Set 25 — The Two-Wattmeter Method
Set 24 closed with a measurement problem. A wattmeter reads the average of \(vi\) across one pair of terminals, so measuring three-phase power looks as though it needs three of them — and a neutral connection that a three-wire system does not offer. But with no neutral the three line currents are forced to sum to zero, so one is determined by the other two and only two independent measurements can exist. This set derives the method, works it in both directions, and marks carefully where it stops being valid.
The connection. Each wattmeter carries one line current in its current coil and the voltage from that line to a common third line across its pressure coil. With line B as the common reference, \(W_1\) reads \(\mathbf{V}_{AB}\) with \(\mathbf{I}_A\), and \(W_2\) reads \(\mathbf{V}_{CB}\) with \(\mathbf{I}_C\).
For a balanced load, with \(\theta\) the impedance angle:
\[ W_1 = V_LI_L\cos\left(\theta+30°\right), \qquad W_2 = V_LI_L\cos\left(\theta-30°\right) \]Sum and difference:
\[ P_T = W_1 + W_2 = \sqrt3\,V_LI_L\cos\theta \]\[ Q_T = \sqrt3\left(W_2-W_1\right) = \sqrt3\,V_LI_L\sin\theta \]Power factor from the readings alone:
\[ \tan\theta = \sqrt3\,\frac{W_2-W_1}{W_2+W_1} \]The sum is always valid — balanced or not, star or delta — by Blondel's theorem. The power-factor formula is valid only for a balanced load, as Problem 12 shows.
Below 0.5 power factor (\(\theta > 60°\)) the smaller reading goes negative and its meter must be reversed, the reading then being subtracted.
Convention: RMS values throughout; positive (abc) sequence and lagging loads unless stated.
Prove that the power delivered through an \(n\)-wire system can always be measured with \(n-1\) wattmeters, and show the result does not depend on balance, connection, or waveform.
Start from the instantaneous power crossing the boundary into the load. With all voltages measured from an arbitrary reference point \(o\):
This is exact — it is just the definition of power flow, with no assumption yet made about the load.
Apply KCL to the whole load. Charge cannot accumulate inside it, so
One current is redundant. This is the entire content of the theorem.
Choose the reference to be conductor \(n\) itself, so \(v_{no} = 0\):
The \(n\)th term vanishes because its voltage is zero by construction, not because its current is. There are now \(n-1\) terms, each a voltage times a current — exactly what one wattmeter measures.
Averaging gives the readings:
What the proof did not assume:
| Not assumed | Consequence |
|---|---|
| Balanced load | Works for any imbalance — Problem 12 |
| Star or delta | Works for either, or a mixture |
| Sinusoidal waveform | Works with harmonics — Set 23, Problem 18 |
| Balanced source | Works for any source |
| A particular reference conductor | Any of the \(n\) may be chosen — Problem 15 |
Only KCL and the definition of average power were used, which is why the result is so robust.
The practical cases:
| System | \(n\) | Wattmeters |
|---|---|---|
| Single-phase | 2 | 1 |
| Three-phase, three-wire | 3 | 2 |
| Three-phase, four-wire | 4 | 3 |
Note the four-wire case needs three — the neutral breaks the constraint that made two sufficient, because the three line currents no longer sum to zero.
Derive \(W_1 = V_LI_L\cos(\theta+30°)\) and \(W_2 = V_LI_L\cos(\theta-30°)\) for a balanced load, and show where the 30° comes from.
Set up. Positive sequence, phase voltages referred to the neutral, load impedance \(|\mathbf{Z}|\angle\theta\):
The two line voltages, using Set 24, Problem 3:
Note \(\mathbf{V}_{cb} = -\mathbf{V}_{bc}\), which is why the second meter is connected C-to-B rather than B-to-C — reversing it would make \(W_2\) read negative for every load.
Each wattmeter reads \(\operatorname{Re}\left(\mathbf{V}\mathbf{I}^{*}\right)\) — Set 23, Problem 17:
Where the 30° comes from. Each meter compares a line voltage with a line current. But the impedance angle \(\theta\) relates the phase voltage to that current, and the line voltage leads the phase voltage by 30°:
One meter picks up \(+30°\) and the other \(-30°\) because their line voltages sit on opposite sides of their currents. The shift derived in Set 24 for its own sake is exactly what makes the method work.
Sum and difference by the standard identities:
Numerical confirmation. Taking \(V_{ph} = 100\ \text{V}\), \(I_L = 10\ \text{A}\), \(\theta = 36.87°\), computing directly from the phasors gives \(W_1 = 680.4\ \text{W}\) and \(W_2 = 1719.6\ \text{W}\), matching the formulas exactly; their sum is 2400.0 W, and \(\sqrt3(W_2-W_1) = 1800.0\ \text{var}\), both agreeing with \(\sqrt3V_LI_L\cos\theta\) and \(\sqrt3V_LI_L\sin\theta\).
An unbalanced four-wire load has \(\mathbf{V}_{AN} = 100\angle0°\), \(\mathbf{V}_{BN} = 100\angle120°\), \(\mathbf{V}_{CN} = 100\angle{-120°}\ \text{V}\) and line currents \(\mathbf{I}_a = 6.67\angle0°\), \(\mathbf{I}_b = 8.94\angle93.44°\), \(\mathbf{I}_c = 10\angle{-66.87°}\ \text{A}\). Find the total power absorbed.
Why three wattmeters here. The neutral is accessible, so \(n = 4\) and Blondel requires \(n-1 = 3\). Each meter measures one phase directly, referred to the neutral — the two-wattmeter method does not apply.
Note also that \(\mathbf{V}_{BN}\) leads and \(\mathbf{V}_{CN}\) lags, so this is negative (acb) sequence. That makes no difference to the arithmetic, since the currents are given rather than derived.
Each reading is the real part of voltage times conjugate current:
The total:
Note the three power factors differ:
| Phase | Angle | pf | Character |
|---|---|---|---|
| A | 0° | 1.00 | Resistive |
| B | 26.56° | 0.894 | Lagging |
| C | −53.13° | 0.600 | Leading |
Three different loads on three phases — which is exactly the situation a four-wire system exists to accommodate, and exactly why each phase must be metered separately.
The neutral current, for completeness:
Non-zero because the load is unbalanced, and it is precisely this that destroys the constraint \(\sum i_k = 0\) over the three lines and so forbids the two-wattmeter method.
