Set 23 — Single-Phase AC Power
Sets 20 to 22 moved the whole of Part 1 into the frequency domain and produced almost no new theory. That changes here. Multiply a voltage by a current when the two are out of phase and the product is positive for part of each cycle and negative for the rest — energy flows to the load and then back again. What survives the averaging is real power; what cancels is reactive power, which transports nothing yet occupies every conductor between the load and the generator. Separating the two, and understanding why utilities charge for one and penalise the other, is the subject of this set.
Sets 20 to 22 used amplitude phasors, where \(|\mathbf{V}| = V_m\). From this set onward, Part 3 uses RMS phasors, where \(|\mathbf{V}| = V_m/\sqrt2\). Set 22, Problem 19 flagged the change; this is it.
| Quantity | Amplitude phasors (Sets 20–22) | RMS phasors (Set 23 on) |
|---|---|---|
| Average power in \(R\) | \(\tfrac12|\mathbf{I}|^2R\) | \(|\mathbf{I}|^2R\) |
| Complex power | \(\tfrac12\mathbf{V}\mathbf{I}^{*}\) | \(\mathbf{V}\mathbf{I}^{*}\) |
| Maximum power | \(|\mathbf{V}_{Th}|^2/8R_{Th}\) | \(|\mathbf{V}_{Th}|^2/4R_{Th}\) |
Why change. Every factor of \(\tfrac12\) disappears, and AC power formulas become identical in form to DC ones — which is precisely what RMS was invented for (Set 20, Problem 10). It is also universal practice in power engineering: a "230 V supply" always means 230 V RMS.
What does not change. Impedances, phase angles, Kirchhoff's laws and every result of Sets 20 to 22 concerning ratios. Only the scaling of the phasors themselves, and hence the power formulas.
One exception is retained deliberately. Problem 14 works a maximum-power problem stated with an amplitude source, keeping the \(\tfrac12\) explicit, so the two conventions can be seen side by side.
Complex power, with RMS phasors and the conjugate on the current:
\[ \mathbf{S} = \mathbf{V}\mathbf{I}^{*} = P + jQ \]The three powers:
\[ P = VI\cos\theta \ \text{(W)}, \qquad Q = VI\sin\theta \ \text{(var)}, \qquad S = VI \ \text{(VA)} \]with \(\theta = \theta_v - \theta_i\) the impedance angle, and \(S^2 = P^2 + Q^2\).
Power factor:
\[ \text{pf} = \cos\theta = \frac{P}{S} \]Lagging for inductive loads (\(Q > 0\)), leading for capacitive (\(Q < 0\)).
Alternative forms, often quicker:
\[ \mathbf{S} = |\mathbf{I}|^2\mathbf{Z} = \frac{|\mathbf{V}|^2}{\mathbf{Z}^{*}} \]Complex power is conserved. \(P\) and \(Q\) each balance separately over any network — Problem 8.
Correction: a shunt capacitor supplies \(Q_C = Q_1 - Q_2\) without changing \(P\):
\[ C = \frac{P\left(\tan\theta_1 - \tan\theta_2\right)}{\omega V^2} \]
Derive the instantaneous power for \(v = V_m\cos(\omega t + \theta_v)\) and \(i = I_m\cos(\omega t + \theta_i)\). Examine the three cases \(\theta = 0°\), \(60°\) and \(90°\) with \(V_m = 100\ \text{V}\), \(I_m = 5\ \text{A}\), and explain what happens when the power is negative.
The product, using \(\cos A\cos B = \tfrac12\left[\cos(A-B) + \cos(A+B)\right]\):
Two terms: a constant, and one at twice the supply frequency. The second averages to zero over any whole number of cycles, so
The three cases, with \(\tfrac12V_mI_m = 250\ \text{W}\):
| \(\theta\) | Load | \(P\) | \(p(t)\) range | Ever negative? |
|---|---|---|---|---|
| 0° | Resistive | 250 W | 0 to 500 W | No |
| 60° | Mixed | 125 W | −125 to 375 W | Yes |
| 90° | Purely reactive | 0 W | −250 to 250 W | Yes, half the time |
The resistive case is \(p = 250(1+\cos2\omega t)\) — always non-negative, touching zero twice per cycle, and pulsating at 100 Hz on a 50 Hz supply. Energy flows one way only.
This is why incandescent lamps and transformer cores hum at twice the supply frequency: the power, not the voltage, drives the mechanical excitation.
The purely reactive case is the striking one:
The average is exactly zero, yet the instantaneous power reaches \(\pm250\ \text{W}\). Energy flows into the element for a quarter cycle, then back out for the next quarter, indefinitely. Nothing is consumed — but a real current of 5 A amplitude flows in the conductors the whole time.
What negative power means. The load is returning energy to the source. A capacitor discharging or an inductor collapsing its field pushes current back against the supply voltage. Over a cycle the returns exactly cancel the deliveries for a pure reactance, and partly cancel them for a mixed load.
The quantity that has appeared is the amplitude of the circulating flow. Separating the \(2\omega\) term into components in phase and in quadrature with the constant part gives
where \(t'\) is measured from a convenient origin. \(P\) rides on a pulsation that never goes negative; \(Q\) is a pure oscillation with zero mean. Problem 2 names them.
Define complex, real, reactive and apparent power, show they form a right triangle similar to the impedance triangle, and set out the units and their purpose.
Complex power packages both quantities into one number:
The conjugate on the current is essential: it makes the angle the \(v\!-\!i\) difference, which is the impedance angle. Without it the angle would be \(\theta_v+\theta_i\), which depends on the arbitrary time origin and is therefore meaningless.
Its rectangular parts:
| Quantity | Symbol | Unit | Meaning |
|---|---|---|---|
| Real (active, average) | \(P\) | watt (W) | Net energy transferred — what is consumed and billed |
| Reactive | \(Q\) | var | Amplitude of circulating flow — nothing consumed |
| Apparent | \(S = |\mathbf{S}|\) | volt-ampere (VA) | What conductors and machines must be rated for |
| Complex | \(\mathbf{S}\) | VA | Both together |
Three different units for quantities all dimensionally equal to power. The distinction is deliberate: it makes clear from the unit alone which quantity is meant.
