find the star-point displacement and the three phase voltages across the loads.
Why this is harder. Without a neutral, the load's star point is not tied to the source's. It floats to whatever potential makes the three currents sum to zero — and that potential is generally not zero.
Millman's theorem (Set 14) gives the displacement directly:
This is simply KCL at the floating node, solved for its potential — the supernode method of Set 7 applied to a three-branch star.
The admittances:
Evaluating with \(V_{ph} = 230.9\ \text{V}\):
The load's star point sits 29 V away from the source neutral — a substantial displacement, and the entire consequence of removing the neutral wire.
The voltages actually across each load:
| Phase | Load | Voltage across it | vs nominal 230.9 V | Current |
|---|---|---|---|---|
| A | \(10\ \Omega\) | 232.3 V | +0.6% | 23.23 A |
| B | \(10+j10\) | 256.7 V | +11.1% | 18.15 A |
| C | \(20\ \Omega\) | 206.6 V | −10.5% | 10.33 A |
One load is over-volted by 11% and another under-volted by 10.5% — both well outside the ±6% that equipment is normally designed to tolerate.
Verify by KCL, which is the condition that defined \(\mathbf{V}_N\):
With no neutral there is nowhere for a residual current to go, so this must hold exactly — and it is the check that confirms the displacement was computed correctly.
Contrast the two systems:
| Four-wire | Three-wire | |
|---|---|---|
| Star point | Held at source neutral | Floats |
| Load voltages | All equal to \(V_{ph}\) | Unequal |
| Phases | Independent | Coupled |
| Method | Three separate calculations | Millman, then back-substitute |
| Residual current | Flows in neutral | Must be zero |
Set out the neutral conductor's function, explain why it is never fused, and describe the harmonic problem that can make it carry more current than the phases.
Its function is to hold every phase voltage at \(V_L/\sqrt3\) regardless of imbalance. Problems 14 and 15 are the two cases side by side: with a neutral, imbalance produces a modest neutral current; without one, it produces voltage errors of over 10%.
Why it is never fused or switched. Consider what happens if the neutral opens while the phases stay connected:
The system converts instantly from Problem 14's case to Problem 15's. With a badly unbalanced load — say one heavily loaded phase and one lightly loaded — the displacement can be severe:
| Condition | Lightly loaded phase sees |
|---|---|
| Neutral intact | 230 V |
| Neutral open, moderate imbalance | 250–300 V |
| Neutral open, severe imbalance | Approaching 400 V |
In the limit of one phase open-circuit and the other two loaded, the lightly loaded phase approaches the full line voltage. A broken neutral is one of the most destructive faults in low-voltage distribution, and it damages customers' equipment rather than the network's.
The harmonic problem. The balanced-current cancellation relies on the three currents being 120° apart. For the third harmonic and its multiples, the displacement is
so the three third-harmonic currents are in phase. They do not cancel — they add arithmetically in the neutral.
The consequence:
So a load whose current is 33% third harmonic — typical of switched-mode power supplies and LED drivers — gives a neutral current comparable to the phase current even when the fundamental is perfectly balanced:
| Component | Per phase | In neutral |
|---|---|---|
| Fundamental | \(I_1\) | 0 (cancels) |
| 3rd harmonic | \(0.33I_1\) | \(3 \times 0.33I_1 = I_1\) |
| Total | \(1.05I_1\) | \(\approx I_1\) |
The neutral carries nearly the full phase current while being sized — under older practice — at half the phase conductor's cross-section. Overheated neutrals in office buildings full of computers were a recognised problem before standards changed.
Why the third harmonic behaves this way is worth stating generally. Harmonic \(h\) has phase displacement \(120h\) degrees:
| Harmonic | \(120h \bmod 360\) | Sequence | In neutral |
|---|---|---|---|
| 1, 4, 7, … | 120° | Positive | Cancels |
| 2, 5, 8, … | 240° | Negative | Cancels |
| 3, 6, 9, … | 0° | Zero | Adds |
Multiples of three are called triplen harmonics for this reason, and they are the ones that matter for neutral sizing.
The 28.8 kW load of Problem 7 runs at 0.6 lagging on 400 V, 50 Hz. Find the capacitance per phase to correct to 0.95 lagging, in both star and delta, and explain which is preferred.
