Solved Problems · Set 25

The Two-Wattmeter Method

Part 3 · Power Analysis — two instruments measure the power of any three-wire three-phase load, balanced or not. Their sum gives the real power; for a balanced load their difference gives the reactive power as well.

Prof. Mithun Mondal 20 solved · 12 practice · 3 challenge GATE · ESE · University

Set 25 — The Two-Wattmeter Method

Set 24 closed with a measurement problem. A wattmeter reads the average of \(vi\) across one pair of terminals, so measuring three-phase power looks as though it needs three of them — and a neutral connection that a three-wire system does not offer. But with no neutral the three line currents are forced to sum to zero, so one is determined by the other two and only two independent measurements can exist. This set derives the method, works it in both directions, and marks carefully where it stops being valid.

Textbook Chapter 13 · 20 solved · 12 practice · 3 challenge · 12 MCQs

i Method Recap
  • The connection. Each wattmeter carries one line current in its current coil and the voltage from that line to a common third line across its pressure coil. With line B as the common reference, \(W_1\) reads \(\mathbf{V}_{AB}\) with \(\mathbf{I}_A\), and \(W_2\) reads \(\mathbf{V}_{CB}\) with \(\mathbf{I}_C\).

  • For a balanced load, with \(\theta\) the impedance angle:

    \[ W_1 = V_LI_L\cos\left(\theta+30°\right), \qquad W_2 = V_LI_L\cos\left(\theta-30°\right) \]
  • Sum and difference:

    \[ P_T = W_1 + W_2 = \sqrt3\,V_LI_L\cos\theta \]
    \[ Q_T = \sqrt3\left(W_2-W_1\right) = \sqrt3\,V_LI_L\sin\theta \]
  • Power factor from the readings alone:

    \[ \tan\theta = \sqrt3\,\frac{W_2-W_1}{W_2+W_1} \]
  • The sum is always valid — balanced or not, star or delta — by Blondel's theorem. The power-factor formula is valid only for a balanced load, as Problem 12 shows.

  • Below 0.5 power factor (\(\theta > 60°\)) the smaller reading goes negative and its meter must be reversed, the reading then being subtracted.

  • Convention: RMS values throughout; positive (abc) sequence and lagging loads unless stated.

VideoWalkthrough
Problem 1ChallengeBlondel's Theorem

Prove that the power delivered through an \(n\)-wire system can always be measured with \(n-1\) wattmeters, and show the result does not depend on balance, connection, or waveform.

Solution

Start from the instantaneous power crossing the boundary into the load. With all voltages measured from an arbitrary reference point \(o\):

\[ p(t) = \sum_{k=1}^{n} v_{ko}(t)\,i_k(t) \]

This is exact — it is just the definition of power flow, with no assumption yet made about the load.

Apply KCL to the whole load. Charge cannot accumulate inside it, so

\[ \sum_{k=1}^{n} i_k(t) = 0 \;\Longrightarrow\; i_n = -\left(i_1 + i_2 + \cdots + i_{n-1}\right) \]

One current is redundant. This is the entire content of the theorem.

Choose the reference to be conductor \(n\) itself, so \(v_{no} = 0\):

\[ p(t) = \sum_{k=1}^{n-1} v_{kn}(t)\,i_k(t) \]

The \(n\)th term vanishes because its voltage is zero by construction, not because its current is. There are now \(n-1\) terms, each a voltage times a current — exactly what one wattmeter measures.

Averaging gives the readings:

\[ P = \overline{p(t)} = \sum_{k=1}^{n-1} \overline{v_{kn}i_k} = \sum_{k=1}^{n-1} W_k \]
\[ \boxed{\;P_T = \sum_{k=1}^{n-1} W_k\;} \]

What the proof did not assume:

Not assumedConsequence
Balanced loadWorks for any imbalance — Problem 12
Star or deltaWorks for either, or a mixture
Sinusoidal waveformWorks with harmonics — Set 23, Problem 18
Balanced sourceWorks for any source
A particular reference conductorAny of the \(n\) may be chosen — Problem 15

Only KCL and the definition of average power were used, which is why the result is so robust.

The practical cases:

System\(n\)Wattmeters
Single-phase21
Three-phase, three-wire32
Three-phase, four-wire43

Note the four-wire case needs three — the neutral breaks the constraint that made two sufficient, because the three line currents no longer sum to zero.

The theorem trades a conductor for an instrument. A three-wire system saves a conductor (Set 24, Problem 18) and, by the very constraint that saving imposes, also saves a wattmeter. Adding a neutral restores the freedom of the third current and costs a third instrument — the two facts are the same fact.
AnswerReferencing all voltages to one conductor makes its term vanish, leaving \(n-1\) voltage–current products. Requires only KCL, so it holds for any load, connection or waveform.
Problem 2ChallengeDeriving the Two Readings

Derive \(W_1 = V_LI_L\cos(\theta+30°)\) and \(W_2 = V_LI_L\cos(\theta-30°)\) for a balanced load, and show where the 30° comes from.

Solution

Set up. Positive sequence, phase voltages referred to the neutral, load impedance \(|\mathbf{Z}|\angle\theta\):

\[ \mathbf{V}_{an} = V_{ph}\angle0°, \quad \mathbf{V}_{bn} = V_{ph}\angle{-120°}, \quad \mathbf{V}_{cn} = V_{ph}\angle{+120°} \]
\[ \mathbf{I}_a = I_L\angle{-\theta}, \quad \mathbf{I}_b = I_L\angle{-\theta-120°}, \quad \mathbf{I}_c = I_L\angle{-\theta+120°} \]

The two line voltages, using Set 24, Problem 3:

\[ \mathbf{V}_{ab} = \mathbf{V}_{an} - \mathbf{V}_{bn} = \sqrt3\,V_{ph}\angle30° = V_L\angle30° \]
\[ \mathbf{V}_{cb} = \mathbf{V}_{cn} - \mathbf{V}_{bn} = V_L\angle90° \]

Note \(\mathbf{V}_{cb} = -\mathbf{V}_{bc}\), which is why the second meter is connected C-to-B rather than B-to-C — reversing it would make \(W_2\) read negative for every load.

Each wattmeter reads \(\operatorname{Re}\left(\mathbf{V}\mathbf{I}^{*}\right)\) — Set 23, Problem 17:

\[ W_1 = \operatorname{Re}\left(\mathbf{V}_{ab}\mathbf{I}_a^{*}\right) = V_LI_L\cos\left(30° - (-\theta)\right) \]
\[ \boxed{\;W_1 = V_LI_L\cos\left(\theta+30°\right)\;} \]
\[ W_2 = \operatorname{Re}\left(\mathbf{V}_{cb}\mathbf{I}_c^{*}\right) = V_LI_L\cos\left(90° - (120°-\theta)\right) \]
\[ \boxed{\;W_2 = V_LI_L\cos\left(\theta-30°\right)\;} \]

Where the 30° comes from. Each meter compares a line voltage with a line current. But the impedance angle \(\theta\) relates the phase voltage to that current, and the line voltage leads the phase voltage by 30°:

\[ \underbrace{30°}_{\text{line leads phase}} \pm \underbrace{\theta}_{\text{impedance angle}} \]

One meter picks up \(+30°\) and the other \(-30°\) because their line voltages sit on opposite sides of their currents. The shift derived in Set 24 for its own sake is exactly what makes the method work.

Sum and difference by the standard identities:

\[ W_1 + W_2 = V_LI_L\left[\cos(\theta+30°)+\cos(\theta-30°)\right] = 2V_LI_L\cos\theta\cos30° \]
\[ = \sqrt3\,V_LI_L\cos\theta = P_T\;\checkmark \]
\[ W_2 - W_1 = V_LI_L\left[\cos(\theta-30°)-\cos(\theta+30°)\right] = 2V_LI_L\sin\theta\sin30° \]
\[ = V_LI_L\sin\theta = \frac{Q_T}{\sqrt3} \]

Numerical confirmation. Taking \(V_{ph} = 100\ \text{V}\), \(I_L = 10\ \text{A}\), \(\theta = 36.87°\), computing directly from the phasors gives \(W_1 = 680.4\ \text{W}\) and \(W_2 = 1719.6\ \text{W}\), matching the formulas exactly; their sum is 2400.0 W, and \(\sqrt3(W_2-W_1) = 1800.0\ \text{var}\), both agreeing with \(\sqrt3V_LI_L\cos\theta\) and \(\sqrt3V_LI_L\sin\theta\).

Two instruments give three quantities — \(P\), \(Q\) and the power factor — with no phase-measuring equipment at all. The information is carried in the difference of the readings, which the \(\pm30°\) makes sensitive to \(\sin\theta\) while the sum is sensitive to \(\cos\theta\). That is an unusually good return on two moving-coil movements.
AnswerEach meter compares a line voltage with a line current, and the line voltage leads its phase voltage by 30° — so the two arguments become \(\theta\pm30°\)
Problem 3CoreFour-Wire: Three Wattmeters

An unbalanced four-wire load has \(\mathbf{V}_{AN} = 100\angle0°\), \(\mathbf{V}_{BN} = 100\angle120°\), \(\mathbf{V}_{CN} = 100\angle{-120°}\ \text{V}\) and line currents \(\mathbf{I}_a = 6.67\angle0°\), \(\mathbf{I}_b = 8.94\angle93.44°\), \(\mathbf{I}_c = 10\angle{-66.87°}\ \text{A}\). Find the total power absorbed.