A shortcut when the neutral is available. If only the total is wanted and the load impedances are known, \(P_T = \sum|\mathbf{I}_k|^2R_k\) avoids all the angles. Here the angles were given rather than the impedances, so the direct route was the shorter one.
A balanced star load of \(\mathbf{Z}_Y = (8+j6)\ \Omega\) per phase is connected to 208 V lines. Predict \(W_1\) and \(W_2\), and find \(P_T\) and \(Q_T\).
The impedance angle is the power-factor angle:
Line current — star, so it equals the phase current:
The two readings:
\(W_2 > W_1\), confirming a lagging load — consistent with the \(+j6\) in the impedance. Note how unequal they are: a 2.5:1 ratio at a perfectly ordinary 0.8 power factor.
Total real and reactive power:
Check both against Set 24's formulas:
The second is the more convincing check, since it uses the reactance directly and involves no wattmeter theory at all.
Why prediction is worth practising. Working forward from a known load to the expected readings is how a measurement is verified — if the instruments disagree with the prediction, either the connection is wrong or the load is not what it was assumed to be. Problem 16 lists the connection faults this catches.
Two wattmeters on a balanced load read \(W_1 = 460\ \text{W}\) and \(W_2 = 920\ \text{W}\). Find the total power and the power factor, assuming a lagging load.
Total power is the algebraic sum:
The power-factor angle from the ratio of difference to sum:
Why the formula needs no voltage or current. Both readings contain the factor \(V_LI_L\), which cancels in the ratio:
So the power factor is obtained from the two readings alone — no voltmeter, no ammeter, and no knowledge of the load's connection.
The reactive power follows too:
Confirming \(\text{pf} = P/S = 1380/1594 = 0.866\) ✓ — the two routes to the power factor agree.
A memorable special case. Here \(W_2 = 2W_1\) exactly, and the answer came out at exactly 30°. That is worth remembering as a calibration point:
Problem 9 develops the ratio into a general method.
Two wattmeters on a delta-connected load read \(W_1 = 1560\ \text{W}\) and \(W_2 = 2100\ \text{W}\) at a line voltage of 220 V. Find the per-phase real and reactive powers, the power factor, and the phase impedance.
Total and per-phase real power:
Total and per-phase reactive power:
Dividing by three is legitimate here because the load is balanced — each phase carries an equal share. Problem 12 shows what happens when it is not.
Power factor:
Now use the delta connection. The phase voltage equals the line voltage:
The phase impedance:
Check via the phase powers directly:
Note the essential extra information. The wattmeter readings alone gave \(P_T\), \(Q_T\) and the power factor — but the impedance required two further facts: the line voltage, and the knowledge that the load is delta. Had it been star, the same readings would give
The measurement cannot distinguish the two, since Set 24, Problem 6 showed they are indistinguishable from the terminals.
A balanced load runs at 0.4 power factor lagging on 415 V with a line current of 12 A. Find the two readings, verify the total, and explain the sign.
The angle:
Already above 60°, which is the threshold Problem 8 identifies.
The readings, with \(V_LI_L = (415)(12) = 4980\ \text{VA}\):
Why \(W_1\) is negative. Its argument \(\theta+30°\) has passed 90°, so the cosine turns negative:
The voltage across that meter's pressure coil and the current in its current coil are more than 90° apart, so the average of their product is negative — the meter's element is returning power in the accounting sense, though nothing physically flows backwards.
The total is still the algebraic sum:
What to do in practice. A moving-coil wattmeter cannot deflect below zero — the pointer simply drives against its stop, which can damage the movement:
| Step | Action |
|---|---|
| 1 | Reverse the connections to one coil — usually the pressure coil |
| 2 | Read the now-positive deflection |
| 3 | Subtract it rather than adding |
Reversing both coils restores the original negative reading, since two sign changes cancel — a classic laboratory error.
The diagnostic value. A negative reading is not a fault but information: it says immediately that the power factor is below 0.5, without any calculation. On a large motor that would prompt an investigation — a lightly loaded induction motor runs at very poor power factor, and correcting it (Set 24, Problem 17) would show up as the negative reading returning to positive.
Map the behaviour of the two readings across the whole range of power factor from unity to zero, and identify every landmark.
Normalise by taking \(V_LI_L = 1000\ \text{VA}\), so the readings are directly comparable:
| pf | \(\theta\) | \(W_1\) | \(W_2\) | \(W_1/W_2\) | \(P_T\) |
|---|---|---|---|---|---|
| 1.000 | 0° | 866 | 866 | 1.000 | 1732 |
| 0.966 | 15° | 707 | 966 | 0.732 | 1673 |
| 0.866 | 30° | 500 | 1000 | 0.500 | 1500 |
| 0.707 | 45° | 259 | 966 | 0.268 | 1225 |
| 0.500 | 60° | 0 | 866 | 0.000 | 866 |
| 0.400 | 66.4° | −112 | 805 | −0.139 | 693 |
| 0.200 | 78.5° | −317 | 663 | −0.478 | 346 |
| 0.000 | 90° | −500 | 500 | −1.000 | 0 |
The four landmarks:
| Condition | pf | Signature |
|---|---|---|
| \(W_1 = W_2\) | 1.0 | Unity power factor — purely resistive |
| \(W_1 = \tfrac12W_2\) | 0.866 | \(\theta = 30°\) — Problem 5's case |
| \(W_1 = 0\) | 0.5 | One meter reads zero |
| \(W_1 = -W_2\) | 0 | Purely reactive — readings cancel |
Notice \(W_2\) is not monotonic. It peaks at \(\theta = 30°\), where its argument \(\theta-30°\) is zero:
So the larger reading actually rises as the power factor falls from 1.0 to 0.866, then falls thereafter. Only \(W_1\) decreases throughout — which is why it is \(W_1\) that carries the diagnostic information.
The zero-power-factor case is a useful sanity check. With a purely reactive load the readings are equal and opposite, so
as it must be — no real power is consumed. Yet each meter shows a substantial deflection, and each carries full line current. A wattmeter reading zero total does not mean the instruments are idle, exactly as in Set 23, Problem 17.
A useful bound. Since \(|\cos| \le 1\), neither reading can exceed \(V_LI_L\), while the total reaches \(\sqrt3V_LI_L\) at unity power factor. So each meter must be rated for the full \(V_LI_L\) even though it never reads more than \(1/\sqrt3\) of the maximum total.