The reactive powers, exactly as in Set 23, Problem 11 but for the whole three-phase load:
Confirming \(Q_1 = 38.4\) kvar against Problem 7's direct calculation.
aDelta-connected capacitors. Each sees the full line voltage:
bStar-connected capacitors. Each sees only \(V_L/\sqrt3\):
The comparison:
| Delta | Star | Ratio | |
|---|---|---|---|
| Capacitance needed | 191.8 µF | 575.5 µF | 1 : 3 |
| Voltage rating needed | 400 V | 231 V | \(\sqrt3\) : 1 |
| Stored energy \(\tfrac12CV^2\) per unit | Equal | 1 : 1 | |
Delta needs one third of the capacitance but at \(\sqrt3\) times the voltage. Since a capacitor's physical size and cost scale roughly with \(CV^2\) — the stored energy — the two arrangements are comparable in bulk, and the last row makes this precise.
Why delta is usually chosen in practice, despite the equal energy:
| Reason | Detail |
|---|---|
| Lower capacitance | Fewer or smaller elements for the same kvar |
| No neutral needed | Works on any three-wire supply |
| Standard ratings | Capacitors are commonly rated at line voltage |
| Better under imbalance | No floating star point to displace |
Star is preferred where the available capacitor voltage rating is limited, or in high-voltage banks where dividing the voltage is itself the objective.
The result:
A 37% reduction in current, and hence a 60% reduction in line losses — from a passive bank drawing no real power at all.
Show that a three-phase three-wire system transmits a given power over a given distance, at a given voltage and given loss, using 75% of the conductor material required by a single-phase two-wire system.
Fix what must be held equal: the power \(P\), the voltage \(V\) between conductors, the power factor, the distance \(\ell\), and the total \(I^2R\) loss. What is then compared is the total volume of copper.
Single-phase, two wires:
Three-phase, three wires:
The three-phase line current is smaller by \(\sqrt3\) — the single most important consequence of the whole arrangement.
Equate the losses:
Each three-phase conductor may have twice the resistance, because it carries less current and there are three of them rather than two.
Convert to cross-sectional area. Since \(R = \rho\ell/A\), doubling the resistance halves the area:
Compare the total volume of conductor:
Extending the comparison:
| System | Conductors | Relative copper |
|---|---|---|
| Single-phase, 2-wire | 2 | 100% |
| Three-phase, 3-wire | 3 | 75% |
| Three-phase, 4-wire (full neutral) | 4 | 100% |
| Three-phase, 4-wire (half neutral) | 3.5 | 87.5% |
Which is why transmission — where every load is balanced three-phase machinery — uses three wires and no neutral, while distribution to individual premises accepts the fourth conductor's cost in exchange for the voltage stability of Problem 16.
The saving is larger than 25% in practice, because the smaller current also permits smaller insulators, lighter towers and lower-rated switchgear. The copper figure is a lower bound on the economic advantage, not the whole of it.
Establish \(\mathbf{Z}_Y = \mathbf{Z}_\Delta/3\) for balanced loads, show it follows from Set 2's general transformation, and identify when the general form is needed instead.
The general transformation from Set 2, for a delta of \(\mathbf{Z}_{ab}\), \(\mathbf{Z}_{bc}\), \(\mathbf{Z}_{ca}\) to an equivalent star:
The star arm at a node is the product of the two delta arms meeting there, divided by the sum of all three.
For a balanced delta, all three are \(\mathbf{Z}_\Delta\):
One line of algebra, and it holds for complex impedances exactly as for resistances — the transformation was derived from Kirchhoff's laws and linearity, so Set 22, Problem 1's argument applies.
Verify it independently by power. A delta on line voltage \(V_L\) draws
and a star of \(\mathbf{Z}_\Delta/3\) draws
Identical, confirming the equivalence is genuine and not merely a definition.