Solution

Why three wattmeters here. The neutral is accessible, so \(n = 4\) and Blondel requires \(n-1 = 3\). Each meter measures one phase directly, referred to the neutral — the two-wattmeter method does not apply.

Note also that \(\mathbf{V}_{BN}\) leads and \(\mathbf{V}_{CN}\) lags, so this is negative (acb) sequence. That makes no difference to the arithmetic, since the currents are given rather than derived.

Each reading is the real part of voltage times conjugate current:

\[ P_1 = \operatorname{Re}\left(\mathbf{V}_{AN}\mathbf{I}_a^{*}\right) = (100)(6.67)\cos\left(0°-0°\right) = 667\ \text{W} \]
\[ P_2 = (100)(8.94)\cos\left(120°-93.44°\right) = 894\cos26.56° = 800\ \text{W} \]
\[ P_3 = (100)(10)\cos\left(-120°+66.87°\right) = 1000\cos(-53.13°) = 600\ \text{W} \]

The total:

\[ P_T = 667 + 800 + 600 = 2067\ \text{W} \]

Note the three power factors differ:

PhaseAnglepfCharacter
A1.00Resistive
B26.56°0.894Lagging
C−53.13°0.600Leading

Three different loads on three phases — which is exactly the situation a four-wire system exists to accommodate, and exactly why each phase must be metered separately.

The neutral current, for completeness:

\[ \mathbf{I}_N = \mathbf{I}_a+\mathbf{I}_b+\mathbf{I}_c \ne 0 \]

Non-zero because the load is unbalanced, and it is precisely this that destroys the constraint \(\sum i_k = 0\) over the three lines and so forbids the two-wattmeter method.

A shortcut when the neutral is available. If only the total is wanted and the load impedances are known, \(P_T = \sum|\mathbf{I}_k|^2R_k\) avoids all the angles. Here the angles were given rather than the impedances, so the direct route was the shorter one.

The number of wattmeters is set by the number of wires, not the number of phases. Three wires need two meters even for a badly unbalanced load; four wires need three even for a perfectly balanced one. Counting conductors is the reliable way to decide, and it follows straight from Problem 1.
Answer\(P_T = 667+800+600 = 2067\ \text{W}\)
Problem 4CorePredicting the Readings

A balanced star load of \(\mathbf{Z}_Y = (8+j6)\ \Omega\) per phase is connected to 208 V lines. Predict \(W_1\) and \(W_2\), and find \(P_T\) and \(Q_T\).

Solution

The impedance angle is the power-factor angle:

\[ \mathbf{Z}_Y = 8 + j6 = 10\angle36.87°\ \Omega \;\Longrightarrow\; \theta = 36.87°, \quad \cos\theta = 0.8 \ \text{lagging} \]

Line current — star, so it equals the phase current:

\[ I_L = \frac{V_L/\sqrt3}{|\mathbf{Z}_Y|} = \frac{208/1.732}{10} = 12.01\ \text{A} \]

The two readings:

\[ W_1 = V_LI_L\cos\left(\theta+30°\right) = (208)(12.01)\cos66.87° = 981\ \text{W} \]
\[ W_2 = V_LI_L\cos\left(\theta-30°\right) = (208)(12.01)\cos6.87° = 2480\ \text{W} \]

\(W_2 > W_1\), confirming a lagging load — consistent with the \(+j6\) in the impedance. Note how unequal they are: a 2.5:1 ratio at a perfectly ordinary 0.8 power factor.

Total real and reactive power:

\[ P_T = W_1+W_2 = 3461\ \text{W} = 3.46\ \text{kW} \]
\[ Q_T = \sqrt3\left(W_2-W_1\right) = 1.732(1499) = 2596\ \text{var} = 2.60\ \text{kvar} \]

Check both against Set 24's formulas:

\[ P_T = \sqrt3V_LI_L\cos\theta = 1.732(208)(12.01)(0.8) = 3461\ \text{W}\;\checkmark \]
\[ Q_T = 3I_L^2X = 3(12.01)^2(6) = 2596\ \text{var}\;\checkmark \]

The second is the more convincing check, since it uses the reactance directly and involves no wattmeter theory at all.

Why prediction is worth practising. Working forward from a known load to the expected readings is how a measurement is verified — if the instruments disagree with the prediction, either the connection is wrong or the load is not what it was assumed to be. Problem 16 lists the connection faults this catches.

The two readings are unequal whenever \(\theta \ne 0\), and their inequality carries the reactive information. Equal readings mean unity power factor; the more they diverge, the worse the power factor — a relationship precise enough that experienced operators read the power factor off the pair of dials by eye.
Answer\(W_1 = 981\ \text{W}\), \(W_2 = 2480\ \text{W}\), \(P_T = 3.46\ \text{kW}\), \(Q_T = 2.60\ \text{kvar}\)
Problem 5CorePower Factor from Readings

Two wattmeters on a balanced load read \(W_1 = 460\ \text{W}\) and \(W_2 = 920\ \text{W}\). Find the total power and the power factor, assuming a lagging load.

Solution

Total power is the algebraic sum:

\[ P_T = W_1+W_2 = 460+920 = 1380\ \text{W} \]

The power-factor angle from the ratio of difference to sum:

\[ \tan\theta = \sqrt3\,\frac{W_2-W_1}{W_2+W_1} = \sqrt3\,\frac{460}{1380} = \frac{\sqrt3}{3} = 0.5774 \]
\[ \theta = 30° \;\Longrightarrow\; \cos\theta = 0.866 \ \text{lagging} \]

Why the formula needs no voltage or current. Both readings contain the factor \(V_LI_L\), which cancels in the ratio:

\[ \frac{W_2-W_1}{W_2+W_1} = \frac{V_LI_L\sin\theta}{\sqrt3V_LI_L\cos\theta} = \frac{\tan\theta}{\sqrt3} \]

So the power factor is obtained from the two readings alone — no voltmeter, no ammeter, and no knowledge of the load's connection.

The reactive power follows too:

\[ Q_T = \sqrt3\left(W_2-W_1\right) = 1.732(460) = 797\ \text{var} \]
\[ S = \sqrt{1380^2+797^2} = 1594\ \text{VA} \]

Confirming \(\text{pf} = P/S = 1380/1594 = 0.866\) ✓ — the two routes to the power factor agree.

A memorable special case. Here \(W_2 = 2W_1\) exactly, and the answer came out at exactly 30°. That is worth remembering as a calibration point:

\[ \frac{W_1}{W_2} = \frac12 \;\Longleftrightarrow\; \theta = 30° \;\Longleftrightarrow\; \text{pf} = 0.866 \]

Problem 9 develops the ratio into a general method.

Two numbers on two dials give the complete power picture of a balanced load. The sum is \(P\), \(\sqrt3\) times the difference is \(Q\), and their ratio fixes the power factor — all without measuring a single voltage or current. Before electronic instruments this was the only practical way to determine an industrial load's power factor.
Answer\(P_T = 1380\ \text{W}\), \(\cos\theta = 0.866\) lagging, \(Q_T = 797\ \text{var}\)
Problem 6Exam levelReadings to Impedance

Two wattmeters on a delta-connected load read \(W_1 = 1560\ \text{W}\) and \(W_2 = 2100\ \text{W}\) at a line voltage of 220 V. Find the per-phase real and reactive powers, the power factor, and the phase impedance.

Solution

Total and per-phase real power:

\[ P_T = 1560+2100 = 3660\ \text{W}, \qquad P_{ph} = \frac{3660}{3} = 1220\ \text{W} \]

Total and per-phase reactive power:

\[ Q_T = \sqrt3\left(W_2-W_1\right) = 1.732(540) = 935.3\ \text{var} \]
\[ Q_{ph} = \frac{935.3}{3} = 311.8\ \text{var} \]

Dividing by three is legitimate here because the load is balanced — each phase carries an equal share. Problem 12 shows what happens when it is not.

Power factor:

\[ \theta = \tan^{-1}\frac{Q_T}{P_T} = \tan^{-1}\frac{935.3}{3660} = 14.34° \]
\[ \cos\theta = 0.9689 \ \text{lagging} \]

Now use the delta connection. The phase voltage equals the line voltage:

\[ V_{ph} = V_L = 220\ \text{V} \]
\[ I_{ph} = \frac{P_{ph}}{V_{ph}\cos\theta} = \frac{1220}{(220)(0.9689)} = 5.724\ \text{A} \]

The phase impedance:

\[ \mathbf{Z}_{ph} = \frac{V_{ph}}{I_{ph}}\angle\theta = \frac{220}{5.724}\angle14.34° = 38.44\angle14.34°\ \Omega \]
\[ = 37.24 + j9.52\ \Omega \]

Check via the phase powers directly:

\[ R_{ph} = \frac{P_{ph}}{I_{ph}^2} = \frac{1220}{(5.724)^2} = 37.24\ \Omega\;\checkmark \]
\[ X_{ph} = \frac{Q_{ph}}{I_{ph}^2} = \frac{311.8}{32.76} = 9.52\ \Omega\;\checkmark \]

Note the essential extra information. The wattmeter readings alone gave \(P_T\), \(Q_T\) and the power factor — but the impedance required two further facts: the line voltage, and the knowledge that the load is delta. Had it been star, the same readings would give

\[ \mathbf{Z}_Y = \frac{38.44}{3}\angle14.34° = 12.81\angle14.34°\ \Omega \]

The measurement cannot distinguish the two, since Set 24, Problem 6 showed they are indistinguishable from the terminals.