Express the power factor in terms of the ratio \(r = W_1/W_2\) alone, and show why this form is often more convenient.
Start from the standard formula and divide numerator and denominator by \(W_2\):
Verify at three points:
| \(r\) | \(\tan\theta\) | \(\theta\) | pf |
|---|---|---|---|
| 1.000 | 0 | 0° | 1.000 |
| 0.500 | 0.5774 | 30° | 0.866 |
| 0.000 | 1.7321 | 60° | 0.500 |
| −0.139 | 2.2913 | 66.4° | 0.400 |
| −1.000 | \(\infty\) | 90° | 0.000 |
Each row confirms the corresponding row of Problem 8's table.
Why the ratio form is convenient:
| Advantage | Detail |
|---|---|
| Scale-independent | Instrument multiplying factors cancel |
| Units-independent | Works with readings in W, kW, or arbitrary scale divisions |
| Immune to common errors | A CT or PT ratio error affecting both meters equally cancels |
| Single input | One number determines the power factor completely |
The third is the practically important one: if both wattmeters share a current transformer of uncertain ratio, the ratio method still gives the correct power factor even though neither reading is trustworthy in absolute terms.
A worked instance. Two meters read 35 and 87 scale divisions on identical instruments:
No scale factor was needed. To obtain \(P_T\) as well, the multiplier would then have to be applied — the ratio gives the power factor for free, but not the power.
A caution on the sign of \(r\). When \(W_1\) is negative, \(r\) is negative and the formula still holds — but the reading must be entered with its sign. Entering a reversed meter's reading as positive gives a badly wrong power factor, and is the commonest error in the low-power-factor case.
Two wattmeters read 120 W and 920 W, but it is not recorded which is \(W_1\). Show that the power factor magnitude is determined but its character is not, and explain how to resolve the ambiguity.
The total is unambiguous:
Addition is commutative, so the labelling does not matter for the power.
The power factor magnitude is also unambiguous. Taking the two assignments in turn:
Same magnitude, opposite sign — one is a lagging load and the other leading, and the readings alone cannot tell them apart.
The general rule follows from the derivation:
| Character | Sign of \(\theta\) | Which reading is larger |
|---|---|---|
| Inductive (lagging) | \(+\) | \(W_2 > W_1\) |
| Resistive | 0 | Equal |
| Capacitive (leading) | \(-\) | \(W_1 > W_2\) |
Swapping a leading load for a lagging one of the same power factor simply exchanges the two readings — which is exactly why the identity of the meters must be recorded.
Three ways to resolve it:
| Method | Detail |
|---|---|
| Record which meter is which | Best — the ambiguity never arises |
| Know the load | Motors, transformers and most industry are lagging |
| Add capacitance and observe | If the readings converge, it was lagging; if they diverge, leading |
The third is a genuine field technique — Problem 17 works it through. It resolves the ambiguity by perturbing the system in a known direction.
The deeper point. This is the same ambiguity as Set 23, Problem 16: \(\cos\theta\) is an even function, so no measurement of a cosine can recover a sign. The wattmeter pair does encode the sign — in which meter reads higher — but that information is lost the moment the readings are written down as an unlabelled pair.
Show why the difference of the readings gives reactive power, and derive the related single-wattmeter method for measuring \(Q\) alone.
The difference, from Problem 2:
Why the \(\pm30°\) produces a sine. The identity
converts a difference of cosines into a product of sines. The sum did the reverse, giving \(2\cos\theta\cos30°\). So one combination extracts \(\cos\theta\) and the other \(\sin\theta\) — the two meters between them resolve the load's complex power into its rectangular components.
The single-wattmeter method for \(Q\). Connect one wattmeter with its current coil in line A but its pressure coil across \(\mathbf{V}_{bc}\) — the voltage between the other two lines:
One instrument, connected "across the other two lines", reads reactive power directly. This is the cross-connection or varmeter arrangement.
Why it works. \(\mathbf{V}_{bc}\) is in quadrature with \(\mathbf{V}_{an}\) — it lags by 90°:
| Phasor | Angle |
|---|---|
| \(\mathbf{V}_{an}\) | 0° |
| \(\mathbf{V}_{bc}\) | −90° |
Feeding a wattmeter with a voltage in quadrature to the one that defines \(\theta\) turns its cosine into a sine — which is the definition of reactive power. The three-phase system supplies that quadrature voltage for free, which a single-phase system cannot do without a phase-shifting network.
A worked check. For the load of Problem 4 — \(V_L = 208\), \(I_L = 12.01\), \(\theta = 36.87°\):
Matching the two-wattmeter result exactly — and note that 1499 is precisely \(W_2-W_1\) from that problem, as it must be.
For the unbalanced three-wire star load of Set 24, Problem 15 — \(\mathbf{Z}_A = 10\), \(\mathbf{Z}_B = 10+j10\), \(\mathbf{Z}_C = 20\ \Omega\) on 400 V — compute the two wattmeter readings, and test both the sum and the power-factor formula against the true values.
Recover the currents from Set 24, Problem 15, where Millman's theorem gave a star-point displacement of \(28.99\angle89.04°\ \text{V}\):
These sum to zero, as a three-wire system requires.
The true powers, computed element by element:
Only phase B has reactance, so it alone contributes to \(Q\).
The wattmeter readings, with line B as the common reference:
Test the sum:
Exact. Blondel's theorem holds to the last digit, exactly as Problem 1 promised — no assumption of balance was ever made.
Now test the power-factor formula:
Wrong by a factor of more than two — and wrong in sign. The formula reports a strongly capacitive load where the true load is inductive.
Why the sum survives and the difference does not. The sum was derived from KCL alone. The difference was derived from the specific phasor relationships of a balanced load — equal current magnitudes, equal angles, and the exact \(\pm30°\) pattern:
| Result | Derived from | Valid unbalanced? |
|---|---|---|
| \(P_T = W_1+W_2\) | KCL only | Yes |
| \(Q_T = \sqrt3(W_2-W_1)\) | Balanced phasor geometry | No |
| \(\tan\theta = \sqrt3\frac{W_2-W_1}{W_2+W_1}\) | Both of the above | No |
| \(P_{ph} = P_T/3\) | Equal phase shares | No |
What to do instead. For an unbalanced load, the two wattmeters give \(P_T\) and nothing more. Obtaining \(Q\) or a meaningful power factor requires either three-wattmeter measurement with an artificial neutral, or full phasor instrumentation — and even then, "the power factor" of an unbalanced load is a quantity needing careful definition, since each phase has its own.