The power triangle. Since \(P\) and \(Q\) are the legs and \(S\) the hypotenuse:
Why it is similar to the impedance triangle. Writing \(\mathbf{S} = |\mathbf{I}|^2\mathbf{Z}\):
The power triangle is the impedance triangle scaled by \(|\mathbf{I}|^2\) — same angle, same shape. Set 20, Problem 14's voltage triangle is a third member of the family, scaled by \(|\mathbf{I}|\).
The three triangles together:
| Triangle | Sides | Scale factor |
|---|---|---|
| Impedance | \(R\), \(X\), \(|\mathbf{Z}|\) | 1 |
| Voltage | \(V_R\), \(V_X\), \(V\) | \(|\mathbf{I}|\) |
| Power | \(P\), \(Q\), \(S\) | \(|\mathbf{I}|^2\) |
All three share the angle \(\theta\), so knowing any one gives the others immediately.
A caution on "power factor". It is \(\cos\theta\), which is positive for any \(|\theta| < 90°\) and therefore cannot distinguish inductive from capacitive. The words lagging and leading must always be attached — they carry the sign of \(Q\), which \(\cos\theta\) throws away.
A load has \(v(t) = 60\cos(\omega t - 10°)\ \text{V}\) and \(i(t) = 1.5\cos(\omega t + 50°)\ \text{A}\) in the direction of the voltage drop. Find the complex, apparent, real and reactive powers, the power factor and the load impedance.
Convert amplitudes to RMS phasors, following this set's convention:
1Complex and apparent power:
The two \(\sqrt2\) factors combine into the familiar \(\tfrac12\) — which is exactly what the RMS convention absorbs, so it need never be written again.
2Real and reactive powers from the rectangular form:
Negative \(Q\) means capacitive. Note that \(|Q| > P\) here — most of the volt-amperes are doing no work at all.
3Power factor and impedance:
The \(\sqrt2\) factors cancel in the ratio, so impedance is the same whichever convention is used — the point made in the convention block.
Cross-check by the alternative formula:
What a pf of 0.5 costs. The load consumes 22.5 W but the supply must deliver 45 VA — twice the current a resistive load of the same wattage would need, and hence four times the \(I^2R\) loss in the cables feeding it.
A 30 V rms source drives 6 Ω in series with the parallel combination of 4 Ω and \(-j2\ \Omega\). Find the power factor seen by the source and the average power delivered.
Reduce to a single impedance:
The power factor is the cosine of the impedance angle:
Leading, because the net reactance is capacitive. The sign of the angle is the only thing distinguishing this from a lagging 0.9734.
The source current:
The average power, computed two ways.
aFrom the definition:
bFrom the resistance, since only resistance dissipates:
The second route is usually faster and is immune to power-factor sign errors — it uses only the real part of the impedance, which cannot be mistaken for anything else.
Where the power goes. The 6.8 Ω is not a physical resistor — it is 6 Ω plus the 0.8 Ω contributed by the parallel pair. Splitting it:
The capacitor dissipates nothing, as it must — it contributes only to \(Q\).
The reactive power:
Confirming the capacitive character, and giving \(S = \sqrt{125.4^2 + 29.5^2} = 128.8\ \text{VA}\).
A load draws 12 kVA at 0.856 lagging from a 120 V rms supply. Find the real and reactive powers, the peak current, and the load impedance.
Recover the angle from the power factor, taking it positive because the load is lagging:
"Lagging" is what fixes the sign — \(\cos^{-1}\) alone gives no information about it.
1Real and reactive powers:
Check: \(\sqrt{10.272^2 + 6.204^2} = 12.00\) kVA ✓.
2The current, from the definition of complex power:
Note the conjugation at the end — forgetting it reverses the phase and turns a lagging load into a leading one.
The peak current:
This is what matters for saturation, semiconductor ratings and insulation stress; the RMS value is what matters for heating.
3The load impedance:
Cross-check: \(P = |\mathbf{I}|^2R = (100)^2(1.027) = 10.27\) kW ✓, and \(Q = (100)^2(0.620) = 6.20\) kvar ✓.
A shortcut worth knowing:
obtained by combining \(\mathbf{S} = \mathbf{V}\mathbf{I}^{*}\) with \(\mathbf{V} = \mathbf{Z}\mathbf{I}\). It skips the current entirely.
A series load carries \(i(t) = 4\cos(100\pi t + 10°)\ \text{A}\) under \(v(t) = 120\cos(100\pi t - 20°)\ \text{V}\). Find the apparent power and power factor, and determine the two element values.
1Apparent power is the product of the RMS values:
Power factor from the phase difference:
Leading, because the current's phase exceeds the voltage's — the current reaches its peak first.
2The impedance fixes the elements:
Negative reactance confirms a capacitor, consistent with the leading power factor.
The resistance is read directly:
The capacitance, from \(X_C = 1/\omega C\) with \(\omega = 100\pi = 314.16\ \text{rad/s}\), i.e. 50 Hz:
Cross-check the powers:
Matching the direct calculation, and confirming \(\text{pf} = 207.8/240 = 0.866\).
Note the ambiguity this resolves. A power factor of 0.866 alone is consistent with \(\pm30°\) and therefore with either a capacitive or inductive load — and hence with a capacitor of 212 µF or an inductor of \(15/(100\pi) = 47.7\ \text{mH}\). Only the waveforms, or the word "leading", settles which.
Reactive power transports no energy. Show what it actually measures by relating \(Q\) to the energy stored in an inductor, and explain why it nonetheless has real costs.
Take a pure inductor carrying \(I_{rms}\) at frequency \(\omega\). Its reactive power is
Its average stored energy. The instantaneous energy is \(w = \tfrac12Li^2\), and averaging \(i^2\) over a cycle gives \(I_{rms}^2\) by definition:
Compare the two:
Reactive power is the average stored energy, multiplied by \(2\omega\). The factor of two appears because the energy completes two full store-and-return cycles per period of the supply — as Problem 1's \(2\omega\) term showed.
A numerical instance. With \(L = 0.1\ \text{H}\), \(I_{rms} = 5\ \text{A}\) at 50 Hz:
| Quantity | Value |
|---|---|
| \(Q = I^2\omega L\) | 785.4 var |
| \(\overline{w} = \tfrac12LI^2\) | 1.25 J |
| \(2\omega\overline{w}\) | 785.4 var ✓ |
For a capacitor the sign reverses, because it stores in the electric field while the current leads:
Which is why an inductor and a capacitor can exchange reactive power directly, each supplying what the other absorbs — the principle behind every correction capacitor.