Wattmeters see the load as a black box. They determine \(P\), \(Q\) and the power factor without any assumption about what is inside, but converting to a per-phase impedance needs the connection — and no terminal measurement whatever can supply that. It has to come from the nameplate.
Answer\(P_{ph} = 1220\ \text{W}\), \(Q_{ph} = 311.8\ \text{var}\), pf = 0.969 lagging, \(\mathbf{Z}_{ph} = 38.44\angle14.34°\ \Omega\)
Problem 7Exam levelThe Negative Reading

A balanced load runs at 0.4 power factor lagging on 415 V with a line current of 12 A. Find the two readings, verify the total, and explain the sign.

Solution

The angle:

\[ \theta = \cos^{-1}(0.4) = 66.42° \ \text{lagging} \]

Already above 60°, which is the threshold Problem 8 identifies.

The readings, with \(V_LI_L = (415)(12) = 4980\ \text{VA}\):

\[ W_1 = 4980\cos\left(66.42°+30°\right) = 4980\cos96.42° = -557\ \text{W} \]
\[ W_2 = 4980\cos\left(66.42°-30°\right) = 4980\cos36.42° = 4007\ \text{W} \]

Why \(W_1\) is negative. Its argument \(\theta+30°\) has passed 90°, so the cosine turns negative:

\[ \theta + 30° > 90° \;\Longleftrightarrow\; \theta > 60° \;\Longleftrightarrow\; \text{pf} < 0.5 \]

The voltage across that meter's pressure coil and the current in its current coil are more than 90° apart, so the average of their product is negative — the meter's element is returning power in the accounting sense, though nothing physically flows backwards.

The total is still the algebraic sum:

\[ P_T = -557 + 4007 = 3450\ \text{W} \]
\[ \text{check:} \quad \sqrt3V_LI_L\cos\theta = 1.732(4980)(0.4) = 3450\ \text{W}\;\checkmark \]

What to do in practice. A moving-coil wattmeter cannot deflect below zero — the pointer simply drives against its stop, which can damage the movement:

StepAction
1Reverse the connections to one coil — usually the pressure coil
2Read the now-positive deflection
3Subtract it rather than adding

Reversing both coils restores the original negative reading, since two sign changes cancel — a classic laboratory error.

The diagnostic value. A negative reading is not a fault but information: it says immediately that the power factor is below 0.5, without any calculation. On a large motor that would prompt an investigation — a lightly loaded induction motor runs at very poor power factor, and correcting it (Set 24, Problem 17) would show up as the negative reading returning to positive.

The negative reading is the method working correctly, not failing. A wattmeter measures \(\overline{vi}\) for the terminals it is connected to, and that average is genuinely negative here — Blondel's theorem never promised both terms would be positive, only that they would sum to the total.
Answer\(W_1 = -557\ \text{W}\), \(W_2 = 4007\ \text{W}\), \(P_T = 3450\ \text{W}\); negative because pf < 0.5
Problem 8ChallengeThe Full Range

Map the behaviour of the two readings across the whole range of power factor from unity to zero, and identify every landmark.

Solution

Normalise by taking \(V_LI_L = 1000\ \text{VA}\), so the readings are directly comparable:

pf\(\theta\)\(W_1\)\(W_2\)\(W_1/W_2\)\(P_T\)
1.0008668661.0001732
0.96615°7079660.7321673
0.86630°50010000.5001500
0.70745°2599660.2681225
0.50060°08660.000866
0.40066.4°−112805−0.139693
0.20078.5°−317663−0.478346
0.00090°−500500−1.0000

The four landmarks:

ConditionpfSignature
\(W_1 = W_2\)1.0Unity power factor — purely resistive
\(W_1 = \tfrac12W_2\)0.866\(\theta = 30°\) — Problem 5's case
\(W_1 = 0\)0.5One meter reads zero
\(W_1 = -W_2\)0Purely reactive — readings cancel

Notice \(W_2\) is not monotonic. It peaks at \(\theta = 30°\), where its argument \(\theta-30°\) is zero:

\[ W_2 = V_LI_L\cos\left(\theta-30°\right) \ \text{is maximum at } \theta = 30° \]

So the larger reading actually rises as the power factor falls from 1.0 to 0.866, then falls thereafter. Only \(W_1\) decreases throughout — which is why it is \(W_1\) that carries the diagnostic information.

The zero-power-factor case is a useful sanity check. With a purely reactive load the readings are equal and opposite, so

\[ P_T = -500 + 500 = 0 \]

as it must be — no real power is consumed. Yet each meter shows a substantial deflection, and each carries full line current. A wattmeter reading zero total does not mean the instruments are idle, exactly as in Set 23, Problem 17.

A useful bound. Since \(|\cos| \le 1\), neither reading can exceed \(V_LI_L\), while the total reaches \(\sqrt3V_LI_L\) at unity power factor. So each meter must be rated for the full \(V_LI_L\) even though it never reads more than \(1/\sqrt3\) of the maximum total.

The pattern is worth memorising as a diagnostic scale. Equal readings mean unity power factor; a two-to-one ratio means 0.866; one reading at zero means exactly 0.5; and a negative reading means worse than 0.5. An operator glancing at two dials can place a load on that scale without any arithmetic at all.
AnswerEqual at pf 1; ratio 1:2 at pf 0.866; \(W_1 = 0\) at pf 0.5; equal and opposite at pf 0. \(W_2\) peaks at \(\theta = 30°\), not at unity.
Problem 9Exam levelThe Ratio Method

Express the power factor in terms of the ratio \(r = W_1/W_2\) alone, and show why this form is often more convenient.

Solution

Start from the standard formula and divide numerator and denominator by \(W_2\):

\[ \tan\theta = \sqrt3\,\frac{W_2-W_1}{W_2+W_1} = \sqrt3\,\frac{1-r}{1+r} \]
\[ \boxed{\;\tan\theta = \sqrt3\,\frac{1-r}{1+r}, \qquad r = \frac{W_1}{W_2}\;} \]

Verify at three points:

\(r\)\(\tan\theta\)\(\theta\)pf
1.00001.000
0.5000.577430°0.866
0.0001.732160°0.500
−0.1392.291366.4°0.400
−1.000\(\infty\)90°0.000

Each row confirms the corresponding row of Problem 8's table.

Why the ratio form is convenient:

AdvantageDetail
Scale-independentInstrument multiplying factors cancel
Units-independentWorks with readings in W, kW, or arbitrary scale divisions
Immune to common errorsA CT or PT ratio error affecting both meters equally cancels
Single inputOne number determines the power factor completely

The third is the practically important one: if both wattmeters share a current transformer of uncertain ratio, the ratio method still gives the correct power factor even though neither reading is trustworthy in absolute terms.

A worked instance. Two meters read 35 and 87 scale divisions on identical instruments:

\[ r = \frac{35}{87} = 0.4023 \;\Longrightarrow\; \tan\theta = \sqrt3\,\frac{0.5977}{1.4023} = 0.7382 \]
\[ \theta = 36.44° \;\Longrightarrow\; \text{pf} = 0.805 \ \text{lagging} \]

No scale factor was needed. To obtain \(P_T\) as well, the multiplier would then have to be applied — the ratio gives the power factor for free, but not the power.

A caution on the sign of \(r\). When \(W_1\) is negative, \(r\) is negative and the formula still holds — but the reading must be entered with its sign. Entering a reversed meter's reading as positive gives a badly wrong power factor, and is the commonest error in the low-power-factor case.

The ratio carries the power factor; the sum carries the power. Splitting the two readings this way separates the information cleanly — and explains why calibration errors that scale both readings equally corrupt the power measurement while leaving the power factor exact.
Answer\(\tan\theta = \sqrt3(1-r)/(1+r)\) with \(r = W_1/W_2\); scale-independent, so common multiplying errors cancel
Problem 10ChallengeLagging or Leading?

Two wattmeters read 120 W and 920 W, but it is not recorded which is \(W_1\). Show that the power factor magnitude is determined but its character is not, and explain how to resolve the ambiguity.

Solution

The total is unambiguous:

\[ P_T = 120 + 920 = 1040\ \text{W} \]

Addition is commutative, so the labelling does not matter for the power.

The power factor magnitude is also unambiguous. Taking the two assignments in turn:

\[ W_1 = 120,\ W_2 = 920: \quad \tan\theta = \sqrt3\,\frac{800}{1040} = +1.3323 \;\Rightarrow\; \theta = +53.13° \]
\[ W_1 = 920,\ W_2 = 120: \quad \tan\theta = \sqrt3\,\frac{-800}{1040} = -1.3323 \;\Rightarrow\; \theta = -53.13° \]
\[ \cos(\pm53.13°) = 0.6 \ \text{in both cases} \]

Same magnitude, opposite sign — one is a lagging load and the other leading, and the readings alone cannot tell them apart.

The general rule follows from the derivation:

CharacterSign of \(\theta\)Which reading is larger
Inductive (lagging)\(+\)\(W_2 > W_1\)
Resistive0Equal
Capacitive (leading)\(-\)\(W_1 > W_2\)

Swapping a leading load for a lagging one of the same power factor simply exchanges the two readings — which is exactly why the identity of the meters must be recorded.