A balanced delta load of \(15\angle36.87°\ \Omega\) per phase runs on 415 V. Predict the wattmeter readings and confirm that the connection makes no difference to the method.
Delta quantities from Set 24, Problem 11:
The readings use line quantities — which is the whole point:
Matching Set 24, Problem 11's answer of 27.56 kW exactly.
Why the connection is irrelevant to the meters. The wattmeters are connected to the lines, and they see only line voltages and line currents. From outside, a delta of \(\mathbf{Z}\) and a star of \(\mathbf{Z}/3\) are indistinguishable — Set 24, Problem 6 — so they must give identical readings:
The same line current, hence the same readings.
What the meters cannot tell you. Given the readings and the line voltage, the per-phase impedance follows only once the connection is known:
| If the load is... | \(V_{ph}\) | \(I_{ph}\) | \(|\mathbf{Z}_{ph}|\) |
|---|---|---|---|
| Delta | 415 V | 27.67 A | 15 Ω |
| Star | 239.6 V | 47.92 A | 5 Ω |
Same measurements, same power, same power factor — three-to-one difference in the deduced impedance. This is Problem 6's point restated with numbers.
Verify the power factor from the readings:
Recovering the impedance angle exactly, which confirms both the readings and the formula.
Set out the circumstances under which a single wattmeter suffices for a three-phase measurement, and the arrangements used.
Blondel's theorem sets the floor at \(n-1\) instruments for a general load. A single wattmeter can only be enough if extra information — specifically, that the load is balanced — is supplied from outside the measurement.
aBalanced load with an accessible neutral. Measure one phase and multiply by three:
The simplest case, and valid only because balance guarantees the other two phases are identical.
bBalanced load, three-wire, artificial neutral. Create a neutral with two resistors equal to the wattmeter's pressure-coil resistance:
| Element | From | To |
|---|---|---|
| Pressure coil (resistance \(R_p\)) | Line A | Star point |
| Resistor \(R_p\) | Line B | Star point |
| Resistor \(R_p\) | Line C | Star point |
Three equal resistances in star place their common point at the true neutral potential — the balanced case of Set 24, Problem 15, where the Millman displacement vanishes. The meter then reads \(P_T/3\).
cThe two-reading method with one meter. Connect one wattmeter as \(W_1\), record the reading, then switch it to the \(W_2\) position and record again:
Valid only if the load is steady between the two readings — the measurements are no longer simultaneous. A fluctuating load makes this useless, which is the practical reason two meters are preferred.
dReactive power alone, by the cross-connection of Problem 11:
Summary of what each arrangement needs:
| Method | Meters | Requires | Gives |
|---|---|---|---|
| Three-wattmeter | 3 | Neutral access | \(P_T\), any load |
| Two-wattmeter | 2 | Nothing | \(P_T\) any load; \(Q\), pf if balanced |
| One + neutral | 1 | Balance + neutral | \(P_T\) |
| One + artificial neutral | 1 | Balance | \(P_T\) |
| One, switched | 1 | Steady load | \(P_T\) |
| Cross-connected | 1 | Balance | \(Q_T\) only |
The two-wattmeter method is the only row requiring no assumption about the load, which is why it is the standard.
Three choices of common reference line are possible. Show that all three give the same total, and that the individual readings differ. Use a balanced load at 0.8 lagging, 400 V, 10 A.
The three connections, each omitting one line from the pressure-coil references:
| Common line | Meter 1 | Meter 2 | Reading 1 | Reading 2 | Sum |
|---|---|---|---|---|---|
| B | \(\mathbf{V}_{AB},\mathbf{I}_A\) | \(\mathbf{V}_{CB},\mathbf{I}_C\) | 1571 W | 3971 W | 5543 W |
| C | \(\mathbf{V}_{AC},\mathbf{I}_A\) | \(\mathbf{V}_{BC},\mathbf{I}_B\) | 3971 W | 1571 W | 5543 W |
| A | \(\mathbf{V}_{BA},\mathbf{I}_B\) | \(\mathbf{V}_{CA},\mathbf{I}_C\) | 3971 W | 1571 W | 5543 W |
All three agree on the total, exactly as Problem 1's proof requires — the reference conductor was arbitrary throughout.
But the individual readings are permuted. The same pair of numbers appears in every row, in different orders. This matters because
depends on which is called \(W_1\). Rows 2 and 3 would give \(\theta = -36.87°\) — reporting a leading load — unless the labelling convention is applied consistently.
The convention that fixes it. With positive sequence and line B common, label so that
Equivalently: for a lagging load \(W_2 > W_1\) always. Since most industrial loads are lagging, assigning the larger reading to \(W_2\) is usually correct — but it assumes the answer, which is exactly the ambiguity of Problem 10.
Which line to choose in practice:
| Consideration | Preference |
|---|---|
| Convenience of access | Whichever line is easiest to reach |
| Existing current transformers | Use the lines that already have CTs |
| Unbalanced load | Any — the sum is valid regardless |
| Consistency with records | Follow the site standard |
There is no electrical reason to prefer one, which is itself a useful fact: the choice can be made entirely on practical grounds.
The one thing that must not change is the pairing. Meter 1's current coil and its pressure coil must refer to the same line — pairing \(\mathbf{I}_A\) with \(\mathbf{V}_{CB}\) gives a reading with no useful interpretation, and the sum is then simply wrong. Problem 16 lists this among the connection faults.
List the connection faults that corrupt a two-wattmeter measurement, and give the symptom by which each is recognised.
The correct connection, stated precisely:
| Requirement | Detail |
|---|---|
| Current coil | In series with its line, carrying the full line current |
| Pressure coil | From that same line to the common line |
| Polarity marks | The \(\pm\) terminals of both coils joined at the line side |
| Common line | The same line for both meters |
The faults and their symptoms:
| Fault | Symptom | Effect on \(P_T\) |
|---|---|---|
| One coil reversed | That meter reads negative at good pf | Sum too low by \(2W\) |
| Both coils reversed | None — reads correctly | None |
| Current and voltage from different lines | Readings implausible; sum wrong | Arbitrary |
| Different common lines | Sum wrong, often badly | Arbitrary |
| Pressure coil across a phase voltage | Sum is \(1/\sqrt3\) too low | Factor \(\sqrt3\) |
| Both meters on the same line | Readings identical | Meaningless |
The second row is the trap: reversing both coils changes two signs, which cancel. A meter that appears correctly connected may have had both reversed by a previous user.