Why it costs money despite consuming nothing. The reactive current is a real current in real conductors:
| Cost | Reason |
|---|---|
| \(I^2R\) losses in cables | Loss depends on total current, not on phase |
| Transformer and generator rating | Sized in kVA, which includes \(Q\) |
| Voltage drop along lines | \(Q\) flowing through line reactance drops voltage — Problem 8 |
| Reduced usable capacity | Every reactive ampere displaces a real one |
The energy is not lost in the reactive element — but transporting it back and forth wastes energy in everything between.
A load takes 20 kW at 0.8 lagging with \(220\angle0°\ \text{V}\) rms across it, fed through a line of impedance \(0.09 + j0.3\ \Omega\). Find the voltage and power factor at the sending end, by two independent methods.
The load's complex power:
The load current:
The same current flows in the line, since load and line are in series.
aMethod 1 — power balance. The line absorbs
Complex power is conserved, so the source must supply the sum:
bMethod 2 — KVL. The line drop is
Note what conservation does and does not say. Real and reactive powers each balance independently:
| Load | Line | Source | |
|---|---|---|---|
| \(P\) (kW) | 20.00 | 1.16 | 21.16 |
| \(Q\) (kvar) | 15.00 | 3.87 | 18.87 |
| \(S\) (kVA) | 25.00 | 4.04 | 28.36 — not 29.04 |
Apparent power does not add. \(P\) and \(Q\) are conserved; \(S = |P+jQ|\) is a magnitude and obeys no conservation law. Adding kVA figures is one of the commonest errors in power calculations.
The engineering reading. A 13% voltage rise is needed at the sending end to hold 220 V at the load — and note that most of the drop comes from \(Q\) flowing through the line's reactance, not from \(P\) through its resistance. Correcting the power factor would reduce the current, the loss and the voltage drop together.
Three loads share a 240 V rms, 50 Hz supply: \(\mathbf{Z}_1 = 80-j50\ \Omega\), \(\mathbf{Z}_2 = 120+j70\ \Omega\), \(\mathbf{Z}_3 = 60\ \Omega\). Find the total complex power and the input power factor.
Branch currents, all driven by the same voltage:
Total current by KCL:
Note that \(\mathbf{I}_1\) is capacitive (positive imaginary) and \(\mathbf{I}_2\) inductive, so they largely cancel — leaving a small net capacitive component.
The total complex power:
The input power factor:
Leading because \(Q < 0\) overall — the capacitive branch slightly outweighs the inductive one.
Cross-check branch by branch, using \(\mathbf{S}_k = |\mathbf{V}|^2/\mathbf{Z}_k^{*}\):
| Branch | \(P\) (W) | \(Q\) (var) |
|---|---|---|
| \(\mathbf{Z}_1 = 80-j50\) | 517.8 | −323.6 |
| \(\mathbf{Z}_2 = 120+j70\) | 358.1 | +208.9 |
| \(\mathbf{Z}_3 = 60\) | 960.0 | 0 |
| Total | 1835.7 | −114.6 |
Agreeing with the current-based calculation. Adding complex powers is usually the faster route for parallel loads, since each branch is independent.
The practical point. The near-unity power factor here is accidental — the capacitive load happens to cancel the inductive one. In a real installation dominated by motors the result would be strongly lagging, and deliberate correction would be needed.
\(\mathbf{Z}_1 = 60\angle{-30°}\ \Omega\) and \(\mathbf{Z}_2 = 40\angle45°\ \Omega\) are in parallel across \(120\angle10°\ \text{V}\) rms. Find the total apparent, real and reactive powers and the power factor, by two routes.
aRoute 1 — complex power per branch, using \(\mathbf{S} = |\mathbf{V}|^2/\mathbf{Z}^{*}\):
Note the conjugate in the denominator flips each angle's sign, so \(\mathbf{S}\) ends up with the same angle as \(\mathbf{Z}\) — as it must, since both share the impedance angle.
Add:
bRoute 2 — via the total current. The branch currents are
Identical, and note \(481.6\angle16.22° = 462.4 + j134.6\) exactly.
Observe the individual magnitudes:
but the total is only 481.6 VA. Apparent powers do not add, because the branches have different phase angles — the same point as Problem 8's table, seen here as a 20% discrepancy.
Which route to prefer. Route 1 avoids computing currents at all and is immediate for any number of parallel branches. Route 2 gives the supply current, which is needed for cable sizing and for the \(I^2R\) losses upstream. Doing both, as here, is a free check.
A load absorbs 4 kW at 0.8 lagging from a 230 V rms, 50 Hz supply. Find the shunt capacitance needed to raise the overall power factor to 0.95 lagging, and the reduction in supply current.
The key observation: a shunt capacitor changes \(Q\) but not \(P\). It dissipates nothing, and it does not alter the load's own operation — the load still sees 230 V and draws exactly what it did.
Reactive power before and after, from \(Q = P\tan\theta\):
The capacitor supplies the difference:
"Supplies" is the right word: a capacitor's \(Q\) is negative, so adding it to the load's positive \(Q\) reduces the total. The inductive load absorbs reactive power; the capacitor provides it locally instead of the generator providing it down the line.
The capacitance, from \(Q_C = V^2/X_C = \omega CV^2\):
The general formula, worth having directly:
The current reduction. The same real power is now drawn at a better power factor:
A 16% reduction — and since cable losses go as \(I^2\), they fall by 29%.
Why stop at 0.95 rather than correcting to unity? Three reasons:
| Reason | Detail |
|---|---|
| Diminishing returns | 0.8→0.95 needs 1685 var; 0.95→1.0 needs another 1315 var for far less gain |
| Tariff threshold | Utilities typically penalise below 0.9 or 0.95 and pay nothing above |
| Risk of overcorrection | If the load falls, a fixed capacitor makes the pf leading, which is equally penalised and can cause overvoltage |
A factory draws 500 kW at 0.70 lagging. Quantify what correcting to 0.95 achieves — in apparent power, reactive power, line losses and released capacity — and state where the capacitor must be placed.