Three ways to resolve it:

MethodDetail
Record which meter is whichBest — the ambiguity never arises
Know the loadMotors, transformers and most industry are lagging
Add capacitance and observeIf the readings converge, it was lagging; if they diverge, leading

The third is a genuine field technique — Problem 17 works it through. It resolves the ambiguity by perturbing the system in a known direction.

The deeper point. This is the same ambiguity as Set 23, Problem 16: \(\cos\theta\) is an even function, so no measurement of a cosine can recover a sign. The wattmeter pair does encode the sign — in which meter reads higher — but that information is lost the moment the readings are written down as an unlabelled pair.

Label the meters. The pair \((W_1, W_2)\) is an ordered pair, and every formula in this set depends on the order. Reporting "the readings were 120 W and 920 W" throws away exactly the information that distinguishes a capacitor bank from an induction motor.
Answer\(P_T = 1040\ \text{W}\) and \(|\text{pf}| = 0.6\) either way, but lagging if \(W_2 > W_1\) and leading if \(W_1 > W_2\)
Problem 11Exam levelReactive Power from the Difference

Show why the difference of the readings gives reactive power, and derive the related single-wattmeter method for measuring \(Q\) alone.

Solution

The difference, from Problem 2:

\[ W_2 - W_1 = V_LI_L\left[\cos(\theta-30°)-\cos(\theta+30°)\right] \]
\[ = 2V_LI_L\sin\theta\sin30° = V_LI_L\sin\theta \]
\[ Q_T = \sqrt3\,V_LI_L\sin\theta = \sqrt3\left(W_2-W_1\right) \]

Why the \(\pm30°\) produces a sine. The identity

\[ \cos(A-B) - \cos(A+B) = 2\sin A\sin B \]

converts a difference of cosines into a product of sines. The sum did the reverse, giving \(2\cos\theta\cos30°\). So one combination extracts \(\cos\theta\) and the other \(\sin\theta\) — the two meters between them resolve the load's complex power into its rectangular components.

The single-wattmeter method for \(Q\). Connect one wattmeter with its current coil in line A but its pressure coil across \(\mathbf{V}_{bc}\) — the voltage between the other two lines:

\[ \mathbf{V}_{bc} = V_L\angle{-90°}, \qquad \mathbf{I}_a = I_L\angle{-\theta} \]
\[ W = \operatorname{Re}\left(\mathbf{V}_{bc}\mathbf{I}_a^{*}\right) = V_LI_L\cos\left(-90°+\theta\right) = V_LI_L\sin\theta \]
\[ \boxed{\;Q_T = \sqrt3\,W\;} \]

One instrument, connected "across the other two lines", reads reactive power directly. This is the cross-connection or varmeter arrangement.

Why it works. \(\mathbf{V}_{bc}\) is in quadrature with \(\mathbf{V}_{an}\) — it lags by 90°:

PhasorAngle
\(\mathbf{V}_{an}\)
\(\mathbf{V}_{bc}\)−90°

Feeding a wattmeter with a voltage in quadrature to the one that defines \(\theta\) turns its cosine into a sine — which is the definition of reactive power. The three-phase system supplies that quadrature voltage for free, which a single-phase system cannot do without a phase-shifting network.

A worked check. For the load of Problem 4 — \(V_L = 208\), \(I_L = 12.01\), \(\theta = 36.87°\):

\[ W = (208)(12.01)\sin36.87° = 1499\ \text{var-equivalent} \]
\[ Q_T = \sqrt3(1499) = 2596\ \text{var}\;\checkmark \]

Matching the two-wattmeter result exactly — and note that 1499 is precisely \(W_2-W_1\) from that problem, as it must be.

Reactive power is measurable by exactly the same instrument as real power, connected differently. Nothing about a wattmeter distinguishes watts from vars — the distinction lies entirely in which voltage is presented to the pressure coil. That is worth holding onto: \(P\) and \(Q\) are the same product resolved along perpendicular axes, as Set 23, Problem 2's triangle said.
Answer\(\cos(A-B)-\cos(A+B) = 2\sin A\sin B\) turns the difference into \(V_LI_L\sin\theta\). One wattmeter across the other two lines gives \(Q_T = \sqrt3W\) directly.
Problem 12ChallengeUnbalanced Loads

For the unbalanced three-wire star load of Set 24, Problem 15 — \(\mathbf{Z}_A = 10\), \(\mathbf{Z}_B = 10+j10\), \(\mathbf{Z}_C = 20\ \Omega\) on 400 V — compute the two wattmeter readings, and test both the sum and the power-factor formula against the true values.

Solution

Recover the currents from Set 24, Problem 15, where Millman's theorem gave a star-point displacement of \(28.99\angle89.04°\ \text{V}\):

\[ \mathbf{I}_A = 23.23\angle{-7.17°}, \quad \mathbf{I}_B = 18.15\angle{-161.86°}, \quad \mathbf{I}_C = 10.33\angle124.14°\ \text{A} \]

These sum to zero, as a three-wire system requires.

The true powers, computed element by element:

\[ P_{\text{true}} = |\mathbf{I}_A|^2(10) + |\mathbf{I}_B|^2(10) + |\mathbf{I}_C|^2(20) = 10\,823.5\ \text{W} \]
\[ Q_{\text{true}} = |\mathbf{I}_B|^2(10) = 3294.1\ \text{var} \]

Only phase B has reactance, so it alone contributes to \(Q\).

The wattmeter readings, with line B as the common reference:

\[ W_1 = \operatorname{Re}\left(\mathbf{V}_{AB}\mathbf{I}_A^{*}\right) = 7403.3\ \text{W} \]
\[ W_2 = \operatorname{Re}\left(\mathbf{V}_{CB}\mathbf{I}_C^{*}\right) = 3420.2\ \text{W} \]

Test the sum:

\[ W_1 + W_2 = 7403.3 + 3420.2 = 10\,823.5\ \text{W} \]
\[ \text{versus } P_{\text{true}} = 10\,823.5\ \text{W} \;\;\checkmark \]

Exact. Blondel's theorem holds to the last digit, exactly as Problem 1 promised — no assumption of balance was ever made.

Now test the power-factor formula:

\[ \sqrt3\left(W_2-W_1\right) = 1.732\left(3420.2-7403.3\right) = -6898.9 \]
\[ \text{versus } Q_{\text{true}} = +3294.1\ \text{var} \]

Wrong by a factor of more than two — and wrong in sign. The formula reports a strongly capacitive load where the true load is inductive.

Why the sum survives and the difference does not. The sum was derived from KCL alone. The difference was derived from the specific phasor relationships of a balanced load — equal current magnitudes, equal angles, and the exact \(\pm30°\) pattern:

ResultDerived fromValid unbalanced?
\(P_T = W_1+W_2\)KCL onlyYes
\(Q_T = \sqrt3(W_2-W_1)\)Balanced phasor geometryNo
\(\tan\theta = \sqrt3\frac{W_2-W_1}{W_2+W_1}\)Both of the aboveNo
\(P_{ph} = P_T/3\)Equal phase sharesNo

What to do instead. For an unbalanced load, the two wattmeters give \(P_T\) and nothing more. Obtaining \(Q\) or a meaningful power factor requires either three-wattmeter measurement with an artificial neutral, or full phasor instrumentation — and even then, "the power factor" of an unbalanced load is a quantity needing careful definition, since each phase has its own.

This is the single most important limitation in the subject, and it is easy to miss because the sum keeps working perfectly. A student who checks only the total will find the method flawless and go on to apply the power-factor formula with confidence — and get an answer wrong in sign. Always ask whether the load is balanced before using anything beyond the sum.
AnswerSum gives 10 823.5 W, exactly the true power. But \(\sqrt3(W_2-W_1) = -6899\) against a true \(Q\) of +3294 var — the pf formula fails completely.
Problem 13CoreA Delta Load

A balanced delta load of \(15\angle36.87°\ \Omega\) per phase runs on 415 V. Predict the wattmeter readings and confirm that the connection makes no difference to the method.

Solution

Delta quantities from Set 24, Problem 11:

\[ V_{ph} = V_L = 415\ \text{V}, \qquad I_{ph} = \frac{415}{15} = 27.67\ \text{A} \]
\[ I_L = \sqrt3(27.67) = 47.92\ \text{A} \]

The readings use line quantities — which is the whole point:

\[ W_1 = V_LI_L\cos\left(\theta+30°\right) = (415)(47.92)\cos66.87° = 7812\ \text{W} \]
\[ W_2 = V_LI_L\cos\left(\theta-30°\right) = (415)(47.92)\cos6.87° = 19\,744\ \text{W} \]
\[ P_T = 7812 + 19\,744 = 27\,556\ \text{W} \]

Matching Set 24, Problem 11's answer of 27.56 kW exactly.

Why the connection is irrelevant to the meters. The wattmeters are connected to the lines, and they see only line voltages and line currents. From outside, a delta of \(\mathbf{Z}\) and a star of \(\mathbf{Z}/3\) are indistinguishable — Set 24, Problem 6 — so they must give identical readings:

\[ \mathbf{Z}_Y = \frac{15\angle36.87°}{3} = 5\angle36.87°\ \Omega \]
\[ I_L = \frac{415/\sqrt3}{5} = 47.92\ \text{A}\;\checkmark \]

The same line current, hence the same readings.