The prediction check. The most reliable safeguard is to predict the readings before connecting, as in Problem 4. Given an approximate load rating:
A sum that is out by \(\sqrt3\), or a ratio wildly different from expectation, localises the fault immediately.
A worked diagnostic. A load known to be about 5.5 kW at roughly 0.8 lagging is measured, giving readings of 1571 W and −3971 W:
But the magnitudes 1571 and 3971 are exactly those predicted in Problem 15. The diagnosis is a single reversed coil on the second meter; correcting the sign gives
Note that a genuine negative reading (Problem 7) also occurs, so a negative value is not by itself evidence of a fault — the test is whether the sum is plausible.
Distinguishing a true negative from a reversal:
| Observation | Interpretation |
|---|---|
| Sum is plausible, one reading negative | Genuine — pf below 0.5 |
| Sum is implausible or negative | Reversal — check polarity marks |
| Sum is \(1/\sqrt3\) of expectation | Pressure coil on the wrong voltage |
The 28.8 kW load of Set 24 was corrected from 0.6 to 0.95 lagging on 400 V, reducing the line current from 69.28 A to 43.76 A. Show how the wattmeter readings change, and how the pair confirms the correction worked.
Before correction, \(\theta = 53.13°\), \(V_LI_L = (400)(69.28) = 27\,712\ \text{VA}\):
After correction, \(\theta = 18.19°\), \(V_LI_L = (400)(43.76) = 17\,504\ \text{VA}\):
The comparison:
| Before | After | Change | |
|---|---|---|---|
| \(W_1\) | 3315 W | 11 667 W | +252% |
| \(W_2\) | 25 484 W | 17 133 W | −33% |
| \(P_T\) | 28.8 kW | 28.8 kW | Unchanged |
| \(r = W_1/W_2\) | 0.130 | 0.681 | Toward 1 |
| Line current | 69.28 A | 43.76 A | −37% |
The three signatures of a successful correction:
The first is the crucial one. A capacitor consumes no real power, so if \(P_T\) changed, something other than the correction has altered — the load itself, or the connection.
Resolving Problem 10's ambiguity. This is the field technique promised there. Add a known capacitance and observe:
| Observation on adding C | Original load was |
|---|---|
| Readings converge (\(r \to 1\)) | Lagging |
| Readings diverge (\(r\) moves from 1) | Leading — correction is making it worse |
A definite answer from a single perturbation, using instruments already in place.
A warning about overcorrection. Continuing past unity power factor makes the load capacitive, and the readings begin to diverge again — with \(W_1\) now the larger. Since \(r\) passes through 1 and comes back, a single reading of \(r\) cannot distinguish 0.9 lagging from 0.9 leading; only the direction of travel can.
A balanced three-wire load on 415 V, 50 Hz gives readings \(W_1 = 2.4\ \text{kW}\) and \(W_2 = 6.8\ \text{kW}\). Determine everything obtainable: \(P\), \(Q\), \(S\), power factor, line current, and the delta capacitance to correct to unity.
1Real power — the sum:
2Reactive power — \(\sqrt3\) times the difference:
Positive, and \(W_2 > W_1\), so the load is lagging.
3Power factor:
4Apparent power:
Check: \(P/S = 9.2/11.947 = 0.770\) ✓ agreeing with the power factor.
5Line current, from \(S = \sqrt3V_LI_L\):
6Correction to unity requires the capacitors to supply all of \(Q_T\):
Using Set 24, Problem 17's delta formula. At unity power factor the readings would become equal at 4.6 kW each, and the line current would fall to \(9200/(\sqrt3\times415) = 12.80\ \text{A}\) — a 23% reduction.
What could not be determined from these measurements:
| Quantity | Why not |
|---|---|
| Per-phase impedance | Needs the connection — Problem 13 |
| Whether the load is truly balanced | Assumed; two meters cannot test it |
| Harmonic content | Wattmeters read total \(P\) only |
The second is worth dwelling on. Every step after the sum assumed balance, and Problem 12 showed the consequences of that assumption failing.
Identify the systematic errors in a wattmeter measurement, and show which of them the ratio method of Problem 9 escapes.
aPressure-coil burden. The pressure coil draws current, and where that current flows depends on the connection:
| Connection | Current coil also carries | Error |
|---|---|---|
| Pressure coil on the load side | The pressure-coil current | Reads high by \(V^2/R_p\) |
| Pressure coil on the supply side | Load current only | Reads high by \(I^2R_c\) |
Choose whichever error is smaller: the first connection for low currents, the second for high ones — precisely the ammeter–voltmeter trade-off of Set 1.
A numerical instance. With \(V = 400\ \text{V}\), \(R_p = 10\ \text{k}\Omega\), \(I = 20\ \text{A}\), \(R_c = 0.05\ \Omega\):
Comparable here; at 200 A the second becomes 2 kW and the first connection is clearly preferable.
bPressure-coil inductance. The pressure coil is not purely resistive, so its current lags the voltage slightly by an angle \(\beta\). The meter then reads
The error grows as the power factor worsens, and it is worst exactly where the two-wattmeter method is most needed. This is why low-power-factor wattmeters, with compensated pressure coils, exist as a separate instrument class.
cTransformer ratio and phase errors. At high voltage or current, instrument transformers are used, and each introduces both a ratio error and a small phase displacement — the latter again mattering most at low power factor.
Which errors the ratio method escapes:
| Error | Affects \(P_T = W_1+W_2\) | Affects \(r = W_1/W_2\) |
|---|---|---|
| Common scale factor (CT/PT ratio) | Yes | No — cancels |
| Identical calibration error on both | Yes | No — cancels |
| Different errors on the two meters | Yes | Yes |
| Phase error \(\beta\) | Yes | Yes |
| Burden | Yes | Partly |
The ratio is immune to anything scaling both readings equally — which is the commonest instrumentation error, since both meters typically share the same transformer set.
The practical conclusion. A two-wattmeter installation of modest accuracy will give a power factor considerably better than its power measurement, because the power factor depends only on the ratio. Reporting "9.2 kW ± 3% at a power factor of 0.770 ± 0.005" is a perfectly consistent statement, though it looks odd at first sight.