Where it is used:
| Situation | Purpose |
|---|---|
| Line impedance present | Put load and line in one series path — Problem 13 |
| Mixed star and delta loads | Convert all to one form, then add admittances |
| Per-phase equivalent circuit | The method requires star throughout |
| Motor equivalent circuits | Standard models are per-phase star |
A worked instance. A star load of \((6+j8)\ \Omega\) in parallel with a delta load of \((30+j15)\ \Omega\) per phase, on 400 V. Convert the delta:
Now combine per phase, as two impedances across the same \(V_{ph}\):
Using \(P = 3|\mathbf{V}|^2G\) — the conductance form of Set 23, Problem 15 — which avoids inverting the admittance at all.
When the general form is needed. Only when the load is unbalanced. Then the three star arms differ, each given by its own product-over-sum, and no shortcut applies. An unbalanced delta cannot be handled by the per-phase method in any case, so the transformation is usually a step towards a mesh or nodal analysis rather than a simplification in itself.
Summarise what three-phase working achieves and what it costs, and identify the measurement problem that Set 25 must solve.
The gains, each established in this set:
| Gain | Magnitude | Problem |
|---|---|---|
| Constant instantaneous power | Pulsation entirely removed | 1 |
| Self-starting motors | Rotating field for free | 1 |
| Conductor saving | 25% | 18 |
| Two voltages from one supply | \(V_L\) and \(V_L/\sqrt3\) | 3 |
| Choice of connection | 3:1 power ratio available | 12 |
The costs:
| Cost | Detail |
|---|---|
| Three conductors minimum | Four for unbalanced distribution |
| Imbalance is destructive | Voltage errors above 10% — Problem 15 |
| Neutral is critical and vulnerable | Triplen harmonics, never fused — Problem 16 |
| Phase sequence must be right | Motors reverse; sources cannot parallel — Problem 2 |
| \(\sqrt3\) factors invite error | The commonest mistake in the subject |
What is not new. Balanced three-phase analysis introduced no new circuit theory whatever. Problem 13's per-phase equivalent reduces every balanced problem to the single-phase case, so all of Sets 20 to 23 applies unchanged:
Only the unbalanced cases needed genuinely different treatment, and even those used Millman's theorem from Set 14.
The measurement problem. Set 23, Problem 17 established that a wattmeter reads the average of \(vi\) for one pair of terminals. To measure three-phase power the obvious approach uses three wattmeters, one per phase — but this needs access to the neutral, which a three-wire system does not have:
| System | Wattmeters needed | Problem |
|---|---|---|
| Four-wire, unbalanced | 3 | Straightforward |
| Three-wire, balanced | 1 | Needs an artificial neutral |
| Three-wire, any load | 2 | Set 25 |
Why two suffice — the result Set 25 will prove. With no neutral, KCL forces
so one current is determined by the other two, and only two independent measurements are required. This is Blondel's theorem: an \(n\)-wire system needs \(n-1\) wattmeters. Problem 15's KCL check was the same constraint used for a different purpose.
The bonus that makes the method valuable. The two readings do not merely sum to the total power — their difference yields the reactive power and hence the power factor:
So two instruments give \(P\), \(Q\) and the power factor of a balanced load, with no phase-measuring equipment at all. One of them reads negative below 0.5 power factor, which is where the 30° shift of Problem 3 finally earns its keep.
Practice Problems
Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not. All values RMS.
P1. A 415 V star system — find the phase voltage.
Show answer
\(415/\sqrt3 = 239.6 \approx 240\) V — Problem 3.P2. A delta load draws 30 A per phase. Find the line current.
Show answer
\(I_L = \sqrt3(30) = 51.96\) A, lagging the phase current by 30° — Problem 4.P3. A balanced star load of \(15\ \Omega\) per phase on 400 V. Find \(I_L\).
Show answer
\(I_L = I_{ph} = 230.9/15 = 15.4\) A — Problem 9.P4. Convert a delta load of \((18+j24)\ \Omega\) per phase to its star equivalent.
Show answer
\(\mathbf{Z}_Y = (18+j24)/3 = 6+j8\ \Omega\) — Problem 19.P5. A three-phase load takes 20 A at 400 V, 0.85 lagging. Find \(P\) and \(S\).
Show answer
\(S = \sqrt3(400)(20) = 13.86\) kVA; \(P = 11.78\) kW — Problem 7.P6. A balanced four-wire system carries 25 A per phase. Find the neutral current.