What the meters cannot tell you. Given the readings and the line voltage, the per-phase impedance follows only once the connection is known:

If the load is...\(V_{ph}\)\(I_{ph}\)\(|\mathbf{Z}_{ph}|\)
Delta415 V27.67 A15 Ω
Star239.6 V47.92 A5 Ω

Same measurements, same power, same power factor — three-to-one difference in the deduced impedance. This is Problem 6's point restated with numbers.

Verify the power factor from the readings:

\[ \tan\theta = \sqrt3\,\frac{19\,744-7812}{27\,556} = \sqrt3(0.4330) = 0.7500 \]
\[ \theta = 36.87° \;\Longrightarrow\; \cos\theta = 0.8\;\checkmark \]

Recovering the impedance angle exactly, which confirms both the readings and the formula.

The method is connection-blind by design. Every formula in this set is written in line quantities precisely so that the internal arrangement of the load never enters — which is what makes two wattmeters usable on an unknown industrial load, where opening the terminal box to see whether it is star or delta is neither convenient nor safe.
Answer\(W_1 = 7812\ \text{W}\), \(W_2 = 19\,744\ \text{W}\), \(P_T = 27.56\ \text{kW}\) — identical to a star of \(5\angle36.87°\ \Omega\)
Problem 14Exam levelOne-Wattmeter Methods

Set out the circumstances under which a single wattmeter suffices for a three-phase measurement, and the arrangements used.

Solution

Blondel's theorem sets the floor at \(n-1\) instruments for a general load. A single wattmeter can only be enough if extra information — specifically, that the load is balanced — is supplied from outside the measurement.

aBalanced load with an accessible neutral. Measure one phase and multiply by three:

\[ P_T = 3\,\overline{v_{an}i_a} = 3W \]

The simplest case, and valid only because balance guarantees the other two phases are identical.

bBalanced load, three-wire, artificial neutral. Create a neutral with two resistors equal to the wattmeter's pressure-coil resistance:

ElementFromTo
Pressure coil (resistance \(R_p\))Line AStar point
Resistor \(R_p\)Line BStar point
Resistor \(R_p\)Line CStar point

Three equal resistances in star place their common point at the true neutral potential — the balanced case of Set 24, Problem 15, where the Millman displacement vanishes. The meter then reads \(P_T/3\).

cThe two-reading method with one meter. Connect one wattmeter as \(W_1\), record the reading, then switch it to the \(W_2\) position and record again:

\[ P_T = W_{(1)} + W_{(2)} \]

Valid only if the load is steady between the two readings — the measurements are no longer simultaneous. A fluctuating load makes this useless, which is the practical reason two meters are preferred.

dReactive power alone, by the cross-connection of Problem 11:

\[ Q_T = \sqrt3\,W \quad\text{(pressure coil across the other two lines)} \]

Summary of what each arrangement needs:

MethodMetersRequiresGives
Three-wattmeter3Neutral access\(P_T\), any load
Two-wattmeter2Nothing\(P_T\) any load; \(Q\), pf if balanced
One + neutral1Balance + neutral\(P_T\)
One + artificial neutral1Balance\(P_T\)
One, switched1Steady load\(P_T\)
Cross-connected1Balance\(Q_T\) only

The two-wattmeter method is the only row requiring no assumption about the load, which is why it is the standard.

Fewer instruments always means more assumptions. Blondel's \(n-1\) is the number needed when nothing is known about the load; every reduction below it buys economy with a condition that must be independently verified — and a load assumed balanced but actually not will give a wrong answer with no indication that anything is amiss.
AnswerOne meter suffices only for a balanced load — with a real neutral, an artificial neutral, or by switching between the two positions on a steady load
Problem 15Exam levelChoosing the Common Line

Three choices of common reference line are possible. Show that all three give the same total, and that the individual readings differ. Use a balanced load at 0.8 lagging, 400 V, 10 A.

Solution

The three connections, each omitting one line from the pressure-coil references:

Common lineMeter 1Meter 2Reading 1Reading 2Sum
B\(\mathbf{V}_{AB},\mathbf{I}_A\)\(\mathbf{V}_{CB},\mathbf{I}_C\)1571 W3971 W5543 W
C\(\mathbf{V}_{AC},\mathbf{I}_A\)\(\mathbf{V}_{BC},\mathbf{I}_B\)3971 W1571 W5543 W
A\(\mathbf{V}_{BA},\mathbf{I}_B\)\(\mathbf{V}_{CA},\mathbf{I}_C\)3971 W1571 W5543 W
\[ \text{true } P_T = \sqrt3(400)(10)(0.8) = 5543\ \text{W}\;\checkmark \]

All three agree on the total, exactly as Problem 1's proof requires — the reference conductor was arbitrary throughout.

But the individual readings are permuted. The same pair of numbers appears in every row, in different orders. This matters because

\[ \tan\theta = \sqrt3\,\frac{W_2-W_1}{W_2+W_1} \]

depends on which is called \(W_1\). Rows 2 and 3 would give \(\theta = -36.87°\) — reporting a leading load — unless the labelling convention is applied consistently.

The convention that fixes it. With positive sequence and line B common, label so that

\[ W_1 \ \text{takes the lower reading for a lagging load} \]

Equivalently: for a lagging load \(W_2 > W_1\) always. Since most industrial loads are lagging, assigning the larger reading to \(W_2\) is usually correct — but it assumes the answer, which is exactly the ambiguity of Problem 10.

Which line to choose in practice:

ConsiderationPreference
Convenience of accessWhichever line is easiest to reach
Existing current transformersUse the lines that already have CTs
Unbalanced loadAny — the sum is valid regardless
Consistency with recordsFollow the site standard

There is no electrical reason to prefer one, which is itself a useful fact: the choice can be made entirely on practical grounds.

The one thing that must not change is the pairing. Meter 1's current coil and its pressure coil must refer to the same line — pairing \(\mathbf{I}_A\) with \(\mathbf{V}_{CB}\) gives a reading with no useful interpretation, and the sum is then simply wrong. Problem 16 lists this among the connection faults.

The freedom to choose the reference is a consequence of the proof, not an accident. Problem 1 referred all voltages to conductor \(n\) without specifying which conductor that was, so any of the three serves. What the proof does not permit is mismatching a current with a voltage from a different line — that step used the pairing explicitly.
AnswerAll three give \(P_T = 5543\ \text{W}\); the individual readings are permuted, so the \(W_1/W_2\) labelling must follow a stated convention
Problem 16Exam levelConnecting It Correctly

List the connection faults that corrupt a two-wattmeter measurement, and give the symptom by which each is recognised.

Solution

The correct connection, stated precisely:

RequirementDetail
Current coilIn series with its line, carrying the full line current
Pressure coilFrom that same line to the common line
Polarity marksThe \(\pm\) terminals of both coils joined at the line side
Common lineThe same line for both meters

The faults and their symptoms:

FaultSymptomEffect on \(P_T\)
One coil reversedThat meter reads negative at good pfSum too low by \(2W\)
Both coils reversedNone — reads correctlyNone
Current and voltage from different linesReadings implausible; sum wrongArbitrary
Different common linesSum wrong, often badlyArbitrary
Pressure coil across a phase voltageSum is \(1/\sqrt3\) too lowFactor \(\sqrt3\)
Both meters on the same lineReadings identicalMeaningless

The second row is the trap: reversing both coils changes two signs, which cancel. A meter that appears correctly connected may have had both reversed by a previous user.

The prediction check. The most reliable safeguard is to predict the readings before connecting, as in Problem 4. Given an approximate load rating:

\[ W_1 + W_2 \approx P_{\text{nameplate}}, \qquad \frac{W_1}{W_2} \approx \text{value from expected pf} \]

A sum that is out by \(\sqrt3\), or a ratio wildly different from expectation, localises the fault immediately.

A worked diagnostic. A load known to be about 5.5 kW at roughly 0.8 lagging is measured, giving readings of 1571 W and −3971 W:

\[ \text{sum} = 1571 - 3971 = -2400\ \text{W} \quad\text{— clearly wrong} \]

But the magnitudes 1571 and 3971 are exactly those predicted in Problem 15. The diagnosis is a single reversed coil on the second meter; correcting the sign gives

\[ 1571 + 3971 = 5542\ \text{W}\;\checkmark \]

Note that a genuine negative reading (Problem 7) also occurs, so a negative value is not by itself evidence of a fault — the test is whether the sum is plausible.

Distinguishing a true negative from a reversal:

ObservationInterpretation
Sum is plausible, one reading negativeGenuine — pf below 0.5
Sum is implausible or negativeReversal — check polarity marks
Sum is \(1/\sqrt3\) of expectationPressure coil on the wrong voltage
Always predict before measuring. A wattmeter reading is a single number with no internal evidence of its own correctness, so the only check available is comparison with expectation. That is why Problem 4 — working forward from a known load — is a practical skill and not merely an exercise.
AnswerOne coil reversed gives a false negative; both reversed gives no symptom at all. A sum out by \(\sqrt3\) indicates a pressure coil on a phase rather than a line voltage.
Problem 17ChallengeChecking a Correction

The 28.8 kW load of Set 24 was corrected from 0.6 to 0.95 lagging on 400 V, reducing the line current from 69.28 A to 43.76 A. Show how the wattmeter readings change, and how the pair confirms the correction worked.