Sets 20 to 25 completed the sinusoidal steady state. Set out what was established, what was genuinely new, and what remains unaddressed in the whole treatment of AC so far.
The six sets, in one line each:
| Set | Content | Genuinely new? |
|---|---|---|
| 20 · Sinusoids and phasors | The transform itself | Yes — the whole method |
| 21 · AC mesh and nodal | Sets 4–8 with impedances | One item — ill-conditioning |
| 22 · Theorems in frequency domain | Sets 9–14 with impedances | One item — conjugate match |
| 23 · Single-phase power | \(P\), \(Q\), \(S\), power factor | Yes — all of it |
| 24 · Three-phase power | Star, delta, balance | Constant power, rotating field |
| 25 · Two-wattmeter method | Measurement | Blondel's theorem |
The shape of the whole. One transform (Set 20) made two sets of transferred results almost free, because the transform was built to preserve Kirchhoff's laws and linearity. Genuine novelty appeared only where those two premises were insufficient:
Both are non-linear operations on the circuit variables — a maximisation and a multiplication — which is exactly why linearity did not carry them across.
The one idea running through everything is that phase, introduced in Set 20 as a bookkeeping device for time shifts, turns out to control energy:
| Where phase appears | What it decides |
|---|---|
| Impedance angle | The split of \(S\) into \(P\) and \(Q\) |
| Conjugate match | Whether all available power is delivered |
| 120° between sources | Whether total power pulsates |
| 30° line–phase shift | Whether two meters can measure three phases |
The last is a small delight: a phase shift that seemed a mere nuisance in Set 24 became the mechanism of the measurement in Set 25.
The standing limitation. Everything assumed a single frequency in the steady state. Two omissions follow:
| Not addressed | Glimpsed in |
|---|---|
| How a circuit responds across frequency | Set 21, Problem 16 (near resonance) |
| Non-sinusoidal signals | Set 23, Problem 18 (harmonics) |
| Transients in AC circuits | Sets 18–19 were DC only |
Each was met once and set aside. Each now becomes a subject in its own right.
What comes next. Treating \(\omega\) as a variable rather than a constant opens the second half of Part 3:
| Set | Topic | Question answered |
|---|---|---|
| 26–27 | Mutual inductance, transformers | Coupled coils and voltage transformation |
| 28 | Transfer functions, Bode plots | Response across all frequencies |
| 29 | Resonance, \(Q\), bandwidth | Why some frequencies are special |
| 30 | Filters and scaling | Designing frequency selectivity |
| 31–32 | Laplace transform | Transients and steady state together |
| 33–34 | Fourier series and transform | Arbitrary waveforms |
| 35 | Two-port networks | Circuits as black boxes |
Practice Problems
Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not. Balanced lagging loads unless stated.
P1. Readings are 3 kW and 5 kW. Find the total power.
Show answer
8 kW — the algebraic sum, valid for any load — Problem 1.P2. For the same readings, find \(Q_T\).
Show answer
\(Q_T = \sqrt3(5-3) = 3.46\) kvar — balanced load assumed — Problem 11.P3. And the power factor?
Show answer
\(\tan\theta = 3.46/8 = 0.433\), \(\theta = 23.4°\), pf = 0.918 lagging — Problem 5.P4. Two wattmeters read equally. What is the power factor?
Show answer
Unity — the difference is zero, so \(Q = 0\) — Problem 8.P5. One wattmeter reads zero. What is the power factor?
Show answer
Exactly 0.5, since \(\cos(\theta+30°) = 0\) needs \(\theta = 60°\) — Problem 8.P6. How many wattmeters for a four-wire unbalanced system?
Show answer
Three, by Blondel's \(n-1\) — Problems 1 and 3.P7. A load has \(\theta = 45°\) at \(V_LI_L = 2000\ \text{VA}\). Find both readings.
Show answer
\(W_1 = 2000\cos75° = 518\) W; \(W_2 = 2000\cos15° = 1932\) W — Problem 4.P8. Readings are −500 W and 2500 W. Find \(P_T\) and comment.
Show answer
\(P_T = 2000\) W. The negative reading means pf < 0.5 — Problem 7.P9. Both meters have their coils reversed. What is the effect?
Show answer
None — two sign changes cancel, and the readings are correct — Problem 16.P10. For an unbalanced load, which of \(P_T\), \(Q_T\) and pf can the two meters give?
Show answer
Only \(P_T\). The others require balance — Problem 12.P11. The ratio \(W_1/W_2 = 0.5\). Find the power factor.
Show answer
\(\tan\theta = \sqrt3(0.5)/(1.5) = 0.577\), so \(\theta = 30°\) and pf = 0.866 — Problem 9.P12. How would you measure \(Q\) with a single wattmeter?
Show answer
Current coil in one line, pressure coil across the other two lines; then \(Q_T = \sqrt3W\) — Problem 11.
Challenge Problems
Each needs an idea rather than a formula. Decide what the governing principle is before opening the answer.
C1. A 415 V three-wire supply feeds a factory. Two wattmeters read \(W_1 = -1.8\ \text{kW}\) and \(W_2 = 9.4\ \text{kW}\). Determine the load's condition, decide whether the negative reading indicates a fault, and design a delta capacitor bank to bring the power factor to 0.9 lagging — then predict the new readings.