Show answer
Zero — the three currents sum to zero by \(1+a+a^2 = 0\) — Problems 2 and 14.P7. The same impedance is reconnected from star to delta on the same supply. What happens to the power?
Show answer
It triples — Problem 12.P8. A star load of \((9+j12)\ \Omega\) per phase on 400 V. Find \(P\) using the closed form.
Show answer
\(P = V_L^2R/|\mathbf{Z}|^2 = 160\,000(9)/225 = 6400\) W — Problem 8.P9. Why does a broken neutral damage equipment?
Show answer
The star point floats, so lightly loaded phases see well above \(V_{ph}\) — Problems 15 and 16.P10. Which harmonics add in the neutral rather than cancelling?
Show answer
Triplen harmonics — the 3rd, 6th, 9th — because \(120h\) is a multiple of 360° — Problem 16.P11. How much copper does a three-wire three-phase line need relative to single-phase?
Show answer
75%, at equal power, voltage and loss — Problem 18.P12. How is a three-phase motor's direction reversed?
Show answer
Swap any two of the three supply conductors, reversing the phase sequence — Problem 2.
Challenge Problems
Each needs an idea rather than a formula. Decide what the governing principle is before opening the answer.
C1. A factory on a 415 V, 50 Hz supply runs induction motors totalling 75 kW at 0.82 lagging, 40 kW of resistive heating, and a welding plant of 25 kW at 0.65 lagging. Find the total complex power, the line current, and the delta capacitor bank needed to reach 0.95 lagging — then state what it achieves.
Show answer
Tabulate, adding \(P\) and \(Q\) separately as Set 23, Problem 10 requires:Load \(P\) (kW) pf \(\tan\phi\) \(Q\) (kvar) Induction motors 75 0.82 lag 0.6980 52.35 Resistive heating 40 1.00 0 0 Welding plant 25 0.65 lag 1.1691 29.23 Total 140 — — 81.58 \[ \mathbf{S} = 140 + j81.58\ \text{kVA}, \qquad S = 162.03\ \text{kVA} \]Line current from \(S = \sqrt3V_LI_L\):\[ \text{pf} = \frac{140}{162.03} = 0.864 \ \text{lagging} \]The capacitor bank. Target \(Q_2 = 140\tan18.19° = 46.02\) kvar:\[ I_L = \frac{162\,030}{\sqrt3(415)} = 225.4\ \text{A} \]For a delta bank each capacitor sees the full 415 V:\[ Q_C = 81.58 - 46.02 = 35.56\ \text{kvar} \]What it achieves:\[ C = \frac{Q_C}{3\omega V_L^2} = \frac{35\,560}{3(314.16)(415)^2} = 219.1\ \mu\text{F per phase} \]14.7 kVA of transformer capacity released and 17% of the distribution loss eliminated.Quantity Before After pf 0.864 0.950 \(S\) 162.03 kVA 147.37 kVA Line current 225.4 A 205.0 A Line loss 100% 82.7%
Two observations. The 40 kW of resistive heating contributes a full 40 kW to \(P\) and nothing to \(Q\), so it improves the overall power factor considerably — without it the pf would be 0.836. And the welding plant, at only 18% of the real power, contributes 36% of the reactive power: correcting at the welder itself would relieve the factory's internal wiring as well as the supply.C2. A balanced delta load of \(20\angle30°\ \Omega\) per phase runs on 400 V. One phase of the delta goes open-circuit. Find the three line currents and the power, and explain the pattern.