Solution

Before correction, \(\theta = 53.13°\), \(V_LI_L = (400)(69.28) = 27\,712\ \text{VA}\):

\[ W_1 = 27\,712\cos83.13° = 3315\ \text{W} \]
\[ W_2 = 27\,712\cos23.13° = 25\,484\ \text{W} \]
\[ P_T = 28\,799\ \text{W}, \qquad r = \frac{W_1}{W_2} = 0.130 \]

After correction, \(\theta = 18.19°\), \(V_LI_L = (400)(43.76) = 17\,504\ \text{VA}\):

\[ W_1 = 17\,504\cos48.19° = 11\,667\ \text{W} \]
\[ W_2 = 17\,504\cos(-11.81°) = 17\,133\ \text{W} \]
\[ P_T = 28\,800\ \text{W}, \qquad r = 0.681 \]

The comparison:

BeforeAfterChange
\(W_1\)3315 W11 667 W+252%
\(W_2\)25 484 W17 133 W−33%
\(P_T\)28.8 kW28.8 kWUnchanged
\(r = W_1/W_2\)0.1300.681Toward 1
Line current69.28 A43.76 A−37%

The three signatures of a successful correction:

\[ \text{(i) } P_T \ \text{unchanged} \qquad \text{(ii) } r \to 1 \qquad \text{(iii) } I_L \ \text{falls} \]

The first is the crucial one. A capacitor consumes no real power, so if \(P_T\) changed, something other than the correction has altered — the load itself, or the connection.

Resolving Problem 10's ambiguity. This is the field technique promised there. Add a known capacitance and observe:

Observation on adding COriginal load was
Readings converge (\(r \to 1\))Lagging
Readings diverge (\(r\) moves from 1)Leading — correction is making it worse

A definite answer from a single perturbation, using instruments already in place.

A warning about overcorrection. Continuing past unity power factor makes the load capacitive, and the readings begin to diverge again — with \(W_1\) now the larger. Since \(r\) passes through 1 and comes back, a single reading of \(r\) cannot distinguish 0.9 lagging from 0.9 leading; only the direction of travel can.

The pair of readings is a live power-factor indicator. Watching \(r\) approach unity as capacitor stages switch in is the classic way of tuning a bank by eye — and the constancy of the sum throughout is the proof that the capacitors are doing what they should and nothing else.
Answer\(W_1\) rises from 3315 to 11 667 W and \(W_2\) falls from 25 484 to 17 133 W, with \(P_T\) unchanged at 28.8 kW and \(r\) moving from 0.130 to 0.681
Problem 18Exam levelA Complete Measurement

A balanced three-wire load on 415 V, 50 Hz gives readings \(W_1 = 2.4\ \text{kW}\) and \(W_2 = 6.8\ \text{kW}\). Determine everything obtainable: \(P\), \(Q\), \(S\), power factor, line current, and the delta capacitance to correct to unity.

Solution

1Real power — the sum:

\[ P_T = 2.4 + 6.8 = 9.2\ \text{kW} \]

2Reactive power\(\sqrt3\) times the difference:

\[ Q_T = \sqrt3(6.8-2.4) = 1.732(4.4) = 7.621\ \text{kvar} \]

Positive, and \(W_2 > W_1\), so the load is lagging.

3Power factor:

\[ \tan\theta = \frac{7.621}{9.2} = 0.8284 \;\Longrightarrow\; \theta = 39.63° \]
\[ \cos\theta = 0.7702 \ \text{lagging} \]

4Apparent power:

\[ S = \sqrt{9.2^2 + 7.621^2} = \sqrt{84.64+58.08} = 11.947\ \text{kVA} \]

Check: \(P/S = 9.2/11.947 = 0.770\) ✓ agreeing with the power factor.

5Line current, from \(S = \sqrt3V_LI_L\):

\[ I_L = \frac{11\,947}{\sqrt3(415)} = 16.62\ \text{A} \]

6Correction to unity requires the capacitors to supply all of \(Q_T\):

\[ Q_C = 7621\ \text{var} \]
\[ C_\Delta = \frac{Q_C}{3\omega V_L^2} = \frac{7621}{3(314.16)(415)^2} = 46.96\ \mu\text{F per phase} \]

Using Set 24, Problem 17's delta formula. At unity power factor the readings would become equal at 4.6 kW each, and the line current would fall to \(9200/(\sqrt3\times415) = 12.80\ \text{A}\) — a 23% reduction.

What could not be determined from these measurements:

QuantityWhy not
Per-phase impedanceNeeds the connection — Problem 13
Whether the load is truly balancedAssumed; two meters cannot test it
Harmonic contentWattmeters read total \(P\) only

The second is worth dwelling on. Every step after the sum assumed balance, and Problem 12 showed the consequences of that assumption failing.

Two numbers yielded six quantities and a design. That efficiency is why the method survived the whole electromechanical era and remains the standard textbook treatment — but every quantity beyond the first rests on an assumption of balance that the measurement itself cannot verify.
Answer\(P = 9.2\ \text{kW}\), \(Q = 7.62\ \text{kvar}\), \(S = 11.95\ \text{kVA}\), pf = 0.770 lagging, \(I_L = 16.62\ \text{A}\), \(C_\Delta = 47\ \mu\text{F}\)
Problem 19ChallengeInstrument Errors

Identify the systematic errors in a wattmeter measurement, and show which of them the ratio method of Problem 9 escapes.

Solution

aPressure-coil burden. The pressure coil draws current, and where that current flows depends on the connection:

ConnectionCurrent coil also carriesError
Pressure coil on the load sideThe pressure-coil currentReads high by \(V^2/R_p\)
Pressure coil on the supply sideLoad current onlyReads high by \(I^2R_c\)

Choose whichever error is smaller: the first connection for low currents, the second for high ones — precisely the ammeter–voltmeter trade-off of Set 1.

A numerical instance. With \(V = 400\ \text{V}\), \(R_p = 10\ \text{k}\Omega\), \(I = 20\ \text{A}\), \(R_c = 0.05\ \Omega\):

\[ \frac{V^2}{R_p} = \frac{160\,000}{10\,000} = 16\ \text{W}, \qquad I^2R_c = 400(0.05) = 20\ \text{W} \]

Comparable here; at 200 A the second becomes 2 kW and the first connection is clearly preferable.

bPressure-coil inductance. The pressure coil is not purely resistive, so its current lags the voltage slightly by an angle \(\beta\). The meter then reads

\[ W_{\text{indicated}} = \frac{VI\cos(\theta-\beta)}{\cos\beta} \]

The error grows as the power factor worsens, and it is worst exactly where the two-wattmeter method is most needed. This is why low-power-factor wattmeters, with compensated pressure coils, exist as a separate instrument class.

cTransformer ratio and phase errors. At high voltage or current, instrument transformers are used, and each introduces both a ratio error and a small phase displacement — the latter again mattering most at low power factor.

Which errors the ratio method escapes:

ErrorAffects \(P_T = W_1+W_2\)Affects \(r = W_1/W_2\)
Common scale factor (CT/PT ratio)YesNo — cancels
Identical calibration error on bothYesNo — cancels
Different errors on the two metersYesYes
Phase error \(\beta\)YesYes
BurdenYesPartly

The ratio is immune to anything scaling both readings equally — which is the commonest instrumentation error, since both meters typically share the same transformer set.

The practical conclusion. A two-wattmeter installation of modest accuracy will give a power factor considerably better than its power measurement, because the power factor depends only on the ratio. Reporting "9.2 kW ± 3% at a power factor of 0.770 ± 0.005" is a perfectly consistent statement, though it looks odd at first sight.

Errors that are common to both instruments corrupt the power but not the power factor. That is a general principle of ratio measurements, and it is why bridge methods (Set 21, Problem 14) achieve accuracies that absolute measurements cannot — a null or a ratio depends on component matching rather than on absolute calibration.
AnswerBurden, pressure-coil inductance and transformer errors all corrupt \(P_T\). The ratio \(W_1/W_2\) — and hence the power factor — is immune to any error scaling both readings equally.
Problem 20ChallengePart 3 in Review

Sets 20 to 25 completed the sinusoidal steady state. Set out what was established, what was genuinely new, and what remains unaddressed in the whole treatment of AC so far.

Solution

The six sets, in one line each:

SetContentGenuinely new?
20 · Sinusoids and phasorsThe transform itselfYes — the whole method
21 · AC mesh and nodalSets 4–8 with impedancesOne item — ill-conditioning
22 · Theorems in frequency domainSets 9–14 with impedancesOne item — conjugate match
23 · Single-phase power\(P\), \(Q\), \(S\), power factorYes — all of it
24 · Three-phase powerStar, delta, balanceConstant power, rotating field
25 · Two-wattmeter methodMeasurementBlondel's theorem

The shape of the whole. One transform (Set 20) made two sets of transferred results almost free, because the transform was built to preserve Kirchhoff's laws and linearity. Genuine novelty appeared only where those two premises were insufficient:

\[ \text{Optimisation} \Rightarrow \text{conjugate match} \]
\[ \text{Products of signals} \Rightarrow P, Q, S \ \text{and the power factor} \]

Both are non-linear operations on the circuit variables — a maximisation and a multiplication — which is exactly why linearity did not carry them across.