Show answer
Is the negative reading a fault? Test the sum for plausibility first (Problem 16):A positive, sensible total for a factory supply — so the reading is genuine, not a reversed coil. A reversal would have given an implausible or negative sum.\[ P_T = -1800 + 9400 = 7600\ \text{W} \]
The load's condition:\[ \tan\theta = \sqrt3\,\frac{9400-(-1800)}{7600} = \sqrt3\,\frac{11\,200}{7600} = 2.5527 \]Below 0.5, which is exactly why \(W_1\) went negative — consistent, and a useful cross-check on the arithmetic.\[ \theta = 68.61° \;\Longrightarrow\; \text{pf} = 0.3648 \ \text{lagging} \]\[ Q_T = \sqrt3(11\,200) = 19\,399\ \text{var}, \qquad S = \sqrt{7600^2+19\,399^2} = 20\,836\ \text{VA} \]This is a badly under-loaded installation — 20.8 kVA of supply capacity carrying 7.6 kW of useful work. Typically lightly loaded induction motors running on no-load.\[ I_L = \frac{20\,836}{\sqrt3(415)} = 28.99\ \text{A} \]
The capacitor bank. Target \(Q_2 = 7600\tan25.84° = 3681\) var:\[ Q_C = 19\,399 - 3681 = 15\,718\ \text{var} \]The new readings. With \(\theta = 25.84°\) and \(S_{\text{new}} = 7600/0.9 = 8444\ \text{VA}\), so \(V_LI_L = S/\sqrt3 = 4875\):\[ C_\Delta = \frac{15\,718}{3(314.16)(415)^2} = 96.8\ \mu\text{F per phase} \]\[ W_1 = 4875\cos55.84° = 2737\ \text{W}, \qquad W_2 = 4875\cos(-4.16°) = 4862\ \text{W} \]\[ \text{sum} = 7600\ \text{W}\;\checkmark \ \text{unchanged} \]The most striking figure is the last: line losses fall to a sixth. At such a poor starting power factor, correction is exceptionally worthwhile — and the negative reading turning positive is the visible confirmation that it has worked.Before After \(W_1\) −1.8 kW +2.74 kW \(W_2\) 9.4 kW 4.86 kW pf 0.365 0.900 \(I_L\) 28.99 A 11.75 A Line loss 100% 16.4% C2. Show that the two-wattmeter method reads correctly in the presence of harmonics, and explain why the power-factor formula then fails even for a perfectly balanced load.
Show answer
The sum still works. Problem 1's proof used only KCL and the definition of average power — neither assumes a sinusoid:A wattmeter's inertia averages whatever it is given, so\[ p(t) = \sum_{k=1}^{2} v_{kn}(t)i_k(t) \quad\text{holds instant by instant} \]exactly, for any waveform whatever. This is one of the method's great practical strengths: it remains valid on the distorted currents drawn by rectifiers and drives, where a calculation based on \(\sqrt3V_LI_L\cos\phi\) would be meaningless.\[ W_1 + W_2 = \overline{p(t)} = P_T \]
Why the power-factor formula fails. Problem 2 derived it from a specific phasor geometry: one frequency, and a definite \(\pm30°\) between line voltages and phase voltages. With harmonics present there is no single \(\theta\) to find — Set 23, Problem 18 showed the power factor splits into a displacement factor and a distortion factor:The wattmeter difference responds only to the fundamental's quadrature component, so \(\sqrt3(W_2-W_1)\) gives the fundamental reactive power — not the total, and not anything from which the true power factor can be recovered.\[ \text{pf} = \underbrace{\cos\theta_1}_{\text{displacement}} \times \underbrace{\frac{I_1}{I_{rms}}}_{\text{distortion}} \]
The trap this creates. On a modern installation full of switched-mode supplies:The formula flatters the installation, reporting only the displacement factor and ignoring the distortion factor — so it overstates the power factor precisely where the distortion is worst. A true-RMS ammeter and voltmeter, giving \(S = \sqrt3V_{rms}I_{rms}\) and hence \(\text{pf} = P_T/S\), is the correct approach.Quantity From two wattmeters Correct? \(P_T\) Sum Yes, exactly Fundamental \(Q\) \(\sqrt3(W_2-W_1)\) Yes True pf \(P_T/S\) — needs a true-RMS ammeter Only with extra instruments pf from \(\tan\theta\) formula — No — reads too high
The general lesson. The sum rests on conservation and survives everything; the difference rests on geometry and survives only what preserves that geometry. Whenever a result is used beyond the conditions of its derivation, it is worth asking which of the two kinds it is.C3. Two wattmeters are connected to a balanced load but the phase sequence is reversed from what was assumed. Show what happens to the readings, and explain how this could be mistaken for a leading power factor.
Show answer
Set up with negative (acb) sequence:The line voltage now becomes\[ \mathbf{V}_{an} = V_{ph}\angle0°, \quad \mathbf{V}_{bn} = V_{ph}\angle{+120°}, \quad \mathbf{V}_{cn} = V_{ph}\angle{-120°} \]— lagging its phase voltage by 30° instead of leading it. Every 30° in the derivation changes sign.\[ \mathbf{V}_{ab} = \mathbf{V}_{an}-\mathbf{V}_{bn} = V_L\angle{-30°} \]
The readings becomewhich is the original pair exchanged.\[ W_1 = V_LI_L\cos\left(\theta-30°\right), \qquad W_2 = V_LI_L\cos\left(\theta+30°\right) \]
The consequences:A numerical instance. A lagging load at pf 0.8 with \(V_LI_L = 1000\): correct sequence gives \(W_1 = 393\), \(W_2 = 993\) W, reporting \(\theta = +36.87°\) lagging. Reversed sequence gives \(W_1 = 993\), \(W_2 = 393\) W, reporting \(\theta = -36.87°\) — leading. Both give \(P_T = 1386\) W.Quantity Effect of reversed sequence \(P_T = W_1+W_2\) Unchanged — addition is commutative \(W_2-W_1\) Sign reversed Deduced \(\theta\) Sign reversed Deduced character Lagging reported as leading
Why this is genuinely dangerous. An installation diagnosed as leading would have inductors fitted to correct it, driving the true power factor further from unity rather than towards it — and the readings would diverge, appearing to confirm the wrong diagnosis until someone checked the current.
How to detect it. A phase-sequence indicator (Set 24, Problem 2) before connecting, or the perturbation test of Problem 17: add a small capacitance and see whether the line current falls. Current is a scalar magnitude and carries no sequence information, so it cannot be fooled.
The unifying point. This is the third appearance of the same ambiguity — Problem 10 (unlabelled meters), Problem 15 (choice of common line), and now sequence reversal. All three exchange \(W_1\) and \(W_2\), all three leave \(P_T\) untouched, and all three flip the reported character of the load. The sum is robust; the difference depends on conventions that must each be independently established.
Multiple-Choice Questions
Twelve questions in GATE/ESE style. Commit to an answer before opening the explanation.