Show answer
The two surviving branches are unaffected in voltage. This is the key insight: in delta each branch is connected directly across a line pair, so losing one branch does not change the voltage across the others.with \(\mathbf{I}_{bc} = 0\).\[ \mathbf{I}_{ab} = \frac{400\angle0°}{20\angle30°} = 20\angle{-30°}\ \text{A}, \qquad \mathbf{I}_{ca} = \frac{400\angle120°}{20\angle30°} = 20\angle90°\ \text{A} \]
Line currents by KCL at each corner:\[ \mathbf{I}_a = \mathbf{I}_{ab} - \mathbf{I}_{ca} = 20\angle{-30°} - 20\angle90° = 34.64\angle{-60°}\ \text{A} \]The pattern. Line \(a\) — the one joining the two surviving branches — carries \(\sqrt3\) times what the others do:\[ \mathbf{I}_b = -\mathbf{I}_{ab} = 20\angle150°\ \text{A}, \qquad \mathbf{I}_c = \mathbf{I}_{ca} = 20\angle90°\ \text{A} \]Lines \(b\) and \(c\) each feed one branch only, so they carry the branch current directly. The three still sum to zero, as a three-wire system requires.\[ \frac{|\mathbf{I}_a|}{|\mathbf{I}_b|} = \frac{34.64}{20} = \sqrt3 \]
The power:\[ P_{\text{normal}} = \frac{3V_L^2R}{|\mathbf{Z}|^2} = \frac{3(400)^2(17.32)}{400} = 20\,785\ \text{W} \]Exactly two thirds — two branches instead of three, each unchanged.\[ P_{\text{open}} = \tfrac23 P_{\text{normal}} = 13\,856\ \text{W} \]
Why this matters practically. A blown fuse in one delta branch of a motor winding leaves it running at two-thirds power with one line carrying \(\sqrt3\) times the current of the others. The motor keeps turning, which is precisely the danger: the overload is invisible without measurement, and the unbalanced heating destroys the winding over weeks rather than seconds.
Contrast with a star load losing a phase. There the affected branch carries no current at all, and the remaining two are placed in series across a line voltage — each seeing \(V_L/2 = 200\) V instead of 231 V, so the power falls to exactly half — each branch runs at \((200/231)^2 = 75\%\) of its normal dissipation, and only two branches remain, giving \(\tfrac23 \times \tfrac34 = \tfrac12\). The delta failure is the more insidious of the two: it loses less power (two thirds rather than half) while overloading one line conductor by \(\sqrt3\), so the machine keeps working nearly normally while one supply cable cooks.C3. Three windings spaced 120° apart in space carry currents 120° apart in time. Show that the resulting magnetic field has constant magnitude and rotates at \(\omega\), and connect the result to Problem 1.
Show answer
Set up. Each winding produces a field along its own axis, varying sinusoidally in time. At a point at angle \(\theta\) around the stator, the contribution of a winding on axis \(\alpha\) carrying \(I\cos(\omega t - \alpha)\) is proportional to \(\cos(\omega t-\alpha)\cos(\theta-\alpha)\). Summing the three:Expand each product with \(\cos A\cos B = \tfrac12[\cos(A-B)+\cos(A+B)]\):\[ B(\theta,t) = B_m\sum_{\alpha=0,120°,240°}\cos\left(\omega t-\alpha\right)\cos\left(\theta-\alpha\right) \]The first term does not involve \(\alpha\), so it appears three times. The second has \(2\alpha\) taking the values \(0°, 240°, 480° \equiv 120°\) — three angles 120° apart, so those three terms sum to zero.\[ = \frac{B_m}{2}\sum_\alpha\left[\cos\left(\omega t-\theta\right) + \cos\left(\omega t+\theta-2\alpha\right)\right] \]Read the result. The magnitude \(\tfrac32B_m\) is constant in time, and the field's peak is wherever \(\theta = \omega t\) — so it travels once round the stator per electrical cycle. A numerical check confirms the peak sits at 0°, 90° and 180° when \(\omega t\) is 0°, 90° and 180°, with amplitude exactly 1.5 throughout.\[ \boxed{\;B(\theta,t) = \tfrac32 B_m\cos\left(\omega t - \theta\right)\;} \]
The connection to Problem 1. Both results come from the identical step: three quantities at \(120°\) spacing, doubled by a product formula to \(240°\) spacing, summing to zero.The physical unity. Constant power delivered to a machine and a constant-magnitude rotating field inside it are not two coincidences but one theorem seen from two sides — energy enters at a steady rate because the field that carries it neither grows nor shrinks, only turns. A single-phase machine has neither: its power pulsates and its field merely oscillates along one axis, which is why it produces no starting torque at all.Problem 1 This problem Product formed \(v \times i\) \(\text{current} \times \text{winding position}\) Term that cancels \(\cos(2\omega t - \cdots)\) \(\cos(\omega t+\theta-2\alpha)\) Term that survives \(\cos\phi\) — constant power \(\cos(\omega t-\theta)\) — rotating field
Multiple-Choice Questions
Twelve questions in GATE/ESE style. Commit to an answer before opening the explanation.