The three operating points, with \(P\) fixed at 500 kW:
| pf | \(S = P/\text{pf}\) | \(Q = P\tan\theta\) | Relative current |
|---|---|---|---|
| 0.70 | 714.3 kVA | 510.1 kvar | 1.000 |
| 0.85 | 588.2 kVA | 309.9 kvar | 0.824 |
| 0.95 | 526.3 kVA | 164.3 kvar | 0.737 |
The real power never changes — the factory does the same work. Everything in the table is about what the supply system must carry to deliver it.
1Apparent power released:
A transformer sized at 715 kVA now has 188 kVA spare — enough to add roughly 180 kW of further corrected load without replacing it. That deferred capital cost is usually the largest single benefit.
2The capacitor bank required:
3Line losses. Loss goes as \(I^2\), and current goes as \(1/\text{pf}\) at fixed \(P\):
Losses fall to 54% of their previous value — a 46% saving on every watt wasted in cables and transformer windings between the correction point and the supply.
4Where the capacitor goes. This is the part most often got wrong:
| Placement | Relieves | Verdict |
|---|---|---|
| At each motor | Everything upstream, including internal wiring | Best technically; costly |
| At the main switchboard | Transformer and incoming supply | Usual compromise |
| At the supply side of the meter | Nothing the customer owns | Pointless |
A capacitor relieves only the conductors between itself and the generator. Everything downstream still carries the full reactive current.
The tariff mechanism. Utilities recover the cost in one of three ways — a maximum-demand charge in kVA rather than kW, an explicit kvarh charge, or a power-factor penalty multiplier. All three make the same point: the customer's \(Q\) occupies capacity that could have carried someone else's \(P\).
A source has \(\mathbf{V}_{Th} = 20\angle0°\ \text{V rms}\) and \(\mathbf{Z}_{Th} = 5+j6\ \Omega\). Find the load for maximum average power and the power delivered, and compare with the amplitude-convention result of Set 22.
The conjugate match, derived in Set 22, Problem 14 and unaffected by the convention change:
The reactances cancel:
Purely resistive, so the current is in phase with the Thévenin voltage — the matched circuit is at resonance.
The maximum power, with no factor of \(\tfrac12\) because the phasors are RMS:
Compare with Set 22, Problem 19, where the same numbers were used with the amplitude convention:
| If \(20\ \text{V}\) means... | Peak | RMS |
|---|---|---|
| Actual RMS voltage | 14.14 V | 20 V |
| Formula | \(400/8(5)\) | \(400/4(5)\) |
| \(P_{\max}\) | 10 W | 20 W |
Both correct under their own convention. A 20 V RMS source genuinely delivers twice the power of a 20 V peak source, because its RMS value is \(\sqrt2\) times larger and power goes as the square.
The complete power picture at the match:
| Element | \(P\) | \(Q\) |
|---|---|---|
| Load \(5-j6\) | 20 W | −24 var |
| Source impedance \(5+j6\) | 20 W | +24 var |
| Total from source | 40 W | 0 |
The reactive powers cancel exactly, so the source supplies pure real power at unity power factor — while 24 var circulates internally between the two reactances. Efficiency is 50%, as always at maximum power transfer.
A \(150\angle30°\ \text{V}\) amplitude source drives a network in which \(40-j30\ \Omega\) is in parallel with \(j20\ \Omega\), with a resistive load \(R_L\) at the terminals. Find \(R_L\) for maximum power and the power delivered.
Note the convention. This problem is stated with an amplitude source, so the factor \(\tfrac12\) must be retained throughout — a deliberate exception, kept so both conventions appear in one set.
The Thévenin impedance:
The Thévenin voltage, by division onto the \(j20\):
The load is restricted to a resistor, so Set 22, Problem 16's result applies rather than the conjugate match:
Not \(R_{Th} = 9.41\ \Omega\). Because the reactance cannot be cancelled, the optimum resistance is the impedance magnitude.
The load current and power:
Compare with the unrestricted case. Had a complex load been permitted:
So the restriction costs 44% of the available power — much more than Set 22, Problem 16's 22%, because here \(|X_{Th}|\) is more than twice \(R_{Th}\). The more reactive the source, the more a resistive-only load loses.
Several expressions give complex power. Set out when each is quickest, and identify the traps attaching to each.
The four forms, all equivalent with RMS phasors:
| Form | Use when you know | Trap |
|---|---|---|
| \(\mathbf{S} = \mathbf{V}\mathbf{I}^{*}\) | Both \(\mathbf{V}\) and \(\mathbf{I}\) | Conjugate the current, not the voltage |
| \(\mathbf{S} = |\mathbf{I}|^2\mathbf{Z}\) | The current and impedance | No conjugate on \(\mathbf{Z}\) |
| \(\mathbf{S} = |\mathbf{V}|^2/\mathbf{Z}^{*}\) | The voltage and impedance | Conjugate is needed here |
| \(\mathbf{S} = |\mathbf{V}|^2\mathbf{Y}^{*}\) | Voltage and admittance | Same conjugate |
Why the conjugates sit where they do. Start from \(\mathbf{S} = \mathbf{V}\mathbf{I}^{*}\) and substitute:
The conjugate follows the substituted quantity. The reliable check is that \(\mathbf{S}\) must end up with the same angle as \(\mathbf{Z}\) — if it comes out with the opposite sign, a conjugate is misplaced.
Choosing in practice:
| Situation | Best form | Seen in |
|---|---|---|
| Series elements — common current | \(|\mathbf{I}|^2\mathbf{Z}\) | Problems 4, 8 |
| Parallel loads — common voltage | \(|\mathbf{V}|^2/\mathbf{Z}^{*}\) | Problems 9, 10 |
| Waveforms given | \(\mathbf{V}\mathbf{I}^{*}\) | Problem 3 |
| Rated load (kVA and pf given) | \(P = S\cos\theta\), \(Q = S\sin\theta\) | Problems 5, 11 |
For real power alone, the safest expression of all is
It has no conjugate, no angle, no power factor and no sign convention — only the real part of the impedance the current flows through. Whenever the current is available, this should be the default.
A worked comparison. Problem 3's load, three ways:
Fix the sign conventions for reactive power and power factor completely, and explain why "power factor 0.8" is an incomplete specification.