Q1. Blondel's theorem states that an \(n\)-wire system needs
(a) \(n\) wattmeters (b) \(n-1\) (c) \(n+1\) (d) 2 always
Show answer
(b) — one current is determined by the others through KCL — Problem 1.Q2. The total power from two wattmeters is valid for
(a) balanced loads only (b) star loads only (c) any three-wire load (d) sinusoidal supplies only
Show answer
(c). The proof used only KCL, so balance, connection and waveform are all irrelevant — Problems 1 and 12.Q3. The 30° in \(W_1 = V_LI_L\cos(\theta+30°)\) comes from
(a) the impedance angle (b) the line–phase voltage shift (c) the 120° source spacing (d) instrument calibration
Show answer
(b) — the meter compares a line voltage with a line current — Problem 2.Q4. One wattmeter reads zero. The power factor is
(a) 0 (b) 0.5 (c) 0.866 (d) 1.0
Show answer
(b), since \(\cos(\theta+30°) = 0\) requires \(\theta = 60°\) — Problem 8.Q5. Equal readings indicate
(a) a balanced load (b) unity power factor (c) a star connection (d) zero reactive power in one phase
Show answer
(b). Note (a) is wrong — balance is assumed before the formula is used, not deduced from it — Problem 8.Q6. A negative reading means
(a) a wiring fault (b) power factor below 0.5 (c) a leading load (d) an unbalanced load
Show answer
(b), provided the sum is plausible — otherwise suspect a reversed coil — Problems 7 and 16.Q7. Reactive power from the readings is
(a) \(W_2-W_1\) (b) \(\sqrt3(W_2-W_1)\) (c) \(3(W_2-W_1)\) (d) \((W_2-W_1)/\sqrt3\)
Show answer
(b), for a balanced load only — Problems 11 and 12.Q8. For an unbalanced three-wire load, two wattmeters give
(a) \(P\) only (b) \(P\) and \(Q\) (c) nothing useful (d) \(P\), \(Q\) and pf
Show answer
(a). The sum is exact; the difference is meaningless — Problem 12.Q9. Reversing both coils of one wattmeter
(a) reverses its reading (b) doubles it (c) has no effect (d) gives zero
Show answer
(c) — two sign changes cancel, which is why this fault is invisible — Problem 16.Q10. To measure \(Q\) with one wattmeter, the pressure coil goes
(a) line to neutral (b) across the other two lines (c) across its own line pair (d) in series with the load
Show answer
(b) — that voltage is in quadrature, turning the cosine into a sine — Problem 11.Q11. Which quantity is unaffected by an error scaling both readings equally?
(a) \(P_T\) (b) \(Q_T\) (c) the power factor (d) the line current
Show answer
(c) — it depends only on the ratio \(W_1/W_2\) — Problems 9 and 19.Q12. Reversing the phase sequence with a lagging load causes the readings to
(a) both go negative (b) exchange, so the load appears leading (c) both halve (d) become equal
Show answer
(b). \(P_T\) is unchanged, but the deduced character is wrong — Challenge C3.
Key Formulas
All values RMS; balanced positive sequence unless the validity column says otherwise.
| Quantity | Relation | Valid for |
|---|---|---|
| Blondel's theorem | \(n-1\) wattmeters for \(n\) wires | Any load |
| Total power | \(P_T = W_1+W_2\) | Any three-wire load |
| Reading 1 | \(W_1 = V_LI_L\cos(\theta+30°)\) | Balanced |
| Reading 2 | \(W_2 = V_LI_L\cos(\theta-30°)\) | Balanced |
| Reactive power | \(Q_T = \sqrt3(W_2-W_1)\) | Balanced |
| Power factor | \(\tan\theta = \sqrt3\dfrac{W_2-W_1}{W_2+W_1}\) | Balanced |
| Ratio form | \(\tan\theta = \sqrt3\dfrac{1-r}{1+r}\), \(r = W_1/W_2\) | Balanced; scale-free |
| Single-meter \(Q\) | \(Q_T = \sqrt3W\), coil across the other two lines | Balanced |
| Three-wattmeter | \(P_T = \sum\operatorname{Re}(\mathbf{V}_k\mathbf{I}_k^{*})\) | Any four-wire load |
| pf | \(\theta\) | Signature |
|---|---|---|
| 1.000 | 0° | \(W_1 = W_2\) |
| 0.866 | 30° | \(W_1 = \tfrac12W_2\); \(W_2\) is at its maximum |
| 0.500 | 60° | \(W_1 = 0\) |
| \(<0.5\) | \(>60°\) | \(W_1 < 0\) |
| 0.000 | 90° | \(W_1 = -W_2\), sum zero |
Common Mistakes
Using the power-factor formula on an unbalanced load. The sum stays exact while the difference becomes meaningless — so nothing warns you — Problem 12.
Adding the magnitude of a negative reading. The total is the algebraic sum; a reversed meter's reading must be subtracted — Problem 7.
Treating a negative reading as a fault. Below 0.5 power factor it is correct behaviour; test the plausibility of the sum instead — Problems 7 and 16.
Reporting the readings as an unordered pair. Which meter is \(W_1\) determines lagging from leading — Problem 10.
Reversing both coils when only one needs reversing — the two sign changes cancel — Problem 16.
Pairing a current with a voltage from a different line. The proof used the pairing explicitly — Problem 15.
Using different common lines for the two meters. One reference conductor for both — Problem 15.
Dividing \(P_T\) by three for an unbalanced load. The phases do not share equally — Problems 6 and 12.
Deducing a per-phase impedance without knowing the connection. Star and delta differ by three — Problem 13.
Applying \(\tan\theta\) to a distorted waveform. The sum is still exact, but there is no single \(\theta\) — Challenge C2.
Two instruments measure the power of any three-wire three-phase load, and the proof needs nothing beyond Kirchhoff's current law — which is why the sum survives imbalance, unknown connections and harmonic distortion alike. For a balanced load the pair gives more: their difference yields the reactive power, their ratio the power factor, and the 30° line–phase shift that Set 24 derived for its own sake turns out to be the mechanism that makes it possible. The limitation is equally sharp. Everything beyond the sum rests on balanced phasor geometry, and Problem 12 showed the power-factor formula returning an answer wrong in sign while the total remained exact to the last digit.
That closes Part 3's power sequence. Sets 20 to 25 have treated the sinusoidal steady state completely — but always at a single frequency, with \(\omega\) held fixed and the transients of Sets 18 and 19 long decayed. Two questions have been deferred throughout: how a circuit behaves as the frequency varies, and what happens when two coils share a magnetic field rather than an electrical connection.
Next: Set 26 — Mutual Inductance, where a changing current in one coil induces a voltage in another with no conducting path between them. The dot convention, coupling coefficient and coupled-circuit analysis follow, and they lead directly into transformers in Set 27 and the frequency-domain work that occupies the rest of Part 3.