Q1. In a star connection,
(a) \(V_L = V_{ph}\) (b) \(V_L = \sqrt3V_{ph}\) (c) \(I_L = \sqrt3I_{ph}\) (d) \(V_L = 3V_{ph}\)
Show answer
(b), with the line voltage leading by 30°. Currents are equal — Problem 3.Q2. In a delta connection, the line current
(a) equals the phase current (b) leads it by 30° (c) lags it by 30° (d) is in phase
Show answer
(c), and is \(\sqrt3\) times larger — Problem 4.Q3. Total power in a balanced three-phase load is
(a) \(\sqrt3V_LI_L\cos\phi\) (b) \(3V_LI_L\cos\phi\) (c) \(V_LI_L\cos\phi\) (d) depends on the connection
Show answer
(a) — the same formula for star and delta — Problem 4.Q4. The instantaneous power drawn by a balanced three-phase load
(a) pulsates at \(2\omega\) (b) pulsates at \(\omega\) (c) is constant (d) is zero on average
Show answer
(c). The three \(2\omega\) terms are 120° apart and cancel — Problem 1.Q5. A delta load of \(\mathbf{Z}\) per phase is equivalent to a star of
(a) \(3\mathbf{Z}\) (b) \(\mathbf{Z}/3\) (c) \(\sqrt3\mathbf{Z}\) (d) \(\mathbf{Z}\)
Show answer
(b) — from the general product-over-sum with three equal arms — Problem 19.Q6. The same impedance reconnected from star to delta draws
(a) the same power (b) \(\sqrt3\times\) (c) \(3\times\) (d) \(1/3\times\)
Show answer
(c) — \(\sqrt3\) more voltage and \(\sqrt3\) more current per phase — Problem 12.Q7. The neutral current in a balanced four-wire system is
(a) \(3I_{ph}\) (b) \(\sqrt3I_{ph}\) (c) zero (d) \(I_{ph}\)
Show answer
(c), by \(1+a+a^2 = 0\) — Problems 2 and 14.Q8. Which harmonics add arithmetically in the neutral?
(a) all (b) even only (c) 5th and 7th (d) triplen (3rd, 6th, 9th)
Show answer
(d). \(120h\) is a multiple of 360° for these, so they are in phase — Problem 16.Q9. If the neutral of an unbalanced four-wire load breaks,
(a) nothing changes (b) all loads lose supply (c) the star point shifts and voltages become unequal (d) the currents become balanced but unchanged
Show answer
(c). The currents are forced to sum to zero, but the voltages go wrong instead — Problems 15 and 16.Q10. Delta-connected correction capacitors, compared with star for the same kvar, need
(a) three times the capacitance (b) one third (c) the same (d) \(\sqrt3\) times
Show answer
(b), but at \(\sqrt3\) times the voltage rating — Problem 17.Q11. A three-wire three-phase line uses what fraction of single-phase copper, at equal power and loss?
(a) 50% (b) 75% (c) 100% (d) 150%
Show answer
(b) — three conductors of half the area against two of full area — Problem 18.Q12. How many wattmeters are needed for a three-wire three-phase system of any load?
(a) 1 (b) 2 (c) 3 (d) 4
Show answer
(b), by Blondel's theorem: \(n-1\) for an \(n\)-wire system — Problem 20 and Set 25.
Key Formulas
All values RMS; balanced positive sequence unless noted.