The convention follows from \(\mathbf{S} = |\mathbf{I}|^2\mathbf{Z}\), so \(Q\) takes the sign of the reactance:
| Load | \(X\) | \(Q\) | \(\theta\) | Current | pf |
|---|---|---|---|---|---|
| Inductive | \(+\) | absorbs, \(Q>0\) | \(0<\theta<90°\) | Lags | Lagging |
| Resistive | 0 | 0 | 0 | In phase | Unity |
| Capacitive | \(-\) | supplies, \(Q<0\) | \(-90°<\theta<0\) | Leads | Leading |
"Absorbs" and "supplies" are the useful words. An inductor takes reactive power from the system; a capacitor gives it back. They can therefore trade directly, which is the whole basis of correction (Problem 11).
Why "pf = 0.8" is incomplete. The power factor is a cosine, and
so it cannot distinguish the two cases. Two loads at 0.8 pf with the same \(P\) differ entirely:
| Description | \(Q\) for \(P = 4\ \text{kW}\) | Correction needs |
|---|---|---|
| 0.8 lagging | +3.0 kvar | A capacitor |
| 0.8 leading | −3.0 kvar | An inductor |
Applying a capacitor to a leading load makes matters worse, not better — the specification must always carry the word.
How to determine it in practice. Three equivalent tests:
| Test | Lagging if... |
|---|---|
| Sign of \(\operatorname{Im}(\mathbf{Z})\) | Positive |
| Sign of \(\operatorname{Im}(\mathbf{S})\) | Positive |
| Phase of \(\mathbf{I}\) relative to \(\mathbf{V}\) | Current phase is smaller |
All three test the same thing, and the first is usually available with least work.
A note on the sign of \(\mathbf{Y}\). Susceptance reverses relative to reactance — an inductor has \(X > 0\) but \(B < 0\) (Set 20, Problem 11). Since \(\mathbf{S} = |\mathbf{V}|^2\mathbf{Y}^{*}\), the conjugate restores the expected sign:
Explain what an electrodynamometer wattmeter measures, why it reads \(P\) and not \(S\), and what happens if the current coil is reversed.
The construction. A wattmeter has two coils:
| Coil | Connection | Carries |
|---|---|---|
| Current coil | In series with the load | The load current \(i(t)\) |
| Voltage (pressure) coil | In parallel with the load | A current proportional to \(v(t)\) |
Why it reads \(P\). The deflecting torque is proportional to the product of the two coil currents:
The pointer's inertia cannot follow the \(2\omega\) component of Problem 1, so it settles at the average:
The instrument performs the multiplication and the time-averaging mechanically — which is why it reads watts and not volt-amperes, and why it does so correctly for any waveform.
Contrast with separate meters. A voltmeter and ammeter give \(V_{rms}\) and \(I_{rms}\), whose product is \(S\), not \(P\):
The two agree only at unity power factor. Three instruments — voltmeter, ammeter and wattmeter — determine \(P\), \(S\) and hence \(\text{pf} = P/S\) and \(|Q| = \sqrt{S^2-P^2}\). What they cannot give is the sign of \(Q\).
Reversing the current coil reverses the torque, so the reading becomes \(-P\) and the pointer drives backwards against its stop. Both coils have a marked \(\pm\) terminal for this reason; connecting them consistently gives a positive reading for power absorbed by the load.
A wattmeter can legitimately read negative — when the element it measures is supplying power. Set 25's two-wattmeter method depends on this, where one meter routinely reads negative at low power factors.
When can a wattmeter read zero with current flowing? When \(\theta = 90°\) — a purely reactive load. The needle sits at zero while the current coil carries full current and may overheat, which is why a wattmeter's current and voltage ratings must be respected independently of its watts range.
A load has \(v = 100\cos\omega t + 40\cos(3\omega t + 30°)\ \text{V}\) and \(i = 8\cos(\omega t - 30°) + 3\cos(3\omega t - 20°)\ \text{A}\). Find the real power, the RMS values, the apparent power and the power factor — and explain why the last is not the cosine of any angle.
Cross terms vanish. The average of a product of sinusoids at different frequencies is zero:
This orthogonality — noted in Set 20, Problem 18 — means each harmonic contributes power independently.
Power harmonic by harmonic:
Note the third-harmonic angle is \(30° - (-20°) = 50°\), its own phase difference — unrelated to the fundamental's.
RMS values, where mean squares add:
Apparent power and power factor:
Why this is not \(\cos\theta\) for any \(\theta\). There is no single phase difference — the fundamental is displaced by 30° and the harmonic by 50°. The power factor splits into two factors:
approximately reproducing 0.837 — the small difference is the harmonic's own real-power contribution, which the two-factor form neglects. When the harmonic carries no power the identity is exact.
The engineering significance. Distortion degrades power factor even when every harmonic is perfectly in phase:
| Cause | Cured by |
|---|---|
| Displacement (phase lag) | Capacitors — Problem 11 |
| Distortion (harmonics) | Filters or better rectifiers — capacitors do not help |
Worse, a correction capacitor presents a low impedance to harmonics and may resonate with the supply inductance, amplifying them. This is why modern installations full of switched-mode power supplies need harmonic filters, not merely capacitor banks.
Two sources at the same frequency each drive a 10 Ω resistor: acting alone they produce \(60\angle0°\) and \(40\angle60°\ \text{V}\) rms across it. Show that the powers do not add, identify the cross term, and state when superposition of power is valid.
Individual powers:
The actual power. Superpose the voltages first, as Set 22, Problem 12 requires:
Not 520 W. The discrepancy is 240 W — 46% of the naive answer.
Identify the cross term. Expanding \(|\mathbf{V}_A + \mathbf{V}_B|^2\):
When the cross term vanishes. It is proportional to \(\cos(\theta_A - \theta_B)\), so:
| Condition | Cross term | Power superposes? |
|---|---|---|
| Different frequencies | Averages to zero | Yes — Problem 18 |
| Same frequency, 90° apart | \(\cos90° = 0\) | Yes, coincidentally |
| Same frequency, any other angle | Non-zero | No |
Set 22, Problem 12's contributions happened to be 90° apart, which is why its powers appeared to add. That was a coincidence of that circuit, not a rule.
The extreme cases are worth noting. With \(\theta_A = \theta_B\) the voltages add fully:
and with them 180° apart:
— far less than either source alone would give. So the error can go in either direction, and can be arbitrarily large.
Draw together what this set has established about the consequences of phase, and set out what remains before three-phase systems can be treated.