The one idea running through everything is that phase, introduced in Set 20 as a bookkeeping device for time shifts, turns out to control energy:

Where phase appearsWhat it decides
Impedance angleThe split of \(S\) into \(P\) and \(Q\)
Conjugate matchWhether all available power is delivered
120° between sourcesWhether total power pulsates
30° line–phase shiftWhether two meters can measure three phases

The last is a small delight: a phase shift that seemed a mere nuisance in Set 24 became the mechanism of the measurement in Set 25.

The standing limitation. Everything assumed a single frequency in the steady state. Two omissions follow:

Not addressedGlimpsed in
How a circuit responds across frequencySet 21, Problem 16 (near resonance)
Non-sinusoidal signalsSet 23, Problem 18 (harmonics)
Transients in AC circuitsSets 18–19 were DC only

Each was met once and set aside. Each now becomes a subject in its own right.

What comes next. Treating \(\omega\) as a variable rather than a constant opens the second half of Part 3:

SetTopicQuestion answered
26–27Mutual inductance, transformersCoupled coils and voltage transformation
28Transfer functions, Bode plotsResponse across all frequencies
29Resonance, \(Q\), bandwidthWhy some frequencies are special
30Filters and scalingDesigning frequency selectivity
31–32Laplace transformTransients and steady state together
33–34Fourier series and transformArbitrary waveforms
35Two-port networksCircuits as black boxes
Part 3's power sequence ends here, and it ended where it began — with a product of two sinusoids. Set 23 formed \(vi\) and found two quantities where DC had one; Set 25 built an instrument that forms the same product mechanically and reads its average off a dial. Everything between was working out what the two quantities mean and how to arrange three of them so the awkward one cancels.
AnswerOne transform made Sets 21–22 nearly free; genuine novelty arose only from optimisation (conjugate match) and from products of signals (\(P\), \(Q\), \(S\)). The standing limitation — one frequency, steady state — is lifted from Set 28 onward.
Practice

Practice Problems

Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not. Balanced lagging loads unless stated.

  1. P1. Readings are 3 kW and 5 kW. Find the total power.

    Show answer
    8 kW — the algebraic sum, valid for any load — Problem 1.
  2. P2. For the same readings, find \(Q_T\).

    Show answer
    \(Q_T = \sqrt3(5-3) = 3.46\) kvar — balanced load assumed — Problem 11.
  3. P3. And the power factor?

    Show answer
    \(\tan\theta = 3.46/8 = 0.433\), \(\theta = 23.4°\), pf = 0.918 lagging — Problem 5.
  4. P4. Two wattmeters read equally. What is the power factor?

    Show answer
    Unity — the difference is zero, so \(Q = 0\) — Problem 8.
  5. P5. One wattmeter reads zero. What is the power factor?

    Show answer
    Exactly 0.5, since \(\cos(\theta+30°) = 0\) needs \(\theta = 60°\) — Problem 8.
  6. P6. How many wattmeters for a four-wire unbalanced system?

    Show answer
    Three, by Blondel's \(n-1\) — Problems 1 and 3.
  7. P7. A load has \(\theta = 45°\) at \(V_LI_L = 2000\ \text{VA}\). Find both readings.

    Show answer
    \(W_1 = 2000\cos75° = 518\) W; \(W_2 = 2000\cos15° = 1932\) W — Problem 4.
  8. P8. Readings are −500 W and 2500 W. Find \(P_T\) and comment.

    Show answer
    \(P_T = 2000\) W. The negative reading means pf < 0.5 — Problem 7.
  9. P9. Both meters have their coils reversed. What is the effect?

    Show answer
    None — two sign changes cancel, and the readings are correct — Problem 16.
  10. P10. For an unbalanced load, which of \(P_T\), \(Q_T\) and pf can the two meters give?

    Show answer
    Only \(P_T\). The others require balance — Problem 12.
  11. P11. The ratio \(W_1/W_2 = 0.5\). Find the power factor.

    Show answer
    \(\tan\theta = \sqrt3(0.5)/(1.5) = 0.577\), so \(\theta = 30°\) and pf = 0.866 — Problem 9.
  12. P12. How would you measure \(Q\) with a single wattmeter?

    Show answer
    Current coil in one line, pressure coil across the other two lines; then \(Q_T = \sqrt3W\) — Problem 11.
Challenge

Challenge Problems

Each needs an idea rather than a formula. Decide what the governing principle is before opening the answer.

  1. C1. A 415 V three-wire supply feeds a factory. Two wattmeters read \(W_1 = -1.8\ \text{kW}\) and \(W_2 = 9.4\ \text{kW}\). Determine the load's condition, decide whether the negative reading indicates a fault, and design a delta capacitor bank to bring the power factor to 0.9 lagging — then predict the new readings.

    Show answer
    Is the negative reading a fault? Test the sum for plausibility first (Problem 16):
    \[ P_T = -1800 + 9400 = 7600\ \text{W} \]
    A positive, sensible total for a factory supply — so the reading is genuine, not a reversed coil. A reversal would have given an implausible or negative sum.

    The load's condition:
    \[ \tan\theta = \sqrt3\,\frac{9400-(-1800)}{7600} = \sqrt3\,\frac{11\,200}{7600} = 2.5527 \]
    \[ \theta = 68.61° \;\Longrightarrow\; \text{pf} = 0.3648 \ \text{lagging} \]
    Below 0.5, which is exactly why \(W_1\) went negative — consistent, and a useful cross-check on the arithmetic.
    \[ Q_T = \sqrt3(11\,200) = 19\,399\ \text{var}, \qquad S = \sqrt{7600^2+19\,399^2} = 20\,836\ \text{VA} \]
    \[ I_L = \frac{20\,836}{\sqrt3(415)} = 28.99\ \text{A} \]
    This is a badly under-loaded installation — 20.8 kVA of supply capacity carrying 7.6 kW of useful work. Typically lightly loaded induction motors running on no-load.

    The capacitor bank. Target \(Q_2 = 7600\tan25.84° = 3681\) var:
    \[ Q_C = 19\,399 - 3681 = 15\,718\ \text{var} \]
    \[ C_\Delta = \frac{15\,718}{3(314.16)(415)^2} = 96.8\ \mu\text{F per phase} \]
    The new readings. With \(\theta = 25.84°\) and \(S_{\text{new}} = 7600/0.9 = 8444\ \text{VA}\), so \(V_LI_L = S/\sqrt3 = 4875\):
    \[ W_1 = 4875\cos55.84° = 2737\ \text{W}, \qquad W_2 = 4875\cos(-4.16°) = 4862\ \text{W} \]
    \[ \text{sum} = 7600\ \text{W}\;\checkmark \ \text{unchanged} \]
    BeforeAfter
    \(W_1\)−1.8 kW+2.74 kW
    \(W_2\)9.4 kW4.86 kW
    pf0.3650.900
    \(I_L\)28.99 A11.75 A
    Line loss100%16.4%
    The most striking figure is the last: line losses fall to a sixth. At such a poor starting power factor, correction is exceptionally worthwhile — and the negative reading turning positive is the visible confirmation that it has worked.
  2. C2. Show that the two-wattmeter method reads correctly in the presence of harmonics, and explain why the power-factor formula then fails even for a perfectly balanced load.

    Show answer
    The sum still works. Problem 1's proof used only KCL and the definition of average power — neither assumes a sinusoid:
    \[ p(t) = \sum_{k=1}^{2} v_{kn}(t)i_k(t) \quad\text{holds instant by instant} \]
    A wattmeter's inertia averages whatever it is given, so
    \[ W_1 + W_2 = \overline{p(t)} = P_T \]
    exactly, for any waveform whatever. This is one of the method's great practical strengths: it remains valid on the distorted currents drawn by rectifiers and drives, where a calculation based on \(\sqrt3V_LI_L\cos\phi\) would be meaningless.

    Why the power-factor formula fails. Problem 2 derived it from a specific phasor geometry: one frequency, and a definite \(\pm30°\) between line voltages and phase voltages. With harmonics present there is no single \(\theta\) to find — Set 23, Problem 18 showed the power factor splits into a displacement factor and a distortion factor:
    \[ \text{pf} = \underbrace{\cos\theta_1}_{\text{displacement}} \times \underbrace{\frac{I_1}{I_{rms}}}_{\text{distortion}} \]
    The wattmeter difference responds only to the fundamental's quadrature component, so \(\sqrt3(W_2-W_1)\) gives the fundamental reactive power — not the total, and not anything from which the true power factor can be recovered.

    The trap this creates. On a modern installation full of switched-mode supplies:
    QuantityFrom two wattmetersCorrect?
    \(P_T\)SumYes, exactly
    Fundamental \(Q\)\(\sqrt3(W_2-W_1)\)Yes
    True pf\(P_T/S\) — needs a true-RMS ammeterOnly with extra instruments
    pf from \(\tan\theta\) formulaNo — reads too high
    The formula flatters the installation, reporting only the displacement factor and ignoring the distortion factor — so it overstates the power factor precisely where the distortion is worst. A true-RMS ammeter and voltmeter, giving \(S = \sqrt3V_{rms}I_{rms}\) and hence \(\text{pf} = P_T/S\), is the correct approach.

    The general lesson. The sum rests on conservation and survives everything; the difference rests on geometry and survives only what preserves that geometry. Whenever a result is used beyond the conditions of its derivation, it is worth asking which of the two kinds it is.
  3. C3. Two wattmeters are connected to a balanced load but the phase sequence is reversed from what was assumed. Show what happens to the readings, and explain how this could be mistaken for a leading power factor.