| Quantity | Star (Y) | Delta (Δ) |
|---|---|---|
| Voltage | \(V_L = \sqrt3V_{ph}\), leading 30° | \(V_L = V_{ph}\) |
| Current | \(I_L = I_{ph}\) | \(I_L = \sqrt3I_{ph}\), lagging 30° |
| Total power | \(P = \sqrt3V_LI_L\cos\phi = 3V_{ph}I_{ph}\cos\phi = 3|\mathbf{I}_{ph}|^2R\) | |
| Closed form | \(P = V_L^2R/|\mathbf{Z}|^2\) | \(P = 3V_L^2R/|\mathbf{Z}|^2\) |
| Correction capacitor | \(C = Q_C/\omega V_L^2\) | \(C = Q_C/3\omega V_L^2\) |
| Result | Relation | Notes |
|---|---|---|
| Balance identity | \(1 + a + a^2 = 0\) | \(a = 1\angle120°\); underlies everything |
| Instantaneous power | \(p_{\text{total}} = 3V_{ph}I_{ph}\cos\phi\) | Constant — no \(2\omega\) term |
| Delta–star | \(\mathbf{Z}_Y = \mathbf{Z}_\Delta/3\) | Balanced loads only |
| Star–delta power | \(P_\Delta = 3P_Y\) | Same \(\mathbf{Z}\), same \(V_L\) |
| Reactive and apparent | \(Q = \sqrt3V_LI_L\sin\phi\), \(S = \sqrt3V_LI_L\) | \(S^2 = P^2+Q^2\) |
| Neutral current (4-wire) | \(\mathbf{I}_N = \mathbf{I}_a+\mathbf{I}_b+\mathbf{I}_c\) | Zero when balanced |
| Star-point shift (3-wire) | \(\mathbf{V}_N = \dfrac{\sum\mathbf{V}_k\mathbf{Y}_k}{\sum\mathbf{Y}_k}\) | Millman — Set 14 |
| Triplen harmonics | \(I_{N,3} = 3I_{ph,3}\) | In phase, so they add |
| Conductor saving | 75% of single-phase | Equal \(P\), \(V\), loss |
| Rotating field | \(B = \tfrac32B_m\cos(\omega t-\theta)\) | Constant magnitude, rotates at \(\omega\) |
| Per-phase method | Convert Δ→Y, use \(V_L/\sqrt3\), \(\times3\) at the end | Balanced systems only |
| Blondel's theorem | \(n-1\) wattmeters for \(n\) wires | Set 25 |
Common Mistakes
Applying \(\sqrt3\) to the wrong quantity. It goes with whatever needs Kirchhoff's law: voltages in star, currents in delta — Problems 3 and 4.
Using \(3V_LI_L\cos\phi\) instead of \(\sqrt3V_LI_L\cos\phi\). The \(\sqrt3\) form uses line quantities, the factor-3 form uses phase quantities — never mix them — Problem 7.
Taking \(\phi\) as the angle between \(V_L\) and \(I_L\). It is always the impedance angle, which differs by 30° — Problem 5.
Adding line impedance to a delta load directly. Convert to star first — Problem 13.
Using the delta resistance with the line current. After converting, use \(R_\Delta/3\) — Problem 13.
Assuming zero neutral current whenever the source is balanced. The load must be balanced too — Problem 14.
Computing branch current as \(P/\mathbf{V}\) with a phasor denominator. This conjugates the angle; use \(\mathbf{I} = (S/\mathbf{V})^{*}\) — Problem 14.
Applying the per-phase method to an unbalanced load. The neutrals are then at different potentials — Problems 13 and 15.
Sizing a neutral at half the phase conductor on a supply feeding electronic loads — triplen harmonics — Problem 16.
Reconnecting a star-rated load in delta. The phase voltage rises by \(\sqrt3\) and the dissipation triples — Problem 12.
Three-phase working delivers what Set 23 showed single-phase working could not: power that is constant at every instant rather than pulsating between zero and twice its average. The same trigonometric identity — three quantities 120° apart summing to zero — also gives a magnetic field of constant magnitude that rotates by itself, a neutral that carries nothing when the load is balanced, and a 25% saving in conductor material. Balanced analysis introduced no new circuit theory at all, because the per-phase equivalent reduces every such problem to the single-phase case of Sets 20 to 23.
What remains is measurement. A wattmeter reads the average of \(vi\) across one pair of terminals, so measuring three-phase power appears to need three of them — and a neutral connection that a three-wire system does not provide. But with no neutral, the three line currents are forced to sum to zero, so one of them is determined by the other two and only two independent measurements can exist.
Next: Set 25 — the Two-Wattmeter Method, where two instruments measure the power of any three-wire three-phase load, balanced or not. Their sum gives the real power; their difference gives the reactive power and hence the power factor — and below 0.5 power factor one of them reads negative, which is where the 30° shift derived in Problem 3 finally does visible work.