What phase does. In DC there is one power. In AC there are three quantities where one would do, and the angle decides how the volt-amperes divide:
At \(\theta = 0\) the split is entirely into \(P\); at \(90°\) entirely into \(Q\) and nothing is delivered at all.
The consequences established:
| Result | Problem |
|---|---|
| Instantaneous power goes negative when \(\theta \ne 0\) | 1 |
| \(Q = 2\omega \times\) average stored energy | 7 |
| \(P\) and \(Q\) are conserved; \(S\) is not | 8, 10 |
| \(Q\) can be supplied locally — correction works | 11, 12 |
| Power never superposes | 19 |
| Harmonics degrade pf in a way capacitors cannot fix | 18 |
The one irreducible cost. Even at unity power factor, single-phase power pulsates:
from 0 to \(2P\), twice per cycle. No amount of correction removes this — it is inherent in multiplying two sinusoids at the same frequency. A single-phase motor therefore receives pulsating torque, vibrates at \(2\omega\), and cannot start unaided.
What three phases achieve. Take three loads of equal power fed by voltages 120° apart. Their instantaneous powers are
and the three cosines are themselves 120° apart in \(2\omega t\), so they sum to zero:
The pulsation cancels exactly. That is the fundamental reason three-phase power exists, and it is why essentially all generation and transmission uses it.
What Sets 24 and 25 must supply:
| Topic | Why needed |
|---|---|
| Balanced three-phase sources | Three voltages 120° apart |
| Star and delta connections | Line versus phase quantities |
| Per-phase analysis | Reduces a three-phase problem to a single-phase one |
| Two-wattmeter method | Measuring \(P\) and pf with only two instruments |
All of it rests on this set: \(P\), \(Q\), \(S\) and the power factor mean exactly the same things per phase.
Practice Problems
Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not. All phasors are RMS.
P1. A load takes 1.5 kW at 0.6 lagging. Find \(S\) and \(Q\).
Show answer
\(S = 1500/0.6 = 2500\) VA; \(Q = 1500\tan53.13° = 2000\) var — Problem 5.P2. An inductor of reactance \(j8\ \Omega\) carries 10 A rms. Find \(Q\).
Show answer
\(Q = |\mathbf{I}|^2X = 100 \times 8 = 800\) var, absorbed — Problem 16.P3. Find the power factor of a load with \(\mathbf{Z} = 3+j4\ \Omega\).
Show answer
\(\text{pf} = R/|\mathbf{Z}| = 3/5 = 0.6\) lagging — Problem 2.P4. With \(\mathbf{V} = 100\angle0°\) and \(\mathbf{I} = 5\angle{-25°}\), find \(\mathbf{S}\).
Show answer
\(\mathbf{S} = \mathbf{V}\mathbf{I}^{*} = 500\angle25° = 453.2 + j211.3\) VA — Problem 3.P5. A 2 kW load at 0.75 lagging on 240 V, 50 Hz is corrected to 0.9. Find \(C\).
Show answer
\(Q_C = 2000(0.8819-0.4843) = 795\) var, so \(C = 43.9\ \mu\text{F}\) — Problem 11.P6. Find the real power in a 4 Ω resistor carrying 6 A rms.
Show answer
\(P = |\mathbf{I}|^2R = 144\) W — no angle needed — Problem 15.P7. Two loads take \(300+j400\) and \(500-j200\ \text{VA}\). Find the total \(S\).
Show answer
\(\mathbf{S} = 800+j200\), so \(S = 824.6\) VA — not \(500+538 = 1038\) — Problem 10.P8. With \(\mathbf{V}_{Th} = 50\ \text{V rms}\) and \(R_{Th} = 8\ \Omega\) at the conjugate match, find \(P_{\max}\).
Show answer
\(P_{\max} = 50^2/(4\times8) = 78.1\) W — Problem 13.P9. A waveform has harmonic amplitudes 100, 50 and 20 V. Find its RMS value.
Show answer
\(\sqrt{100^2+50^2+20^2}/\sqrt2 = 80.3\) V — mean squares add — Problem 18.P10. A meter shows 1000 VA and a wattmeter 800 W. Find the power factor and \(|Q|\).
Show answer
\(\text{pf} = 0.8\); \(|Q| = \sqrt{1000^2-800^2} = 600\) var — but the sign is unknown — Problem 17.P11. A reactive element stores 0.5 J on average at 50 Hz. Find \(|Q|\).
Show answer
\(|Q| = 2\omega\overline{w} = 2(314.16)(0.5) = 314\) var — Problem 7.P12. When may the powers from two same-frequency sources be added?
Show answer
Only if their contributions are 90° apart, so the cross term vanishes. Otherwise superpose phasors first — Problem 19.
Challenge Problems
Each needs an idea rather than a formula. Decide what the governing principle is before opening the answer.
C1. A factory on a 415 V rms, 50 Hz supply runs three loads: 50 kW at 0.85 lagging, 30 kW at 0.70 lagging, and 20 kW of resistive heating. Find the total complex power, the supply current, and the capacitance needed to correct to 0.95 lagging — then quantify what the correction achieves.
Show answer
Build the table. Real powers add directly; reactive powers from \(Q = P\tan\theta\):Load \(P\) (kW) pf \(\tan\theta\) \(Q\) (kvar) Motors A 50 0.85 lag 0.6197 30.99 Motors B 30 0.70 lag 1.0202 30.61 Heating 20 1.00 0 0 Total 100 — — 61.59 \[ \mathbf{S} = 100 + j61.59\ \text{kVA}, \qquad S = 117.45\ \text{kVA} \]Supply current:\[ \text{pf} = \frac{100}{117.45} = 0.851 \ \text{lagging} \]The capacitor bank. Target \(Q_2 = 100\tan18.19° = 32.87\) kvar, so\[ I = \frac{S}{V} = \frac{117\,450}{415} = 283.0\ \text{A} \]\[ Q_C = 61.59 - 32.87 = 28.72\ \text{kvar} \]What it achieves:\[ C = \frac{Q_C}{\omega V^2} = \frac{28\,720}{(314.16)(415)^2} = 530.9\ \mu\text{F} \]12.2 kVA of transformer capacity released and a fifth of the distribution losses eliminated, from a passive component that consumes nothing.Quantity Before After pf 0.851 0.950 \(S\) 117.45 kVA 105.26 kVA Current 283.0 A 253.7 A Line loss 100% 80.3%
Two practical notes. First, the 20 kW of heating contributes nothing to \(Q\) but a full 20 kW to \(P\), which improves the overall pf — resistive load is always welcome. Second, a fixed 531 µF bank will overcorrect when the motors are lightly loaded, so a switched bank in stages is normal practice.C2. A source of 240 V rms behind \(R_s = 5\ \Omega\) and \(L_s = 20\ \text{mH}\) feeds a fixed 10 Ω resistive load. Determine how the delivered power varies with frequency, and explain why the inductor reduces the power without dissipating any.