    Show answer
    Set up with negative (acb) sequence:
    \[ \mathbf{V}_{an} = V_{ph}\angle0°, \quad \mathbf{V}_{bn} = V_{ph}\angle{+120°}, \quad \mathbf{V}_{cn} = V_{ph}\angle{-120°} \]
    The line voltage now becomes
    \[ \mathbf{V}_{ab} = \mathbf{V}_{an}-\mathbf{V}_{bn} = V_L\angle{-30°} \]
    lagging its phase voltage by 30° instead of leading it. Every 30° in the derivation changes sign.

    The readings become
    \[ W_1 = V_LI_L\cos\left(\theta-30°\right), \qquad W_2 = V_LI_L\cos\left(\theta+30°\right) \]
    which is the original pair exchanged.

    The consequences:
    QuantityEffect of reversed sequence
    \(P_T = W_1+W_2\)Unchanged — addition is commutative
    \(W_2-W_1\)Sign reversed
    Deduced \(\theta\)Sign reversed
    Deduced characterLagging reported as leading
    A numerical instance. A lagging load at pf 0.8 with \(V_LI_L = 1000\): correct sequence gives \(W_1 = 393\), \(W_2 = 993\) W, reporting \(\theta = +36.87°\) lagging. Reversed sequence gives \(W_1 = 993\), \(W_2 = 393\) W, reporting \(\theta = -36.87°\)leading. Both give \(P_T = 1386\) W.

    Why this is genuinely dangerous. An installation diagnosed as leading would have inductors fitted to correct it, driving the true power factor further from unity rather than towards it — and the readings would diverge, appearing to confirm the wrong diagnosis until someone checked the current.

    How to detect it. A phase-sequence indicator (Set 24, Problem 2) before connecting, or the perturbation test of Problem 17: add a small capacitance and see whether the line current falls. Current is a scalar magnitude and carries no sequence information, so it cannot be fooled.

    The unifying point. This is the third appearance of the same ambiguity — Problem 10 (unlabelled meters), Problem 15 (choice of common line), and now sequence reversal. All three exchange \(W_1\) and \(W_2\), all three leave \(P_T\) untouched, and all three flip the reported character of the load. The sum is robust; the difference depends on conventions that must each be independently established.
MCQ

Multiple-Choice Questions

Twelve questions in GATE/ESE style. Commit to an answer before opening the explanation.

  1. Q1. Blondel's theorem states that an \(n\)-wire system needs

    (a) \(n\) wattmeters   (b) \(n-1\)   (c) \(n+1\)   (d) 2 always

    Show answer
    (b) — one current is determined by the others through KCL — Problem 1.
  2. Q2. The total power from two wattmeters is valid for

    (a) balanced loads only   (b) star loads only   (c) any three-wire load   (d) sinusoidal supplies only

    Show answer
    (c). The proof used only KCL, so balance, connection and waveform are all irrelevant — Problems 1 and 12.
  3. Q3. The 30° in \(W_1 = V_LI_L\cos(\theta+30°)\) comes from

    (a) the impedance angle   (b) the line–phase voltage shift   (c) the 120° source spacing   (d) instrument calibration

    Show answer
    (b) — the meter compares a line voltage with a line current — Problem 2.
  4. Q4. One wattmeter reads zero. The power factor is

    (a) 0   (b) 0.5   (c) 0.866   (d) 1.0

    Show answer
    (b), since \(\cos(\theta+30°) = 0\) requires \(\theta = 60°\) — Problem 8.
  5. Q5. Equal readings indicate

    (a) a balanced load   (b) unity power factor   (c) a star connection   (d) zero reactive power in one phase

    Show answer
    (b). Note (a) is wrong — balance is assumed before the formula is used, not deduced from it — Problem 8.
  6. Q6. A negative reading means

    (a) a wiring fault   (b) power factor below 0.5   (c) a leading load   (d) an unbalanced load

    Show answer
    (b), provided the sum is plausible — otherwise suspect a reversed coil — Problems 7 and 16.
  7. Q7. Reactive power from the readings is

    (a) \(W_2-W_1\)   (b) \(\sqrt3(W_2-W_1)\)   (c) \(3(W_2-W_1)\)   (d) \((W_2-W_1)/\sqrt3\)

    Show answer
    (b), for a balanced load only — Problems 11 and 12.
  8. Q8. For an unbalanced three-wire load, two wattmeters give

    (a) \(P\) only   (b) \(P\) and \(Q\)   (c) nothing useful   (d) \(P\), \(Q\) and pf

    Show answer
    (a). The sum is exact; the difference is meaningless — Problem 12.
  9. Q9. Reversing both coils of one wattmeter

    (a) reverses its reading   (b) doubles it   (c) has no effect   (d) gives zero

    Show answer
    (c) — two sign changes cancel, which is why this fault is invisible — Problem 16.
  10. Q10. To measure \(Q\) with one wattmeter, the pressure coil goes

    (a) line to neutral   (b) across the other two lines   (c) across its own line pair   (d) in series with the load

    Show answer
    (b) — that voltage is in quadrature, turning the cosine into a sine — Problem 11.
  11. Q11. Which quantity is unaffected by an error scaling both readings equally?

    (a) \(P_T\)   (b) \(Q_T\)   (c) the power factor   (d) the line current

    Show answer
    (c) — it depends only on the ratio \(W_1/W_2\) — Problems 9 and 19.
  12. Q12. Reversing the phase sequence with a lagging load causes the readings to

    (a) both go negative   (b) exchange, so the load appears leading   (c) both halve   (d) become equal

    Show answer
    (b). \(P_T\) is unchanged, but the deduced character is wrong — Challenge C3.
Formulas

Key Formulas

All values RMS; balanced positive sequence unless the validity column says otherwise.

QuantityRelationValid for
Blondel's theorem\(n-1\) wattmeters for \(n\) wiresAny load
Total power\(P_T = W_1+W_2\)Any three-wire load
Reading 1\(W_1 = V_LI_L\cos(\theta+30°)\)Balanced
Reading 2\(W_2 = V_LI_L\cos(\theta-30°)\)Balanced
Reactive power\(Q_T = \sqrt3(W_2-W_1)\)Balanced
Power factor\(\tan\theta = \sqrt3\dfrac{W_2-W_1}{W_2+W_1}\)Balanced
Ratio form\(\tan\theta = \sqrt3\dfrac{1-r}{1+r}\), \(r = W_1/W_2\)Balanced; scale-free
Single-meter \(Q\)\(Q_T = \sqrt3W\), coil across the other two linesBalanced
Three-wattmeter\(P_T = \sum\operatorname{Re}(\mathbf{V}_k\mathbf{I}_k^{*})\)Any four-wire load
pf\(\theta\)Signature
1.000\(W_1 = W_2\)
0.86630°\(W_1 = \tfrac12W_2\); \(W_2\) is at its maximum
0.50060°\(W_1 = 0\)
\(<0.5\)\(>60°\)\(W_1 < 0\)
0.00090°\(W_1 = -W_2\), sum zero
Pitfalls

Common Mistakes

  1. Using the power-factor formula on an unbalanced load. The sum stays exact while the difference becomes meaningless — so nothing warns you — Problem 12.

  2. Adding the magnitude of a negative reading. The total is the algebraic sum; a reversed meter's reading must be subtracted — Problem 7.

  3. Treating a negative reading as a fault. Below 0.5 power factor it is correct behaviour; test the plausibility of the sum instead — Problems 7 and 16.

  4. Reporting the readings as an unordered pair. Which meter is \(W_1\) determines lagging from leading — Problem 10.

  5. Reversing both coils when only one needs reversing — the two sign changes cancel — Problem 16.

  6. Pairing a current with a voltage from a different line. The proof used the pairing explicitly — Problem 15.

  7. Using different common lines for the two meters. One reference conductor for both — Problem 15.

  8. Dividing \(P_T\) by three for an unbalanced load. The phases do not share equally — Problems 6 and 12.

  9. Deducing a per-phase impedance without knowing the connection. Star and delta differ by three — Problem 13.

  10. Applying \(\tan\theta\) to a distorted waveform. The sum is still exact, but there is no single \(\theta\) — Challenge C2.

Looking Ahead

Two instruments measure the power of any three-wire three-phase load, and the proof needs nothing beyond Kirchhoff's current law — which is why the sum survives imbalance, unknown connections and harmonic distortion alike. For a balanced load the pair gives more: their difference yields the reactive power, their ratio the power factor, and the 30° line–phase shift that Set 24 derived for its own sake turns out to be the mechanism that makes it possible. The limitation is equally sharp. Everything beyond the sum rests on balanced phasor geometry, and Problem 12 showed the power-factor formula returning an answer wrong in sign while the total remained exact to the last digit.

That closes Part 3's power sequence. Sets 20 to 25 have treated the sinusoidal steady state completely — but always at a single frequency, with \(\omega\) held fixed and the transients of Sets 18 and 19 long decayed. Two questions have been deferred throughout: how a circuit behaves as the frequency varies, and what happens when two coils share a magnetic field rather than an electrical connection.

Next: Set 26 — Mutual Inductance, where a changing current in one coil induces a voltage in another with no conducting path between them. The dot convention, coupling coefficient and coupled-circuit analysis follow, and they lead directly into transformers in Set 27 and the frequency-domain work that occupies the rest of Part 3.