Show answer
Set up. The circuit is a single loop:\[ \mathbf{Z} = 15 + j\omega L_s, \qquad |\mathbf{I}| = \frac{240}{\sqrt{225 + (\omega L_s)^2}} \]Evaluating:\[ P_L = |\mathbf{I}|^2(10) = \frac{576\,000}{225 + (\omega L_s)^2} \]The resolution of the apparent paradox. The inductor's average power is exactly zero — it absorbs \(Q = |\mathbf{I}|^2\omega L_s\) and no \(P\). Yet the delivered power falls by 74% at 200 Hz. How can a lossless element reduce the power?\(f\) \(\omega L_s\) \(|\mathbf{I}|\) \(P_L\) DC 0 16.00 A 2560 W 50 Hz 6.28 Ω 14.76 A 2178 W 100 Hz 12.57 Ω 12.27 A 1504 W 200 Hz 25.13 Ω 8.20 A 672 W
It does not consume power; it limits current. The reactance adds to the impedance magnitude, so less current flows, so less power is dissipated in the resistances — both the load's and the source's. The energy that "disappears" was never generated: the source delivers less, because the current it drives is smaller.Confirm with a balance at 200 Hz. \(|\mathbf{I}| = 8.20\) A gives \(P_{\text{load}} = 672\) W, \(P_{R_s} = 336\) W, total 1008 W supplied, and \(Q = (8.20)^2(25.13) = 1690\) var circulating. The source delivers \(S = \sqrt{1008^2+1690^2} = 1968\) VA at pf 0.512.\[ P_{\text{source}} = |\mathbf{I}|^2(15) \ \text{— falls with } |\mathbf{I}| \]
The lesson. A reactance costs nothing in energy but everything in capacity — the same conclusion as Problem 7, arrived at from the opposite direction. Cancelling it with a series capacitor at the operating frequency would restore the full 2560 W, which is precisely what a matching network does.C3. For a series \(RL\) circuit with \(R = 10\ \Omega\), \(L = 50\ \text{mH}\) on 100 V rms at 50 Hz, verify by direct computation that \(Q = 2\omega\overline{w}\), and use the result to explain why \(Q\) is frequency-dependent while stored energy is not.
Show answer
Circuit quantities. At 50 Hz, \(X_L = 2\pi(50)(0.05) = 15.71\ \Omega\):\[ \mathbf{Z} = 10 + j15.71 = 18.62\angle57.52°\ \Omega, \qquad |\mathbf{I}| = \frac{100}{18.62} = 5.370\ \text{A rms} \]\[ P = |\mathbf{I}|^2R = 288.4\ \text{W}, \qquad Q = |\mathbf{I}|^2X_L = 453.0\ \text{var} \]The stored energy:\[ S = 537.0\ \text{VA}, \qquad \text{pf} = 0.537 \ \text{lagging} \]\[ \overline{w} = \tfrac12L|\mathbf{I}|^2 = \tfrac12(0.05)(5.370)^2 = 0.7210\ \text{J} \]exactly matching \(Q\).\[ 2\omega\overline{w} = 2(314.16)(0.7210) = 453.0\ \text{var}\;\checkmark \]
Why \(Q\) depends on frequency but energy does not — properly stated. The relation \(Q = 2\omega\overline{w}\) has \(\omega\) in it explicitly, so at fixed current a higher frequency gives more \(Q\) for the same stored energy. The energy stored depends only on \(L\) and the current; the reactive power counts how often that energy is shuttled back and forth.
The distinction sharpened. \(\overline{w}\) is measured in joules and is a state of the field. \(Q\) is measured in var, has dimensions of power, and describes a rate of exchange. Doubling the frequency at constant current leaves the stored energy unchanged but doubles the rate at which it moves — hence doubles \(Q\), and doubles the burden on the conductors.
A caution. In this circuit raising the frequency does not hold the current constant — \(X_L\) rises, the current falls, and \(Q = |\mathbf{I}|^2X_L\) changes in a more complicated way. The clean statement requires fixing the current, which is why \(Q = 2\omega\overline{w}\) is best read as a definition of what \(Q\) measures rather than as a prediction of how it varies.
Multiple-Choice Questions
Twelve questions in GATE/ESE style. Commit to an answer before opening the explanation.
Q1. Complex power is defined as
(a) \(\mathbf{V}\mathbf{I}\) (b) \(\mathbf{V}^{*}\mathbf{I}\) (c) \(\mathbf{V}\mathbf{I}^{*}\) (d) \(|\mathbf{V}||\mathbf{I}|\)
Show answer
(c). The conjugate on the current makes the angle equal the impedance angle — Problem 3.Q2. The unit of reactive power is
(a) watt (b) var (c) volt-ampere (d) joule
Show answer
(b). All three are dimensionally power; the different units mark which quantity is meant — Problem 2.Q3. For a purely reactive load, the average power is
(a) \(VI\) (b) \(VI/2\) (c) zero (d) negative
Show answer
(c), although the instantaneous power reaches \(\pm VI\) — Problem 1.Q4. A load with \(Q > 0\) is
(a) capacitive, leading (b) inductive, lagging (c) resistive (d) undetermined
Show answer
(b). Positive \(Q\) means the load absorbs reactive power — Problem 16.Q5. Which quantity is not conserved when loads are combined?
(a) \(P\) (b) \(Q\) (c) \(\mathbf{S}\) (d) \(S\)
Show answer
(d) — apparent power is a magnitude, and magnitudes do not add — Problems 8 and 10.Q6. A shunt capacitor for power-factor correction changes
(a) \(P\) only (b) \(Q\) only (c) both (d) neither
Show answer
(b). It dissipates nothing, so \(P\) is untouched — Problem 11.Q7. Reactive power equals
(a) \(\omega\overline{w}\) (b) \(2\omega\overline{w}\) (c) \(\overline{w}/\omega\) (d) unrelated to stored energy
Show answer
(b) — the factor of two because energy is exchanged twice per cycle — Problem 7.Q8. With RMS phasors, \(P_{\max}\) at the conjugate match is
(a) \(|\mathbf{V}_{Th}|^2/8R_{Th}\) (b) \(|\mathbf{V}_{Th}|^2/4R_{Th}\) (c) \(|\mathbf{V}_{Th}|^2/2R_{Th}\) (d) \(|\mathbf{V}_{Th}|^2/R_{Th}\)
Show answer
(b). Option (a) is for amplitude phasors — Problem 13.Q9. A wattmeter reading zero with substantial current means
(a) an open circuit (b) a purely reactive load (c) a fault (d) unity power factor
Show answer
(b) — and the current coil may still be overloaded — Problem 17.Q10. Harmonic distortion degrades power factor by
(a) a displacement factor (b) a distortion factor (c) neither (d) increasing \(P\)
Show answer
(b), which capacitors cannot correct — Problem 18.Q11. Two same-frequency sources give 100 W and 200 W separately. Together they give
(a) 300 W (b) 100 W (c) somewhere between 17 and 583 W (d) 141 W
Show answer
(c). The cross term ranges over \(\pm2\sqrt{P_AP_B} = \pm283\) W depending on the phase difference — Problem 19.Q12. At unity power factor, single-phase instantaneous power
(a) is constant (b) pulsates between 0 and \(2P\) (c) is zero (d) goes negative
Show answer
(b) at \(2\omega\) — the pulsation three-phase systems exist to cancel — Problems 1 and 20.
Key Formulas
All phasors RMS unless stated.
| Quantity | Relation | Notes |
|---|---|---|
| Instantaneous power | \(p = \tfrac12V_mI_m\left[\cos\theta + \cos(2\omega t+\theta_v+\theta_i)\right]\) | Constant plus \(2\omega\) term |
| Complex power | \(\mathbf{S} = \mathbf{V}\mathbf{I}^{*} = P+jQ\) | Conjugate the current |
| Real power | \(P = VI\cos\theta = |\mathbf{I}|^2R\) | Watt (W) |
| Reactive power | \(Q = VI\sin\theta = |\mathbf{I}|^2X\) | var |
| Apparent power | \(S = VI = |\mathbf{S}|\) | VA |
| Power triangle | \(S^2 = P^2+Q^2\) | Similar to impedance triangle |
| Power factor | \(\text{pf} = \cos\theta = P/S\) | State lagging or leading |
| Alternative forms | \(\mathbf{S} = |\mathbf{I}|^2\mathbf{Z} = |\mathbf{V}|^2/\mathbf{Z}^{*}\) | \(\angle\mathbf{S} = \angle\mathbf{Z}\) always |
| Reactive power meaning | \(Q = 2\omega\overline{w}\) | Stored energy, not transferred |
| Conservation | \(\sum\mathbf{S}_k = 0\) | \(P\) and \(Q\) separately; not \(S\) |
| Correction capacitance | \(C = \dfrac{P\left(\tan\theta_1-\tan\theta_2\right)}{\omega V^2}\) | Must be at the load end |
| Capacitor reactive power | \(Q_C = -\omega CV^2\) | Negative — supplies |
| Conjugate match | \(\mathbf{Z}_L = \mathbf{Z}_{Th}^{*}\), \(P_{\max} = |\mathbf{V}_{Th}|^2/4R_{Th}\) | RMS; 50% efficiency |
| Restricted resistive load | \(R_L = |\mathbf{Z}_{Th}|\) | Penalty grows with \(X_{Th}/R_{Th}\) |
| Power with harmonics | \(P = \sum_k V_kI_k\cos\theta_k\) | Cross terms vanish |
| Distortion factor | \(\text{pf} = \cos\theta_1 \times I_1/I_{rms}\) | Capacitors cannot correct the second |
| Superposition of power | \(P = P_A+P_B+\dfrac{2\operatorname{Re}(\mathbf{V}_A\mathbf{V}_B^{*})}{R}\) | Cross term usually non-zero |
Common Mistakes
Adding apparent powers. \(P\) and \(Q\) add; \(S\) does not. Always combine through \(P+jQ\) — Problems 8 and 10.
Omitting the conjugate in \(\mathbf{S} = \mathbf{V}\mathbf{I}^{*}\), giving a meaningless angle — Problem 3.
Putting the conjugate in the wrong place. \(|\mathbf{I}|^2\mathbf{Z}\) has none; \(|\mathbf{V}|^2/\mathbf{Z}^{*}\) does. Check that \(\angle\mathbf{S} = \angle\mathbf{Z}\) — Problem 15.
Quoting a power factor without "lagging" or "leading". The cosine cannot distinguish them — Problem 16.
Mixing amplitude and RMS conventions, giving a factor-of-two error in every power — see the convention block and Problem 13.
Assuming a capacitor changes \(P\). It changes only \(Q\) — Problem 11.
Placing the correction capacitor on the supply side of the meter. It relieves only what lies between it and the generator — Problem 12.
Superposing powers from same-frequency sources. Superpose phasors, then compute power once — Problem 19.
Using \(R_L = R_{Th}\) when the load must be resistive. The correct value is \(|\mathbf{Z}_{Th}|\) — Problem 14.
Applying \(\text{pf} = \cos\theta\) to a distorted waveform. With harmonics there is no single \(\theta\) — Problem 18.
Phase, which through Sets 20 to 22 only shifted waveforms about, turns out to govern energy itself. The volt-amperes a supply must carry divide into a real part that is delivered and consumed, and a reactive part that flows out and back twice per cycle, delivering nothing while occupying every conductor on the way. Reactive power is not an accounting fiction — Problem 7 identified it as \(2\omega\) times the energy genuinely stored in the fields — and because that energy can be stored anywhere, a capacitor beside the load can supply it and spare the whole system upstream.
One cost remains that no correction can remove. Even at unity power factor, single-phase power pulsates between zero and twice its average, twice every cycle. A single-phase motor therefore produces pulsating torque and cannot start unaided, and a single-phase generator must survive a shaft torque that varies at \(2\omega\).
Next: Set 24 — Three-Phase Power, where three sources 120° apart make the pulsation cancel exactly, and the constant total power of Problem 20 becomes the organising principle of every generation and transmission system in use.